This solicitation requests proposals for a firm fixed-price contract to provide all plant, labor, transportation, materials, tools, equipment, appliances and supervision necessary to construct a small arms range and conventionally constructed CATM facility. Scope of work includes site work, utilities, structural, architectural, mechanical and electrical systems to support the CATM facility and firing range. The magnitude of the project is estimated between $5,000,000 to $10,000,000. Construction is to be completed within 360 calendar days after notice to proceed. The NAICS code is 236220 and small business size standard is $39.5 million. This action is set aside for small businesses. A pre-proposal conference will be held on June 3, 2021 and site visit will follow. Questions are due by June 19, 2021. Proposals are due by June 22, 2021. Evaluation factors are best value past performance and price. Award will be made without discussions to the responsible offeror whose proposal follows the solicitation instructions and is determined most advantageous to the Government considering the factors. Interested offerors must register in SAM. Plans and specifications are available at beta.SAM. All inquiries must be in writing. Place of performance is Duluth National Guard Base, MN. The soliciting agency is Department of the Army Minnesota Army National Guard.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Construct Small Arms Range 7/2/2021
FMKM179063
ADDENDUM 04 Page 1 of 1
LHB #180940
ANSWERS TO CONTRACTOR QUESTIONS: None
CHANGES TO SPECIFICATIONS: None
CHANGES TO DRAWINGS:
1. Replace Drawing Sheet E401 – ENLARGED ELECTRICAL PLANS & DIAGRAMS (attached).
2. Replace Drawing Sheet E602 – ELECTRICAL SCHEDULES (attached).
ATTACHMENTS: Sheets E401 and E602
End of Addendum 04
F
S
FS
JJ
KEYED SHEET NOTESKEYED SHEET NOTES
J
5 6
ELEC
TELE
EF-1
FCU
TMGB
48"
W
A
B
T1
15cd
W 48"
B
11,13
11,132
T2
GFCI
48" 7
SECP
17 19
FACP
RCK/11
RCK/12
21,23
21,23
A
11,13
A
21,23
5 6
SDP
MDP
J
MECH
F-2 F-1
CP-1
1/10
UH-1
WH-1
B
13,15,17 B
10,12B
21 B
B
GFCI
48"
A
B
GFCI
48"
48"
GFCI
48"
GFCI
48"
48" 15
ERV-1
LEVEL 1
ROOF
GRADE
ELEC 106
MV
DISTRIBUTION
TRANSFORMER
T-SA/DOMOPS
T1
MDP
9SPD
SECONDARY
CONNECTION
CABINET
SCC-SA
M
10 11
SPD
A B
M
M 12
11 11 11 11 11 11 17 7 11
15 15 15 15 15 16
17 17 17
RCU RHU REF
SDP
T2
FIRE SUPPR
WATER
SERVICE
STEEL REINF.
IN BASE OF
FOOTING
STEEL
STRUCTURE
MBG1
G N
MAIN
SWBD
#3/0 CU
T-1
GND BUS
#3/0 CU
C U
(2) GND ROD
ELECTRODES
WATER
SERVICE LIGHTNING
PROTECTION
GND RODS
C U
TMGB
C U
3/
C
U
#3/0 CU
#4 CU
T-2
C U
1. REFER TO COMMUNICATIONS RISER DIAGRAM FOR CONDUCTOR
SIZE.
2. PROVIDE #3/0 CU BONDING JUMPER ACROSS METER.
3. PROVIDE RACEWAY AND CONDUCTORS TO EXTERIOR CONDENSING
UNIT. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL
INFORMATION.
4. REFER TO DETAILS ON T5## SERIES OF DRAWINGS FOR ADDITIONAL
INFORMATION/REQUIREMENTS FOR COMMUNICATION ROOM.
5. BACKBONE CABLING CONDUITS. REFER TO ELECTRICAL SITE PLAN
AND TECHNOLOGY RISER DIAGRAM FOR FOR ADDITIONAL
INFORMATION.
6. PROVIDE FIRE RATED PLYWOOD BOARDS TO LINE COMMUNICATION
ROOM. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
7. PROVIDE CABLETRAY ABOVE RACKS AND AS NOTED/SHOWN ON
COMMUNICATION DETAILS.
8. PROVIDE CONDUIT ONLY FOR FUTURE DOMOPS BUILDING SERVICE
CONDUCTORS.
9. PROVIDE CONDUITS FROM TRANSFORMER TO MANHOLE MH-A1, AS
NOTED ON ELECTRICAL SITE PLAN. INSTALL PRIMARY FEEDER CABLE
AS NOTED ON ELECTRICAL SITE PLAN.
10. PROVIDE 480/277V, 3PH, 4W, 1600A CONNECTION CABINET WITH
METERING COMPARTMENT ACCOMMODATIONS. PROVIDE (1)400/3 AND
(1)800/3 BREAKERS FOR SMALL ARMS AND DOMOPS FEEDERS.
PROVIDE BUSSING AND SPACE ACCOMMODATIONS FOR A FUTURE
800/3 FUSED DISCONNECT.
11. PROVIDE METERING FOR TWO BREAKERS AND ACCOMMODATIONS
FOR A FUTURE THIRD METER. REFER TO SPECIFICATIONS FOR
POWER METERING REQUIREMENTS.
12. PROVIDE DISTRIBUTION STYLE PANELBOARD.
13. PROVIDE HOUSEKEEPING PAD AND ISOLATION PADS/SPRINGS FOR
FLOOR MOUNTED TRANSFORMERS. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
14. PROVIDE 600/3AS; 500AF FUSED ENCLOSED SWITCH.
15. PROVIDE FEEDERS TO FIRING RANGE'S ENCLOSED
SWITCHES/PANELBOARDS. COORDINATE WITH SUPPLIED FIRING
RANGE PRIOR TO WORK COMMENCING FOR ADDITIONAL
REQUIREMENTS.
16. ADDITIONAL LANES BID OPTION: PROVIDE FEEDERS TO FIRING
RANGE'S ENCLOSED SWITCHES/ PANELBOARDS. COORDINATE WITH
SUPPLIED FIRING RANGE PRIOR TO WORK COMMENCING FOR
ADDITIONAL REQUIREMENTS.
17. PROVIDE FEEDERS TO FIRING RANGE'S HVAC EQUIPMENT.
COORDINATE WITH SUPPLIED FIRING RANGE PRIOR TO WORK
COMMENCING FOR ADDITIONAL REQUIREMENTS.
18. PROVIDE MANUFACTURER'S STRUCTURE FOR STACKING
TRANSFORMERS, WITH LARGER TRANSFORMER LOCATED ON THE
BOTTOM.
A. ALL TRANSFORMERS TO HAVE A DELTA PRIMARY UNLESS NOTED OTHERWISE.
GENERAL NOTES:
1. PROVIDE HOUSEKEEPING EQUIPMENT PAD FOR TRANSFORMER AS CALLED OUT IN SPECIFICATIONS.
2. PROVIDE CONCRETE PAD AS DETAILED ON DRAWING.
3. PROVIDE VIBRATION PADS/SPRINGS.
SCHEDULE NOTES:
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
CONSTRUCT SMALL
ARMS RANGE
XXX
FMKM179063
COPYRIGHT 2020 BY LHB, INC. ALL RIGHTS RESERVED.
NO DATE ISSUED FOR
21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446
10/5/20
MARK J. VINCENT
52349
B3 FINAL SUBMITTAL
B
IM
/1
M n A
N G
C o n s tr u c t S m a ll A rm s R a n g e /1
M n A
N G
C o n s tr u c t S m a ll A rm s R a n g e
M E
P
.r v t
/1
/2
:3
:2
P M
E401
10/5/2020
AML
MJV
180940
ENLARGED ELECTRICAL
PLANS & DIAGRAMS
1/4" = 1'-0"1
ENLARGED ELECTRICAL PLAN - ELEC 109 & TELE 111
1/4" = 1'-0"2
ENLARGED ELECTRICAL PLAN - MECH 120
NOT TO SCALE4
ELECTRICAL POWER DISTRIBUTION DIAGRAM
NOT TO SCALE3
GROUNDING RISER DIAGRAM
TRANSFORMER SCHEDULE
IDENTIFICATION KVA PHASE
PRIMARY
VOLTAGE
SECONDARY
VOLTAGE IMPEDANCE
MOUNTING
STYLE NOTES
T1 75 3 480 V 208Y/120 3% FLOOR 1,3
T2 300 3 480 V 208Y/120 3% FLOOR 1,3
T-SA/ DOMOPS 500 3 13800 V 480Y/277 3% GRADE 2
NO DATE REVISION
1 06/19/2021 ADDENDUM 02
2 07/01/2021 ADDENDUM 04
30 5000 5320 (14) 500 KCMIL (14) 3"C 2#500 & 2#350 GND (14) 3-1/2"C 3#500 & 2#350 GND (14) 4"C 4#500 & 2#350 GND
29 4000 4180 (11) 500 KCMIL (11) 3"C 2#500 & 1#500 GND (11) 3-1/2"C 3#500 & 1#500 GND (11) 4"C 4#500 & 1#500 GND
28 3000 3040 (8) 500 KCMIL (8) 3"C 2#500 & 1#400 GND (8) 3-1/2"C 3#500 & 1#400 GND (8) 3-1/2"C 4#500 & 1#400 GND
27 2500 2660 (7) 500 KCMIL (7) 3"C 2#500 & 1#350 GND (7) 3-1/2"C 3#500 & 1#350 GND (7) 3-1/2"C 4#500 & 1#350 GND
26 2000 2010 (6) 400 KCMIL (6) 2-1/2"C 2#400 & 1#250 GND (6) 3"C 3#400 & 1#250 GND (6) 3-1/2"C 4#400 & 1#250 GND
25 1600 1675 (5) 400 KCMIL (5) 2-1/2"C 2#400 & 1#4/0 GND (5) 3"C 3#400 & 1#4/0 GND (5) 3-1/2"C 4#400 & 1#4/0 GND
24 1600 1680 (4) 600 KCMIL (4) 3"C 2#600 & 1#4/0 GND (4) 3-1/2"C 3#600 & 1#4/0 GND (4) 4"C 4#600 & 1#4/0 GND
23 1200 1240 (4) 350 KCMIL (4) 2-1/2"C 2#350 & 1#3/0 GND (4) 3"C 3#350 & 1#3/0 GND (4) 3"C 4#350 & 1#3/0 GND
22 1000 1020 (4) 250 KCMIL (4) 2"C 2#250 & 1#2/0 GND (4) 2-1/2"C 3#250 & 1#2/0 GND (4) 3"C 4#250 & 1#2/0 GND
21 800 855 (3) 300 KCMIL (3) 2-1/2"C 2#300 & 1#1/0 GND (3) 2-1/2"C 3#300 & 1#1/0 GND (3) 3"C 4#300 & 1#1/0 GND
20 600 620 (2) 350 KCMIL (2) 2-1/2"C 2#350 & 1#1 GND (2) 3"C 3#350 & 1#1 GND (2) 3"C 4#350 & 1#1 GND
19 500 510 (2) 250 KCMIL (2) 2"C 2#250 & 1#2 GND (2) 2-1/2"C 3#250 & 1#2 GND (2) 3"C 4#250 & 1#2 GND
18 400 400 (2) 3/0 AWG (2) 1-1/2"C 2#3/0 & 1#3 GND (2) 2"C 3#3/0 & 1#3 GND (2) 2-1/2"C 4#3/0 & 1#3 GND
17 400 380 500 KCMIL 2-1/2"C 2#500 & 1#3 GND 3"C 3#500 & 1#3 GND 3-1/2"C 4#500 & 1#3 GND
16 300 310 350 KCMIL 2-1/2"C 2#350 & 1#4 GND 3"C 3#350 & 1#4 GND 3"C 4#350 & 1#4 GND
15 250 255 250 KCMIL 2"C 2#250 & 1#4 GND 2-1/2"C 3#250 & 1#4 GND 3"C 4#250 & 1#4 GND
14 225 230 4/0 AWG 2"C 2#4/0 & 1#4 GND 2"C 3#4/0 & 1#4 GND 2-1/2"C 4#4/0 & 1#4 GND
13 200 200 3/0 AWG 1-1/2"C 2#3/0 & 1#6 GND 2"C 3#3/0 & 1#6 GND 2-1/2"C 4#3/0 & 1#6 GND
12 175 175 2/0 AWG 1-1/2"C 2#2/0 & 1#6 GND 2"C 3#2/0 & 1#6 GND 2"C 4#2/0 & 1#6 GND
11 150 150 1/0 AWG 1-1/4"C 2#1/0 & 1#6 GND 1-1/2"C 3#1/0 & 1#6 GND 2"C 4#1/0 & 1#6 GND
10 125 130 1 AWG 1-1/4"C 2#1 & 1#6 GND 1-1/2"C 3#1 & 1#6 GND 2"C 4#1 & 1#6 GND
9 100 100 3 AWG 1-1/4"C 2#3 & 1#8 GND 1-1/4"C 3#3 & 1#8 GND 1-1/4"C 4#3 & 1#8 GND
8 90 100 3 AWG 1-1/4"C 2#3 & 1#8 GND 1-1/4"C 3#3 & 1#8 GND 1-1/4"C 4#3 & 1#8 GND
7 80 85 4 AWG 1"C 2#4 & 1#8 GND 1-1/4"C 3#4 & 1#8 GND 1-1/4"C 4#4 & 1#8 GND
6 70 85 4 AWG 1"C 2#4 & 1#8 GND 1-1/4"C 3#4 & 1#8 GND 1-1/4"C 4#4 & 1#8 GND
5 60 65 6 AWG 1"C 2#6 & 1#10 GND 1"C 3#6 & 1#10 GND 1-1/4"C 4#6 & 1#10 GND
4 50 40 8 AWG 3/4"C 2#8 & 1#10 GND 1"C 3#8 & 1#10 GND 1"C 4#8 & 1#10 GND
3 40 40 8 AWG 3/4"C 2#8 & 1#10 GND 1"C 3#8 & 1#10 GND 1"C 4#8 & 1#10 GND
2 30 30 10 AWG 3/4"C 2#10 & 1#10 GND 3/4"C 3#10 & 1#10 GND 1"C 4#10 & 1#10 GND
1 20 20 12 AWG 3/4"C 3#12 & 1#12 GND 3/4"C 3#12 & 1#12 GND 3/4"C 4#12 & 1#12 GND
2 - WIRE WITH GROUND 3 - WIRE WITH GROUND 4 - WIRE WITH GROUND
TAGS FEEDER
AMPS
ACTUAL
AMPS
CONDUCTOR SIZE
FEEDER AND CONDUIT SIZES
COPPER FEEDER SCHEDULE
1. PROVIDE WEATHER RESISTANT NEMA-3R DISCONNECT.
2. PROVIDE CONDUIT AND CONDUCTORS TO EXTEND SCHEDULED CONDUCTORS THROUGH EXTERIOR CONDENSING UNIT ACCU-3 TO INTERIOR CASSETTE FCU WITHIN THE
ELECTRICAL ROOM, PER MANUFACTURER INSTRUCTIONS.
3. PROVIDE DUCT SMOKE DETECTOR PER NFPA REQUIREMENTS IN RETURN DUCT OF UNIT.
SCHEDULE NOTES:
FILE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Signature:
Typed or Printed Name:
Date: Reg. No.:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
DULUTH, MINNESOTA
148th FIGHTER WING
MINNESOTA AIR
NATIONAL GUARD
CONSTRUCT SMALL
ARMS RANGE
XXX
FMKM179063
COPYRIGHT 2020 BY LHB, INC. ALL RIGHTS RESERVED.
NO DATE ISSUED FOR
21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446
10/5/20
MARK J. VINCENT
52349
B3 FINAL SUBMITTAL
B
IM
/1
M n A
N G
C o n s tr u c t S m a ll A rm s R a n g e /1
M n A
N G
C o n s tr u c t S m a ll A rm s R a n g e
M E
P
.r v t
/1
/2
:3
:2
P M
E602
10/5/2020
AML
MJV
180940
ELECTRICAL
SCHEDULES
ELECTRICAL EQUIPMENT SCHEDULE
NO. DESCRIPTION ROOM
LOAD
VOLT PHASE
CONDUIT &
WIRE SIZE
STARTER
COMPONENT
CONTROL DEVICE
COMPONENT
DISCONNECT
COMPONENT NOTESHP A W
0 0 208 3 DIGITAL CONTROL
ACCU-1 AIR COOLED CONDENSING UNIT SITE 18 0 208 1 2#6, 1#10G,
1"C
BY DIV 23 BY DIV 23 NFS 1
ACCU-2 AIR COOLED CONDENSING UNIT SITE 18 0 208 1 2#6, 1#10G,
1"C
BY DIV 23 BY DIV 23 NFS 1
ACCU-3 AIR COOLED CONDENSING UNIT SITE 15 0 208 1 2#10, 1#10G,
3/4"C
BY DIV 23 BY DIV 23 NFS 1,2
CP-1 PUMP 120 1/10 0 0 120 1 1#12, 1#12G,
3/4"C
BY DIV 23 BY DIV 23 MRS (DIV 26)
CUH-1 CABINET UNIT HEATER 100 18 0 208 3 3#10, 1#10G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT
(DIV 23)
CUH-2 CABINET UNIT HEATER 110 12 0 208 3 3#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT
(DIV 23)
EF-1 EXHAUST FAN 109 1/4 0 0 120 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) DIGITAL CONTROL
(DIV 23)
MRS (DIV 26)
ERV-1 AIR TO AIR HEAT EXCHANGER 120 2 0 0 208 3 3#12, 1#12G,
3/4"C
DIGITAL CONTROL
(DIV 23)
NFS
F-1 FURNACE 120 9 0 120 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) DIGITAL CONTROL
(DIV 23)
MRS (DIV 26)
F-2 FURNACE 120 9 0 120 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) DIGITAL CONTROL
(DIV 23)
MRS (DIV 26)
FCU FAN COIL UNIT 111 1 0 208 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS 2
HD1 HAND DRYER 104 8 0 120 1 2#10, 1#10G,
3/4"C
W/UNIT W/UNIT W/UNIT
HD2 HAND DRYER 106 8 0 120 1 2#10, 1#10G,
3/4"C
W/UNIT W/UNIT W/UNIT
RP-1 RADIANT CEILING PANEL 104 & 106 5 0 208 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS
RP-2 RADIANT CEILING PANEL 105A 6 0 208 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS
UH-1 UNIT HEATER 120 24 0 208 1 2#10, 1#10G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT
(DIV 23)
WH-1 WATER HEATER 120 5 0 120 1 2#12, 1#12G,
3/4"C
INTEGRAL (DIV 23) INTEGRAL (DIV 23) MRS (DIV 26)
NOTES:
FIRING RANGE 108077 VA 125.00% 135096 VA
HEAT 20301 VA 100.00% 20301 VA EST. DEMAND CURRENT: 497 A
KTCH 360 VA 100.00% 360 VA CONN. CURRENT: 428 A
SPEC 2880 VA 100.00% 2880 VA EST. DEMAND LOAD: 413324 VA
MTR 211737 VA 114.24% 241888 VA CONN. LOAD: 355820 VA
COMP 3600 VA 100.00% 3600 VA
LITES 2166 VA 125.00% 2708 VA
RCPT 7740 VA 100.00% 7740 VA
Other 0 VA 0.00% 0 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
6 -- 3 100 A 0.0 kVA SPARE 5 100 A 1 20 A 0.2 kVA LITES SITE 4 400 A 3 300 A 302.1 kVA T2 3 100 A 1 20 A 0.8 kVA LITES 101,102,103,104,106,110B,120 2 200 A 3 150 A 52.1 kVA T1 1 100 A 1 20 A 1.2 kVA LITES 100,105,105A,107,107A,109,110,111
CKT FRAME POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES
SECTION No. 1
BUS AMPS: 800 AMPS SPECIAL:
MAIN DEVICE: 800 A MLO A.I.C. RATING: 35,000 AMPS SYMMETRICAL
LOCATION: ELEC 109 VOLTAGE: 480Y/277 V. 3 ø 4 W.
DISTRIBUTION PANEL: MDP
NOTES:
HEAT 20301 VA 100.00% 20301 VA
KTCH 360 VA 100.00% 360 VA
SPEC 2880 VA 100.00% 2880 VA EST. DEMAND CURRENT: 147 A
MTR 17251 VA 105.43% 18187 VA CONNECTED CURRENT: 145 A
COMP 3600 VA 100.00% 3600 VA ESTIMATED DEMAND: 53068 VA
RCPT 7740 VA 100.00% 7740 VA CONNECTED LOAD: 52132 VA
Other 0 VA 0.00% 0 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 152 A 162 A 127 A
TOTAL LOAD: 18 kVA 19 kVA 15 kVA
SPARE 20 A 1 53 0.0 12.7 54
SPARE 20 A 1 51 0.0 13.0 52
SPARE 20 A 1 49 0.0 12.0 50
3 20 A PANEL B
SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE
SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE
SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE
SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE
SPARE 20 A 1 39 0.0 0.0 40 1 20 A SPARE
SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE
SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE
SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE
SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE
SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE
SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE
SPARE 20 A 1 25 0.0 0.2 26 1 20 A RCPT VENDING MACHINE 110B
23 0.0 0.7 24 1 20 A SPEC EWC 110B
SPEC RCPT 111 20 A 2
21 0.0 1.0 22 1 20 A SPEC HD2 106
RCPT111 20 A 1 19 0.0 1.0 20 1 20 A SPEC HD1 104
RCPT 111 20 A 1 17 0.0 0.2 18 1 20 A KTCH MICROWAVE 102
RCPT 120 20 A 1 15 0.9 0.2 16 1 20 A KTCH REFRIG 102
13 0.0 0.7 14 1 20 A RCPT 102,110
SPEC RCPT 111 20 A 2
11 0.0 0.7 12 1 20 A RCPT 102,110
RCPT 111 20 A 1 9 1.1 1.1 10 1 20 A COMP 102
RCPT 109,111 20 A 1 7 0.5 1.4 8 1 20 A COMP 102
RCPT WP GFCI 20 A 1 5 0.7 0.2 6 1 20 A RCPT PRINTER 101
RCPT 105,105A,107,107A,110 20 A 1 3 0.9 0.9 4 1 20 A COMP,RCPT 100,101
RCPT 103,105,105A,107,107A,110 20 A 1 1 1.1 0.9 2 1 20 A COMP,RCPT 101
LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION
BUS AMPS: 225 AMPS
MAIN DEVICE: 225 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL
LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.
PANELBOARD: A
NOTES:
EST. DEMAND CURRENT: 107 A
CONNECTED CURRENT: 105 A
HEAT 20301 VA 100.00% 20301 VA ESTIMATED DEMAND: 38656 VA
SPEC 168 VA 100.00% 168 VA CONNECTED LOAD: 37720 VA
MTR 17251 VA 105.43% 18187 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 100 A 109 A 107 A
TOTAL LOAD: 12 kVA 13 kVA 13 kVA
SPACE -- -- 53 0.0 0.0 54 -- -- SPACE
SPACE -- -- 51 0.0 0.0 52 -- -- SPACE
SPACE -- -- 49 0.0 0.0 50 -- -- SPACE
SPACE -- -- 47 0.0 0.0 48 -- -- SPACE
SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE
SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE
SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE
SPARE 20 A 1 39 0.0 0.0 40 1 20 A SPARE
SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE
SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE
SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE
SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE
HEAT TRACE 20 A 1 29 0.2 0.0 30 1 20 A SPARE
CP-1 120 20 A 1 27 0.4 1.6 28
EF-1 109 20 A 1 25 0.7 1.6 26
2 25 A ACCU-3 & FCU
WH-1 120 20 A 1 23 0.6 1.9 24
F-2 120 20 A 1 21 1.1 1.9 22
2 45 A ACCU-2
F-1 120 20 A 1 19 1.1 1.9 20
17 0.9 1.9 18
2 45 A ACCU-1
15 0.9 0.0 16 1 20 A SPAREERV-1 15 A 3
13 0.9 0.0 14 1 20 A SPARE
11 1.4 2.5 12
9 1.4 2.5 10
2 30 A UH-1 120
CUH-2 110 20 A 3
7 1.4 1.2 8
5 2.2 1.2 6
2 20 A RCP-2 105A
3 2.2 1.0 4CUH-1 100 25 A 3
1 2.2 1.0 2
2 20 A RCP-1 104 & 106
LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION
BUS AMPS: 225 AMPS
MAIN DEVICE: 225 A MLO SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL
LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.
PANELBOARD: B
100 A
NO DATE REVISION
1 06/19/2021 ADDENDUM 02
2 07/01/2021 ADDENDUM 04
NOTES:
EST. DEMAND CURRENT: 997 A
CONN. CURRENT: 839 A
EST. DEMAND LOAD: 359174 VA
CONN. LOAD: 302149 VA
FIRING RANGE 108077 VA 125.00% 135096 VA
MTR 194534 VA 115.47% 224638 VA
LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
9 200 A 3 150 A 51.5 kVA REF 8 200 A 3 150 A 26.9 kVA RHU 7 400 A 3 350 A 116.9 kVA RCU 6 200 A 3 150 A 18.0 kVA FIRING RANGE 5 200 A 3 150 A 18.0 kVA FIRING RANGE 4 200 A 3 150 A 18.0 kVA FIRING RANGE 3 200 A 3 150 A 18.0 kVA FIRING RANGE 2 200 A 3 150 A 18.0 kVA FIRING RANGE 1 200 A 3 150 A 18.0 kVA FIRING RANGE
CKT FRAME POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES
SECTION No. 1
BUS AMPS: 1000 AMPS SPECIAL:
MAIN DEVICE: 1000 A MCB A.I.C. RATING: 22,000 AMPS SYMMETRICAL
LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.
DISTRIBUTION PANEL: SDP