2027-07 Addendum 1.pdf
PDF 1 MB Posted
- Attached to
- HVAC Upgrades - DPW Garage
- Solicitation number
- BID 2027-07
- Issued by
- Fairfield County, Connecticut
About this file
This addendum to ITB 2027-07 modifies contract documents for HVAC system upgrades at the Town of Stratford Department of Public Works Garage located at 550 Patterson Avenue, Stratford, Connecticut. The project scope includes removal of the existing steam boiler and associated heating system; installation of new gas-fired rooftop makeup air units with associated gas piping; installation of new infrared heating units with associated gas piping; new electrical work for the heating system replacement; and roof framing modifications to support the new rooftop HVAC units. An alternate bid item covers removal of an existing underground oil tank. The pre-bid walk-through was held September 2, 2026 at 10:00 a.m., with bid opening scheduled for September 18, 2026 at 10:00 a.m. The project award is anticipated on or about October 16, 2026, with construction mobilization beginning December 1, 2026 and substantial completion targeted for January 29, 2027. Final contract close-out is required by February 26, 2027.
Addendum #1, issued September 3, 2026, includes revisions to the bid form to incorporate tank removal unit costs, an updated milestone schedule, and an asbestos testing report and abatement specification. Asbestos testing conducted in April 2020 identified asbestos-containing materials in the boiler packing (approximately 150 square feet), boiler gaskets (approximately 5 square feet), and boiler masonry. Connecticut regulations require that any work disturbing asbestos-containing materials be performed by a licensed asbestos abatement contractor. The bid form requires contractors to include a $10,000 allowance for unforeseen conditions, with unused portions credited back to the owner. Contractors must also provide unit pricing for removal of contaminated soil and soil testing. The existing roof is a built-up roof system under warranty by W.P. Hickman Systems, Inc., and any roofing subcontractor must maintain appropriate certifications. Connecticut Temperature Controls (CTC) serves as the town's controls vendor. State of Connecticut prevailing wages are required if the total bid exceeds $100,000.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
9/3/2026
Addendum 1 1 of 2
ADDENDUM #1
HVAC Upgrades:
DPW Maintenance Garage
550 Patterson Ave.
Stratford, CT 06614
TOWN PROJECT NUMBER: 2027-07
ISSUED: 9/3/2026
PROJECT TEAM
Architect / Project Manager Mechanical Engineer
Addendum 1 2 of 2
The work shall be carried out in accordance with the following supplemental instructions and in accordance with the Contract Documents.
PROJECT MANUAL CHANGES
1. Bid Form
• Bid Form revised to include Tank Removal related Unit Costs. See attached.
2. 01009 – Milestone Schedule
• Revised. See attached.
3. Asbestos Testing Report and Abatement/Removal Specification
• The existing boiler contains asbestos.
• See attached testing report and abatement specification.
MISCELLANEOUS CHANGES / CLARIFICATIONS
1. Requests For Information (RFI) Log
• See attached RFI Log.
2. HVAC Controls / Sequence of Operation
• See attached.
*** END OF ADDENDUM #1 ***
Bid Form
BID FORM
Bids must be submitted to the Town of Stratford Purchasing Office, attention Phillip Ryan, Purchasing Agent, on the following form signed by an authorized company officer. Bids will be opened on Friday, September 18, 2026, 10:00am.
Phillip Ryan, Purchasing Agent Town of Stratford 2725 Main Street Stratford, CT 06615
HVAC Upgrades:
DPW Maintenance Garage 550 Patterson Ave.
Stratford, CT
To Whom It May Concern:
(I, We) ______________________________________ the undersigned having visited the project site at the Stratford DPW and having familiarized ourselves with the local conditions affecting the cost of the work and with Contract Documents and all addenda thereto, hereby propose to furnish all labor, materials, tools, equipment, insurance to pay all applicable taxes, and to do and perform all things as provided in the drawings and specifications for the following sum(s):
BASE BID:
Refer to enclosed drawings and specifications.
Contractor shall include all monies and fees to complete documented project as indicated in bid documents. Contractor shall include a $10,000 allowance in base bid number for unforeseen conditions and changes to be used at Architect and Owners discretion. Any unused portion of allowance shall be credited back to owner.
Slab Repair Scope Only
*Written Form: __________________________________________________________
*Dollars: ($_________________)
*PLEASE NOTE THAT STATE OF CONNECTICUT PREVAILING WAGES MUST BE
USED IF TOTAL BID EXCEEDS $100,000.
Bid Form
ALTERNATE #1:
Remove underground oil tank. Refer to drawing MD-100 and spec section 026500.
*Written Form: ________________________________________________________
*Dollars: ($_________________) ADD ALTERNATE
UNIT PRICES:
Contractor must include unit prices for all items listed below, or bid could be rejected at client discretion. Shall include installed price.
1. Removal of Contaminated Soil $____________Per Cubic Yard
2. Soil Testing $____________Per Sample
ADDENDA
In submitting this proposal, I have received and included in this Proposal, the following Addenda:
Addendum No. Date
Signed:________________________________ ____________________________________
Signature Corporate Seal
Company Name : _________________________________________________________
Address : _________________________________________________________
City, St, Zip Code : _________________________________________________________
Phone : (__ __ __) - __ __ __ - __ __ __ __
Email : _________________________________________________________
Milestone Schedule
DPW Maintenance Garage 01009-1
SECTION 01009
MILESTONE SCHEDULE
PART 1 – GENERAL
1.01 MASTER SCHEDULE
The following milestone schedule serves as a basis for bidding. A Master Schedule shall be developed at a general meeting of the successful bidder within fourteen (14) days of Letter of Intent to Award the Contracts. This Master Schedule will incorporate the milestones listed below.
1.02 Milestone Dates:
A. Issue for Bid: 8/24/2026
B. Pre-Bid Walk-Through: 9/2/2026, 10:00am
C. Bid Opening: 9/18/2026, 10:00am
D. Award Project – on or about: 10/16/2026
E. Submittals & Shop Drawings: 10/30/2026
F. Start Construction/Mobilization: 12/1/2026
G. Substantial Completion: 1/29/2027
H. Final Close-out of Contract: 2/26/2027
• Final Milestone Schedule to be coordinated and approved by the Town of
Stratford and Stratford Public Schools
• Final close out of all contracts shall be by or prior to the date established above. All work including, but not limited to punch lists, project closeout, testing, balancing, owners operation, warranties, etc. shall be complete.
END OF MILESTONE SCHEDULE
AMC
Environmental,LLC
April22,2020
Mr.DanWakeling TownofStratford 1000EastBroadway StratfordCT06615
RE: AsbestosTestingatStratfordDPWGarage,Stratford,CT
DearMr.Wakeling:
INTRODUCTION
EnclosedaretheresultsofthebulksamplesobtainedonApril17,2020,todeterminethepresenceor absenceofasbestosintheboilerroomattheStratfordDPWGarage,550PatersonAve.,Stratford,CT.
Thetestingwaslimitedtothematerialslistedbelow.
RESULTS
Thesamplesinthetablebelowdocumentedlevelsofasbestosgreaterthan1% andthereforeare consideredasasbestoscontainingmaterials.
TABLE-1ASBESTOSCONTAININGMATERIALS
Sample# SampleLocation SampleDescription
B041701,02,03 BoilerRoom BoilerPacking
B041716,17 BoilerRoom BoilerGasket
Presumed BoilerRoom BoilerMasonry
TheRegulationsoftheStateofConnecticutrequirethatanyworkwhichmaydisturbasbestoscontaining materialsbeperformedbyaLicensedAsbestosAbatementContractor.
NON-ASBESTOSCONTAININGSAMPLES
Inaddition,thesamplesinTable2didnotdocumentthepresenceofasbestos,and thereforeareconsiderednon-asbestoscontainingmaterials.
AMC
Environmental, LLC
Phone:
203.378.5020
Fax:
203.375.7344
Email:
amc@amcenviro.com
P.O Box 423 Stratford, CT
06615
EnvironmentalMonitoring&consulting
TABLE-2NON-ASBESTOSCONTAININGMATERIALS
Sample# SampleLocation SampleDescription B041704,05,06 BoilerRoom Breeching24inch
B041707,08,09 BoilerRoom FiberGlass(papercovering)8inchLine
B041710,11,12 BoilerRoom InteriorBoilerDebris
B041713,14,15 BoilerRoom InteriorBoilerInsulation(door)
B041718,19 BoilerRoom FiberGlass(papercovering)5inchLine
B041820,21,22 BoilerRoom FiberGlass(papercovering)3inchLine
TheRegulationsoftheStateofConnecticutrequirethatanyworkwhichmaydisturb asbestoscontainingmaterialsbeperformedbyaLicensedAsbestosAbatementContractor.
Thankyoufortheopportunitytoprovideourservices.Ifyouhaveanyquestions,pleasedonothesitate tocall.
Verytrulyyours, JasonPringle Principal StateofCTAsbestosInsp./Mgmt.Planner#000269
Enclosure Note: ThedefinitionofAsbestosContainingMaterialasstatedintheStateofConnecticutStandardsforAsbestosAbatementismaterialcomposedof asbestosofanytypeandinanamountgreaterthan1%byweight,eitheraloneormixedwithotherfibrousornon-fibrousmaterial.
EMSL Analytical, Inc.
29 North Plains Highway, Unit # 4 Wallingford, CT 06492
Tel/Fax: (203) 284-5948 / (203) 284-5978 http://www.EMSL.com / wallingfordlab@emsl.com
242002435EMSL Order:
Customer ID: AMCT50
Customer PO:
Project ID:
Attention: Phone:Jason Pringle (203) 378-5020
Fax:AMC Environmental, LLC (203) 375-7344
Received Date:30 Hazel Terrace 04/20/2020 11:00 AM
Analysis Date:Suite 25 04/21/2020
Collected Date:Woodbridge, CT 06525 04/17/2020
Project: STRATFORD DPW-GARAGE
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
B041701
242002435-0001
None DetectedNon-fibrous (Other)60%Min. Wool40%Brown
Non-Fibrous
Homogeneous
BOILER RM -
BOILER PACKING
B041702
242002435-0002
2% ChrysotileNon-fibrous (Other)58%Min. Wool40%Brown
Non-Fibrous
Homogeneous
BOILER RM -
BOILER PACKING
B041703
242002435-0003
Positive Stop (Not Analyzed)BOILER RM -
BOILER PACKING
B041704
242002435-0004
None DetectedVermiculite
Non-fibrous (Other)
2%
67%
Cellulose
Min. Wool
Fibrous (Other)
6%
15%
10%
Brown
Non-Fibrous
Homogeneous
BOILER RM -
BREECHING 24
INCH
B041705
242002435-0005
None DetectedNon-fibrous (Other)72%Cellulose
Synthetic
Min. Wool
5%
8%
15%
Brown
Non-Fibrous
Homogeneous
BOILER RM -
BREECHING 24
INCH
B041706
242002435-0006
None DetectedNon-fibrous (Other)82%Synthetic
Min. Wool
3%
15%
Brown
Non-Fibrous
Homogeneous
BOILER RM -
BREECHING 24
INCH
B041707
242002435-0007
None DetectedNon-fibrous (Other)30%Cellulose
Glass
50%
20%
Tan/Silver
Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER COVERING)
8 INCH LINE
B041708
242002435-0008
None DetectedNon-fibrous (Other)30%Cellulose
Glass
50%
20%
Tan
Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER COVERING)
8 INCH LINE
B041709
242002435-0009
None DetectedNon-fibrous (Other)45%Cellulose
Glass
40%
15%
Tan
Non-Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER COVERING)
8 INCH LINE
B041710
242002435-0010
None DetectedNon-fibrous (Other)92%Fibrous (Other)8%Gray/Orange
Non-Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
DEBRIS
B041711
242002435-0011
None DetectedNon-fibrous (Other)92%Fibrous (Other)8%Gray/Rust
Non-Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
DEBRIS
B041712
242002435-0012
None DetectedNon-fibrous (Other)90%Fibrous (Other)10%Gray
Non-Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
DEBRIS
B041713
242002435-0013
None DetectedNon-fibrous (Other)25%Min. Wool75%Brown/Tan
Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
INSULATION (DOOR)
B041714
242002435-0014
None DetectedNon-fibrous (Other)25%Min. Wool75%Brown/Tan
Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
INSULATION (DOOR)
B041715
242002435-0015
None DetectedNon-fibrous (Other)30%Min. Wool70%Brown/Tan
Non-Fibrous
Homogeneous
BOILER RM -
INTERIOR BOILER
INSULATION (DOOR)
Initial report from: 04/21/2020 11:27:30
Page 1 of 2ASB_PLM_0008_0001 - 1.78 Printed: 4/21/2020 11:27 AM
EMSL Analytical, Inc.
29 North Plains Highway, Unit # 4 Wallingford, CT 06492
Tel/Fax: (203) 284-5948 / (203) 284-5978 http://www.EMSL.com / wallingfordlab@emsl.com
242002435EMSL Order:
Customer ID: AMCT50
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
B041716
242002435-0016
70% ChrysotileNon-fibrous (Other)30%Black
Fibrous
Homogeneous
BOILER RM -
BOILER HEAD
GASKET
B041717
242002435-0017
Positive Stop (Not Analyzed)BOILER RM -
BOILER HEAD
GASKET
B041718
242002435-0018
None DetectedNon-fibrous (Other)45%Cellulose
Glass
45%
10%
Tan/Silver
Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER COVERING)
5 INCH LINE
B041719
242002435-0019
None DetectedNon-fibrous (Other)40%Cellulose
Glass
50%
10%
Tan
Non-Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER COVERING)
5 INCH LINE
B041720
242002435-0020
None DetectedNon-fibrous (Other)40%Cellulose
Glass
50%
10%
Tan/Silver
Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER
COVERING)) 3 INCH
LINE
B041721
242002435-0021
None DetectedNon-fibrous (Other)45%Cellulose
Glass
45%
10%
Tan/Silver
Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER
COVERING)) 3 INCH
LINE
B041722
242002435-0022
None DetectedNon-fibrous (Other)45%Cellulose
Glass
40%
15%
Tan
Non-Fibrous
Homogeneous
BOILER RM -
FIBERGLASS
(PAPER
COVERING)) 3 INCH
LINE
Analyst(s)
Danny Sandhu (6)
Tara Svendsen (14)
Danny Sandhu, Asbestos Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Wallingford, CT NVLAP Lab Code 200700-0, Initial report from: 04/21/2020 11:27:30
Page 2 of 2ASB_PLM_0008_0001 - 1.78 Printed: 4/21/2020 11:27 AM
ASBESTOSREMOVALPROJECTDESIGN
FOR:
TOWNOFSTRATFORD
STRATFORDDEPARTMENTOFPUBLICWORKSGARAGE
550PATERSONAVE.
STRATFORD,CT
PREPAREDFOR:
DANWAKELING
TOWNOFSTRATFORD
DEPARTMENTOFPUBLICWORKS
PREPAREDBY:
AMCENVIRONMENTAL,LLC
P.O.BOX423
STRATFORD,CT06615
(203)378-5020
April22,2020
AsbestosRemoval
AMCEnvironmental,LLC 550PatersonAve.
April22,2020 Stratford,CT
1.1 ProjectDescription
A. Theworkconsistsofalllabor,materials,equipmentandincidentalsrequired toremovetheasbestoscontainingcontaminatedmaterialsidentifiedin paragraph2.0.
B. Theworkconsistsoftheremovalanddisposalofapproximately200square feetofsheetrock/jointcompound.
1.2 ApplicableCodes
TheContractorshallbesolelyresponsibleforconductingthisprojectandsupervising allworkinamanner,whichwillbeinconformancewithallfederal,stateandlocal regulationsandguidelinespertainingtoasbestosabatement.Specifically,the Contractorshallcomplywiththerequirementsofthefollowing:
A. StateofConnecticutLicense&TrainingRequirements20-440-1 through20-440-9
B. NESHAPSRegulation(40CFR61,SubpartM);
C. OSHAAsbestosRegulations(29CFR1910.1001and1926.1101);
D. USEPAAHERARegulation(40CFR763FinalRuleandNotice) E. ConnecticutDEPRegulations(Section22a-209-8(I)andSection22a-220of theConnecticutGeneralStatutes);
F. Section19a-332a-1toSection19a-332a-16,inclusiveoftheRegulationsof
ConnecticutStateAgencies.
G. ConnecticutBasicBuildingCode;
H. ConnecticutFireSafetyCode;
I. Localhealthandsafetycodes,ordinancesorregulationspertainingto asbestosremediationandallnationalcodesandstandardsincluding ASTM/ANSIandUnderwriter’sLaboratories.
1.3 Exemptions
Anydeviationfromthesespecificationsrequiresthewrittenapprovalandauthorization fromtheOwnerandProjectDesigner.
1.4 Notifications,Postings,SubmittalsandPermits
TheContractorwillmakethefollowingnotificationsandprovidethesubmittalstothe followingagenciespriortothecommencementofremovalworkiftheamountof asbestoscontainingmaterialinvolvesmorethanten(10)linearfeetormorethan twentyfive(25)squarefeet.
A. ConnecticutDepartmentofEnvironmentalProtection SolidWasteManagementUnit 79ElmStreet Hartford,CT06106 (OnlyifdisposingofasbestoswasteinConnecticut)
B. Chief,EnvironmentalHealthServices DepartmentofPublicHealth EnvironmentalHealthSection 410CapitolAvenue,MS#51AIR P.O.Box340308 Hartford,CT06134-0308
April22,2020 Stratford,CT
Theminimuminformationincludedinthenotificationtotheseagenciesinclude:
1. Nameandaddressofbuildingowner/operator
2. Buildinglocation
3. Buildingsize,ageanduse
4. Amountoffriableasbestos
5. Workschedule,includingproposedstartandcompletiondate
6. Asbestosremovalprocedurestobeused
7. Nameandlocationofdisposalsiteforgeneratedasbestoswaste,residueand debris
1.5 WorkSiteSafetyPlan
TheContractorshallestablishasetofemergencyproceduresandshallpostthemina conspicuousplaceattheworksite.Thesafetyplanshouldincludeprovisionsforthe following:
A. Evacuationofinjuredworkers.
B. Emergencyandfireexitroutesfromallworkareas.
C. Emergencyfirstaidtreatment.
D. Localtelephonenumbersforemergencyservicesincludingambulance,fire andpolice.
E. Amethodtonotifyoccupantsofthebuildingintheeventofafireorother emergencyrequiringevacuationofthebuilding.
F. 24hoursitesecurityprogram.
TheContractorisresponsiblefortrainingallworkersintheseprocedures.
1.6 AlternateWorkPractices(AWP)
AnymodificationfromthestandardworkpracticesidentifiedintheStateof ConnecticutDepartmentofPublicHealth(DPH)StandardforAsbestosAbatement Section19a-332a-1to19a-332a-16mustberequestedinwritingfromtheDPH.Any suchrequestshallbepreparedbyalicensedProjectDesigner.
AWP’sarerequiredtoprovideanequivalentorgreaterlevelofcontrolofasbestos emissions.TheOwnerrequiresacopyofthewrittenapprovalbytheState DepartmentofPublicHealthforanyAlternateWorkPracticepriortoimplementation.
1.7 WorkSiteAbatementResponsibilities
A. TheContractorshallmaintaincontrolofandberesponsibleforaccesstoall workareastoensurethefollowingrequirements:
1. Non-essentialpersonnelareprohibitedfromenteringthearea;
2. Allauthorizedpersonnelenteringtheworkareashallreadthe“worker protectionprocedures”whicharepostedattheentrypointstothe enclosuresystem,andshallbeequippedwithproperlyfitted respiratorsandprotectiveclothing;
3. Allpersonnelwhoareexitingfromthedecontaminationenclosure systemshallbeproperlydecontaminated;
4. Asbestoswastethatistakenoutoftheworkareamustbeadequately wet,properlybaggedandlabeledinaccordancewiththisproject
April22,2020 Stratford,CT design.Thesurfaceofthebagsshallbedecontaminated.Asbestos leavingtheenclosuresystemmustbetransportedoffsiteor immediatelyplacedinlocked,postedtemporarystorageonsite.Any material,equipment,orsuppliesthatarebroughtoutofthe decontaminationenclosuresystemshallbecleanedand decontaminatedbywetcleaningand/orHighEfficiencyParticulateAir (HEPA)vacuumingallsurfaces.
5. Allpolyethylenesheetingshallbeflameretardantorsimilar.
B. Contractor’sResponsibilities
TheAsbestosAbatementContractorshallassumefullresponsibilityand liabilityforthecompliancewithallapplicableFederal,State,andlocal regulationspertainingtoworkpractices,haulinganddisposalofAsbestos ContainingMaterial(ACM),andprotectionofworkers,visitorstothesite,and personsoccupyingareasadjacenttothesite.Contractorisresponsiblefor providingmedicalexaminationsandmaintainingmedicalrecordsofpersonnel asrequiredbytheapplicableFederal,Stateandlocalrequirements.
ContractorshallholdtheProjectDesignerandOwner(‘s)Representative harmlessforfailuretocomplywithanyapplicablework,hauling,disposal, safety,healthorotheronthepartofhimself,hisemployees,orhis subcontractors.Contractorincursallsampling/analyticalcostsforsamplingto complywithOSHAregulations.TheContractorisresponsibleforrestoringall workareasandauxiliaryareasutilizedduringabatementtoconditionsequal toorbetterthanoriginal.Anydamagecausedduringtheperformanceof abatementactivitiesshallberepairedbytheContractor.TheContractorwill postappropriatesignageacceptabletotheOwnertodirectvisitorstoasign-in locationandwillbriefanysuchpersonnelonareasofabatementactivity.
1.8 Contractor’sAirSamplingResponsibility
A. TheContractorshallmonitorairborneasbestosconcentrationsintheworkers’ breathingzoneandtoestablishconditionsandworkproceduresfor maintainingcompliancewithOSHARegulations29CFR1910.1001and 1926.1001.
B. TheContractor’sairsamplingprofessionalshalldocumentallairsampling resultsandprovideallairsamplingreportstotheOwneratthecompletionof the project.
C. Allairsamplingshallbeconductedinaccordancewithmethodsdescribedin OSHAstandardsCFR1910.1001and1926.1101.
1.9 UponCompletionofAbatement,theContractorshallsubmitcopiesofalltransport manifests,tripticketsanddisposalreceiptsforallasbestoswastematerialsremoved fromtheworkareasduringtheabatementprocess.Submitaprojectreportthatshall includeacertificateofcompletion,datedandsignedbyanauthorizedrepresentative oftheContractorandthewasteshipmentrecordsignedbytheoperatorofthe licensedlandfill.
2.0 ScopeofWork
Theabatementincludestheremovalofapproximately150sq.ft.ofasbestos containingboilerpacking,approximately5sq.ft.ofboilergaskets,interiorboiler masonryandanyassociatedmaterialsfromtheboilerlocatedintheBoilerRoom.
Thematerialsshallberemovedinitsentiretyunderfullcontainmentthatisunder
April22,2020 Stratford,CT negativepressurewithacontiguousthree(3)stagedecontaminationunit.The negativeairexhaustshallbeexhaustedoutsideofthebuilding.Allwastematerials willberemovedusingwetmethodsandremovedfromcontainmentthroughthe decontaminationunit.
ProjectDesigner: JasonPringle LicenseNo. 000252
Maintenance Garage, Stratford Department of Public Works
Heating System Replacement Sequence of Operations
August 24, 2026
Sequence of Operation
1) Heating and Ventilation Units
a) Factory Controls
i) Each heating and ventilation unit shall be furnished with the manufacturer’s factory-installed, factory-wired, programmed, and tested microprocessor control system.
ii) The controller shall include a lighted local display and keypad for adjusting setpoints, schedules, and override periods and for reviewing operating status and alarms.
iii) Provide factory-installed outdoor-air and supply-discharge temperature sensors.
iv) Building management system communication is not required. All control, adjustment, status indication, and alarm review shall be available locally at the unit controller.
b) Unit Enable and Scheduling
i) Provide a permanent, factory-approved jumper between terminals R and G unless an external shutdown or enable contact is indicated.
ii) Occupied and unoccupied operation shall be controlled through the factory controller’s internal seven-day programmable time clock.
iii) The controller shall accommodate at least seven occupancy schedules.
iv) Provide a temporary occupied-mode override through the local keypad and a dry-contact input. The override period shall be adjustable and initially set at one hour.
v) Heating shall not be permitted until supply-fan operation and the manufacturer’s required minimum airflow have been proven.
c) Occupied Mode
i) Upon initiation of occupied mode, the controller shall complete its initialization sequence and energize the outdoor-air damper actuator.
ii) The controller shall prove that the outdoor-air damper is open before starting the supply fan.
iii) After an adjustable delay, start the supply fan.
iv) The factory-installed variable-frequency drive shall operate the supply fan at a constant speed established during testing and balancing. Fan speed shall not normally modulate.
d) Heating Control
i) The factory controller shall modulate the direct-fired gas burner to maintain an adjustable supply-discharge-air-temperature setpoint, initially 68°F.
ii) Heating shall be disabled when the outdoor-air temperature is above an adjustable heating-lockout setpoint, initially 60°F.
iii) The supply fan shall continue to operate during occupied periods when heating is locked out.
iv) When the heating requirement is below the burner’s minimum stable firing rate, the factory controller shall cycle the burner using an adjustable 5°F discharge-air-temperature deadband.
v) Following a temperature-controlled burner shutdown, the burner shall remain off for at least five minutes before being permitted to restart.
vi) Burner safety recycling, ignition, purge, shutdown, and lockout functions required by the equipment listing or manufacturer shall take precedence over the minimum off-time requirement.
e) Unoccupied Mode
i) During unoccupied periods, the supply fan shall be off, the outdoor-air damper shall be de-energized and spring-returned to its closed position, and the gas burner shall be disabled.
ii) Disable the unit’s unoccupied cycle-on-room-temperature function.
iii) Unoccupied space-temperature control shall be provided by the radiant tube heating system.
f) Preoccupancy Warm-Up
i) Disable the heating and ventilation unit’s factory morning warm-up and cooldown functions.
ii) Preoccupancy warm-up shall be provided by the radiant tube heaters.
iii) The heating and ventilation units shall remain off during preoccupancy warm-up and shall start at the scheduled occupied time.
g) Safeties and Interlocks
i) Burner operation shall be prohibited until supply-fan operation and minimum required airflow are proven.
ii) Loss of supply-fan status or airflow proof shall immediately disable the burner and initiate the applicable factory alarm.
iii) If supply-air temperature falls below an adjustable low-limit setpoint, initially 35°F, for an adjustable period, initially 300 seconds, the controller shall shut down the unit and initiate an alarm.
iv) Provide factory-installed manual-reset high-temperature limits, flame safeguard, ignition controls, gas-pressure switches, airflow switches, and other safety controls required by the equipment listing.
v) Burner ignition, flame failure, pre-purge, post-purge, safety shutdown, recycling, and manual-reset operation shall comply with the equipment manufacturer’s requirements and listing.
vi) Upon restoration of power, the unit shall automatically return to its scheduled operating mode, except where manual reset is required by a safety device.
vii) Where a fire-alarm shutdown signal is available, shut down the supply fan, disable the burner, and close the outdoor-air damper upon receipt of the signal.
h) Alarm Management
i) The factory controller shall record available alarm descriptions, dates, times, temperatures, and unit status for local review.
ii) Provide local indication for the following conditions:
(1) Global alarm.
(2) Outdoor-air temperature sensor failure.
(3) Supply-discharge temperature sensor failure.
(4) Low supply-air temperature.
(5) Dirty filter.
(6) Direct-fired gas-burner or flame failure.
(7) Supply-fan failure.
(8) High-temperature safety trip.
(9) Loss of airflow proof.
iii) Burner and high-temperature safety lockouts shall require manual reset where required by the manufacturer or equipment listing.
2) Radiant Tube Heaters
a) Each radiant tube heater or heating zone shall be controlled independently by a commercial programmable space thermostat.
b) During occupied periods, the radiant tube heaters shall maintain an adjustable space-temperature setpoint, initially 68°F.
c) During unoccupied periods, the radiant tube heaters shall maintain an adjustable setback temperature, initially 55°F.
d) The thermostats shall initiate preoccupancy warm-up sufficiently in advance of the occupied period to achieve the occupied space-temperature setpoint by the scheduled occupancy time.
e) Locate thermostats where they represent typical occupant conditions and are not directly exposed to the radiant tubes, exterior doors, direct sunlight, or supply-air discharge.
f) Provide each heater with the manufacturer’s flame safeguard, ignition controls, airflow or combustion-air proving, high-temperature limits, post-purge controls, and other safeties required by its listing.
g) Following restoration of power, the radiant heaters shall automatically return to their scheduled operating mode, except where manual reset is required by a safety device.
RFI LOG
DPW Maintenance Garage Date: 9/3/2026
Question Date Received
Directed To Response Response Date
1 Please provide information in case there is oil contamination in soil.
9/1/2026 Town See attached revised Bid Form that includes unit pricing to remove contaminated soil and soil testing.
9/1/2026
2 The boiler, flue, and related steam piping to be demolished may have ACM’s. This will need to be tested, with proper reports.
9/1/2026 Town See attached asbestos testing report from AMC Environmental and Abatement Specification.
9/1/2026
3 There will be roofing work to consider. Is there a bond on the roof?
9/1/2026 Town Existing roof is a built-up roof system under warranty by W.P.
Hickman Systems, Inc. Roofing sub-contractor must have appropriate certifications to maintain roof warranty.
9/1/2026
4 Please clarify site restoration scope of work in regards to tank removal?
9/1/2026 Snyder Site shall be restored to as-found condition and disturbed areas paved.
9/1/2026
5 Is there a BMS system currently in place at this location? If so, what vendor currently serves the system. If no BMS, is there a preferred vendor?
9/1/2026 Landmark The building does not currenty have a BMS system.
Connecticut Temperature Controls (CTC) is the town controls vendor.
9/3/2026
6 I did not see a sequence of operation for the new HVAC equipment temperature controls. Can this be provided, or clarified?
9/1/2026 Landmark Addendum #1: See attached controls information and Sequence of Operation.
9/3/2026
7 Please advise regarding building use and coordination during construction.
9/2/2026 Snyder/Town Vehicle repair operations much continue during construction so coordnation is needed between contractor and mechanics to phase work accordingly.
9/3/2026
8 Does the 4000 gallon underground fuel storage tank have an identification number? This info will be required by the State of Connecticut if it is to be removed.
9/3/2026 Snyder/Town Indentification number will be provided after project is awarded. 9/3/2026
9 Can the spacing of gas pipe roof supports be spaced at 8 ft. on center in lieu of 4 ft. on center? 8 ft. O/C will meet code for steel pipe supports.
9/3/2026 Landmark To be addressed in future Addendum.
10 Will the Town of Stratford waive local Permit Fees for this Town funded project?
9/3/2026 Snyder/Town Yes 9/3/2026
11 Oil tank is located below a concrete pad at grade. Can this area be covered with asphalt paving after tank removal in lieu of a concrete pad?
9/3/2026 Snyder/Town Yes 9/3/2026
12 How much fuel oil will be left in the tank at the time of tank removal? Or will this be a Unit Price to remove and dispose per gallon?
9/3/2026 Snyder/Town To be addressed in future Addendum.
13 Please confirm the gas pressure from the utility building meter for gas pressure regulators to be installed for new heating units.
9/3/2026 Landmark To be addressed in future Addendum.
| PROJECT TEAM |
| *** END OF ADDENDUM #1 *** |
| 02.1 BID FORM (Garage HVAC).pdf |
| BID FORM |
| 02.2 01009 Milestone Schedule.pdf |
| END OF MILESTONE SCHEDULE |
| 03 ASBESTOS REPORT & SPEC.pdf |
| 01 RFI Log (DPW Garage) |
| Sheet1 |
| 02 Tank Location Sketch |
| ScreenHunter 610 |
| 03 Job Site Photos |
| 04.1 2020-04-22 DPW Garage Asbestos Report |
| 04.2 2020-04-22 DPW Garage Asbestos Spec |
| 05 REVISED DRAWINGS |
| Stratford DPW - Mech-MD-100 |
| Stratford DPW - Mech-MD-101 |
| Stratford DPW - Mech-M-100 |
| Stratford DPW - Mech-M-101 |
| Stratford DPW - Mech-M-300 |
| Stratford DPW - Mech-M-400 |
| Stratford DPW - Mech-M-401 |
| Stratford DPW - Fuel Gas-FG-200 |
| ADPDDE.tmp |
| PROJECT TEAM |
| *** END OF ADDENDUM #2 *** |