36C24418B0585-0001001.pdf

PDF 690 KB Posted

Attached to
Correct Retro-Commissioning Discrepancies Phase 2 #503-15-205
Solicitation number
36C24418B0585
Issued by

About this file

36C24418B0585 0001 Drawing 01-E001.pdf

View the file

Other files

File Type Posted
36C24419C0030-000.docx DOCX document
36C24418B0585-0004001.pdf PDF
36C24418B0585-0004000.docx DOCX document
36C24418B0585-0003001.pdf PDF
36C24418B0585-0003000.docx DOCX document
36C24418B0585-0002002.pdf PDF
36C24418B0585-0002001.pdf PDF
36C24418B0585-0002000.docx DOCX document
36C24418B0585-0001005.pdf PDF
36C24418B0585-0001003.pdf PDF
36C24418B0585-0001004.pdf PDF
36C24418B0585-0001006.pdf PDF
36C24418B0585-0001002.pdf PDF
36C24418B0585-0001000.docx DOCX document
36C24418B0585-003.docx DOCX document
36C24418B0585-001.docx DOCX document
36C24418B0585-006.docx DOCX document
36C24418B0585-002.docx DOCX document
36C24418B0585-005.pdf PDF
36C24418B0585-004.pdf PDF
36C24418B0585-000.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THIS IS A STANDARD SYMBOL LIST. ALL SYMBOLS MAY NOT APPEAR ON THIS PROJECT.

RECEPTACLES, FURNITURE FEEDS

THE ABOVE MOUNTING ELEVATIONS ARE TO CENTER OF DEVICE AND SHALL BE

ADHERED TO UNLESS SPECIFICALLY NOTED OR DETAILED OTHERWISE ON THE

DRAWINGS AND/OR SPECIFICATIONS.

IN FLOOR JUNCTION BOXES FLUSH TO

FINISHED FLOOR (FF)

IN MASONRY CONSTRUCTION THE MOUNTING HEIGHTS SHALL BE USED FOR

REFERENCE TO THE NEAREST BLOCK OR BRICK COURSING.

COORDINATE THE INSTALLATION AND MOUNTING ELEVATIONS OF ALL EQUIPMENT,

DEVICES, CONTROLS AND APPURTENANCES WITH ARCHITECT AND ALL AFFECTED

TRADES PRIOR TO INSTALLATION. DOCUMENT ALL MOUNTING ELEVATIONS FOR ALL

EQUIPMENT, DEVICES,CONTROLS AND APPURTENANCES AT THE TIME OF SHOP

DRAWING SUBMITTAL.

3.

2.

1.

0'-0"

1'-5" A.F.F.

STANDARD MOUNTING HEIGHTS

RECESSED LIGHTING FIXTURES, CEILING

MOUNTED RECEPTACLES, INDICATING LIGHTS,

ETC.

CEILING

ELECTRICAL SYMBOLS LEGEND

CEILING/PENDANT MOUNTED LED EXIT SIGN WITH BATTERY BACKUP.

DUPLEX RECEPTACLE IN A 4" SQUARE BOX WITH PLASTER RING (IN DRYWALL)

SINGLE GANG BOX IN MASONRY.

XX: WP=WEATHERPROOF OUTLET INSIDE AN IN-USE TYPE ENCLOSURE,

SS=SURGE SUPPRESSOR, GFI= GROUND FAULT INTERRUPTER,

TR=TAMPER RESISTANT, S=SURFACE MTD

SINGLE RECEPTACLE IN A 4" SQUARE BOX WITH PLASTER RING (IN

DRYWALL) SINGLE GANG. BOX IN MASONRY.

WALL SWITCH, CONTROL: X=

3: 3 WAY

NON-FUSED DISCONNECT SWITCH

VARIABLE FREQUENCY DRIVE

SINGLE PHASE MOTOR CONNECTION

XX=HORSE POWER

ABOVE COUNTER DEVICES, GFI RECEPTACLES IN

RESTROOMS.

3'-6" A.F.F.

WALL SWITCHES, THERMOSTATS, CONTROL DEVICES,

TO CENTER OF BOX

4'-0" A.F.F.

TOP OF PANELBOARDS (<6'-0" TALL)

6'-0" A.F.F.

TOP MOST PORTION OF OPERATING HANDLE OF

DISCONNECT SWITCHES / CIRCUIT BREAKERS

6'-6" A.F.F.

WALL MOUNTED LIGHTS IN STAIRS, MECH ROOMS,

ETC.

7'-0" A.F.F.

DRAWING KEYNOTE - DEMOLITION

EQUIPMENT TAG

REVISION TRIANGLE WITH REVISION CLOUD

GROUND PER NATIONAL ELECTRIC CODE

JUNCTION BOX - WALL MOUNTED

JUNCTION BOX - CEILING OR EQUIPMENT MOUNTED

XX

X

XX

XX

J

J

FX

EX

SPECIAL RECEPTACLE IN A 4" SQUARE BOX

XX = NEMA CONFIGURATION AND AMP RATINGXX

VFD

INDICATED MOUNTED ABOVE COUNTERTOP (REFER TO STANDARD

MOUNTING HEIGHTS DETAIL ON THIS SHEET)

XX

DOUBLE GANG BACKBOX W/ SINGLE GANG DEVICE RING. 1 1/4" EMT

CONDUIT W/ PULL STRING TO ABOVE ACCESSIBLE CEILING

X

PUSHBUTTON:

E=EMERGENCY STOP, A=AUTO DOOR PUSH BUTTON

X - Y

RECEPTACLE TAG:

X= PANEL NAME

Y= CIRCUIT NUMBER

S

SURFACE MOUNTED ELECTRICAL PANELBOARD

RECESSED MOUNTED ELECTRICAL PANELBOARD

N E

W

E X

IS

T

IN

G

N E

W

E X

IS

T

IN

G

ADA INSTALLATION GUIDELINES

34"

46"

MAX.

(NOTE #2)

44"

MAX.

(FOR 20-25")

(NOTE #2)

10-24" 25" MAX.

48"

MAX.

(FOR 20")

(NOTE #2)

OBSTRUCTED HIGH

SIDE REACH

OBSTRUCTED HIGH

FORWARD REACH

48"

MAX.

(NOTE #2)

10"

MAX.

15"

MIN.

48"

MAX.

(NOTE #2)

15"

MIN.

OBSTRUCTED

SIDE REACH

OBSTRUCTED

FORWARD REACH

NOTES:

1. THESE GUIDELINES SHALL BE USED FOR THE INSTALLATION OF THE FOLLOWING

DEVICES:

- WALL SWITCHES

-CONTROL SWITCHES

-RECEPTACLES

-VISUAL DISPLAY TOUCH PANELS

2. NOTE THAT THIS HEIGHT IS TO THE TOP-MOST PART OF THE DEVICE THAT AN OCCUPANT

REQUIRES ACCESS TO.

LIGHTING & CONTROLS SYMBOLS

SURFACE/PENDANT MOUNTED LINEAR FULLY ENCLOSED FIXTURE

FX = FIXTURE TYPE

POWER SYMBOLS

DOUBLE DUPLEX RECEPTACLE IN A 4" SQUARE BOX

XX: WP=WEATHERPROOF OUTLET INSIDE AN IN-USE TYPE ENCLOSURE,

SS=SURGE SUPPRESSOR, GFI= GROUND FAULT INTERRUPTER,

TR=TAMPER RESISTANT, S=SURFACE MTD

FUSED DISCONNECT SWITCH (XX=SWITCH SIZE, YY=FUSE SIZE,

Z=# OF POLES)

THREE PHASE MOTOR CONNECTION

XX=HORSE POWER

WALL MOUNTED GROUND BUS BAR (COPPER)

ANNOTATION SYMBOLS

M

M

XX/YY/Z

STANCHION MOUNTED DEVICE

DRAWING KEYNOTE - PLAN / ELEVATION NEW WORK

1. THIS PROJECT WILL REQUIRE SHUT-DOWNS TO THE NORMAL POWER SYSTEM OF THE

HOSPITAL, WHICH WILL REQUIRE SECOND OR THIRD SHIFT WORK, AS WELL AS

WEEKEND WORK. THE CONTRACTOR SHALL COORDINATE THIS WORK WITH THE COR,

AND PLAN HIS WORK ACCORDINGLY.

2. DURING ALL UTILITY SHUT-DOWNS OF THE NORMAL POWER SYSTEM, THE

CONTRACTOR SHALL HAVE AN EMERGENCY GENERATOR ON SITE WITH 24 HOURS OF

FUEL. THE CONTRACTOR SHALL HAVE SUITABLE TEMPORARY CABLES NEEDED TO

PROVIDE EMERGENCY CONNECTIONS TO THE SWITCHGEAR IN THE EVENT THERE IS A

PROBLEM.

3. THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP)

DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE

PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO

STARTING THE PROJECT, FOR SIGN OFF.THE MOP MAY BE REVISED BASED ON

CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE

COR SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE

PRESENTED TO THE COR AND ENGINEER FOR SIGN OFF.

UTILITY SHUTDOWNS

STROBE UNIT SYNCHRONIZED - CEILING MOUNT

(XX-CD = CANDELA RATING): WP = WEATHERPROOF, WG = WIREGUARD

FIRE ALARM TERMINAL CABINET (NAC)FATC

FS

FS

FIRE SPEAKER/STROBE UNIT - CEILING MOUNTED

(XX-CD = CANDELA RATING): WP = WEATHERPROOF, WG = WIREGUARD

FIRE SPEAKER/STROBE UNIT - WALL MOUNTED

(XX-CD = CANDELA RATING): WP = WEATHERPROOF, WG = WIREGUARD

STROBE UNIT SYNCHRONIZED - WALL MOUNT

(XX-CD = CANDELA RATING): WP = WEATHERPROOF, WG = WIREGUARD

XX-CD

FIRE ALARM SYMBOLS

XX-CD

XX-CD

XX-CD

DD

SD

DUCT SMOKE DETECTOR (X = S - SUPPLY, R - RETURN)

SMOKE DETECTOR

MANUAL PULL STATIONF

FX

DENOTES FIXTURE IS CONNECTED

TO EMERGENCY POWER

WALL MOUNTED LED EXIT SIGN WITH BATTERY BACKUP. EX

M

S MOTOR RATED SWITCH

X

1. CONTRACTOR SHALL PROVIDE POWER CONNECTIONS FOR THE TEMPORARY AIR

HANDLING UNITS. VERIFY THE NORMAL OR EMERGENCY POWER NEEDS OF EACH AIR

HANDLING UNITS AND PROVIDE POWER FROM THE NEAREST AVAILABLE AND CAPABLE

SOURCE. CONTRACTOR SHALL INVESTIGATE AND ASSURE THE POWER SOURCES ARE

ABLE TO CARY THE LOADS. PROVIDE 30 DAY METER READING OF EACH POWER SOURCE.

TEMPORARY POWER

CONSULTANTS:

Drawing Title

Approved: Project Director

Project Title:

Location:

Date: Checked: Drawn:

Drawing Number

Building Number

Project Number

Office of Construction and Facilities Management

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

FULLY SPRINKLERED

A

B

C

D

E

F

6 " o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t

209 SANDUSKY STREET

PITTSBURGH, PA 15212

PH: 412.287.7333

www.ae-works.com

AE WORKS PROJECT NUMBER:

ARCHITECTS/ENGINEERS:SEAL

Revision# Date

6/ 8/

:1

9:

A M

CORRECT

RETRO-COMMISSIONING

DISCREPANCIES

503-15-205

BK BK

JAMES E. VAN ZANDT MEDICAL CENTER

ALTOONA, PA 16602

01-E001

ELECTRICAL SYMBOLS, ABBREVIATIONS AND

NOTES

06/07/2018

14-

100% CONSTRUCTION DOCUMENTS

SS SOIL STACK

ST PR STATIC PRESSURE

ST STL STAINLESS STEEL

STD STANDARD

STER STERILIZER

STL STEEL

STOR STORAGE

STR STRAINER

STRUCT STRUCTURAL

SUSP SUSPENDED

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL TOP

T TOP

TA THROWAWAY

TAN TANGENT

TC TELECOMMUNICATIONS

CONTRACTOR

TCV TEMPERATURE CONTROL VALVE

TDV TRIPLE DUTY VALVE

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TG TONGUE & GROOVE

TH THERMOMETER

THRES THRESHOLD

TR TEMPERATURE RISE

TRANS TRANSITION

TRANSR TRANSFORMER

TSTAT THERMOSTAT

TV TURNING VANES OR TELEVISION

TYP TYPICAL

UC UNDER CABINET OR UNDER CUT

UFD UNDER FLOOR DUCT

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORIES

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VAL VALVE

VD VOLUME DAMPER

VENT VENTILATION

VERT VERTICAL

VFS VENTURI FLOW STATION

VIF VERIFY IN FIELD

VL VENT LINE

VR VAPOR RETARDER

VS VENT STACK

VTR VENT THROUGH ROOF

W WATT

W/ WITH

W/O WITHOUT

WB WET BULB

WC WALL COVERING

WCL WATER CLOSET

WD WOOD

WF WIDE FLANGE

WFMD WATER FLOW MEASURING DEVICE

WG WALL GUARD OR WATER GAUGE

WHCH WHEEL CHAIR

WIN WINDOW

WMS WIRE MESH SCREEN

WP WEATHERPROOF

WPS WALL PROTECTION SYSTEM

WSCT WAINSCOT

WT WINDOW TREATMENT

WTD WATER TEMPERATURE DROP

WWF WELDED WIRE FABRIC

X DEMO

XN TO BE RELOCATED / NEW LOCATION

XR EXISTING TO REMAIN

ZVB ZONE VALVE BOX

ZVC ZONE VALVE CABINET

LDB LEAVING DRY BULB

LED LIGHT EMITTING DIODE

LF LINEAR FEET

LIN LINEAR

LOC LOCATION OR LOCATE

LPT LOW POINT

LSDC LINEAR SUPPLY DIFFUSER CEILING

LT LIGHT

LTG LIGHTING

LV LOW VOLTAGE

LVR LOUVER

LWB LEAVING WET BULB

LWC LINEAR WOOD CEILING

LWT LEAVING WATER TEMPERATURE

MAN MANUAL

MAT MIXED AIR TEMPERATURE

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH ONE THOUSAND BTU / HOUR

MC MECHANICAL CONTRACTOR

MC METAL CLAD CABLE

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MO MASONRY OPENING

MOD MOTOR OPERATED DAMPER

MONO MONOLITHIC

MTD MOUNTED

MTG HT MOUNTING HEIGHT

MTL METAL

MTLH METAL HALIDE

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

N/A NOT APPLICABLE

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NUMBER OR NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

OPER OPERATED

OPNG OPENING

OPP OPPOSITE

ORD OVERFLOW ROOF DRAIN

PB PULL BOX

PC PLUMBING CONTRACTOR

PD PUMP DISCHARGE

PG PRESSURE GAUGE WITH COCK

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRD PRESSURE DIFFERENTIAL VALVE

PRELIM PRELIMINARY

PRT PRESSURE TAP

PRV PRESSURE REDUCING VALVE

PT PAINT OR POTENTIAL

TRANSFORMER

RO ROUGH OPENING

QT QUARRY TILE

R RADIUS

RA RETURN AIR / RELIEF AIR

RB RUBBER BASE

RC REMOVE COMPLETELY

RD ROOF DRAIN

RE RELOCATE EXISTING

REC RECESSED

RECPT RECEPTACLE

REF REFERENCE

REFL REFLECTOR

REG REGISTER

REINF REINFORCING

REM REMOVE

REQD REQUIRED

RET RETURN

REV REVISE

REX REMOVE EXISTING

RF RESILIENT FLOOR

RFI REQUEST FOR INFORMATION

RGS RIGID GALVANIZED STEEL CONDUIT

RH ROOF HATCH

RM ROOM

RN REMOVE AND REPLACE WITH NEW

RR REMOVE AND REPLACE

RS RAPID START

RV RELIEF VALVE

RWC RAIN WATER CONDUCTOR

SA SUPPLY AIR

SAN SANITARY SEWER ABOVE GROUND

SAN-BXR SANITARY SEWER - BURIED

EXISTING TO REMAIN

SAN-XR SANITARY SEWER ABOVE GROUND -

EXISTING TO REMAIN

SCHED SCHEDULE

SD SMOKE DAMPER OR SMOKE

DETECTOR

SDISP SOAP DISPENSER

SF SQUARE FOOT

SHT SHEET

SHT MTL SHEET METAL

SHTG SHEATHING

SIM SIMILAR

SM SURFACE MOUNTED

SNC SANITARY NAPKIN CABINET

SND SANITARY NAPKIN DISPOSER

SP STANDPIPE OR STATIC PRESSURE

SPC SPECIMEN PASS-THRU CABINET

SPEC SPECIFICATIONS

SPS STATIC PRESSURE SENSOR

SR SERVICE RECEPTOR

EIFS EXTERIOR INSULATION AND

FINISHING SYSTEM

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEC CAB ELECTRICAL CABINET

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

ENTR ENTRANCE

EO ELECTRICAL OUTLET

EQ EQUAL

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWB ENTERING WET BULB

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXAUST AIR

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

XP EXPLOSION PROOF

F/S FIRE / SMOKE DAMPER

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAT FINAL AIR TEMPERATURE

FB FIRE BLANKET

FC FLEXIBLE CONNECTION OR

FOOTCANDLE

FD FLOOR DRAIN OR FIRE DAMPER

FDN FOUNDATION

FDV FIRE DEPARTMENT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FH FIRE HOSE

FHC FIRE HOSE CABINET

FHP FULL HEIGHT PARTITION

FHV FIRE HOSE VALVE

FIN FINISH

FIXT FIXTURE

FL FLOW LINE

FLA FULL LOAD AMPERES

FLASH FLASHING

FLEX FLEXIBLE

FLG FLANGE

FLG C FLANGE CONNECTION

FLR FLOOR

FLUOR FLUORESCENT

FP FIRE PROOFING

FRMG FRAMING

FS FLOOR SINK

FSTOP FIRESTOPPING

FT FOOT / FEET

FT HD FEET OF HEAD

FTC FOOTCANDLES

FTG FOOTING

FUR FURRING

G GAS OR ELECTRICAL GROUND

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GEN GENERATOR

GENL GENERAL

GFCI GROUND FAULT CIRCUIT

INTERRUPTOR

GL GLASS

GLV GLOBE VALVE

GND GROUND

GPM GALLONS PER MINUTE

GR GRADE

GRAV GRAVITY

GRD BM GRADE BEAM

GV GATE VALVE

GWB GYPSUM BOARD

H HIGH

HB HOSE BIB

HC HEATING CONTRACTOR

HDCP HANDICAP

HDR HEADER

HDW HARDWARE

HID HIGH INTENSITY DISCHARGE

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HORSE POWER

HPD HIGH PRESSURE DRIP

HPF HIGH POWER FACTOR

HR HANDRAIL

HSKP HOUSEKEEPING

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VELOCITY

HVAC HEATING, VENTILATING, AIR

CONDITIONING

HW HOT WATER

HWD HARD WOOD

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HWS&R HOT WATER SUPPLY AND RETURN

HZ HERTZ

ID INSIDE DIAMETER

IER INVERTED ECCENTRIC REDUCER

IG ISOLATED GROUND

IME INSULATED METAL ENCLOSURE

IN INCH

INCAND INCANDESCENT

INCL INCLUDED

INSUL INSULATION

INT INTERIOR

INTERL INTERLOCK

INV INVERT

ISO ISOLATION

IVS ISOLATED VALVE STATION

J-BOX JUNCTION BOX

JST JOIST

JT JOINT

KO KNOCK OUT

kVA KILOVOLT AMPERE kVAR KILOVAR (REACTANCE) kW KILOWATT kWH KILOWATT HOUR METER

LAT LEAVING AIR TEMPERATURE

LAV LAVATORY

LB POUND

& AND

A AIR (CLINICAL)

AAP ALARM ANNUNCIATOR PANEL

AAV AUTOMATIC AIR VENT

AB ANCHOR BOLT

ABV ABOVE

ACC DR ACCESS DOOR

ACFL ACCESS

ACOUS ACOUSTICAL

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICAN DISABILITIES ACT

ADD ADDENDUM

ADDL ADDITIONAL

ADJ ADJUSTABLE

ADMIN ADMINISTRATION

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISHED GRADE

AFMD AIR FLOW MEASURING DEVICE

AHU AIR HANDLING UNIT

AL ALIGN

ALT ALTERNATE

ALUM ALUMINUM

AMP AMPERE

AP ACCESS PANEL

APC ARCHITECTURAL PRECAST

CONCRETE

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASY ASYMMETRIC

ATC AUTOMATIC TEMPERATURE

CONTROL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AWT AVERAGE WATER TEMPERATURE

BAT BATTERY

BC BALANCING COCK OR BARE

COPPER

BDD BACKDRAFT DAMPER

BFC BELOW FINISH CEILING

BFE BOTTOM FOOTING ELEVATION

BFG BELOW FINISHED GRADE

BG BUMPER GUARD

BLDG BUILDING

BLKG BLOCKING

BLT BORROWED LIGHT

BLW BELOW

BM BEAM

BO BY OWNER

BOF BY OWNER FUTURE

BOT BOTTOM

BR BRICK

BRG BEARING

BRKR BREAKER

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT UP ROOFING

C CONDUIT

CAB CABINET

CANTL CANTILEVER

CAP CAPACITY

CATV CABLE TELEVISION

CCT CUBICLE CURTAIN TRACK

CCTV CLOSED CIRCUIT TELEVISION

CFH CUBIC FEET / HOUR

CFM CUBIC FEET / MINUTE

CH CHANNEL

CHK V CHECK VALVE

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CHWS&R CHILLED WATER SUPPLY AND

RETURN

CJ CONTROL JOINT

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CL CENTERLINE

CLG CEILING

CLG MTD CEILING MOUNTED

CLR CLR

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUE / CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

COORD COORDINATE

CORR CORRIDOR

CPT CARPET OR CONTROL POWER

TRANSFORMER

CT CERAMIC TILE

CTR CENTER

CU COPPER

CV CONTROL VALVE

CW COLD WATER

D DEPTH OR DEEP

DB DRY BULB

dB DECIBEL

DCW DOMESTIC COLD WATER

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAILS

DF DRINKING FOUNTAIN

DHW DOMESTIC HOT WATER

DIA DIAMETER

DIAG DIAGONAL OR DIAGRAM

DIFF DIFFUSER

DIM DIMENSION

DISC DISCONNECT

DISCH DISCHARGE

DISP DISPENSER

DIST DISTRIBUTION

DIV DIVISION

DL DOWN LIGHT

DN DOWN

DP DISTRIBUTION PANEL

DPR DAMPER

DR DRAIN

DS DOWNSPOUT

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EDB ENTERING DRY BULB

EF EXHAUST FAN

ABBREVIATION LEGEND

ELECTREICAL DRAWING INDEX

Sheet

Number Sheet Name

01-E001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES

01-ED101 ELECTRICAL DEMOLITION PLAN

01-E101 ELECTRICAL NEW WORK PLAN

01-E701 ELECTRICAL SCHEDULES AND DETAILS

ELECTRICAL GENERAL NOTES

1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL E SERIES CONTRACT DRAWINGS.

2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR" THE CONTRACTOR IS RESPONSIBLE FOR THAT WORK.

3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK. BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND

RELATED SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.

4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.

5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS TO THE SATISFACTION OF ALL CONCERNED TRADES.

6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.

7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM OF 3/4" UNLESS OTHERWISE NOTED.

8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS

AND/OR CABLE TERMINATIONS.

9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION BOXES IS UNIMPEDED.

10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.

INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH MANUFACTURER'S

DETAILED INSTALLATION PROCEDURES.

11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE NEMA 4X STAINLESS STEEL AND RATED FOR THAT APPLICATION.

12 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL WITHOUT THE USE OF SPECIALIZED TOOLS.

13 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION, (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED

CONTRACTORS.

14 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED), AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE

AUTHORITY HAVING JURISDICTION.

15 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.

16 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

17 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.

18 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF

THE PROJECT, PRIOR TO INSTALLATION.

19 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED.

COORDINATE THIS WORK WITH THE OWNERS REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR SHALL

PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.

20 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR INSTALLATIONS.

21 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO PERFORMING ANY WORK.

22 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND

MECHANICAL/ELECTRICAL ROOMS.

23 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL GROUNDING AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE

DOCUMENTS.

24 THE CONTRACTOR SHALL PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS. AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC

VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE OWNER.

25 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL

UTILITY COMPANIES.

26 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT WORK, IF ANY, HAS TO BE

COMPLETED DURING SECOND OR THIRD SHIFT.

27 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION. THE CONTRACTOR SHALL COORDINATE THESE REQUIREMENTS WITH THE

OWNER.

28 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING QUANTITIES OF MATERIALS REQUIRED TO COMPLETE THE PROJECT.

29 THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY

DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.

30 THE CONTRACTOR SHALL PROVIDE ALL NEW OPENINGS IN EXISTING PARTITIONS, EXTERIOR WALLS, FLOORS, AND ROOFS FOR THE INSTALLATION OF ANY NEW ELECTRICAL WORK. FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES FOR THIS NEW WORK. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES INSTALLED THROUGH EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.

31 THE CONTRACTOR SHALL PROTECT ALL EXISTING MATERIALS THAT ARE TO REMAIN IN PLACE FROM DAMAGE. ANY DAMAGE TO EXISTING FINISHES, MATERIALS, ETC., SHALL BE REPLACED BY THE CONTRACTOR TO MATCH

THE ADJACENT FINISH.

32 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK. DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE

ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.

33 THE CONTRACTOR SHALL PROVIDE ALL TRAFFIC CONTROL, FLAGMEN, SIGNAGE, ETC. WHEN DOING WORK THAT INTERFERES WITH PUBLIC RIGHT-OF-WAY.

34 THE CONTRACTOR SHALL HAVE ALL UTILITIES VERIFIED IN AND AROUND ANY EXCAVATION AREA PRIOR TO PERFORMING ANY UNDERGROUND INSTALLATION WORK.

35 THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER PRIOR TO STARTING THE PROJECT, FOR SIGN OFF. THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.

36 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS.

37 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE EXISTING AND NEW DISTRIBUTION SYSTEM REQUIRED TO ACCURATLY SIZE AND RATE THE NEW EQUIPMENT ADDED AS PART OF THIS PROJECT.

38 THESE DRAWINGS DO NOT INDICATED ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES AND EXISTING CONDITIONS.

39 PROVIDE ALL JUNCTION BOXES AND OTHER PULL POINTSAS REQUIRED FOR EASE OF PULLING AND A CODE COMPLIANT INSTALLATION. ALL JUNCTION BOXES AND OTHER PULL POINTS SHALL BE ACCESSABLE

40 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED, ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. SHARING OF NEUTRALS IS PROHIBITED. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL GROUND

WIRE. USE OF THE CONDUIT SYSTEM FOR THE GROUND PATH IS PROHIBITED.

41 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE WIRES, INCLUDING THE GROUND, AND CONDUIT AS REQUIRED PER NEC.

42 THE COMPLETE BRANCH WIRING SYSTEM IS NOT SHOWN ON THE DRAWINGS. AN ABBREVIATED FORMAT IS USED TO INDICATE WHICH FIXTURES/DEVICES ARE CONNECTED TO A COMMON CIRCUIT OR SWITCH. THIS IS PROVIDED AS A GUIDE TO THE CONTRACTOR TO ILLUSTRATE CIRCUITS AND CONTROL INTENT. ACTUAL WIRING MAY BE DIFFER DUE TO FIELD CONDITIONS.

43 COLOR CODING OF WIRES SHALL BE AS PER NEC.

44 CONTRACTOR SHALL MAKE AN ALLOWANCE FOR AND PROVIDE ADDITIONAL EXIT SIGNAGE AS PER THE AHJ'S REQUIREMENTS AND REQUESTS.

45 PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE IS TO BE CONNECTED TO NEAREST 120/208V PANEL AND PROVIDED WITH THE APPROPRIATE CIRCUIT BREAKER AS NEEDED.

46 PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS ARE TO BE PROVIDED FROM EMERGENCY (LIFE SAFETY) BRANCH PANEL. MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME CIRCUIT (I.E., DEDICATED CIRCUIT IS NOT REQUIRED).

47 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING, AND SPECIALTY TRADES).

ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTOR’S WORK. THIS WORK SHALL BE

INSTALLED AS PER NEC REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER.

BethKassahun Stamp