F5W61608 USPFO Warehouse Ohio Army National Guard Rev. 0 Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 1
SECTION 078446 - FIRE-RESISTIVE JOINT SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes fire-resistive joint systems for the following:
1. Head-of-wall joints.
2. Wall-to-wall joints.
B. Related Sections include the following:
1. Division 07 Section "Thermal Insulation" for floor-to-wall joints indicated as perime-ter fire-containment systems between perimeter edge of fire-resistance-rated floor assemblies and back of non-fire-resistance-rated exterior curtain walls.
2. Division 07 Section "Manufactured Roof Expansion Joints" for fire-resistive roof expansion assemblies.
3. Division 07 Section "Penetration Firestopping" for systems installed in openings in walls and floors with and without penetrating items.
4. Division 07 Section "Joint Sealants" for non-fire-resistive joint sealants.
5. Division 07 Section "Expansion Control" for fire-resistive joint systems consisting of metal frames and covers.
1.2 PERFORMANCE REQUIREMENTS
A. General: Provide fire-resistive joint systems that are produced and installed to resist spread of fire according to requirements indicated, resist passage of smoke and other gases, and maintain original fire-resistance rating of assembly in which fire-resistive joint systems are installed.
B. Joint Systems in and between Fire-Resistance-Rated Constructions: Provide systems with assembly ratings equaling or exceeding the fire-resistance ratings of construction that they join, and with movement capabilities and L-ratings indicated as determined by
UL 2079.
1. Load-bearing capabilities as determined by evaluation during the time of test.
C. Perimeter Fire-Resistive Joint Systems: For joints between edges of fire-resistance-rated floor assemblies and exterior curtain walls, provide systems of type and with rat-ings indicated below and those indicated in the Fire-Resistive Joint System Schedule at the end of Part 3, as determined by NFPA 285 and UL 2079.
1. UL-Listed, Perimeter Fire-Containment Systems: Integrity ratings equaling or ex-ceeding fire-resistance ratings of floor or floor/ceiling assembly forming one side of joint.
2. OPL-Listed, Perimeter Fire-Barrier Systems: F-ratings equaling or exceeding fire-resistance ratings of floor or floor/ceiling assembly forming one side of joint.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 2
D. For fire-resistive systems exposed to view, provide products with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, as determined per
ASTM E 84.
1.3 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: For each fire-resistive joint system, show each kind of construction condition in which joints are installed; also show relationships to adjoining construction.
Include fire-resistive joint system design designation of testing and inspecting agency acceptable to authorities having jurisdiction that demonstrates compliance with re-quirements for each condition indicated.
1. Submit documentation, including illustrations, from a qualified testing and inspect-ing agency that is applicable to each fire-resistive joint system configuration for construction and penetrating items.
C. Product Certificates: For each type of fire-resistive joint system, signed by product manufacturer.
D. Qualification Data: For Installer.
E. Field quality-control test reports.
F. Evaluation Reports: Evidence of fire-resistive joint systems' compliance with ICBO ES AC30, from the ICBO Evaluation Service.
G. Research/Evaluation Reports: For each type of fire-resistive joint system.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: A firm that has been approved by FMG according to FMG 4991, "Approval of Firestop Contractors."
B. Installation Responsibility: Assign installation of through-penetration firestop systems and fire-resistive joint systems in Project to a single qualified installer.
C. Source Limitations: Obtain fire-resistive joint systems, for each kind of joint and con-struction condition indicated, through one source from a single manufacturer.
D. Fire-Test-Response Characteristics: Provide fire-resistive joint systems that comply with the following requirements and those specified in Part 1 "Performance Require-ments" Article:
1. Fire-resistance tests are performed by a qualified testing and inspecting agency.
A qualified testing and inspecting agency is UL or another agency performing test-ing and follow-up inspection services for fire-resistive joint systems acceptable to authorities having jurisdiction.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 3
2. Fire-resistive joint systems are identical to those tested per methods indicated in Part 1 "Performance Requirements" Article and comply with the following:
a. Fire-resistive joint systems correspond to those indicated by referencing sys-tem designations of the qualified testing and inspecting agency.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Deliver fire-resistive joint system products to Project site in original, unopened contain-ers or packages with qualified testing and inspecting agency's classification marking applicable to Project and with intact and legible manufacturers' labels identifying prod-uct and manufacturer, date of manufacture, lot number, shelf life, curing time, and mix-ing instructions for multicomponent materials.
B. Store and handle materials for fire-resistive joint systems to prevent their deterioration or damage due to moisture, temperature changes, contaminants, or other causes.
1.6 PROJECT CONDITIONS
A. Environmental Limitations: Do not install fire-resistive joint systems when ambient or substrate temperatures are outside limits permitted by fire-resistive joint system manu-facturers or when substrates are wet due to rain, frost, condensation, or other causes.
B. Ventilate fire-resistive joint systems per manufacturer's written instructions by natural means or, if this is inadequate, forced-air circulation.
1.7 COORDINATION
A. Coordinate construction of joints to ensure that fire-resistive joint systems are installed according to specified requirements.
B. Coordinate sizing of joints to accommodate fire-resistive joint systems.
C. Notify Owner's inspecting agency at least seven days in advance of fire-resistive joint system installations; confirm dates and times on days preceding each series of installa-tions.
D. Do not cover up fire-resistive joint system installations that will become concealed be-hind other construction until Owner's inspecting agency and building inspector of au-thorities having jurisdiction have examined each installation.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Available Products: Subject to compliance with requirements, fire-resistive joint sys-tems that may be incorporated into the Work include, but are not limited to, those sys-tems indicated in the Fire-Resistive Joint System Schedule at the end of Part 3.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 4
2.2 FIRE-RESISTIVE JOINT SYSTEMS
A. Compatibility: Provide fire-resistive joint systems that are compatible with joint sub-strates, under conditions of service and application, as demonstrated by fire-resistive joint system manufacturer based on testing and field experience.
B. Accessories: Provide components of fire-resistive joint systems, including primers and forming materials, that are needed to install fill materials and to comply with Part 1 "Performance Requirements" Article. Use only components specified by fire-resistive joint system manufacturer and approved by the qualified testing and inspecting agency for systems indicated.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and conditions, with Installer present, for compliance with require-ments for joint configurations, substrates, and other conditions affecting performance of work.
1. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Surface Cleaning: Clean joints immediately before installing fire-resistive joint systems to comply with fire-resistive joint system manufacturer's written instructions and the fol-lowing requirements:
1. Remove from surfaces of joint substrates foreign materials that could interfere with adhesion of fill materials.
2. Clean joint substrates to produce clean, sound surfaces capable of developing op-timum bond with fill materials. Remove loose particles remaining from cleaning operation.
3. Remove laitance and form-release agents from concrete.
B. Priming: Prime substrates where recommended in writing by fire-resistive joint system manufacturer using that manufacturer's recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces.
C. Masking Tape: Use masking tape to prevent fill materials of fire-resistive joint system from contacting adjoining surfaces that will remain exposed on completion of Work and that would otherwise be permanently stained or damaged by such contact or by clean-ing methods used to remove smears from fire-resistive joint system materials. Remove tape as soon as possible without disturbing fire-resistive joint system's seal with sub-strates or damaging adjoining surfaces.
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 5
3.3 INSTALLATION
A. General: Install fire-resistive joint systems to comply with Part 1 "Performance Re-quirements" Article and fire-resistive joint system manufacturer's written installation in-structions for products and applications indicated.
B. Install forming/packing/backing materials and other accessories of types required to support fill materials during their application and in position needed to produce cross-sectional shapes and depths required to achieve fire ratings indicated.
C. Install fill materials for fire-resistive joint systems by proven techniques to produce the following results:
1. Fill voids and cavities formed by openings and forming/packing/backing materials as required to achieve fire-resistance ratings indicated.
2. Apply fill materials so they contact and adhere to substrates formed by joints.
3. For fill materials that will remain exposed after completing Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes.
3.4 FIELD QUALITY CONTROL
A. Inspecting Agency: Engage a qualified independent inspecting agency to inspect fire-resistive joint systems and prepare inspection reports.
B. Testing Services: Inspecting of completed installations of fire-resistive joint systems shall take place in successive stages as installation of fire-resistive joint systems pro-ceeds. Do not proceed with installation of joint systems for the next area until inspect-ing agency determines completed work shows compliance with requirements.
1. Inspecting agency shall state in each report whether inspected fire-resistive joint systems comply with or deviate from requirements.
C. Remove and replace fire-resistive joint systems where inspections indicate that they do not comply with specified requirements.
D. Additional inspecting, at Contractor's expense, will be performed to determine compli-ance of replaced or additional work with specified requirements.
E. Proceed with enclosing fire-resistive joint systems with other construction only after in-spection reports are issued and fire-resistive joint systems comply with requirements.
3.5 CLEANING AND PROTECTING
A. Clean off excess fill materials adjacent to joints as Work progresses by methods and with cleaning materials that are approved in writing by fire-resistive joint system manu-facturers and that do not damage materials in which openings occur.
B. Provide final protection and maintain conditions during and after installation that ensure fire-resistive joint systems are without damage or deterioration at time of Substantial
Defense Supply Center Columbus, Ohio 30 January 2009 Bid Final
FIRE-RESISTIVE JOINT SYSTEMS 078446 - 6
Completion. If damage or deterioration occurs despite such protection, cut out and remove damaged or deteriorated fire-resistive joint systems immediately and install new materials to produce fire-resistive joint systems complying with specified require-ments.
3.6 FIRE-RESISTIVE JOINT SYSTEM SCHEDULE
A. Designation System for Joints in or between Fire-Resistance-Rated Constructions: Al-phanumeric systems listed in UL's "Fire Resistance Directory" under Product Cate-gory XHBN.
B. Designation System for Joints at the Intersection of Fire-Resistance-Rated Floor or Floor/Ceiling Assembly and an Exterior Curtain-Wall Assembly: Alphanumeric systems listed in UL's "Fire Resistance Directory" under Product Category XHDG:
C. Head-of-Wall Fire-Resistive Joint Systems FRJS-#1:
1. UL-Classified System: FW-D.-0042 for steel studs and gypsum board assembly.
2. Assembly Rating: 1 hour.
3. Nominal Joint Width: Partition thickness.
4. Movement Capabilities: Class II 50 percent compression or extension
D. Head-of-Wall Fire-Resistive Joint Systems FRJS-#2:
1. UL-Classified System: FW-D-0097 for CMU assembly
2. Assembly Rating: 1 hour.
3. Nominal Joint Width: Partition thickness.
4. Movement Capabilities: Class II 14 percent compression or extension
E. Wall-to-Wall Fire-Resistive Joint Systems FRJS-#3:
1. UL-Classified Systems: WW-D-0040 for steel stud and gypsum board assembly to
CMU.
2. Assembly Rating: 1 hour.
3. Nominal Joint Width: 1/2 inch, ¾ inch maximum.
4. Movement Capabilities: Class II 17 percent compression or extension.
F. Wall-to-Wall Fire-Resistive Joint Systems FRJS-#4:
1. UL-Classified Systems: WW-D-0032 for CMU assembly.
2. Assembly Rating: 1 hour.
3. Nominal Joint Width: 3/8 inch.
4. Movement Capabilities: Class II 12.5 percent compression or extension.
END OF SECTION 078446