This solicitation is for the upgrade of building 504 fire detection and installation of fire suppression at Volk Field Air National Guard Base in Camp Douglas, Wisconsin. The single firm fixed price contract will be awarded by the United States Property and Fiscal Office in Wisconsin. Work includes upgrading fire detection panels to Monaco Vulcan systems and installing a fire suppression system. The project value is estimated between $1 million to $5 million. The North American Industry Classification code is 236220 for commercial and institutional buildings. The small business set aside contract duration is 365 days from notice to proceed. The pre-bid conference will be held on-site with registration required. The bid opening will follow FAR and DFARS procedures. Interested parties must be registered in SAM.gov, which will also host the solicitation and amendments. A bid bond is required. Funding availability is anticipated by September 30, 2022.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Job Name:

Description:

Entered by: B. Parson Checked By: Project Number: 1220390

Test Date: 6/16/2022 Time: 8:10 AM

Entered Values Calculated Values Static pressure PSIG

(1) 54 K value (4) 449.4

Resid pressure PSIG

(2) 50

Resid Flow at 10 PSIG

(5) 3468.0

Resid Flow GPM (3) 950

Resid Flow at 20 PSIG

(5) 3017.2

Flowing Outlet psi 32 Flow Pressure

Orifice size (6) 2.5 0.00 54.00

Orifice Coeff (6) 0.9 387.35 53.24

774.70 51.26

1162.05 48.20

NFPA 291 FLOW CALC. 949.5029858 1549.40 44.13

1936.75 39.08

Preliminary Calculated Demand 2324.10 33.10

Pressure (psi) 58.6 2711.45 26.20

Flow (gpm) 1796 3098.80 18.41

3486.15 9.74

3873.50 0.21

Notes:

WIANG Volk Field B504 HEF Removal

1) Static Pressure is the pressure at the hydrant with the hydrant closed.

2) Residual Pressure is the pressure at the hydrant with the hydrant flowing. If the flowing hydrant is not the same hydrant as the static pressure hydrant, the flowing hydrant data must be corrected to reflect the friction loss between the two hydrants.

3) Residual Flow is the flowrate at the hydrant when it is open.

6) Calculated pitot pressure can be used to validate measured pitot pressure and other data. Typical flow tests are based on fitting flow coefficient of 0.88, and a 2.5" orifice. See Fire Prot Hdbk, 18th ed, p 6-81. FM Global requires c=0.80

4) The K value can be used in the formula Q=K*∆H^.54 to model the pipeline flow.

5) The Residual flow at 10 or 20 PSIG is the maximum GPM that a pumper truck could draw from the hydrant. Fire Chief may allow a lower minimum PSIG. The minimum PSIG is necessary to keep the pump from cavitating. 20 PSIG is generally used for FM Global

Fire Pump Demands / Requirements

950, 50

3017.2, 20

Demand, 1796, 58.6

0 500 1000 1500 2000 2500 3000 3500 4000 4500

P S

IG

GPM

Hydrant Flow Test

X:\FY22\1220390\03.DISC\03.06.Fire Prot\02.Water Flow Test\Fire Demands-WIANG B504 HEF Removal.xls Page 1