36C24418B0585-0001004.pdf

PDF 807 KB Posted

Attached to
Correct Retro-Commissioning Discrepancies Phase 2 #503-15-205
Solicitation number
36C24418B0585
Issued by

About this file

36C24418B0585 0001 Drawing 01-E701.pdf

View the file

Other files

File Type Posted
36C24419C0030-000.docx DOCX document
36C24418B0585-0004001.pdf PDF
36C24418B0585-0004000.docx DOCX document
36C24418B0585-0003001.pdf PDF
36C24418B0585-0003000.docx DOCX document
36C24418B0585-0002002.pdf PDF
36C24418B0585-0002001.pdf PDF
36C24418B0585-0002000.docx DOCX document
36C24418B0585-0001001.pdf PDF
36C24418B0585-0001005.pdf PDF
36C24418B0585-0001003.pdf PDF
36C24418B0585-0001006.pdf PDF
36C24418B0585-0001002.pdf PDF
36C24418B0585-0001000.docx DOCX document
36C24418B0585-003.docx DOCX document
36C24418B0585-001.docx DOCX document
36C24418B0585-006.docx DOCX document
36C24418B0585-002.docx DOCX document
36C24418B0585-005.pdf PDF
36C24418B0585-004.pdf PDF
36C24418B0585-000.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3 1A

A

SECTION A-A

FLOOR OR WALL ASSEMBLY -- MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS *. MAX DIAM OF OPENING IS 12 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

THROUGH PENETRANTS -- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

THE ANNULAR SPACE SHALL BE 0 IN. (POINT CONTACT) TO MAX 1-1/4 IN. THE FOLLOWING TYPES AND SIZES OF

METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE -- NOM 10 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE -- NOM 10 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT -- NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.

D. COPPER TUBING -- NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. COPPER PIPE -- NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

PACKING MATERIAL -- MIN 3 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FOR NOM 4 IN. DIAM (AND SMALLER) PIPES, CONDUITS OR TUBINGS AND A MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FOR PIPE GREATER THAN NOM 4 IN. DIAM, FIRMLY PACKED INTO OPENING AS A PERMANENT FORM.

PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS

REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

FILL, VOID OR CAVITY MATERIAL* -- SEALANT -- MIN 1/2 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH THE TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL. AT THE POINT OF CONTACT LOCATION BETWEEN PIPE AND CONCRETE, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE/PIPE INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF WALL. W RATING

APPLIES ONLY WHEN CP601S OR CP604 SEALANT IS USED.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP601S, CP604, CP606 OR FS-ONE SEALANT

*BEARING THE UL CLASSIFICATION MARK

2 1B

1A

D

D

SECTION D-D

WALL ASSEMBLY -- THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS -- WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN

THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. WIDER AND 4 TO 6 IN. HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. CLEARANCE IS PRESENT BETWEEN THE

PENETRATING ITEM AND THE FRAMING ON ALL FOUR SIDES.

B. GYPSUM BOARD* -- 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE

INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4 IN.

FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN. FOR WOOD STUD WALLS.

THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.

THROUGH-PENETRANTS -- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM PERPENDICULAR. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE -- NOM 30 IN DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE -- NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT -- NOM 4 IN DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. DIAM STEEL CONDUIT.

D. COPPER TUBING -- NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. COPPER PIPE -- NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

FILL, VOID OR CAVITY MATERIAL* -- SEALANT -- MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH

SURFACES OF WALL .

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-ONE SEALANT

*BEARING THE UL CLASSIFICATION MARK

LENGTH AS REQUIRED

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

NOTES

1. METAL CHANNEL STRUT SUPPORT LONGER THAN

36" SHALL BE INSTALLED WITH A CENTER SUPPORT

ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 0533, RACEWAYS AND

BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY

EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER

TO SPECIFICATION SECTION 10 05 41, SEISMIC

RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL

COMPONENTS.

LOCKING SQUARE

WASHER & LOCKNUT

3/8" MIN GALVANIZED

THREADED ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

WALL SLEEVE

SEAL ALL PENETRATIONS

NOTES:

1. LABEL SHALL BE DISPLAYED ON ALL SWITCHBOARDS, PANELBOARDS,

TRANSFER SWITCHES AND PULLBOXES (MULTIPLE VOLTAGES).

2. NAMEPLATE SHALL BE WHITE LETTERING ON BLACK MICARTA.

3. IF ONLY ONE VOLTAGE IS PRESENT, LABEL SHALL INDICATE ONLY THAT

RESPECTIVE VOLTAGE.

2" H

IG

H

4" WIDE

VOLTAGE

208Y / 120V

PHASE A BLACK

PHASE B RED

PHASE C BLUE

NEUTRAL WHITE

VOLTAGE

480Y / 277V

PHASE A BROWN

PHASE B ORANGE

PHASE C YELLOW

NEUTRAL GRAY

GROUND

PHASE

CONDUCTOR

CONDUITBREAKER SIZE

NOTE:

1. PROVIDE A CONDUCTOR PER BREAKER POLE. THESE ARE THE MINIMUM SIZES REQUIRED

FOR EACH CIRCUIT. CONTRACTOR TO MAKE ALL THE NECESSARY FIELD ADJUSTMENTS TO

COMPENSATE FOR VOLTAGE DROP.

2. IN GENERAL, VOLTAGE DROP FOR ANY BRANCH CIRCUIT SHALL NOT EXCEED 3%. VOLTAGE

DROP FOR ANY FEEDER SHALL NOT EXCEED 2%. WHERE VOLTAGE DROP EXCEEDS THESE

REQUIREMENTS, THE CONTRACTOR SHALL INCREASE THE SIZE OF THE CONDUCTORS AND

RACEWAY AS REQUIRED.

BRANCH CIRCUIT WIRING SCHEDULE

NEUTRAL

CONDUCTOR

3/4"

3/4"

3/4"

1"

1"

1"

1"

1-1/4"

1-1/4"

1-1/2"

15A

20A

30A

35A

40A

45A

50A

60A

70A

80A

STAINLESS

CLAMP (TYP.)

PREFABRICATED RUBBER BOOT

CAP WITH GRADUATED STEPS

AND WEATHER-PROOF

PRESSURE SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

ROOF MEMBRANE

ROOF

WATER CUT-OFF

MASTIC COMPATIBLE

WITH ROOF MEMBRANE

CONDUIT CLAMP

SIZE AS REQUIRED INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

CONDUIT CLAMP

SIZE AS REQUIRED

LOCKING SQUARE WASHER

AND LOCKNUT

3/8" MIN. GALVANIZED

THREADED ROD, (TYP.)

STEEL EXPANSION ANCHOR

MULTIPLE MEMBRANE STRIPPING PLIES

FEATHERED AT FIELD OF ROOF BY

ROOFING CONTRACTOR. PRIME FLANGE

BEFORE STRIPPING.

PRE-FABRICATED FORMED .06" THICK

ALUMINUM FLASHING ROUND COLLAR

WITH MIN. 3" WIDE FLANGE

ATTACH TO ROOF PER MANUFACTURER'S

INSTRUCTIONS

BATT INSULATION

CONDUIT

(TYP.)

SEAL-OFF

FITTING

(TYP.)

1. MAINTAIN A MINIMUM CLEARANCE OF 12" ON ALL SIDES OF ROOF PENETRATION

FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF AND STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE

PROPER METHODS AND MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

GENERAL NOTES:

ARC FLASH AND SHOCK HAZARD

APPROPRIATE PPE REQUIRED

480Y/277V-3∅-4W-60HZ

2500 AMPERES HORIZONTAL BUS

SHORT-CIRCUIT CURRENT RATING

65,000 AMPERES RMS SYM

TYPICAL PANELBOARD

OR SWITCHBOARD

NOTES:

1. THE PROSPECTIVE SYMMETRICAL FAULT CURRENT AT A NOMINAL VOLTAGE TO WHICH AN

APPARATUS OR SYSTEM IS ABLE TO BE CONNECTED WITHOUT SUSTAINING DAMAGE EXCEEDING

ACCEPTANCE CRITERIA, SHALL BE DISPLAYED ON THE EXTERIOR OF THE STRUCTURE, OR ON THE

INSIDE COVER OF A PANELBOARD.

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

6/ 8/

:1

9:

A M

CORRECT

RETRO-COMMISSIONING

DISCREPANCIES

503-15-205

BK BK

JAMES E. VAN ZANDT MEDICAL CENTER

ALTOONA, PA 16602

01-E701

ELECTRICAL SCHEDULES AND DETAILS

06/07/2018

14-

100% CONSTRUCTION DOCUMENTS

EQUIPMENT CONNECTION SCHEDULE

TAG IDENTIFICATION HP

FLA /

MCA

VOLTAGE / PH /

LOAD

CKT. BKR /

MCP PANEL CKT. #

NEMA

TYPE

DISC / POLES /

FUSE FEEDER SIZE

CONDUIT

SIZE COMMENTS

AHU-1 (RF-1) AHU-1 RETURN FAN 2 3.4 FLA 480 V/3-2823 VA 15A ME-MCC1 2 1 VFD W/ 30A/3P (3) #12, (1) #12 GND 3/4" RE-USE EXISTING MCP

AHU-1 (SF-1) AHU-1 SUPPLY FAN 15 21 FLA 480 V/3-17438 VA 50A ME-MCC1 1 1 VFD W/ 60A/3P (3) #6, (1) #10 GND 1" RE-USE EXISTING MCP

AHU-3 (RF-3) AHU-3 RETURN FAN 10 32.2 FLA 208 V/3-11587 VA 60A ESP-3H 44,46,48 1 VFD W/ 60A/3P (3) #4, (1) #10 GND 1-1/4" PROVIDE NEW CIRCUIT BREAKER

AHU-3 (SF-3) AHU-3 SUPPLY FAN 30 92 FLA 208 V/3-33105 VA 125A ESP-3H 49,51,53 1 VFD W/ 200A/3P (3) #1, (1) #6 GND 2" PROVIDE NEW CIRCUIT BREAKER

AHU-5 (RF-5) AHU-5 RETURN FAN 5 7.6 FLA 480 V/3-6311 VA 15A ME-MCC2 9 1 VFD W/ 30A/3P (3) #12, (1) #12 GND 3/4" RE-USE EXISTING MCP

AHU-5 (SF-5) AHU-5 SUPPLY FAN 10 14 FLA 480 V/3-11626 VA 25A ME-MCC2 7 1 VFD W/ 30A/3P (3) #10, (1) #10 GND 3/4" PROVIDE NEW MCP

AHU-6 (RF-6) AHU-6 RETURN FAN 3 11 FLA 208 V/3-3958 VA 20A PP-4 1,3,5 1 VFD W/ 30A/3P (3) #12, (1) #12 GND 3/4" RE-USE EXISTING CIRCUIT BREAKER

AHU-6 (SF-6) AHU-6 SUPPLY FAN 15 48.3 FLA 208 V/3-17380 VA 100A PP-4 16,18,20 1 VFD W/ 100A/3P (3) #1, (1) #8 GND 2" RE-USE EXISTING CIRCUIT BREAKER

RTU-L ROOF TOP UNIT - LAUNDRY - 51.9 MCA 208 V/3-17056 VA 60A PPAC 13,15,17 3R VFD W/ 60A/3P (3) #4, (1) #10 GND 1-1/4" PROVIDE NEW CIRCUIT BREAKER

NOT TO SCALE

CONDUIT THROUGH CONCRETE WALL - FLOOR ASSEMBLY

NOT TO SCALE

CONDUIT THROUGH FIRE RATED DRYWALL PARTITION

NOT TO SCALE

CONDUIT TRAPEZE MOUNTING DETAIL

NOT TO SCALE

DETAIL - WALL SLEEVE

NOT TO SCALE

BRANCH WIRING IDENTIFICATION

NOT TO SCALE

CONDUIT ROOF PENETRATION DETAIL

NOT TO SCALE

EQUIPMENT LABELING REQUIREMENTS

EQUIPMENT SCHEDULE NOTES:

1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF EQUIPMENT.

2. E.C. SHALL VERIFY AND COORDINATE EXACT OCPD AND OVERLOAD RATING WITH RESPECTIVE CONTRACTOR AND EQUIPMENT SUPPLIER. ADJUST CIRCUIT ACCORDINGLY.

3. PROVIDE CIRCUITING AND CONNECTIONS FROM ALL VFDS, FUSED AND NON-FUSED DISCONNECT SWITCHES, COMBINATION STARTERS, MANUAL MOTOR STARTERS, AND

CONTROLLERS TO MECHANICAL EQUIPMENT SERVED. CONDUCTOR AND CONDUIT SIZES SHALL MATCH THOSE SERVING THE EQUIPMENT FROM THE PANELBOARD.

427.8 :TOTAL DEMAND LOAD (A)

154.1 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

427.8 :TOTAL CONNECTED LOAD (A)

1. RE-USE EXISTING CIRCUIT BREAKER. 154.1 :TOTAL CONNECTED LOAD (KVA)

NOTES: 428.1 428.1 428.1 :CONNECTED LOAD/PHASE (A)

51.4 51.4 51.4 :CONNECTED LOAD/PHASE (KVA)

41 42

39 40

37 0.50 -- -- -- 38

35 -- -- -- 2.10 0.50 -- -- -- 36

33 -- -- -- 2.10 0.50 15 A 3 EXISTING - 1 QUAD + 1 DUPLEX RM. 11 34

31 EXISTING - COND. PUMP RM 11 3 30 A 2.10 0.00 -- -- -- 32

29 -- -- -- 15.00 0.00 -- -- -- 30

27 -- -- -- 15.00 0.00 15 A 3 SPARE 28

25 EXISTING - PANEL K 3 200 A 15.00 0.00 -- -- -- 26

23 -- -- -- 0.00 0.00 -- -- -- 24

21 -- -- -- 0.00 0.00 150 A 3 EXISTING - KITC. BOOSTER HEATER-NOT... 22

19 SPARE 3 225 A 0.00 5.79 -- -- -- 20

17 -- -- -- 0.00 5.79 -- -- -- 18

15 -- -- -- 0.00 5.79 100 A 3 AHU-6 (SF-6) (See Note 1) 16

13 SPARE 3 50 A 0.00 0.00 -- -- -- 14

11 -- -- -- 0.00 0.00 50 A 2 SPARE 12

9 -- -- -- 0.00 0.00 -- -- -- 10

7 SPARE 3 50 A 0.00 0.00 50 A 2 SPARE 8

5 -- -- -- 1.32 26.66 -- -- -- 6

3 -- -- -- 1.32 26.66 -- -- -- 4

1 AHU-6 (RF-6) (See Note 1) 3 20 A 1.32 26.66 350 A 3 EXISTING - UPS NEW COMP RM 2

NO DESCRIPTION P TRIP A B C TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING EXISTING MOUNTING: SURFACE

BUS RATING: 600 A MCB RATING: 600 A FED FROM:

RATINGS: 208/120V, 3PH, 4W MAINS TYPE: MCB LOCATION:

EXISTING PANEL PP-4

158.9 :TOTAL DEMAND LOAD (A)

57.3 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

158.9 :TOTAL CONNECTED LOAD (A)

1. PROVIDE NEW CIRCUIT BREAKER. 57.3 :TOTAL CONNECTED LOAD (KVA)

NOTES: 159.0 159.0 159.0 :CONNECTED LOAD/PHASE (A)

19.1 19.1 19.1 :CONNECTED LOAD/PHASE (KVA)

41 42

39 40

37 38

35 36

33 34

31 32

29 -- -- -- 1.90 30

27 -- -- -- 1.90 28

25 EXISTING - HEAT PUMP 3 20 A 1.90 26

23 -- -- -- 0.00 1.90 -- -- -- 24

21 -- -- -- 0.00 1.90 -- -- -- 22

19 SPARE 3 30 A 0.00 1.90 20 A 3 EXISTING - HEAT TRACE 20

17 -- -- -- 5.69 2.90 -- -- -- 18

15 -- -- -- 5.69 2.90 -- -- -- 16

13 RTU-L (See Note 1) 3 60 A 5.69 2.90 30 A 3 EXISTING KITCHEN PUMP 14

11 -- -- -- 4.80 0.00 -- -- -- 12

9 -- -- -- 4.80 0.00 -- -- -- 10

7 EXISTING - KITCHEN FAN 3 50 A 4.80 0.00 50 A 3 SPARE 8

5 -- -- -- 1.90 0.00 -- -- -- 6

3 -- -- -- 1.90 0.00 -- -- -- 4

1 EXISTING - HEAT PUMP 3 20 A 1.90 0.00 200 A 3 SPARE 2

NO DESCRIPTION P TRIP A B C TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING EXISTING MOUNTING: SURFACE

BUS RATING: 400 A MCB RATING: 400 A FED FROM:

RATINGS: 208/120V, 3PH, 4W MAINS TYPE: MCB LOCATION:

EXISTING PANEL PPAC

34.1 :TOTAL DEMAND LOAD (A)

28.4 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

TRIP SIZE AS INDICATED AND RECOMMENDED BY EQPM. MANUFACTURER. 34.1 :TOTAL CONNECTED LOAD (A)

1. PROVIDE NEW OR MODIFY EXISTING BUCKET WITH NEW FUSE/BREAKER 28.4 :TOTAL CONNECTED LOAD (KVA)

NOTES: 34.1 34.1 34.1 :CONNECTED LOAD/PHASE (A)

9.5 9.5 9.5 :CONNECTED LOAD/PHASE (KVA)

9 Space -- -- 0.0 --

8 SPARE 3 15 A 0.0 0.0 0.0

7 EXISTING - 1-SF7 3 3 A 0.3 0.3 0.3

6 EXISTING - 1-EF17 3 7 A 0.8 0.8 0.8

5 EXISTING - 1-EF8 3 3 A 0.3 0.3 0.3

4 EXISTING - 1-EF6 3 7 A 0.8 0.8 0.8

3 EXISTING - 1-EF5 3 3 A 0.4 0.4 0.4

2 AHU-1 (RF-1) 3 15 A 0.9 0.9 0.9 SEE NOTE 1

1 AHU-1 (SF-1) 3 50 A 5.8 5.8 5.8 SEE NOTE 1

CKT CIRCUIT DESCRIPTION POLES TRIP A B C REMARKS

BREAKER LOAD (KVA)

A.I.C. RATING EXISTING MOUNTING: Surface

BUS RATING: 600 A FED FROM:

RATINGS: 480/277V, 3PH, 4W MAINS TYPE: MLO LOCATION:

EXISTING SWITCHBOARD ME-MCC1

156.9 :TOTAL DEMAND LOAD (A)

130.4 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

TRIP SIZE AS INDICATED AND RECOMMENDED BY EQPM. MANUFACTURER. 156.9 :TOTAL CONNECTED LOAD (A)

1. PROVIDE NEW OR MODIFY EXISTING BUCKET WITH NEW FUSE/BREAKER 130.4 :TOTAL CONNECTED LOAD (KVA)

NOTES: 157.0 157.0 157.0 :CONNECTED LOAD/PHASE (A)

43.5 43.5 43.5 :CONNECTED LOAD/PHASE (KVA)

16 Space -- -- 0.0 --

15 SPARE 3 15 A 0.0 0.0 0.0

14 SPARE 3 15 A 0.0 0.0 0.0

13 EXISTING - 1-P6 3 15 A 2.1 2.1 2.1

12 EXISTING - 1-P5 3 15 A 3.1 3.1 3.1

11 Space -- -- 0.0 --

10 EXISTING - 1-EF13 3 3 A 0.3 0.3 0.3

9 AHU-5 (RF-5) 3 15 A 2.1 2.1 2.1 SEE NOTE 1

8 EXISTING - 1-RF2 3 15 A 2.1 2.1 2.1

7 AHU-5 (SF-5) 3 25 A 3.9 3.9 3.9 SEE NOTE 1

6 EXISTING - 1-SF4 3 50 A 7.5 7.5 7.5

5 EXISTING - 1-SF2 3 100 A 14.4 14.4 14.4

4 EXISTING - 1-EF11 3 3 A 0.6 0.6 0.6

3 EXISTING - 1-EF9 3 3 A 0.3 0.3 0.3

2 EXISTING - 1-EF3 3 7 A 1.3 1.3 1.3

1 EXISTING - 1-EF1 3 30 A 5.8 5.8 5.8

CKT CIRCUIT DESCRIPTION POLES TRIP A B C REMARKS

BREAKER LOAD (KVA)

A.I.C. RATING EXISTING MOUNTING: Surface

BUS RATING: 600 A FED FROM:

RATINGS: 480/277V, 3PH, 4W MAINS TYPE: MLO LOCATION:

EXISTING SWITCHBOARD ME-MCC2

215.7 :TOTAL DEMAND LOAD (A)

77.7 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

215.7 :TOTAL CONNECTED LOAD (A)

PROVIDE NEW CIRCUIT BREAKERS. 77.7 :TOTAL CONNECTED LOAD (KVA)

NOTES: 232.5 207.5 207.5 :CONNECTED LOAD/PHASE (A)

27.9 24.9 24.9 :CONNECTED LOAD/PHASE (KVA)

53 -- -- -- 11.04 0.00 -- -- Space 54

51 -- -- -- 11.04 0.00 -- -- Space 52

49 AHU-3 (SP-3) (See Note 1) 3 125 A 11.04 0.00 -- -- Space 50

47 -- -- -- 0.00 3.86 -- -- -- 48

45 -- -- -- 0.00 3.86 -- -- -- 46

43 SPARE 3 100 A 0.00 3.86 60 A 3 AHU-3 (RF-3) (See Note 1) 44

41 -- -- -- 0.00 1.00 -- -- -- 42

39 -- -- -- 0.00 1.00 -- -- -- 40

37 SPARE 3 50 A 0.00 1.00 40 A 3 EXISTING - AIR COMPRESSOR 38

35 -- -- -- 1.00 1.00 -- -- -- 36

33 -- -- -- 1.00 1.00 -- -- -- 34

31 EXISTING - AIR COMPRESSOR 3 30 A 1.00 1.00 20 A 3 EXISTING - EF-11 32

29 -- -- -- 1.00 1.00 -- -- -- 30

27 -- -- -- 1.00 1.00 -- -- -- 28

25 EXISTING - 1-EF10 3 15 A 1.00 1.00 20 A 3 EXISTING - EF-13 26

23 Space -- -- 0.00 0.00 -- -- Space 24

21 Space -- -- 0.00 0.00 -- -- Space 22

19 EXISTING - HUMIDIFIER SF2 & SF3 1 20 A 1.00 1.00 20 A 1 EXISTING - HUMIDIFIER SF4 & SF5 20

17 EXISTING - 1-EF21 1 20 A 1.00 0.00 20 A 1 SPARE 18

15 EXISTING - 1-EF15 1 20 A 1.00 0.00 20 A 1 SPARE 16

13 EXISTING - 1-EF14 1 20 A 1.00 1.00 20 A 1 EXISTING - AIR DRYER 14

11 EXISTING - 1-EF12 1 20 A 1.00 1.00 20 A 1 EXISTING - STEAM TRAP PANEL 12

9 EXISTING - 1-UH2 & 1-UH4 1 20 A 1.00 1.00 20 A 1 EXISTING - RECPT - PENTHOUSE 10

7 EXISTING - 1-UH1 & 1-UH3 1 20 A 1.00 1.00 20 A 1 EXISTING - RECPT - PENTHOUSE 8

5 EXISTING - LTG - PENTHOUSE 1 20 A 1.00 1.00 20 A 1 EXISTING - DIRECT DIGITAL CONTROL 6

3 EXISTING - LTG - PENTHOUSE 1 20 A 1.00 1.00 20 A 1 EXISTING - RECPT - PENTHOUSE 4

1 EXISTING - LTG - PENTHOUSE 1 20 A 1.00 1.00 20 A 1 EXISTING - LTG - PENTHOUSE 2

NO DESCRIPTION P TRIP A B C TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING EXISTING MOUNTING: SURFACE

BUS RATING: 225 A FED FROM:

RATINGS: 208/120V, 3PH, 4W MAINS TYPE: MLO LOCATION:

EXISTING PANEL ESP-3H

BethKassahun Stamp