PowerPanelsNema4xSS.xlsx
XLSX spreadsheet 478 KB Posted
- Attached to
- Multnomah Falls Lodge Electrical Upgrades
- Solicitation number
- 1240BH21R0011-1
About this file
This document outlines requirements for an electrical upgrade project at the Multnomah Falls Lodge. The USDA Forest Service will issue an RFP to demolish and replace all electric panels, install an ATS, emergency shut-off switch, strobe lights, distribution panels, main switchboard, panelboard T, lighting, and other electrical equipment. Site work is included for installing the main switchboard and ATS. Prospective awardees must be registered in SAM and maintain registration through award and performance. The anticipated project value is between $1,000,000 to $5,000,000 with an expected start date of October 2021. A site visit is scheduled for April 28th and pre-bid conference call is scheduled for May 4th.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Multnomah Falls Panel change summary | 5/5/21 | SDS | ||||||||||
| The following panels are listed as Nema Configurations | ||||||||||||
| Drawing | PANEL | Original Feeder Breaker | New Feeder Breaker | New feeder Size | Feeder Brkr Changed? From Original Size | AIC Rating | 1-Line AIC Available | NEMA # Original | NEMA # Revised | BID Option Original | Rev Bid Option | |
| E1.2 E6.1 | ATS-1 | N/A | 1500 | 5-3/0 | Y | 100 KA | 56 KA | Nems 3R SS | Nema 3R SS | Base | Base | AIC not shown, 100KA |
| E1.2 E6.1 | SWB-1 | N/A | 1600 | 5-3/0 | Y | 100 KA | 53 KA | Nems 4X SS | Nema 3R SS | Base | Base | |
| E7.22 | DP1 | N/A | 1200 | 3-500 KCMIL | Y | 65 KA | 35 KA | Nems 4X SS | Nema 3R SS | Base | Base | |
| E7.23 | DP2 | N/A | 1200 | 3-500 KCMIL | Y | 65 KA | 35 KA | Nems 4X SS | Nema 3R SS | Base | Base | |
| E7.3 | Panel C | 300 | 400 | 500 KCMIL | Y | 22 KA | 20 KA | Nems 4X SS | Nems 4X SS | 1 | Base | Combines AA, C, Compresor panel |
| E7.14 | Panel R | 200 | 225 | 4/0 | Y | 35 KA | 30 KA | Nems 4X SS | Nems 4X SS | 8 | Base | |
| E7.7 | Panel J | 200 | 225 | 4/0 | Y | 35 KA | 30 KA | Nems 4X SS | Nems 4X SS | 9 | Base | |
| E7.12 | Panel Q | 90 | 225 | 4/0 | Y | 35 KA | 25 KA | Nems 4X SS | Nems 4X SS | 10 | Base | |
| E7.21 | Panel T | 100 | 225 | 4/0 | Y | 50 KA | 44 KA | Nems 4X SS | Nems 4X SS | Base | Base | |
| E7.16 | Panel SB1 | 400 | 400 | 500 KCMIL | N | 22 KA | 13 KA | Nema 1 | Nema 1 | 4 | ||
| E7.18 | Panel SB2 | 400 | 400 | 500 KCMIL | N | 22 KA | 13 KA | Nema 1 | Nema 1 | 5 | ||
| E7.20 | Panel SB3 | 225 | 225 | 4/0 | N | 22 KA | 10 KA | Nema 1 | Nema 1 | 6 | ||
| E7.5 | Panel H | 200 | 200 | 3/0 | N | 22 KA | 20 KA | Nema 1 | Nema 1 | 2 | Combines 2 panels HP 920594 & Hp920604 | |
| E7.9 | Panel M | 300 | 300 | 300 KCMIL | N | 22 KA | 20 KA | Nema 1 | Nema 1 | 3 | Combines old M&N panels in office to hallway | |
| E7.11 | Panel N | 225 | 225 | 4/0 | N | 22 KA | 22 KA | Nema 1 | Nema 1 | 7 | ||
| E6.1 | Elevator | 250 | 200 | 3/0 | Y | 22 KA | 22 KA | NA | NA | Base | Base | Breaker changed to 200A from 250A was too large |
| E6.1 | Booster WH | 250 | 250 | 4/0 | N | 22 KA | 22 KA | NA | NA | Base | Base | |
| <--------- Nema 4X SS panel from Timberline Lodge |