FXSB182423 Repair Tactics/Intel/Mission Planning, H18 Questions and Answers
7 October 2019
Q1: Can EMT be used?
A1: Yes it can be used, but it is not mandatory.
Q2: Is SIPRNET required for epoxy of all electrical fittings?
A2: Not clear on what this question is asking.
Q3: Is the existing fire alarm and all other systems being brought into the space on fiber now, or will we have to upgrade systems to eliminate the copper coming in and leaving the space?
A3: All electrical devices can be copper, only networks need to be fiber.
Q4: Is the power separated, do we need a filter on the main feeder to the SCIF?
A4: Existing power will be fine.
Q5: Will a self-contained comm room AC unit be considered vs a split system? Condenser heat would be rejected to the ceiling/interstitial space above.
A5: Yes, a self-contained AC unit would be acceptable as long as it can maintain cooling in the room to 72 degrees or lower with all equipment running.
Q6: In previous Q&A dated 11 Sept 2019, response #30 addresses sound masking as a last resort and not to be utilized in place of ICS705 requirements. Please confirm white noise is NOT a requirement for this project.
A6: Confirmed, white noise is NOT a requirement for this project.