2026-MPW-162-DIV_28.pdf
PDF 335 KB Posted
- Attached to
- Annex EV Chargers
- Solicitation number
- 2026-MPW-162
- Issued by
- Pierce County, Washington
About this file
This specification document outlines the technical requirements for electronic safety and security systems at Pierce County Annex in Tacoma, Washington, including access control, IP security video systems, and supporting electrical infrastructure. The project encompasses three primary divisions: Section 280000 for electronic safety and security work referencing general electrical provisions; Section 281300 for access control system installation requiring a Lenel On-Guard certified contractor with minimum five years of experience and completion of at least five comparable projects within the past five years; and Section 282300 for IP-based security video system installation with specified hardware including 8MP outdoor bullet cameras (Axis P1488-LE model), media converters, fiber optic cabling, and associated infrastructure. The contractor must provide complete installation, configuration, programming, and testing services, maintain existing building operations during modifications, coordinate with the owner for system programming and access point naming, conduct pre-testing within 21 days before acceptance testing, provide acceptance test demonstrations with trained technicians, and complete post-system testing 45 days after final acceptance. Additive Alternate #1 includes five security cameras, OneReach devices for both intermediate distribution frame and camera sides, and cabling to connect cameras to the existing telecommunications room switch.
The specification requires contractor qualifications including Lenel On-Guard or manufacturer certification, direct access to required tools and test equipment, employment of certified technicians within 100 miles of the project site, and detailed submittals including product data, shop drawings, acceptance test plans, and record drawings in AutoCAD and PDF formats. The contractor must maintain emergency egress routes, limit individual door offline time to eight hours or less, provide a one-year warranty covering all labor and parts from the date of acceptance, include 30-minute maximum response time activation support on the day before, day of, and day after system launch, and furnish spare entrance protection devices to the owner. All work must comply with National Electrical Code Article 725, UL standards (UL 50, UL 294, UL 60950-1, UL 60950-22), FCC regulations, ANSI standards, and IEC requirements. Cable labeling, installation in conduit where required, proper grounding to building safety systems, and comprehensive documentation including operation and maintenance manuals are mandated deliverables.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 280000
ELECTRONIC SAFETY AND SECURITY WORK SPECIFIED IN DIVISION 26
PIERCE COUNTY
ANNEX EVSE SERVICE 280000 - 1 CD SET
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Description: The following sections apply to Work in this Division:
1. Section 260500 General Electrical Provisions
2. Section 260510 Basic Electrical Materials and Methods
3. Section 260511 Electrical Connections for Equipment
4. Section 260512 Electrical Demolition
5. Section 260519 Wire and Cables
6. Section 260529 Supporting Devices
7. Section 260533 Raceway Systems
8. Section 260534 Outlet Boxes
9. Section 260548 Vibration Isolation and Seismic Control for Electrical
Systems
10. Section 260553 Electrical Identification
PART 2 - PRODUCTS
Not used.
PART 3 - EXECUTION
Not used.
END OF SECTION 280000
SECTION 281300
ACCESS CONTROL SYSTEM
PIERCE COUNTY
ANNEX EVSE SERVICE 281300 - 1 CD SET
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Description: Provide an electronic access control system and other relevant components and accessories required to provide a complete operating system as specified herein.
B. General Requirements: Drawings and general provisions of the Contract, including General and
Supplementary Conditions, Division 01 sections and Section 270500 apply to Work in this section.
C. The work involved for this project includes modifications to the electronic access doors and portals in an operational environment. For the duration of this project, the contractor shall maintain the existing operations at each door where work is being undertaken. (i.e. if a door is normally unlocked by the access control system from 8:00a – 5:00p that door can be manually unlocked for the same duration). If a door is normally locked and the contractor is performing work at that door, the contractor shall not permit entry to users.
D. The work specified for this project shall require close coordination with the owner to ensure that operations are maintained during and after individual doors have been converted for use on the new system. It is anticipated that for the duration of this project there are (2) active access control systems and that doors will be converted from the old system to the new system in a well-coordinated and incremental manner.
1. Individual doors shall be “off-line” for 8 hours or less with functional building operations being maintained throughout this duration.
E. Emergency egress routes and portals shall be maintained, and no work shall create an unsafe condition for building occupants.
1.2 RELATED SECTIONS
A. Related Sections
1. 260500 – General Provisions
2. 260510 – Basic Materials and Methods
3. 260533 – Raceway Systems
4. 260534 – Outlet Boxes
5. 271100 – Telecommunications System
1.3 QUALITY ASSURANCE
A. The system and its components shall be Underwriters Laboratories, Inc., listed under the appropriate UL testing standard as listed herein for security access control applications.
B. Codes and Standards:
1. American National Standards Institute (ANSI):
a. ANSI C63.4 Methods of Measurement of Radio-Noise Emissions from Low-Voltage
Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz.
2. Federal Communications Commission (FCC):
a. Title 47 CFR – Part 15; Class B – Radiated and Conducted Emissions.
b. Title 47 CFR – Part 68; rules governing the connection of Terminal Equipment (TE) to the Public Switched Telephone Network (PSTN).
3. Underwriters Laboratories, Inc. (UL):
ANNEX EVSE SERVICE 281300 - 2 CD SET
a. UL 50 – Enclosures for Electrical Equipment.
b. UL 294 – Access Control System Units.
c. UL 60950-1 – Information Technology Equipment - Safety.
4. Provide all wiring in accordance with Article 725 of the National Electrical Code and local ordinances, and other sections of these specifications.
C. Qualifications:
1. Contractor shall be a Lenel On-Guard certified installer, pre-qualified by the manufacturer for the purpose of offering the services as specified herein, at the time of bid.
2. Contractors bidding security work shall have a minimum of five years of experience in the construction, testing, and servicing of systems of the type and magnitude specified herein.
3. The contractor shall have completed at least five projects of equal or larger in size to this project within the past five years.
4. Contractor shall have direct access to the tools and test equipment required to complete the work as defined herein.
5. The contractor shall employ Lenel OnGuard certified technicians skilled in the maintenance of the access control system and shall be located within 100 miles of the project site.
1.4 SUBMITTALS
A. Provide submittals in accordance with Division 01 and Section 270500.
B. Product Data:
1. Submittals must be approved in writing prior to materials being ordered.
2. Submit with data arranged under basic categories, such as, certifications, personnel training, manufacturer warranty, products, test equipment and calibration, and similar items. Include index with the submittals.
3. Organize by specification infrastructure component sections described in Part 1 and Part 2 of this section.
4. Submit Product Data information sheets for coordination with item and model number.
5. Where more than one product is shown on a page, mark product with arrow or by other means to identify exact product or products being submitted by specific part number.
6. Submit samples of cable/ device labels.
7. Submit resumes and certifications of technicians and project manager who will support this project. Certifications shall include:
a. Manufacturer’s certification to provide warranty
b. Approved manufacturer classes satisfactorily completed
8. All submittals must be approved by the Owner and the Engineer before ordering product.
C. Acceptance Test Plan:
1. An acceptance test plan form shall be prepared/ provided by the contractor.
2. This form shall include separate sections for each building, device and a column indicating the result of the testing performed by the contractor (pass/fail), and an empty column for recording findings during the walk-through.
D. Shop Drawings:
1. Shop drawings shall provide details of proposed system and the equipment and work to be provided. Proposed pathways shall include conduit and pull box sizes and core drill penetration locations from the access control panel to each door.
ANNEX EVSE SERVICE 281300 - 3 CD SET
2. Shop drawings shall include point-to-point drawings of systems, wiring diagrams of individual devices and labeling. Include individual circuit voltage drop calculations, battery backup calculations, and other calculations as required.
3. Connections to other equipment/ systems not specified herein, i.e. network switches, fire alarm panels (EST), power, client workstations, printers etc.
4. Shop drawings shall be provided in a timely manner to allow review and comments by the
Owner/ Owner representative. Shop drawings shall be 100% accepted by the Owner/ Owner representative prior to start of work.
E. Record Drawings:
1. Keep complete set of security drawings in job-site office to show actual installation of cabling and equipment during construction.
2. Use of this set of drawings for recording as-built conditions.
3. Indicate where material, equipment, and system component are installed differently from that shown on the Drawings.
4. Prepare electronic set of Record Drawings, incorporating changes during construction.
Submit Record Drawings to the Owner’s Representative for review and acceptance.
5. Submit Record Drawings using latest version of AutoCAD software or as approved by the
Owner, and in PDF format. Request final architectural background drawing files that incorporate floor plan and program spaces numbering modifications.
a. AutoCAD drawings shall be e-transmitted to include backgrounds, title blocks and other associated files.
6. Submit electronic copy of Record Drawings in full-size PDF and AutoCAD format, on CD-
ROM.
a. Record drawings shall include layout for each individual panel including but not limited to; card layout, IP addressing, point terminations, load calculations, power circuit ID< panel wire schematics, dipswitch and jumper settings for Lenel and LifeSafety panels.
b. Provide panel layout and as-built drawings in the panel for all doors served, stored in a re-closable vinyl envelope.
F. Project Closeout:
1. Submit closeout documentation to the Owner’s Representative and Architect under provisions of Division 01, Section 270500 and this section.
2. Provide all project closeout documentation including but not limited to; test acceptance documentation, copy of purchase order for Lenel devices, Record Drawings, manufacturer warranty and Operation and Maintenance Manuals.
1.5 SYSTEM REQUIREMENTS
A. Type of System:
1. Contractor shall coordinate with Owner and follow County standards as directed for access point naming format for all programming.
2. Access control system shall provide a means of electronically accessing and controlling access to the building in lieu of a manual key/lock system.
3. Access control system and devices shall be provided as shown on the associated Contract
Documents.
4. Contractor shall provide, and program for both initial and final programming for the Access
Control System.
5. Contractor shall test all devices to ensure correct termination and that all devices operate correctly.
ANNEX EVSE SERVICE 281300 - 4 CD SET
6. Contractor shall be responsible for connecting the Access Control System to the customer network by means of connecting patch cords to the designated telecommunications outlets, patch panels and Ethernet switch ports.
7. Access credentials (access cards) are not required under this specification and shall be provided by the Owner.
8. Access control devices shall be equipped with tamper switches and end-of-line resistors as shown in the Contract Documents.
9. Electronic locking hardware (wired and wireless) at access-controlled doors shall be provided by the security contractor as required by the Contract Documents.
10. Wireless locking hardware shall communicate with the gateway continuously without interruption.
11. Electronic access control doors with auto operators shall be integrated with the card reader functions.
12. Cabling routed below structure shall be within conduit raceways. Contractor shall coordinate exact cable pathway requirements with WWU Engineer.
1.6 PRE-CONSTRUCTION MEETINGS
A. The subcontractor shall attend the pre-construction meeting as required by the Contractor or the
Owner’s Representative.
B. Provide a schedule, indicating installation tasks, time duration for each task and coordination items to be discussed 5 days prior to the meeting, to the Contractor and to the Owner’s Representative.
1.7 MATERIAL PROVISIONS
A. Deliver materials to the Owner under provisions of this section.
B. Contractor shall be responsible to provide a material transmittal for all materials being provided to the Owner as described herein and that are not permanently installed. Transmittal shall be signed by the General Contractor and the Owner receiving the materials.
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Substitutions: The substitution of products shall not be considered under the terms and conditions of this Section.
2.2 SOFTWARE AND LICENSES
A. Owner shall provide Lenel Systems International “OnGuard” Series ADV, Security Management
System (SMS) Software.
2.3 HARDWARE
A. Security Management System (SMS) hardware shall be equipped with the access control field hardware required to receive alarms and administer all access granted or denied decisions. All field hardware must be designed to meet UL 294 requirements. The SMS must be able to retrieve device serial numbers from all field hardware, excluding card readers, biometric readers, and keypads.
1. Manufacturer Lenel:
ANNEX EVSE SERVICE 281300 - 5 CD SET
a. Intelligent system controllers (ISC), Part No. LNL-X3300
b. Input control module (ICM), Part No. LNL-1100
c. Output control module (OCM), Part No. LNL-1200
d. Dual reader interface module (DRI), Part No. LNL-1320
e. The current or latest version of equipment shall be provided.
B. Readers:
1. Contactless smart card readers shall be designed to securely read, interpret, and authenticate access control data from 13.56 MHz and 125 Hz contactless smart card credentials.
a. Manufacturer Lenel:
1) Mullion, Part No. LNL-MT11-485
2) Standard, Part No. LNL-MT15-485
2.4 POWER SUPPLIES AND BATTERIES
A. Enclosure shall provide power supply 12V and 24V, tamper switch and minimum 4-hour battery backup. 4-hour battery backup shall be based on a door being operated every 5 minutes. Panel shall be UL 294-Listed power supplies for 12V DC and 24V DC applications.
1. Manufacturer LifeSafety Power:
a. 12V& 24V 400W, Part No. FPO150/250-2C82D8PE8M2
B. Batteries shall be Absorbent Glass Mat (AGM) technology for superior performance, valve regulated, spill proof construction, power/volume ratio yielding unrivaled energy density, rugged impact resistant ABS case and cover (UL94-HB).
1. Manufacturer Yuasa, 7Ah minimum
2.5 REQUEST TO EXIT DEVICES
2.6 ELECTRONIC HARDWARE
A. Provide Gate Lock with all accessories required.
1. Gate Lock shall be Securitron Model LL1-FSM
a. Provide with FMK Flex Mount Gate Lock Bracket Kit
2.7 CABLING
A. End-of-Line (EOL) Resistors shall be provided on all door contacts and request to exit inputs.
Locate EOL Resistors as close to the sensing device as possible.
1. End-of-Line (EOL) resistor pack with 1000-Ohm supervisory resistors.
B. Cabling shall be sized to provide minimum resistance and minimum voltage drop to the devices being supplied. Voltages delivered to all devices shall be within the tolerance specified by the device manufacturer.
1. Cabling shall be a minimum 18 AWG solid copper conductors for power connectivity.
2. Twisted pair cable shall be used to prevent EMI/RFI interference with the proper operation of the circuits.
C. Cable shall be indoor/outdoor, CMR (riser) rated, unless otherwise noted.
D. Each electronic access control door/ equipment shall have a multiple conductor cable installed with a yellow outer jacket with the following sub cables:
ANNEX EVSE SERVICE 281300 - 6 CD SET
1. Labelled “Lock Power Cable”: 1x 4/C unshielded solid #18 AWG – gray jacket with purple stripe.
2. Labelled “Card reader”: 1x 6/C shielded solid #22 AWG – gray jacket with yellow stripe.
3. Labelled “Door Contact”: 1x 2/C unshielded solid #22 AWG – gray jacket with green stripe.
4. Labelled “Rex / Spare”: 1x 4/C unshielded solid #22 AWG – gray jacket with red stripe.
a. Manufacturer Windy City Wire, Part No. 4ELEM-WBT-BLK
E. For individual devices, not directly associated with access control, door cabling shall have stranded copper conductors and shall be as follows:
1. Gateway: 24 AWG-4C with overall shield (RS-485) and 18 AWG-2C (power).
2. Card readers: 22 AWG-6C with overall shield.
3. Door position switch: 22 AWG-2C
4. Keyed switch: 18 AWG-4C
5. Request to exit: 22 AWG-4C
6. Electrified lock/exit device: 16 AWG-4C
a. Refer to manufacturer requirements.
7. Electrified mag lock: 16 AWG-2C
8. Sounder/ strobes w/tamper switch: 18 AWG-4C
9. Relay: 22 AWG-2C
10. Door operator: 22 AWG-2C
F. Coordinate additional cabling requirements, other than those listed herein, for devices within the access control system shop drawings.
G. Provide service loops as required per NFPA 731 4.5.8.9.
2.8 FIRE RETARDANT PLYWOOD BACKBOARDS
A. Plywood backboards shall be 3/4” fire retardant ACX plywood to cover the walls as indicated in the
Contract Documents. Backboard shall bear a seal identifying the plywood is fire retardant.
Backboard shall be painted white with the seal left exposed for permanent identification.
2.9 DOCUMENT STORAGE AND LABELING
A. As-built documentation shall be stored at each panel location stored in a 10 inch x 13 inch vinyl re-closable envelope.
1. Manufacturer Uline, Part No. S-7713 or approved equal
B. Cable labels shall be heat shrinkable, white with black thermal transfer lettering.
1. Manufacturer Hellermann Tyton, ShrinkTrak series or approved equal
PART 3 - EXECUTION
3.1 IP DEVICE MATRIX
A. Contractor shall request the IP Device Matrix from the Owner in writing a minimum of three weeks in advance of starting the installation of IP devices.
B. Complete the owner furnished IP Address matrix, in Microsoft Excel format, indicating the devices;
make, model, MAC address, cable port number, room name and room number. Coordinate the specific function identifications and classifications with the Owner and Owner’s Representative prior to the start of the installation.
ANNEX EVSE SERVICE 281300 - 7 CD SET
3.2 PRE-INSTALLATION
A. Provide complete wireless survey where wireless locks are to be installed to verify locations of gateways.
3.3 INSTALLATION
A. Provide labor, tools, supplies, hardware, materials, and equipment required for the design, installation, configuration/ programming and testing of a complete and operational system.
B. Spare cable/ conductors located in the access control/ power supply panels and at door junction box shall not be cut back or shortened. Provide heat shrink tubing around the other conductors that are terminated and spare conductors covering the ends of the conductors.
C. Install equipment in accordance with manufacturer’s instructions, approved Shop Drawings and as indicated on the Contract Documents.
D. Cabling shall be installed in conduit. Cabling shall not be enclosed in conduit or raceways containing AC power.
E. Devices shall be securely mounted. Provide necessary backing.
F. Properly ground the system per NEC requirements to the building safety grounding system to prevent electrostatic charges and other transient electrical surges from damaging the control panel.
G. Door hardware power supplies shall be provided by Division 28.
3.4 LABELING
A. General:
1. Labels shall be heat shrink, permanent typewritten labels produced by a labeling machine.
2. Labels shall be installed on the overall cable and each individual break out sub-group terminated to each device at both ends.
3. Labels shall be located within 6 inches of cable termination and placed so they can be easily read.
4. Font type for each type of label shall be Arial with maximum size font allowed.
5. Labeling information will be reviewed at the Pre-Construction Meeting.
6. Labeling shall be completed prior to the Substantial Completion date of the project.
a. Labeling for overall cable shall be as follows:
1) AB-1.01 where:
a) AB = Building abbreviation
b) 1 = Floor number
c) 01 = Door number sequential
b. Labeling for sub-groups shall be as follows:
1) AB-1.01.CR1 where:
a) AB = Building abbreviation
b) 1 = Floor number
c) 01 = Door number sequential
d) CR = Device Abbreviation (see below)
e) 1 = Device number (per door) sequential
c. Device Abbreviations
1) CR - Card Reader
ANNEX EVSE SERVICE 281300 - 8 CD SET
2) DP - Door Position Switch
3) EL - Electronic Lock
4) ES - Electric Strike
5) MG - Magnetic Lock
6) RX - Request-To-Exit
a) Coordinate abbreviations for devices not listed above.
3.5 PROGRAMMING
A. Programming of the system shall include, but not limited to:
1. Programming user/ groups, door groups, creating maps, door schedules, access cards and e-mail notifications as defined by the Owner.
2. The system shall be programmed with “normal” opening and closing periods for each day of the week and thus suppressing the scheduled opening/ closing reports. The system shall only report on opening/ closings outside the pre-defined schedule.
3. Forced entry detection shall be enabled at doors equipped with a request to exit (REX). A forced entry shall be generated immediately whenever the door is opened without authorization. Authorization shall be determined by card, REX transaction at the door, or by command from the host system as described. Doors without a REX device shall not report forced entry.
4. Door held open detection shall be enabled at electronic controlled doors. A door held open event shall be generated immediately when the door is held open longer than 3 to 5 seconds.
5. The system shall automatically re-lock the electronic controlled portal when the door is sensed as closed and/or whenever the 2 second door relay unlock time expires.
6. ADA door opener motor shall not operate when door is in a locked state from the exterior button. Interior button shall always operate door and unlock the door hardware if the door is in a locked state. Provide relays and cabling for card reader operation with ADA openers.
7. Other programming requirements shall be coordinated with the Owner and shall be provided at no additional cost to Owner.
3.6 PRE-TESTING
A. After Work is completed, and prior to requesting the acceptance test, Contractor shall conduct a final inspection, and an operational pre-test of all equipment and system features. Contractor shall correct any deficiencies discovered as the result of the inspection and operational pre-test.
B. Submit written notification to the Owner’s Representative and the A/E that systems have been tested, are operating properly, and are ready for Acceptance at least 21 days prior to the requested test date.
3.7 FINAL ACCEPTANCE
A. Contractor shall submit a request for the Acceptance test in writing to the Owner no less than twenty-one days prior to the requested test date. The request for acceptance test shall constitute a certification from the Contractor that all Work is complete and in compliance with the Contract
Documents; all systems have been tested; and that all corrections have been made.
B. Acceptance test shall be scheduled during a period when the building is open and a complete system test can be accomplished. Contractor shall provide the services of a technician to perform the acceptance test. Technicians performing the acceptance test shall have been involved in the
ANNEX EVSE SERVICE 281300 - 9 CD SET
installation of this project and shall be thoroughly familiar with all aspects of the Work. Technicians shall be equipped with portable two-way radios that will be used during the test.
C. Contractor shall provide all ladders, tools, test equipment, and other facilities needed to accomplish the Acceptance test.
D. During acceptance test, Contractor shall demonstrate all equipment and system features to the
Owner. Contractor shall fully cooperate with the Owner and provide assistance with the inspection and test. Contractor shall remove and reinstall covers, open and restore wiring connections, operate equipment, and perform other reasonable work as requested by the Owner.
E. Any portions of the Work found to be deficient or not in compliance with the Contract Documents will be rejected. Owner will record any such deficiencies observed during the Acceptance test. A copy of said list will be provided to Contractor. Contractor shall promptly correct all deficiencies.
F. The contractor shall provide project site activation support with 30 minute maximum response time on the day before, day of and the day after launch. Exact dates shall be coordinated with Owner’s
Security Project Manager at least 2 weeks prior to the project site activation date.
3.8 WARRANTY AND SERVICE
A. Contractor shall provide parts and labor guarantee on all Work. Unless otherwise specified herein, Contractor’s guarantee shall be for a period of one (1) year from Date of Acceptance, except where any specific guarantees from a supplier or equipment manufacturer extends for a longer time.
B. Contractor’s guarantee shall cover all costs associated with troubleshooting, repair, and replacement of defective Work, including costs of labor, transportation, lodging, materials, and equipment.
END OF SECTION 281300
SECTION 282300
IP SECURITY VIDEO SYSTEM
PIERCE COUNTY
ANNEX EVSE SERVICE 271100 - 1 CD SET
GENERAL
1.1 SECTION INCLUDES
A. Description: Provide an IP based security video system and other relevant components and accessories required to provide a complete operating system as specified herein.
B. General Requirements: Drawings and general provisions of the Contract, including
General and Supplementary Conditions, Division 01 sections and Section 260500 apply to Work in this section.
C. Contractor Provided IP Cameras and Cabling is part of Additive Alternate #1.
1.2 RELATED SECTIONS
A. Related Sections
1. 260500 – General Electrical Provisions
2. 260510 – Basic Electrical Materials and Methods
3. 260533 – Raceway Systems
4. 260534 – Outlet Boxes
5. 271100 – Telecommunications System
6. 281300 – Access Control System
1.3 QUALITY ASSURANCE
A. The system and its components shall be Underwriters Laboratories, Inc., listed under the appropriate UL testing standard as listed herein for security video applications.
B. Codes and Standards:
1. National Electrical Manufacturers Association (NEMA):
a. NEMA 250 – Enclosures for Electrical Equipment
2. Federal Communications Commission (FCC):
a. Title 47 CFR – Part 15; Class A – General
3. International Electrotechnical Commission (IEC):
a. IEC 60529 – Ingress Protection
4. Underwriters Laboratories, Inc. (UL):
a. UL 60950-22 – Information Technology Equipment – Safety (Outdoors)
5. Provide all wiring in accordance with Article 725 of the National Electrical Code and local ordinances, and other sections of these specifications.
C. Qualifications:
1. Contractor shall be a certified reseller/dealer, pre-qualified by the manufacturer for the purpose of offering the services as specified herein, at the time of bid.
2. Contractors bidding security work shall have a minimum of five years of experience in the construction, testing, and servicing of systems of the type and magnitude specified herein.
3. Contractor shall have completed at least five projects of equal or larger in size to this project within the past five years.
4. Contractor shall have direct access to the tools and test equipment required to complete the work as defined herein.
5. Contractor shall employ certified technicians skilled in the maintenance of the IP security video system and shall be located within 100 miles of the project site.
PIERCE COUNTY
ANNEX EVSE SERVICE 271100 - 2 CD SET
1.4 SUBMITTALS
A. Provide submittals in accordance with Division 01 and Section 260500.
B. Product Data:
1. Submit with data arranged under basic categories, such as, certifications, personnel training, manufacturer warranty, products, test equipment and calibration, and similar items. Include index with the submittals.
2. Organize by specification infrastructure component sections described in Part 1 and Part 2 of this section.
3. Submit Product Data information sheets for coordination with item and model number.
4. Where more than one product is shown on a page, mark product with arrow or by other means to identify exact product or products being submitted by specific part number.
C. Acceptance Test Plan:
1. An acceptance test plan form shall be prepared/provided by the contractor.
2. This form shall include separate sections for each device and a column indicating the result of the testing performed by the contractor (pass/fail), and an empty column for recording findings during the walk-through.
D. Shop Drawings:
1. Drawings shall provide details of proposed system and the equipment and work to be provided. Drawings shall include camera mounting details for each type of installation and wiring diagrams of individual devices.
2. Connections to other equipment/systems not specified herein.
E. Record Drawings:
1. Keep complete set of security drawings in job-site office to show actual installation of cabling and equipment during construction.
2. Use of this set of drawings for recording as-built conditions.
3. Indicate where material, equipment, and system component are installed differently from that shown on the Drawings.
4. Record drawings shall indicate camera name as programmed in the VMS, IP address (or DHCP scope information) and horizontal station patch panel port for each camera.
5. Prepare electronic set of Record Drawings, incorporating changes during construction. Submit Record Drawings to the Owner’s Representative for review and acceptance.
6. Submit Record Drawings using latest version of AutoCAD software or as approved by the Owner, and in PDF format. Request final architectural background drawing files that incorporate floor plan and program spaces numbering modifications.
a. AutoCAD drawings shall be e-transmitted to include backgrounds, title blocks and other associated files.
7. Submit electronic copy of Record Drawings in full-size PDF and AutoCAD format, on flash drive.
F. Project Closeout:
1. Submit closeout documentation to the Owner’s Representative and Architect under provisions of Division 01, Section 260500 and this section.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 1 CD SET
GENERAL
1.1 SECTION INCLUDES
A. Description: Provide an IP based security video system and other relevant components and accessories required to provide a complete operating system as specified herein.
B. General Requirements: Drawings and general provisions of the Contract, including
General and Supplementary Conditions, Division 01 sections and Section 260500 apply to Work in this section.
C. Contractor Provided IP Cameras and Cabling is part of Additive Alternate #1.
1.2 RELATED SECTIONS
A. Related Sections
1. 260500 – General Electrical Provisions
2. 260510 – Basic Electrical Materials and Methods
3. 260533 – Raceway Systems
4. 260534 – Outlet Boxes
5. 271100 – Telecommunications System
6. 281300 – Access Control System
1.3 QUALITY ASSURANCE
A. The system and its components shall be Underwriters Laboratories, Inc., listed under the appropriate UL testing standard as listed herein for security video applications.
B. Codes and Standards:
1. National Electrical Manufacturers Association (NEMA):
a. NEMA 250 – Enclosures for Electrical Equipment
2. Federal Communications Commission (FCC):
a. Title 47 CFR – Part 15; Class A – General
3. International Electrotechnical Commission (IEC):
a. IEC 60529 – Ingress Protection
4. Underwriters Laboratories, Inc. (UL):
a. UL 60950-22 – Information Technology Equipment – Safety (Outdoors)
5. Provide all wiring in accordance with Article 725 of the National Electrical Code and local ordinances, and other sections of these specifications.
C. Qualifications:
1. Contractor shall be a certified reseller/dealer, pre-qualified by the manufacturer for the purpose of offering the services as specified herein, at the time of bid.
2. Contractors bidding security work shall have a minimum of five years of experience in the construction, testing, and servicing of systems of the type and magnitude specified herein.
3. Contractor shall have completed at least five projects of equal or larger in size to this project within the past five years.
4. Contractor shall have direct access to the tools and test equipment required to complete the work as defined herein.
5. Contractor shall employ certified technicians skilled in the maintenance of the IP security video system and shall be located within 100 miles of the project site.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 2 CD SET
1.4 SUBMITTALS
A. Provide submittals in accordance with Division 01 and Section 260500.
B. Product Data:
1. Submit with data arranged under basic categories, such as, certifications, personnel training, manufacturer warranty, products, test equipment and calibration, and similar items. Include index with the submittals.
2. Organize by specification infrastructure component sections described in Part 1 and Part 2 of this section.
3. Submit Product Data information sheets for coordination with item and model number.
4. Where more than one product is shown on a page, mark product with arrow or by other means to identify exact product or products being submitted by specific part number.
C. Acceptance Test Plan:
1. An acceptance test plan form shall be prepared/provided by the contractor.
2. This form shall include separate sections for each device and a column indicating the result of the testing performed by the contractor (pass/fail), and an empty column for recording findings during the walk-through.
D. Shop Drawings:
1. Drawings shall provide details of proposed system and the equipment and work to be provided. Drawings shall include camera mounting details for each type of installation and wiring diagrams of individual devices.
2. Connections to other equipment/systems not specified herein.
E. Record Drawings:
1. Keep complete set of security drawings in job-site office to show actual installation of cabling and equipment during construction.
2. Use of this set of drawings for recording as-built conditions.
3. Indicate where material, equipment, and system component are installed differently from that shown on the Drawings.
4. Record drawings shall indicate camera name as programmed in the VMS, IP address (or DHCP scope information) and horizontal station patch panel port for each camera.
5. Prepare electronic set of Record Drawings, incorporating changes during construction. Submit Record Drawings to the Owner’s Representative for review and acceptance.
6. Submit Record Drawings using latest version of AutoCAD software or as approved by the Owner, and in PDF format. Request final architectural background drawing files that incorporate floor plan and program spaces numbering modifications.
a. AutoCAD drawings shall be e-transmitted to include backgrounds, title blocks and other associated files.
7. Submit electronic copy of Record Drawings in full-size PDF and AutoCAD format, on flash drive.
F. Project Closeout:
1. Submit closeout documentation to the Owner’s Representative and Architect under provisions of Division 01, Section 260500 and this section.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 3 CD SET
2. Provide all project closeout documentation including but not limited to;
Acceptance Test documentation, IP device matrix, camera views, record drawings, manufacturer warranties and Operation and Maintenance Manuals.
1.5 SYSTEM REQUIREMENTS
A. Type of System:
1. System is an existing IP Video recording system. Coordinate with Owner for video channel licensing.
1.6 OWNER FURNISHED CONTRACTOR INSTALLED (OFCI) EQUIPMENT
A. Material Handling and Delivery: Coordinate delivery of OFCI equipment. Receive, off load, transport, store, hoist, unpack, dispose of packing, same as for other project equipment arriving at job site. Requirements of the Contract Documents apply to OFCI equipment.
B. Operation and Maintenance Data: Obtain from the Owner operation and maintenance data for the OFCI equipment and incorporate them into the Operations and Maintenance
Manuals.
1.7 PRE-CONSTRUCTION MEETINGS
A. Subcontractor shall attend the pre-construction meeting as required by the Contractor or the Owner’s Representative.
B. Provide a schedule, indicating installation tasks, time duration for each task and coordination items to be discussed 5 days prior to the meeting, to the Contractor and to the Owner’s Representative.
1.8 MANUFACTURER CERTIFICATION
A. Contractor shall be a certified install/dealer, pre-qualified by the manufacturer for the purpose of offering the warranty at the time of bid, as specified herein.
1.9 MATERIAL PROVISIONS
A. Deliver materials to the Owner under provisions of this section.
B. Contractor shall be responsible to provide a material transmittal for all materials being provided to the Owner as described herein and that are not permanently installed.
Transmittal shall be signed by the General Contractor and the Owner receiving the materials.
PRODUCTS
2.1 MANUFACTURERS
A. Substitutions: The substitution of products shall adhere to the requirements defined in
Division 01 and this section.
1. Submit requests for substitutions a minimum of 10 days prior to Bid date.
Request submitted less than 10 days prior to, shall not be accepted.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 4 CD SET
2.2 HARDWARE AND ENCLOSURES
A. Provide hardware components including but not limited to; 1.5-inch NPT pipe, mounting accessories, pole attachment accessories and/or brackets (i.e., pendent, goose and/or corner) as required. Hardware components shall be of same manufacturer as the camera and match in color or shall be painted to match camera housing.
B. Control equipment, media converters, POE injectors, modules, and other such devices that are installed exterior to the facility shall be contained within enclosures of non-metal construction. Provide NEMA 4 enclosures for all equipment that is not provided by the manufacturer in a suitable enclosure, unless otherwise noted.
C. Pole Mounted Enclosure:
1. Enclosure shall be a NEMA 4X junction box with pole mounting hardware for pole mounted cameras and equipment. Junction box shall support multiple cameras located on the same pole.
a. Manufacturer Axis:
1) Surveillance cabinet, Part No. T98A15-VE
2) Pole mounting hardware, Part No. T91B57
2.3 CAMERAS
A. 8MP Outdoor Bullet Camera:
1. Cameras shall be an 8 MP vandal resistant, wide dynamic range with HD resolution at 20fps. Camera shall provide the minimum following features; tamper alarms, video loss/change detections, varifocal, remote focus, record on motion, audio, I/O contacts and dual streaming with H.264, H.265 and MJPEG video compression. Camera shall be powered via PoE (802.af).
a. Manufacturer Axis:
1) IP camera, Part No. P1488-LE
2) Pole Mount, Part No. T91B47
2.4 IP DEVICE CONNECTIVITY
A. Modular Patch Cords, Category 6:
1. Patch cords shall be UL listed, constructed from Category 6 4-pair 24 AWG and meet FCC Part 65 plug and termination.
a. Non-plenum patch cables shall be utilized in a concealed j-box or non-plenum ceiling spaces.
b. Low smoke zero halogen patch cables shall be utilized in above plenum rated ceiling spaces.
2. Category 6 patch cords shall be provided for each IP camera and PoE injector for the connection at the device end.
a. Manufacturer Leviton:
1) OneReach extender to camera (pole), 5-foot, Part No. 6D460- 5W
2) Low-smoke zero halogen, Part No. 6Z460-WH01 (1M)
3) Non-plenum, 4-foot, Part No. 6D460-04W
B. Media Converters:
1. Camera Side
a. OneReach 2-Port Remote PoE Port shall be mounted in the camera cabinet.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 5 CD SET
1) Manufacturer Leviton:
a) Berk-Tek OneReach Remote PoE 2-Port, Part No.
81001535
b) Berk-Tek One-Reach Single-Mode LC Duplex Pigtail
Remote End, Part No. 11101279
2. Building Side
a. Rack mount bracket shall be 1-RU, accepting up to (2) individual 1-port media module.
b. Media module shall contain (1) RJ45 ports on the front and (1) corresponding LC 1000BASE-LX (Single-mode) duplex ports on the back.
1) Manufacturer Leviton:
a) OneReach Rack Mount 1-RU Bracket, Part No.
81000463
b) OneReach 1-Port Source PoE Device with AC power adaptor, part No. 81001515
3. Ethernet Over Fiber Extender Cabling
a. Ethernet over fiber extender cabling shall be indoor/outdoor OneReach
LC pre-connectorized composite with (4) OS2 fiber and (2) 12AWG solid conductor, plenum rated.
1) Manufacturer Leviton:
a) Berk-Tek OneReach Cable Assembly, Part No.
ACPC004AB0403-002X12AWG
b) Berk-Tek OneReach M8 Pigtail, Part No. 11099456
2.5 OPEN CABLING SUPPORTS
A. Accessories and mounting hardware shall be provided for securing supports to structure for a complete and working installation of open cabling supports. Supports shall comply with TIA requirements for structured cabling systems and pathway supports. Follow manufacturer’s recommendations for quantity of cables supported.
B. Hook & Loop Fasteners:
1. Hook and loop fastener rolls shall be 0.5-inch in width. Shear strength. Hook and loop fasteners installed in plenum air spaces shall be UL Listed (plenum) and be in the color maroon.
a. Manufacturer Leviton or equal:
1) Non-plenum 75’ roll, Part No. 43115-075
2) Plenum 75’ roll, Part No. 43115-75P
C. Circular Cable Retainer:
1. Cable retainers shall be of plastic material with rounded edges, plenum rated, utilizing an easy-lock closure and an attachment base. Cable retainers shall be screwed into structure and only be utilized in spaces that are extremely tight and
J-hooks do not have sufficient space to be mounted.
a. Manufacturer Erico Caddy, Part No. CAT CR50
D. J-Hooks:
1. J-hooks shall have a Galvanized finish with rounded edges for smoother cable pull and greater corrosion resistance.
a. Manufacturer Erico Caddy:
1) 1-inch Dia., Part No. CAT16HP
2) 1-5/16-inch Dia., Part No. CAT21HP
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 6 CD SET
2.6 CABLING
A. Cabling shall be sized to provide minimum resistance and minimum voltage drop to the devices being supplied. Voltages delivered to all devices shall be within the tolerance specified by the device manufacturer.
1. Cabling shall be a minimum 18 AWG copper conductors for power connectivity.
2. Twisted pair cable shall be used to prevent EMI/RFI interference with the proper operation of the circuits.
B. Provide cables consistent with the manufacturer’s recommendations. The following general guidelines shall be followed for wiring installation:
1. Wiring shall be appropriately color-coded with permanent wire markers.
2. Cabling shall have stranded copper conductors.
C. Cable shall be NFPA 262, CMP (plenum) rated unless otherwise noted.
1. Cables installed in underground applications shall be rated for wet environments.
D. Coordinate additional cabling requirements, other than those listed herein, for devices within the IP security video system shop drawings.
2.7 CABLE ENTRANCE PROTECTION
A. Provide cable building entrance protection for all new OneReach assembly cable that leave the building envelope.
B. Entrance Protection Block shall be grounded to the telecommunications grounding bar, electrical panel ground bar, or equal grounding source. Grounding shall be #12 AWG conductor minimum.
C. The #12 AWG Entrance Protection shall be secured to a shelf mounted in the rack.
Contractor shall provide rack mount shelf. It may also be wall mounted in an easily accessible location. All cabling shall be secured and organized.
D. The Category 6 Entrance Protection shall be secured in the camera cabinet.
E. #12 AWG Entrance Protection shall be Ditek DTK-2MHLP48BWB or approved equal.
F. Category 6 Entrance Protection shall be Ditek DTK-MRJEXTS or approved equal.
G. Contractor to provide 1 spare DTK-2MHLP48BWB device and 1 spare DTK-MRJEXTS to
Owner. Contractor shall include labor for installation of those spares.
EXECUTION
3.1 IP DEVICE MATRIX
A. Contractor shall request the IP Device Matrix from the Owner in writing a minimum of three weeks in advance of starting the installation of IP devices.
B. Complete the owner furnished IP Address matrix, in Microsoft Excel format, indicating the devices; make, model, MAC address, cable port number, room name and room number.
Coordinate the specific function identifications and classifications with the Owner and
Owner’s Representative prior to the start of the installation.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 7 CD SET
3.2 INSTALLATION
A. Provide labor, tools, supplies, software, hardware, materials, and equipment required for the installation, configuration/programming and testing of a complete and operational security video system.
B. Install equipment in accordance with manufacturer’s instructions, approved Shop
Drawings and as indicated on the Contract Documents.
C. Devices shall be securely mounted, provide necessary backing/supports.
D. Cameras shall be mounted in a manner that foreign objects don’t obstruct the view of the camera, i.e., structural elements, light fixtures, mechanical ducts, electrical conduits, signage, vegetation, etc.
E. Camera images shall be set whereas the ceiling, area above the horizon, or non-essential area shall consist of less than 1/10 of the overall frame.
F. Coordinate field of view requirements with owner prior to and after installation of cameras to achieve an acceptable system.
1. Final camera view/placement shall be coordinated with the owner/engineer. An on-site walk-through shall be conducted to review camera locations and heights prior to installation.
G. Neatly dress and secure wiring. Do not obstruct access to power supplies, fans, network interface cards or other components.
H. Cabling shall be installed in conduit, cable tray or using open cabling methods when installed above accessible ceilings.
I. Where subject to mechanical damage, wiring shall be enclosed in metal conduits or surface metallic raceway.
J. Cabling shall not be enclosed in conduit or raceways containing AC power.
K. Properly ground equipment per NEC requirements to the building safety grounding system to prevent electrostatic charges and other transient electrical surges from damaging the cameras.
3.3 PROGRAMMING
A. Programming of the cameras shall include, but not limited to:
1. Current firmware shall be uploaded to the camera, set for DHCP and assigned a temporary password prior to installation.
2. Exterior camera shall mask out areas of excessive unchanging movement (i.e.
trees, streets and freeways) to avoid recording non-applicable items.
3. Cameras located behind staff work areas shall mask out PC monitors and their direct working space.
4. Cameras shall be zoomed out to 100% unless situation requires otherwise.
5. Cameras shall record on motion/AI; sensitivity/parameters shall be coordinated with the owner.
6. Cameras shall send automatic alerts to notify the owner of tamper, loss video, loss connection or other issues.
7. WDR shall be enabled on interior and exterior cameras.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 8 CD SET
8. Cameras shall be set to record 5 seconds of pre and post motion where capturing pedestrians and 10 seconds of pre and post motion where capturing vehicle traffic.
9. Cameras shall be named within the system as follows:
a. S.B.C001.Y where:
1) S = School/Site ID
2) B = Bldg. ID
3) C001 = Camera ID
4) Y (interior camera) = room & location (i.e., N, NW, S, SE, etc.)
5) Y (exterior camera) = location & view
B. Video management software and other software specified herein shall be installed and configured on each server per the manufacturer’s installation guidelines.
1. System is existing.
2. Programming requirements shall be coordinated with the owner and shall be provided at no additional cost to owner.
3. Provide pre-configured default camera view templates for each camera view for the owner to revert to if needed.
C. At the completion of the installation, provide an updated IP device matrix, in Microsoft
Excel format, indicating complete camera information and the horizontal station patch panel port.
3.4 PRE-TESTING
A. After Work is completed, and prior to requesting the acceptance test, Contractor shall conduct a final inspection, and an operational pre-test of all equipment and system features. Contractor shall correct any deficiencies discovered as the result of the inspection and operational pre-test.
B. Submit written notification to the Owner’s Representative and the A/E that systems have been tested, are operating properly, and are ready for Acceptance at least 21 days prior to the requested test date.
3.5 FINAL ACCEPTANCE
A. Acceptance test shall be scheduled during a period when the building is unoccupied and a complete system test can be accomplished.
B. Contractor shall provide the services of no fewer than two (2) skilled technicians to perform the acceptance test. Technicians performing the acceptance test shall have been involved in the programming and installation of this project and shall be thoroughly familiar with all aspects of the Work. Technicians shall be equipped with portable two-way radios that will be used during the test.
C. Contractor shall provide all ladders, tools, test equipment, and other facilities needed to accomplish the Acceptance test.
D. During acceptance test, Contractor shall demonstrate all equipment, system features and camera views to the Owner. Contractor shall fully cooperate with the Owner and provide assistance with the inspection and test. Contractor shall remove and reinstall covers, open and restore wiring connections, operate equipment, and perform other reasonable work as requested by the Owner.
PIERCE COUNTY
ANNEX EVSE SERVICE 282300 - 9 CD SET
E. Any portions of the Work found to be deficient or not in compliance with the Contract
Documents will be rejected. Owner will record any such deficiencies observed during the
Acceptance test. A copy of said list will be provided to Contractor and all deficiencies shall promptly be corrected.
3.6 POST SYSTEM TESTING
A. Post system testing shall be completed 45 days after final acceptance is achieved to verify system function.
B. The post system process includes testing that is intended to test system function under operational conditions. The Contractor shall provide the required labor, materials, and test equipment to perform the tests. Technicians performing the post system test shall have been involved in the programming and installation of this project and shall be thoroughly familiar with all aspects of the Work. The Contractor and Owner will conduct and document the testing, upon acceptance the Owner shall sign the test report to verify tests were performed.
C. Post system testing shall include verification of, but not limited to:
1. Quality of video on client PC with 4x4 camera views for live and recorded viewing.
2. Verify exterior cameras are masked for areas with excessive unchanging movement, i.e. trees across the street and roadways to avoid recording non-applicable items.
3. Cameras are configured to record on motion and sensitivity is appropriate.
4. Cameras are sending automatic tamper alerts & loss video alerts.
5. Camera analytics are configured properly to record/send alert.
6. WDR is enabled on interior and exterior cameras.
7. Cameras are using proper H.264/5 compression. Coordinate with Owner.
8. Cameras are set to use variable frame rates.
9. Live and/or recording resolutions are set accordingly.
10. Cameras are zoomed out at 100% and focused.
11. Frame rate settings in no motion and motion observed.
12. Camera settings for pre and post motion retention on recording.
13. Interior cameras located behind staff work areas mask out PC monitors and their direct working space.
14. Monitoring from an offsite location.
15. System is configured with the camera “maps” that will illustrate the location of each camera based upon a graphical depiction of the space served.
16. Recorders are load balanced.
17. Retention and archive settings.
18. Programming adjustments shall correct any Owner issues experienced over the past 45 days.
3.7 WARRANTY AND…