36C24618R0839-003.pdf

PDF 7 MB Posted

Attached to
Project 659-16-103, Replace Campus Fire Alarm System Federal contract opportunity
Solicitation number
36C24618R0839
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

36C24618R0839 CONTRACT ATTACHMENT A - DRAWINGS FILE 2 - 02-Sheets_FD101-FD116.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Project 659-16-103, Replace Campus Fire Alarm System, newest first.
File Type Posted
36C24618R0839-0003002.pdf PDF
36C24618R0839-0003001.pdf PDF
36C24618R0839-0003000.docx DOCX document
36C24618R0839-0002001.pdf PDF
36C24618R0839-0002000.docx DOCX document
36C24618R0839-004.pdf PDF
36C24618R0839-013.docx DOCX document
36C24618R0839-008.pdf PDF
36C24618R0839-012.pdf PDF
36C24618R0839-009.pdf PDF
36C24618R0839-002.pdf PDF
36C24618R0839-006.pdf PDF
36C24618R0839-001.docx DOCX document
36C24618R0839-014.pdf PDF
36C24618R0839-005.pdf PDF
36C24618R0839-010.pdf PDF
36C24618R0839-007.pdf PDF
36C24618R0839-011.pdf PDF
36C24618R0839-000.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FACP-43

FACP-42

FB-42

FACP-06

FB-06FACP-07

FB-07

FB-07A

FB-05

FACP-05

FB-10

FACP-15

FB-15

FB-18

FACP-18

FANA-18

FB-11

FACP-11

FANCC

FACP-04

FB-04AFB-04

FACP-13

FB-13

FB-21

FACP-21

FB-01

FACP-01

FB-01A

FACP-14E

FACP-02

FB-02

FACP-03

FB-03

FACP-09

FACP-08

FB-08

EXISTING

MANHOLE #3

EXISTING

MANHOLE #2

EXISTING

MANHOLE #9

EXISTING

MANHOLE #11

PULL BOX

EXISTING

MANHOLE #1

FACP-20

EXISTING HAND HOLE #7

EXISTING HAND HOLE #6

EXISTING

MANHOLE #4

EXISTING

MANHOLE #8

EXISTING

MANHOLE #5

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

1 EXISTING FIRE ALARM FIBER ROUTING

1" = 100'

FD101

FIBER-OPTIC SITE PLAN EXISTING/DEMOLITION

GENERAL NOTES

1. LINES SHOWN REPRESENT APPROXIMATE ROUTING

OF EXISTING FIBER-OPTIC CABLING. FOR EXISTING

INTERCONNECTIONS, SEE SHEET FD-601.

2. LOCATIONS OF FACP AND FIBER BOXES (FB) SHOWN

ARE APPROXIMATE. SEE EXISTING/DEMO PLANS FOR

EACH BUILDING FOR EXACT LOCATIONS.

3. MOST FIBER CABLING IS SHARED WITH OIT,

SECURITY, AND/OR ENERGY MANAGEMENT.

THEREFORE, MOST EXISTING FIBER SHALL REMAIN.

FIRE ALARM STRANDS SHALL BE DISCONNECTED

FROM PATCH PANEL AND SHALL BE LABELED AS

SPARE.

4. ALL FIBER-OPTIC CABLING WHICH IS SOLELY FOR

THE FIRE ALARM SYSTEM SHALL BE DEMOLISHED.

KNOWN DEDICATED FIRE ALARM FIBER IS AS NOTED

ON SHEET FD-601.

5. EXISTING MANHOLES TO REMAIN. CONTRACTOR

SHALL PROVIDE A LABEL FOR EACH MANHOLE,

SIGNAL MANHOLE #1 THOUGH SIGNAL MANHOLE #12.

6. CONTRACTOR SHALL SURVEY THE EXISTING FIRE

ALARM LOOP BEFORE ANY WORK CAN START.

COORDINATE WITH COR.

DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8

6/25/2018

G001

TRANSFORMER RM

G03

MECH RM

G04

ELEVATOR SHAFT

G02

MECH RM

G05

MACH RM

G08

STORAGE

G06

OFFICE/CONF ROOM

G09

OFFICE

G06C

CORR.

G07

STAIR

G10

FILE STORAGE

F

F

TC FB FACP

XD

XD

135F

OFFICE

135C

OFFICE

135B

OFFICE

135A

OFFICE

CONF SPACE

STAIRS#3

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TOILET

CLOSET

15 144

TOILET

LOBBY

120A

OFFICE

OI&T Closet

OFFICE

OFFICE

OFFICE

108D

OFFICE

OFFICE

104A

OFFICE

108C

OFFICE

104B

OFFICE

300 108B

OFFICE

OFFICE

104C

OFFICE

PIV

LOBBY

STAIRS#2

C&P

103A

STORAGE

CORRIDOR

OFFICE

108A

OFFICE

TOILET

F. TOILET

OFFICE

STAIR#1

MOP

F. TOILET

M. TOILET

102A

OFFICE

M. TLT

STORAGE

106A

CORRIDOR

106B

CORRIDOR

124A

LOBBY

F

F

F

F

F

F

F

F

F

F

TC

F

~30'

~30'

F

F F

XD

XD

XD

XD

XN

XN

XD

DIRECTOR'S OFFICE

222A Assoc Dir Office

OFFICE

OFFICE

STOR.

CONF. RM.

435 213

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

234A

TOILET

OFFICE

OFFICE

OFFICE

STORAGE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

STAIR#2

OFFICE

STAIR#3

LOUNGE

CORR.

STAIR#1

TOILET

M. TOILET

TOILET

MOP

TOILET

CLOSET

TOILET

CLOSET

TOILET

JANITOR

STORAGE

204A

CORR.

251A

TOILET

F

F

F F

F

F

F

F

F

F

F

XD

XN

XNXD

XD

XNXN

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD102

BLDG 1 EXISTING/DEMOLITION

1 FIRST FLOOR

3/32" = 1'2 SECOND FLOOR

3/32" = 1'

3 GROUND FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. DEMO EXISTING FACP. EXTEND EXISTING SLC

CIRCUITS TO NEW FACP LOCATION.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

G062

GENERAL STORAGE

442 SF

G059

AUTOPSY SUITE

446 SF

GO56

MORGUE RECEIVING

324 SF

G055

TOILET

135 SF

G061

CORRIDOR

288 SF

G003

PATIENT EFFECTS

1194 SF

G003A

STOR.

G003B

CHANG'G RM

84 SF

G004

LOUNGE

253 SF

G006 M.T.

70 SF

G008

OFFICE

G002A

MECH

185 SF

G002

CLOTH. ROOM

2127 SF

G058

UNEXCAVATED

G001

UNEXCAVATED

G028

MRI EXAM/SCAN

309 SF

G031

EMERG GEN

51 SF

G009

MECHANICAL ROOM

G010

CLEAN SUPPLY

169 SF

G063

ELEV LOBBY

223 SF

G013

M. SHOWER

182 SF

G014

MALE LOCK.

227 SF

G016

GENERAL STORAGE

672 SF

G017A

MECHANICAL

G017

UNEXCAVATED

G011

F. LOCK. RM

161 SF

G019

UNEXCAVATED

G068

STOR.

96 SF

G020A

ELECTRICAL

G019A

FIRE ALARM EQUIP

22 SF

G

E

LE

C C

L 8 S

F

G012

F. SHOWER

182 SF

G

E

LE

C

C L

G060

MECH

39 SF

G028G

COMP RM

176 SF

G028E

COMPUTER RM

157 SF

G028D

WAITING

164 SF

G028A

VEST

114 SF

G028C

HC TOILET

47 SF

G028B

STORAGE

57 SF

G020E

TOILET

50 SF

GO20F

STAFF

112 SF

G020G

OFFICE

90 SF

G020H

CONTROL

224 SF

G020J

MRI EXAM

491 SF

G020B

WAITING ROOM

334SF

G020L

MECHANICAL

88 SF

G020M

EQUIP STOR

113 SF

G020 i

EQUIP STORAGE

G020K

GEN STORAGE

100 SF

GO20 D

TLT/DRESS

58 SF

GO20P

SUB WAIT

69 SF

G020N

HOLD

150 SF

G020D

HALL

71 SF

G070

FEC

4GO48

CORRIDOR

GO18

CORRIDOR

GO30

CORRIDOR

G032

TRANSFORMER

491 SF

G050

LINEN

G049

STAIR

G036

FEC

G070A

BULK STOR.

146 SF

SMOKE BARRIER

2 HR FIRE WALL

2 HR FIRE WALL2 HR FIRE WALL

SMOKE BARRIER

1 HR FIRE WALL

FFFF

S

F S

F S

F S

F S F

S

FF

F S

FC

TC

F S

FB

F S

FACP

TC

F S

F S

F S

F S

F S

F

F

FC

F

F

FOER

AATP

XN XD

XN

XN

XN

XN

XN

XN

FS

FS

F

F

FS

F

F

FS

FF

S

FS

F

F

F F

FS

FS

F

F

1 2

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD103

BLDG 2 GROUND FLOOR

EXISTING/DEMOLITION 2

1 BLDG 2 GROUND FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

KEYED NOTES #

1. REPLACE FACP. BACKBOX/CABINET MAY BE

RE-USED IN-PLACE IF ADEQUATELY SIZED.

PROVIDE NEW FIBER PATCH PANEL.

2. REPLACE AATP (NOTIFIER XPIQ) WITH A NACP

AND DAA. RECONFIGURE NAC AND SPEAKER

CIRCUITS AS REQUIRED.

DENTAL LAB

DENTAL OP #8

STAIRS #4

1147A

DENTAL OP #7

DENTAL BREAK

FIRE CLS

1141A

DENTAL O

P #5

1149A

DENTAL O

P #6

1149B

DENTAL O

P #4

DENTAL STORAGE

CLEAN STOR.

DENTAL OP#3

DENTAL O

P#2

DENTAL

PHARMACY

EXAM

VAULT

STAIRS

1157A

ELEC. CLS

PHARMACY

ELEC

STORAGE

D

U M

B W

A

ITE

R S

OFFICE

CLINIC

OFFICE

OFFICE

TOILET

1009B

WAITING AREA

CONF ROOM

STORAGE

LOBBY

RECEPTION

EXAM

EXAM

NURSE

EXAM

1167A

TOILET

EXAM

EXAM

BREAK RM

OFFICE

OFFICE

EXAM

EXAM

1006A

EXAM

1007A

STOR

1010A

ELEC

FEC

OFFICE

STAIRS

TO

IL

ET

CLEAN SUPPLY

STOR.

STOR.

STAIRS

TOILET

ELEC.

M.O.D. OFFICE

ENTRANCE

M. TOILET

IV STORAGE

S

TO

R A

G E

66 11

M C

LO

S

E T

OFFICE

OFFICE

OFFICE

OFFICE

1096B

OFFICE

OFFICE

STORAGE

OFFICE

OFFICE

TOILET

TOILET

LOCKERS

CLEAN LINEN

EXAM

EXAM

EXAM

1083STORAGE23

TOIL/SHWR

OFFICE

STAIRS

LOUNGE

TOILET

HOLDING

EXAM

EXAM

TOILET

1064STORAGE10

VESTIBULE

1081STORAGE23

PA

SS

AG

E

1065CLOSET11 1066UTILITY40

1188A

ELECT.

1190A

TELE

TELE. CLS

1170A

SOILED UTILITY

STOR.

STOR.

OFFICE

OFFICE

1D147

PROCEDURE

1D147B

MED

1D111

CLEAN

1D112

TOILET

1D113

STORAGE

1D114

CONSULT

1D115

CONSULT

1D116

CONSULT

1D117

EXAM

1D118

EXAM

1D113A

TELE

1D147A

TOILET

1D146

ELEC

1D142

SOILED

1D143

SPD

1D144

CLEAN LINEN

1D150

TOILET

C1-15

CORR

1D151

LOUNGE

C1-14

CORR

1D104

WOMEN

1D105

MEN

C1-11

CORR

1D103

MECH

1D102

HAC

1D101D

TOILET

1D101C

DR. OFFICE

1D131

CONFERENCE

1D130

EXAM

1D129

EXAM

1D128

EXAM

1D127

EXAM

1D126

EXAM

1D125

EXAM

1D124

EXAM

1D123

EXAM

1D122

EXAM

1D121

EXAM

1D120

EXAM

1D145A

STORAGE

1D141

OFFICE

1D140

OFFICE

1D145

H. A. S.

1D110 screening

1D106

WAITING

1D101

PASSAGE

1D101B

A. O.

1D101A

SECRETARY

1D100B

OFFICE

C1-12

VESTIBULE

C1-12

CORR

1096C

WAITING

1096A

OFFICE

961101A

STORAGE

BUILDING 2 1st FLOOR

STORAGE

ELEC

1159A

WAITING

1159B

OFFICE

1159C

CORRIDOR

1D100A

OFFICE

1140A

DIRTY

B WING CENTER WING A WINGCENTER WING

2 HR FIRE WALL

F

TO BUILDING 3 & LAB (20)

E SD

CORRIDOR

OFFICE

COFFEE SHOP

WAITING AREA

OFFICE

OFFICE

LOBBY

GEN STORAGE

CORRIDOR

FIRE ALARM

C1-13

CORR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

TOILET

1192A

ELECT.

LINEN CHUTE

LINEN CHUTE

FEC

DENTAL X-RAY

DENTAL O

P #9

OFFICE

HALLWAY

FAC

1050A

ELEC

HALLWAY

AOD

F TLT

M TLT

CORR

VESTIBULE

POLICE

HOLDING

WAITING

CORR

OFFICE

EXAM

EXAM

OFFICE

OFFICE

EXIT CORR

EXAM

701054

EXAM

GEN STORAGE

STAIRS

1096D

CLEAN SUPPLY

RN ALCOVE

LINEN

1063OBSERVATION492

1070ELEC. 27

OFFICE

MED ROOM

F

F

F S

F

F S

F

F

F

F S

F

F

F

F F

F

F

F

F

F S

F

F

F

F

F

F

FA

A

P

F

F

F

TC

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F S F

S F S F

S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S F S

F S

F S

F S

F S F

S

F S

F

F

F

F

F

F F

F

F

F

F S

F

F

F

F F

F

F

F S

F

F

F

F

F S

F

F S

F

F

F

F S

F

F

F

F F

F

F

F

F

F S

F

F

F

F

F

F

FA

A

P

F

F

F

TC

F S

A A

TP

MATCHLINE A

MATCHLINE B

XN

XN

XD

DENTAL LAB

DENTAL OP #8

STAIRS #4

1147A

DENTAL OP #7

DENTAL BREAK

FIRE CLS

1141A

DENTAL O

P #5

1149A

DENTAL O

P #6

DENTAL STORAGE

CLEAN STOR.

CORRIDOR

DENTAL X-RAY

DENTAL O

P #9

F

F S

F S

F

F

MATCHLINE A

CLEAN LINEN

EXAM

EXAM

EXAM

1083STORAGE23

TOIL/SHWR

OFFICE

STAIRS

LOUNGE

TOILET

HOLDING

EXAM

EXAM

1081STORAGE23

PA

SS

AG

E

1065CLOSET11 1066UTILITY

CORRIDOR

FIRE ALARM

S

F S

F S

F F

MATCHLINE B

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD104

BLDG 2 FIRST FLOOR

EXISTING/DEMOLITION 2

1 BLDG 2 FIRST FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8

6/25/2018 ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg

PIPE CHASE

STAIRS

XRAY

CONTROL RM

DRESSING

XRAY

CONT RM

DRESSING

XRAY

FILM PROCESS

WORK ROOM

CT SCANNER

XRAY

HALLWAY

CT OPER.

CLEAN STOR

2110A

OFFICE

2110B

OFFICE

EXAM

TOILET

2110C

WAITING

NUC MED 2107

NUC MED

CONFERENCE

WAITING ROOM

OFFICE

2098A

OFFICE

2098B

OFFICE

2098C

OFFICE

2098D

OFFICE

2098E

OFFICE

2098F

OFFICE

OFFICE

OFFICE

GEN STOR

TOILET

TOILET

D/W

EXAM

EXAM

EXAM

OFFICE

OFFICE

TLT

STAIRS

WAITING ROOM

TOILET

GEN STOR

TOILET

OFFICE

OFFICE

TLT

OFFICE

OFFICE

TLT

EXAM

FEC

TOILET

EXAM

CLEAN SUP

48 2058

TOILET

OFFICE

HAC

TLT

CLOSET

2059A

TOILET

EXAM

EXAM

OFFICE

LOCK

COMPUTER ROOM

OFFICE

OFFICE

BLOOD BANK

HEMATOLOGY

2012A

GEN STOR

2143A

OFFICE

STOR

LAB

LAB

LAB

LAB

LAB

TLT

LAB

LAB

LAB

2151A

GEN STOR

HAC

STAIRS

2155A

OFFICE

2153B

OFFICE

LINEN CHUTE

17 2161

OFFICE

OFFICE

LOCKERS

TOILET

LOCKERS

TLT

ELECT

TOILET

2168A

TEL

STORAGE

TOIL.

TLT

TLT

TLT

BREAK ROOM

OFFICE

HAC

CONT RM

2130A

ELECT

FEC

ELECT.

2098G

BATHROOM

2098I

CLOSET

2095A

GEN STOR.

2098H

RECEPT.

FAC

WAITING

2152107A

HOT LAB

2090A

OFFICE

BONE DENS

BUILDING 2 2nd FLOOR

EXAM

2027A Corridor

CT SCANNER 2

HAC

CORRIDOR

LAB

LAB

FEMALE ST. TLT

LOCKERS

BREAK AREA

ST W

KSTN O

FFICE

CHIEF OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

OFFICE

2035A

HALL WAY

HALL W

AY

HALL WAY

2030A

TECH WKSTN

WAITING

STAIRS

ROOF

BLOOD STAGING

SPECIMEN TLT

SPECIMEN TLT2029

WAITING

BLOOD DRAW

BLOOD DRAW

BLOOD DRAW

FEC

TELE

STORAGE

2133A

ELE CLST

CORRIDOR

ELEC

CORRIDOR

CORRIDOR

FEC

CORRIDOR

FEC

STAIRS

STAIRS

LINEN CHUTE

2161A

OFFICE

CENTER WINGB WING CENTER WING A WING

TO LAB BUILDING

F

F

F

F

F

F

F

F

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F

SF

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

F F

F

F

F

F

F

F

F

F

F

F

F

TC

F

F

F

F S

F S

F S

F S

F

F

F F

F

A A

TP

NACP

F

F S

XR

XD

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD105

BLDG 2 SECOND FLOOR

EXISTING/DEMOLITION 2

1 BLDG 2 SECOND FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

DocuSign Envelope ID: 94B147EA-25A3-4143-9BDC-8EC43B57B4A8

6/25/2018 ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg ftp://image.autodesk.com/drawing/RECTANGULAR_SINK.dwg

B WING CENTER WING CENTER WING A WING

ROOF

ROOF

FAC

3077A

3069A

STORAGE

TLT

STAIR #3

STAIR #3

3071A

ELEC

MEDICATION

3072B

ALCOVE

3063A

PAT. TLT

PAT. ROOM

3064A

PAT. TLT

PAT. ROOM

ANT. ISO

3066A

PAT. TLT

ISO. PAT ROOM

3068A

PAT. TLT

ANT. ISO

ISO. PAT ROOM

3001A

STAIR #1

STAIR #4

3002A

STAIR #1

STAIR #4

3003A

MECH RM

OFFICE

3165A

FAC

FA

C

CORR

3091A

TEL

STOR

CONF

3101A

OFFICE

OFFICE

BREAK

TLT

F.TLT

LAB.STO

WAITING

1353090

EQUIP STOR

CORR

3094A

OFFICE

3094K

OFFICE

3094J

OFFICE

3094B

OFFICE

3094L

GEN STOR

3094C

CONF RM

3094I

OFFICE

3094H

OFFICE

3094D

OFFICE

3094E

OFFICE

3094F

OFFICE

3094G

OFFICE

LINEN CHUTE

STAIR #6

PIPE

TLT

CORR

CORR

FAC

ELEC

HAC

M.TLT

F.TLT

EQUIP STO

M.TLT

TLT

CLEAN SUP

SOIL LN

3163A

FAC

3160A

ELEC

3161A

TELE PHONE

DIST RM

MOP

EQUIP STORAGE

BLD GAS

EKG

STAIR #5

LOCKER

OFFICE

OFFICE

SUPP

CLEAN SUP

EQUIP STOR

NURSE ST

NURSE STATION

CORRIDOR

3058A

PAT. TLT

PAT. ROOM

3059A

PAT. TLT

PAT. ROOM

FAC

TLT

EQUIP STOR

1-BED

1-BED

1-BED

1-BED

1653014

F. TLT

TLT

1-BED

1-BED

1603018

M.TLT

M.TLT

TLT

CL.UTIL

47 3026

1-BED

1-BED

TLT

TLT

1-BED

1-BED

TLT

TLT

1-BED

160 3035 Dialysis

3044A

STAIR

3043A

STAIR

3044B

PAT. TLT

ANTE ISOL

ISO. PAT. ROOM

3050A

PAT. TLT

ANTE ISOL

ISO. PAT. ROOM

3045D

ALCOVE

3043B

PAT. TLT

PAT ROOM

3051A

BAR. PAT TLT

BARIATRIC PAT. ROOM

3042A

PAT. TLT

PAT ROOM

ALCOVE

SOIL UTIL

EQUIP. STOR

3040A

PAT. TLT

PAT ROOM

3045B

CORRIDOR

3039A

PAT. TLT

PAT ROOM

MECH RM

3054A

PAT. TLT

PAT ROOM

NOURISHMENT

CLEAN SUP

EQUIP STOR

3045A

EQUIP

F

F

F

F

F

F

F

F

F

F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

TC

F

F

F

F

F

A A

TP

XD

FS

FS

FF

FS

F

F S

F

F

F

F

FS

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD106

BLDG 2 THIRD FLOOR

EXISTING/DEMOLITION 2

1 BLDG 2 THIRD FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

SHOWER

TOILET

TOILET

WOMEN'S LOCKERS

CORRIDOR

4110B

CORRIDOR

4110A

MEN'S LOCKERS

SHOWER

4130A

MEN'S LOCKERS

CLEAN

SUPPLY

SUPPLIES/

CLEAN UTILITY

STAFF

WORKSTATION

PATIENT HOLDING

CASE CART HOLDING

MED GAS

OR #5

SUB STERILE

SURGICAL CORRIDOR

OR #6

OR #7

SCRUB #2

SCRUB #1

HAC

STORAGE #1

ELECTRICAL

STORAGE #2

EQUIPMENT

EQUIPMENT

FP

ROOF

4129A

OFFICE

SOILED

UTILITY

TOILET

STAIRS

LINEN

CHUTE

MINOR OR

REGISTRATION

4149 ELEC CL

MINOR O R

4152A

B WING CENTER WING CENTER WING A WING

SMOKE

BARRIER

SMOKE

BARRIER

SMOKE

BARRIER

SMOKE

BARRIER

TELECOM

FAC

6 4039

CORRIDOR

CORRIDOR

GEN STORAGE

GEN STORAGE

CORRIDOR

FAC

STAIRS

OPER. ROOM #3

OPER. ROOM #2

MECH

STORAGE

SCRUB ROM

SCRUB RM

MECH RM

STORAGE

OPER. ROOM #1

4013A

PAT. LOCKER

WASH ROOM

CLEAN SUPPLY

GEN STORAGE

CORRIDOR

NURSE STATION

EQUIP STOR

RECEPTION

OFFICE

PH 1 PACU

EXAM

EXAM

4017B

TLT

TLT/SHW

PH 2 RM 3

EXAM

EXAM

OFFICE

EQUIP STORAGE

EQUIPMENT STORAGE

EQUIP STORAGE

FAC

ELECT

4017A

STORAGE

ELEC

PRE OP

D/W

4154A

TELE

LINEN

STORAGE

4129A

TOILET

UTILITY

ELEC

HAC

PASS

TOILET

GEN STORAGE

TOILET

SOILED

ELECT CLS

STAIRS

FAC

OFFICE

SURGERY WAITING

STORAGE

TOILET

TOILET

4100B

EQUIP STORAGE

4100A

EQUIP STORAGE

PH 1 PACU

F S

F S

F S

F S

F S

F S

F S F

S

F S

F S

F S

F S

F S

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F F

F

TC

F

F

A A

TP

XD

XN

XN

XN

F

F F

F

F

F

F

F

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD107

BLDG 2 FOURTH FLOOR

EXISTING/DEMOLITION 2

1 BLDG 2 FOURTH FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

1. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

F S

F S

F S

FC

FC

FC FC

FC

FC

FF

EPREAR

F

XN

XN

XN

XN XN

XN

XN

XN

B WING CENTER WING CENTER WING A WING

SMOKE

BARRIER

SMOKE

BARRIER

SMOKE

BARRIER

SMOKE

BARRIER

CLOSET

CORRIDOR

CORRIDOR

PIPE SP

5005B

CORRIDOR

CORRIDOR

FEC

5023A

CORRIDOR

SOILED UTIL

CORRIDOR

PIPE SP

PIPE SP

PIPE SP

PIPE SP

PIPE SPACE

PIPE SP

5062B

EXAM

5062A

OFFICE

5062C

COPY

MAS

5025A

EXAM #3

NURSE TRIAGE

EXAM

5068A

EXAM

WAITING

TELE

5020A

PROCEDURE ROOM

TELE

ELEC

F. TLT

SPD

TOILET

EQUIP STOR

EXAM #7

EXAM #6

EXAM #5

EXAM #4

HAC

5020B

TOILET ROOM

PHARM

FAC

EXAM #1

EXAM #2

BREAK RM

EXAM #3

EXAM #1

EXAM

EXAM

HEALTH ADMIN.

PIPE CHASE

5095A

PIPE CHASE

5027A

OFFICE

5026A

OFFICE

CL

5005A

ELECT

5081A

ELECT.

ELEC

STORAGE

5068C

OFFICE

L. CHUTE

STAIRS

TOILET

D U

M B

W A

IT

LINEN

ALCOVE

IV MIXTURE ROOM

HAC

CHG RM

STOR

TOILET

STOR.

ELECT.

LINEN CHUTE

STAIRS

5091A

ADMIN CLERKS

TOILET

OFFICE

EXAM

GEN STOR

OFFICE

FAC

STORAGE

OFFICE

TOILET

TEL.CL.

BREAK

5087HAC96

OFFICE

OFFICE

OFFICE

OFFICE

MECH

OFFICE

OFFICE

OFFICE

TOILET

EQUIP STOR

MECHANICAL

COPY ROOM

OFFICE

STRESS TESTING

STRESS TESTING

UROLOGY WAITING

Workroom

Shared Office

EXAM #2

EXAM #4

EXAM #5

M & F TOILET

5027A

ELECTRIC

PIPE SPACE

PIPE SPACE

EQUIP. STORAGE

5034A

FAC

6 5034

PIPE SPACE

OFFICE

ULTRASOUND

OFFICE/EXAM

OFFICE/EXAM

5039A

OFFICE/EXAM

TOILET/SHOWER

OFFICE/EXAM

OFFICE/EXAM

EXAM

5042A

ELEC

UTILITY

BREAK RM

TOILET

STORAGE

NOUR. KIT.

SOILED

WO CLINIC WAIT

OFFICE

F S

F S

F S

F S

F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F S

F

SF

S F S

F F

F

F

F S

F S

F S

F S

F S

F F

FF

F F F

F S

F S

TC

FC

A A

TP

FC

XN

XN

XN

XN

XN

XD

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD108

BLDG 2 FIFTH FLOOR AND PENTHOUSE

EXISTING/DEMOLITION 2

1 BLDG 2 FIFTH FLOOR

3/32" = 1'

HEALTH CARE OCCUPANCY - FULLY SPRINKLERED

2 BLDG 2 PENTHOUSE

3/32" = 1' INDUSTRIAL OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

KEYED NOTES #

1. DEMOLISH EXISTING AATP (NOTIFIER XPIQ).

EXTEND EXISTING NAC AND SPEAKER CIRCUITS

TO NEW NACP AND DAA LOCATION.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

G058

PRINT SHOP

G052

STOR.

G057

PIPE SPACE

G056

DARK RM

G054

PRINT SHOP

G054A

PIPE SPACE

G050

PASS

G049

STAIRS#3

G048

CORR.

G046

TELE.

G059A

ELECTRICAL

G045

OFFICE

G044

STORAGE

295G026

STORAGE

142 G042

SOIL LIN

G027

OFFICE

G023

MECHANICAL RM

G024

TRANS RM

G025

OFFICE

G022

EQUIP. SHOP

G021

STOR

G018

MOP

G017

WELDING SHOP

G015

LOCKERS

G013

TLT

G012

LOCKERS

G005

LOCKERS

G007

TLT

G004

STOR.

G001

SHEET METAL & EQUIP. SHOP

G006

OFFICE

G003

STORAGE

54 G008

OFFICE ENV. MAN. SVC.

G039

LAUNDRY

G038

CART CHARGING ROOM

G037

EMS STORAGE

G035

VENDING

G029

STAIR #2

G020

STOR.

G053

HAC

G053A

ELECT.

G050A

FEC

G048A

CORR.

G028

CLOS.

G032

FEC

G032A

ELECT.

G039

ELECT.

G011

CORRIDOR

G016

PASS.

G041

CORRIDOR

G030

ELEV. LOBBY

G001A

ELECT.

G054A

PRINT SHOP

G040

CORRIDOR

G033

CORRIDOR

GO19

DUMB WAITER SHAFT

CENTER WING A WING

F S

F S

F S

F S

F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F S

F

TC

F

F

FACP

F

F

F

F

F

XN

XN

NACP

DAA

XR

Electrical

A-006

Alcove

A-005

Elevator Lobby

A-002

Cart Alcove

A-004 Elev Mach

A-001

FM

TO BUILDING 2

TO BUILDING 3

C

C C

AT

AT

AT

AT

C

FACP

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD109

BLDG 3 AND BLDG 20 GROUND FLOOR

EXISTING/DEMOLITION 3, 20

1 BLDG 3 GROUND FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

2 BLDG 20 GROUND FLOOR

3/32" = 1'

GENERAL NOTES

KEYED NOTES #

1. REPLACE FACP. EXISTING BACKBOX/CABINET

MAY BE RE-USED IN-PLACE IF

ADEQUATELY-SIZED. PROVIDE NEW FIBER PATCH

PANEL.

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

CENTER WINGB WING CENTER WING A WING

CORRIDOR

CORRIDOR

CORRIDOR

1046A

RECEPTIONIST

STORAGE

ELEV LOBBY

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

PIPE SPACE

CORRIDOR

DECEDENT AF

HLTH BENS

SUPV

1083B

ID CARD

1083A

WAITING

ADVISOR

ADVISOR

ADVISOR

1090A

WORK AREA

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CORR.

OFFICE

OFFICE

OFFICE

CANTEEN DINING

KITCHEN

CANTEEN

HAC

STORAGE

OFFICE

OFFICE

MULTI USE

1099B

OFFICE

1099A

OFFICE

TLT

OFFICE

OFFICE

OFFICE

TLT

TLT

1008A

OFFICE

OFFICE

OFFICE

TOILET

LOBBY

OFFICE

OFFICE

OFFICE

GEN STORAGE

1120A

CONF.

OFFICE

OFFICE

TOILET

PIPE SPACE

PIPE SPACE

OFFICE

1104A

OFFICE

1104B

OFFICE

OFFICE

OFFICE

STAIRS

P

IP

E S

P A

C E

OFFICE

STORAGE

TOILET

KITCHEN

CLOSET

TEL CL

TLT

TLT

OFFICE

BREAK

TLT

1111A

ELECT

FEC

STORAGE

OPTICAL SHOP

1024A

RESTROOM

TOILET

OFFICE

OFFICE

OFFICE

BATH/SHW

STAIRS

FEC

ELEV. LOB

1058A

ELECT.

OFFICE

OFFICE

OFFICE

OFFICE

1431026A

STOR.

OFFICE

OFFICE

OFFICE

1029A

CONF.

1026B

BATHROOM

FEC

1016A

ELECT

STAIRS #1

1017A

CORRIDOR

OFFICE

OFFICE

BREAK

OFFICE

1026C

TELE

OFFICE

OFFICE

OFFICE

1006A

OFFICE

OFFICE

TO BUILDING 2 & LAB

F S

F S

F S F

S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S F

S

F S

F S

F S

F S

F S

F S

F S

F

F

F

F S

F

FF

F

F

F

FAAP

F S

F

F S

F

F F

F S

~55'

N A

C P

D A

A

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis, IN Philadelphia, PA Pittsburgh, PA Virginia Beach, VA Fort Collins, CO GURLITZ

ARCHITECTURAL

23894

SEAL

FD110

BLDG 3 FIRST FLOOR

EXISTING/DEMOLITION 3

1 BLDG 3 FIRST FLOOR

3/32" = 1'

BUSINESS OCCUPANCY - FULLY SPRINKLERED

GENERAL NOTES

1. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET IN HALF-TONE AND WITH NO TAG

ARE EXISTING-TO-REMAIN.

2. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XD' ARE TO BE

DEMOLISHED.

3. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XN' ARE TO BE

REPLACED.

4. FIRE ALARM DEVICES AND EQUIPMENT SHOWN

ON THIS SHEET WITH THE TAG 'XR' ARE TO BE

RELOCATED.

5. SEE CORRESPONDING 'FA' SHEET FOR NEW

DEVICE LOCATIONS.

6. WHERE NEW WALL DEVICES ARE NOT LOCATED

IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, PROVIDE

STAINLESS STEEL BLANK COVER FOR BOX. CUT

OFF CONDUIT ABOVE CEILING AND REMOVE TO

NEAREST JUNCTION BOX.

7. WHERE NEW CEILING DEVICES ARE NOT

LOCATED IN EXACTLY THE SAME LOCATION AS A

PREVIOUSLY-DEMOLISHED DEVICE, REPLACE

CEILING TILE TO MATCH EXISTING TILES.

REMOVE CONDUIT AND WIRE TO THE NEAREST

JUNCTION BOX.

8. REPLACE ALL EXISTING DUCT DETECTORS AND

ASSOCIATED KEY SWITCHES. NEW KEY SWITCH

LOCATION SHALL BE ACCESSIBLE, WITH HEIGHT

ACCORDING TO NOTES AND SPECIFICATIONS.

B WING CENTER WING CENTER WING A WING

S

F S

F S

F S

F S

F S F

S F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F S

F

F

FF

FF

FFF

F

F F

F

F

TC

F

A A

TP

XN

XD

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked:

Building Number

A/E Project Number

Drawing Number

Drawn:

Revisions: Date

ENGINEERS/ARCHITECT:

W.G. (BILL) HEFNER VAMC

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

FACILITY MANAGEMENT

DIVISION MANAGER

659-16-103

Architect

PROJECT LEAD

Fire Alarm, Electrical Engineer

VAMC SALISBURY

1601 Brenner Ave, Salisbury, NC 28144

100% CONSTRUCTION DOCUMENTS

SCBRSB11 DEC 2017

15-447REPLACE/UPGRADE CAMPUS

FIRE ALARM SYSTEM

(919) 858-7420 Consulting Group, PA www.acg-pa.com

Raleigh, NC Indianapolis,…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.