This solicitation requests proposals for a firm fixed-price contract to provide all plant, labor, transportation, materials, tools, equipment, appliances and supervision necessary to construct a small arms range and conventionally constructed CATM facility. Scope of work includes site work, utilities, structural, architectural, mechanical and electrical systems to support the CATM facility and firing range. The magnitude of the project is estimated between $5,000,000 to $10,000,000. Construction is to be completed within 360 calendar days after notice to proceed. The NAICS code is 236220 and small business size standard is $39.5 million. This action is set aside for small businesses. A pre-proposal conference will be held on June 3, 2021 and site visit will follow. Questions are due by June 19, 2021. Proposals are due by June 22, 2021. Evaluation factors are best value past performance and price. Award will be made without discussions to the responsible offeror whose proposal follows the solicitation instructions and is determined most advantageous to the Government considering the factors. Interested offerors must register in SAM. Plans and specifications are available at beta.SAM. All inquiries must be in writing. Place of performance is Duluth National Guard Base, MN. The soliciting agency is Department of the Army Minnesota Army National Guard.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Construct Small Arms Range 7/2/2021

FMKM179063

ADDENDUM 04 Page 1 of 1

LHB #180940

ANSWERS TO CONTRACTOR QUESTIONS: None

CHANGES TO SPECIFICATIONS: None

CHANGES TO DRAWINGS:

1. Replace Drawing Sheet E401 – ENLARGED ELECTRICAL PLANS & DIAGRAMS (attached).

2. Replace Drawing Sheet E602 – ELECTRICAL SCHEDULES (attached).

ATTACHMENTS: Sheets E401 and E602

End of Addendum 04

F

S

FS

JJ

KEYED SHEET NOTESKEYED SHEET NOTES

J

5 6

ELEC

TELE

EF-1

FCU

TMGB

48"

W

A

B

T1

15cd

W 48"

B

11,13

11,132

T2

GFCI

48" 7

SECP

17 19

FACP

RCK/11

RCK/12

21,23

21,23

A

11,13

A

21,23

5 6

SDP

MDP

J

MECH

F-2 F-1

CP-1

1/10

UH-1

WH-1

B

13,15,17 B

10,12B

21 B

B

GFCI

48"

A

B

GFCI

48"

48"

GFCI

48"

GFCI

48"

48" 15

ERV-1

LEVEL 1

ROOF

GRADE

ELEC 106

MV

DISTRIBUTION

TRANSFORMER

T-SA/DOMOPS

T1

MDP

9SPD

SECONDARY

CONNECTION

CABINET

SCC-SA

M

10 11

SPD

A B

M

M 12

11 11 11 11 11 11 17 7 11

15 15 15 15 15 16

17 17 17

RCU RHU REF

SDP

T2

FIRE SUPPR

WATER

SERVICE

STEEL REINF.

IN BASE OF

FOOTING

STEEL

STRUCTURE

MBG1

G N

MAIN

SWBD

#3/0 CU

T-1

GND BUS

#3/0 CU

C U

(2) GND ROD

ELECTRODES

WATER

SERVICE LIGHTNING

PROTECTION

GND RODS

C U

TMGB

C U

3/

C

U

#3/0 CU

#4 CU

T-2

C U

1. REFER TO COMMUNICATIONS RISER DIAGRAM FOR CONDUCTOR

SIZE.

2. PROVIDE #3/0 CU BONDING JUMPER ACROSS METER.

3. PROVIDE RACEWAY AND CONDUCTORS TO EXTERIOR CONDENSING

UNIT. REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL

INFORMATION.

4. REFER TO DETAILS ON T5## SERIES OF DRAWINGS FOR ADDITIONAL

INFORMATION/REQUIREMENTS FOR COMMUNICATION ROOM.

5. BACKBONE CABLING CONDUITS. REFER TO ELECTRICAL SITE PLAN

AND TECHNOLOGY RISER DIAGRAM FOR FOR ADDITIONAL

INFORMATION.

6. PROVIDE FIRE RATED PLYWOOD BOARDS TO LINE COMMUNICATION

ROOM. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. PROVIDE CABLETRAY ABOVE RACKS AND AS NOTED/SHOWN ON

COMMUNICATION DETAILS.

8. PROVIDE CONDUIT ONLY FOR FUTURE DOMOPS BUILDING SERVICE

CONDUCTORS.

9. PROVIDE CONDUITS FROM TRANSFORMER TO MANHOLE MH-A1, AS

NOTED ON ELECTRICAL SITE PLAN. INSTALL PRIMARY FEEDER CABLE

AS NOTED ON ELECTRICAL SITE PLAN.

10. PROVIDE 480/277V, 3PH, 4W, 1600A CONNECTION CABINET WITH

METERING COMPARTMENT ACCOMMODATIONS. PROVIDE (1)400/3 AND

(1)800/3 BREAKERS FOR SMALL ARMS AND DOMOPS FEEDERS.

PROVIDE BUSSING AND SPACE ACCOMMODATIONS FOR A FUTURE

800/3 FUSED DISCONNECT.

11. PROVIDE METERING FOR TWO BREAKERS AND ACCOMMODATIONS

FOR A FUTURE THIRD METER. REFER TO SPECIFICATIONS FOR

POWER METERING REQUIREMENTS.

12. PROVIDE DISTRIBUTION STYLE PANELBOARD.

13. PROVIDE HOUSEKEEPING PAD AND ISOLATION PADS/SPRINGS FOR

FLOOR MOUNTED TRANSFORMERS. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS.

14. PROVIDE 600/3AS; 500AF FUSED ENCLOSED SWITCH.

15. PROVIDE FEEDERS TO FIRING RANGE'S ENCLOSED

SWITCHES/PANELBOARDS. COORDINATE WITH SUPPLIED FIRING

RANGE PRIOR TO WORK COMMENCING FOR ADDITIONAL

REQUIREMENTS.

16. ADDITIONAL LANES BID OPTION: PROVIDE FEEDERS TO FIRING

RANGE'S ENCLOSED SWITCHES/ PANELBOARDS. COORDINATE WITH

SUPPLIED FIRING RANGE PRIOR TO WORK COMMENCING FOR

ADDITIONAL REQUIREMENTS.

17. PROVIDE FEEDERS TO FIRING RANGE'S HVAC EQUIPMENT.

COORDINATE WITH SUPPLIED FIRING RANGE PRIOR TO WORK

COMMENCING FOR ADDITIONAL REQUIREMENTS.

18. PROVIDE MANUFACTURER'S STRUCTURE FOR STACKING

TRANSFORMERS, WITH LARGER TRANSFORMER LOCATED ON THE

BOTTOM.

A. ALL TRANSFORMERS TO HAVE A DELTA PRIMARY UNLESS NOTED OTHERWISE.

GENERAL NOTES:

1. PROVIDE HOUSEKEEPING EQUIPMENT PAD FOR TRANSFORMER AS CALLED OUT IN SPECIFICATIONS.

2. PROVIDE CONCRETE PAD AS DETAILED ON DRAWING.

3. PROVIDE VIBRATION PADS/SPRINGS.

SCHEDULE NOTES:

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.

Signature:

Typed or Printed Name:

Date: Reg. No.:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

DULUTH, MINNESOTA

148th FIGHTER WING

MINNESOTA AIR

NATIONAL GUARD

CONSTRUCT SMALL

ARMS RANGE

XXX

FMKM179063

COPYRIGHT 2020 BY LHB, INC. ALL RIGHTS RESERVED.

NO DATE ISSUED FOR

21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446

10/5/20

MARK J. VINCENT

52349

B3 FINAL SUBMITTAL

B

IM

/1

M n A

N G

C o n s tr u c t S m a ll A rm s R a n g e /1

M n A

N G

C o n s tr u c t S m a ll A rm s R a n g e

M E

P

.r v t

/1

/2

:3

:2

P M

E401

10/5/2020

AML

MJV

180940

ENLARGED ELECTRICAL

PLANS & DIAGRAMS

1/4" = 1'-0"1

ENLARGED ELECTRICAL PLAN - ELEC 109 & TELE 111

1/4" = 1'-0"2

ENLARGED ELECTRICAL PLAN - MECH 120

NOT TO SCALE4

ELECTRICAL POWER DISTRIBUTION DIAGRAM

NOT TO SCALE3

GROUNDING RISER DIAGRAM

TRANSFORMER SCHEDULE

IDENTIFICATION KVA PHASE

PRIMARY

VOLTAGE

SECONDARY

VOLTAGE IMPEDANCE

MOUNTING

STYLE NOTES

T1 75 3 480 V 208Y/120 3% FLOOR 1,3

T2 300 3 480 V 208Y/120 3% FLOOR 1,3

T-SA/ DOMOPS 500 3 13800 V 480Y/277 3% GRADE 2

NO DATE REVISION

1 06/19/2021 ADDENDUM 02

2 07/01/2021 ADDENDUM 04

30 5000 5320 (14) 500 KCMIL (14) 3"C 2#500 & 2#350 GND (14) 3-1/2"C 3#500 & 2#350 GND (14) 4"C 4#500 & 2#350 GND

29 4000 4180 (11) 500 KCMIL (11) 3"C 2#500 & 1#500 GND (11) 3-1/2"C 3#500 & 1#500 GND (11) 4"C 4#500 & 1#500 GND

28 3000 3040 (8) 500 KCMIL (8) 3"C 2#500 & 1#400 GND (8) 3-1/2"C 3#500 & 1#400 GND (8) 3-1/2"C 4#500 & 1#400 GND

27 2500 2660 (7) 500 KCMIL (7) 3"C 2#500 & 1#350 GND (7) 3-1/2"C 3#500 & 1#350 GND (7) 3-1/2"C 4#500 & 1#350 GND

26 2000 2010 (6) 400 KCMIL (6) 2-1/2"C 2#400 & 1#250 GND (6) 3"C 3#400 & 1#250 GND (6) 3-1/2"C 4#400 & 1#250 GND

25 1600 1675 (5) 400 KCMIL (5) 2-1/2"C 2#400 & 1#4/0 GND (5) 3"C 3#400 & 1#4/0 GND (5) 3-1/2"C 4#400 & 1#4/0 GND

24 1600 1680 (4) 600 KCMIL (4) 3"C 2#600 & 1#4/0 GND (4) 3-1/2"C 3#600 & 1#4/0 GND (4) 4"C 4#600 & 1#4/0 GND

23 1200 1240 (4) 350 KCMIL (4) 2-1/2"C 2#350 & 1#3/0 GND (4) 3"C 3#350 & 1#3/0 GND (4) 3"C 4#350 & 1#3/0 GND

22 1000 1020 (4) 250 KCMIL (4) 2"C 2#250 & 1#2/0 GND (4) 2-1/2"C 3#250 & 1#2/0 GND (4) 3"C 4#250 & 1#2/0 GND

21 800 855 (3) 300 KCMIL (3) 2-1/2"C 2#300 & 1#1/0 GND (3) 2-1/2"C 3#300 & 1#1/0 GND (3) 3"C 4#300 & 1#1/0 GND

20 600 620 (2) 350 KCMIL (2) 2-1/2"C 2#350 & 1#1 GND (2) 3"C 3#350 & 1#1 GND (2) 3"C 4#350 & 1#1 GND

19 500 510 (2) 250 KCMIL (2) 2"C 2#250 & 1#2 GND (2) 2-1/2"C 3#250 & 1#2 GND (2) 3"C 4#250 & 1#2 GND

18 400 400 (2) 3/0 AWG (2) 1-1/2"C 2#3/0 & 1#3 GND (2) 2"C 3#3/0 & 1#3 GND (2) 2-1/2"C 4#3/0 & 1#3 GND

17 400 380 500 KCMIL 2-1/2"C 2#500 & 1#3 GND 3"C 3#500 & 1#3 GND 3-1/2"C 4#500 & 1#3 GND

16 300 310 350 KCMIL 2-1/2"C 2#350 & 1#4 GND 3"C 3#350 & 1#4 GND 3"C 4#350 & 1#4 GND

15 250 255 250 KCMIL 2"C 2#250 & 1#4 GND 2-1/2"C 3#250 & 1#4 GND 3"C 4#250 & 1#4 GND

14 225 230 4/0 AWG 2"C 2#4/0 & 1#4 GND 2"C 3#4/0 & 1#4 GND 2-1/2"C 4#4/0 & 1#4 GND

13 200 200 3/0 AWG 1-1/2"C 2#3/0 & 1#6 GND 2"C 3#3/0 & 1#6 GND 2-1/2"C 4#3/0 & 1#6 GND

12 175 175 2/0 AWG 1-1/2"C 2#2/0 & 1#6 GND 2"C 3#2/0 & 1#6 GND 2"C 4#2/0 & 1#6 GND

11 150 150 1/0 AWG 1-1/4"C 2#1/0 & 1#6 GND 1-1/2"C 3#1/0 & 1#6 GND 2"C 4#1/0 & 1#6 GND

10 125 130 1 AWG 1-1/4"C 2#1 & 1#6 GND 1-1/2"C 3#1 & 1#6 GND 2"C 4#1 & 1#6 GND

9 100 100 3 AWG 1-1/4"C 2#3 & 1#8 GND 1-1/4"C 3#3 & 1#8 GND 1-1/4"C 4#3 & 1#8 GND

8 90 100 3 AWG 1-1/4"C 2#3 & 1#8 GND 1-1/4"C 3#3 & 1#8 GND 1-1/4"C 4#3 & 1#8 GND

7 80 85 4 AWG 1"C 2#4 & 1#8 GND 1-1/4"C 3#4 & 1#8 GND 1-1/4"C 4#4 & 1#8 GND

6 70 85 4 AWG 1"C 2#4 & 1#8 GND 1-1/4"C 3#4 & 1#8 GND 1-1/4"C 4#4 & 1#8 GND

5 60 65 6 AWG 1"C 2#6 & 1#10 GND 1"C 3#6 & 1#10 GND 1-1/4"C 4#6 & 1#10 GND

4 50 40 8 AWG 3/4"C 2#8 & 1#10 GND 1"C 3#8 & 1#10 GND 1"C 4#8 & 1#10 GND

3 40 40 8 AWG 3/4"C 2#8 & 1#10 GND 1"C 3#8 & 1#10 GND 1"C 4#8 & 1#10 GND

2 30 30 10 AWG 3/4"C 2#10 & 1#10 GND 3/4"C 3#10 & 1#10 GND 1"C 4#10 & 1#10 GND

1 20 20 12 AWG 3/4"C 3#12 & 1#12 GND 3/4"C 3#12 & 1#12 GND 3/4"C 4#12 & 1#12 GND

2 - WIRE WITH GROUND 3 - WIRE WITH GROUND 4 - WIRE WITH GROUND

TAGS FEEDER

AMPS

ACTUAL

AMPS

CONDUCTOR SIZE

FEEDER AND CONDUIT SIZES

COPPER FEEDER SCHEDULE

1. PROVIDE WEATHER RESISTANT NEMA-3R DISCONNECT.

2. PROVIDE CONDUIT AND CONDUCTORS TO EXTEND SCHEDULED CONDUCTORS THROUGH EXTERIOR CONDENSING UNIT ACCU-3 TO INTERIOR CASSETTE FCU WITHIN THE

ELECTRICAL ROOM, PER MANUFACTURER INSTRUCTIONS.

3. PROVIDE DUCT SMOKE DETECTOR PER NFPA REQUIREMENTS IN RETURN DUCT OF UNIT.

SCHEDULE NOTES:

FILE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

I HEREBY CERTIFY that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.

Signature:

Typed or Printed Name:

Date: Reg. No.:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

DULUTH, MINNESOTA

148th FIGHTER WING

MINNESOTA AIR

NATIONAL GUARD

CONSTRUCT SMALL

ARMS RANGE

XXX

FMKM179063

COPYRIGHT 2020 BY LHB, INC. ALL RIGHTS RESERVED.

NO DATE ISSUED FOR

21 W. Superior St., Ste 500 | Duluth, MN 55802 | 218.727.8446

10/5/20

MARK J. VINCENT

52349

B3 FINAL SUBMITTAL

B

IM

/1

M n A

N G

C o n s tr u c t S m a ll A rm s R a n g e /1

M n A

N G

C o n s tr u c t S m a ll A rm s R a n g e

M E

P

.r v t

/1

/2

:3

:2

P M

E602

10/5/2020

AML

MJV

180940

ELECTRICAL

SCHEDULES

ELECTRICAL EQUIPMENT SCHEDULE

NO. DESCRIPTION ROOM

LOAD

VOLT PHASE

CONDUIT &

WIRE SIZE

STARTER

COMPONENT

CONTROL DEVICE

COMPONENT

DISCONNECT

COMPONENT NOTESHP A W

0 0 208 3 DIGITAL CONTROL

ACCU-1 AIR COOLED CONDENSING UNIT SITE 18 0 208 1 2#6, 1#10G,

1"C

BY DIV 23 BY DIV 23 NFS 1

ACCU-2 AIR COOLED CONDENSING UNIT SITE 18 0 208 1 2#6, 1#10G,

1"C

BY DIV 23 BY DIV 23 NFS 1

ACCU-3 AIR COOLED CONDENSING UNIT SITE 15 0 208 1 2#10, 1#10G,

3/4"C

BY DIV 23 BY DIV 23 NFS 1,2

CP-1 PUMP 120 1/10 0 0 120 1 1#12, 1#12G,

3/4"C

BY DIV 23 BY DIV 23 MRS (DIV 26)

CUH-1 CABINET UNIT HEATER 100 18 0 208 3 3#10, 1#10G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT

(DIV 23)

CUH-2 CABINET UNIT HEATER 110 12 0 208 3 3#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT

(DIV 23)

EF-1 EXHAUST FAN 109 1/4 0 0 120 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) DIGITAL CONTROL

(DIV 23)

MRS (DIV 26)

ERV-1 AIR TO AIR HEAT EXCHANGER 120 2 0 0 208 3 3#12, 1#12G,

3/4"C

DIGITAL CONTROL

(DIV 23)

NFS

F-1 FURNACE 120 9 0 120 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) DIGITAL CONTROL

(DIV 23)

MRS (DIV 26)

F-2 FURNACE 120 9 0 120 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) DIGITAL CONTROL

(DIV 23)

MRS (DIV 26)

FCU FAN COIL UNIT 111 1 0 208 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS 2

HD1 HAND DRYER 104 8 0 120 1 2#10, 1#10G,

3/4"C

W/UNIT W/UNIT W/UNIT

HD2 HAND DRYER 106 8 0 120 1 2#10, 1#10G,

3/4"C

W/UNIT W/UNIT W/UNIT

RP-1 RADIANT CEILING PANEL 104 & 106 5 0 208 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS

RP-2 RADIANT CEILING PANEL 105A 6 0 208 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) NFS

UH-1 UNIT HEATER 120 24 0 208 1 2#10, 1#10G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) W/EQUIPMENT

(DIV 23)

WH-1 WATER HEATER 120 5 0 120 1 2#12, 1#12G,

3/4"C

INTEGRAL (DIV 23) INTEGRAL (DIV 23) MRS (DIV 26)

NOTES:

FIRING RANGE 108077 VA 125.00% 135096 VA

HEAT 20301 VA 100.00% 20301 VA EST. DEMAND CURRENT: 497 A

KTCH 360 VA 100.00% 360 VA CONN. CURRENT: 428 A

SPEC 2880 VA 100.00% 2880 VA EST. DEMAND LOAD: 413324 VA

MTR 211737 VA 114.24% 241888 VA CONN. LOAD: 355820 VA

COMP 3600 VA 100.00% 3600 VA

LITES 2166 VA 125.00% 2708 VA

RCPT 7740 VA 100.00% 7740 VA

Other 0 VA 0.00% 0 VA

LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

6 -- 3 100 A 0.0 kVA SPARE 5 100 A 1 20 A 0.2 kVA LITES SITE 4 400 A 3 300 A 302.1 kVA T2 3 100 A 1 20 A 0.8 kVA LITES 101,102,103,104,106,110B,120 2 200 A 3 150 A 52.1 kVA T1 1 100 A 1 20 A 1.2 kVA LITES 100,105,105A,107,107A,109,110,111

CKT FRAME POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES

SECTION No. 1

BUS AMPS: 800 AMPS SPECIAL:

MAIN DEVICE: 800 A MLO A.I.C. RATING: 35,000 AMPS SYMMETRICAL

LOCATION: ELEC 109 VOLTAGE: 480Y/277 V. 3 ø 4 W.

DISTRIBUTION PANEL: MDP

NOTES:

HEAT 20301 VA 100.00% 20301 VA

KTCH 360 VA 100.00% 360 VA

SPEC 2880 VA 100.00% 2880 VA EST. DEMAND CURRENT: 147 A

MTR 17251 VA 105.43% 18187 VA CONNECTED CURRENT: 145 A

COMP 3600 VA 100.00% 3600 VA ESTIMATED DEMAND: 53068 VA

RCPT 7740 VA 100.00% 7740 VA CONNECTED LOAD: 52132 VA

Other 0 VA 0.00% 0 VA

LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

TOTAL AMPS: 152 A 162 A 127 A

TOTAL LOAD: 18 kVA 19 kVA 15 kVA

SPARE 20 A 1 53 0.0 12.7 54

SPARE 20 A 1 51 0.0 13.0 52

SPARE 20 A 1 49 0.0 12.0 50

3 20 A PANEL B

SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE

SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE

SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE

SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE

SPARE 20 A 1 39 0.0 0.0 40 1 20 A SPARE

SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE

SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE

SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE

SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE

SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE

SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE

SPARE 20 A 1 25 0.0 0.2 26 1 20 A RCPT VENDING MACHINE 110B

23 0.0 0.7 24 1 20 A SPEC EWC 110B

SPEC RCPT 111 20 A 2

21 0.0 1.0 22 1 20 A SPEC HD2 106

RCPT111 20 A 1 19 0.0 1.0 20 1 20 A SPEC HD1 104

RCPT 111 20 A 1 17 0.0 0.2 18 1 20 A KTCH MICROWAVE 102

RCPT 120 20 A 1 15 0.9 0.2 16 1 20 A KTCH REFRIG 102

13 0.0 0.7 14 1 20 A RCPT 102,110

SPEC RCPT 111 20 A 2

11 0.0 0.7 12 1 20 A RCPT 102,110

RCPT 111 20 A 1 9 1.1 1.1 10 1 20 A COMP 102

RCPT 109,111 20 A 1 7 0.5 1.4 8 1 20 A COMP 102

RCPT WP GFCI 20 A 1 5 0.7 0.2 6 1 20 A RCPT PRINTER 101

RCPT 105,105A,107,107A,110 20 A 1 3 0.9 0.9 4 1 20 A COMP,RCPT 100,101

RCPT 103,105,105A,107,107A,110 20 A 1 1 1.1 0.9 2 1 20 A COMP,RCPT 101

LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION

BUS AMPS: 225 AMPS

MAIN DEVICE: 225 A MAIN CB SPECIAL:

MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL

LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.

PANELBOARD: A

NOTES:

EST. DEMAND CURRENT: 107 A

CONNECTED CURRENT: 105 A

HEAT 20301 VA 100.00% 20301 VA ESTIMATED DEMAND: 38656 VA

SPEC 168 VA 100.00% 168 VA CONNECTED LOAD: 37720 VA

MTR 17251 VA 105.43% 18187 VA

LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

TOTAL AMPS: 100 A 109 A 107 A

TOTAL LOAD: 12 kVA 13 kVA 13 kVA

SPACE -- -- 53 0.0 0.0 54 -- -- SPACE

SPACE -- -- 51 0.0 0.0 52 -- -- SPACE

SPACE -- -- 49 0.0 0.0 50 -- -- SPACE

SPACE -- -- 47 0.0 0.0 48 -- -- SPACE

SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE

SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE

SPARE 20 A 1 41 0.0 0.0 42 1 20 A SPARE

SPARE 20 A 1 39 0.0 0.0 40 1 20 A SPARE

SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE

SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE

SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE

SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE

HEAT TRACE 20 A 1 29 0.2 0.0 30 1 20 A SPARE

CP-1 120 20 A 1 27 0.4 1.6 28

EF-1 109 20 A 1 25 0.7 1.6 26

2 25 A ACCU-3 & FCU

WH-1 120 20 A 1 23 0.6 1.9 24

F-2 120 20 A 1 21 1.1 1.9 22

2 45 A ACCU-2

F-1 120 20 A 1 19 1.1 1.9 20

17 0.9 1.9 18

2 45 A ACCU-1

15 0.9 0.0 16 1 20 A SPAREERV-1 15 A 3

13 0.9 0.0 14 1 20 A SPARE

11 1.4 2.5 12

9 1.4 2.5 10

2 30 A UH-1 120

CUH-2 110 20 A 3

7 1.4 1.2 8

5 2.2 1.2 6

2 20 A RCP-2 105A

3 2.2 1.0 4CUH-1 100 25 A 3

1 2.2 1.0 2

2 20 A RCP-1 104 & 106

LOAD DESCRIPTION BKR P CKT A B C CKT P BKR LOAD DESCRIPTION

BUS AMPS: 225 AMPS

MAIN DEVICE: 225 A MLO SPECIAL:

MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICAL

LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.

PANELBOARD: B

100 A

NO DATE REVISION

1 06/19/2021 ADDENDUM 02

2 07/01/2021 ADDENDUM 04

NOTES:

EST. DEMAND CURRENT: 997 A

CONN. CURRENT: 839 A

EST. DEMAND LOAD: 359174 VA

CONN. LOAD: 302149 VA

FIRING RANGE 108077 VA 125.00% 135096 VA

MTR 194534 VA 115.47% 224638 VA

LOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS

9 200 A 3 150 A 51.5 kVA REF 8 200 A 3 150 A 26.9 kVA RHU 7 400 A 3 350 A 116.9 kVA RCU 6 200 A 3 150 A 18.0 kVA FIRING RANGE 5 200 A 3 150 A 18.0 kVA FIRING RANGE 4 200 A 3 150 A 18.0 kVA FIRING RANGE 3 200 A 3 150 A 18.0 kVA FIRING RANGE 2 200 A 3 150 A 18.0 kVA FIRING RANGE 1 200 A 3 150 A 18.0 kVA FIRING RANGE

CKT FRAME POLES RATING KVA DESCRIPTION/NAMEPLATE NOTES

SECTION No. 1

BUS AMPS: 1000 AMPS SPECIAL:

MAIN DEVICE: 1000 A MCB A.I.C. RATING: 22,000 AMPS SYMMETRICAL

LOCATION: ELEC 109 VOLTAGE: 208Y/120 V. 3 ø 4 W.

DISTRIBUTION PANEL: SDP