This document is a comprehensive set of bid documents for the Wittman Airport Control Tower Chiller Upgrade/Replacement project in Winnebago County, Wisconsin. The project involves replacing the existing chiller (CH-1) with a new chiller (CH-001) in the airport's control tower, including electrical and mechanical system modifications. The project is scheduled for implementation in October 2025, with detailed engineering drawings prepared by Berners-Schober Associates, Inc. located in Green Bay, WI. The bid documents include detailed floor plans, electrical schematics, equipment schedules, and technical specifications for the chiller replacement.
The electrical scope includes removing the existing chiller's electrical connections and installing a new 208V, 3-phase electrical feed using a 200A circuit breaker, with specific conduit and wiring requirements. The new chiller (CH-001) has specifications including a 33.3 kW capacity, 4 compressors, and dimensions of 128x99x88 inches, weighing approximately 3,700 lbs. The project involves coordination between electrical and HVAC contractors, with specific instructions for system integration, including refilling the system with a 40% propylene glycol mix and updating the existing electrical panel directory. The work will be contained within the airport's control tower facility, primarily in rooms 110, 111, 114, and surrounding areas.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GAS METER
G G
EE
E
UNDERGROUND
GAS
UNDERGROUND
ELECTRIC
UNDERGROUND
ELECTRIC
EXISTING
A/C COND.
8' HIGH DECORATIVE
FENCE
EXISTING
ELECTRICAL
TRANSFORMER
W W
EXISTING
CHILLER
6" WATERD
UNDERGROUND
FIBER
PAD
EQUIPMENT
ROOM
BOILER
ROOM
EMERGENCY
GENERATOR
ROOM
MAINTENANCE
OFFICE
109JANITOR'S
CLOSET
TELECOM
CORRIDOR
STAIR
ELEVATOR
LOBBY
8'-6" x 11'-6" x 9 1/2" CONCRETE
PAD W/ #4 @ 10" EACH WAY -
SEE DETAIL J6/A101.
COORDINATE PAD TO EXTEND
6" BEYOND EACH SIDE OF
CHILLER PROVIDED.
SAWCUT AND REMOVE 8'-7" x 8'-7" SECTION
OF EXISTING BITUMINOUS PAVEMENT.
J6 A101
(VERIFY LOCATION)
(VERIFY
LOCATION)
(VERIFY LOCATION)
EXISTING 3/4" CRUSHED
AGGREGATE BASE
COURSE
1/2" PRE-MOLDED JOINT
FILLER AROUND PAD
EXISTING 1 3/4" BITUMINOUS
BINDER COURSE
EXISTING 1 3/4" BITUMINOUS
SURFACE COURSE
6"
9 1/2" (VERIFY)3" CLEAR
#4 @ 10" O/C
EACH WAY
HAND COMPACT
EXISTING BASE COURSE
SAWCUT AND REMOVE 8'-7" x 8'-7" SECTION
OF EXISTING BITUMINOUS PAVEMENT
4,000 PSI AIR-ENTRAINED
CONCRETE PAD
LMoravec23WINN0300A101WF01
FI
R
ST
F
LO
O
R P
LA
N
A N
D D
ET
AI
LS
A101 N
Date:
Revisions:
No.
Sh ee t T itl e:
Description:
Pi ne
S tre et
G re en B ay , W
I 5
0-
2-w w w .b er ne rs sc ho be r.c om
PROJECT
NUMBER
DATE
ISSUED
SHEET
NUMBER
BID DOCUMENT SET
W
IT
TM
A
N A
IR
PO
R T
C O
N
TR
O L
TO
W
ER
C
H
IL
LE
R
U
PG
R A
D E/
R
EP
LA
C
EM
EN
T
23WINN03.00
OCTOBER, 2025
C
4, B
ER
N
ER
S-
SC
H O
BE
R
A
SS
O C
IA
TE
S, IN
C
P O
B
ER
EZ
N
Y R
O A
D
O
SH
K O
SH
W I |
10/21/20251. BID DOCUMENT SET
W
IN
N
EB
AG
O
C O
U N
TY
N
KEY PLAN
NO SCALE
4'0" 2' 8' 12' A101
A3 FIRST FLOOR PLAN
1/4" = 1'-0"
A101
J6 CONCRETE PAD
1/4" = 1'-0"
AREA OF
WORK
2'0" 1' 4' 6'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
116 8"
EXISTING
UNIT HEATER
T HWR
HWS
43 "
12"-UP
122 "
H W
R
EXISTING
BOILER
EXISTING
PUMP (P-1)
C W
R
8"
EXISTING
GLYCOL
FEEDER
43 "
HWR
T
EXISTING
EXHAUST
FAN F-003
CWR
CWS
122 " X=8'-4"
EXPANSION
TANK
AIR SEPARATOR
122 "
EYE WASH
STATION
TCP
V 43 "
CWS/R
3" RACKED
X=6'-0". SUPPORT
C W
S/
RVALVE, DRAIN AND FLEX
AT UNIT CONNECTION
122 "RACKED ON
WALL, X=6'-0"
CONTROL AND
POWER PANEL
NEW CHILLER CH-001 SET ON
CONCRETE PAD. PROVIDE
VIBRATION ISOLATORS
PRESSURE GAUGE
AND VALVES
BRICK/BLOCK
MASONRY WALL
FROM WALL
M
EXISTING GAS
METER/PIPING
TERMINATE
IN TANK
EXISTING
CONDENSING
UNIT
PRECAST
WALL PANEL
SUPPORT PIPING FROM
WALL/ CONCRETE PAD
STRAINER ON
INLET PIPE
FIRE DEPARTMENT
CONNECTION (4' CLEARANCE)
EXISTING
ELECTRICAL
TRANSFORMER
TRANSFORMER CLEARANCE
EXISTING CHILLER
PAD TO REMAIN
116 8"
EXISTING
UNIT HEATER
T HWR
HWS
43 "
12"-UP
122 "
H W
R
EXISTING
BOILER
EXISTING
PUMP (P-1)
C W
R
8"
EXISTING
GLYCOL
FEEDER
43 "
T
EXISTING
EXHAUST
FAN F-003
REMOVE EXISTING
CHILLER (CH-1)
CWR
CWS
122 " X=8'-4"
EXPANSION
TANK
AIR SEPARATOR
REMOVE EXISTING
HEAT EXCHANGER
3HP PUMP
EXP. TANK
122 "
(P-2)
A
EYE WASH
STATION
TCP
M
EXISTING GAS
METER/PIPING
EXISTING
CONDENSING
UNIT
B
TRANSFORMER
TRANSFORMER CLEARANCE
340 CFM
T
C W
S C
W R
H W
S H
W R
EXISTING
AHU-001
2" D1 "14
1 "14
D
43 "
EXISTING
FANCOIL
UNIT
INSTALL BALL VALVE
IN BYPASS LOOP
INSTALL BALL VALVE
IN TCV BYPASS PIPE
PIPE INSULATION
(SEE SPECS)
USE HIGH DENSITY
INSULATION
CHILLED WATER PIPE
U-BOLT
EXISTING 14" MASONRY
CAVITY WALL
EXISTING 14" PRECAST
CONCRETE WALL
3 1/2"
8"
8"
UNISTRUT A1063 FLAT
PLATE FITTING TYP.
PROVIDE (3) 3/8" DIA. STAINLESS STEEL
THREADED ROD ANCHORS W/ 3 1/2"
MINIMUM EMBEDMENT IN DEWALT AC100+
GOLD VINYLSETER ADHESIVE AT
PRECAST WALL CONDITION
1 1/4" PRE-GALVANIZED A1000
UNISTRUT x 30" LONG
PROVIDE (3) 3/8" DIA. STAINLESS STEEL
THREADED ROD ANCHORS INCLUDING
STAINLESS STEEL SCREEN TUBES W/
8" EMBEDMENT IN DEWALT AC100+
GOLF VINYLESTER ADHESIVE AT
MASONRY CAVITY WALL CONDITION.
PIPE INSULATION
(SEE SPECS)
USE HIGH DENSITY
INSULATION
CHILLED WATER PIPE
U-BOLT
LMoravec23WINN0300M101WF01
FI
R
ST
F
LO
O
R P
LA
N
S, S
C H
ED
U
LE
S
AN
D
D
ET
AI
LS
M101 N
Date:
Revisions:
No.
Sh ee t T itl e:
Description:
Pi ne
S tre et
G re en B ay , W
I 5
0-
2-w w w .b er ne rs sc ho be r.c om
PROJECT
NUMBER
DATE
ISSUED
SHEET
NUMBER
BID DOCUMENT SET
W
IT
TM
A
N A
IR
PO
R T
C O
N
TR
O L
TO
W
ER
C
H
IL
LE
R
U
PG
R A
D E/
R
EP
LA
C
EM
EN
T
23WINN03.00
OCTOBER, 2025
C
4, B
ER
N
ER
S-
SC
H O
BE
R
A
SS
O C
IA
TE
S, IN
C
P O
B
ER
EZ
N
Y R
O A
D
O
SH
K O
SH
W I |
10/21/20251. BID DOCUMENT SET
W
IN
N
EB
AG
O
C O
U N
TY
N
KEY PLAN
NO SCALE
M101
A6 FIRST FLOOR PLAN - NEW WORK
1/4" = 1'-0" 4'0" 2' 8' 12'
N
4'0" 2' 8' 12' M101
F6 FIRST FLOOR PLAN - DEMOLITION
1/4" = 1'-0"
- CUT EXISTING WALLS FOR NEW WORK. PATCHING OFWALL BY
THIS TRADE.
- PROVIDE ADDITIONAL OFFSETS IN NEW WORK AS REQUIRED FOR
EXISTING CONDITIONS AND COORDINATED INSTALLATIONS.
- REFILL SYSTEM WITH 40% PROPYLENE GLYCOL MIX.
- PROVIDE ADDITIONAL FOR NEW SYSTEM EXTENSION. MATCH EXISTING
FLUID.
NEW CONNECTION TO EXISTING PIPING.
PROVIDE NEW CONNECTION AT BUILDING EXTERIOR AND ROUTE
PIPES VERTICALLY UP AND INCREASE TO 3". PROVIDE (2) 3" VALVED
AND CAPPED PIPE STUBS FOR FUTURE OR TEMPORARY CHILLER
CONNECTION AT X=2'-0". INSULATE VALVES AND PIPE STUBS.
PROVIDE NEW EXPANDED BAS PANEL AND POINTS TO NEW CHILLER.
COORDINATE MOUNTING ABOVE FIRE DEPARTMENT CONNECTIONS
AND AROUND OTHER WALL PENETRATIONS.
VALVED BYPASS (NORMALLY CLOSED) FOR FLUSH/CIRCULATION
PRIOR TO OPERATION OF CHILLER.
COORDINATE CHILLER ORIENTATION & PIPE CONNECTIONS FOR
CHILLER PROVIDED. INSTALL ALL ACCESSORIES, FLOW SWITCH, ETC.
REQUIRED BY MANUFACTURER OR FURNISHED WITH CHILLER.
(THIS SHEET ONLY)
PLAN KEYED NOTES
A REMOVE RELIEF PIPE TO ALLOW RECONFIGURATION TO GLYCOL
FEEDER TANK.
REMOVE CHILLER PACKAGE AND PIPING OUTSIDE OF THE
BUILDING.
- REMOVE ALL DUCTS, PIPING, AND EQUIPMENT NOTED AND/OR
SHOWN DASHED.
- THIS TRADE SHALL PATCH WALL OPENINGS REMAINING AFTER
DEMOLITION TO MATCH ADJACENT SURFACES.
- DRAIN APPROXIMATELY 145 GALLONS OF 40% PROPYLENE GLYCOL
MIX AND SALVAGE FOR REUSE.
(THIS SHEET ONLY)
PLAN KEYED NOTES
AREA OF
WORK
M101
A1 JUNCTION LEVEL FLOOR PLAN - NEW WORK
1/4" = 1'-0"
N
4'0" 2' 8' 12'
B
TAG LOCATION REFRIGERANT
DESIGN
CAPACITY
(TONS)
# COMPRESSORS, #
CIRCUITS EER/IPLV
EVAPORATOR CONDENSER ELECTRICAL MAXIMUM
ASSEMBLED
DIMENSIONS
(LxWxH)
REMARKSGPM
(DESIGN) FLUID EWT
(°F) LWT (°F) MAX. PDF
(FT)
FOULING
FACTOR (HR
SQ/FT F/BTU)
AMBIENT FAN DIAMETER MIN.
AMBIENT MOCP MCA KW VOLT PH STARTER
TYPE
CH-001 EXTERIOR R-32 28 4 SCROLL - 2 11.0/19.2 75 40%
PROPYLENE 54 44 14 0.0001 95°F 2 32 0°F 175 161 31.0 208 3 ACROSS LINE 128x99x88 3700 LBS, 88dbA, 4 COMPRESSORS, SINGLE
POINT DISCONNECT SWITCH
NOTES:
1. PROVIDE DUAL PUMP PACKAGE (5 HP EACH) WITH CHILLER. 75 GPM AT 75 FEET WPD PUMP SELECTION.
AIR COOLED WATER CHILLER SCHEDULE
M101
F1 PIPE HANGER
NO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text D
CH-001
EQUIPMENT
ROOM
BOILER
ROOM
EMERGENCY
GENERATOR
ROOM
109JANITOR'S
CLOSET
STAIR
EX. EMERGENCY
GENERATOR
A MDP
B
1 3
EX. UTILITY SERVICE
TRANSFORMER
GF/RT
RUN CONDUIT AND PULL BOX
ALONG BUILDING ABOVE COLD
WATER SUPPLY AND RETURN
PIPING. COORDINATE WITH HVAC
CONTRACTOR.
A-391
LB
J
CONTROL PANEL WITH
INTEGRAL DISCONNECT
TCP
(EX)
(EX) (EX)
(EX)
2 TURN
DOWN
2 4
PROVIDE NEW NEMA 3R PULL
BOX (SIZE AS REQUIRED)
EX
CH-001
EQUIPMENT
ROOM
BOILER
ROOM
EMERGENCY
GENERATOR
ROOM
109JANITOR'S
CLOSET
STAIR
EX. EMERGENCY
GENERATOR
A MDP
B
B
EXISTING DISCONNECT TO REMAIN
B
A
EX EQUIPMENT
TO REMAIN
EX. UTILITY SERVICE
TRANSFORMER
TCP
(EX)
(EX) (EX)
C
B
A
(EX)
aburnett23WINN0300E101WF01
FI
R
ST
F
LO
O
R P
LA
N
S
E101 N
Date:
Revisions:
No.
Sh ee t T itl e:
Description:
Pi ne
S tre et
G re en B ay , W
I 5
0-
2-w w w .b er ne rs sc ho be r.c om
PROJECT
NUMBER
DATE
ISSUED
SHEET
NUMBER
BID DOCUMENT SET
W
IT
TM
A
N A
IR
PO
R T
C O
N
TR
O L
TO
W
ER
C
H
IL
LE
R
U
PG
R A
D E/
R
EP
LA
C
EM
EN
T
23WINN03.00
OCTOBER, 2025
C
4, B
ER
N
ER
S-
SC
H O
BE
R
A
SS
O C
IA
TE
S, IN
C
P O
B
ER
EZ
N
Y R
O A
D
O
SH
K O
SH
W I |
10/21/20251. BID DOCUMENT SET
W
IN
N
EB
AG
O
C O
U N
TY
N
KEY PLAN
NO SCALE
2'0" 1' 4' 6'
N
2'0" 1' 4' 6'
AREA OF
WORK
(THIS SHEET ONLY)
DEMOLITION PLAN KEYED NOTES
A
B
REMOVE CONNECTIONS TO EXISTING CHILLER COMPLETE. REMOVE
POWER CIRCUITS BACK TO EXISTING MDP. ALL CIRCUITS TO REMAIN
ACTIVE UNTIL NEW CHILLER IS UP AND RUNNING CUT OFF CONDUITS
4" ABOVE GRADE OR AWAY FROM BUILDING AND CAP.
EXISTING 200A FUSED DISCONNECT AND 200A FEEDER (3 #3/0, 1 #6
GND IN 2" C) TO REMAIN. EXISTING 200A BREAKER IN MDP TO REMAIN.
RELABEL BREAKER AS "CHILLER" AT END OF PROJECT.
EXISTING 3P/175A SERVING EXISTING CHILLER TO BE MARKED AS
"SPARE" AT END OF PROJECT AFTER DISCONNECTION AND REMOVAL
OF, EXISTING FEEDER.
DEMOLITION NOTES
1. ALL ELECTRICAL EQUIPMENT/FIXTURES AND DEVICES SHOWN
DASHED ON THE DEMOLITION PLAN ARE INTENDED TO BE
DISCONNECTED AND REMOVED UNLESS NOTED OTHERWISE.
ELECTRICAL ITEMS REMOVED AND NOT RELOCATED REMAIN THE
PROPERTY OF THE OWNER. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE DISPOSAL OF ANY MATERIAL THE OWNER
DOES NOT WANT TO REUSE OR RETAIN.
2. THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK
REQUIRED AND DO NOT INDICATE EVERY J-BOX, CONDUIT, OR WIRE
THAT MUST BE REMOVED. THE CONTRACTOR SHALL VISIT THE SITE
TO DETERMINE THE SCOPE OF DEMOLITION NECESSARY TO
ACCOMMODATE THE ELECTRICAL WORK. REFER TO SPECS FOR
ADDITIONAL REQUIREMENTS.
3. GC SHALL REMOVE AND REPLACE ALL CEILING TILES AS REQUIRED
FOR FOR THE EXECUTION OF ELECTRICAL WORK OUTSIDE THE
LIMITS OF CONSTRUCTION. DAMAGED TILES SHALL BE REPLACED BY
THE GC WITH IDENTICAL MATERIAL.
(THIS SHEET ONLY)
NEW WORK PLAN KEYED NOTES
UTILIZE SPARE 20A/1P BREAKER WITHIN PANEL "A" TO FEED THE NEW
RECEPTACLE VIA 2 - #12 AND #12 GROUND IN 3/4" CONDUIT.
UTILIZE EMT CONDUIT INSIDE THE BUILDING, H.W.R. ON THE
EXTERIOR FACE OF THE BUILDING AND PVC UNDERGROUND.
REFERENCE THE EXISTING PANEL SCHEDULE AND MOTOR SCHEDULE
ON SHEET E601.
PROVIDE A 3/4" CONDUIT FROM CONTROL PANEL TO TCP IN ROOM 111
FOR USE BY MECHANICAL CONTRACTOR. (EMPTY).
EXTEND 3# 2/0, 1 #6 GND IN 2" C TO NEW CHILLER. PROVIDE NEW 175A
CLASS RK5 TYPE TR FUSES IN EXISTING DISCONNECT.
E101
D4 FIRST FLOOR DEMOLITION PLAN
1/4" = 1'-0"
E101
A4 FIRST FLOOR NEW WORK PLAN
1/4" = 1'-0"
C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text D
Date:
Revisions:
No.
Sh ee t T itl e:
Description:
Pi ne
S tre et
G re en B ay , W
I 5
0-
2-w w w .b er ne rs sc ho be r.c om
PROJECT
NUMBER
DATE
ISSUED
SHEET
NUMBER
BID DOCUMENT SET
W
IT
TM
A
N A
IR
PO
R T
C O
N
TR
O L
TO
W
ER
C
H
IL
LE
R
U
PG
R A
D E/
R
EP
LA
C
EM
EN
T
23WINN03.00
OCTOBER, 2025
C
4, B
ER
N
ER
S-
SC
H O
BE
R
A
SS
O C
IA
TE
S, IN
C
P O
B
ER
EZ
N
Y R
O A
D
O
SH
K O
SH
W I |
10/21/20251. BID DOCUMENT SET
W
IN
N
EB
AG
O
C O
U N
TY
aburnett23WINN0300E601WLS
LE
G
EN
D
S
AN
D S
C H
ED
U
LE
S
E601
A AMPER(S)
A/C AIR CONDITIONING UNIT
ADA AMERICANS WITH DISABILITIES ACT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC ANTICIPATED INTERRUPTING CURRENT
ALT ALTERNATE
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BW BLANKET WARMER
C CONDUIT
CAPS CARD ACCESS POWER SUPPLY
CATV CABLE ANTENNA TELEVISION
CB CIRCUIT BREAKER
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CT CURRENT TRANSFORMER
DIST DISTRIBUTION
DO DOOR OPERATOR
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EX EXISTING
FA FIRE ALARM
FDR FEEDER
FLA FULL LOAD AMPS
FPC FIRE PROTECTION CONTRACTOR
FSC FOOD SERVICE CONTRACTOR
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI,GF GROUND FAULT INTERRUPTER
GND GROUND
HID HIGH INTENSITY DISCHARGE
HP HORSE POWER
HVAC HEATING, VENTILATING, A/C CONTRACTOR
HWR HEAVY WALL RIGID CONDUIT
IMC INTERMEDIATE METALLIC CONDUIT
J-BOX JUNCTION BOX
KEC KITCHEN EQUIPMENT CONTRACTOR
KV KILOVOLTS
KVA KILOVOLT AMPERE(S)
KW KILOWATT(S)
LCP LIGHTING CONTROL PANEL
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MIL(S)
MDP MAIN DISTRIBUTION PANEL
MGAP MEDICAL GAS ALARM PANEL
MLO MAIN LUG ONLY
MTS MANUAL TRANSFER SWITCH
NAP NITROGEN ALARM PANEL
N.E.C. NATIONAL ELECTRIC CODE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OH OVERHEAD
PLGC PLUMBING CONTRACTOR
PNL PANEL
PRESS PRESSURE MONITOR
PRI PRIMARY
PTZ PAN, TILT, ZOOM
PVC POLYVINYL CHLORIDE
(R) ROOF
REC RECEPTACLE
RT RAIN TIGHT
SCP SUMP PUMP CONTROL PANEL
SHPS SECURITY HARDWARE POWER SUPPLY
SPC SPECIAL PURPOSE CONNECTION
SWBD SWITCHBOARD
TC TIME CLOCK
TCC TEMPERATURE CONTROL CONTRACTOR
TCP TEMPERATURE CONTROL PANEL
TCPS TEMPERATURE CONTROL POWER SUPPLY
TELE TELEPHONE
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UC UNDERCABINET
UG UNDERGROUND
UH UNIT HEATER
U.N.O. UNLESS NOTED OTHERWISE
UPS UNINTERRUPTED POWER SYSTEM
V VOLT(S)
VFD VARIABLE FREQUENCY DRIVE
W WATT(S)
WP WEATHERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
NOTE:
THIS COMPRISES A COMPLETE LIST OF ITEMS. NOT ALL
ABBREVIATIONS MAY NECESSARILY BE REPRESENTED ON THIS
PROJECT.
DESCRIPTION (MOUNTING)SYMBOL
ELECTRICAL SYMBOLS LEGEND
DESCRIPTION (MOUNTING)SYMBOL DESCRIPTION (MOUNTING)SYMBOL
SURFACE CEILING FIXTURE - 2X4, 2X2, 1X4
RECESSED CEILING FIXTURE - 2X4, 2X2, 1X4
SURFACE/PENDANT FIXTURE
EMERGENCY BATTERY PACK (WALL, CEILING)
EXIT SIGN - SINGLE FACE (CEILING, WALL)
WALL MOUNTED FIXTURE
LIGHTING FIXTURES
FIXTURE CONNECTED TO EMERGENCY LIFE SAFETY BRANCH POWER
TRACK LIGHTING
UNDERCABINET LIGHT/NARROW STRIP LIGHT
WALL WASH DOWN LIGHT FIXTURE (ROUND, SQUARE)
RT
SINGLE RECPT. ( NORMAL, EMERG.) - STANDARD HEIGHT
WIRING DEVICES
GF
DUPLEX RECEPT. W/ GROUND FAULT
DOUBLE DUPLEX RECEPT. (NORMAL, EMERG.) - STANDARD HEIGHT
SPECIAL PURPOSE CONNECTION
DUPLEX RECEPT. W/ RAIN TIGHT COVER
POWER EQUIPMENT
PANELBOARD (EXISTING, NEW)
DISCONNECT SWITCH - FUSED, NON-FUSED
ELECTRIC MOTOR
MANUAL STARTER
COMBINATION MAGNETIC STARTER/DISCONNECT
TRANSFORMER
POWER METER OR TRANSOCKET
TRANSFER SWITCH - AUTOMATIC/MANUAL (ATS/MTS)
MAGNETIC STARTER
RELAY CONTACTOR
OUTDOOR UTILITY POLE
DIGITAL TIMER SWITCH
MS
VARIABLE FREQUENCY DRIVE
PULL BOX
JUNCTION BOX WITH BLANK COVER
CONDUIT SLEEVES THRU WALL ABOVE ACCESSIBLE CEILING
RACEWAYS
BUSWAY
CONDUIT STUBBED OR CAPPED
UNDERGROUND/UNDER SLAB CONDUIT
COMBINATION POWER/COMMUNICATION POLE
CABLE TRAY
M
COMMUNICATIONS EQUIPMENT
DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) - ABOVE COUNTER
DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) - STANDARD HEIGHT
W
INTERCOM (MASTER)
WIRELESS DATA ACCESS POINT / WIFI (CEILING, WALL)
I
#X
DATA/VOICE RACK
CATV OUTLET (WALL, CEILING) TV TV
FIRE ALARM AND DETECTOR DEVICES
MANUAL PULL STATION
STROBE ONLY
SMOKE DETECTOR
DOOR HOLD OPEN
DUCT SMOKE DETECTOR (##)
SMOKE DETECTOR FOR ELEVATOR CONTROL
HEAT/THERMAL DETECTOR
REMOTE TEST SWITCH W/ INDICATOR (WALL, CEILING)
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
S
H
S
HORN ONLY
SPEAKER ONLY
H #
S #
HORN/STROBE
SPEAKER/STROBE
S
S
HORN LOUDSPEAKER
# CEILING MOUNTED SPEAKER/STROBE
CEILING SPEAKER, RECESSED
S
SER
H
DS
DH
RT
FACP
FAAP
AREA OF RESCUE ASSISTANCE/REFUGE
NOTES:
(1)
(5)
(6)
THIS COMPRISES A COMPLETE LIST OF ITEMS. NOT ALL SYMBOLS MAY NECESSARILY BE REPRESENTED ON THIS PROJECT.*
(3)
(4)
(2)
L
RK
CATV OUTLET W/ PILLOW SPEAKER CONTROL JACK (WALL, CEILING) TV TVN N
EXTERIOR TELEPHONE PEDESTALTP
ABOVE GRADE/CONCEALED ABOVE CEILING CONDUIT
FIXTURE CONNECTED TO EMERGENCY AND NORMAL POWER
FIXTURE CONNECTED TO EMERG. CRITICAL/EQUIP. BRANCH POWER
SOLID STATE, REDUCED VOLTAGE STARTERSS
1" CONDUIT STUBBED UP TO ACCESSIBLE SPACE ABOVE CEILING FROM 4" SQUARE JUNCTION BOX W/ SINGLE GANG DEVICE RING. ALL CONDUIT STUBS SHALL BE TERMINATED W/ BUSHINGS.
FIXTURE TYPE: SEE LIGHT FIXTURE SCHEDULE (LOCATION AROUND SYMBOL MAY VARY)
CIRCUIT NUMBER: SEE PLAN FOR PANEL BEING USED. (LOCATION AROUND SYMBOL MAY VARY)
NOT USED.
RECEPTACLE CIRCUIT NUMBER: SEE PLAN FOR PANEL BEING USED. (LOCATION AROUND SYMBOL MAY VARY)
DEVICE HEIGHT (ONLY USED FOR SPECIAL HEIGHT REQUIREMENTS)
#X - INDICATES QUANTITY AND TYPE OF DROPS:
2D 2V/2D
TYPE OF DROPS: COMBINATION VOICE/DATA
D = DATA
V = VOICE
QUANTITY OF DROPS
REFERENCE THE SCHEDULE ON THIS SHEET.
RT
2U DUPLEX RECEPT. W/ TWO USB PORTS
T
SINGLE RECPT. ( FLOOR, CEILING)
DUPLEX RECEPT. ( NORMAL, EMERG.) - STANDARD HEIGHT
POWER SUPPLY - WALL,CEILINGPS
DUPLEX RECEPT. ( NORMAL, EMERG.) - AC OR HIGH MT.
DUPLEX RECEPT. (FLOOR, CEILING)
DOUBLE DUPLEX RECEPT. ( NORMAL, EMERG.) - AC OR HIGH MT.
DOUBLE DUPLEX RECEPT. (FLOOR, CEILING)
4U
FOUR PORT USB DEVICE
DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) (FLOOR, CEILING)
WALL TELEPHONE [VOICE/DATA] OUTLET
M MONITOR DATA OUTLET - STANDARD HEIGHT
M MONITOR DATA OUTLET - ABOVE COUNTER
ECB-XX ECB-XX ENCLOSED CIRCUIT BREAKER {ECB} (EXISTING, NEW)
GAP GAP GENERATOR ANNUNCIATOR PANEL {GAP} (EXISTING, NEW)
ATSA ATSA ATS ANNUNCIATOR PANEL {ATSA} (EXISTING, NEW)
A LIGHTNING PROTECTION AIR TERMINAL
L LIGHTNING PROTECTION CABLE
FIRE SPRINKLER BELLF
PS
DESCRIPTION (MOUNTING)SYMBOL
RK WALL MOUNTED DATA/VOICE CABINET
C CHIME ONLY
#X #X
#X
CONDUIT RISING UP
CONDUIT DROPPING DOWN
DUPLEX RECEPT. AND 4-PORT USB DEVICE IN COMMON BOX
H # CEILING MOUNTED HORN/STROBE
RECESSED CEILING FIXTURE WITH CENTER ELEMENT - 2X4, 2X2, 1X4 S # CEILING MOUNTED STROBE
CEILING FAN SPEED SWITCHFLIM LINE ISOLATION MONITOR (REMOTE)
RECESSED LINEAR / RECESSED CONTINUOUS LINEAR FIXTURE
K2K K3 K4
PUSHBUTTON SWITCH/PUSH PAD
SWITCH W/ PILOT LIGHT
SWITCH & DUPLEX RECPT. MOUNTED IN COMMON BOX
WALL BOX DIMMER SWITCH
SEPARATELY SWITCHED BALLASTS (DUAL-LEVEL)
SWITCH - 1, 2 POLE; 3, 4 WAY
D
P
2 3 4
KEY SWITCH - 1, 2 POLE; 3, 4 WAY
DIMMER SYSTEM COMPONENT
LOW VOLTAGE SWITCH/RELAY CONTROL SWITCH
D
PUSHBUTTON SWITCH (2-BUTTON, 3-BUTTON)
EMERGENCY STOP PUSHBUTTONE
LIGHT SENSOR
PHOTOCELL
TIME CLOCK
LS
PC
TC
LOW VOLTAGE SWITCHING RELAY PANEL
XX
DIRECTIONAL OCCUPANCY SENSOR, CEILINGXX
XX DIRECTIONAL OCCUPANCY SENSOR,WALL MOUNT
OS XX 360 DEGREE OCCUPANCY SENSOR, CEILING
AUTOMATIC LIGHTING CONTROLS
OCCUPANCY SENSOR,WALL SWITCH
RECESSED DOWN LIGHT FIXTURE (ROUND, SQUARE)
SCONCE/WALL MOUNT FIXTURE
EXIT SIGN - DOUBLE FACE (CEILING, WALL)
CELL PHONE SIGNAL BOOST
FOOT SWITCH (LIGHTING CONTROL)FT
XX
GF
(2)
J JUNCTION BOX
LV
CEILING MOUNT LIGHT FIXTURE, AOR ENTRY SIGNAGE
WALL MOUNT LIGHT FIXTURE, AOR ENTRY SIGNAGE
RA RA
RA RA
SURFACE MOUNTED CONDUIT
WAVE TO OPENW
INTERCOMI
CT CURRENT TRANSFORMER CABINET
WARNING LIGHT - SINGLE FACE (CEILING, WALL)
COMBO SINGLE FACE EXIT SIGN AND EMERGENCY LIGHT (CEILING, WALL)
F UNDERGROUND FIBER
SR DUPLEX RECEPT. W/ SAFETY TYPE (TAMPER-RESISTANT)
NAC NAC POWER SIGNAL BOOSTER POWER SUPPLY
FIRE ALARM TRANSPONDER PANEL FATP
DEVICE MOUNTING HEIGHT LEGEND
DESCRIPTION MOUNTING HEIGHT
LEGEND NOTES:
LIGHT SWITCH
PUSHBUTTON SWITCH
BLANK BOX
45 5/8" CENTERED AFF.
42" CENTERED AFF.
PUSHBUTTON (EMERGENCY STOP) 48" CENTERED AFF.
RECEPTACLES - STANDARD HEIGHT 18" CENTERED AFF. OR AS NOTED ON PLAN
18" CENTERED AFF. OR AS NOTED ON PLAN
18" CENTERED AFF.DATA/VOICE OUTLET - STANDARD HEIGHT
WALL TELEPHONE 45 5/8" CENTERED AFF.
INTERCOM 45 5/8" CENTERED AFF.
CATV OUTLET 18" CENTERED AFF OR AS NOTED ON PLAN
FIRE ALARM PULL STATION 45 5/8" CENTERED AFF.
FIRE ALARM AUDIO/VISUAL DEVICES
FIRE ALARM VISUAL DEVICES
80" AFF TO BOTTOM OF LENS
80" AFF TO BOTTOM OF LENS
SPEAKER (WALL MOUNTED)
VOLUME CONTROL
MICROPHONE JACK
DIGITAL CLOCK
CLOCK/SPEAKER
WALL CLOCK
CARD READER
80" AFF TO BOTTOM OF DEVICE.
45 5/8" CENTERED AFF.
18" CENTERED AFF. OR AS NOTED ON PLAN
CENTERED 16" TO 8" BELOW CEILING.
CENTERED 18" TO 9" BELOW CEILING.
CENTERED 18" TO 9" BELOW CEILING.
45 5/8" CENTERED AFF.
NURSE CALL DOME LIGHT CENTERED ABOVE DOOR.
NURSE CALL (EM) PULL STATION (TOILET) 48" AFF WITH CORD 6" AFF.
(SHOWER) 84" AFF WITH CORD 6" AFF.
NURSE CALL CODE BLUE 54" CENTERED AFF.
NURSE CALL DUTY STATION 54" CENTERED AFF.
NURSE CALL CALL CORD 54" CENTERED AFF.
NURSE CALL MASTER STATION AT DESK, EXACT LOCATION TO BE FIELD
VERIFIED.
MONITOR DATA OUTLET 18" CENTERED AFF OR AS NOTED ON PLAN
CATV OUTLET W/ PILLOW SPKR CTRL JACK 18" CENTERED AFF OR AS NOTED ON PLAN
OCCUPANCY SENSOR WALL SWITCH 45 5/8" CENTERED AFF.
FAN SPEED SWITCH 45 5/8" CENTERED AFF.
FIRE ALARM REMOTE TEST SWITCH 48" CENTERED AFF.
NURSE CALL STANDARD STATION 54" CENTERED AFF.
NURSE CALL GRAPHICAL STATION 54" CENTERED AFF.
PA HORN WALL SPEAKER 80" AFF TO BOTTOM OF DEVICE. OR AS
NOTED OTHERWISE
RESCUE ASSISTANCE CALL STATION 45 5/8" CENTERED AFF.
6" CENTERED ABOVE COUNTER.
4" CENTERED ABOVE BACKSPLASH.
RECEPTACLES - ABOVE COUNTER
45 5/8" AFF MOUNTED ASIDE OF SINKS;
COORDINATE WITH MIRROR LOCATION.
OR AS NOTED ON PLAN
RECEPTACLES - HIGH MOUNT
DATA/VOICE OUTLET - ABOVE COUNTER 6" CENTERED ABOVE COUNTER.
4" CENTERED ABOVE BACKSPLASH.
1. THE ABOVE LIST OF MOUNTING HEIGHTS SHALL BE USED FOR
INSTALLATION OF DEVICES UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
2. EXACT MOUNTING HEIGHTS OF DEVICES MAY BE SLIGHTLY ADJUSTED IN
THE FIELD TO ACCOMMODATE BLOCK COURSES AND UNIFORMITY OF
THE WALL. REFERENCE DEVICE MOUNTING DETAIL ---/E500.
3. THE ABOVE ITEMS COMPRISE A COMPLETE LIST AND NOT ALL ITEMS
MAY BE APPLICABLE TO THIS PROJECT.
MOTOR SCHEDULE
NO. SERVING HP VOLTS PHASE
LOAD
LOCATION PANEL CKT BREAKER
WIRE
CONDUIT
SIZE
STARTER DISCONNECT
NOTES
KW FLA MCA NO. SIZE GND TYPE ENCLOS.
(NEMA) BY MOUNT SIZE FUSE
SIZE
ENCLOS.
(NEMA) BY MOUNT
1 CHILLER (CH-001) - 208 3 33.3 - 163 EXTERIOR MDP 200A/3P 3 #2/0 #6 2" MAG 3R ES WU 200A - IWS ES OU 1,2,3,4
ABBREVIATIONS:
COMB - COMBINATION STARTER/FUSED DISCONNECT
MAG - MAGNETIC STARTER
MAN - MANUAL STARTER
VFD - VARIABLE FREQUENCY DRIVE
TS - TOGGLE SWITCH/HORSE POWER RATED SWITCH
IWS - INTEGRAL WITH STARTER
SS - SOLID STATE; REDUCED VOLTAGE STARTER
NU - NEAR UNIT
OU - ON UNIT
WU - WITH UNIT
EC - ELECTRICAL CONTRACTOR
ES - EQUIPMENT SUPPLIER
HVAC - HEATING/VENTILATING CONTRACTOR
PLGC - PLUMBING CONTRACTOR
EX - EXISTING
NOTES:
1. REUSE EXISTING BREAKER IN EXISTING MDP PANEL INDICATED TO FEED NEW CHILLER. UPDATE THE PANEL DIRECTORY.
2. COORDINATE WITH HVAC TRADE FOR ELECTRICAL REQUIREMENTS.
3. WIRE DIRECT TO CONTROL PANEL/DISCONNECT ON UNIT.
4. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT SIZE OF FUSES FOR CHILLER. ASSUMED MAX OCPD IS 175A. IF LOWER AMPERAGE FUSES ARE REQUIRED, ELECTRICAL CONTRACTOR TO PROVIDE. (NO COST TO PROJECT FOR SMALLER FUSES AMPERAGE).
EXISTING PANEL SCHEDULE
PANEL
DESIGNATION MANUFACTURER LOCATION TYPE BUS
AMPS MCB MLO VOLTAGE
RATING
PHASE /
WIRE
TUBS
RATING
(A.I.C.)
CIRCUIT BREAKERS
NOTES
NO. CKT.
TOTAL
BREAKER
SPACE
MOUNT QTY. AMP POLE TYPE
EX
MDP
SQUARE D
TYPE HCN 110 PP 600 X - 208/120 3-PHASE
4-WIRE 1 - - SURFACE 25K 1 200A 3P TM 2
EX
A
SQUARE D
TYPE NQOD 110 P 225 - X 208/120 3-PHASE
4-WIRE 2 42 - SURFACE 10K 1 20A 1P TM 1
ABBREVIATIONS:
ECB - ENCLOSED CIRCUIT BREAKER
FTL - FEED THRU LUGS
GFCI - GROUND FAULT CIRCUIT INTERRUPTING
L - LOAD CENTER
MCC - MOTOR CONTROL CENTER
P - PANELBOARD
PP - POWER PANEL
SFL - SUB FEED LUGS (KIT)
ST - SHUNT-TRIP
SP - SPARE BREAKER
SWBD - SWITCHBOARD
TM - THERMAL MAGNETIC
USS - UNIT SUB-STATION
NOTES:
1. PROVIDE NEW BOLT-ON BREAKER(S) FOR EXISTING PANEL. THEY SHALL BE THE SAME TYPE AND HAVE AN AIC RATING WHICH MATCHES THE EXISTING BREAKERS. UPDATE THE PANEL DIRECTORY.
2. REUSE QD 200A/3P. (SQUARE D #QDA32200-25KAIC)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text L
AutoCAD SHX Text K
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text S
S
| T001 TITLE SHEET |
| A101 FIRST FLOOR PLAN AND DETAILS |
| A101 FIRST FLOOR PLAN AND DETAILS |
| X23WINN0300AWF01 |
| X1001 CONCRETE PAD |
| M101 FIRST FLOOR PLANS, SCHEDULES AND DETAILS |
| M101 FIRST FLOOR PLANS, SCHEDULES AND DETAILS |
| X23WINN0300HWF01 |
| X23WINN0300HWF01(2) |
| X23WINN0300HWFJL |
| X0003 PIPE HANGER |
| E101 FIRST FLOOR PLANS |
| E101 FIRST FLOOR PLANS |
| X23WINN0300HWF01 |
| X23WINN0300HWF01(2) |
| E601 LEGENDS AND SCHEDULES |
| E601 LEGENDS AND SCHEDULES |