2026-10-21_Hangar_#1_&_2_-_Roof_Replacement_Bid_Set.pdf
PDF 7 MB Posted
- Attached to
- Hangars 1 and 2 Roof Replacement
- Solicitation number
- 001-2027
- Issued by
- Florida
About this file
This is a bid set document prepared by Passero Associates for the City of Lake City, Florida, for the replacement of roofing systems on Hangars 1 and 2 located at 102 SE Academic Avenue, Lake City, Florida. The project involves complete demolition and replacement of existing metal roof panels, purlins, gutters, and downspouts on two aircraft hangars at Lake City Gateway Airport. The work is divided into four bid areas: Roof Area A (Storage), Roof Area B (Hangar #1), Roof Area C (Office), and Roof Area D (Hangar #2). Each bid item includes demolition, new 22-gauge standing seam metal roof panels, new steel purlins spaced approximately 5 feet on center, new metal gutters and downspouts, flashing, trim, and temporary removal or replacement of interior and roof equipment. The project is phased to minimize operational impact to the airport, with Phase One addressing Roof Areas A and B and Phase Two addressing Roof Areas C and D, with a maximum construction timeline of 240 calendar days. The site is located on the airside of a secured airport requiring special security access, escort requirements for deliveries, and badged workers. Bids were to be received by the City through the OpenGov e-Procurement Portal by November 19, 2026 at 2:00 PM local time, with bid opening occurring at 2:15 PM the same day.
The specifications require compliance with the 2023 Florida Building Code, Factory Mutual (FM) Global Standards 1-28, 1-29, and 1-31, and ASCE 7 wind load requirements. The contractor must provide delegated design calculations for the roof system and purlins, which must be within 5 percent of the weight of the existing system, and submit existing roof system weight verification through core sampling. The contractor is responsible for all permits, approvals, site safety, temporary shoring, haul route stabilization and restoration, waste disposal via contractor-supplied dumpster, and daily site cleanup. The project documents include architectural, structural, and civil drawings with detailed specifications sections. Contractors were required to visit the site prior to bidding to verify existing conditions and coordinate staging areas with the owner and tenants. The owner will provide suitable fill material, with the contractor responsible for handling and hauling from a distance of up to 2.5 miles. All materials and labor costs, including mobilization, barricade installation and maintenance, temporary access roads, and equipment are to be included in the bid price.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Hangars_1_and_2_Roof_Replacement.pdf | ||
| Hangars_1_&_2_Roof_Technical_Specifications.pdf | ||
| General_Provisions.pdf | ||
| LCQ_AAR_Hangars_1_&_2_BID_DOCUMENTS.docx | DOCX document | |
| LCQ_AAR_Hangars_1_&_2_Price_Form.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B C
D
PROJECT
LOCATION
GENERAL
G-001 SYMBOLS & DETAILS
G-002 SITE USE PLAN
G-003 BID PLAN
CIVIL
C-100 CONSTRUCTION SAFETY & PHASING PLAN
ARCHITECTURAL
AD-100 OVERALL DEMOLITION ROOF PLAN
A-100 OVERALL ROOF PLAN
A-300 OVERALL BUILDING SECTION & DETAILS
STRUCTURAL
S-001 GENERAL NOTES AND DESIGN CRITERIA
VICINITY MAP:
DRAWING INDEX:
CLIENT:
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
ARCHITECTURAL & STRUCTURAL:
LOCATION MAP:
HANGAR #1 & 2 - ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
LAKE CITY, FL 32025
OCTOBER 21, 2026
CONTRACT DOCUMENTS FOR:
CITY OF LAKE CITY
205 N. MARION AVENUE
LAKE CITY, FL 32055
BID SET
20070044.A037
PROJECT
LOCATION
N
EARTH/COMPACT FILL
ROCK
BRICK (PLAN/SECTION)
METALS (SECTION)
PLYWOOD
BATT/LOOSE INSUL.
GLASS (ELEVATION)
POROUS FILL/GRAVEL
(PLANS/SECTIONS)
CONCRETE
BRICK (ELEVATION)
WOOD, FINISHED
GLASS BLOCK
CERAMIC TILE (ELEV)
(AROUND MEMBER)
SPRAY FIREPROOF
PLASTER(SECT.)
SAND/MORTAR
CONCRETE BLK.
(SECTION)
WOOD BLOCKING
RIGID INSUL.
EIFS (ELEV.)
PLASTER/PLAS BD.
ARCHITECTURAL ROOF
SHINGLES
XXX
XXX
XXX
A
102A
X#.#
COLUMN NO. (NEW)
FIRST FLR.
0.00'
WORK POINT
ELEV/FIN. FLOOR, ROOF)
CENTER LINE
WINDOW/FRAME TYPE
DOOR NUMBER
REVISION
WALL TYPE
ROOM
NAME/NUMBER
INDICATOR
1 COLUMN NO. (EXISTING)
# HR FIRE RATING
X#.# WALL TYPE ONLY
N
8 A600
INTERIOR ELEVATION INDICATOR
ELEV. NUMBER
SHEET LOCATED
INDICATED # OF VIEW
A300
NO. OF SECTION
SHEET LOCATED ON
WALL SECTION INDICATOR
19'
A600
NORTH ARROW
NO. OF SECTION
PLAN DETAILS
SHEET LOCATED ON
NEW DOOR
EXISTING DOOR
DOOR REMOVED
REVISION
PLACE W/ DATE IN REVISED
PORTION OF SHT.
PLAN DETAIL INDICATOR
GRAPHIC SYMBOLS
ABBREVIATIONS
MATERIALS SYMBOLS
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
G-001
SYMBOLS & DETAILS
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET
# NUMBER
& AND
@ AT
± PLUS OR MINUS
≈ ALMOST EQUALT TO
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACT ACOUSTICAL TILE
AD ACCESS DOOR
ADD. ADDENDUM
ADJ. ADJACENT
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ATTN ATTENUATION
AUTO AUTOMATIC
BC BRICK COURSE
BD BOARD
BEJ BRICK EXPANS, JOINT
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRK BRICK
BSMT BASEMENT
BUR BUILT-UP ROOFING
CAB CABINET
CG CORNER GUARD
CH CABINET HEATER
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLL CONTACT LIMIT LINE
THE ARCHITECT CERTIFIES TO THE BEST OF THEIR KNOWLEDGE AND BELIEF, THE PLANS AND SPECIFICATIONS ARE IN ACCORDANCE WITH THE
APPLICABLE REQUIREMENTS OF THE "FLORIDA BUILDING CODE".
BUILDING NOTES DURING CONSTRUCTION:
CONTRACTOR SHALL FOLLOW THE FLORIDA BUILDING CODE. THEY SHALL COMPLY WITH CHAPTER 33 "SAFEGUARDS DURING CONSTRUCTION" OF FLORIDA BUILDING CODE. THIS SECTION COVERS SAFETY DURING CONSTRUCTION AND THE PROTECTION OF ADJACENT PUBLIC AND PRIVATE PROPERTIES. THE ARCHITECT IS NOT RESPONSIBLE FOR ENFORCING THIS ON THE CONTRACTOR.
ARCHITECT'S CERTIFICATION
CLR CLEAR
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CNTOR CONTRACTOR
CNTR COUNTER
COL COLUMN
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOS
CPT CARPET
CRS COURSE
CS COUNTER SINK
CSW CASEWORK
CT CERAMIC TILE
CTR CENTER
CW COLD WATER
DBL DOUBLE
DEMO DEMOLISH
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DN DOWN
DO DITTO
DR DOOR
DS DOWNSPOUT
DWG DRAWING
EA EACH
EATD EXIT ACCESS TRAVEL DISTANCE
EERO EMERGENCY ESCAPE & RESCUE
OPENING
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMERG EMERGENCY
ENCL ENCLOSURE
EO EQUIPMENT BY OWNER
EPDM ETHYLENE PROPYLEYNE DIENE
M-CLASS (ROOFING)
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXF EXHAUST FAN
EXIST EXISTING
EXP EXPANSION
EXPD EXPOSED
EXT EXTERIOR
EXTN EXTENSION
FA FIRE ALARM
FACT FACTORY
FBC FURNISHED BY CONTRACTOR
FBO FURNISHED BY OWNER
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FF FINISHED FACE OR FINISHED
FLOOR
FIN FINISHED
FIXT FIXTURE
FL FLUSH
FLR FLOOR
FO FRAME OPENING
FP FIRE PROOFING
FR FIRE RESISTANT
FT FOOT
FTG FOOTING
FUR FURRING
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GL GLASS
GWB GYPSUM WALL BOARD
GYP GYPSUM WALL OR CEILING
BOARD
HDCP HANDICAP
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATION AIR
CONDITIONING
HVI HEARING & VISUALLY IMPAIRED
IBC INTERNATIONAL BUILDING CODE
OR INSTALLED BY CONTRACTOR
ID INSIDE DIAMETER
ILO IN LIEU OF
INS. GL INSULATED GLAZING
INSUL INSULATION
INT INTERIOR
INV INVERT
IRGWB IMPACT RESISTANT GYPSUM
WALL BOARD
JAN JANITOR
JT JOINT
LAM LAMINATED
LAV LAVATORY
LEN LENGTH
LF LINEAR FEET
LGT LIGHT
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION
LP LOW POINT
LTWT LIGHT WEIGHT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MHP MOP HOPPER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODULAR
MRGWB MOISTURE RESISTANT GYPSUM
WALL BOARD
MTL METAL
MTP METAL TOILET PARTITION
NAT NATURAL
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFICIENT
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
PBD PARTICLE BOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FEET
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLF POUNDS PER LINEAR FEET
PLGL PLATE GLASS
PLUMB PLUMBING
PLYWD PLYWOOD
PN PANEL
PNT PAINTED
POL POLISHED
PPGL POLISHED PLATE GLASS
PR PRIMED
PREF PREFINISHED
PREFAB PREFABRICATED
PROJ PROJECTION
PSF POUNDS PER SQUARE FEET
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA RETURN AIR
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RECPT RECEPTACLE (ELECTRIC)
REF REFERENCE
REQD REQUIRED
RESIL RESILIENT
RET RETURN
REV REVISION, REVISED
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
RW RIGHT OF WAY
SD SMOKE DETECTOR, STORM
DRAIN
SECT SECTION
SHT SHEET
SIM SIMILAR
SP STAND PIPE
SPEC SPECIFIED, SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS SERVICE SINK
SSTL STAINLESS STEEL
STC SOUND TRANSMISSION
COEFFICIEN
STD STANDARD
STL STEEL
STORM STORM SEWER
STRUCT STRUCTURAL
SUSP SUSPENDED
SW SWITCH
SYM SYMMETRICAL
T&G TONGUE AND GROOVE
TB TACKBOARD
TEL, TELE TELEPHONE
TEMP TEMPERATURE, TEMPORARY
TEMPGL TEMPERED GLASS
TEX TEXTURE
THK THICKNESS
TME TO MATCH EXISTING
TOIL TOILET
TOS TOP OF STEEL
TOW TOP OF WALL
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UR URINAL
VCT VINYL COMPOSITION TILE
VENT VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VP VISION PANEL
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WGL WIRE GLASS
WGT WEIGHT
WR WATER REPELLANT
WS WEATHER STRIP
WSCT WAINSCOT
WWF WELDED WIRE FABRIC
YD YARD
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
THE PLANS ARE BASED UPON INFORMATION FURNISHED TO THE ARCHITECT BY THE OWNER, CONSISTING OF DRAWINGS PREPARED BY OTHERS, THESE PLANS HAVE BEEN MODIFIED TO REFLECT ACTUAL CONDITIONS BASED ON LIMITED FIELD OBSERVATIONS. TO THE BEST OF THE ARCHITECT'S KNOWLEDGE AND BELIEF, THE INFORMATION ON THESE DRAWINGS IS BELIEVED TO BE ACCURATE. THE ARCHITECT DOES
NOT GUARANTEE ITS ACCURACY.
WHERE SURFACES ARE TO BE REPLACED, SURFACES THAT ARE TO REMAIN SHALL BE REPAIRED AND PATCHED. THE CONTRACTOR SHALL PREPARE EXISTING CONDITIONS TO RECEIVE NEW WORK AND MATCH EXISTING ADJACENT SURFACES.
ANY DISRUPTION IN THE CONTINUITY OF EXISTING UTILITY LINES WITHIN THE FACILITIES SITE SHALL BE COORDINATED WITH OWNER. REFER
TO SPECIFICATION SECTION 01 10 00 - SUMMARY.
GENERAL CONTRACTOR AND SUBCONTRACTORS SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE REQUIREMENTS OF
APPLICABLE LAWS, CODES, REGULATIONS, SAFETY STANDARDS.
THIS CONTRACT REQUIRES COMPLETE, FINISHED WORKABLE PROJECT OF THE AREAS INDICATED BY THE CONTRACT DOCUMENTS, AND SHALL INCLUDE ALL MATERIALS AND LABOR NECESSARY TO COMPLETE SAME, REGARDLESS OF WHETHER OR NOT EACH AND EVERY NECESSARY WORK OR ITEM IS SPECIFICALLY INDICATED ON ANY OTHER PORTION OF THE DRAWING AND/OR NOTES.
CONTRACTOR SHALL COORDINATE STAGING AREAS WITH OWNER.
THE CONTRACTOR SHALL MAINTAIN A SAFE ENVIRONMENT DURING ALL PHASES OF CONSTRUCTION.
THE CONTRACTOR SHALL CLEAR THE PROJECT SITE OF ALL TRASH, RUBBISH AND DEBRIS DAILY. DISPOSE OF ALL WASTE MATERIAL IN A LEGAL MANNER. CONTRACTOR SHALL SUPPLY HIS OWN DUMPSTER AT LOCATION AS DIRECTED BY OWNER.
THE CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF OTHER SYSTEMS INSIDE THE SCOPE OF WORK DURING CONSTRUCTION.
DUE TO THE NATURE OF WORK INVOLVED IN REMODELING, UNFORESEEABLE CONDITIONS MAY ARISE DURING CONSTRUCTION. ANY UNFORESEEN CONDITION THAT AFFECTS THE PROGRESS OF THE WORK SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT FOR REVIEW.
ANY EXISTING EQUIPMENT OR BUILDING COMPONENTS NOT TO BE REUSED MUST BE COMPLETELY REMOVED AND DISPOSED OF
PROPERLY.
NO ANIMALS ALLOWED ON THE JOB SITE.
1.
2.
3.
4.
5.
6.
7.
8.
9.
CONTRACTOR SHALL PROVIDE THEIR OWN DUMPSTER FOR TRASH REMOVAL FROM ALL TRADES AND ALL WORK RELATING TO THIS PROJECT. THE CONTRACTOR SHALL NOT BE ALLOWED TO USE EXISTING DUMPSTER ON SITE. DEMOLITION DEBRIS SHALL BE DISPOSED STRICTLY IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL AUTHORITIES REQUIREMENTS.
DO NOT SAW CUT INTO OR REMOVE STRUCTURAL WALLS, COLUMNS AND BEAMS. EXPOSE ALL STRUCTURAL LOAD BEARING
CONDITIONS FOR ARCHITECT'S OBSERVATION.
IF DURING DEMOLITION, THE EXISTING STRUCTURE IS FOUND TO CONTAIN ASBESTOS OR LEAD, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COMPLY WITH THE PROVISIONS OF LOCAL STATUTES AND TO NOTIFY THE DEPARTMENT OF ENVIRONMENTAL PROTECTION OF THEIR INTENTIONS TO REMOVE ASBESTOS AND/OR LEAD, WHEN APPLICABLE, AND IN ACCORDANCE WITH STATE AND
FEDERAL LAW.
CONTRACTOR SHALL OBTAIN ALL NECESSARY APPROVALS AND/OR PERMITS BEFORE COMMENCING WORK FROM PROPER
AUTHORITIES HAVING JURISDICTION.
THE DEMOLITION PLANS ARE GENERAL IN NATURE AND DO NOT ATTEMPT TO INDICATE SMALLER INDIVIDUAL ITEMS WHICH MAY ALSO NEED TO BE REMOVED. THEREFORE, THE CONTRACTOR SHALL VISIT THE SITE TO DETERMINE WHETHER SUCH NON-SPECIFIED ITEMS EXIST AND ARE TO BE REMOVED TO ACHIEVE THE OVERALL INTENT. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS INCLUDING STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING, AND REPORT ANY DISCREPANCIES TO
THE ARCHITECT.
DURING DEMOLITION THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFE STABILITY OF THE STRUCTURE UNTIL THE OPERATION IS COMPLETE. ANY OBSERVATION BY THE ARCHITECT DOES NOT RELIEVE THE CONTRACTOR FROM THEIR
RESPONSIBILITY TO PROVIDE FOR SAFETY AND PROTECTION OF PERSONS AND PROPERTY.
PROTECT ALL EXISTING AREAS AND/OR ITEMS NOT INCLUDED FOR DEMOLITION FROM DUST AND DAMAGE, BY USE OF WATER MISTING, TEMPORARY ENCLOSURES OR OTHER SUITABLE METHODS. ANY DAMAGE OCCURRING DURING DEMOLITION SHALL BE FIXED OR REPLACED BY THE CONTRACTOR TO THE SATISFACTION OF THE ARCHITECT, TO MATCH EXISTING AT NO
ADDITIONAL COST TO THE OWNER.
CONTRACTOR IS ADVISED THAT THERE MAY BE CONCEALED PIPELINES, ELECTRICAL, TELEPHONE, CABLE WIRES, COLUMNS, BEAMS OR OTHER STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING ITEMS, ETC. ALTHOUGH THE DOCUMENTS PRODUCED BY THE ARCHITECT AND ENGINEERS ARE BELIEVED TO BE SUBSTANTIALLY CORRECT. THE ARCHITECT, ENGINEERS AND OWNER DO NOT GUARANTEE THE LOCATION OR EXISTENCE OR CONDITION OF ANY CONCEALED ITEMS. CONTRACTOR MUST PROCEED WITH CAUTION DURING DEMOLITION AND MUST MAKE THEIR OWN DETERMINATION, MEASUREMENTS AND EVALUATION OF THE WORKING CONDITION OF EXISTING CONCEALED ITEMS. ANY ENVIRONMENTALLY SENSITIVE MATERIAL, ENCOUNTERED DURING DEMOLITION SHALL BE REPORTED IN WRITING TO OWNER AND DISPOSED OF IN ACCORDANCE WITH
STATE AND FEDERAL REGULATIONS.
PRIOR TO DEMOLITION THE CONTRACTOR SHALL WALK THE SITE AND PROVIDE A WRITTEN LIST, PHOTOGRAPHS AND/OR VIDEOTAPES OF ANY DAMAGE TO EXISTING FINISHES, MISSING EQUIPMENT, NON-OPERABLE EQUIPMENT, ANY WATER DAMAGE, ETC.
GENERAL DEMOLITION NOTES:
A.
B.
C.
D.
E.
F.
A.
B.
C.
D.
E.
F.
G.
H.
FIRE PROTECTION DURING CONSTRUCTION:
FIRE PROTECTION DURING CONSTRUCTION - INTERNATIONAL FIRE CODE LATEST EDITION:
STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS, INCLUDING THOSE IN UNDERGROUND LOCATIONS, SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS, AND CHAPTER 33 OF THE INTERNATIONAL BUILDING CODE.
THE SUITABILITY, DISRUPTION, AND MAINTENANCE OF EXTINGUISHERS SHALL BE IN ACCORDANCE WITH NFPA 10 AND SECTION 3315.
[241:4.10.1] AT LEAST ONE APPROVED FIRE EXTINGUISHER ALSO SHALL BE PROVIDED IN PLAIN SIGHT ON EACH FLOOR AT EACH USABLE STAIRWAY AS
SOON AS SIGNIFICANT COMBUSTIBLE MATERIAL IS PRESENT. [241:4.10.4]
SUITABLE FIRE EXTINGUISHERS SHALL BE PROVIDED ON SELF-PROPELLED EQUIPMENT. [241:4.10.5] FREE ACCESS TO PERMANENT, TEMPORARY, OR PORTABLE FIRST-AID FIRE EQUIPMENT SHALL BE MAINTAINED AT ALL TIMES [241:4.10.6] A WATER SUPPLY FOR FIRE PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS SIGNIFICANT
COMBUSTIBLE MATERIAL IS PRESENT. [241:6.3.1]
FLAMMABLE AND COMBUSTIBLE LIQUIDS AND FLAMMABLE GASES - INTERNATIONAL FIRE CODE LATEST EDITION:
STORAGE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS SHALL BE IN ACCORDANCE WITH NFPA CHAPTER 30, UNLESS OTHERWISE MODIFIED
BY THIS SECTION. [241:7.8.1.1]
STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GAL. (227 L) WITHIN 50 FT (15 M) OF THE STRUCTURE. [241:7.8.1.2] STORAGE AREAS SHALL BE KEPT FREE OF WEEDS, DEBRIS, AND COMBUSTIBLE MATERIAL NOT NECESSARY TO THE STORAGE. [241:7.8.1.3] OPEN FLAMES AND SMOKING SHALL NOT BE PERMITTED IN FLAMMABLE AND COMBUSTIBLE LIQUIDS STORAGE AREAS. [241:7.8.1.4] SUCH STORAGE AREAS SHALL BE APPROPRIATELY POSTED AS "NO SMOKING" AREAS. [241:7.8.1.5]
STORAGE AREAS SHALL BE APPROPRIATELY POSTED AS "NO SMOKING" AREAS. [242:7.8.1.6]
CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS. [241:7.8.2.2] CLASS I LIQUIDS SHALL BE DISPENSED ONLY WHERE THERE ARE NO OPEN FLAMES OR OTHER SOURCES OF IGNITION WITHIN THE POSSIBLE
PATH OF VAPOR TRAVEL. [241:7.8.2.4]
GENERAL NOTES:
BIDDERS GENERAL NOTES:
1.
2.
3.
4.
BIDDERS SHALL REVIEW DOCUMENTS INDEX AND VERIFY THAT THEY HAVE RECEIVED ALL COPIES OF ALL DOCUMENTS. DO NOT BID THE PROJECT OR COMMENCE CONSTRUCTION WITHOUT HAVING A COMPLETE SET OF DOCUMENTS.
BIDDERS SHALL PROMPTLY NOTIFY THE ARCHITECT IN WRITING OF ANY AMBIGUITY, INCONSISTENCY, OR ERRORS WHICH THEY MAY DISCOVER UPON EXAMINATION OF THE BIDDING DOCUMENTS. DO NOT BID OR PROCEED IN AREAS OF DISCREPANCIES
UNTIL ALL SUCH DISCREPANCIES ARE FULLY RESOLVED.
PRIOR TO SUBMITTING BIDS, THE CONTRACTOR SHALL VISIT THE JOB SITE TO FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS.
THEY SHALL IMMEDIATELY NOTIFY THE ARCHITECT, IN WRITING, OF ANY DISCREPANCIES OR INCONSISTENCIES EXISTING. FAILURE TO VERIFY THE EXISTING CONDITIONS SHALL NOT RELIEVE THE CONTRACTOR OF ANY EXPENSES OR RESPONSIBILITIES RESULTING
FROM THAT FAILURE.
THE CONTRACTOR SHALL INCLUDE IN THEIR BID ALL COSTS ASSOCIATED WITH MATERIAL, HANDLING, STORAGE, AND DELIVERY.
FIRE PROTECTION DURING CONSTRUCTION:
NO. DATE BY DESCRIPTION
DEMOLITION PHASING GENERAL NOTES:
1.
2.
A.
B.
C.
D.
E.
IMPORTANT: THIS SITE IS LOCATED ON THE AIRSIDE OF A SECURED
AIRPORT THEREFORE SPECIAL SECURITY REQUIREMENTS SHALL BE
REQUIRED TO GAIN ACCESS THROUGH THE SECURITY GATES
INCLUDING THE REQUIREMENTS OF ESCORTS FOR DELIVERIES AND THE
SITE SHALL REMAIN SECURE AT ALL TIMES. REFER TO C-100 FOR MORE
SITE INFORMATION.
NOTE: IN COMPANY WITH THE OWNER, OR ITS REPRESENTATIVE, VISIT
THE SITE AND VERIFY THE EXTENT AND LOCATION OF SELECTIVE
DEMOLITION REQUIRED.
CAREFULLY IDENTIFY LIMITS OF SELECTIVE DEMOLITION.
MARK INTERFACE SURFACES AS REQUIRED TO ENABLE WORKERS TO
ALSO IDENTIFY ITEMS TO BE REMOVED AND ITEMS TO BE LEFT IN
PLACE INTACT.
TAKE PHOTOGRAPHIC RECORDS OF ALL ADJACENT SURFACES TO
REMAIN.
ALL REQUIRED APPROVALS, BUILDING AND OTHER PERMITS FROM
PROPER AUTHORITIES HAVING JURISDICTION IN CONNECTION
WITH THE CONSTRUCTION AND COMPLETION OF THIS PROJECT IS
THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO INSURE THAT
ALL CONSTRUCTION IS PERFORMED IN THE STRICTEST COMPLIANCE
INCLUDING CONSTRUCTION DOCUMENTS FOR PERMITTING AND
SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE
REQUIREMENTS OF APPLICABLE LAWS, CODES, REGULATIONS, ADA,
LIFE SAFETY AND STANDARDS.
HANGAR #8
(FOR
REFERENCE
ONLY)
HANGAR #3
(FOR REFERENCE ONLY)
HANGAR #5
(FOR REFERENCE ONLY)
SE
T
IM
BE
RW
O
LF
D
RI
V
E
A-102
AREA
OF
WORK
HANGAR #2
HANGAR #1
STAGING AREAS:
FINAL STAGING AREA TO
BE COORDINATED WITH
OWNER AND TENANT
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
G-002
SITE USE PLAN
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET
1" = 100'-0"1 SITE USE PLANN
A
B
C
D
BID PLAN GENERAL NOTES:
1.
2.
3.
4.
5.
THIS SHEET IS FOR BIDDING PURPOSES ONLY. IT GENERALLY DEPICTS
ROOF AREAS A, B, C, AND D AS THEY CORRESPOND TO THE BID ITEMS
ON THE PRICE FORM.
ROOF AREA BOUNDARIES ARE APPROXIMATE AND DO NOT DEFINE THE
SCOPE OF WORK. REFER TO DRAWINGS AND SPECIFICATIONS FOR THE
COMPLETE SCOPE.
EACH BID ITEM SHALL INCLUDE ALL WORK WITHIN THE ASSOCIATED
ROOF AREA, INCLUDING DEMOLITION, NEW ROOF PANELS, FLASHING,
TRIM, GUTTERS, DOWNSPOUTS, PURLIN REPLACEMENT, ACCESSORIES,
AND TEMPORARY REMOVAL/SHORING/REPLACEMENT OF INTERIOR
AND ROOF EQUIPMENT, UNLESS NOTED OTHERWISE.
WHERE ROOF AREAS MEET, INCLUDE IN EACH BID ITEM ALL FLASHING,
TRIM, AND TERMINATIONS REQUIRED TO MAKE THAT AREA COMPLETE
AND WEATHERTIGHT WHETHER OR NOT ADJACENT AREAS ARE
AWARDED.
ALTERNATE NO. 1 (ACCELERATED BUILDING SHUTDOWN) APPLIES TO
ALL ROOF AREAS. REFER TO SECTION 01 23 00.
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
G-003
BID PLAN
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET0' 8' 16' 32' 64'
1/32" = 1'-0"
1 BID PLANN
TAXIWAY D
TA
XI
W
AY
E
HANGAR #8
(FOR
REFERENCE
ONLY)
HANGAR #3
(FOR REFERENCE ONLY)
HANGAR #4
(FOR REFERENCE ONLY)
HANGAR #6
(FOR REFERENCE ONLY)
HANGAR #5
(FOR REFERENCE ONLY)
HANGAR #9
(FOR REFERENCE ONLY)
SE
T
IM
BE
RW
O
LF
D
RI
V
E
EXISTING 500,000 GAL
GROUND WATER
STORAGE TANK
EXISTING PUMP HOUSE
A
B
D
PROPOSED
WORK AREA
A-102
SE
A
CADEM
IC
A
VE
SE
F
O
UN
D A
TIO
N
P L
SE
T
IM
BE
RW
O
LF
D
RI
V
E
SE
C
O
LL
EG
E
PL
HANGAR #2
HANGAR #1
C
CFM56-5B
CFM56-5B
A321-100
A321-100
CFM
56-5B
CFM
56-5B
A321-100
A3
-1
CFM56-5B
CFM56-5B
A321-100
A32 1-
C
FM
56-5B
C
FM
56-5B
A321-100
A3
-1
HANGAR 1
STAGING AREA
HANGAR 2
STAGING AREA
P2
P3
P4
B2-2
P1
B2-3
B2-1
B1-1
B1-2
B2-4 L1
S1
B1-3
B1-4
S1
BARRICADE TO BE MOVED DURING
DELIVERY AND PLACED BACK AFTER
NO MOVEMENT
BEYOND HOLD BARS
MINIMUM 30'
BUFFER
ALL WORKERS SHALL BE BADGED
AND DELIVERY TRUCKS SHALL BE
ESCORTED
LEVEL 1
+0' - 0"
ROOF
+59' - 6"
HANGAR EAVE
+34' - 6"
D C B A
OFFICE EAVE
+26' - 4"
STORAGE EAVE
+18' - 8"
TOWER, V.I.F.
+71' - 6"
LEGEND:
LOW PROFILE BARRICADE, HANGAR 1,
(SEE MISCELLANEOUS DETAILS)
LOW PROFILE BARRICADE, HANGAR 2,
(SEE MISCELLANEOUS DETAILS)
CONTRACTOR HANGAR 1 ACCESS /
ON & OFF-SITE HAUL ROUTE
CONTRACTOR HANGAR 2 ACCESS /
ON & OFF-SITE HAUL ROUTE
CONTRACTOR STAGING AREA
HANGAR 2 ROOF REPLACEMENT AREA
HANGAR 1 ROOF REPLACEMENT AREA
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
(904) 757-6106
AAR AIRFRAME MRO
102 ACADEMIC AVENUE
LAKE CITY , FL 32025
NO. DATE BY DESCRIPTION
C-100
CONSTRUCTION
SAFETY & PHASING
PLAN
20070044.A037
OCTOBER 9, 2026
AAR HANGARS
RE-ROOF
LAKE CITY
COLUMBIA, FLORIDA
LAKE CITY
GATEWAY AIRPORT
LAKE CITY
COLUMBIA COUNTY, FLORIDA
Project Manager Principal-in-Charge
Project Architect
Designed by
B. WENTE
J. RAY
A. VOLLENWEIDER, A.I.A.
B. BRADLEY, P.E.
GENERAL PHASING NOTES:
1. THE PROJECT DOES NOT REQUIRE AND AIRFIELD FACILITY CLOSURES. CONTRACTOR
SHALL COORDINATE THE START OF CONSTRUCTION WITH THE OWNER FOR THE
ISSUANCE OF REQUIRED NOTAMS DURING THE COURSE OF THIS PROJECT.
CONTRACTOR SHALL COORDINATE THE STAGING AREA LOCATION WITH THE OWNER
IF WORK IS TO BE PERFORMED DURING THE FIRE SEASON, WHICH GENERALLY
OCCURS DURING THE SUMMER MONTHS.
2. THE INTENT OF THIS CONTRACT IS TO COMPLETE THE PROJECT WITH A MINIMAL
AMOUNT OF OPERATIONAL IMPACT TO THE AIRPORT. NO RUNWAY, TAXIWAY,
APRON, OR AIRPORT ROADWAY SHALL BE CLOSED.
3. THE CONTRACTOR SHALL STABILIZE, MAINTAIN, AND REMOVE, WHEN NO LONGER
NEEDED, ALL TEMPORARY ACCESS AND HAUL ROADS REQUIRED TO FULFILL THE
CONTRACT. THE AFFECTED AREAS SHALL BE RESTORED PRIOR TO FINAL
ACCEPTANCE.
4. AT THE COMPLETION OF EACH DAY'S WORK, THE CONTRACTOR SHALL REMOVE ANY
EQUIPMENT AND CLEAN THE WORK AREA TO REMOVE ANY DEBRIS TO THE
SATISFACTION OF THE ENGINEER AND OWNER.
5. ALL REQUIRED MAINTENANCE AND PROTECTION OF TRAFFIC DEVICES SHALL BE
INSTALLED AND APPROVED BY THE ENGINEER PRIOR TO STARTING WORK.
6. THE CONTRACTOR SHALL STABILIZE AND MAINTAIN THE TEMPORARY ON-SITE HAUL
ROUTES AND PROVIDE FOR ANY TEMPORARY DITCH/WET AREA CROSSINGS THAT
MAY BE REQUIRED. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
COORDINATE OFF-SITE HAUL ROUTES WITH THE APPROPRIATE OWNERS WHO HAVE
JURISDICTION OVER THEM TO OBTAIN ANY REQUIRED PERMIT. ON-SITE HAUL
ROUTES SHALL BE RESTORED TO ITS ORIGINAL CONDITIONS TO THE SATISFACTION
OF THE OWNER. THE COST FOR THE HAUL ROUTES SHALL BE INCLUDED IN ITEM
101.
7. THE OWNER WILL PROVIDE SUITABLE FILL NEEDED FOR THIS PROJECT. THE
CONTRACTOR WILL BE RESPONSIBLE FOR HANDLING AND HAULING THE MATERIAL
TO THE PROJECT SITE FROM A DISTANCE OF 2.5 MILES.
8. CONTRACTOR SHALL TEST STOCKPILE MATERIAL FOR SUITABILITY
DEMOLITION PHASING GENERAL NOTES:
1. IMPORTANT: SITE IS TO REMAIN SECURE AT ALL TIMES.
2. NOTE: IN COMPANY WITH THE OWNER, OR ITS
REPRESENTATIVE, VISIT THE SITE AND
VERIFY THE EXTENT AND LOCATION OF
SELECTIVE DEMOLITION REQUIRED.
A. CAREFULLY IDENTIFY LIMITS OF SELECTIVE DEMOLITION.
B. MARK INTERFACE SURFACES AS REQUIRED TO ENABLE
WORKERS TO ALSO IDENTIFY ITEMS TO BE REMOVED AND
ITEMS TO BE LEFT IN PLACE INTACT.
PROJECT PHASING:
PHASE ONE:
1. DEMOLISH AND RE-ROOF STORAGE (ROOF A) & HANGAR #1
(ROOF B).
PHASE TWO:
1. DEMOLISH AND RE-ROOF OFFICE (ROOF C) & HANGAR #2
(ROOF D).
*Construction time shall not exceed two hundred forty (240)* calendar days.
RED FLASHING SOLAR LIGHT W/
BATTERIES
(ONE REQUIRED)
(TO BE PROVIDED AND
MAINTAINED BY CONTRACTOR)
10-INCH X 10-INCH X 96-INCH LENGTH ORANGE AND WHITE
HDPE BARRIER OR APPROVED ALTERNATE AS DECIDED BY
THE AIRPORT.
12-INCH X 12-INCH BRIGHT ORANGE NYLON FLAG WITH 12
GA. DIAGONAL WIRE STIFFENER TOP SHALL BE MAX. 24-INCH
ABOVE PAVEMENT
(ONE FLAG PER UNIT - TYPICAL)
NOTES:
1. CONTRACTOR SHALL PROVIDE THE NECESSARY AMOUNT FOR
NEW LOW PROFILE BARRICADES, PLACE, MAINTAIN AND
REMOVE BARRICADES AS REQUIRED.
2. WATER BALLASTED LIGHTED SAFETY/CONSTRUCTION
BARRICADES SHALL BE ORANGE AND WHITE ALTERNATED EACH
8 FEET LONG, AR10X96 HDPE SPN OR APPROVED EQUIVALENT.
BARRICADES SHALL HAVE A MAXIMUM 4 FOOT SPACING
BETWEEN THEM. ALL COST FOR PROVIDING, MOVING, LIGHTS,
FLAGS AND MAINTAINING BARRICADES SHALL BE INCIDENTAL TO
THE "MOBILIZATION" ITEM OF WORK.
3. CONTRACTOR TO ALSO FURNISH AND INSTALL SPECIFIED LIGHT
FOR EACH BARRICADE. CONTRACTOR TO PLACE AND MAINTAIN
BARRICADES AND LIGHTS IN ACCORDANCE WITH
CONSTRUCTION SAFETY AND PHASING PLANS, AND PER OWNER
FOR DURATION OF CONTRACT.
4. CONTRACTOR SHALL INSPECT LOW PROFILE BARRICADES DAILY
TO ENSURE NO DISPLACEMENT HAS OCCURRED. CONTRACTOR
SHALL MAINTAIN PROPER BALLAST TO PREVENT BARRICADE
MOVEMENT.
SCALE: NTS
LOW-PROFILE BARRICADE
1" = 50'
1 SOUTH ELEVATION
A-200
AutoCAD SHX Text st
AutoCAD SHX Text st
AutoCAD SHX Text 6"pine
AutoCAD SHX Text 14"pine
AutoCAD SHX Text 12"redmaple
AutoCAD SHX Text 200'
AutoCAD SHX Text 0'
AutoCAD SHX Text 400'
AutoCAD SHX Text
SCALE: 1" = 200'
AutoCAD SHX Text 100'
DEMOLITION SCOPE:
THE EXISTING CONDITION / DEMOLITION DRAWINGS ARE INTENDED AS A
GENERAL GUIDE TO THE DEMOLITION REQUIRED FOR THIS PROJECT.
DEMOLITION IS NOT SHOWN INCOMPLETE DETAIL AND IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO REMOVE EXISTING
CONSTRUCTION AS REQUIRED TO ACCOMPLISH THE DESIGN INTENT FOR
THE WORK SHOWN AND REASONABLY IMPLIED FOR THE PROJECT. REFER TO
THE WORK SHOWN ON ALL OTHER DRAWINGS IN THE SET FOR THE EXTENT
OF THE DEMOLITION REQUIRED TO PERFORM THE WORK INTENT.
GENERAL CONDITIONS:
VISIT THE JOB SITE TO VERIFY EXISTING CONDITIONS AND DIMENSIONS
PRIOR TO BEGINNING ANY WORK. NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES PRIOR TO BEGINNING THE WORK.
QUESTIONABLE ITEMS, INCLUDING BUT NOT LIMITED TO FOUND /
UNKNOWN CONDITIONS AND ITEMS NOT SHOWN / LISTED IN THE
CONTRACT DOCUMENTS, SHALL BE COORDINATED WITH THE
ARCHITECT BEFORE REMOVING.
DEMOLITION PLAN GENERAL NOTES:
USE OF REMOVED ITEMS TO COMPLY WITH SPECIFICATION SECTION
01 60 00, UNLESS NOTED OTHERWISE.
REPAIR EXISTING EXTERIOR METAL PANEL AS REQUIRED.
CONTRACTOR TO VERIFY ALL CONDITIONS PRIOR TO BIDDING AND
DEMOLITION.
DEMOLITION CONTRACTOR SHALL MAKE A SITE VISIT PRIOR TO
SUBMITTING DEMOLITION BID.
ALL REQUIRED APPROVALS, BUILDING AND OTHER PERMITS FROM
PROPER AUTHORITIES HAVING JURISDICTION IN CONNECTION WITH
THE CONSTRUCTION AND COMPLETION OF THIS PROJECT IS THE
SOLE RESPONSIBILITY OF THE CONTRACTOR.
IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO INSURE THAT
ALL CONSTRUCTION IS PERFORMED IN THE STRICTEST COMPLIANCE
INCLUDING CONSTRUCTION DOCUMENTS FOR PERMITTING AND
SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE
REQUIREMENTS OF APPLICABLE LAWS, CODES, REGULATIONS, ADA,
LIFE SAFETY AND STANDARDS.
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17
2-A 2-A
2-B 2-B
1-A 1-A
1-B 1-B
1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 1-12 1-13 1-14 1-151-3.5
1-C 1-C
'-0
0' -0
0' -0
0'
-0
LO
W
R O
O F
'-0
0' -0
0' -0
8'
-0
0'
-0
0'
-0
0'
-0
67'-7" 267'-5"
335'-0"
6'-0" 24'-6" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 24'-6" 5'-0"
410'-0"
24'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 24'-0"
6'-0" 398'-0" 6'-0"
0'
-0
V.I.F.
55'-0"
V .I.
F.
'-0
SL
O
PE
SL
O
PE
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
HANGAR
DOORS
BELOW TO
REMAIN
NOTE: ALL INTERIOR HIGH BAY LIGHTING,
HEATERS, HVLS FANS, FIRE SUPPRESSION
PIPING, FALL PROTECTION, ELECTRICAL
CONDUITS, COMPRESSED AIR PIPING,
AND ANY OTHER ITEMS SUPPORTED FROM
GIRDERS, PURLINS, TO REMAIN.
CONTRACTOR TO PROVIDE TEMPORARY
SUPPORTS DURING RE-ROOFING AND
REPLACEMENT OF PURLINS AS REQUIRED.
EXISTING PEMB STEEL TRUSS
GIRDERS TO REMAIN
SLOPESLOPE RI
D G
E
RIDGE
3"
3"
3"
3"
RIDGE
EXISTING PEMB STEEL TRUSS
GIRDERS TO REMAIN
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
34 4
TYP.
TYP.
TYP.
TYP.
HA
N
G A
R
HA
N G
A R
LO
W
R O
O F
'-0
REMOVE AND DISPOSE OF STAIR
AND CATWALK SERVICING THE
CONTROL TOWER.
REMOVE EXISTING
PURLINS AS REQUIRED
AND ROOFING
ABOVE TAIL DOOR
DOGHOUSE FEATURE
OF HANGAR #2.
PREPARE SURFACES
FOR NEW WORK.
DISCONNECT AND
DISPOSE OF EXISTING
ROOF SIREN ON
HANGAR #1.
SALVAGE ALL MECHANICAL
UNITS FOR REUSE, REINSTALL
IN ORIGINAL LOCATIONS.
VERIFY EXISTING
ROOF PENETRATIONS
AS NEEDED.
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
AD-100
OVERALL
DEMOLITION ROOF
PLAN
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET0' 8' 16' 32' 64'
1/32" = 1'-0"
1 ROOF DEMOLITION PLAN
KEYNOTES - DEMO FLOOR PLANS
1 REMOVE EXISTING STEEL ROOF PURLINS AS REQUIRED;
5'-0" O.C., TYP. REFER TO UNIT PRICE FOR ASSUMED QUANTITY.
2 REMOVE ENTIRE METAL ROOFING INCLUDING EAVE AND RIDGE
FLASHING
3 REMOVE EXISTING GUTTER
4 REMOVE EXISTING DOWNSPOUT
5 REMOVE ALL EXISTING TRANSLUCENT ROOF PANELS
6 REMOVE ENTIRE EXISTING CONTROL TOWER
7 REMOVE EXISTING PURLINS AS REQUIRED AND ROOFING
ABOVE TAIL DOOR DOGHOUSE FEATURE; REFER TO 4/AD-100
8 EXISTING SLIDING DOOR TRACK TO REMAIN. REMOVE EXISTING
METAL ROOFING AND PREPARE FOR NEW WORK.
9 DISCONNECT AND DISPOSE OF EXISTING ROOF SIREN; REFER TO
3/AD-100
10 REMOVE AND DISPOSE OF STAIR AND CATWALK; REFER TO
5/AD-100
11 SALVAGE ALL MECHANICAL UNITS FOR REUSE, REINSTALL IN
ORIGINAL LOCATIONS; REFER TO 2/AD-100
12 EXISTING DOWNSPOUT TO REMAIN
N
N.T.S.5 EXISTING CONDITION - STAIR & CATWALK
N.T.S.4 EXISTING CONDITION - TAIL DOOR
N.T.S.3 EXISTING CONDITION - SIREN
N.T.S.2 EXISTING CONDITION - EQUIP.
2-1 2-2 2-3 2-4 2-5 2-6 2-7 2-8 2-9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17
2-A 2-A
2-B 2-B
1-A 1-A
1-B 1-B
1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 1-12 1-13 1-14 1-151-3.5
1-C 1-C
'-0
0' -0
0' -0
0'
-0
0'
-0
V.I.F.
55'-0"
SL
PE
SL
PE
SLOPESLOPE
EAVE - UPPER ROOF
EAVE - UPPER ROOF
3"
3"
3"
3"
3"
EAVE - UPPER ROOF
EAVE - LOWER ROOF
EAVE - UPPER ROOF
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
2 2
2 22
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
410'-0"
24'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 24'-0"
6'-0" 398'-0" 6'-0"
V .I.
F.
'-0
67'-7" 267'-5"
335'-0"
6'-0" 24'-6" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 24'-6" 5'-0"
A-300
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
A-300
A-300
A-300
A-300
A-300
NOTE: ALL INTERIOR HIGH BAY LIGHTING,
HEATERS, HVLS FANS, FIRE SUPPRESSION
PIPING, FALL PROTECTION, ELECTRICAL
CONDUITS, COMPRESSED AIR PIPING,
AND ANY OTHER ITEMS SUPPORTED FROM
GIRDERS, PURLINS, TO REMAIN.
CONTRACTOR TO PROVIDE TEMPORARY
SUPPORTS DURING RE-ROOFING AND
REPLACEMENT OF PURLINS AS REQUIRED.
LO
W
R O
O F
'-0
0' -0
0' -0
8'
-0
0'
-0
0'
-0
0'
-0
HA
N
G A
R
HA
N G
A R
LO
W
R O
O F
'-0
DS1DS1DS1DS1
DS1DS1DS1DS1
DS2
DS2
DS1DS1DS2
DS2
DS2
DS2
DS2 DS1 DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS1
DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2 DS2
DS1 DS1 DS1 DS1 DS1 DS1 DS1 DS1 DS1 DS1
DS2DS2
DS2DS2DS2
DS2
DS2DS2DS2DS2DS2DS2DS2DS2DS2DS2DS2
DS3
DS3DS3
DS3
@ DOOR
+/- 3'-0" SGSG
@ EQUIP.
+/- 3'-0" SGSG
@ DOOR
+/- 3'-0" SGSG
RI
D
G E
RIDGE
RIDGE
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
HANGAR
DOORS
BELOW TO
REMAIN
(NO WORK)
ROOF PLAN GENERAL NOTES:
1.
2.
3.
ALL REQUIRED APPROVALS, BUILDING AND OTHER PERMITS FROM PROPER AUTHORITIES
HAVING JURISDICTION IN CONNECTION WITH THE CONSTRUCTION AND COMPLETION OF
THIS PROJECT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO INSURE THAT ALL CONSTRUCTION IS
PERFORMED IN THE STRICTEST COMPLIANCE INCLUDING CONSTRUCTION DOCUMENTS
FOR PERMITTING AND SHALL COMPLETE ALL WORK IN ACCORDANCE WITH THE
REQUIREMENTS OF APPLICABLE LAWS, CODES, REGULATIONS, ADA, LIFE SAFETY AND
STANDARDS.
ALL DIMENSIONS ARE FROM FACE OF WALL TO FACE OF WALL UNLESS NOTED OR SHOWN
OTHERWISE. ANY DIMENSIONS NOT SHOWN OR DEEMED QUESTIONABLE ARE TO BE
VERIFIED BY GC PRIOR TO BID. DO NOT SCALE DRAWINGS.
PROVIDE METAL BLOCKING SUPPORTS AS REQUIRED FOR ALL SURFACE MOUNTED ITEMS.
COORDINATE WORK OF THIS TRADE WITH OTHER TRADES.
PROVIDE FLEXIBLE EPDM RUBBER OR SILICONE BOOT AND SECURE TO METAL PANEL AT ALL
PIPE PENETRATIONS THROUGH ROOF.
PROVIDE CURB FLASHING AT ALL MECHANICAL CURBS INDICATED. APPLY SEALANT AT ALL
PLUMBING FIXTURES AT JUNCTURE WITH WALL.
PROVIDE FLASHING WHERE VERTICAL WALLS INTERSECT LOWER ROOF BETWEEN HANGARS.
PROVIDE FLASHING AT ALL EAVE CONDITIONS.
GUTTERS / DOWNSPOUTS:
DIMENSIONS SHALL BE VERIFIED IN FIELD.
COORDINATE DOWNSPOUT ROUTING IN FIELD TO AVOID EQUIPMENT, DOORS,
WINDOWS, OR OTHER OBSTRUCTIONS. PROVIDE SPLASH GUARDS WHERE GUTTER
INSTALLATION IS PREVENTED BY ADJACENT INTERRUPTIONS.
FINAL LOCATION OF DOWNSPOUTS SHALL MAINTAIN UNOBSTRUCTED CIRCULATION
AND EGRESS.
ROOF PLAN LEGEND
NEW CONTINUOUS PREFINISHED PREMANUFACTURED 4" x 6" RECTANGULAR
METAL DOWNSPOUT TO ROOF BELOW (APPLY ELASTOMERIC ROOF SEALANT
COATING DIRECTLY TO METAL PANELS RECEIVING THE CONSTANT STREAM
FROM DOWNSPOUT DISCHARGE)
DS1
NEW CONTINUOUS PREFINISHED PREMANUFACTURED 4" x 6" RECTANGULAR
METAL DOWNSPOUT TO CONCRETE SPLASH BLOCK
DS2
EXISTING CIRCULAR DOWNSPOUT TO UNDERGROUND STORMWATER SYSTEM
TO REMAIN
DS3
SPLASH GUARD IN LIEU OF GUTTER ABOVE INTERRUPTIONS AS NEEDEDSG
APPLICABLE CODES:
2023 FLORIDA BUILDING CODE, BUILDING
2023 FLORIDA BUILDING CODE, EXISTING BUILDING
2023 FLORIDA FIRE PREVENTION CODE
(NFPA 1: FIRE CODE 2021, FLORIDA SPECIFIC EDITION
NFPA 101: FIRE SAFETY CODE 2021, FLORIDA SPECIFIC EDITION)
NFPA 220: STANDARDS ON TYPES OF BUILDING CONSTRUCTION, 2024
OCCUPANCY
OCCUPANCY CLASSIFICATION
S-1 (AIRCRAFT HANGAR)
OCCUPANCY LOADING
CHAPTER 3
FBC
STORAGE
NFPA 101
PARAGRAPH 6.1.13
OCCUPANCY CATEGORIES
STORAGE
SECTION 311.2
STORAGE
PARAGRAPH 6.1.13.1
STORAGE: 300 GROSS STORAGE: MP*
CONSTRUCTION
CONSTRUCTION TYPE
ENERGY CODE
II-B
TABLE 601
II(000)
TABLE 4.1.1
TABLE 1004.5 TABLE 7.3.1.2
*OCCUPANCY LOADING CALCULATIONS
RESTRICTED BY MORE STRINGENT FBC LOAD FACTOR.
FBC NFPA 220
AREA AND HEIGHT LIMITATIONS
BUILDING HEIGHT
PROVIDED
+/-71 FT 6 IN (EXISTING)
NUMBER OF STORIES 1 STORY (EXISTING)
AREA DETERMINATION 166,063 SF (EXISTING)
NOTES
REFER TO S-001 FOR DESIGN CRITERIA AND WEIGHT REQUIREMENTS.
IN ACCORDANCE WITH FBC - EXISTING BUILDING, CHAPTER 6, THE SCOPE OF THIS WORK IS
CLASSIFIED AS AN ALTERATION LEVEL 1.
WORK SHALL COMPLY WITH FLORIDA PRODUCT APPROVALS.
• EXISTING BUILDING - INSULATION NOT IN SCOPE AND NOT PROPOSED TO CHANGE.
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
A-100
OVERALL ROOF PLAN
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET
KEYNOTES - ROOF PLAN
1 NEW STANDING SEAM ROOF SYSTEM INCLUDING PURLINS AS REQUIRED; REFER TO
S-001 AND SPECIFICATIONS FOR MATERIAL REQUIREMENTS
2 NEW CONTINUOUS PREFINISHED PREMANUFACTURED 8" x 8" METAL GUTTER 3 NEW CONTINUOUS PREFINISHED PREMANUFACTURED 14" x 14" METAL
GUTTER WITH HEAVY DUTY BRACKETS
4 DOWNSPOUT; REFER TO ROOF PLAN LEGEND
5 DOWNSPOUT; REFER TO ROOF PLAN LEGEND. REBUILD COLLECTOR BOX
AND MODIFY EXISTING PIPE AS NEEDED TO CONNECT TO NEW GUTTER SYSTEM.
6 NEW STANDING SEAM ROOF SYSTEM OVER EXISTING SLIDING DOOR TRACK
7 REINSTALL ALL MECHANICAL UNITS IN ORIGINAL LOCATIONS; REFER TO 2/AD-100.
PROVIDE NEW INSULATION ON PIPING INCLUDING HURRICANE TIE-DOWNS AS
REQUIRED BY CODE.
8 NEW PURLINS AS NEEDED AT DEMOLISHED CONTROL TOWER
9 NEW 12" CONTINUOUS RIDGE VENTING
0' 8' 16' 32' 64' 1/32" = 1'-0"
1 ROOF PLANN
LEVEL 1
+0' - 0"
T.O. ROOF RIDGE, V.I.F.
+59' - 6"
T.O. HANGAR EAVE, V.I.F.
+34' - 6"
2-A 2-B 1-A 1-B 1-C
T.O. OFFICE EAVE, V.I.F.
+26' - 4"
T.O. STORAGE EAVE, V.I.F.
+18' - 8"
T.O. DOGHOUSE, V.I.F.
+71' - 6"
200'-0" 29'-0" 200'-0" 29'-0" 10'-2 1/2"
EA
V
E
HE
IG
HT
, V .I.
F.
'-4
'-8
" V .I.
F.
'-6
" V .I.
F.
'-6
" V .I.
F.
3" / 12"3" / 12"3" / 12" 3" / 12"
'-6 " V
.I.
F.
'-2
" V .I.
F.
'-6
" V .I.
F.59 '-6
" V .I.
F.
A-300
Sim
A-300
Sim
A-300
Sim
NEW 22 GAUGE
METAL ROOF
PANELS OVER NEW
STEEL PURLINS AS
REQUIRED, REFER
TO S-001
NEW 22 GAUGE METAL
ROOF PANELS OVER NEW
STEEL PURLINS AS
REQUIRED, REFER TO S-001
HANGAR #1HANGAR #2
A-300
Sim
NOTE: ALL INTERIOR HIGH BAY LIGHTING,
HEATERS, HVLS FANS, FIRE SUPPRESSION
PIPING, FALL PROTECTION, ELECTRICAL
CONDUITS, COMPRESSED AIR PIPING,
AND ANY OTHER ITEMS SUPPORTED FROM
GIRDERS, PURLINS, TO REMAIN.
CONTRACTOR TO PROVIDE TEMPORARY
SUPPORTS DURING RE-ROOFING AND
REPLACEMENT OF PURLINS AS REQUIRED.
NEW 22 GAUGE METAL
ROOF PANELS OVER
NEW STEEL PURLINS AS
REQUIRED, REFER TO
S-001
200'-0" 268'-2 1/2"
NEW 22 GAUGE METAL
ROOF PANELS OVER NEW
STEEL PURLINS AS
REQUIRED, REFER TO S-001
NEW 22 GAUGE METAL
ROOF PANELS OVER
NEW STEEL PURLINS AS
REQUIRED, REFER TO
S-001
T.O. HANGAR EAVE, V.I.F.
+34' - 6"
2-A
NEW STEEL PURLIN AS REQUIRED,
REFER TO S-001
PRE-ENGINEERED PREFINISHED METAL
WALL & ROOF FLASHING TO ALLOW
ROOF EXPANSION & CONTRACTION
PREFINISHED PREFABRICATED 8" X 8"
METAL GUTTER WITH GUTTER STRAP
11 GA. X 1 1/2" GALV. MTL.
GUTTER BRACKET
EXISTING STEEL GIRDER (NO WORK)
EXISTING METAL WALL PANEL
TO REMAIN (NO WORK)
DOWNSPOUT STRAP @ 5'-0" O.C.
PREFINISHED METAL 4"X6"
DOWNSPOUT
22 GAUGE MIN. METAL ROOF PANEL EXISTING STEEL TRUSS
GIRDER
NEW STEEL PURLIN AS
REQUIRED, REFER TO
S-001
3" / 12"
T.O. HANGAR EAVE, V.I.F.
+34' - 6"
1-A
NEW STEEL PURLIN AS REQUIRED,
REFER TO S-001
PRE-ENGINEERED PREFINISHED METAL
WALL & ROOF FLASHING TO ALLOW
ROOF EXPANSION & CONTRACTION
PREFINISHED PREFABRICATED 8" X 8"
METAL GUTTER WITH GUTTER STRAP
11 GA. X 1 1/2" GALV. MTL.
GUTTER BRACKET
EXISTING STEEL GIRDER (NO WORK)
EXISTING METAL WALL PANEL
TO REMAIN (NO WORK)
DOWNSPOUT STRAP @ 5'-0" O.C.
PREFINISHED METAL 4"X6"
DOWNSPOUT
22 GAUGE MIN. METAL ROOF PANEL EXISTING STEEL TRUSS
GIRDER
NEW STEEL PURLIN AS
REQUIRED, REFER TO
S-001
3" / 12"
EXISTING METAL WALL
PANEL TO REMAIN.
TEMPORARILY UNSECURE
SECTIONS AS NEEDED TO
INSTALL NEW FLASHING
UNDERNEATH. REINSTALL
WALL PANEL IN
ORIGINAL CONFIG.
PREFINISHED METAL
4" X 6" ELBOW
NEW STEEL PURLIN AS REQUIRED,
REFER TO S-001
EXISTING STEEL BEAM TO REMAIN
EXISTING STEEL TRUSS GIRDER
FLASHING PER
ROOF MANUF.
M
IN
1/
4"
APPLY ELASTOMERIC
ROOF SEALANT
COATING DIRECTLY
TO METAL PANELS
RECEIVING THE
CONSTANT STREAM
FROM DOWNSPOUT
DISCHARGE
PRE-ENGINEERED
METAL WALL &
ROOF FLASHING
EXISTING
STRUCTURAL
STEEL FRAMING
(NO WORK)
EXISTING METAL
WALL PANELS
(NO WORK)
NEW 22 GAUGE METAL
ROOF PANEL
NEW STEEL PURLIN AS
REQUIRED, REFER TO
S-001
Passero Associates
DRAWING NO.:
DATE:
PROJECT NO.:
CLIENT:
STAMP:
PROJECT MANAGER
PROJECT ARCHITECT
DESIGNER
(904) 757-6106335 S. LEGACY TRAIL, SUITE B-102
ST. AUGUSTINE, FL 32092
UNAUTHORIZED USE OF THESE DRAWINGS IS A VIOLATION OF
FLORIDA ADMINISTRATIVE CODE 61G15-27.001 AND FLORIDA
STATUTE 471.033(1). THESE PLANS ARE COPYRIGHT PROTECTED. ©
A-300
OVERALL BUILDING
SECTION & DETAILS
20070044.A037
OCTOBER 21, 2026
CITY OF LAKE CITY
JUSTIN VOLLENWEIDER, AIA
JUSTIN VOLLENWEIDER, AIA
NATALIE BERGERON, ASSOC. AIA
205 N. MARION AVENUE
LAKE CITY, FL 32055
HANGAR #1 & 2 -
ROOF REPLACEMENT
102 SE ACADEMIC AVENUE
TOWN/CITY: LAKE CITY
COUNTY: COLUMBIA STATE: FLORIDA
BID SET
0" 8' 16' 32' 64' 3/64" = 1'-0"
4 BUILDING SECTION - WEST/EAST
0" 3" 6" 1' 2' 1" = 1'-0"
1 GUTTER / DOWNSPOUT DETAIL
0" 3" 6" 1' 2' 1" = 1'-0"
2 GUTTER / DOWNSPOUT DETAIL @ OFFICE
0" 3" 6" 1' 2' 1" = 1'-0"
3 GABLE / RAKE FLASHING DETAIL
1. ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE ARCHITECTURAL,
MECHANICAL, ELECTRICAL, HVAC, AND PLUMBING DRAWINGS AND SPECIFICATIONS.
2. THE CONTRACTOR(S) SHALL VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ELEVATIONS, ETC. IN
THE FIELD AND NOTIFY THE OWNER'S REPRESENTATIVE OF ANY DISCREPANCIES PRIOR TO THE START
OF CONSTRUCTION OR SHOP DRAWINGS.
3. THE DRAWINGS ARE INTENDED TO REQUIRE AND TO INCLUDE ALL LABOR, MATERIAL AND EQUIPMENT
PROPER FOR THE WORK.
4. ALL WORK SHALL COMPLY WITH ALL LOCAL, STATE AND NATIONAL CODES AND REQUIREMENTS.
5. THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES, AND SAFETY PROCEDURES. THE ARCHITECT/ENGINEER SHALL NOT BE
RESPONSIBLE FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR, SUBCONTRACTORS OR THEIR
AGENTS OR EMPLOYEES OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK.
6. OBSERVE ALL OSHA AND OTHER APPLICABLE SAFETY REQUIREMENTS INCLUDING THE USE OF SAFETY
GLASSES, HARD HATS, AND PROTECTION OF AREA WHEN WORKING OVERHEAD. THE CONTRACTOR
SHALL ASSUME RESPONSIBILITY FOR CONSTRUCTION SAFETY AT ALL TIMES.
7. COORDINATE WORK OF ALL DISCIPLINES (STRUCT., ARCH., MECH., ELECT., ETC.) WITH EXISTING
CONDITIONS, SPECIAL REQUIREMENTS, CONSTRUCTION SCHEDULE AND OTHER CONTRACTORS
PERFORMING WORK AT THE SITE.
8. ALL TEMPORARY SHORING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR
SHALL DESIGN AND PROVIDE ANY TEMPORARY SHORING, BRACING, ETC., AS NEEDED FOR THE
WORK SO AS NOT TO ENDANGER THE STRUCTURAL INTEGRITY OF ANY EXISTING FEATURE.
9. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR ANY DAMAGE DONE TO EXISTING
FEATURES AS A RESULT OF THIS WORK. DAMAGED ITEMS SHALL BE REPLACED IN KIND AND AT NO
ADDITIONAL COST TO THE OWNER.
10. DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LAYOUT PRIOR
TO CONSTRUCTION. ALL DIMENSIONS ON STRUCTURAL DRAWINGS SHALL BE CHECKED AGAINST
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND CIVIL DRAWINGS AND ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER’S REPRESENTATIVE.
IMMEDIATELY. SEE THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS NOT SHOWN ON THE
STRUCTURAL DRAWINGS. REFER TO MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS
FOR OPENINGS NOT SHOWN ON STRUCTURAL DRAWINGS. CHANGES AFFECTING THE LAYOUT
SHOWN MUST BE SPECIFIC AND CLEARLY CONVEYED TO THE OWNER’S REPRESENTATIVE IN WRITTEN
FORM AS A CHANGE FOR INCLUSION INTO THESE PLANS.
11. SHOP DRAWINGS: REPRODUCTION OF DESIGN DRAWINGS SHALL NOT BE PERMITTED FOR SHOP
DRAWING SUBMISSIONS. THE GENERAL CONTRACTOR/CONSTRUCTION MANAGER SHALL REVIEW
AND PROVIDE REVIEW STAMP ON SHOP DRAWING SUBMISSIONS PRIOR TO SUBMITTAL TO
ARCHITECT/ENGINEER INDICATING UNDERSTANDING AND ACCEPTANCE OF SUBMITTAL AND
CONFIRMING CONFORMANCE TO PROJECT PLANS/SPECIFICATIONS.
12. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ERECTION PROCEDURE AND
SEQUENCE TO INSURE THE SAFETY OF THE BUILDING AND ITS COMPONENT PARTS DURING ERECTION.
THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF WHATEVER TEMPORARY BRACING, GUYS
OR TIE-DOWNS MAY BE NECESSARY.
13. EQUIPMENT FRAMING LOADS, OPENINGS AND STRUCTURE IN ANY WAY RELATED TO HVAC,
PLUMBING, PROCESS OR ELECTRICAL REQUIREMENTS ARE SHOWN FOR BIDDING PURPOSES ONLY.
CONTRACTOR SHALL OBTAIN APPROVAL OF THE PERTINENT TRADES BEFORE PROCEEDING WITH SUCH
PORTION OF THE WORK. EXCESS COST RELATED TO VARIATION IN THESE REQUIREMENTS SHALL BE
BORNE BY THE APPROPRIATE CONTRACTOR.
14. ANY EXISTING MEMBER OR SITE INFORMATION REQUIRED BY THE CONTRACTOR'S DELEGATED DESIGN
ENGINEER FOR THE DESIGN (MEMBER PROPERTIES, DIMENSIONS, ETC.), SHALL BE PROVIDED BY THE
CONTRACTOR.
GENERAL NOTES:
PROVIDE DOCUMENTS, DOCUMENTATION, AND INFORMATION INDICATED PREPARED BY A
PROFESSIONAL ENGINEER LICENSED IN THE STATE THE WORK IS PERFORMED.
1. TEMPORARY SHORING (INCLUDING ANY SHORING AS REQUIRED FOR BUILDING STABILITY WHILE
ROOF DECK IS NOT IN PLACE)
2. COLD-FORMED METAL PURLINS SUPPORTING ROOF DECK. EXISTING PURLINS WITH MORE THAN 10
PERCENT SECTION LOSS DUE TO CORROSION ARE TO BE REPLACED WITH PURLINS DESIGNED TO MEET
THE STANDARDS IN 2023 FLORIDA BUILDING CODE AND FM 1-28, 1-29, AND 1-31 REQUIREMENTS.
3. ROOF DECK DESIGN AND ATTACHMENT. ROOF DECK IS TO BE DESIGNED FOR FM GLOBAL
STANDARDS (1-28, 1-29, AND 1-31), ASCE 7 COMPONENTS AND CLADDING LOAD, AND ASCE 7 IN-
PLANE DIAPHRAGM LOADS FOR THE MWFRS. THE IN-PLANE DIAPHRAGM DESIGN LOAD FOR THE
MWFRS IS 1.6 KLF.
4. STRUCTURAL STEEL CONNECTIONS.
DELEGATED DESIGN NOTES:
RENOVATION AND EXISTING STRUCTURE NOTES:
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, ETC., NECESSARY FOR THE PROPER
CONSTRUCTION AND ALIGNMENT OF THE NEW PORTIONS OF THE STRUCTURE TO THE EXISTING
STRUCTURE. THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS NECESSARY FOR PROPER
FABRICATION AND ERECTION OF ALL STRUCTURAL MEMBERS. THE CONTRACTOR SHALL SUPPORT, BRACE AND SECURE EXISTING STRUCTURES AS REQUIRED. THE CONTRACTOR IS SOLELY RESPONSIBLE
FOR THE SAFETY OF EXISTING STRUCTURES DURING CONSTRUCTION.
2. BEFORE PROCEEDING WITH ANY WORK WITHIN OR ADJACENT TO THE EXISTING STRUCTURE, THE
CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS. DURING THE PROCESS OF
CONSTRUCTION, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE
EXISTING STRUCTURE WHERE THE EXISTING STRUCTURE IS MODIFIED TO ACCOMMODATE NEW
CONSTRUCTION AND TO PROTECT FROM DAMAGE THOSE PORTIONS OF THE EXISTING STRUCTURE, WHICH ARE TO REMAIN.
3. ALL EXISTING STRUCTURAL ELEMENTS (SLABS, BEAMS, WALLS, COLUMNS, FOUNDATIONS...) SHALL
REMAIN INTACT UNLESS SPECIFICALLY NOTED TO BE REMOVED BY THE DEMOLITION DOCUMENTS OR
OTHERWISE NOTED ON THE STRUCTURAL DRAWINGS.
4. INFORMATION PROVIDED ON THESE DRAWINGS RELATED TO EXISTING CONDITIONS IS BASED ON
AVAILABLE DESIGN DOCUMENTS. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY AND AWAIT
DIRECTION FROM THE OWNER’S REPRESENTATIVE IF ANY DISCREPANCY BETWEEN THE CONTRACT
DOCUMENTS AND THE EXISTING CONDITIONS IS DISCOVERED.
1. FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH THE "LIGHT GAGE COLD FORMED
STEEL DESIGN MANUAL", LATEST EDITION AND THE AISI SPECIFICATIONS FOR THE DESIGN OF COLD-
FORMED STEEL STRUCTURAL MEMBERS, LATEST EDITION.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE FINAL DESIGN AND PERFORMANCE OF ALL COLD-
FORMED METAL FRAMING. ALL SIZES, GAGES AND DESIGN REQUIREMENTS SHOWN ON THESE
DRAWINGS ARE TO BE CONSIDERED MINIMUM REQUIREMENTS AND NOT FINAL REQUIREMENTS.
3. PROVIDE CLIPS, CONNECTIONS, STRAPPING AND/OR BRIDGING FOR TEMPORARY LATERAL BRACING
AND ALL ITEMS NECESSARY FOR COMPLETE INSTALLATION.
4. ALL WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3 "STRUCTURAL WELDING CODE – SHEET
STEEL", LATEST EDITION AND PERFORMED BY CERTIFIED, LICENSED WELDER.
5. DETAILING AND FABRICATION OF ALL COLD-FORMED STRUCTURAL MEMBERS SHALL CONFORM TO
THE AISI SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, LATEST
EDITION.
6. COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR ALL COLD FORMED METAL
FRAMING LOCATIONS AND REQUIREMENTS. COORDINATE LOCATIONS AND DESIGN FOR ALL WALL
HUNG EQUIPMENT.
7. PROVIDE AND COORDINATE VERTICAL SLIP CONNECTIONS TO STRUCTURAL STEEL MEMBERS WHERE
REQUIRED. ACCOUNT FOR A MINIMUM DEFLECTION OF 1 INCH UNLESS NOTED OTHERWISE.
8. REMOVE EXISTING CORRODED/DETERIORATED MATERIAL FROM EXISTING PURLINS. EXISTING PURLINS
THAT HAVE MORE THAN 10 PERCENT SECTION LOSS (WHEN COMPARING THE CROSS SECTION WITH
THE REMOVED MATERIAL VS THE COMPLETE EXISTING CROSS SECTION) SHALL BE REPLACED WITH
NEW PURLINS DESIGNED BY THE CONTRACTOR'S DELEGATED DESIGN ENGINEER TO MEET THE
REQUIREMENTS OF 2023 FLORIDA BUILDING CODE AND FM GLOBAL REQUIREMENTS.
9. ROOF PURLINS SHALL HAVE A MINIMUM OF 16 GA THICKNESS AND SHALL BE DESIGNED BY THE
CONTRACTOR'S DELEGATED DESIGN ENGINEER TO MEET A DEFLECTION LIMIT OF L/240. ROOF
PURLINS SHALL BE SPACED AT APPROXIMATELY 5'-0" OC AND SHALL BE INSTALLED IN THE SAME
LOCATION AS THE EXISTING PURLIN THAT IS TO BE REMOVED. DELEGATED DESIGN CALCULATIONS
ARE TO BE SUBMITTED TO EOR FOR REVIEW PRIOR TO INSTALLATION OF PURLINS.
10. THE DELEGATED DESIGN FOR THE ROOF SYSTEM AND PURLINS SHALL BE WITHIN 5% OF THE WEIGHT OF
THE EXISTING SYSTEM. CONTRACTOR TO CORE EXISTING ROOF SYSTEM AND SUBMIT EXISTING ROOF
WEIGHT IN PSF. IF THE PROPOSED DESIGN EXCEEDS THIS 5% THRESHOLD IT IS THE CONTRACTOR'S
DELEGATED DESIGN ENGINEER'S RESPONSIBILITY TO VERIFY THE ADEQUACY OF THE EXISTING TRUSSES, COLUMNS, AND FOUNDATIONS FOR THE ADDITIONAL LOAD.
COLD-FORMED METAL FRAMING NOTES:
1. SUBMITTALS:
A. SUBMIT SHOP DRAWINGS INCLUDING LAYOUT AND TYPES OF DECK PANELS, ANCHORAGE
DETAILS, REINFORCING CHANNELS, PANS, CUT DECK OPENINGS, SPECIAL JOINTING,
ACCESSORIES, AND ATTACHMENTS TO OTHER CONSTRUCTION.
B. SUBMIT PRODUCT DATA FOR EACH TYPE OF DECK, ACCESSORY, AND PRODUCT INDICATED.
2. COMPLY WITH THE FOLLOWING CODES AND STANDARDS:
A. AISI / STEEL DECK INSTITUTE "C-2011 STANDARD FOR COMPOSITE STEEL DECK-SLABS"
B. AMERICAN WELDING SOCIETY (AWS) D1.3 "STRUCTURAL WELDING CODE- SHEET STEEL", 2015.
3. ROOF DECK CONNECTIONS: IN ACCORDANCE WITH DELEGATED DESIGN.
4. DESIGN ROOF DECK IN ACCORDANCE WITH THE FOLLOWING:
A. YIELD STRENGTH, Fy = 50 KSI
5. THE CONTRACTOR SHALL VERIFY THE SIZE AND LOCATION OF ALL OPENINGS, SLEEVES, INSERTS, ETC., WITH SHOP DRAWINGS OF THE EQUIPMENT TO BE INSTALLED. SEE MECHANICAL DRAWINGS FOR
LOCATIONS OF PIPE SLEEVES. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF OPENINGS IN
ROOF.
6. ACCESSORIES:
A. GENERAL: PROVIDE MANUFACTURER'S STANDARD ACCESSORY MATERIALS FOR DECK THAT
COMPLY WITH REQUIREMENTS INDICATED.
B. FLEXIBLE CLOSURE STRIPS: VULCANIZED, CLOSED-CELL, SYNTHETIC RUBBER.
C. MISCELLANEOUS SHEET METAL DECK ACCESSORIES: STEEL SHEET, MINIMUM YIELD STRENGTH OF
33 KSI, NOT LESS THAN .0359-INCH DESIGN UNCOATED THICKNESS, OF SAME MATERIAL AND
FINISH AS DECK; OF PROFILE INDICATED OR REQUIRED FOR APPLICATION.
D. POUR STOPS AND GIRDER FILLERS: STEEL SHEET, MINIMUM YIELD STRENGTH OF 33 KSI, OF SAME
MATERIAL AND FINISH AS DECK, AND OF THICKNESS AND PROFILE RECOMMENDED BY SDI
SPECIFICATIONS AND COMMENTARY FOR OVERHANG AND SLAB DEPTH.
7. EXISTING ROOF DECK IS TO BE REPLACED IN IT'S ENTIRETY. THE NEW ROOF DECK SHALL BE DESIGNED
BY THE CONTRACTOR'S DELEGATED DESIGN ENGINEER TO MEET THE REQUIREMENTS OF 2023 FLORIDA
BUILDING CODE, FM 1-28, 1-29, AND 1-31. THE ROOF DECK DESIGN WILL INCLUDE THE IN-PLANE
DIAPHRAGM DESIGN FOR THE LATERAL LOADS FOR THE MWFRS (IN ACCORDANCE WITH FLORIDA
BUILDING CODE) PER EXISTING FLORIDA BUILDING CODE SECTION 707.3.2. THE DIAPHRAGM DESIGN
IS TO BE COMPLETED BY THE CONTRACTOR'S DELEGATED DESIGN ENGINEER AND CAN
INCORPORATE EXISTING IN-PLANE DIAPHRAGM BRACING.
8. THE DELEGATED DESIGN FOR THE ROOF SYSTEM AND PURLINS SHALL BE WITHIN 5% OF THE WEIGHT OF
THE EXISTING SYSTEM. CONTRACTOR TO CORE EXISTING ROOF SYSTEM AND SUBMIT EXISTING ROOF
WEIGHT IN PSF. IF THE PROPOSED DESIGN EXCEEDS THIS 5% THRESHOLD IT IS THE CONTRACTOR'S
DELEGATED DESIGN ENGINEER'S RESPONSIBILITY TO VERIFY THE ADEQUACY OF THE EXISTING TRUSSES, COLUMNS, AND FOUNDATIONS FOR THE ADDITIONAL…
This is the start of the file's text. The full file is on GovTribe.