36C24419B0040-008.pdf

PDF 1 MB Posted

Attached to
Replace Mechanical Rooms, Project No. 542-18-105 Federal contract opportunity
Solicitation number
36C24419B0040
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

36C24419B0040 Electrical June 2019.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Replace Mechanical Rooms, Project No. 542-18-105, newest first.
File Type Posted
36C24419C0185-000.docx DOCX document
36C24419B0040-0002001.pdf PDF
36C24419B0040-0002004.pdf PDF
36C24419B0040-0002000.docx DOCX document
36C24419B0040-0002002.pdf PDF
36C24419B0040-0002003.pdf PDF
36C24419B0040-0002005.pdf PDF
36C24419B0040-0001000.docx DOCX document
36C24419B0040-0001001.pdf PDF
36C24419B0040-004.pdf PDF
36C24419B0040-005.pdf PDF
36C24419B0040-001.docx DOCX document
36C24419B0040-006.pdf PDF
36C24419B0040-003.pdf PDF
36C24419B0040-007.pdf PDF
36C24419B0040-002.pdf PDF
36C24419B0040-000.docx DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

L L

ELECTRICAL ABBREVIATIONS LIST

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORDCOORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED

PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND

WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE

BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL

PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND

THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED

MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO

AVOID CONFLICT DURING CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR

SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO

INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR

MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE

ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR

EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE

DEVICE'S SCREW TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT

UNLESS NOTED OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND

CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,

LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN

APPROVED THIRD PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE

SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC

PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE

MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT

BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE

BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS

DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. LOCAL DISCONNECTS SHALL BE NEMA 3R.

SHORT CIRCUIT CURRENT CALCULATIONS WILL BE

PERFORMED ON THE ELECTRICAL SYSTEM USING A

BOLTED THREE PHASE FAULT CONDITION FOR

CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND

MECHANICAL STRESS TO THE SYSTEM FOR

CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT

VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR

THE STARTING POINT OF THE CALCULATIONS.

METHOD OF SHORT CIRCUIT

CURRENT CALCULATIONS

USING OHM'S LAW AND THE KNOWN RESISTIVITY

CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM

PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS

TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO

AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP

OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP

CALCULATIONS

ELECTRICAL SYMBOL LEGEND

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED - NEMA 3R

DISCONNECT SWITCH FUSED - NEMA 3R

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

MAX 72" TOP

MAX 72" TOP

MOTOR-RATED SWITCH

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

EQUIPMENT CONNECTION

AS

NOTED

E

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

PUMP MOTOR

VFD VARIABLE FREQUENCY DRIVE

M

LIGHTING SYMBOL LEGEND

2' X 2' RECESSED DIRECT/INDIRECT TROFFER

2' X 4' RECESSED DIRECT/INDIRECT TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

48"

CENTER

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE

LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

OS

OS

LS

--- 4' LED STRIP FIXTURE - GASKETED AND

APPROVED FOR WET LOCATION

BID DEDUCTS

1. DDC CONTROLS (USE LOCAL CONTROLLERS FOR INDIVIDUAL PIECES OF EQUIPMENT ONLY).

2. CHILLED WATER FLOW METERS.

3. ALL WORK ASSOCIATED WITH BUILDING 8.

4. ALL WORK ASSOCIATED WITH BUILDING 6.

5. ALL WORK ASSOCIATED WITH BUILDING 2.

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:3

P M

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

VFD VFD VFD

V F

D

CWP-1

CWP-2

HWP-1 HWP-2

B07G

MECH.

ROOM

EF-1

6 6

7 7

B14C

MECH.

ROOM

DHWCP-1

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:4

P M

ED101

BUILDINGS 2 & 4 ELECTRICAL

DEMOLITION PLAN

2 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

2, 4

1 PUMP TO BE DEMOLISHED, SEE MECHANICAL PLANS.

DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

RECIRCULATION PUMP. CIRCUIT SHALL BE REUSED

FOR NEW PUMP, SEE NEW WORK PLAN EP101.

2 DISCONNECTS SERVING CWP-1, CWP-2, HWP-1, AND

HWP-2 SHALL BE DEMOLISHED.

3 EXISTING BRANCH CIRCUITS SERVING CWP-1 AND

CWP-2 SHALL BE REMOVED. EXISTING BRANCH

CIRCUITS SERVING HWP-1 AND HWP-2 SHALL BE

REMOVED. CIRCUIT SHALL BE REUSED, SEE NEW

WORK PLAN EP101.

4 DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

VENTILATION FAN. CIRCUIT SHALL BE REUSED FOR

NEW FAN, SEE NEW WORK PLAN EP101.

5 DEMOLISH LIGHTS AND CIRCUIT. CIRCUIT SHALL BE

REUSED, SEE NEW WORK PLAN EP101. (TYP)

6 DEMOLISH FOUR CWP AND HWP VFD'S AND

CONDUCTORS COMPLETELY (SEE NOTE A).

7 DEMOLISH VFD CIRCUITS BACK TO PANEL 'FCU-4'

LOCATED IN IT CLOSET B09 COMPLETELY (SEE NOTE

A).

A. COMPLETELY DEMOLISH CONDUCTORS,

CONDUITS, AND J-BOXES BACK TO ELECTRICAL

PANEL.

B. COMPLETELY DEMOLISH ELECTRICAL DEVICES

SHOWN ON THIS PLAN.

Scale: 1/2" = 1'-0"

BUILDING 4 ELECTRICAL DEMOLITION PLAN

Scale: 1/2" = 1'-0"

BUILDING 2 ELECTRICAL DEMOLITION PLAN

N

AREA OF WORK

BUILDING 2 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 4 KEY PLAN

SCALE: NO SCALE

MECHANICAL ROOM B01

(LOCATION OF PANEL 'FCU-4')

IT CLOSET B09

(LOCATION OF DDC

TERMINATION)0 1 2 4

NORTH

PLAN

0 1 2 4

N O

R T H

PLAN

VFD

F

D V

F D

V F

D

HWP-2 HWP-1

CWP-1

CWP-2

PANEL 'FCU-7'

PANEL

'MEP-7A'

MECH.

ROOM

(ETR)

(ETR)

PANEL LOCATED ON

LOWER LEVEL.

DEDICATED

WORKING SPACE

(TYP)

CP-1

B09

MECH.

ROOM

DHWCP-1

CP-1

MECH.

ROOM

EF-1

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:4

P M

ED102

BUILDINGS 6 & 7 ELECTRICAL

DEMOLITION PLAN

3 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

6, 7

Scale: 1/2" = 1'-0"

BUILDING 7 LOWER LEVEL ELECTRICAL DEMOLITION PLAN

1 PUMP TO BE DEMOLISHED, SEE MECHANICAL

PLANS. DEMOLISH CIRCUIT (SEE SHEET NOTE

A) TO RECIRCULATION PUMP. CIRCUIT SHALL

BE REUSED FOR NEW PUMP, SEE NEW WORK

PLAN EP102.

2 DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

CONDENSATE PUMP. CIRCUIT SHALL BE

REUSED FOR NEW PUMP, SEE NEW WORK

PLAN EP102.

3 DEMOLISH CONDUCTORS BETWEEN VFD AND

PUMP COMPLETELY (SEE SHEET NOTE A).

4 DISCONNECT AND REMOVE THE BRANCH

CIRCUIT CONDUCTORS, CONDUIT AND VFD'S

FROM PANEL 'MEP-7A' TO CHILL WATER

PUMPS CWP-1 AND CWP-2.

5 DISCONNECT AND REMOVE THE BRANCH

CIRCUIT CONDUCTORS, CONDUIT AND VFD'S

FROM PANEL 'MEP-7A' TO HOT WATER

RECIRCULATION PUMPS HWP-1 AND HWP-2.

6 DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

VENTILATION FAN. CIRCUIT SHALL BE

REUSED FOR NEW FAN, SEE NEW WORK

PLAN EP102.

7 DEMOLISH LIGHTS AND CIRCUIT. CIRCUIT

SHALL BE REUSED, SEE NEW WORK PLAN

EP102. (TYP)

8 DEMOLISH FOUR CWP AND HWP VFD'S AND

CONDUCTORS COMPLETELY (SEE SHEET

NOTE A).

Scale: 1/2" = 1'-0"

BUILDING 6 ELECTRICAL DEMOLITION PLAN

Scale: 1/2" = 1'-0"

BUILDING 7 UPPER LEVEL ELECTRICAL DEMOLITION PLAN

N

AREA OF WORK

BUILDING 6 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 7 KEY PLAN

SCALE: NO SCALE

IT CLOSET B20

(LOCATION OF DDC

TERMINATION)0 1 2 4

N O

R T H

PLAN

0 1 2 4

NORTH

PLAN

0 1 2 4

N O

R T H

PLAN

A. COMPLETELY DEMOLISH CONDUCTORS,

CONDUITS, AND J-BOXES BACK TO ELECTRICAL

PANEL.

B. COMPLETELY DEMOLISH ELECTRICAL DEVICES

SHOWN ON THIS PLAN.

F

D V

F D

V F

D V

F D

9-HWP-2

9-HWP-1

9-CWP-2

9-CWP-1

PANEL

'ELP-9'

(ETR)

SWBD

(ETR)

PANEL

'MCP-9A'

PANEL

'FCU-9'

9-HWP-2

9-CWP-1

9-CWP-2

9-HWP-1

3 4

3 4

XFMR

ROOM

B10

MECH.

ROOM

EF-1

CP-1

B10

MECH.

ROOM

DHWCP-1

CP-1

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:4

P M

ED103

BUILDINGS 8 & 9 ELECTRICAL

DEMOLITION PLAN

4 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

8, 9

Scale: 3/8" = 1'-0"

BUILDING 9 ELECTRICAL DEMOLITION PLAN

1 PUMP TO BE DEMOLISHED, SEE MECHANICAL

PLANS. DEMOLISH CIRCUIT (SEE SHEET NOTE

A) TO CONDENSATE PUMP. CIRCUIT SHALL BE

REUSED FOR NEW PUMP, SEE NEW WORK

PLAN EP103.

2 IF PANEL 'MCP-9A' HAS NOT BEEN REPLACED

IN A PREVIOUS PROJECT, DEMOLISH PANEL.

PROTECT EXISTING FEEDER AND BRANCH

CIRCUIT WIRING FOR RECONNECTION TO NEW

EQUIPMENT.

3 DISCONNECT AND REMOVE THE BRANCH

CIRCUIT CONDUCTORS, CONDUIT AND VFD'S

FROM PANEL 'MEP-9A' TO CHILL WATER PUMPS

CWP-1 AND CWP-2.

4 DISCONNECT AND REMOVE THE BRANCH

CIRCUIT CONDUCTORS, CONDUIT AND VFD'S

FROM PANEL 'MEP-9A' TO HOT WATER

RECIRCULATION PUMPS HWP-1 AND HWP-2.

5 DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

RECIRCULATION PUMP. CIRCUIT SHALL BE

REUSED FOR NEW PUMP, SEE NEW WORK

PLAN EP103.

6 DEMOLISH CIRCUIT (SEE SHEET NOTE A) TO

VENTILATION FAN. CIRCUIT SHALL BE REUSED

FOR NEW FAN, SEE NEW WORK PLAN EP103.

7 DEMOLISH LOCAL PUMP/ MOTOR DISCONNECT.

8 DEMOLISH LIGHTS AND CIRCUIT. CIRCUIT

SHALL BE REUSED, SEE NEW WORK PLAN

EP103. (TYP)

Scale: 1/2" = 1'-0"

BUILDING 8 ELECTRICAL DEMOLITION PLAN

N

AREA OF WORK

BUILDING 8 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 9 KEY PLAN

SCALE: NO SCALE

IT CLOSET B01B

(LOCATION OF DDC

TERMINATION)

0 1 2 4

NORTH

PLAN

0 21 4

N O

R T H

PLAN

A. COMPLETELY DEMOLISH CONDUCTORS,

CONDUITS, AND J-BOXES BACK TO ELECTRICAL

PANEL.

B. COMPLETELY DEMOLISH ELECTRICAL DEVICES

SHOWN ON THIS PLAN.

E

E E E

V F

D

VFD VFD VFD

P S I A T ° F

CERTIFIED BY:

M A X I M U M A L L O W A B L E W O R K I N G P R E S S U R E

° F A T P S I

M I N I M U M D E S I G N M E T A L T E M P E R A T U R E

M F G . S / N

Y E A R B U I L T

W

ASME

THERMAFLO INC

E E

M

E

M

MM

P S

I A

T

F

C E R T

IF

IE

D

B Y

M A

X I

M U

M

A

L O

W A

B

W O

R K

I N

G

P R

E S

S U

R E

F

A T

P S

I

M I

N I

M

D

S I

T

T

M

P E

R A

T U

R E

M F

S

N

Y E

B

I

L T

WA

S

M E

T H E R

M A F

LO

I N C

M M

A

A

A

A A A

A

4-CWP-1

4-CWP-2

4-HWP-2

4-HWP-1

'FCU-4'

2,4,6

2 4

DDC PANEL

4-CP-1

4-EF-MECH

2-12 AWG

1-12 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

3-12 AWG

1-12 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

'FCU-4'

26,28,30

'FCU-4' - 29

'FCU-4'

7,9,11

'FCU-4'

1,3,5

'FCU-4'

8,10,12

3-8 AWG

1-10 AWG EG

IN 3/4" C

'FCU-4' - 14

'FCU-4' - 14

4-DHWCP-1

B07G

MECH.

ROOM

3-8 AWG

1-10 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

'FCU-4' - 14

4-EF-VFD

2-12 AWG

1-12 AWG EG

IN 3/4" C

'FCU-4' - 14

'FCU-4' - 14

3-8 AWG

1-10 AWG EG

IN 3/4" C

4-TCV-1

2-12 AWG

1-12 AWG EG

IN 3/4" C

'PANEL'

EX CKT

B14C

MECH.

ROOM

2-DHWCP-1

2-TCV-1

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:5

P M

EP101

BUILDINGS 2 & 4 POWER PLAN

5 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

2, 4

0 1 2 4

NORTH

PLAN

1 RECONNECT NEW CIRCULATION PUMP TO

EXISTING CIRCUIT.

2 INSTALL UNISTRUT SUPPORT STRUCTURE TO

MOUNT SAFETY DISCONNECT SWITCH.

3 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

CWP-1 AND CWP-2 AND FROM DISCONNECTS

TO RELOCATED PUMPS.

4 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

HWP-1 AND HWP-2 AND FROM DISCONNECTS

TO RELOCATED PANELS.

5 INSTALL DISCONNECT AND BRANCH CIRCUIT

FROM PANEL 'FCU-4'. INSTALL NEW 15A-3P

BREAKER FOR DUPLEX CONDENSER PUMP –

SEE PANEL SCHEDULE.

6 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘FCU-4’ TO VENTILATION FAN.

7 CONNECT DDC PANEL TO RACK IN IT CLOSET

B09. COORDINATE WITH OIT AND DDC

CONTRACTOR.

8 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘FCU-4’ TO NEW DDC PANEL.

9 ADJUST LIGHT FIXTURE LOCATION AS

CEILING CONDITIONS PERMIT. ENSURE

UNIFORM ILLUMINATION THROUGHOUT

MECHANICAL ROOM. (TYP)

10 WATER HEATER CONTROL PANEL,

SINGLE-POINT CONNECTION.

Scale: 1/2" = 1'-0"

BUILDING 4 ELECTRICAL POWER PLAN

A. VFD'S SHOWN ARE SUPPLIED BY MECHANICAL

CONTRACTOR, INSTALLED BY ELECTRICAL

CONTRACTOR.

B. ELECTRICAL CONTRACTOR PROVIDED

DISCONNECTS SHALL BE INTERLOCKED WITH

VFD'S TO PREVENT RUNAWAY.

Scale: 1/2" = 1'-0"

BUILDING 2 ELECTRICAL POWER PLAN

EXISTING PANEL 'FCU-4'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 80

PANEL / FEEDER (TOTAL KVA) 28.65

TOTAL DEMAND AMPERES PER PHASE 90 76 73

NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED. TOTAL KV... 9.55 8.21 7.79 10.81 9.13 8.71

LOCATION: SUB-BASEMENT B01 SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 100A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 3.98 3.98 3.98 100% 3.98 3.98 3.98

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 3.69 3.69 3.69 125% 4.61 4.61 4.61

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

0.54 0.54 0.12

<=10 KVA@100% 0.54 0.54 0.12

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.34 0.00 0.00 125% 1.68 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

16.93 15.59 15.17 TOTAL

SUB TOTAL 7.92 7.92 7.50 9.01 7.67 7.67 SUB TOTAL

NEW DDC PANEL --- --- 0.12 1P-20 29 30 --- --- 0.29

SPARE --- 0.00 --- 1P-20 27 28 --- 0.29 ---

SPARE 0.00 --- --- 1P-20 25 26

3P-15

0.29 --- ---

CONDENSATE PUMP 4-CP-1

SPARE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 19 20 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE

EXISTING CIRCUIT --- 0.54 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE

EXISTING CIRCUIT 0.54 --- --- 1P-20 13 14 1P-20 1.34 --- --- LIGHTING, 4-EF, 4-DHWCP-1

--- --- 3.69 11 12 --- --- 3.69

--- 3.69 --- 9 10 --- 3.69 ---CHILLED WATER PUMP 4-CWP-2

3.69 --- ---

3P-40

7 8

3P-40

3.69 --- ---

HOT WATER PUMP 4-HWP-2

--- --- 3.69 5 6 --- --- 3.69

--- 3.69 --- 3 4 --- 3.69 ---CHILLED WATER PUMP 4-CWP-1

3.69 --- ---

3P-40

1 2

3P-40

3.69 --- ---

HOT WATER PUMP 4-HWP-1

A B C A B C

LOAD SERVED KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase LOAD SERVED

0 1 2 4

N O

R T H

PLAN

N

AREA OF WORK

BUILDING 2 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 4 KEY PLAN

SCALE: NO SCALE

MECHANICAL ROOM B01

(LOCATION OF PANEL 'FCU-4')

IT CLOSET B09

(LOCATION OF DDC

TERMINATION)

P S I A T ° F

CERTIFIED BY:

M A X I M U M A L L O W A B L E W O R K I N G P R E S S U R E

° F A T P S I

M I N I M U M D E S I G N M E T A L T E M P E R A T U R E

M F G . S / N

Y E A R B U I L T

W

ASME

THERMAFLO INC

M M

P S

I A

T

F

C E R T

IF

IE

D

B Y

M A

X I

M

L O

W A

B

R K

I

E S

S U

R E

F

A T

P S

I

M I

N I

M

S I

T

M

P E

R A

T U

R E

M F

N

Y E

I

L T

WA

S

M E

T H E R

M A F

LO

I N C

M M

E

M

M

E

V F

D V

F D

V F

D

VFD

E

E

E

E

A AA

A

PANEL 'FCU-7'

PANEL

'MEP-7A'

7-HWP-1 7-HWP-2

7-CWP-17-CWP-2

7-CP-1

DDC PANEL

MECH.

ROOM

TO VFD

TO VFD

'MEP-7A'

26,28,30

TO UPPER

LEVEL LIGHTS

3-12 AWG

1-12 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C'MEP-7A' - 14

2-DHWCP-1

2-TCV-1

3-6 AWG

1-10 AWG EG

IN 1" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-7A' - 29

3-8 AWG

1-10 AWG EG

IN 1" C

3-6 AWG

1-10 AWG EG

IN 1" C

TO VFD

EP102

B09

MECH.

ROOM

2-12 AWG

1-12 AWG EG

IN 3/4" C

'PANEL'

EX CKT

6-DHWCP-16-TCV-1

6-CP-1

'PANEL'

EX CKT

3-12 AWG

1-12 AWG EG

IN 3/4" C

NEW STEEL GRATE

MEZZANINE FLOOR

AA

A A

2-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-7A' - 14

7-EF-MECH

'MEP-7A' - 14

TO LOWER

LEVEL LIGHTS

MECH.

ROOM

2-12 AWG

1-12 AWG EG

IN 3/4" C

TO HWP

DISCONNECT

TO HWP

DISCONNECT

3-8 AWG

1-10 AWG EG

IN 1" C

'MEP-7A'

2,4,6

'MEP-7A'

8,10,12

'MEP-7A'

7,9,11

2-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-7A' - 14

7-EF-VFD

3-6 AWG

1-10 AWG EG

IN 1" C

'MEP-7A'

1,3,5

TO CWP

DISCONNECTS

M A

X H

E

IG

H T

FLOOR

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:0

P M

EP102

BUILDINGS 6 & 7 POWER PLAN

6 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

6, 7

1 RECONNECT NEW CIRCULATION PUMP TO

EXISTING CIRCUIT.

2 CONNECT DDC PANEL TO RACK IN IT CLOSET

B20. COORDINATE WITH OIT AND DDC

CONTRACTOR.

3 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

CWP-1 AND CWP-2 AND FROM DISCONNECTS

TO RELOCATED PUMPS.

4 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

HWP-1 AND HWP-2 AND FROM DISCONNECTS

TO RELOCATED PANELS.

5 INSTALL BRANCH CIRCUIT FROM PANEL

'MEP-7A'. INSTALL NEW 15A-3P BREAKER FOR

DUPLEX CONDENSER PUMP – SEE PANEL

SCHEDULE.

6 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-7A’ TO VENTILATION FAN.

7 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-7A’ TO CIRCULATION

PUMP.

8 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-7A’ TO NEW DDC PANEL.

9 ADJUST LIGHT FIXTURE LOCATIONS BELOW

MEZZANINE AS CEILING CONDITIONS PERMIT.

ENSURE UNIFORM ILLUMINATION

THROUGHOUT MECHANICAL ROOM.

10 ADJUST LIGHT FIXTURE LOCATIONS ABOVE

MEZZANINE AS CEILING CONDITIONS PERMIT.

ENSURE UNIFORM ILLUMINATION

THROUGHOUT MECHANICAL ROOM.

11 WATER HEATER CONTROL PANEL,

SINGLE-POINT CONNECTION.

12 INSTALL UNISTRUT SUPPORT STRUCTURE TO

MOUNT SAFETY DISCONNECT SWITCH.

MOUNT DISCONNECTS STACKED VERTICALLY

ON STRUCTURAL BEAM WITH SAFETY

DISCONNECT HANDLES NOT TO EXCEED 6'-7"

AFF.

Scale: 1/2" = 1'-0"

BUILDING 7 LOWER LEVEL ELECTRICAL POWER PLAN

Scale: 1/2" = 1'-0"

BUILDING 6 ELECTRICAL POWER PLAN

Scale: 1/2" = 1'-0"

BUILDING 7 UPPER LEVEL ELECTRICAL POWER PLAN

N

AREA OF WORK

BUILDING 6 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 7 KEY PLAN

SCALE: NO SCALE

EXISTING PANEL 'MEP-7A'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 99

PANEL / FEEDER (TOTAL KVA) 35.59

TOTAL DEMAND AMPERES PER PHASE 109 95 92

NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED. TOTAL KV... 11.40 10.06 9.64 13.12 11.45 11.03

LOCATION: SUB-BASEMENT B01 SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 100A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 3.98 3.98 3.98 100% 3.98 3.98 3.98

MINIMUM AIC (K AMPS) 22 MOTORS AND

EQUIPMENT

LARGEST 5.54 5.54 5.54 125% 6.93 6.93 6.93

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

0.54 0.54 0.12

<=10 KVA@100% 0.54 0.54 0.12

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.34 0.00 0.00 125% 1.68 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

20.63 19.29 18.87 TOTAL

SUB TOTAL 11.62 11.62 11.20 9.01 7.67 7.67 SUB TOTAL

NEW DDC PANEL --- --- 0.12 1P-20 29 30 --- --- 0.29

SPARE --- 0.00 --- 1P-20 27 28 --- 0.29 ---

SPARE 0.00 --- --- 1P-20 25 26

3P-15

0.29 --- ---

CONDENSATE PUMP 7-CP-1

SPARE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.00 SPARE

SPARE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- SPARE

SPARE 0.00 --- --- 1P-20 19 20 1P-20 0.00 --- --- SPARE

SPARE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPARE

EXISTING CIRCUIT --- 0.54 --- 1P-20 15 16 1P-20 --- 0.00 --- SPARE

EXISTING CIRCUIT 0.54 --- --- 1P-20 13 14 1P-20 1.34 --- --- LIGHTING, 7-EF, 7-DHWCP-1

--- --- 5.54 11 12 --- --- 3.69

--- 5.54 --- 9 10 --- 3.69 ---CHILLED WATER PUMP 7-CWP-2

5.54 --- ---

3P-60

7 8

3P-40

3.69 --- ---

HOT WATER PUMP 7-HWP-2

--- --- 5.54 5 6 --- --- 3.69

--- 5.54 --- 3 4 --- 3.69 ---CHILLED WATER PUMP 7-CWP-1

5.54 --- ---

3P-60

1 2

3P-40

3.69 --- ---

HOT WATER PUMP 7-HWP-1

A B C A B C

LOAD SERVED KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase LOAD SERVED

A. VFD'S SHOWN ARE SUPPLIED BY MECHANICAL

CONTRACTOR, INSTALLED BY ELECTRICAL

CONTRACTOR.

B. ELECTRICAL CONTRACTOR PROVIDED

DISCONNECTS SHALL BE INTERLOCKED WITH

VFD'S TO PREVENT RUNAWAY.

IT CLOSET B20

(LOCATION OF DDC

TERMINATION)0 1 2 4

N O

R T H

PLAN

0 1 2 4

NORTH

PLAN

0 1 2 4

N O

R T H

PLAN

Scale: No Scale

BUILDING 7 COLD WATER PUMP DISCONNECT ELEVATION

F

D V

F D

V F

D V

F D

PS

I

AT

°F

C E

R

TI

F

IE

D B

Y:

M

AX

IM

UM

A

LL

O W

AB

LE

RK

IN

PR

ES

SU

RE

°F

AT

PS

I

M I

N I

M

ES

IG

T

AL

T

EM

P

ER

AT

UR

E

M

FG

S

/N

YE

A

R B

UI

L

T

WA

S

M E

TH

E

R M

A

FL

O I

N C

M M

M

E

E

M

E

P S

I A

T

F

C E R T

IF

IE

D

B Y

M A

X I

M

L O

W A

B

R K

I

E S

S U

R E

F

A T

P S

I

M I

N I

M

S I

T

M

P E

R A

T U

R E

M F

N

Y E

I

L T

WA

S

M E

T H E R

M A F

LO

I N C

M M

9-HWP-29-HWP-1 9-CWP-2

9-CWP-1

A

A

A

A

SWBD

(ETR)

PANEL

'FCU-9'

PANEL

'MEP-9A'

PANEL

'ELP-9'

(ETR)

9-CP-1

2-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-9A' - 149-DHWCP-1

8-TCV-1

'MEP-9A'

26,28,30

3-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-9A' - 14

TO VFD

TO VFD

TO VFD

TO VFD

TO 9-HWP-2

DISCONNECT

TO 9-CWP-1

DISCONNECT

TO 9-CWP-2

DISCONNECT

TO 9-HWP-1

DISCONNECT

'MEP-9A'

1,3,5

'MEP-9A'

8,10,12

'MEP-9A'

7,9,11

'MEP-9A'

2,4,6

3-8 AWG

1-10 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

9-EF-MECH

'MEP-9A' - 14

3 4

DDC PANEL

2-12 AWG

1-12 AWG EG

IN 3/4" C

'MEP-9A' - 29

XFMR

ROOM

B10

MECH.

ROOM

2-12 AWG

1-12 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

3-10 AWG

1-10 AWG EG

IN 3/4" C

9-EF-VFD

'MEP-9A' - 14

2-12 AWG

1-12 AWG EG

IN 3/4" C

3-10 AWG

1-10 AWG EG

IN 3/4" C

3-8 AWG

1-10 AWG EG

IN 3/4" C

2-12 AWG

1-12 AWG EG

IN 3/4" C

'PANEL'

EX CKT

8-DHWCP-1

8-TCV-1

8-CP-1

'PANEL'

EX CKT

3-12 AWG

1-12 AWG EG

IN 3/4" C

B10

MECH.

ROOM

## KEY NOTES:

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:1

P M

EP103

BUILDINGS 8 & 9 POWER PLAN

7 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

8, 9

1 RECONNECT NEW CIRCULATION PUMP TO

EXISTING CIRCUIT.

2 IF PANEL 'MEP-9A' HAS BEEN INSTALLED IN

PREVIOUS PROJECT, PROVIDE VA WITH FULL

CREDIT. OTHERWISE, INSTALL NEW PANEL

'MEP-9A' AS SHOWN.

3 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

CWP-1 AND CWP-2 AND FROM DISCONNECTS

TO RELOCATED PUMPS.

4 INSTALL NEW BRANCH CIRCUIT FROM VFD’S

TO SAFETY DISCONNECT SWITCHES AT

HWP-1 AND HWP-2 AND FROM DISCONNECTS

TO RELOCATED PANELS.

5 INSTALL BRANCH CIRCUIT FROM PANEL

'MEP-9A'. INSTALL NEW 15A-3P BREAKER FOR

DUPLEX CONDENSER PUMP – SEE PANEL

SCHEDULE.

6 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-9A’ TO VENTILATION FAN.

7 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-9A’ TO CIRCULATION

PUMP.

8 INSTALL NEW 120V/20A BRANCH CIRCUIT

FROM PANEL ‘MEP-9A’ TO NEW DDC PANEL.

9 ADJUST LIGHT FIXTURE LOCATION AS

CEILING CONDITIONS PERMIT. ENSURE

UNIFORM ILLUMINATION THROUGHOUT

MECHANICAL ROOM.

10 CONNECT DDC PANEL TO RACK IN IT CLOSET

B01B. COORDINATE WITH OIT AND DDC

CONTRACTOR.

11 TEMPORARY CONSTRUCTION ENTRANCE

SHALL BE USED BY CONTRACTORS TO

ACCESS AREA OF WORK.

12 TEMPORARY RATED WALL TO ENCLOSE

OPENING IN MECHANICAL ROOM WALL FOR

CONSTRUCTION ENTRANCE.

13 WATER HEATER CONTROL PANEL,

SINGLE-POINT CONNECTION.

Scale: 3/8" = 1'-0"

BUILDING 9 ELECTRICAL POWER PLAN

Scale: 1/2" = 1'-0"

BUILDING 8 ELECTRICAL POWER PLAN 0 1 2 4

NORTH

PLAN

PANEL 'MEP-9A'

(TOTAL KVA) X 1000 = TOTAL AMPS

VOLTS X 1.732 73

PANEL / FEEDER (TOTAL KVA) 26.28

TOTAL DEMAND AMPERES PER PHASE 83 70 66

NOTE: ALL MOTOR CIRCUIT BREAKERS SHALL BE HACR RATED. TOTAL KV... 8.76 7.42 7.00 10.02 8.34 7.92

SIGN 0.00 0.00 0.00 125% 0.00 0.00 0.00

DEDICATED RECEPT 0.00 0.00 0.00 100% 0.00 0.00 0.00

NEUTRAL RATING 100% FIX. ELEC. SPACE HEAT 0.00 0.00 0.00 100% 0.00 0.00 0.00

BUS RATING 225A WATER HEATERS 0.00 0.00 0.00 125% 0.00 0.00 0.00

MCB RATING MLO ALL OTHERS 3.19 3.19 3.19 100% 3.19 3.19 3.19

MINIMUM AIC (K AMPS) 22,000 MOTORS AND

EQUIPMENT

LARGEST 3.69 3.69 3.69 125% 4.61 4.61 4.61

SERVICE ENTR. RATED YES X NO >10KVA@50% 0.00 0.00 0.00

MAIN CIRCUIT BREAKER YES X NO GENERAL USE

RECEPT

0.54 0.54 0.12

<=10 KVA@100% 0.54 0.54 0.12

ISOLATED GROUND BUS YES X NO GENERAL LIGHTING 1.34 0.00 0.00 125% 1.68 0.00 0.00

MOUNTING SURFACE A B C A B C

C/B TEMP. 75 C. RATING 120 208 V 3 PH 4 WIRE

LOAD TYPE

CONNECTED KVA NEC DEM

FACTOR

DEMAND KVA

15.35 14.01 13.59 TOTAL

SUB TOTAL 7.13 7.13 6.71 8.22 6.88 6.88 SUB TOTAL

NEW DDC PANEL --- --- 0.12 1P-20 29 30 --- --- 0.29

SPACE --- 0.00 --- 1P-20 27 28 --- 0.29 ---

SPACE 0.00 --- --- 1P-20 25 26

3P-15

0.29 --- ---

CONDENSATE PUMP 9-CP-1

SPACE --- --- 0.00 1P-20 23 24 1P-20 --- --- 0.00 SPACE

SPACE --- 0.00 --- 1P-20 21 22 1P-20 --- 0.00 --- SPACE

SPACE 0.00 --- --- 1P-20 19 20 1P-20 0.00 --- --- SPACE

SPACE --- --- 0.00 1P-20 17 18 1P-20 --- --- 0.00 SPACE

LCTP PANEL --- 0.54 --- 1P-20 15 16 1P-20 --- 0.00 --- SPACE

RECEPT - ROOM B10 0.54 --- --- 1P-15 13 14 1P-20 1.34 --- --- LIGHTING, 9-EF, 9-DHWCP-1

--- --- 2.90 11 12 --- --- 2.90

--- 2.90 --- 9 10 --- 2.90 ---HOT WATER PUMP 9-HWP-2

2.90 --- ---

3P-30

7 8

3P-30

2.90 --- ---

HOT WATER PUMP 9-HWP-1

--- --- 3.69 5 6 --- --- 3.69

--- 3.69 --- 3 4 --- 3.69 ---CHILLED WATER PUMP 9-CWP-2

3.69 --- ---

3P-40

1 2

3P-40

3.69 --- ---

CHILLED WATER PUMP 9-CWP-1

A B C A B C

LOAD SERVED KVA / Phase

CKT

BRKR

CKT

NO

NEUTRAL

A B C

CKT

NO

CKT

BRKR

KVA / Phase LOAD SERVED

N

AREA OF WORK

BUILDING 8 KEY PLAN

SCALE: NO SCALE

N

AREA OF WORK

BUILDING 9 KEY PLAN

SCALE: NO SCALE

A. VFD'S SHOWN ARE SUPPLIED BY MECHANICAL

CONTRACTOR, INSTALLED BY ELECTRICAL

CONTRACTOR.

B. ELECTRICAL CONTRACTOR PROVIDED

DISCONNECTS SHALL BE INTERLOCKED WITH

VFD'S TO PREVENT RUNAWAY.

IT CLOSET B01B

(LOCATION OF DDC

TERMINATION)

0 21 4

N O

R T H

PLAN

STRUCTURAL CEILING

SUSPENDED CEILINGLIGHT FIXTURE

WALL

ELECTRICAL

EQUIPMENT

EXCLUSIVE

DEDICATED

SPACE

FRONT EDGE PLAN

OF ELECTRICAL

EQUIPMENT

SEE T

ABLE 'A

CLEARANCE SHALL BE 30" OR WIDTH OF

EQUIPMENT IF EQUIPMENT IS WIDER THAN 30".

CLEARANCE DOES NOT HAVE TO BE CENTERED

WITH EQUIPMENT BUT AT MUST BE AT LEAST

EVEN WITH ONE EDGE. EQUIPMENT DOOR SHALL

BE ABLE TO OPEN AT LEAST 90 DEGREES.

NOTE:

THIS FIGURE ILLUSTRATES THE WORKING SPACE IN FRONT OF ELECTRICAL EQUIPMENT

REQUIRED BY NEC 110.16.

NOTE:

THIS FIGURE ILLUSTRATES THE EXCLUSIVE DEDICATED SPACE

REQUIRED ABOVE AND BELOW PANELBOARDS FOR ELECTRICAL

DISTRIBUTION TO AND FROM PANELBOARDS REQUIRED BY NEC.

ALL ELECTRICAL EQUIPMENT

PANELBOARDS

TABLE 'A' - WORKING CLEARANCE

STRUCTURAL CEILING

SUSPENDED CEILING

WALL

LIGHT FIXTURE

PANELBOARD

EXCLUSIVE

DEDICATED

SPACE

EXCLUSIVE

DEDICATED

SPACE

VOLTAGE TO GROUND

(NOMINAL)

MINIMUM CLEAR DISTANCE

0 - 150

150 - 600

3' - 0"

3' - 0"

3' - 0"

3' - 6"

3' - 0"

4' - 0"

CONDITION 1 CONDITION 2 CONDITION 3

GENERAL NOTES:

1. ELECTRICAL EQUIPMENT INCLUDES BUT IS NOT LIMITED TO PANELBOARDS, SAFETY

SWITCHES, MOTOR STARTERS, JUNCTION BOXES, AND OTHER ELECTRICAL

DISTRIBUTION AND CONTROLS EQUIPMENT.

2. PIPING, DUCTS OR EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR

ARCHITECTURAL APPURTENANCES SHALL NOT BE PERMITTED TO BE INSTALLED IN,

ENTER, OR PASS THROUGH THE DEDICATED SPACES SHOWN ABOVE.

TABLE 'A' DEFINITIONS:

CONDITION 1:

CONDITION 2:

CONDITION 3:

EXPOSED LIVE PARTS ON ONE SIDE AND NO LIVE OR

GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING

SPACE.

OR

EXPOSED LIVE PARTS ON BOTH SIDES EFFECTIVELY GUARDED

BY SUITABLE WOOD OR OTHER INSULATING MATERIALS.

EXPOSED LIVE PARTS ON ONE SIDE AND GROUNDED PARTS

ON THE OTHER SIDE.

EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING

SPACE (NOT GUARDED AS PROVIDED IN CONDITION 1) WITH

THE OPERATOR BETWEEN.

INSULATED WIRE OR INSULATED BUSBARS OPERATING AT NOT OVER 300V

SHALL NOT BE CONSIDERED LIVE PARTS.

M

IN

IM

U

M

M

IN

IM

U

M

1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM)

WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF

OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN.

(305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.

C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL

ELECTRICAL METALLIC TUBING

D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING - THE FOLLOWING TYPES OF STEEL FLEXIBLE METAL GAS

PIPING MAY BE USED:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

OMEGA FLEX INC

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

TITEFLEX CORP

A BUNDY CO

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ON PIPING MAY OR MAY

NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

WARD MFG INC

3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT

LOCATION ON BOTH SIDES OF WALL.

THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN

WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.

THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 HR.

3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,

*BEARING THE UL CLASSIFICATION MARKING

SYSTEM NO.W-L-1001

JUNE 15, 2005

F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)

T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT

MAX PIPE OR

CONDUIT DIAM

IN. (mm)

1 (25)

1 (25)

4 (102)

6 (152)

12 (305)

F RATING

HR

1 OR 2

3 OR 4

1 OR 2

3 OR 4

1 OR 2

T RATING

HR

0+, 1 OR 2

3 OR 4

SECTION A-A

1B

1A

3A

A

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:3

P M

E-501

ELECTRICAL DETAILS

8 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

Scale: N.T.S.

DEDICATED WORKING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Scale: N.T.S.

UL PENETRATION DETAIL W-L-1001

LIGHTING FIXTURE SCHEDULE

A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE

FOR MISMATCHED OR INACCURATE PART NUMBERS.

B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.

C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE

SUBMITTALS.

D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH

THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.

E. AMBIENT TEMPERATURE OPERATION IS -40oF UP TO +122oF.

GENERAL NOTES:

STEAM CONDENSATE PUMP SCHEDULE

MARK LOCATION

SYSTEM

AND/OR

SERVICE

TYPE UNIT

FLOW

EACH

PUMP

DISCHARGE

PRESSURE

MIN

RECEIVER

SIZE

MOTOR

BASIS OF DESIGN

MANUF.

BASIS OF DESIGN

MODEL NO.

REMARKSNOMINAL POWER

EACH

PHASE VOLT RPM

GPM PSIG GAL HP

4-CP-1 BUILDING 4 MER BLDG 4 STEAM DUPLEX 22.5 20 21 1/2 3 208 3500 SPIRAX SARCO VNS152 1, 2, 3

6-CP-1 BUILDING 6 MER BLDG 6 STEAM DUPLEX 22.5 20 21 1/2 3 208 3500 SPIRAX SARCO VNS152 1, 2, 3

7-CP-1 BUILDING 7 MER BLDG 7 STEAM DUPLEX 22.5 20 21 1/2 3 208 3500 SPIRAX SARCO VNS152 1, 2, 3

8-CP-1 BUILDING 8 MER BLDG 8 STEAM DUPLEX 22.5 20 21 1/2 3 208 3500 SPIRAX SARCO VNS152 1, 2, 3

9-CP-1 BUILDING 9 MER BLDG 9 STEAM DUPLEX 22.5 20 21 1/2 3 208 3500 SPIRAX SARCO VNS152 1, 2, 3

FAN SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG SERVED

AIR FLOW ESP TSP

FAN MOTOR

ELECTRICAL

CONTROL

SEQUENCE

REMARKS

TYPE WHEEL

DIAMETER

MIN %

EFF

DRIVE

FAN MAX

RPM

NOMINAL

POWER

PHASE VOLT RPM SPEED CONTROL

CFM IN W.G. IN W.G. IN BHP HP

4-EF-MECH BUILDING 4 MER BUILDING 4 MER 1,620 0.15 0.348 SIDEWALL PROPELLER AXIAL 14 40% DIRECT 1,502 0.22 1/3 1 115 1725 CONSTANT COOLING

THERMOSTAT

1, 2, 4, 5

4-EF-VFD

BUILDING 4 VFD

CLOSET

BUILDING 4 VFD

CLOSET

100 0.25 0.25 SQUARE INLINE CENTRIFUGAL 6 19% DIRECT 1,536 0.02 1/15 1 115 1725 CONSTANT COOLING

THERMOSTAT

7-EF-MECH BUILDING 7 MER BUILDING 7 MER 2,700 0.25 0.25 SQUARE INLINE CENTRIFUGAL 18 35% BELT 764 0.33 1/2 1 115 1725 CONSTANT COOLING

THERMOSTAT

1, 3, 4, 5

7-EF-VFD STORAGE B02 STORAGE B02 250 0.25 0.25 SQUARE INLINE CENTRIFUGAL 8 30% DIRECT 1,320 0.03 1/10 1 115 1725 CONSTANT COOLING

THERMOSTAT

9-EF-MECH BUILDING 9 MER BUILDING 9 MER 1,400 0.15 0.254 SIDEWALL PROPELLER AXIAL 16 31% DIRECT 1,036 0.18 1/4 1 115 1725 CONSTANT COOLING

THERMOSTAT

1, 2, 4, 5

9-EF-VFD TRANSFORMER

B12

TRANSFORMER

B12

350 0.25 0.25 SQUARE INLINE CENTRIFUGAL 9 40 DIRECT 1,239 0.03 1/10 1 115 1725 CONSTANT COOLING

THERMOSTAT

HYDRONIC PUMP SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE

TYPE

CIRCULATING

FLUID

MIN %

EFF

ELECTRICAL

MOTOR

BASIS OF

DESIGN

MANUF.

BASIS OF DESIGN

MODEL NO.

REMARKS

FLUID

FLOW HEAD NPSH

REQUIRED

SP GR

NOMINAL

POWER

PHASE VOLT MAX RPM SPEED CONTROL

GPM FT FT HP

4-CWP-1 BUILDING 4 MER BUILDING 4 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 325 77 9.4 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3

4-CWP-2 BUILDING 4 MER BUILDING 4 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 325 77 9.4 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3, 4

4-HWP-1 BUILDING 4 MER BUILDING 4 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 305 71 8.65 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3

4-HWP-2 BUILDING 4 MER BUILDING 4 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 305 71 8.65 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3, 4

7-CWP-1 BUILDING 7 MER BUILDING 7 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 295 100 14 1 66 15 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2GB 1, 2, 3

7-CWP-2 BUILDING 7 MER BUILDING 7 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 295 100 14 1 66 15 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2GB 1, 2, 3, 4

7-HWP-1 BUILDING 7 MER BUILDING 7 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 280 85 11.9 1 72 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2EB 1, 2, 3

7-HWP-2 BUILDING 7 MER BUILDING 7 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 280 85 11.9 1 72 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2EB 1, 2, 3, 4

9-CWP-1 BUILDING 9 MER BUILDING 9 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 260 70 7.4 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3

9-CWP-2 BUILDING 9 MER BUILDING 9 CHILLED WATER

BASE MOUNTED END

SUCTION

WATER 260 70 7.4 1 77 10 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2.5BB 1, 2, 3, 4

9-HWP-1 BUILDING 9 MER BUILDING 9 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 260 50 17.9 1 63 7.5 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2BD 1, 2, 3

9-HWP-2 BUILDING 9 MER BUILDING 9 HEATING WATER

BASE MOUNTED END

SUCTION

WATER 260 50 17.9 1 63 7.5 3 208 1800 VARIABLE BELL & GOSSETT e-1510 2BD 1, 2, 3, 4

Revisions: Date

Drawing Title:

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/6

/2

:1

:3

P M

E-601

ELECTRICAL SCHEDULES

9 9CGS ABT

RENOVATE MECHANICAL

ROOMS & EQUIPMENT

PHASE 1

1400 BLACKHORSE HILL RD

COATESVILLE, PA 19320

05/01/2019

100% CONSTRUCTION DOCUMENTS

542-18-10517-251

TYPE MANUFACTURER CATALOG NUMBER LAMP DESCRIPTION VOLTAGE LOAD (VA) MOUNTING DESCRIPTION

A COLUMBIA LXEM4-40ML-RFP-EU LED; 4,760 LUMENS, 80 CRI;

4000K

4' INDUSTRIAL STRIP ENCLOSURE AND GASKETED WITH

RIBBED, FROSTED POLYCARBONATE LENS; WET

LOCATION.

120-277V 37.4 SUSPENDED

*FOR REFERENCE ONLY, SEE MECHANICAL DRAWINGS FOR REMARKS.

*FOR REFERENCE ONLY, SEE MECHANICAL DRAWINGS FOR REMARKS.

*FOR REFERENCE ONLY, SEE MECHANICAL DRAWINGS FOR REMARKS.

Sheets
E-001 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS
ED101 - BUILDINGS 2 & 4 ELECTRICAL DEMOLITION PLAN
ED102 - BUILDINGS 6 & 7 ELECTRICAL DEMOLITION PLAN
ED103 - BUILDINGS 8 & 9 ELECTRICAL DEMOLITION PLAN
EP101 - BUILDINGS 2 & 4 POWER PLAN
EP102 - BUILDINGS 6 & 7 POWER PLAN
EP103 - BUILDINGS 8 & 9 POWER PLAN
E-501 - ELECTRICAL DETAILS
E-601 - ELECTRICAL SCHEDULES