3-Set Chester Courthouse 25.08.18 issued for rebid combine pdf.pdf
PDF 3 MB Posted
- Solicitation number
- Not on record
- Issued by
- Delaware County, Pennsylvania
About this file
The document is a comprehensive rehabilitation project set of construction documents for the 1724 Chester Courthouse located at 412 Avenue of the States in Chester, Pennsylvania, involving multiple stakeholders including the Pennsylvania Historical and Museum Commission, Delaware County, and various design and engineering firms such as J&M Preservation Studio and IMEG Consultants. The project involves a historic preservation rehabilitation of the 1724 Chester Courthouse, which is listed on the National Register of Historic Places, with a total building area of 2,520 square feet across two floors and an attic. The project includes exterior building envelope repairs, interior building repairs, plumbing system updates, electrical system upgrades, and the installation of a lightning protection system, with work funded by the Historic Preservation Fund administered by the National Park Service, Department of the Interior.
The project documents include multiple bid alternates with optional scope items, such as removing non-historic partition walls, replacing storm windows, installing a kitchenette, and painting various interior surfaces. The rehabilitation is subject to the Secretary of the Interior's Standards for the Treatment of Historic Properties, with a construction timeline spanning from August 2024 to August 2025. The estimated project budget and specific funding allocations are not explicitly stated, but the project will require careful preservation techniques to maintain the building's historical integrity. The construction will involve localized stone wall repairs, wood trim restoration, window repairs, plaster work, electrical system upgrades including fire alarm and lighting improvements, and the installation of a comprehensive lightning protection system, all while maintaining the building's historical significance and architectural character.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4TH STREET (39 F.T. R.O.W.)
DEPARTMENT
BUILDING
FORMER
POLICE
A
LL
EY
COMMUNITY PARK
CHESTER
COURTHOUSE
"CITY HALL
COURTYARD"
(PER JUNE
2003 DEED BY
CATANIA
ENGINEERING)
SAN
4TH STREET (39 F.T. R.O.W.)
#406-408 AVENUE OF THE STATES
DEPARTMENT
BUILDING
FORMER
POLICE
A
LL
EY
COMMUNITY PARK
C O U R
TY
A R D
CHESTER
COURTHOUSE
"CITY HALL
COURTYARD"
(PER JUNE
2003 DEED BY
CATANIA
ENGINEERING)
SAN
A-1.1
A A-1.1
SYMBOLS ABBREVIATIONS
1. THE CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH THE OWNER'S.
OPERATION REQUIREMENTS AND THE PROJECT PROGRESS SCHEDULE.
2. CONTRACTORS ARE SOLELY RESPONSIBLE FOR THE HEALTH AND SAFETY OF ITS WORKERS
DURING THE EXECUTION OF THIS CONTRACT. CONTRACTOR SHALL COMPLY WITH THE MOST
CURRENT CONSTRUCTION SAFETY REGULATIONS OF OSHA AND REQUIREMENTS OF THE
GENERAL CONDITIONS TO THE CONSTRUCTION CONTRACT.
3. CONTRACTOR RESPONSIBLE FOR PROTECTING ALL ADJACENT NON-WORK AREAS FROM DAMAGE.
PROTECTION METHODS AT THE CONTRACTORS DISCRETION. ALL EXISTING CONSTRUCTION,
EQUIPMENT, FINISHES, ETC. TO REMAIN THAT ARE DAMAGED, DISTURBED OR REMOVED IN THE COURSE OF THE WORK SHALL BE REPAIRED OR RESTORED TO THEIR PRE-EXISTING CONDITION AT
NO ADDITIONAL EXPENSE TO THE OWNER. REPAIRS TO ANY DAMAGED ITEMS MUST BE MADE
IN-KIND PER THE GENERAL CONDITIONS TO THE CONSTRUCTION CONTRACT.
4. THE CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING CONDITIONS IN THE FIELD PRIOR TO
COMMENCING WORK AND SHALL NOTIFY THE PROFESSIONAL OF ANY CONFLICTS AND
DISCREPANCIES IN THE PLANS AND SPECIFICATIONS RELATIVE TO SAID CONDITIONS.
5. UPON REMOVAL OF MATERIALS DURING ALL WORK, CONTRACTOR SHALL NOTIFY THE
PROFESSIONAL FOR INSPECTION OF EXPOSED CONDITIONS FOR REVIEW OF EXISTING ELEMENTS
THAT WERE CONCEALED DURING THE PROFESSIONAL'S DESIGN PHASE.
6. ALL CONSTRUCTION SHALL BE PERFORMED IN A GOOD, WORKMANLIKE MANNER FOLLOWING
ACCEPTED CONSTRUCTION PRACTICES AND TOLERANCES. DEFECTIVE OR DAMAGED MATERIALS
SHALL NOT BE USED AND SHALL BE REPLACED.
7. CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERS ON-SITE AND WITHIN CLOSE PROXIMITY TO
ANY WORK REQUIRING TORCHES OR SOLDERING EQUIPMENT.
8. CONTRACTOR RESPONSIBLE FOR MAINTAINING A CLEAN AND ORDERLY JOB SITE AT ALL TIMES.
9. MEANS AND METHODS FOR SCAFFOLDING AND OVERHEAD PROTECTION SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR. STAGING AND CONSTRUCTION SEQUENCING PLAN SHALL
BE PROVIDED BY THE CONTRACTOR PRIOR TO COMMENCING WORK.
10. ANY DAMAGE CAUSED TO GROUNDS, TURF, LANDSCAPE FEATURES, AND ROADWAYS SHALL BE
REPAIRED BY THE CONTRACTOR AT NO EXTRA COST TO THE OWNER PER THE GENERAL
CONDITIONS TO THE CONSTRUCTION CONTRACT.
11. OWNER SHALL PROVIDE CONTRACTOR WITH POWER TO FACILITATE CONSTRUCTION ACTIVITIES.
OWNER MAKES NO GUARANTEES THAT POWER AND ELECTRIC SUPPLIED WILL MEET ALL
CONSTRUCTION ACTIVITY NEEDS.WATER SERVICE SHALL NOT BE TURNED ON UNTIL
MECHANICAL SYSTEM IS FULLY FUNCTIONAL (BY OTHERS).
12. CONTRACTOR SHALL PROVIDE RESTROOM FACILITIES ON-SITE FOR CONSTRUCTION PERSONNEL
INCLUDING POTABLE WATER.
13. MASONRY POINTING WORK SHALL NOT BE CONDUCTED IN TEMPERATURES LESS THAN
40-DEGREES FAHRENHEIT AND RISING OVER A 24-HOUR PERIOD.
14. THE ORGANIZATION OF THE KEYNOTES ON THE DRAWINGS SHALL NOT CONTROL THE
CONTRACTOR IN ORGANIZING THE DIVISION OF WORK AMONG THEIR SUBCONTRACTORS.
15. CONTRACTOR SHALL PROVIDE FINAL CLEANING OF INTERIOR AND EXTERIOR OF JOB SITE SO
BUILDING CAN OPEN FOR OPERATION. CLEANING INCLUDES BROOM SWEEPING, VACUUMING
AND WIPING DOWN ALL SURFACES OF DIRT AND DUST. WINDOWS SHALL BE CLEANED.
KITCHENETTE AND RESTROOMS SHALL BE CLEANED IF WORK IS COMPLETED.
16. THE 1724 CHESTER COURTHOUSE IS ON THE NATIONAL REGISTER FOR ITS ARCHITECTURAL AND HISTORIC SIGNIFICANCE. IT IS CONSIDERED TO HAVE IRREPLACEABLE CULTURAL, MATERIAL, AND AESTHETIC VALUE. THE WORK IS FUNDED BY THE HISTORIC PRESERVATION FUND, ADMINISTERED BY THE NATIONAL PARK SERVICE, DEPARTMENT OF THE INTERIOR. THE FUNDING OF WHICH IS SUBJECT TO HAVING ALL WORK ITEMS MEET THE SECRETARY OF THE INTERIOR'S
STANDARDS FOR THE TREATMENT OF HISTORIC PROPERTIES.
SITE PLAN NOTES:
1. SITE PLAN TAKEN FROM DEED DESCRIPTIONS ONLY. NO ATTEMPT HAS BEEN MADE TO VERIFY CLOSURE. NO PHYSICAL SURVEY WAS PERFORMED. LOCATION OF #406-408 AVENUE OF THE STATES BUILDING TO THE SOUTH IS FOR REFERENCE ONLY AND IS APPROXIMATE BASED UPON PREVIOUS
RECORDS.
1.1. TAX MAP: 49-16-158:000
FOLIO NUMBER: 49-03-00680-00
DEED JANUARY 20,1977
DEED BOOK 2597
D DOWNSPOUT
EX'G EXISTING
ga. GAUGE
HDG HOT-DIPPED GALVANIZED
HHB HEX HEAD BOLT
L/C LIMIT-OF-CONTRACT
LF LINEAR FOOT
L.P LOW POINT
MPH MILES PER HOUR
NEC. NECESSARY
NHL NATURALLY HYDRAULIC LIME
NIC NOT INCLUDED IN CONTRACT
NTS NOT TO SCALE
PSF POUNDS PER SQUARE FOOT
PT PRESSURE TREATED
REQ REQUIRED
S STACK
SF SQUARE FOOT
SST STAINLESS STEEL
TYP TYPICAL
VIF VERIFY IN FIELD
GENERAL NOTES
412 AVENUE OF THE STATES
CHESTER, PA 19013
1724 CHESTER COURTHOUSE
A4
1 PHOTO
DETAIL ID
DOOR ID
WINDOW ID
REVISION ID
SECTION
ELEVATION
KEYNOTE
COL/BEAM GRID\
JOIST/RAFTER DIRECTION
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
AGS J&M
LIST OF DRAWINGS:
CS COVER PAGE
G1.0 GENERAL: KEY PLAN, PHOTOS, AND CODE REVIEW
A1.1 FIRST FLOOR PLAN
A1.2 SECOND FLOOR PLAN
A1.3 ATTIC FLOOR AND ROOF PLAN
A1.4 ROOF FRAMING DIAGRAM AND CUPOLA DETAILS
A2.1 ELEVATIONS: NORTH AND EAST
A2.2 ELEVATIONS: SOUTH AND WEST
A3.1 KITCHENETTE DETAILS
A4.1 WINDOW DETAILS
A5.1 TYPICAL WALL DETAILS
A6.1 SCHEDULES
P000 PLUMBING COVER SHEET
P211 FLOOR PLAN - LEVEL 01 - PLUMBING
P213 FLOOR PLAN - LEVEL 03 - PLUMBING
P600 PLUMBING SCHEDULES
M000 HVAC COVER SHEET
M212 FLOOR PLAN-LEVEL 02- HVAC
M213 FLOOR PLAN-ATTIC-HVAC
M600 MECHANICAL SCHEDULES
E000 ELECTRICAL COVER SHEET
E101 ELECTRICAL DEMOLITION PLAN- LEVEL 01
E102 ELECTRICAL DEMOLITION PLAN- LEVEL 02
E103 ELECTRICAL DEMOLITION PLAN- ATTIC
E201 ELECTRICAL FLOOR PLAN - LEVEL 01- LIGHTING
E202 ELECTRICAL FLOOR PLAN - LEVEL 02- LIGHTING
E211 ELECTRICAL FLOOR PLAN - LEVEL 01 - POWER AND SYSTEMS
E212 ELECTRICAL FLOOR PLAN - LEVEL 02 - POWER AND SYSTEMS
E213 ELECTRICAL FLOOR PLAN - ATTIC - POWER AND SYSTEMS
E600 ELECTRICAL SCHEDULES
COVER PAGE
SCOPE OF WORK:
EXTERIOR BUILDING ENVELOPE REPAIRS:
1. LOCALIZED STONE WALL REPAIRS INVOLVING, STONE PATCHING AND
REPOINTING WITH MORTAR SPECIFIED BY MORTAR ANALYSIS.
2. MINOR REPAIRS TO THE EXTERIOR WOOD TRIM, FASCIAS, SOFFITS, EAVES,
AND THE CUPOLA.
3. REPAIRS TO THE SECOND FLOOR WINDOWS PER THE PROPOSED
SCHEDULE ON PAGE A6.1. EXTERIOR PAINTING ONLY. PAINT PROVIDED BY
OWNER.
INTERIOR BUILDING REPAIRS:
1. REPAIRS AND INTERIOR PAINTING IN SELECT LOCATIONS. PAINT TO BE
PROVIDED BY OWNER.
2. SAND AND PAINT, COLUMNS AND DROP BEAM ON FIRST FLOOR.
3. EPOXY REPAIRS TO STRINGERS.
4. PLASTER REPAIRS IN SELECT LOCATIONS. REPAIRS SHALL BE PAINTED.
PLUMBING SYSTEMS:
1. REPAIR TO EX'G SANITARY PIPING ON SECOND FLOOR.
ELECTRICAL SYSTEMS:
1. UPGRADE FIRE ALARM DETECTION SYSTEM.
2. REPLACE SECOND FLOOR LIGHT FIXTURES INCLUDING ALL EMERGENCY
LIGHTS AND EXIT SIGNS. FIXTURES PROVIDED BY OWNER.
3. REPLACE EXTERIOR LIGHTS BELOW PENT EAVE. FIXTURES PROVIDED BY
OWNER.
LIGHTNING PROTECTION SYSTEM:
1. INSTALL LIGHTNING PROTECTION SYSTEM PER SPECIFICATIONS.
CS
BID ALTERNATES:
BID ALT 1: REMOVE THE NON- HISTORIC SECOND FLOOR PARTITION
WALLS. REPAIR PLASTER AND PAINT WHERE PARTITION
WALLS INTERSECT FULL- HEIGHT WALLS.
BID ALT 2: REMOVE AND REPLACE EXTERIOR STORM WINDOWS FOR
THE SECOND FLOOR.
BID ALT 3A: ROUGH IN FOR KITCHENETTE @ SECOND FLOOR. INSTALL
SANITARY DRAINAGE AND VENTING FOR KITCHENETTE
FIXTURES.
BID ALT 3B: INSTALL KITCHENETTE CABINETRY AND APPLIANCES.
BID ALT 4A: PREP & PAINT PLASTER WALLS, AND CEILING (ALL ABOVE
WAINSCOT). PAINT PROVIDED BY OWNER.
BID ALT 4B: PREP & PAINT WAINSCOT AND ALL TRIM, BENCHES,
STAIRS ETC., (BEYOND BASE SCOPE OF WORK). PAINT PROVIDED BY
OWNER.
BID ALT 5: PREP AND PAINT WALLS, CEILING, AND TRIM OF 2ND
FLOOR (BEYOND BASE SCOPE OF WORK) PAINT PROVIDED BY OWNER.
CS
SITE PLAN
PROJECT NORTH
UNIT PRICES:
UNIT PRICE 1: REPOINTING PSF
UNIT PRICE 2: DOMESTIC WATER REPLACEMENT PIPING PLF &
SANITARY REPLACEMENT PIPING PLF.
LOCAL JURISDICTION: CITY OF CHESTER
ZONING: CBD- CENTRAL BUSINESS DISTRICT
DATE OF CONSTRUCTION: 1724
LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES.
ALL WORK SHALL CONFORM TO THE SECRETARY OF THE
INTERIOR STANDARDS FOR THE TREATMENT OF HISTORIC PROPERTIES.
OWNER: PENNSYLVANIA HISTORICAL AND MUSEUM COMMISSION.
USING AGENCY: COUNTY OF DELAWARE
SITE COORDINATES: 39.847612, -75.359709
CONSTRUCTION CODES: PA UCC, IBC 2018, IPC 2018, IEBC 2018, ASCE 7-16
DESIGN ITEM CRITERIA CODE REFERENCE
USE GROUPS:
FIRST FLOOR A-3 (MUSEUM) IBC 303
SECOND FLOOR B- BUSINESS IBC 304
NUMBER OF EX'G STORIES 2 (PLUS CUPOLA AND ATTIC)
CONSTRUCTION TYPE IIIB IBC 602.3
FIRE RESISTANCE REQ.
- EXTERIOR WALLS 2 HOUR IBC 601
- ROOF 0 HOUR IBC 601
EXISTING FIRE PROTECTION SYSTEMS IBC 903
- FIRE DETECTION INSTALLED IN ALL LEVELS 903.2.1.3
- INSTALL ONE FIRE EXTINGUISHER PER LEVEL
ROOF ASSEMBLY CLASS C (MIN) IBC 1505.1
BASIC WIND SPEED 112 MPH ASCE-7
(RISK CATEGORY II)
GROUND SNOW LOAD 25 PSF ASCE-7, FIG 7-1
GROSS SF OF BLDG: 2,520 SF
SF PER FLOOR:
FIRST FLOOR: 1,260 SF
SECOND FLOOR: 1,260 SF
DESIGN CRITERIA
CHESTER
COURTHOUSE
CS
LOCATION MAP
N
ALLOWANCES
1. PROVIDE ALLOWANCE TO REPLACE 15 LF OF SANITARY
PIPING AND 15 LF OF DOMESTIC WATER PIPING.
NOT FOR
CONSTRUCTION
ACCESS NOTES:
1. OWNER WILL PROVIDE A HIGH-REACH FOR CONTRACTOR/
SUBCONTRACTOR'S USE FOR A 3 MONTH PERIOD. CERTIFIED OPERATORS
ARE REQUIRED.
2. GC SHALL COORDINATE SCHEDULES.
AutoCAD SHX Text S
AutoCAD SHX Text S
RI
D
G E
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
KEY PLAN, PHOTO
AND CODE REVIEW
G1.0AGS J&M
G1.0
KEY PLAN
G1.0
G1.0
PHOTO: SOUTH ELEVATION
G1.0
PHOTO:WEST ELEVATION
G1.0
G1.0
G1.0
PHOTO: NORTH ELEVATIONPHOTO: EAST ELEVATION
G1.0
G1.0
N
G1.0
FIRST FLOOR EGRESS DIAGRAM
KEY:
EXISTING ACCESS PATH
PATH FROM MOST REMOTE POINT
A-A
B- B
D-D E-E
C -C
E-E
E-E
D -D
G1.0
SECOND FLOOR EGRESS DIAGRAM
PROJECT NORTH
KEY:
EXISTING ACCESS PATH
PATH FROM MOST REMOTE POINT
OLD
COURT ROOM
FF TO CEILING AT 14' -4
9/16" A.F.F.
(MAX. HEIGHT)
EX'G PLATFORM TO
CEILING: 13'-7 9/16"
EX'G PLATFORM TO
CEILING: 12'-0 3/16"
EX'G
PLATFORM
TO CEILING:
10'-0"
4' -2
/2
35'-0 1/2"
35'-0 1/2"
'-2
/2
8' -1
/1
6" 8'
-3
/4
9'-11 9/16"
'-0
/4
'-1
30'-11 13/16" INTERIOR DIM
'-1
/4
" I N
TE
RI
O R
D
IM
'-2
/1
6"
STO
N
E M A
RK
ER
FLA
G
STO
N
E
STONE
'-6
/2
4'
-9
3'-11"
STAIRWELL/
VESTIBULE
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
FIRST FLOOR PLAN
A1.1AGS J&M
1.1
1.2 1.3
1.4
1.5
1.6
1.7
1.8
1.9
A1.1
FIRST FLOOR PLAN
SCALE: 1/4"=1'-0"
STAIR LANDING
WALL UNDER STAIRS
UNDERSIDE OF STAIRS
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH IBC AND IEBC 2018, CITY CODES, AND ACCEPTABLE
CONSTRUCTION PRACTICES.
2. THE BUILDING SHALL NOT BE LEFT OPEN TO WEATHER, ANIMALS OR INTRUDERS AND CARE SHALL BE TAKEN DURING CONSTRUCTION. THE OWNER AND CONTRACTOR SHALL COMMUNICATE ON ACCEPTABLE METHODS.
3. ALL INSPECTIONS SHALL OCCUR PER CODE AND CITY REQUIREMENTS.
4. CONTRACTOR AND/OR WASTE HAULER SHALL FOLLOW ALL LOCAL CODE REQUIREMENTS RELATIVE TO
RESPONSIBLE WASTE REMOVAL AND DISPOSAL.
DEMOLITION NOTES
N
PROJECT NORTH
BID ALT 1A: DEMOLISH NON-LOAD
BEARING PARTITIONS. REPAIR
PLASTER AND PAINT WALLS
WHERE PARTITIONS INTERSECTED
THE PERIMETER WALLS. FILL-IN
ANY HOLES IN STONE FLOOR
WITH REPAIR MORTAR. CONSULT
WITH A/E PRIOR TO ANY STONE
PATCHING.
GENERAL NOTES
1. CONTRACTOR SHALL REPAIR PLASTER WALLS AND CEILINGS. SEE SCHEDULE.
2. CONTRACTOR SHALL PREP AND PAINT ALL PLASTER REPAIRS. PAINT PROVIDED BY OWNER.
3. CONTRACTOR SHALL PAINT COLUMNS AND DROP BEAM. SPOT PRIME AS REQ TO CONCEAL TANNIN BLEED. NO OTHER PAINTING WORK INCLUDED
IN BASE SCOPE OF WORK. PAINT PROVIDED BY OWNER.
4. ANY FURNISHING REMAINING IN THE BUILDING DURING CONSTRUCTION SHALL BE TIGHTLY TARPED/ WRAPPED AND PROTECTED FROM DAMAGE.
A5.1
EXISTING 7/8" THICK WOOD WAINSCOT
MOUNTED TO WOOD BLOCKING
EMBEDDED INTO STONE. NO METAL LATH
ASSEMBLY BEHIND WAINSCOT.
EXISTING METAL LATH AND PLASTER
AROUND DOORWAY OVER ORIGINAL
PLASTER SYSTEM.
A5.1
EX'G THERMOSTAT
BID ALT 4A: PREP & PAINT PLASTER WALLS, AND CEILING (ALL ABOVE WAINSCOT). PAINT PROVIDED BY OWNER.
BID ALT 4B: PREP & PAINT WAINSCOT AND ALL TRIM, BENCHES, STAIRS ETC, (BEYOND BASE SCOPE OF WORK). PAINT
PROVIDED BY OWNER.
BASE SCOPE
WORK BY OTHERS
KEY:
8' -1
/1
6"
EX'G FF TO CEILING:
8'-4 5
16"
35'-0 1/2"
35'-0 1/2"
'-2
/2
8' -3
/4
9'-11 9/16"
'-0
/4
'-1
'-0
/1
6"
'-9
/8
OFFICE
HALL
2ND FLOOR LOBBY
15'-11 1/16"
'-5
1/
'-2
/8
3'
-7
/1 6"
3' -0
/8
5'-3 1/2"
2' -3
/4
15'-9 5/8"
'-1
3/
3'-8 11/16"
6'-5"
15'-8 7/8"
4'-10 15/16"
2' -0
/4
7'-8 7/16"
16'-1"
5'-1 11/16"4'-9 3/4"
7'-8 7/16" 7'-7 3/16"
24'-7 1/4"
MEETING
ROOM
CHIMNEY/
FIREPLACE
7' -1
0"
6" 3'-5"
1'-3"
3' -1
1"
8' -2
/8
'-2
/8
24"
REF
2'-0"2'-6" 1'-0"
C A
B 2' -0
2"
'-1
/1 6"
5'-8"
15'-8 7/8"
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
SECOND FLOOR PLAN
A1.2AGS J&M
A1.2
SECOND FLOOR PLAN
SCALE: 1/4"=1'-0"
2.1 2.2
2.3
2.4
2.5
2.62.7
2.8
2.9
2.10
2.11
1 3
55 5 6 6
7B
A3.1
BID ALT 3B: INSTALL
CABINETRY, COUNTER
TOP AND APPLIANCES
PER SCHEDULE.
N
PROJECT NORTH
BID ALT 1B: DEMOLISH
NON-LOAD BEARING
PARTIAL HEIGHT
PARTITIONS.
EX'G FIXTURES TO
REMAIN.
GENERAL NOTES
1. EX'G CARPET TILES AND LIGHTLY SAND FLOORS TO REMOVE RESIDUE BY OWNER.
2. CONTRACTOR SHALL REPAIR PLASTER WALLS AND CEILINGS. CONTRACTOR SHALL PAINT ALL PLASTER REPAIRS. NO OTHER
PAINTING REQUIRED IN BASE OF SCOPE OF WORK. PAINT PROVIDED BY OWNER.
3. SEE WINDOW AND DOOR SCHEDULE FOR REPAIRS ON SHEET A6.1.
A3.1
A5.1
A5.1
7A
7C
BY OWNER: DEMOLISH
WALL HUNG SHELVES
AND REPAIR PLASTER
WALLS AS SPECIFIED.
ELIMINATE THE
EXPOSED WIRING AS
FEASIBLE.
BY OWNER: PATCH
DAMAGED WALL
BEHIND AND ADJ. TO
TOILET FIXTURE PRIOR
TO PAINTING. SAND
AND PRIME BEFORE
PAINTING.
BID ALT 3B: REMOVE THE
EXISTING RACEWAY WHERE
THE CABINETRY SHALL BE
INSTALLED
BID ALT 1: REMOVE THE NON- HISTORIC SECOND FLOOR PARTITION WALLS. REPAIR PLASTER AND PAINT WHERE PARTITION WALLS INTERSECT
FULL-HEIGHT WALLS.
BID ALT 2: REMOVE AND REPLACE EXTERIOR STORM WINDOWS FOR THE SECOND FLOOR.
BID ALT 3A: ROUGH IN FOR KITCHENETTE @ SECOND FLOOR. INSTALL SANITARY DRAINAGE AND VENTING FOR KITCHENETTE FIXTURES.
BID ALT 3B: INSTALL KITCHENETTE CABINETRY AND APPLIANCES.
BID ALT 5: PREP AND PAINT WALLS, CEILING, AND TRIM OF 2ND FLOOR. PAINT PROVIDED BY OWNER.
HVAC VENTS TO BE
REPLACED BY OWNER,
TYP.
BASE SCOPE
WORK BY OTHERS
KEY:
ATTIC
ROOM
BOILER
ROOM
8' -8
/4
9'-4"
32'-6 1/4"
'-4
/8
13'-0"
2'-4 3/4"
13'-3 1/2"
5' -6
9'-0"
RIDGE HEIGHT: 13'-8"
BAY WINDOW BELOW
CH
6'-10"
EX'G FJ: 3"x9" @ 20"-22" O.C WITH
BATT INSULATION
EX'G RR: 2-3/4" X 7-1/8" SPACED @
26" TO 28" O.C
STEP U
P: 5"
SLOPE DN SLOPE DN
EXISTING CHIMNEY
EXISTING DOWNSPOUT
EXISTING DOWNSPOUTEXISTING CHIMNEY
EXISTING DOWNSPOUT
EXISTING DOWNSPOUT
LINE OF WALL
FACE BELOW
EXISTING
VENT STACK
SLOPE DN SLOPE DN
RI
D
G E
RI
D
G E
RID
GE
RIDGE
RIDGE
RID
GE
EXISTING CUPOLA WITH
BRASS BELL (NOTE THAT
THIS IS ACTIVE) VALLEY
SLOPE DN
SLOPE DN
SLOPE DN
VALLEYSEE CUPOLA WINDOW
DETAIL 2/A1.4.
NOTE: ROOF FRAMING IS
DIAGRAMMATIC AND IS FOR
REFERENCE ONLY.
REMOVE ABANDONED FLUE VENT AND CAP
MASONRY CHIMNEY TO MATCH EX'G.
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
ATTIC FLOOR AND
ROOF PLAN
A1.3
A1.3
ATTIC FLOOR PLAN
SCALE: 1/4"=1'-0"
3.1
N
PROJECT NORTH
GENERAL NOTES
1. SEE WINDOW AND DOOR SCHEDULE FOR REPAIRS ON SHEET A6.1.
2. ALL LEADERS AND GUTTERS TO BE CLEANED OF DEBRIS. SCOPE LINES TO ENSURE PROPER DRAINAGE. INSPECT LEADERS AND GUTTERS FOR ANY
OPEN SEAMS OR HOLES AND REPAIR AS REQ.
3. SHINGLE ROOFING WORK BY OTHERS.
A5.1
A4.1
A1.3
ROOF PLAN
SCALE: 1/4"=1'-0"
N
PROJECT NORTH
A4.1
A5.1
A1.4
AutoCAD SHX Text
RIDGE
AutoCAD SHX Text
RIDGE
2X8 COLLAR TIES AT
CENTERLINE
2-1/2" x 6" COLLAR
TIES AT CENTERLINE
3-1/2" x 3-1/2" POST, TYPICAL.
SEE CUPOLA WINDOW
DETAIL 2/A1.4.
NOT SURVEYED.
NOTE: ROOF FRAMING IS
DIAGRAMMATIC AND IS FOR
REFERENCE ONLY.
CUPOLA FLOOR
INTERIOR CUPOLA
7' -0
EX'G INTERIOR WALLS ARE
SHEATHED WITH 5/4" THICK X
5-1/4" ON THE DIAGONAL
BOARDS. FLOOR FRAMING 3-3/4"
TALL X 2" WIDE.
2'-0 1/2"
4' -7
/8
SEE WINDOW SCHEDULE
FOR REPAIRS ON A6.1.
FIXED WOOD LOUVERS. SEE SCHEDULE
FOR REPAIRS.
REMOVE EX'G GLASS AND INSTALL BIRD
SCREEN BETWEEN LOUVER AND
CASEMENT
EX'G WOOD CASEMENT. SEE SCHEDULE
FOR REPAIRS.
EX'G 5/4" INTERIOR WOOD WALL
PANELING
EX'G FRAME WALL
EX'G EXTERIOR WOOD KEYSTONE TRIM
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
ROOF DIAGRAM AND
CUPOLA DETAILS
A1.4
A1.4
ROOF FRAMING DIAGRAM
SCALE: 1/4"=1'-0"
N
PROJECT NORTH
4.1
4.2
4.3
4.4
A5.1
A1.4
CUPOLA WINDOW INTERIOR ELEVATION
SCALE: 3/4"=1'-0"
A1.4
CUPOLA WINDOW SECTION DETAIL
SCALE: 1-1/2"=1'-0"
A1.4
40'-2 1/2"
40'-8 1/2"
'-4
/8
8'
-4
/1 6"
FIRST FLOOR
FIRST FLOOR CEILING
SECOND FLOOR
SECOND FLOOR CEILING
ATTIC FLOOR
UNDERSIDE OF RIDGE
'-8
INTERIOR CUPOLA
7' -0
FI
RS
T
FL
O O
R W
IN
D
O W
S, D
O O
RS
A N
D O
V
ER
H A
N G
N O
T
IN
S C
O
PE
PA
IN
T
LO
SS
REMOVE ABANDONED
FLUE VENT AND CAP
MASONRY CHIMNEY TO
MATCH EX'G.
EX'G CEDAR SHINGLES, TYP.
EX'G COPPER FLASHING AND
GUTTERS, TYP.
EX'G WOOD TRIMWORK,
SILL, AND WINDOWS TYP.
EX'G ASHLAR STONE
MASONRY, TYP.
EX'G ASHLAR STONE
MASONRY, TYP.
EX'G HORIZONTAL
WOOD SIDING, TYP.
35'-0 1/2"
35'-6 3/8" 8'-6 7/8"
8'-6 3/4"
'-4
/8
8'
-4
/1 6"
FIRST FLOOR
FIRST FLOOR CEILING
SECOND FLOOR
SECOND FLOOR CEILING
ATTIC FLOOR
UNDERSIDE OF RIDGE
FI
RS
T
FL
O O
R W
IN
D
O W
S, D
O O
RS
, A
N D
O V
ER
H
A N
G N
O T
IN
S
C O
PE
'-8
INTERIOR CUPOLA
7' -0
PA
IN
T
LO
SS
SPALL (STONE): REMOVE LOOSE MATERIAL AND PATCH WITH JAHN REPAIR MORTARS.
VEGETATION GROWTH: REMOVED BY OWNER.
OPEN JOINT: ALL OPEN AND DETERIORATED JOINTS SHALL BE RAKED OUT AND REPOINTED
WOOD ROT: CONTRACTOR SHALL REMOVE ROTTED WOOD AND INSTALL DUTCHMAN OR EPOXY REPAIR. VIF IN A/E.
CRACKING: CONTRACTOR SHALL CLEAN DEBRIS FROM MASONRY CRACK AND FILL WITH MORTAR. RAKE MORTAR
FLUSH WITH ADJ. SURFACE
PAINT FAILURE: CONTRACTOR SHALL ASSUME MINOR EPOXY REPAIR REQUIRED PRIOR TO PRIMING AND PAINTING
REPAIR LEGEND:
REMOVE EX'G MORTAR & REPOINT.
REPOINTING NOT IN BASE SCOPE. OWNER MAY ELECT ADD'L POINTING USING UNIT COST.
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
ELEVATIONS:
NORTH & EAST
A2.1
A2.1
EAST ELEVATION
SCALE: 1/4"=1'-0"
2.1 2.2
2.3 2.4 2.52.3
OWNER SHALL REMOVE/
CUT BACK SHRUBS
AWAY FROM BUILDING
GENERAL NOTES
1. SEE WINDOW AND DOOR SCHEDULE FOR REPAIRS ON SHEET A6.1.
2. FIRST FLOOR EXTERIOR PAINT BY OTHERS.
3. ROOFING WORK BY OTHERS.
4. SEE ROOF PLAN FOR DRAINAGE REPAIRS.
5. INSTALL URETHANE BASED JOINT SEALANT TO MATCH MORTAR COLOR AROUND ALL WINDOWS AND DOORS. TOOL CONCAVE TO RECESS JOINT, TYP.
WOOD REPAIR AND
PAINTING REQUIRED
FOR EAVES AND SOFFITS,
TYP.
WOOD REPAIR AND
PAINTING REQUIRED ON
GABLE TRIM, TYP.
ALL WINDOWS SILL AND
SHUTTERS ABOVE THE
FIRST FLOOR SHALL BE
REPAINTED.
MINOR WOOD REPAIR, LOUVER
RESTORATION AND PAINTING REQ.
ON CUPOLA, TYP.
A2.1
NORTH ELEVATION
SCALE: 1/4"=1'-0"
LIGHTNING PROTECTION
CONDUCTOR
OPEN MASONRY JOINTS
40'-6"
41'-0"
8'-6 3/4" 35'-6 1/2" 8'-6 3/4" 35'-0 1/2"
FIRST FLOORFIRST FLOOR
'-4
/8
8'
-4
/1 6"
FIRST FLOOR CEILING
SECOND FLOOR
SECOND FLOOR CEILING
ATTIC FLOOR
UNDERSIDE OF RIDGE
FIRST FLOOR CEILING
SECOND FLOOR
SECOND FLOOR CEILING
ATTIC FLOOR
UNDERSIDE OF RIDGE
'-4
/8
8'
-4
/1 6"
'-8
INTERIOR CUPOLA
7' -0
INTERIOR CUPOLA
7' -0
'-8
FI
RS
T
FL
O O
R W
IN
D
O W
S, D
O O
RS
A N
D O
V
ER
H A
N G
N O
T
IN
S C
O
PE
FI
RS
T
FL
O O
R W
IN
D
O W
S, D
O O
RS
A N
D O
V
ER
H A
N G
N O
T
IN
S C
O
PE
PA
IN
T
LO
SS
PA
IN
T
LO
SS
REMOVE ABANDONED FLUE
VENT AND CAP MASONRY
CHIMNEY TO MATCH EX'G.
EX'G CEDAR SHINGLES, TYP.
EX'G COPPER FLASHING AND
GUTTERS, TYP.
EX'G ASHLAR STONE
MASONRY, TYP.
EX'G ASHLAR STONE
MASONRY, TYP.
EX'G HORIZONTAL
WOOD SIDING, TYP.
SPALL (STONE): REMOVE LOOSE MATERIAL AND PATCH WITH JAHN REPAIR MORTARS.
VEGETATION GROWTH: REMOVED BY OWNER.
OPEN JOINT: ALL OPEN AND DETERIORATED JOINTS SHALL BE RAKED OUT AND REPOINTED
WOOD ROT: CONTRACTOR SHALL REMOVE ROTTED WOOD AND INSTALL DUTCHMAN OR EPOXY REPAIR. VIF IN A/E.
CRACKING: CONTRACTOR SHALL CLEAN DEBRIS FROM MASONRY CRACK AND FILL WITH MORTAR. RAKE MORTAR
FLUSH WITH ADJ. SURFACE
PAINT FAILURE: CONTRACTOR SHALL ASSUME MINOR EPOXY REPAIR REQUIRED PRIOR TO PRIMING AND PAINTING
REPAIR LEGEND:
REMOVE EX'G MORTAR & REPOINT.
REPOINTING NOT IN BASE SCOPE. OWNER MAY ELECT ADD'L POINTING USING UNIT COST.
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
ELEVATIONS:
SOUTH AND WEST
A2.2
A2.2
SOUTH ELEVATION
SCALE: 1/4"=1'-0"
A2.2
WEST ELEVATION
SCALE: 1/4"=1'-0"
2.8 2.9 2.10 2.112.5 2.6 2.7
3.1
BY OWNER: REMOVE
ALL IVY FROM
BUILDING.
GENERAL NOTES
1. SEE WINDOW AND DOOR SCHEDULE FOR REPAIRS ON SHEET A6.1.
2. FIRST FLOOR EXTERIOR PAINT BY OTHERS.
3. ROOFING WORK BY OTHERS.
4. SEE ROOF PLAN FOR DRAINAGE REPAIRS.
5. INSTALL URETHANE BASED JOINT SEALANT TO MATCH MORTAR COLOR AROUND ALL WINDOWS AND DOORS. TOOL CONCAVE TO RECESS JOINT, TYP.
WOOD REPAIR AND
PAINTING REQUIRED
FOR EAVES AND SOFFITS,
TYP.
WOOD REPAIR AND
PAINTING REQUIRED ON
GABLE TRIM, TYP.
ALL WINDOWS SILL AND
SHUTTERS ABOVE THE FIRST
FLOOR SHALL BE REPAINTED.
MINOR WOOD REPAIR, LOUVER
RESTORATION AND PAINTING REQ.
ON CUPOLA, TYP.
REMOVE EX'G
LOUVER AND REPAIR
EXISTING WINDOW.
A4.1
EX'G SHUTTERS ARE MISSING
FROM WINDOW. REFERENCE
WINDOW SCHEDULE FOR
REPAIR DETAILS.
LIGHTNING PROTECTION
CONDUCTOR
OPEN MASONRY JOINTS
15'-8 7/8"
8' -4
/1
6"
24" REF
2'-6"2'-6" 1'-0"2"
FILLER
PANEL 2'-0" 2'-11"
MAINTAIN
EXISTING CHAIR
RAIL
COUNTERTOP TO BE
TEMPLATED TO
ACCOMMODATE
THE EXISTING
CHAIR RAIL- ADD
CAULKING
EX'G CHAIR RAIL
EX'G BASEBOARDFILLER/CAP PIECE
TO BE SCRIPTED
AROUND CHAIR
RAIL.
GFCI OUTLET
4' -6
SHELVING WITH
CONCEALED BRACKETS
3' -6
2'-6"2'-6"
CABINETS
SHALL HAVE
FINISHED
PANELS, TYP.
EX'G CHAIR
RAIL
EX'G BASEBOARD
CHAIR RAIL
BEYOND
1 7/8" CABINETRY
OFFSET FROM
CHAIR RAIL
2'-0"
FILLER/CAP PIECE TO
BE SCRIPTED
AROUND CHAIR RAIL
AND BASEBOARD TO
COVER GAP
BETWEEN BACK OF
CABINET AND WALL.
1' -6
3'-8 11/16" 4'-10 15/16"
24"
REF
2'-0"2'-6" 1'-0"
CAB
2' -0
2" 5'-8"
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
BID ALT 3A: KITCHENETTE
DETAILS
A3.1
A3.1
BID ALT: KITCHENETTE INTERIOR ELEVATION
SCALE: 1/2"=1'-0"
A3.1
BID ALT: KITCHENETTE SIDE ELEVATION
SCALE: 1/2"=1'-0"
A3.1
BID ALT: KITCHENETTE FLOOR PLAN
SCALE: 1/2"=1'-0"
A3.1
A3.1
DEEP GUIDE CHANNEL STOP
REPLACEMENT STORMS TO
HAVE MEETING RAILS ALIGN
WITH WOOD SASHES BEYOND
PER ALLIED HOL-OP SERIES
H-10: HOL FRAMING (T-9)
H STYLE SILL EXPANDER.
PER ALLIED HOL-OP SERIES H-10:
HOL FRAMING (D-42)
RETAINING CLIP
PER ALLIED HOL-OP SERIES
H-10: HOL FRAMING (S-101)
PER ALLIED HOL-OP SERIES
H-10: HOL FRAMING (D-42)
PER ALLIED HOL-OP SERIES
H-10: HOL FRAMING (D-50)
PER ALLIED HOL-OP SERIES
H-10: HOL FRAMING (CS-3)
1/ 4"
1/
8"
1/ 2"
1/
1/
2"
3"
1/
2"
7/
8"
3/4"
7/
8"
2"
INSIDE OUTSIDE
1/2 SCREEN
UPPER SASH LOWER SASH
SPRING LOADED LATCH
BAR ASSEMBLY
PER ALLIED HOL SERIES H-10: HOL
FRAMING (D-45)
FOAM TAPE AND ANCHORS AS
REQUIRED
NOTCH AROUND
SHUTTER PINTELS TO
ALLOW STORM
WINDOW FLANGE TP
ALIGN WITH
BRICKMOULD.
2"
2 7/8" 2 3/4"
3"
3/ 4"
2 3/8"2 3/8"
2"
2 7/8"2 3/4"
OUTSIDE
INSIDE
2 3/4" 2 7/8" 2"
1/
8" 1/
4"
1/
2"
2 3/8"
1/
1/
2"
STORM WINDOW OUTLINE
EX'G FLOOR JOISTS: 3"X9"
EX'G ROOF RAFTERS: 2
-3/4" x 7 1/8"
18'-3 1/2"
EX'G ROOF RAFTERS: 2-3/4" x 7 1/8"
7' -1
0"9' -6
3/
1/
4"
4' -0
2'-6"
5"
1' -1
/1
6"
REMOVE EX'G LOUVER AND
REPAIR EXISTING WINDOW
SASHES.
'-1
7/
8"
EX'G COLLAR TIE: 2-1/2"X6"
EX'G COLLAR TIE: 2X8
EX'G STUD WALL WITH
GYP.
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
WINDOW DETAILS
A4.12 A4.1
REPLACEMENT STORM WINDOW SECTION DETAIL W/ EX'G WINDOW
SCALE: 6"=1'-0"
A4.1 SCALE: 6"=1'-0"
A4.1
BID ALT: EX'G WINDOW WITH REPLACEMENT STORM WINDOW APPLIED
SCALE: 1-1/2"=1'-0"
REPLACEMENT STORM WINDOW SECTION DETAIL W/ EX'G WINDOW
A4.1
A4.1
A4.1
INTERIOR ELEVATION: BOILER ROOM WINDOW WITH LOUVER
SCALE: 1/2"=1'-0"
GENERAL NOTES
1. SEE WINDOW SCHEDULE FOR TYP. REPAIR NOTES.
2. EX'G STORM WINDOW FLANGE IS 3/4" AND IS FASTENED TO THE WOOD FRAME WITH WOOD SCREWS. EX'G STORM WINDOW BRAND BASED ON
PREVIOUS DOCUMENTATION IS BELIEVED TO BE HARVEY TRU CHANNEL STORM WINDOW.
3. EX'G STORM WINDOW CAN BE REMOVED FROM THE INTERIOR, HOWEVER THE INTERIOR SASHES MAY INTERFERE AND MAY BECOME DAMAGED.
CONTRACTOR SHALL REVIEW MEANS AND METHODS WITH A/E PRIOR TO COMMENCING WORK.
4' -6
PLASTER FINISH
2X DOUBLE TOP PLATE
2X SOLE PLATE
EXISTING ATTIC FLOOR CAVITY
EXISTING FLOOR CAVITY (UNVERIFIED
FLOOR FRAMING)
EX'G 2X STUD SPACED @ 16" O.C
BASEBOARD
PLASTER CEILING- EXISTING
COMPOSITION OF PLASTER IS
UNKNOWN. VIF
EX'G WOOD FLOOR
BOARDS
EX'G BATT INSULATION
EX'G PLASTER
EX'G SLAB/ STONE PAVERS
EX'G FLOOR JOISTS: ASSUMED 3"X9"
EX'G STONE WALL
EX'G WALL WITH 1/8" FINISHED PLASTER
COAT WITH BROWN COAT ON METAL
LATH (1" THICKNESS) OVER ORIGINAL 3
COAT PLASTER BEYOND.
'-4
/8
8'
-4
/1 6"
EX'G FLOOR JOISTS: 3"X9"
EX'G ROOF RAFTERS: 2
-3/4" x 7 1/8"
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
TYPICAL DETAILS
A5.1
A5.1
FOR REFERENCE: EX'G PARTITION WALL SECTION
@ 2ND FLOOR
SCALE: 1" = 1'-0"
A5.1
FOR REFERENCE: EXTERIOR WALL SECTION
SCALE: 1/2" = 1'-0"
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
0.1 08.30.24SCHEMATIC SUBMISSION
0.2 10.23.24DD SUBMISSION
0.3 11.18.2475% SUBMISSION
0.4 12.19.2490% SUBMISSION
0.5 01.24.25100% SUBMISSION
1 03.17.25BID ADDENDUM
08/21/25
2 08.21.25ISSUED FOR REBID
J&MAGS
SCHEDULES
A6.1
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
COLD WATER - POTABLECW
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
SANITARY DRAINAGESAN
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
BACKFLOW PREVENTER
EXPANSION JOINT
#.#" IS THE EXPANSION TRAVEL INCHESEJ-#
AIR ADMITTANCE VALVE
SAFETY RELIEF VALVE
W/ DRIP PAN ELBOW
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
FLOOR SINKFS
GARBAGE DISPOSERGD
GREASE INTERCEPTORGI
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYL or LAV
MOP BASINMB
MH MANHOLE
MIXING VALVEMV
NEUTRALIZATION TANKNT
OIL SEPARATOROS
ROOF DRAINRD
SHOWERSH
SINKSK
SERVICE SINKSS
TRENCH DRAINTD
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WASH FOUNTAINWF
WATER HEATERWH
WASHING MACHINE FIXTUREWMF
YARD CLEANOUTYCO
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
EXISTINGE
FLOW METERFM
WATER SOFTENERWS
WATER METERWM
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
DUCTILE IRONDI
UTILITY BOXUB
SHORT CIRCUIT CURRENT RATINGSCCR
DOWNDN
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
BUILDING CODE: IBC 2018 EDITION
FIRE CODE: IEBC 2018
PLUMBING CODE: IPC 2018 EDITION
MECHANICAL CODE: IMC 2018 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2017 EDITION
ENERGY CONSERVATION CODE: IECC 2018
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
CIVIL CONTRACTORC.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
CONSTRUCTION MANAGERC.M.
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT
LIMITED TO PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING,
EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED
FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY
AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. CATALOG AND MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE
GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED.
CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE DESCRIPTION OF MATERIAL
SCHEDULED ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING.
THE DESCRIPTION OF THE MATERIAL AND SCHEDULED PERFORMANCE TAKES
PRECEDENCE OVER THE MODEL NUMBER. THE FIRST MANUFACTURER SCHEDULED
IS THE BASIS OF DESIGN.
3. DETERMINATION OF QUANTITIES OF MATERIAL AND EQUIPMENT REQUIRED SHALL
BE MADE BY THE CONTRACTOR FROM THE DOCUMENTS. WHERE MATERIAL AND/OR
QUANTITY DISCREPANCIES ARISE BETWEEN DRAWINGS, SCHEDULES AND/OR
SPECIFICATIONS, THE HIGHER QUALITY/ GREATER NUMBER SHALL GOVERN.
4. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS
OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER
TRADES.
5. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO
PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE
COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT
FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES.
BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE
ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT
ORDERS.
6. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND
MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE
PROPER ACCESS.
7. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A
FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT
ADDITIONAL COST OR EXPENSE TO OTHERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH
ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM
THE BASIS OF DESIGN.
9. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL
CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
10. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES
DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION,
FIRE RATING, AND FINISH.
11. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS
WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC.
COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE
REQUIRED ACCESS PANELS PRIOR TO BIDDING.
12. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS,
PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND
ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS
RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
13. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC
LEVELS WITHIN ROOMS.
14. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE
WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE
WATERTIGHT.
15. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG
DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR
EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH
LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
16. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.
17. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT
NOT LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL
CENTERS, TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
18. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH /
DEPTH OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0”
ABOVE THE EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER.
SYSTEMS FOREIGN TO THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED
IN THE DEDICATED ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH THEIR WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO
THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS
RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN
THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES
PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE
BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL
APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
5. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.
6. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK
UNLESS NOTED OTHERWISE.
PLUMBING GENERAL NOTES:
PLUMBING SLOPE REQUIREMENTS:
INTERIOR:
SANITARY WASTE: ≤2-1/2”ø=1/4” PER FOOT ≥3”ø = 1/8” PER FOOT ≥8”ø = 1/16” PER FOOT
GREASE WASTE: 1/4” PER FOOT
STORM (GRAVITY): 1/8” PER FOOT
CONDENSATE AND INDIRECT DRAINAGE: 1/8” PER FOOT
SANITARY AND GREASE VENT: NO SPECIFIC PITCH, PITCH TO FIXTURES
DOMESTIC WATER: NO SPECIFIC PITCH, PITCH TO FIXTURES
BASED ON PLUMBING CODE: IPC-2018
PLUMBING SHEET INDEX
P000 PLUMBING COVERSHEET
P211 FLOOR PLAN - LEVEL 01 - PLUMBING
P213 FLOOR PLAN - LEVEL 03 - PLUMBING
P600 PLUMBING SCHEDULES
GRAND TOTAL: 4
NOTES: (APPLIES TO ALL PLUMBING FIXTURES LISTED BELOW)
1) SIZES SHOWN ARE MINIMUMS. LARGER SIZES SHOWN ON THE DRAWING SHALL DICTATE THE
ROUGH-IN SIZE. 2) SANITARY RISERS UP IN WALL TO FIXTURES SHALL BE A MINUMUM OF 2". 3) DOMESTIC WATER BRANCH PIPING OUTSIDE OF THE WALL/CHASE SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. ONLY THE FINAL RISE-DROP SHALL BE SMALLER. 4) FINAL SANITARY
SIZE SHALL MATCH P-TRAP SIZE (REFER TO MATERIAL LIST).
PLUMBING ROUGH-IN SCHEDULE
TAG NAME DESCRIPTION
COLD
WATER
HOT
WATER SANITARY VENT
SK-1 SINK 1/2" 1/2" 1 1/2" 1 1/2"
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2209 CHESTNUT STREET
PHILADELPHIA, PA 19103
P: 215.569.0400 F: 215.569.2664 www.imegcorp.com
PROJECT #24004655.00
PRELIMINARY
NOT FOR
CONSTRUCTION
PROJECT #24004655.00
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES,
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
CONSULTANT
SEAL
P000
PLUMBING COVERSHEET
KMRDSS
2025-08-21
75% SUBMISSION 11/15/24
90% SUBMISSION 12/18/24
100% SUBMISSION 01/24/25
2 ISSUED FOR REBID 08.21.25
ta g ta g ta g ta g ta g
3/4"CW - E
4"SAN - E
OUTLINE OF
RESTROOMS ABOVE
WH-1
3"V - E
3/4"CW - E
4"SAN - E
EXISTING WATER CLOSETS
AND LAVATORIES
BID ALT 3A: PROVIDE SANITARY, VENT,
AND CW ROUGH-IN PIPING FOR FUTURE
KITCHENETTE FIXTURE CONNECTIONS
BID ALT 3B: FURNISH AND INSTALL
KITCHENETTE FIXTURES AND WH-1
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2209 CHESTNUT STREET
PHILADELPHIA, PA 19103
P: 215.569.0400 F: 215.569.2664 www.imegcorp.com
PROJECT #24004655.00
PRELIMINARY
NOT FOR
CONSTRUCTION
PROJECT #24004655.00
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES,
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
CONSULTANT
SEAL
P211
FLOOR PLAN - LEVEL 01 -
PLUMBING
KMRDSS
2025-08-21
N O R
HT
1/4" = 1'-0"1
FLOOR PLAN - LEVEL 01 - PLUMBING
N O R
HT
1/4" = 1'-0"2
FLOOR PLAN - LEVEL 02 - PLUMBING
KEYNOTES:
1. CONTRACTOR TO INVESTIGATE CAUSE OF
WATER DAMAGE TO FIRST FLOOR CEILING.
PROVIDE ALLOWANCE TO REPLACE 15FT OF
SANITARY PIPING AND 15 FT OF DOMESTIC
WATER PIPING .
2. BID ALT 3A/B: PLUMBING FOR SK-1 SHALL BE AS
FOLLOWS: CONNECT TO 4" SAN IN FIRST
FLOOR CEILING. CONNECT TO 3" V IN ATTIC.
CONNECT TO CW IN EITHER WALL OF
ADJACENT TOILET ROOM OR IN FIRST FLOOR
CEILING.
75% SUBMISSION 11/15/24
90% SUBMISSION 12/18/24
R
ID
G E
1/2"CW -E
4"SAN - E
3"V - E
3/4"CW - E
4" VTR - E
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2209 CHESTNUT STREET
PHILADELPHIA, PA 19103
P: 215.569.0400 F: 215.569.2664 www.imegcorp.com
PROJECT #24004655.00
PRELIMINARY
NOT FOR
CONSTRUCTION
PROJECT #24004655.00
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES,
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
CONSULTANT
SEAL
P213
FLOOR PLAN - LEVEL 03 -
PLUMBING
KMRDSS
2025-08-21
N O R
HT
1/4" = 1'-0"1
FLOOR PLAN - ATTIC - PLUMBING
KEYNOTES:
1. DEMOLISH EXISTING CW MAKEUP PIPING TO
BOILER AND RELATED HEAT TRACE.
N O R
HT
1/4" = 1'-0"2
FLOOR PLAN - ROOF - PLUMBING
75% SUBMISSION 11/15/24
90% SUBMISSION 12/18/24
LEVEL 01
LEVEL 02
ATTIC
4" VTR - E
S A
N
E
4" SAN - E
3" V- E
V
E
ALT 3A/B: PROVIDE 1-1/2" SAN AND V TO
SK-1. CONNECT TO EXISTING SANITARY
RISER AND VENT IN ATTIC
ALT 3A/B: PROVIDE 3/4" CW TO WH-1
/4
C
W
E
TO EXISTING RESTROOMS
(WC AND LAV)
EXISTING DSFU: 10
ALT DSFU: 12
ALT 3A/B: PROVIDE 3/4" CW TO SK-1
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2209 CHESTNUT STREET
PHILADELPHIA, PA 19103
P: 215.569.0400 F: 215.569.2664 www.imegcorp.com
PROJECT #24004655.00
PRELIMINARY
NOT FOR
CONSTRUCTION
PROJECT #24004655.00
REVIEWED BY:
NO. DATEREVISION / ISSUE
DRAWING NAME:
REVISIONS:
DRAWN BY:
DATE:
105 RUTGERS AVENUE, #244
SWARTHMORE, PA 19081
PHONE: 215.769.1133
EMAIL: Info@JMPreservation.com
J&M
PRESERVATION
STUDIO
412 AVE OF THE STATES,
CHESTER, PA 19013
CONTRACT # eDPW-040225
REHABILITATION
1724 CHESTER
COURTHOUSE
CONSULTANT
SEAL
P600
PLUMBING SCHEDULES
KMRDSS
2025-08-21
PLUMBING MATERIAL LIST - BID ALTERNATE
TAG NAME DESCRIPTION MANUFACTURER AND MODEL
SK-1 SINK - ACCESSIBLE, SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK, 18 GAUGE TYPE 304 STAINLESS STEEL, 22" (SIDE-TO-SIDE) x 17" (FRONT-TO-BACK) OVERALL SIZE, 25" x 15" x 6" DEEP BOWL, SOUND DEADENING ON BOTTOM OF BASIN, 3-1/2" DIAMETER DRAIN OUTLET LOCATION OFF-CENTERED REAR IN BOWL, REMOVABLE TYPE 304 STAINLESS STEEL BASKET STRAINER WITH NEOPRENE STOPPER.
SINK TRIM - SINGLE HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SWING SPOUT, NOMINAL 8" REACH, AERATOR, LEVER HANDLE, SINGLE HOLE SUPPLIES.
MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH PROJECT WATER CONSERVATION REQUIREMENTS. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AND ESCUTCHEON
PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED
SOFT COPPER SUPPLY LINES.
SINK - AMERICAN STANDARD
(18SB6252211.075), ELKAY, JUST,
FRANKE
SINK TRIM - DELTA 19805Z SD-DST)
PLUMBING (WITH POWER) MATERIAL LIST - BID ALTERNATE
TAG NAME DESCRIPTION
ELECTRICAL
MANUFACTURER AND MODEL W
A
T T
S
O F
S T
A G
E S
F L
A
M C
A
M O
C P
V O
L T
A G
E
P H
A S
E S
DISCONNECT
B
Y (N
O T
E A
T
Y P
E (N
O T
E B
WH-1 WATER HEATER - ELECTRIC, UNDERCABINET, GLASS-LINED WELDED STEEL TANK, 150 PSI WORKING PRESSURE, FIBERGLASS OR FOAM INSULATION, BRASS WATER CONNECTIONS AND DRAIN VALVE, ASME APPROVED T&P RELIEF VALVE, MAGNESIUM ANODE ROD, LOW WATT DENSITY IMMERSION ELEMENTS, AUTOMATIC THERMOSTAT WITH EXTERNAL ADJUSTMENT, HIGH TEMPERATURE CUTOFF SWITCH, ENCLOSED CONTROLS AND ELECTRICAL JUNCTION BOX, 1-YEAR WARRANTY, UL LISTED, COMPLIANT TO NAECA, ASHRAE 90.1 AND ASHRAE 90A.
4 GALLON CAPACITY, 24 MINUTE MAXIMUM RECOVERY.
ELECTRICAL REQUIREMENTS - PLUG, 120V GROUNDED OUTLET.
SET WATER TEMPERATURE AT 140°F.
1440 1 12 15 20 120 1 MFR PLUG WATER HEATER -
EEMAX (EMT-4)
1 = SENSOR ONLY
2 = SENSOR WITH ADJUSTMENT
3 = SENSOR WITH OVERRIDE
4 = SENSOR WITH ADJUSTMENT AND OVERRIDE.
[H] CONTROL / SENSOR TYPE
MFR = MANUFACTURER
MC = MECHANICAL CONTRACTOR
GC = BY GENERAL CONTRACTOR
[G] CURB / PAD BY:
STD = STANDARD CURB
SAC = SOUND ATTENUATOR CURB
CONC = CONCRETE BASE (HOUSEKEEPING PAD)
[G] CURB / PAD TYPE:
MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
[F] RPM DEVIATION
NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF
MOTOR NAME PLATE RATING.
[E] HORSEPOWER LIMITATION
FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED
VALUE, WITH THE SCHEDULED WHEEL TYPE.
SUBSTITUTION OF BI OR BIA FANS FOR FC IS
ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
[D] RPM LIMITATION
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
ECM = ELECTRONICALLY COMMUTATED MOTOR
NOTE: PROVIDE SHAFT GROUNDING ON MOTORS
DRIVEN BY A VFD AS REQUIRED PER SPECIFICATIONS
22 05 13 AND 23 05 13.
[C] CONTROLLER STARTER TYPE:
CB = CIRCUIT BREAKER
F = FUSED
NF = NON-FUSED
PLUG = PLUG AND CORD
[B] DISCONNECT TYPE:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR,
INSTALLED BY ELECTRICAL CONTRACTOR.
MFR/EC = FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR.
TCC = TEMPERATURE CONTROL CONTRACTOR
[A] DISCONNECT AND CNTLR/STARTER FURNISHED
AND INSTALLED BY:
SCHEDULE GENERAL KEY
SK-1 SHALL BE PROVIDED UNDER BID ALTERNATE 3B.
WH-1 SHALL BE PROVIDED UNDER BID ALTERNATE 3B
GENERAL NOTES:
1. REFER TO THE SPECIFICATIONS FOR TYPE DESCRIPTIONS AND JACKETING REQUIREMENTS.
2. TYPE A INSULATION IS NOT ALLOWED IN NON-AIR CONDITIONED SPACES, SUCH AS MECHANICAL ROOMS, EXTERIOR, ATTICS, ETC.
3. TYPE B INSULATION GREATER THAN 1" THICK SHALL BE INSTALLED USING MULTIPLE LAYERS OF 3/4" OR 1" WITH STAGGERED SEAMS.
4. TYPE E IS NOT ALLOWED IN RETURN AIR PLENUMS, UNLESS LISTED AND LABELED AS 25/50 RATED PER ASTM E84/UL723
5. TYPE G 4" SHALL BE INSTALLED IN TWO (2) 2" LAYERS WITH STAGGERED SEAMS.
6. PROVIDE…