Text version
KC-46A Beddown
Alter Facilities for Maintenance
Specifications
Prepared for
U.S. Army Corps of Engineers
Revision 4
02 November 2018
CH2M HILL, Inc.
2095 Lakeside Centre Way
Suite 200 Knoxville, TN 37922
KC-46A Beddown
Alter Facilities for Maintenance
Specifications Stamp Page
Prepared for
U.S. Army Corps of Engineers
Revision 4
CH2M HILL, Inc.
2095 Lakeside Centre Way
Suite 200 Knoxville, TN 37922
USACE NYD JB MDL 695847
Revi s i on 4
SECTI ON 28 31 64. 00 10
FI RE DETECTI ON AND ALARM SYSTEM, ADDRESSABLE
08/09
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
NFPA 72 ( 2016) Nat i onal Fi r e Al ar m and Si gnal i ng Code
NFPA 90A ( 2018) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
UNDERWRI TERS LABORATORI ES ( UL)
UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or El ect r i cal I nt er medi at e Met al Condui t - - Steel
UL 1971 ( 2002; Repr i nt Oct 2008) Si gnal i ng Devi ces f or t he Hear i ng I mpai r ed
UL 268 ( 2016; Repr i nt Jul 2016) UL St andar d f or Saf et y Smoke Det ect or s f or Fi r e Al ar m Systems
UL 268A ( 2008; Repr i nt Oct 2014) Smoke Det ect or s f or Duct Appl i cat i on
UL 38 ( 2008; Repr i nt Nov 2013) Manual Si gnal i ng Boxes f or Fi r e Al ar m Syst ems
UL 464 ( 2016; Repr i nt Sep 2017) UL St andar d f or
SECTI ON 28 31 64. 00 10 Page 1
Saf et y Audi bl e Si gnal i ng Devi ces f or Fi r e Al ar m and Si gnal i ng Syst ems, I ncl udi ng Accessories
UL 521 ( 1999; Repr i nt Oct 2016) UL St andar d f or Saf et y Heat Det ect or s f or Fi r e Pr ot ect i ve Si gnal i ng Syst ems
UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel
UL 797 ( 2007; Repr i nt Mar 2017) UL St andar d f or Saf et y El ect r i cal Met al l i c Tubi ng - - St eel
1. 2 SUBMITTALS
Revi s i on 1
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00
SUBMI TTAL PROCEDURES: :
Revi s i on 1
SD- 02 Shop Dr awi ngs
Det ai l Dr awi ngs; G
SD- 03 Pr oduct Dat a
St or age Bat t er i es; G Revi s i on 2 Revi s i on 2
Techni cal Dat a and Comput er Sof t war e; G
Training
Testing
SD- 06 Test Repor t s
Test i ng; G
SD- 07 Cer t i f i cat es
Equi pment ; G
Qualifications
Revi s i on 2 Revi s i on 2
SECTI ON 28 31 64. 00 10 Page 2
1. 3 QUALI TY ASSURANCE
1. 3. 1 Qualifications
Submi t pr oof of qual i f i cat i ons f or r equi r ed per sonnel . The i nst al l er shal l submi t pr oof of exper i ence f or t he f i r e al ar m t echni c i an, and t he i nst al l i ng company.
1. 3. 1. 1 Engi neer and Techni c i an
Revi s i on 1
a. Regi st er ed Pr of essi onal Engi neer havi ng t aken and passed t he NCEES Fi r e Pr ot ect i on Engi neer i ng Exam and wi t h ver i f i cat i on of exper i ence and at l east 4 year s of cur r ent exper i ence i n t he desi gn of t he f i r e pr ot ect i on and det ect i on syst ems.
b. Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es ( NI CET) qual i f i cat i ons as an engi neer i ng t echni c i an i n f i r e al ar m syst ems pr ogr am wi t h ver i f i cat i on of exper i ence and cur r ent NI CET certificate. A NI CET Level I I I may per f or m desi gn f unct i ons f or t hi s pr oj ect under t he super vi s i on of a NI CET Level I V Techni c i an or a FPE.
c. The Regi st er ed Pr of essi onal Engi neer may per f or m al l r equi r ed i t ems under t hi s speci f i cat i on. The NI CET Fi r e Al ar m Techni c i an shal l per f or m onl y t he i t ems al l owed by t he speci f i c cat egor y of cer t i f i cat i on hel d.
1. 3. 1. 2 Installer
The i nst al l i ng Cont r act or shal l pr ovi de t he f ol l owi ng: NI CET Fi r e Al ar m Techni c i ans t o per f or m t he i nst al l at i on of t he syst em. A mi ni mum of a NI CET Level III Fi r e Al ar m Techni c i an shal l super vi se t he i nst al l at i on of t he f i r e al ar m syst em. NI CET Level 2 or hi gher Fi r e Al ar m Techni c i an shal l i nst al l and t er mi nat e f i r e al ar m devi ces, cabi net s and panel s. An el ect r i c i an or NI CET Level 1 Fi r e Al ar m Techni c i an shal l i nst al l condui t f or t he f i r e al ar m syst em. Fi r e Al ar m Techni c i ans t o per f or m t he i nst al l at i on of t he syst em. A Fi r e Al ar m Techni c i an wi t h a mi ni mum of 4 year s of exper i ence shal l per f or m/ super vi se t he i nst al l at i on of t he f i r e al ar m syst em. Fi r e Al ar m Techni c i ans wi t h a mi ni mum of 2 year s of exper i ence shal l be ut i l i zed t o assi st i n t he i nst al l at i on and t er mi nat e f i r e al ar m devi ces, cabi net s and panel s. An el ect r i c i an shal l be al l owed t o i nst al l wi r e or cabl e and t o i nst al l condui t f or t he f i r e al ar m syst em.
The Fi r e Al ar m t echni c i ans i nst al l i ng t he equi pment shal l be f act or y t r ai ned i n t he i nst al l at i on, adj ust ment , t est i ng, and oper at i on of t he equi pment speci f i ed her ei n and on t he dr awi ngs.
1. 3. 1. 3 Fi r e Pr ot ect i on Engi neer
I nst al l at i ons needi ng desi gns or modi f i cat i ons of f i r e det ect i on, f i r e al ar m, or f i r e suppr essi on syst ems r equi r e t he ser vi ces and r evi ew of a qual i f i ed f i r e pr ot ect i on engi neer . For t he pur poses of meet i ng t hi s r equi r ement , a qual i f i ed f i r e pr ot ect i on engi neer i s def i ned as an i ndi v i dual meet i ng one of t he f ol l owi ng condi t i ons:
a. An engi neer ( PE havi ng successf ul l y t aken and passed t he NCEES PE Exam) havi ng a Bachel or of Sci ence or Mast er s of Sci ence Degr ee i n Fi r e Pr ot ect i on Engi neer i ng f r om an accr edi t ed uni ver si t y engi neer i ng pr ogr am, pl us a mi ni mum of 2 year s ' wor k exper i ence i n f i r e pr ot ect i on
SECTI ON 28 31 64. 00 10 Page 3 engineering.
Revi s i on 1
b. A r egi st er ed pr of essi onal engi neer ( P. E. ) i n f i r e pr ot ect i on engineering.
c. A r egi st er ed PE i n a r el at ed engi neer i ng di sci pl i ne and member gr ade st at us i n t he Nat i onal Soci et y of Fi r e Pr ot ect i on Engi neer s.
1. 3. 2 Det ai l Dr awi ngs
Submi t det ai l dr awi ngs consi st i ng of a compl et e l i s t of equi pment and mat er i al , i ncl udi ng manuf act ur er ' s descr i pt i ve and t echni cal l i t er at ur e, cat al og cut s, and i nst al l at i on i nst r uct i ons. Not e t hat t he cont r act dr awi ngs show l ayout s based on t ypi cal audi bl e appl i ances. Check t he l ayout based on t he act ual audi bl e devi ces t o be i nst al l ed and make any necessar y r evi s i ons i n t he det ai l dr awi ngs. The det ai l dr awi ngs shal l al so cont ai n compl et e wi r i ng and schemat i c di agr ams f or t he equi pment f ur ni shed, equi pment l ayout , and any ot her det ai l s r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and wi l l pr oper l y f unct i on as a uni t . Det ai l dr awi ngs and det ai l ed poi nt - t o- poi nt wi r i ng di agr am shal l be pr epar ed and si gned by a Regi st er ed Pr of essi onal Engi neer . Di agr am shal l i ncl ude connect i ons bet ween syst em devi ces, appl i ances, cont r ol panel s, super vi sed devi ces, and equi pment t hat i s act i vat ed or cont r ol l ed by t he panel .
1. 4 TECHNI CAL DATA AND COMPUTER SOFTWARE
Revi s i on 1
Techni cal dat a and comput er sof t war e - Exi st i ng t o r emai n unl ess new devi ces r equi r ed pr ogr ammi ng.
Revi s i on 1
PART 2 PRODUCTS
2. 1 SYSTEM DESCRI PTI ON
The expansi on of t he f i r e det ect i on and al ar m syst em shal l r esul t i n a compl et e, super v i sed f i r e al ar m r epor t i ng syst em conf i gur ed i n accor dance with NFPA 72; except i ons ar e accept abl e as di r ect ed by t he Cont r act i ng Of f i cer . Fur ni sh equi pment compat i bl e and UL l i s t ed, FM appr oved, or appr oved or l i s t ed by a nat i onal l y r ecogni zed t est i ng l abor at or y i n accor dance wi t h t he appl i cabl e NFPA st andar ds. Locks shal l be keyed al i ke.
2. 1. 1 Operation
The exi st i ng i nput and out put f unct i ons of t he exi st i ng f i r e al ar m syst em shal l not change. The syst em shal l ent er i nt o t he al ar m mode by act uat i on of any al ar m i ni t i at i ng devi ce. Al ar m and super vi sor y i ni t i at i ng devi ces shal l be i ndi v i dual l y addr essabl e. Al ar m i ni t i at i ng devi ces shal l be connect ed t o s i gnal l i ne c i r cui t s ( SLC) , Cl ass A, i n accor dance wi t h NFPA 72.
Connect al ar m not i f i cat i on appl i ances t o not i f i cat i on appl i ance c i r cui t s ( NAC) , Cl ass B i n accor dance wi t h NFPA 72. Audi bl e, and v i sual appl i ances and syst ems shal l compl y wi t h NFPA 72. Fi r e al ar m syst em component s r equi r i ng power , except f or t he cont r ol panel power suppl y, shal l oper at e on 24 Vol t s dc.
SECTI ON 28 31 64. 00 10 Page 4
2. 1. 2 Oper at i onal Feat ur es
The syst em f unct i ons not be changed ot her t han t o accept a new f l ow swi t ch i n bui l di ng 3101.
2. 1. 3 Al ar m Funct i ons
Al ar m f unct i ons - out put s and act i ons shal l not be changed
2. 1. 4 I nt er f ace Wi t h Exi st i ng Fi r e Al ar m Equi pment
The equi pment speci f i ed her ei n shal l oper at e as an ext ensi on t o an exi st i ng conf i gur at i on. Submi t cer t i f i ed copi es of cur r ent appr oval s or l i s t i ngs i ssued by an i ndependent t est l ab i f not l i s t ed by UL, FM or ot her nat i onal l y r ecogni zed t est i ng l abor at or y, showi ng compl i ance wi t h speci f i ed NFPA st andar ds. The new equi pment shal l be connect ed t o an exi st i ng cont r ol panel i n t he exi st i ng par t of t he bui l di ng i f pr esent , and exi st i ng moni t or i ng equi pment at t he Super vi s i ng St at i on. Exi st i ng moni t or i ng equi pment shal l be expanded, modi f i ed, or suppl ement ed as necessar y t o ext end t he exi st i ng cont r ol moni t or i ng f unct i ons t o t he new poi nt s or zones. New component s shal l be capabl e of mer gi ng wi t h t he exi st i ng conf i gur at i on wi t hout degr adi ng t he per f or mance of ei t her syst em. The scope of t he accept ance t est s of par agr aph Test i ng shal l i ncl ude aspect s of oper at i on t hat i nvol ve combi ned use of bot h new and exi st i ng por t i ons of t he f i nal conf i gur at i on.
2. 1. 5 I nt er f ace Wi t h ot her Equi pment
I nt er f aci ng component s shal l be f ur ni shed as r equi r ed t o connect t o subsyst ems or devi ces whi ch i nt er act wi t h t he f i r e al ar m syst em, such as super vi sor y or al ar m cont act s i n suppr essi on syst ems, I nci pi ent smoke det ect i on syst ems, door r el eases, et c.
2. 2 STANDARD PRODUCTS
Pr ovi de mat er i al and equi pment whi ch ar e t he st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s f or at l east 5 year s pr i or t o bi d openi ng. Equi pment shal l be suppor t ed by a ser vi ce or gani zat i on t hat can pr ovi de ser vi ce wi t hi n 4 hour s of notification.
2. 3 NAMEPLATES
Maj or component s of equi pment shal l have t he manuf act ur er ' s name, addr ess, t ype or st y l e, vol t age and cur r ent r at i ng, and cat al og number on a noncor r osi ve and nonheat - sensi t i ve pl at e whi ch i s secur el y at t ached t o t he equipment.
2. 4 CONTROL PANEL
2. 4. 1 Remot e Syst em Audi bl e/ Vi sual Di spl ay
Revi s i on 1
Exi st i ng t o r emai n.
SECTI ON 28 31 64. 00 10 Page 5
Revi s i on 1
2. 4. 2 Ci r cui t Connect i ons
Connect c i r cui t conduct or s ent er i ng or l eavi ng t he panel t o scr ew- t ype t er mi nal s wi t h each conduct or and t er mi nal mar ked f or i dent i f i cat i on.
2. 4. 3 Syst em Expansi on and Modi f i cat i on Capabi l i t i es
Pr ovi de, as par t of t hi s cont r act , any equi pment and sof t war e needed by qual i f i ed t echni c i ans t o i mpl ement f ut ur e changes t o t he f i r e al ar m syst em.
2. 4. 4 Addr essabl e Cont r ol Modul e
The cont r ol modul e shal l be capabl e of oper at i ng as a r el ay ( dr y cont act f or m C) f or i nt er f aci ng t he cont r ol panel wi t h ot her syst ems, and t o cont r ol door hol der s or i ni t i at e el evat or f i r e ser vi ce. The modul e shal l be UL l i s t ed as compat i bl e wi t h t he cont r ol panel . The i ndi cat i ng devi ce or t he ext er nal l oad bei ng cont r ol l ed shal l be conf i gur ed as a Cl ass B not i f i cat i on appl i ance c i r cui t s. The syst em shal l be capabl e of super vi s i ng, audi bl e, v i sual and dr y cont act c i r cui t s. The cont r ol modul e shal l have bot h an i nput and out put addr ess. The super vi s i on shal l det ect a shor t on t he super vi sed c i r cui t and shal l pr event power f r om bei ng appl i ed t o t he c i r cui t . The cont r ol model shal l pr ovi de addr ess set t i ng means compat i bl e wi t h t he cont r ol panel ' s SLC super vi s i on and st or e an i nt er nal i dent i f y i ng code. The cont r ol modul e shal l cont ai n an i nt egr al LED t hat f l ashes each t i me t he cont r ol modul e i s pol l ed.
2. 4. 5 Addr essabl e I ni t i at i ng Devi ce Ci r cui t s Modul e
Revi s i on 1
Conf i gur e t he i ni t i at i ng devi ce bei ng moni t or ed as Cl ass B al l devi ces.
The syst em shal l be capabl e of def i ni ng any modul e as an al ar m modul e and r epor t al ar m t r oubl e, l oss of pol l i ng, or as a super vi sor y modul e, and r epor t i ng super v i sor y shor t , super vi sor y open or l oss of pol l i ng. The modul e shal l be UL l i s t ed as compat i bl e wi t h t he cont r ol panel . The moni t or modul e shal l pr ovi de addr ess set t i ng means compat i bl e wi t h t he cont r ol panel ' s SLC super vi s i on and st or e an i nt er nal i dent i f y i ng code.
Moni t or modul e shal l cont ai n an i nt egr al LED t hat f l ashes each t i me t he moni t or modul e i s pol l ed. Pul l s t at i ons wi t h a moni t or modul e i n a common backbox ar e not r equi r ed t o have an LED. Exi st i ng f i r e al ar m syst em i ni t i at i ng devi ce c i r cui t s shal l not be changes but may be expanded wi t h t he use of t er mi nal st r i ps i n mar ked and l abel ed back boxes wher e necessar y and wher e pr oven t o be accept abl e by Bat t er y Cal cul at i ons.
Revi s i on 1
2. 5 STORAGE BATTERI ES
Revi s i on 3
Submi t subst ant i at i ng bat t er y cal cul at i ons f or super vi sor y and al ar m power r equi r ement s. Amper e- hour r equi r ement s f or each syst em component and each panel component , and t he bat t er y r echar gi ng per i od shal l be i ncl uded.
Pr ovi de st or age bat t er i es whi ch ar e 24 Vdc seal ed, l ead- cal c i um t ype r equi r i ng no addi t i onal wat er wi t h ampl e capaci t y, wi t h pr i mar y power di sconnect ed, t o oper at e t he f i r e al ar m syst em f or a per i od of 48 hour s.
SECTI ON 28 31 64. 00 10 Page 6
Fol l owi ng t hi s per i od of bat t er y oper at i on, t he bat t er i es shal l have ampl e capaci t y t o oper at e al l component s of t he syst em, i ncl udi ng al l al ar m si gnal i ng devi ces i n t he t ot al al ar m mode f or a mi ni mum per i od of 15 mi nut es. Locat e bat t er i es at t he bot t om of t he panel or i f necessar y due t o space const r ai nt s i n a separ at e bat t er y cabi net . Pr ovi de bat t er i es wi t h over cur r ent pr ot ect i on i n accor dance wi t h NFPA 72. Separ at e bat t er y cabi net s shal l have a l ockabl e, hi nged cover s i mi l ar t o t he f i r e al ar m panel . The l ock shal l be keyed t he same as t he f i r e al ar m cont r ol panel .
Pai nt t he cabi net s t o mat ch t he f i r e al ar m cont r ol panel . Wher e a f i r e al ar m syst em i s pr ovi ded wi t h addi t i onal not i f i cat i on devi ces pr ovi de new bat t er y cal cul at i ons and addi t i onal bat t er y capaci t y as r equi r ed.
Revi s i on 3
Revi s i on 3 Revi s i on 3
2. 6 ADDRESSABLE MANUAL FI RE ALARM STATI ONS
Revi s i on 1
Addr essabl e manual f i r e al ar m st at i ons shal l conf or m t o t he appl i cabl e r equi r ement s of UL 38. Manual st at i ons shal l be connect ed i nt o s i gnal l i ne c i r cui t s. St at i ons shal l be i nst al l ed on sur f ace or semi sur f ace mount ed out l et boxes. Manual st at i ons shal l be mount ed at 48 i nches. St at i ons shal l be doubl e act i on t ype. St at i ons shal l be f i ni shed i n r ed, wi t h r ai sed l et t er oper at i ng i nst r uct i ons of cont r ast i ng col or . St at i ons r equi r i ng t he br eaki ng of gl ass or pl ast i c panel s f or oper at i on ar e not accept abl e. The use of a key or wr ench shal l be r equi r ed t o r eset t he st at i on. Gr avi t y or mer cur y swi t ches ar e not accept abl e. Swi t ches and cont act s shal l be r at ed f or t he vol t age and cur r ent upon whi ch t hey oper at e. Addr essabl e pul l s t at i ons shal l be capabl e of bei ng f i el d pr ogr ammed, shal l l at ch upon oper at i on and r emai n l at ched unt i l manual l y r eset . St at i ons shal l have a separ at e scr ew t er mi nal f or each conduct or .
Sur f ace mount ed boxes shal l be mat ched and pai nt ed t he same col or as t he f i r e al ar m manual st at i ons.
Revi s i on 1
2. 7 FI RE DETECTI NG DEVI CES
Fi r e det ect i ng devi ces shal l compl y wi t h t he appl i cabl e r equi r ement s of NFPA 72, NFPA 90A, UL 268, UL 268A, and UL 521. The det ect or s shal l be pr ovi ded as i ndi cat ed. Det ect or base shal l have scr ew t er mi nal s f or maki ng connect i ons. No sol der connect i ons wi l l be al l owed. Det ect or s l ocat ed i n conceal ed l ocat i ons ( above cei l i ng, r ai sed f l oor s, et c. ) shal l have a r emot e v i s i bl e i ndi cat or LED/ LCD. Addr essabl e f i r e det ect i ng devi ces, except f l ame det ect or s, shal l be dynami cal l y super vi sed and uni quel y i dent i f i ed i n t he cont r ol panel . Al l f i r e al ar m i ni t i at i ng devi ces shal l be i ndi v i dual l y addr essabl e, except wher e i ndi cat ed. I nst al l ed devi ces shal l conf or m t o NFPA 70 hazar d c l assi f i cat i on of t he ar ea wher e devi ces ar e t o be i nst al l ed.
SECTI ON 28 31 64. 00 10 Page 7
2. 7. 1 Smoke Det ect or s
Desi gn smoke det ect or s f or det ect i on of abnor mal smoke densi t i es. Smoke det ect or s shal l be phot oel ect r i c or t ype. Det ect or s shal l cont ai n a v i s i bl e i ndi cat or LED/ LCD t hat shows when t he uni t i s i n al ar m condi t i on.
Det ect or s shal l not be adver sel y af f ect ed by v i br at i on or pr essur e.
Det ect or s shal l be t he pl ug- i n t ype i n whi ch t he det ect or base cont ai ns t er mi nal s f or maki ng wi r i ng connect i ons. Det ect or s t hat ar e t o be i nst al l ed i n conceal ed ( above f al se cei l i ngs, et c. ) l ocat i ons shal l be pr ovi ded wi t h a r emot e i ndi cat or LED/ LCD sui t abl e f or mount i ng i n a f i ni shed, v i s i bl e l ocat i on.
2. 7. 1. 1 Phot oel ect r i c Det ect or s
Det ect or s shal l oper at e on a l i ght scat t er i ng concept usi ng an LED l i ght sour ce. Fai l ur e of t he LED shal l not cause an al ar m condi t i on. Det ect or s shal l be f act or y set f or sensi t i v i t y and shal l r equi r e no f i el d adj ust ment s of any k i nd. Det ect or s shal l have an obscur at i on r at i ng i n accor dance wi t h UL 268. Addr essabl e smoke det ect or s shal l be capabl e of havi ng t he sensi t i v i t y bei ng r emot el y adj ust ed by t he cont r ol panel .
2. 7. 1. 2 Duct Det ect or s
Duct - mount ed phot oel ect r i c smoke det ect or s shal l be f ur ni shed and i nst al l ed wher e i ndi cat ed and i n accor dance wi t h NFPA 90A. Uni t s shal l consi st of a smoke det ect or as speci f i ed i n par agr aph Phot oel ect r i c Det ect or s, mount ed i n a speci al housi ng f i t t ed wi t h duct sampl i ng t ubes. Det ect or c i r cui t r y shal l be mount ed i n a met al l i c encl osur e ext er i or t o t he duct . Det ect or s shal l have a manual r eset . Det ect or s shal l be r at ed f or ai r vel oci t i es t hat i ncl ude ai r f l ows bet ween 500 and 4000 f pm. Det ect or s shal l be power ed f r om t he f i r e al ar m panel . Sampl i ng t ubes shal l r un t he f ul l wi dt h of t he duct . The duct det ect or package shal l conf or m t o t he r equi r ement s of NFPA 90A, UL 268A, and shal l be UL l i s t ed f or use i n ai r - handl i ng syst ems. The cont r ol f unct i ons, oper at i on, r eset , and bypass shal l be cont r ol l ed f r om t he f i r e al ar m cont r ol panel . Li ght s t o i ndi cat e t he oper at i on and al ar m condi t i on; and t he t est and r eset but t ons shal l be v i s i bl e and accessi bl e wi t h t he uni t i nst al l ed and t he cover i n pl ace.
Det ect or s mount ed above 6 f eet and t hose mount ed bel ow 6 f eet t hat cannot be easi l y accessed whi l e st andi ng on t he f l oor , shal l be pr ovi ded wi t h a r emot e det ect or i ndi cat or panel cont ai ni ng t est and r eset swi t ches. Remot e l amps and swi t ches as wel l as t he af f ect ed f an uni t s shal l be pr oper l y i dent i f i ed i n et ched pl ast i c pl acar ds. Det ect or s shal l have auxi l i ar y cont act s t o pr ovi de cont r ol , i nt er l ock, and shut down f unct i ons speci f i ed i n Sect i on 23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC. The det ect or s shal l be suppl i ed by t he f i r e al ar m syst em manuf act ur er t o ensur e compl et e syst em compatibility.
2. 8 NOTI FI CATI ON APPLI ANCES
Audi bl e appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 464.
Devi ces shal l be connect ed i nt o not i f i cat i on appl i ance c i r cui t s. Devi ces shal l have a separ at e scr ew t er mi nal f or each conduct or . Audi bl e appl i ances shal l gener at e a uni que audi bl e sound f r om ot her devi ces pr ovi ded i n t he bui l di ng and sur r oundi ng ar ea. Sur f ace mount ed audi bl e appl i ances shal l be pai nt ed r ed. Recessed audi bl e appl i ances shal l be i nst al l ed wi t h a gr i l l t hat i s pai nt ed r ed.
Revi s i on 1
SECTI ON 28 31 64. 00 10 Page 8
2. 8. 1 Vi sual Not i f i cat i on Appl i ances
Vi sual not i f i cat i on appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 1971 and t he cont r act dr awi ngs. Appl i ances shal l have c l ear hi gh i nt ensi t y opt i c l ens, xenon f l ash t ubes, and out put whi t e l i ght . Device shal l be mar ked wi t h " ALERT" St r obe f l ash r at e shal l be bet ween 1 t o 3 f l ashes per second and a mi ni mum of 75 candel a. St r obe shal l be sur f ace mount ed unl ess not ed ot her wi se on dr awi ngs or i n t hi s speci f i cat i on.
2. 8. 2 Combi nat i on Audi bl e/ Vi sual Not i f i cat i on Appl i ances
Combi nat i on audi bl e/ v i sual not i f i cat i on appl i ances shal l pr ovi de t he same r equi r ement s as i ndi v i dual uni t s except t hey shal l mount as a uni t i n st andar d backboxes. Uni t s shal l be f act or y assembl ed. Any ot her audi bl e not i f i cat i on appl i ance empl oyed i n t he f i r e al ar m syst ems shal l be appr oved by t he Cont r act i ng Of f i cer .
2. 8. 3 Fi r e Al ar m Speaker s
Audi bl e appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 464.
Appl i ances shal l be connect ed i nt o not i f i cat i on appl i ance c i r cui t s.
Sur f ace mount ed audi bl e appl i ances shal l be pai nt ed r ed.
a. Speaker s shal l conf or m t o t he appl i cabl e r equi r ement s of UL 1480.
Speaker s shal l have s i x di f f er ent sound out put l evel s and oper at e wi t h audi o l i ne i nput l evel s of 70. 7 VRMs and 25 VRMs, by means of sel ect abl e t ap set t i ngs. Tap set t i ngs shal l i ncl ude t aps of 1/ 8, 1/ 4, 1/ 2, 1, and 2 wat t . Speaker s shal l i ncor por at e a hi gh ef f i c i ency speaker f or maxi mum out put at mi ni mum power acr oss a f r equency r ange of 150 Hz t o 10, 000 Hz, and shal l have a seal ed back const r uct i on.
Speaker s shal l be capabl e of i nst al l at i on on st andar d 4 i nch squar e el ect r i cal boxes. Wher e speaker s and st r obes ar e pr ovi ded i n t he same l ocat i on, t hey may be combi ned i nt o a s i ngl e wal l or cei l i ng mount ed uni t . Al l i nput s shal l be pol ar i zed f or compat i bi l i t y wi t h st andar d r ever se pol ar i t y super vi s i on of c i r cui t wi r i ng v i a t he FMCP.
b. Pr ovi de speaker mount i ng pl at es const r uct ed of col d r ol l ed st eel havi ng a mi ni mum t hi ckness of 16 gauge or mol ded hi gh i mpact pl ast i c and equi pped wi t h mount i ng hol es and ot her openi ngs as needed f or a compl et e i nst al l at i on. Fabr i cat i on mar ks and hol es shal l be gr ound and f i ni shed t o pr ovi de a smoot h and neat appear ance f or each pl at e. Each pl at e shal l be pr i med and pai nt ed.
c. Speaker s shal l ut i l i ze scr ew t er mi nal s f or t er mi nat i on of al l f i el d wiring.
Revi s i on 1
2. 9 FI RE DETECTI ON AND ALARM SYSTEM PERI PHERAL EQUI PMENT
Revi s i on 1 Revi s i on 1
2. 9. 1 Conduit
Condui t and f i t t i ngs shal l compl y wi t h NFPA 70, UL 6, UL 1242, and UL 797.
SECTI ON 28 31 64. 00 10 Page 9
2. 9. 2 Wiring
Wi r i ng shal l conf or m t o NFPA 70. Wi r i ng f or 120 Vac power shal l be No. 12 AWG mi ni mum. The SLC wi r i ng shal l be copper cabl e i n accor dance wi t h t he manuf act ur er s r equi r ement s. Wi r i ng f or f i r e al ar m dc c i r cui t s shal l be No.
16 or 14 AWG mi ni mum dependent on t he most ef f ect i ve means of ut i l i z i ng t he avai l abl e power suppl i es. Vol t ages shal l not be mi xed i n any j unct i on box, housi ng, or devi ce, except t hose cont ai ni ng power suppl i es and cont r ol r el ays. Wi r i ng shal l conf or m t o NFPA 70. Syst em f i el d wi r i ng shal l be sol i d copper and i nst al l ed i n met al l i c condui t or el ect r i cal met al l i c t ubi ng, except t hat r i gi d pl ast i c condui t may be used under s l ab- on- gr ade.
Conduct or s shal l be col or coded. Conduct or s used f or t he same f unct i ons shal l be s i mi l ar l y col or coded. Wi r i ng code col or shal l r emai n uni f or m t hr oughout t he c i r cui t . Pi gt ai l or T- t ap connect i ons t o i ni t i at i ng devi ce c i r cui t s, super v i sor y al ar m ci r cui t s, and not i f i cat i on appl i ance c i r cui t s ar e pr ohi bi t ed. Expansi on of c i r cui t l oop usi ng scr ew t er mi nal bl ocks i s al l owed f or Cl ass B c i r cui t s.
PART 3 EXECUTI ON
3. 1 EXAMINATION
Af t er becomi ng f ami l i ar wi t h det ai l s of t he wor k, ver i f y di mensi ons i n t he f i el d and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng t he wor k.
3. 2 INSTALLATION
I nst al l al l wor k as shown, i n accor dance wi t h NFPA 70 and NFPA 72, and i n accor dance wi t h t he manuf act ur er ' s di agr ams and r ecommendat i ons, unl ess ot her wi se speci f i ed. Smoke det ect or s shal l not be i nst al l ed unt i l const r uct i on i s essent i al l y compl et e and t he bui l di ng has been t hor oughl y cleaned.
3. 2. 1 Power Suppl y f or t he Syst em
Pr ovi de a s i ngl e dedi cat ed c i r cui t connect i on f or suppl y i ng power f r om a br anch ci r cui t t o each bui l di ng f i r e al ar m syst em. The power shal l be suppl i ed as shown on t he dr awi ngs. The power suppl y shal l be equi pped wi t h a l ocki ng mechani sm and mar ked i n r ed wi t h t he wor ds " FI RE ALARM CI RCUI T
CONTROL".
3. 2. 2 Wiring
Condui t s i ze f or wi r i ng shal l be i n accor dance wi t h NFPA 70. Wi r i ng f or t he f i r e al ar m syst em shal l not be i nst al l ed i n condui t s, j unct i on boxes, or out l et boxes wi t h conduct or s of l i ght i ng and power syst ems. Not mor e t han t wo conduct or s shal l be i nst al l ed under any devi ce scr ew t er mi nal .
The wi r es under t he scr ew t er mi nal shal l be st r ai ght when pl aced under t he t er mi nal t hen c l amped i n pl ace under t he scr ew t er mi nal . The wi r es shal l be br oken and not t wi st ed ar ound t he t er mi nal . Ci r cui t conduct or s ent er i ng or l eavi ng any mount i ng box, out l et box encl osur e, or cabi net shal l be connect ed t o scr ew t er mi nal s wi t h each t er mi nal and conduct or mar ked i n accor dance wi t h t he wi r i ng di agr am. Connect i ons and spl i ces shal l be made usi ng scr ew t er mi nal bl ocks. The use of wi r e nut t ype connect or s i n t he syst em i s pr ohi bi t ed. Wi r i ng wi t hi n any cont r ol equi pment shal l be r eadi l y accessi bl e wi t hout r emovi ng any component par t s. The f i r e al ar m equi pment manuf act ur er ' s r epr esent at i ve shal l be pr esent f or t he connect i on of wi r i ng t o t he cont r ol panel .
SECTI ON 28 31 64. 00 10 Page 10
3. 2. 3 Cont r ol Panel
Revi s i on 1
Exi st i ng t o Remai n.
Revi s i on 1
3. 2. 4 Detectors
Det ect or s shal l be l ocat ed and i nst al l ed i n accor dance wi t h NFPA 72.
Det ect or s shal l be connect ed i nt o s i gnal l i ne c i r cui t s or i ni t i at i ng devi ce c i r cui t s as i ndi cat ed on t he dr awi ngs. Det ect or s shal l be at l east 12 i nches f r om any par t of any l i ght i ng f i x t ur e. Det ect or s shal l be l ocat ed at l east 3 f eet f r om di f f user s of ai r handl i ng syst ems. Each det ect or shal l be pr ovi ded wi t h appr opr i at e mount i ng har dwar e as r equi r ed by i t s mount i ng l ocat i on. Det ect or s whi ch mount i n open space shal l be mount ed di r ect l y t o t he end of t he st ubbed down r i gi d condui t dr op. Condui t dr ops shal l be f i r ml y secur ed t o mi ni mi ze det ect or sway. Wher e l engt h of condui t dr op f r om cei l i ng or wal l sur f ace exceeds 3 f eet , sway br aci ng shal l be pr ovi ded. Det ect or s i nst al l ed i n conceal ed l ocat i ons ( above cei l i ng, r ai sed f l oor s, et c. ) shal l have a r emot e v i s i bl e i ndi cat or LED/ LCD i n a f i ni shed, v i s i bl e l ocat i on.
3. 2. 5 Not i f i cat i on Appl i ances
Not i f i cat i on appl i ances shal l be mount ed 80 i nches above t he f i ni shed f l oor or 6 i nches bel ow t he cei l i ng, whi chever i s l ower .
3. 2. 6 Annunci at or Equi pment
Revi s i on 1
Exi st i ng t o Remai n.
Revi s i on 1
Revi s i on 2
3. 2. 7 Addr essabl e I ni t i at i ng Devi ce Ci r cui t s Modul e
The i ni t i at i ng devi ce c i r cui t s modul e shal l be used t o connect super vi sed convent i onal i ni t i at i ng devi ces ( wat er f l ow swi t ches, wat er pr essur e swi t ches, manual f i r e al ar m st at i ons, hi gh/ l ow ai r pr essur e swi t ches, and t amper swi t ches) . The modul e shal l mount i n an el ect r i cal box adj acent t o or connect ed t o t he devi ce i t i s moni t or i ng and shal l be capabl e of St y l e B super vi sed wi r i ng t o t he i ni t i at i ng devi ce. I n or der t o mai nt ai n pr oper super vi s i on, t her e shal l be no T- t aps al l owed on st y l e B l i nes.
Addr essabl e i ni t i at i ng devi ce c i r cui t s modul es shal l moni t or onl y one i ni t i at i ng devi ce each. Cont act s i n suppr essi on syst ems and ot her f i r e pr ot ect i on subsyst ems shal l be connect ed t o t he f i r e al ar m syst em t o per f or m super vi sor y and al ar m f unct i ons as speci f i ed i n Sect i on 21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON, NFPA 72 and, as i ndi cat ed on t he dr awi ngs and as speci f i ed her ei n.
Revi s i on 2
SECTI ON 28 31 64. 00 10 Page 11
3. 2. 8 Addr essabl e Cont r ol Modul e
Addr essabl e and cont r ol modul es shal l be i nst al l ed i n t he out l et box or adj acent t o t he devi ce t hey ar e cont r ol l i ng. I f a suppl ement ar y suppr essi on r el easi ng panel i s pr ovi ded, t hen t he moni t or modul es shal l he mount ed i n a common encl osur e adj acent t o t he suppr essi on r el easi ng panel and bot h t hi s encl osur e and t he suppr essi on r el easi ng panel shal l be i n t he same r oom as t he r el easi ng devi ces. Al l i nt er connect i ng wi r es shal l be super vi sed unl ess an open ci r cui t or shor t c i r cui t abnor mal condi t i on does not af f ect t he r equi r ed oper at i on of t he f i r e al ar m syst em. I f cont r ol modul es ar e used as i nt er f aces t o ot her syst ems, such as HVAC or el evat or cont r ol , t hey shal l be wi t hi n t he cont r ol panel or i mmedi at el y adj acent t o i t . Cont r ol modul es t hat cont r ol a gr oup of not i f i cat i on appl i ances shal l be adj acent t o t he f i r st not i f i cat i on appl i ance i n t he not i f i cat i on appl i ance c i r cui t s. Cont r ol modul es t hat connect t o devi ces shal l super vi se t he not i f i cat i on appl i ance c i r cui t s. Cont r ol modul es t hat connect t o auxi l i ar y syst ems or i nt er f ace wi t h ot her syst ems ( non- l i f e saf et y syst ems) and wher e not r equi r ed by NFPA 72, shal l not r equi r e t he secondar y c i r cui t s t o be super vi sed. Cont act s i n suppr essi on syst ems and ot her f i r e pr ot ect i on subsyst ems shal l be connect ed t o t he f i r e al ar m syst em t o per f or m r equi r ed al ar m f unct i ons as speci f i ed i n Sect i on 21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON and NFPA 72, as i ndi cat ed on t he dr awi ngs and as speci f i ed her ei n.
3. 3 OVERVOLTAGE AND SURGE PROTECTI ON
3. 3. 1 Power Li ne Sur ge Pr ot ect i on
Al l equi pment connect ed t o al t er nat i ng cur r ent c i r cui t s shal l be pr ot ect ed f r om sur ges i n accor dance wi t h I EEE C62. 41. 1/ I EEE C62. 41. 2 B3 combi nat i on wavef or m and NFPA 70. Fuses shal l not be used f or sur ge pr ot ect i on. The sur ge pr ot ect or shal l be r at ed f or a maxi mum l et t hr u vol t age of 350 Vol t s ac ( l i ne- t o- neut r al ) and 350 Vol t ac ( neut r al - t o- gr ound) .
3. 3. 2 Low Vol t age DC Ci r cui t s Sur ge Pr ot ect i on
Al l I DC, NAC, and communi cat i on cabl es/ conduct or s, except f i ber opt i cs, shal l have sur ge pr ot ect i on i nst al l ed at each poi nt wher e i t exi t s or ent er s a bui l di ng. Equi pment shal l be pr ot ect ed f r om sur ges i n accor dance with I EEE C62. 41. 1/ I EEE C62. 41. 2 B3 combi nat i on wavef or m and NFPA 70. The sur ge pr ot ect or shal l be r at ed t o pr ot ect t he 24 Vol t dc equi pment . The maxi mum dc c l ampi ng vol t ages shal l be 36 V ( l i ne- t o- gr ound) and 72 Vol t dc (line-to-line).
3. 3. 3 Si gnal Li ne Ci r cui t Sur ge Pr ot ect i on
Al l SLC cabl es/ conduct or s, except f i ber opt i cs, shal l have sur ge pr ot ect i on/ i sol at i on c i r cui t s i nst al l ed at each poi nt wher e i t exi t s or ent er s a bui l di ng. The ci r cui t shal l be pr ot ect ed f r om sur ges i n accor dance wi t h I EEE C62. 41. 1/ I EEE C62. 41. 2 B3 combi nat i on wavef or m and NFPA 70. The sur ge pr ot ect or / i sol at or shal l be r at ed t o pr ot ect t he equipment.
3. 4 SUPERVI SI NG STATI ON PROVI SI ONS
3. 4. 1 Revi s i ons t o Exi st i ng Faci l i t i es
Exi st i ng super vi s i ng component s shal l be modi f i ed as i ndi cat ed on t he dr awi ngs and pr ogr ammi ng shal l be updat ed i f r equi r ed t o accommodat e t he
SECTI ON 28 31 64. 00 10 Page 12 r evi sed conf i gur at i on. Accept ance t est i ng shal l i ncl ude pr ocedur es t hat woul d demonst r at e t hat oper at i on of exi st i ng equi pment has not been degr aded and t hat t he r evi sed conf i gur at i on pl us i nt er f aci ng component s oper at es compat i bl y wi t h t he new f i r e al ar m syst em at t he pr ot ect ed pr emi ses. Wor k on exi st i ng equi pment shal l be per f or med i n accor dance wi t h t he manuf act ur er ' s i nst r uct i ons or under super vi s i on of t he manuf act ur er ' s representative.
3. 4. 2 Addi t i ons t o Exi st i ng Faci l i t i es
Suppl ement al component s shal l be added t o t he exi st i ng super vi s i ng equi pment as r equi r ed t o accommodat e t he new f i r e al ar m syst em t o be i nst al l ed at t he pr ot ect ed pr emi ses and as i ndi cat ed on t he dr awi ngs. Al l pr esent f unct i ons shal l be ext ended, i ncl udi ng r ecor di ng and st or age i n memor y, and pr ogr ammi ng shal l be updat ed i f r equi r ed t o accommodat e t he r evi sed conf i gur at i on. Accept ance t est i ng shal l i ncl ude pr ocedur es t hat woul d demonst r at e t hat oper at i on of exi st i ng equi pment has not been degr aded and t hat t he expanded conf i gur at i on oper at es compat i bl y wi t h t he new f i r e al ar m syst em.
3. 5 TRAINING
Revi s i on 1
Expansi on of exi st i ng f i r e al ar m syst ems wi t hi n Bui l di ngs 2201 and 3101 wi l l not r equi r e t r ai ni ng.
Revi s i on 1
3. 6 TESTING
Not i f y t he Cont r act i ng Of f i cer at l east 21 days bef or e t he pr el i mi nar y and accept ance t est s ar e t o be conduct ed. Per f or m t he t est s i n accor dance wi t h t he appr oved t est pr ocedur es i n t he pr esence of t he Cont r act i ng Of f i cer .
The cont r ol panel manuf act ur er ' s r epr esent at i ve shal l be pr esent t o super vi se t est s. Fur ni sh i nst r ument s and per sonnel r equi r ed f or t he t est s.
a. Submi t det ai l ed t est pr ocedur es, pr epar ed and si gned by a Regi st er ed Pr of essi onal Engi neer or a NI CET Level 4 Fi r e Al ar m Techni c i an, f or t he f i r e det ect i on and al ar m syst em 60 days pr i or t o per f or mi ng syst em tests.
b. Submi t t est r epor t s, i n bookl et f or m, showi ng f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, upon compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l document r eadi ngs, t est r esul t s and i ndi cat e t he f i nal posi t i on of cont r ol s. I ncl ude t he NFPA 72 Cer t i f i cat e of Compl et i on and NFPA 72 I nspect i on and Test i ng For m, wi t h t he appr opr i at e t est r epor t s.
3. 6. 1 Pr el i mi nar y Test s
Upon compl et i on of t he i nst al l at i on, subj ect t he syst em t o f unct i onal and oper at i onal per f or mance t est s i nc l udi ng t est s of each i nst al l ed i ni t i at i ng and not i f i cat i on appl i ance, when r equi r ed. Test s shal l i ncl ude t he megger i ng of syst em conduct or s t o det er mi ne t hat t he syst em i s f r ee f r om gr ounded, shor t ed, or open ci r cui t s. Conduct t he megger t est pr i or t o t he i nst al l at i on of f i r e al ar m equi pment . I f def i c i enci es ar e f ound, cor r ect i ons shal l be made and t he syst em shal l be r et est ed t o assur e t hat i t i s f unct i onal . Af t er compl et i ng t he pr el i mi nar y t est i ng compl et e and
SECTI ON 28 31 64. 00 10 Page 13 submi t t he NFPA 72, Cer t i f i cat e of Compl et i on and Test i ng For m.
3. 6. 2 Accept ance Test
Revi s i on 1
Accept ance t est i ng shal l not be per f or med unt i l t he Cont r act or has compl et ed and submi t t ed t he Cer t i f i cat e of Compl et i on. Conduct t est i ng i n accor dance wi t h NFPA 72. The r ecommended t est s i n NFPA 72 ar e consi der ed mandat or y and shal l ver i f y t hat pr evi ous def i c i enci es have been cor r ect ed.
The Fi r e Al ar m Techni c i an super vi s i ng t he i nst al l at i on of t he f i r e al ar m syst em shal l at t end t he t est i ng of t he syst em. The t est shal l i ncl ude al l r equi r ement s of NFPA 72 and t he f ol l owi ng:
Revi s i on 1
a. Test of each f unct i on of t he cont r ol panel .
b. Test of each ci r cui t i n bot h t r oubl e and nor mal modes.
c. Test s of each al ar m i ni t i at i ng devi ces i n bot h nor mal and t r oubl e conditions.
d. Test s of each cont r ol c i r cui t and devi ce wher e t hey ar e i mpact ed by t he syst em expansi ons.
e. Test s of each al ar m not i f i cat i on appl i ance i n expanded syst ems.
f . Compl et e oper at i onal t est s under emer gency power suppl y.
g. Vi sual i nspect i on of wi r i ng connect i ons.
h. Openi ng t he c i r cui t at each al ar m i ni t i at i ng devi ce and not i f i cat i on appl i ance t o t est t he wi r i ng super vi sor y f eat ur e.
i . Gr ound f aul t .
j . Shor t c i r cui t f aul t s.
k. St r ay vol t age.
l . Loop r esi st ance.
- - End of Sect i on - -
SECTI ON 28 31 64. 00 10 Page 14
| PN 163007 Alter Facilities for Maintenance_R4_Specifications_11.02.18_Cover |
| PN 163007 Alter Facilities for Maintenance_R4_Specifications_11.02.18_StampPage |
| 28 31 64.00 10 |
| 28 31 64.00 10 - FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 QUALITY ASSURANCE |
| 1.3.1 Qualifications |
| 1.3.1.1 Engineer and Technician |
| 1.3.1.2 Installer |
| 1.3.1.3 Fire Protection Engineer |
1.3.2 Detail Drawings
1.4 TECHNICAL DATA AND COMPUTER SOFTWARE
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.1.1 Operation |
| 2.1.2 Operational Features |
| 2.1.3 Alarm Functions |
| 2.1.4 Interface With Existing Fire Alarm Equipment |
| 2.1.5 Interface With other Equipment |
| 2.2 STANDARD PRODUCTS |
| 2.3 NAMEPLATES |
| 2.4 CONTROL PANEL |
| 2.4.1 Remote System Audible/Visual Display |
| 2.4.2 Circuit Connections |
| 2.4.3 System Expansion and Modification Capabilities |
| 2.4.4 Addressable Control Module |
| 2.4.5 Addressable Initiating Device Circuits Module |
| 2.5 STORAGE BATTERIES |
| 2.6 ADDRESSABLE MANUAL FIRE ALARM STATIONS |
| 2.7 FIRE DETECTING DEVICES |
| 2.7.1 Smoke Detectors |
| 2.7.1.1 Photoelectric Detectors |
| 2.7.1.2 Duct Detectors |
| 2.8 NOTIFICATION APPLIANCES |
| 2.8.1 Visual Notification Appliances |
| 2.8.2 Combination Audible/Visual Notification Appliances |
| 2.8.3 Fire Alarm Speakers |
| 2.9 FIRE DETECTION AND ALARM SYSTEM PERIPHERAL EQUIPMENT |
| 2.9.1 Conduit |
| 2.9.2 Wiring |
| PART 3 EXECUTION |
| 3.1 EXAMINATION |
| 3.2 INSTALLATION |
| 3.2.1 Power Supply for the System |
| 3.2.2 Wiring |
| 3.2.3 Control Panel |
| 3.2.4 Detectors |
| 3.2.5 Notification Appliances |
| 3.2.6 Annunciator Equipment |
| 3.2.7 Addressable Initiating Device Circuits Module |
| 3.2.8 Addressable Control Module |
| 3.3 OVERVOLTAGE AND SURGE PROTECTION |
| 3.3.1 Power Line Surge Protection |
| 3.3.2 Low Voltage DC Circuits Surge Protection |
| 3.3.3 Signal Line Circuit Surge Protection |
| 3.4 SUPERVISING STATION PROVISIONS |
| 3.4.1 Revisions to Existing Facilities |
| 3.4.2 Additions to Existing Facilities |
| 3.5 TRAINING |
| 3.6 TESTING |
| 3.6.1 Preliminary Tests |
| 3.6.2 Acceptance Test |