USACE NYD JB MDL 695847
Revi s i on 1
SECTI ON 21 13 18. 00 10
PREACTI ON AND DELUGE SPRI NKLER SYSTEMS, FI RE PROTECTI ON
05/09
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ASME I NTERNATI ONAL ( ASME)
ASME B16. 1 ( 2015) Gr ay I r on Pi pe Fl anges and Fl anged Fi t t i ngs Cl asses 25, 125, and 250
ASME B16. 11 ( 2016) For ged Fi t t i ngs, Socket - Wel di ng and Threaded
ASME B16. 21 ( 2011) Nonmet al l i c Fl at Gasket s f or Pi pe Flanges
ASME B16. 3 ( 2011) Mal l eabl e I r on Thr eaded Fi t t i ngs, Cl asses 150 and 300
ASME B16. 4 ( 2011) St andar d f or Gr ay I r on Thr eaded Fi t t i ngs; Cl asses 125 and 250
ASME B16. 9 ( 2012) St andar d f or Fact or y- Made Wr ought St eel But t wel di ng Fi t t i ngs
ASME B18. 2. 2 ( 2015) Nut s f or Gener al Appl i cat i ons:
Machi ne Scr ew Nut s, Hex, Squar e, Hex Fl ange, and Coupl i ng Nut s ( I nch Ser i es)
ASTM I NTERNATI ONAL ( ASTM)
ASTM A135/ A135M ( 2009; R2014) St andar d Speci f i cat i on f or El ect r i c- Resi st ance- Wel ded St eel Pi pe
ASTM A183 ( 2014) St andar d Speci f i cat i on f or Car bon St eel Tr ack Bol t s and Nut s
ASTM A449 ( 2014) St andar d Speci f i cat i on f or Hex Cap Scr ews, Bol t s, and St uds, St eel , Heat Tr eat ed, 120/ 105/ 90 ksi Mi ni mum Tensi l e St r engt h, Gener al Use
ASTM A47/ A47M ( 1999; R 2014) St andar d Speci f i cat i on f or Fer r i t i c Mal l eabl e I r on Cast i ngs
ASTM A53/ A53M ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess
SECTI ON 21 13 18. 00 10 Page 1 04 Sept ember 2018
ASTM A536 ( 1984; R 2014) St andar d Speci f i cat i on f or Duct i l e I r on Cast i ngs
ASTM A795/ A795M ( 2013) St andar d Speci f i cat i on f or Bl ack and Hot - Di pped Zi nc- Coat ed ( Gal vani zed) Wel ded and Seaml ess St eel Pi pe f or Fi r e Pr ot ect i on Use
ASTM F436 ( 2011) Har dened St eel Washer s
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS
I NDUSTRY ( MSS)
MSS SP- 71 ( 2011; Er r at a 2013) Gr ay I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 13 ( 2016; TI A 16- 1; TI A 16- 2; TI A 16- 3 2016;
Er r at a 17- 1; Er r at a 17- 2) St andar d f or t he I nst al l at i on of Spr i nkl er Syst ems
NFPA 24 ( 2016; ERTA 2016) St andar d f or t he I nst al l at i on of Pr i vat e Fi r e Ser v i ce Mai ns and Thei r Appur t enances
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
NFPA 72 ( 2016) Nat i onal Fi r e Al ar m and Si gnal i ng Code
U. S. DEPARTMENT OF DEFENSE ( DOD)
UFC 3- 310- 04 ( 2013; wi t h Change 1) Sei smi c Desi gn f or Buildings
UFC 3- 600- 01 ( 2016; wi t h Change 1) Fi r e Pr ot ect i on Engi neer i ng f or Faci l i t i es
SECTI ON 21 13 18. 00 10 Page 2
UNDERWRI TERS LABORATORI ES ( UL)
UL Bl d Mat Di r ( updat ed cont i nuousl y onl i ne) Bui l di ng Mat er i al s Di r ect or y
UL Fi r e Pr ot Di r ( 2012) Fi r e Pr ot ect i on Equi pment Di r ect or y
1. 2 SYSTEM DESCRI PTI ON
a. Pr ovi de pr e- act i on syst em f or t he new BOT Si mul at or r oom and suppor t i ng comput er r oom. Fur ni sh pi pi ng of f set s, f i t t i ngs, and any ot her accessor i es as r equi r ed t o pr ovi de a compl et e i nst al l at i on and t o el i mi nat e i nt er f er ence wi t h ot her const r uct i on. I nst al l spr i nkl er over and under duct s, pi pi ng and pl at f or ms when such equi pment can negat i vel y af f ect or di sr upt t he spr i nkl er di schar ge pat t er n and coverage.
b. Pr ovi de pr eact i on spr i nkl er syst em( s) i n t he new BOT Si mul at or r oom and suppor t i ng comput er r oom. The spr i nkl er syst em shal l pr ovi de f i r e spr i nkl er pr ot ect i on f or t he ent i r e ar ea. Except as modi f i ed her ei n, t he syst em shal l meet t he r equi r ement s of NFPA 13 and NFPA 72. The spr i nkl er syst em shal l be a s i ngl e i nt er l ocked syst em t hat r equi r es t he act uat i on of an al ar m i ni t i at i ng devi ce t o open t he wat er cont r ol ( del uge) val ve.
c. Desi gn any por t i ons of t he spr i nkl er syst em t hat ar e not i ndi cat ed on t he dr awi ngs or ar e not speci f i ed her ei n, i ncl udi ng l ocat i ng spr i nkl er s, pi pi ng, and equi pment , and s i ze pi pi ng and equi pment .
Det er mi ne pi pe s i zes whi ch ar e not i ndi cat ed on t he dr awi ngs by hydr aul i c cal cul at i ons.
Revi s i on 1
d. Remove Pr e- act i on spr i nkl er pr ot ect i on and pi pi ng f or t he syst ems pr ot ect i ng under neat h t he WST si mul at or s.
e. Pr ovi de new cont r ol and r el ease panel and ni t r ogen gener at or s f or t he exi st i ng t o r emai n WST pr e- act i on syst em.
Revi s i on 1
1. 2. 1 Hydr aul i c Desi gn
Hydr aul i cal l y desi gn t he syst em t o di schar ge a mi ni mum densi t y of 0.20 gpm/ squar e f oot over t he hydr aul i cal l y most demandi ng 2500 squar e f eet of f l oor ar ea. The mi ni mum pi pe s i ze f or br anch l i nes i n gr i dded syst ems shal l be 1- 1/ 4 i nch. Hydr aul i c cal cul at i ons shal l be i n accor dance wi t h t he Ar ea/ Densi t y Met hod of NFPA 13. Wat er vel oci t y i n t he pi pi ng shal l not exceed 20 f t / s.
Revi s i on 1
1. 2. 1. 1 Hose Demand
Add an al l owance f or ext er i or hose st r eams of 250 gpm t o t he spr i nk l er syst em demand at t he f i r e hydr ant shown on t he dr awi ngs c l osest t o t he poi nt wher e t he wat er ser vi ce ent er s t he bui l di ng.
SECTI ON 21 13 18. 00 10 Page 3 04 Sept ember 2018 e3enmrt3 Highlight e3enmrt3 Highlight
1. 2. 1. 2 Basi s f or Cal cul at i ons
Revi s i on 1
Base t he desi gn of t he syst em upon a wat er suppl y wi t h a st at i c pr essur e of 65, and a f l ow of 1384 at a r esi dual pr essur e of 58. Wat er suppl y shal l be pr esumed avai l abl e at t he base of t he r i ser . Base hydr aul i c cal cul at i ons upon t he Hazen- Wi l l i ams f or mul a wi t h a " C" val ue of 120 f or schedul e 40 bl ack st eel pi pi ng and 100 f or exi st i ng under gr ound pi pi ng.
Revi s i on 1
a. Out l i ne hydr aul i c cal cul at i ons as i n NFPA 13, except t hat cal cul at i ons shal l be per f or med by comput er usi ng sof t war e i nt ended speci f i cal l y f or f i r e pr ot ect i on syst em desi gn usi ng t he desi gn dat a shown on t he dr awi ngs. Submi t hydr aul i c cal cul at i ons, i ncl udi ng a dr awi ng showi ng hydr aul i c r ef er ence poi nt s and pi pe segment s. Sof t war e t hat uses k- f act or s f or t ypi cal br anch l i nes i s not accept abl e. Cal cul at i ons shal l subst ant i at e t hat t he desi gn ar ea used i n t he cal cul at i ons i s t he most demandi ng hydr aul i cal l y .
b. Pl ot wat er suppl y cur ves and syst em r equi r ement s on semi - l ogar i t hmi c gr aph paper so as t o pr esent a summar y of t he compl et e hydr aul i c cal cul at i on. Pr ovi de a summar y sheet l i s t i ng spr i nkl er s i n t he desi gn ar ea and t hei r r espect i ve hydr aul i c r ef er ence poi nt s, el evat i ons, act ual di schar ge pr essur es and act ual f l ows. I ndi cat e el evat i ons of hydr aul i c r ef er ence poi nt s ( nodes) . Document at i on shal l i dent i f y each pi pe i ndi v i dual l y and t he nodes connect ed t her et o. I ndi cat e f or each pi pe t he di amet er , l engt h, f l ow, vel oci t y, f r i c t i on l oss, number and t ype f i t t i ngs, t ot al f r i c t i on l oss i n t he pi pe, equi val ent pi pe l engt h and Hazen- Wi l l i ams coef f i c i ent .
c. For gr i dded syst ems, cal cul at i ons shal l show peaki ng of demand ar ea f r i c t i on l oss t o ver i f y t hat t he hydr aul i cal l y most demandi ng ar ea i s bei ng used. Al so f or gr i dded syst ems, i ncl ude a f l ow di agr am i ndi cat i ng t he quant i t y and di r ect i on of f l ows. A dr awi ng showi ng hydr aul i c r ef er ence poi nt s ( nodes) and pi pe desi gnat i ons used i n t he cal cul at i ons shal l be i ncl uded and shal l be i ndependent of shop drawings.
1. 2. 2 Spr i nkl er Cover age
Uni f or ml y space spr i nkl er s on br anch l i nes. Pr ovi de 100 per cent cover age i n t he new BOT Si mul at or addi t i on and t he suppor t i ng comput er r oom.
Cover age per spr i nkl er shal l be i n accor dance wi t h NFPA 13, but shal l not exceed 130 squar e f eet f or or di nar y hazar d occupanci es, and 225 squar e f eet f or l i ght hazar d occupanci es.
1. 2. 3 Cont r ol Syst em
The cont r ol syst em shal l meet t he r equi r ement s of NFPA 72. The cont r ol panel shal l be l i s t ed i n UL Fi r e Pr ot Di r or FM APP GUI DE f or " Rel easi ng Devi ce Ser vi ce" . The cont r ol panel and t he sol enoi d val ve t hat act i vat es t he wat er cont r ol val ves shal l be compat i bl e wi t h each ot her .
Compat i bi l i t y shal l be i n accor dance wi t h speci f i c UL l i s t i ng or FM appr oval of t he cont r ol equi pment .
SECTI ON 21 13 18. 00 10 Page 4 04 Sept ember 2018
1. 2. 3. 1 Power Suppl y
Pr ovi de t he pr i mar y oper at i ng power f r om t wo si ngl e- phase 120 VAC ci r cui t s.
Exi st i ng dedi cat e c i r cui t s may be r e- used. Tr ansf er f r om nor mal t o backup power and r est or at i on f r om backup t o nor mal power shal l be f ul l y aut omat i c and shal l not i ni t i at e a f al se al ar m. Loss of pr i mar y power shal l not pr event act uat i on of t he r espect i ve aut omat i c wat er cont r ol val ve upon act i vat i on of any al ar m i ni t i at i ng devi ce. Pr ovi de backup power t hr ough use of r echar geabl e, seal ed, l ead cal c i um st or age bat t er i es.
1. 2. 3. 2 Ci r cui t Requi r ement s
Connect al ar m i ni t i at i ng devi ces t o i ni t i at i ng devi ce c i r cui t s ( I DC) , Cl ass B or t o s i gnal l i ne c i r cui t s ( SLC) , Cl ass B, i n accor dance wi t h NFPA 72.
Al ar m not i f i cat i on or i ndi cat i ng appl i ances shal l be connect ed t o i ndi cat i ng appl i ance c i r cui t ( I AC) , CLASS B i n accor dance wi t h NFPA 72.
Pr ovi de a separ at e c i r cui t f or act uat i on of each i ndi v i dual aut omat i c wat er cont r ol val ve. Ful l y super vi se t he c i r cui t s t hat act uat e t he wat er cont r ol val ves so t hat t he occur r ence of a s i ngl e open or a s i ngl e gr ound f aul t condi t i on i n t he i nt er connect i ng conduct or s wi l l be i ndi cat ed at t he cont r ol panel .
1. 2. 4 Syst em Oper at i onal Feat ur es
I ncl ude i n t he syst em a I nci pi ent Smoke det ect i on syst em, manual act uat i on st at i ons, super v i sor y and al ar m swi t ches, al ar m not i f i cat i on appl i ances, cont r ol panel and associ at ed equi pment . Pr ovi de pr eact i on spr i nkl er syst em pi pi ng wi t h super vi sor y ni t r ogen pr essur e not t o exceed 30 psi g.
1. 2. 4. 1 Syst em Act uat i on
Act i vat i on of t he ALARM condi t i on by t he I SD panel or a s i ngl e manual act uat i on st at i on shal l act uat e al ar m zone ci r cui t s of t he cont r ol panel t hat , i n t ur n, shal l act uat e t he cor r espondi ng aut omat i c wat er cont r ol val ve. Act uat i on of t he aut omat i c wat er cont r ol val ve shal l cause wat er t o f i l l t he pr eact i on syst em pi pi ng and be di schar ged f r om f used spr i nkl er s.
1. 2. 4. 2 Al ar m Funct i ons
Act i vat i on of t he al ar m l evel at t he i nci pi ent smoke det ect i on syst em or spr i nkl er pr essur e al ar m swi t ch or manual act uat i on st at i on shal l cause t he i l l umi nat i on of t he r espect i ve zone annunci at or , and act i vat i on of t he bui l di ng f i r e al ar m syst em t r ansmi ssi on of t he al ar m t o t he base- wi de f i r e r epor t i ng syst em. Val ve t amper al ar m shal l be moni t or ed by t he syst em cont r ol panel and t r ansmi t t ed t o t he bui l di ng f i r e al ar m syst em as a t r oubl e al ar m.
1. 2. 4. 3 Super vi sor y Funct i ons
The r educt i on of super vi sor y ni t r ogen pr essur e wi t hi n t he spr i nkl er syst em pi pi ng t o l ess t han 10 psi or t he occur r ence of a s i ngl e open or a s i ngl e gr ound f aul t i n any al ar m i ni t i at i ng devi ce c i r cui t , i n t he aut omat i c wat er cont r ol val ve act uat i on c i r cui t , i n any al ar m i ndi cat i ng appl i ance c i r cui t or i n ot her el ect r i cal l y super vi sed c i r cui t shal l cause t he i ndi v i dual l y l abel l ed cont r ol panel t r oubl e l i ght t o be i l l umi nat ed, t he audi bl e t r oubl e al ar m t o be act i vat ed, and a t r oubl e al ar m t o be t r ansmi t t ed t o t he bui l di ng f i r e al ar m cont r ol panel and t o base- wi de f i r e r epor t i ng syst em.
SECTI ON 21 13 18. 00 10 Page 5
1. 3 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Shop Dr awi ngs; G
As- Bui l t Dr awi ngs
SD- 03 Pr oduct Dat a
Fi r e Pr ot ect i on Speci al i s t ; G
I nst al l er Qual i f i cat i ons
Li st of Submi t t al s
Mat er i al s and Equi pment ; G
Spar e Par t s
OnSi t e Tr ai ni ng; G
SD- 05 Desi gn Dat a
Sway Br aci ng
Hydr aul i c Cal cul at i ons; G
St or age Bat t er i es; G
SD- 06 Test Repor t s
Pr el i mi nar y Test s; G
Fi nal Accept ance Test s
SD- 07 Cer t i f i cat es
I nspect i on by Fi r e Pr ot ect i on Speci al i s t ; G
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i ng and Mai nt enance I nst r uct i ons; G
1. 4 QUALI TY ASSURANCE
Compl i ance wi t h r ef er enced NFPA st andar ds i s mandat or y. Appl i cabl e mat er i al and i nst al l at i on st andar ds r ef er enced i n Appendi x A of NFPA 13 and NFPA 24 shal l be consi der ed mandat or y t he same as i f such r ef er enced st andar ds wer e speci f i cal l y l i s t ed i n t hi s speci f i cat i on. I n t he event of a conf l i c t bet ween speci f i c pr ovi s i ons of t hi s speci f i cat i on and appl i cabl e NFPA st andar ds, t hi s speci f i cat i on gover ns. I ncor por at e al l r equi r ement s t hat exceed t he mi ni mum r equi r ement s of NFPA 13 i nt o t he desi gn. I nt er pr et
SECTI ON 21 13 18. 00 10 Page 6 r ef er ence t o " aut hor i t y havi ng j ur i sdi ct i on" t o mean t he Cont r act i ng Officer.
1. 4. 1 Fi r e Pr ot ect i on Speci al i s t
Per f or m t he wor k speci f i ed i n t hi s sect i on under t he super vi s i on of and cer t i f i ed by t he Fi r e Pr ot ect i on Speci al i s t ( FPS) who i s a r egi st er ed pr of essi onal engi neer and a Ful l Member of t he Soci et y of Fi r e Pr ot ect i on Engi neer s. Submi t t he name and document at i on of cer t i f i cat i on of t he pr oposed FPS, no l at er t han 14 days af t er t he Not i ce t o Pr oceed and pr i or t o t he submi t t al of t he spr i nkl er syst em shop dr awi ngs and hydr aul i c cal cul at i ons. The FPS shal l pr epar e and submi t a l i s t of submi t t al s, r el at ed t o f i r e pr ot ect i on, f r om t he Cont r act Submi t t al Regi st er t hat r el at e t o t he successf ul i nst al l at i on of t he spr i nkl er syst ems( s) , no l at er t han 7 days af t er t he appr oval of t he FPS. The submi t t al s i dent i f i ed on t hi s l i s t shal l be accompani ed by a l et t er of appr oval s i gned and dat ed by t he FPS when submi t t ed t o t he Gover nment . The FPS shal l be r egul ar l y engaged i n t he desi gn and i nst al l at i on of t he t ype and compl exi t y of syst em speci f i ed i n t he Cont r act document s, and shal l have ser ved i n a s i mi l ar capaci t y f or at l east t hr ee syst ems t hat have per f or med i n t he manner i nt ended f or a per i od of not l ess t han 6 mont hs.
1. 4. 2 I nst al l er Qual i f i cat i ons
Wor k speci f i ed i n t hi s sect i on shal l be per f or med by t he Spr i nkl er Syst em I nst al l er . I nst al l er s wi l l be over seen by a mi ni mum of a t echni c i an cer t i f i ed as a Level I V Techni c i an by Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es ( NI CET) i n t he Aut omat i c Spr i nkl er Syst em Layout subf i el d of Fi r e Pr ot ect i on Engi neer i ng Technol ogy i n accor dance wi t h NI CET 1014- 7. Submi t t he name and document at i on of cer t i f i cat i on of t he pr oposed Spr i nkl er Syst em I nst al l er , concur r ent wi t h submi t t al of t he FPS Qual i f i cat i ons. The I nst al l er shal l be r egul ar l y engaged i n t he i nst al l at i on of t he t ype and compl exi t y of syst em speci f i ed i n t he Cont r act document s, and shal l have ser ved i n a s i mi l ar capaci t y f or at l east t hr ee syst ems t hat have per f or med i n t he manner i nt ended f or a per i od of not l ess t han 6 mont hs.
1. 4. 3 Shop Dr awi ngs
Submi t di gi t al copi es of t he Spr i nkl er Syst em Dr awi ngs, no l at er t han 21 days pr i or t o t he st ar t of spr i nk l er syst em i nst al l at i on. The dr awi ngs shal l conf or m t o t he r equi r ement s est abl i shed f or wor ki ng pl ans as pr escr i bed i n NFPA 13. Dr awi ngs shal l i ncl ude pl an and el evat i on v i ews demonst r at i ng t hat t he equi pment wi l l f i t t he al l ot t ed spaces wi t h c l ear ance f or i nst al l at i on and mai nt enance. Updat e t he Shop Dr awi ngs t o r ef l ect as- bui l t condi t i ons af t er al l r el at ed wor k i s compl et ed. Each set of dr awi ngs shal l i ncl ude t he f ol l owi ng:
a. Descr i pt i ve i ndex of dr awi ngs i n t he submi t t al wi t h dr awi ngs l i s t ed i n sequence by dr awi ng number . A l egend i dent i f y i ng devi ce symbol s, nomencl at ur e, and convent i ons used.
b. Fl oor pl ans dr awn t o a scal e not l ess t han 1/ 8" = 1' - 0" whi ch c l ear l y show l ocat i ons of spr i nkl er s, r i ser s, pi pe hanger s, sei smi c separ at i on assembl i es, sway br aci ng, i nspect or ' s t est connect i ons, dr ai ns, and ot her appl i cabl e det ai l s necessar y t o c l ear l y descr i be t he pr oposed ar r angement . I ndi cat e each t ype of f i t t i ng used and t he l ocat i ons of bushi ngs, r educi ng coupl i ngs, and wel ded j oi nt s.
SECTI ON 21 13 18. 00 10 Page 7
c. Act ual cent er - t o- cent er di mensi ons bet ween spr i nkl er s on br anch l i nes and bet ween br anch l i nes; f r om end spr i nkl er s t o adj acent wal l s; f r om wal l s t o br anch l i nes; f r om spr i nkl er f eed mai ns, cr oss- mai ns and br anch l i nes t o f i ni shed f l oor and r oof or cei l i ng. A det ai l shal l show t he di mensi on f r om t he spr i nkl er and spr i nkl er def l ect or t o t he cei l i ng i n f i ni shed ar eas.
d. Longi t udi nal and t r ansver se bui l di ng sect i ons showi ng t ypi cal br anch l i ne and cr oss- mai n pi pe r out i ng as wel l as el evat i on of each t ypi cal spr i nkl er above f i ni shed f l oor .
e. Det ai l s of each t ype of r i ser assembl y; pi pe hanger ; sway br aci ng f or ear t hquake pr ot ect i on, and r est r ai nt of under gr ound wat er mai n at poi nt - of - ent r y i nt o t he bui l di ng, and el ect r i cal devi ces and i nt er connect i ng wi r i ng.
f . Compl et e poi nt - t o- poi nt wi r i ng di agr am of t he det ect i on and cont r ol syst em. I ndi cat e t he det ai l ed i nt er connect i on of cont r ol panel modul es t o t he devi ces, t he number and si ze of conduct or s i n each condui t , and s i ze of condui t . Connect i on poi nt s shal l be i ndi cat ed and coor di nat ed wi t h t he t er mi nal i dent i f i cat i on mar ked on t he devi ces. Pr ovi de compl et e i nt er nal wi r i ng schemat i c of t he cont r ol panel and each el ect r i cal devi ce. Det ai l ed descr i pt i on of t he f unct i ons of t he cont r ol panel and each modul e shal l be pr ovi ded.
1. 5 DELI VERY, STORAGE, AND HANDLI NG
Al l equi pment del i ver ed and pl aced i n st or age shal l be housed i n a manner t o pr ecl ude any damage f r om t he weat her , humi di t y and t emper at ur e var i at i ons, di r t and dust , or ot her cont ami nant s. Addi t i onal l y, al l pi pes shal l ei t her be capped or pl ugged unt i l i nst al l ed.
1. 6 EXTRA MATERI ALS
Submi t spar e par t s dat a f or each di f f er ent i t em of mat er i al and equi pment speci f i ed. The dat a shal l i ncl ude a compl et e l i s t of par t s and suppl i es, wi t h cur r ent uni t pr i ces and sour ce of suppl y, and a l i s t of par t s r ecommended by t he manuf act ur er t o be r epl aced af t er 1 year and 3 year s of ser vi ce. I ncl ude al i s t of speci al t ool s and t est equi pment r equi r ed f or mai nt enance and t est i ng of t he pr oduct s suppl i ed.
PART 2 PRODUCTS
2. 1 STANDARD PRODUCTS
Pr ovi de mat er i al s and equi pment whi ch ar e st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of such pr oduct s and t hat essent i al l y dupl i cat e i t ems t hat have been i n sat i sf act or y use f or at l east 2 year s pr i or t o bi d openi ng. Submi t manuf act ur er ' s cat al og dat a i ncl uded wi t h t he Spr i nkl er Syst em Dr awi ngs f or al l i t ems speci f i ed her ei n.
Hi ghl i ght t he dat a t o show model , s i ze, opt i ons, et c. , t hat ar e i nt ended f or consi der at i on. Dat a shal l be adequat e t o demonst r at e compl i ance wi t h al l cont r act r equi r ement s. I n addi t i on, pr ovi de a compl et e equi pment l i s t t hat i ncl udes equi pment descr i pt i on, model number and quant i t y.
2. 2 NAMEPLATES
Al l equi pment shal l have a namepl at e t hat i dent i f i es t he manuf act ur er ' s name, addr ess, t ype or st y l e, model or ser i al number , and cat al og number .
SECTI ON 21 13 18. 00 10 Page 8
2. 3 REQUI REMENTS FOR FI RE PROTECTI ON SERVI CE
Mat er i al s and equi pment shal l have been t est ed by Under wr i t er s Labor at or i es, I nc. and l i s t ed i n UL Fi r e Pr ot Di r or appr oved by Fact or y Mut ual and l i s t ed i n FM APP GUI DE. Wher e t he t er ms " l i s t ed" or " appr oved" appear i n t hi s speci f i cat i on, such shal l mean l i s t ed i n UL Fi r e Pr ot Di r or
FM APP GUI DE.
2. 4 ABOVEGROUND PI PI NG COMPONENTS
2. 4. 1 St eel Pi pe
Except as modi f i ed her ei n, st eel pi pe shal l be bl ack as per mi t t ed by NFPA 13 and shal l conf or m t o appl i cabl e pr ovi s i ons of ASTM A795/ A795M, ASTM A53/ A53M, or ASTM A135/ A135M. Pi pe i n whi ch t hr eads or gr ooves ar e cut or r ol l ed f or med shal l be Schedul e 40 or shal l be l i s t ed by Under wr i t er s ' Labor at or i es t o have a cor r osi on r esi st ance r at i o ( CRR) of
1. 0 or gr eat er af t er t hr eads or gr ooves ar e cut or r ol l ed f or med. Pi pe shal l be mar ked wi t h t he name of t he manuf act ur er , k i nd of pi pe, and ASTM designation.
2. 4. 2 Fi t t i ngs f or Non- Gr ooved St eel Pi pe
Fi t t i ngs shal l be cast i r on conf or mi ng t o ASME B16. 4, st eel conf or mi ng t o ASME B16. 9 or ASME B16. 11, or mal l eabl e i r on conf or mi ng t o ASME B16. 3.
St eel pr ess f i t t i ngs shal l not be used. Fi t t i ngs i nt o whi ch spr i nk l er s, dr op ni ppl es or r i ser ni ppl es ( spr i gs) ar e scr ewed shal l be t hr eaded t ype.
Pl ai n- end f i t t i ngs wi t h mechani cal coupl i ngs, f i t t i ngs t hat use st eel gr i ppi ng devi ces t o bi t e i nt o t he pi pe and segment ed wel ded f i t t i ngs shal l not be used.
2. 4. 3 Gr ooved Mechani cal Joi nt s and Fi t t i ngs
Joi nt s and f i t t i ngs shal l be desi gned f or not l ess t han 175 psi ser vi ce and shal l be t he pr oduct of t he same manuf act ur er ; segment ed wel ded f i t t i ngs shal l not be used. Fi t t i ng and coupl i ng houses shal l be mal l eabl e i r on conf or mi ng t o ASTM A47/ A47M, Gr ade 32510; duct i l e i r on conf or mi ng t o ASTM A536, Gr ade 65- 45- 12. Gasket s shal l be of s i l i con compound and appr oved f or dr y f i r e pr ot ect i on syst ems. Gasket shal l be t he f l ush t ype t hat f i l l s t he ent i r e cavi t y bet ween t he f i t t i ng and t he pi pe. Nut s and bol t s shal l be heat - t r eat ed st eel conf or mi ng t o ASTM A183 and shal l be cadmi um pl at ed or z i nc el ect r opl at ed.
2. 4. 4 Flanges
Fl anges shal l conf or m t o NFPA 13 and ASME B16. 1. Gasket s shal l be non- asbest os compr essed mat er i al i n accor dance wi t h ASME B16. 21, 1/ 16 i nch t hi ck, and f ul l f ace or sel f - cent er i ng f l at r i ng t ype.
2. 4. 4. 1 Bolts
Bol t s shal l be ASTM A449, Type 1. Bol t s shal l ext end no l ess t han t hr ee f ul l t hr eads beyond t he nut wi t h bol t s t i ght ened t o t he r equi r ed t or que.
2. 4. 4. 2 Nuts
Nut s shal l be hexagon t ype conf or mi ng t o ASME B18. 2. 2 .
SECTI ON 21 13 18. 00 10 Page 9
2. 4. 4. 3 Washers
Washer s shal l meet t he r equi r ement s of ASTM F436. Fl at c i r cul ar washer s shal l be pr ovi ded under al l bol t heads and nut s.
2. 4. 5 Pi pe Hanger s
Hanger s shal l be l i s t ed i n UL Fi r e Pr ot Di r or FM APP GUI DE and of t he t ype sui t abl e f or t he appl i cat i on, const r uct i on, and pi pe t ype and si ze t o be supported.
2. 4. 6 Valves
2. 4. 6. 1 Cont r ol Val ve and Gat e Val ve
Manual l y oper at ed spr i nkl er cont r ol val ve and gat e val ve shal l be out s i de st em and yoke ( OS&Y) t ype and shal l be l i s t ed i n UL Bl d Mat Di r or
FM APP GUI DE.
2. 4. 6. 2 Check Val ves
Check val ve 2 i nches and l ar ger shal l be l i s t ed i n UL Bl d Mat Di r or FM APP GUI DE. Check val ves 4 i nches and l ar ger shal l be of t he swi ng t ype wi t h f l anged cast i r on body and f l anged i nspect i on pl at e, shal l have a c l ear wat er way and shal l meet t he r equi r ement s of MSS SP- 71, f or Type 3 or 4.
2. 5 AUTOMATI C WATER CONTROL VALVE ( DELUGE VALVE)
Aut omat i c wat er cont r ol val ve ( del uge val ve) shal l be el ect r i cal l y- act uat ed and r at ed f or a wor ki ng pr essur e of 175 psi . Val ve shal l be capabl e of bei ng r eset wi t hout openi ng t he val ve. El ect r i cal sol enoi d val ve used t o act uat e t he wat er cont r ol val ve shal l be an i nt egr al component of t he val ve or shal l be appr oved f or use by t he wat er cont r ol val ve manuf act ur er .
Sol enoi d val ve shal l be r at ed at 24 vol t s di r ect cur r ent , and shal l be nor mal l y c l osed t ype t hat oper at es when ener gi zed. Sol enoi d val ves shal l be r at ed f or a maxi mum pr essur e di f f er ent i al of 175 psi . Wat er cont r ol val ve shal l be equi pped wi t h a means t o pr event t he val ve f r om r et ur ni ng t o t he c l osed posi t i on unt i l bei ng manual l y r eset . Assembl y shal l be compl et e wi t h t he val ve manuf act ur er ' s st andar d t r i m pi pi ng, dr ai n and t est val ves, pr essur e gauges, and ot her r equi r ed appur t enances. I ncl ude wi t h each assembl y an emer gency r el ease devi ce f or manual l y t r i ppi ng t he wat er cont r ol val ve i n t he event of a power or ot her syst em f ai l ur e. Devi ce shal l be a st andar d accessor y component of t he val ve manuf act ur er and shal l be l abel ed as t o i t s f unct i on and met hod of oper at i on. Val ves l ocat ed i n hazar dous l ocat i ons shal l be appr oved f or t he hazar d c l assi f i cat i on of t he ar ea wher e l ocat ed.
2. 6 SUPERVI SORY NI TROGEN SYSTEM
2. 6. 1 Ni t r ogen- Ai r Compr essor
Ni t r ogen Gener at or - ai r compr essor assembl y shal l be s i ngl e st age oi l l ess t ype, ai r cool ed, el ect r i c- mot or dr i ven, equi pped wi t h a check val ve, cent r i f ugal pr essur e and moi st ur e unl oader , pr essur e swi t ch f or aut omat i c st ar t i ng and st oppi ng. Pr essur e swi t ch shal l be set t o st ar t t he compr essor at 20 psi , or as r ecommended by t he manuf act ur er and st op i t at 30 psi , or a r ecommended by t he manuf act ur er . A saf et y r el i ef val ve, set t o oper at e at 65 psi , or a r ecommended by t he manuf act ur er shal l be
SECTI ON 21 13 18. 00 10 Page 10 pr ovi ded. The compr essor shal l be s i zed t o pr essur i ze t he syst em t o 30 psi wi t hi n 30 mi nut es. The basi s of desi gn f or t hi s pr oj ect i s t he Pot t er I NS- 100 I nt el l i gen or an appr oved equi val ent syst em t hat occupi es an equi val ent amount of space and r equi r es no addi t i on el ect r i cal c i r cui t r y or suppor t equi pment .
2. 6. 2 Ni t r ogen Pr essur e Mai nt enance Devi ce
Devi ce shal l be a pr essur e r egul at or t hat aut omat i cal l y r educes suppl y ni t r ogen pr essur e t o t he mi ni mum pr essur e r equi r ed t o be mai nt ai ned i n t he pi pi ng syst em. The devi ce shal l have a cast br onze body and val ve housi ng compl et e wi t h di aphr agm assembl y, spr i ng, f i l t er , bal l check t o pr event backf l ow, 1/ 16 i nch r est r i c t i on t o pr event r api d pr essur i zat i on of t he syst em, and adj ust ment scr ew. The devi ce shal l be capabl e of r educi ng maxi mum i nl et pr essur e of 100 psi t o a f i xed out l et pr essur e adj ust abl e t o 30 psi .
2. 6. 3 Ni t r ogen Suppl y Pi pi ng Syst em
Each pr eact i on syst em shal l be equi pped wi t h a separ at e pr essur e mai nt enance devi ce, shut of f val ve, bypass val ve and pr essur e gauge. Pi pi ng shal l be gal vani zed st eel i n accor dance wi t h ASTM A795/ A795M or
ASTM A53/ A53M.
2. 6. 4 Low Ni t r ogen/ Ai r Pr essur e Swi t ch
Revi s i on 1
Each pr eact i on syst em shal l be pr ovi ded wi t h a ni t r ogen/ ai r pr essur e swi t ch connect ed t o t he cont r ol panel . Upon r educt i on of super vi sor y ai r pr essur e t o appr oxi mat el y 10 psi , t he l ow ni t r ogen pr essur e swi t ch shal l act uat e t he audi bl e al ar m devi ce and a r ed l ow- ni t r ogen al ar m l i ght on t he cont r ol panel annunci at or .
Revi s i on 1
2. 7 SPRINKLERS
Spr i nkl er s f or pr eact i on syst ems shal l be aut omat i c, f usi bl e sol der or gl ass bul b t ype; spr i nkl er s f or del uge syst ems shal l be open t ype wi t hout t he f usi bl e el ement . Spr i nkl er s wi t h i nt er nal O- r i ngs shal l not be used.
Spr i nkl er s shal l be used i n accor dance wi t h t hei r l i s t ed cover age l i mi t at i ons. Temper at ur e c l assi f i cat i on shal l be or di nar y . Spr i nkl er s i n hi gh heat ar eas i ncl udi ng at t i c spaces or i n c l ose pr oxi mi t y t o uni t heat er s shal l have t emper at ur e c l assi f i cat i on i n accor dance wi t h NFPA 13.
Ext ended cover age spr i nkl er s shal l not be used.
2. 7. 1 Pendent Spr i nkl er
Pendent spr i nkl er shal l be of t he f usi bl e st r ut or gl ass bul b t ype, or di nar y t emper at ur e qui ck- r esponse t ype wi t h nomi nal 1/ 2 i nch or i f i ce.
Pendent spr i nkl er s shal l have a pol i shed chr ome f i ni sh.
2. 7. 2 Upr i ght Spr i nkl er
Upr i ght spr i nkl er shal l be or di nar y t emper at ur e br ass qui ck- r esponse t ype and shal l have a nomi nal 1/ 2 i nch or i f i ce.
SECTI ON 21 13 18. 00 10 Page 11 04 Sept ember 2018
2. 8 ACCESSORIES
2. 8. 1 Spr i nkl er Cabi net
Spar e spr i nkl er s shal l be pr ovi ded i n accor dance wi t h NFPA 13 and shal l be packed i n a sui t abl e met al or pl ast i c cabi net . Spar e spr i nkl er s shal l be r epr esent at i ve of , and i n pr opor t i on t o, t he number of each t ype and t emper at ur e r at i ng of t he spr i nkl er s i nst al l ed. At l east one wr ench of each t ype r equi r ed shal l be pr ovi ded.
2. 8. 2 Pendent Spr i nkl er Escut cheon
Escut cheon shal l be one- pi ece met al l i c t ype wi t h a dept h of l ess t han 3/ 4 i nch and sui t abl e f or i nst al l at i on on pendent spr i nkl er s. The escut cheon shal l have a f act or y f i ni sh t hat mat ches t he pendent spr i nkl er heads.
2. 8. 3 Pi pe Escut cheon
Escut cheon shal l be pol i shed chr omi um- pl at ed z i nc al l oy, or pol i shed chr omi um- pl at ed copper al l oy. Escut cheons shal l be ei t her one- pi ece or spl i t - pat t er n, hel d i n pl ace by i nt er nal spr i ng t ensi on or set scr ew.
2. 8. 4 Spr i nkl er Guar d
Guar d shal l be a st eel wi r e cage desi gned t o encase t he spr i nkl er and pr ot ect i t f r om mechani cal damage. Guar ds shal l be pr ovi ded on spr i nkl er s l ocat ed bel ow 7 f oot 6 i nches as i ndi cat ed.
2. 8. 5 I dent i f i cat i on Si gn
Val ve i dent i f i cat i on s i gn shal l be mi ni mum 6 i nches wi de by 2 i nches hi gh wi t h enamel baked f i ni sh on mi ni mum 18 gauge st eel or 0. 024 i nch al umi num wi t h r ed l et t er s on a whi t e backgr ound or whi t e l et t er s on r ed backgr ound.
Wor di ng of s i gn shal l i ncl ude, but not be l i mi t ed t o " mai n dr ai n, " " auxi l i ar y dr ai n, " " i nspect or ' s t est , " " al ar m t est , " " al ar m l i ne, " and si mi l ar wor di ng as r equi r ed t o i dent i f y oper at i onal component s.
2. 9 CONTROL PANEL
Panel shal l be UL l i s t ed or FM appr oved f or " Rel easi ng Devi ce Ser vi ce" or shal l have modul es appr oved f or t hi s pur pose. Panel shal l cont ai n al l component s and equi pment r equi r ed t o pr ovi de t he speci f i ed oper at i onal and super vi sor y f unct i ons of t he syst em. House component s i n a sur f ace
- mount ed st eel cabi net wi t h hi nged door and cyl i nder l ock. Cont r ol panel shal l be a c l ean, uncl ut t er ed, and or der l y f act or y assembl ed and wi r ed uni t . Panel shal l i ncl ude i nt egr al " power on, " " al ar m, " and " t r oubl e" l amps wi t h annunci at i on of each al ar m, super vi sor y and t r oubl e s i gnal . The panel shal l have pr omi nent r i gi d pl ast i c or met al i dent i f i cat i on pl at es f or l amps, zones, cont r ol s, met er s, f uses, and swi t ches. Namepl at es f or f uses shal l al so i ncl ude amper e r at i ng. Cont r ol panel swi t ches shal l be wi t hi n t he l ocked cabi net . Pr ovi de a sui t abl e means f or t est i ng t he wor ki ng condi t i on and accur acy of t he cont r ol panel v i sual i ndi cat i ng devi ces ( met er and l amps) . Met er s and l amps shal l be pl ai nl y v i s i bl e when t he cabi net door i s c l osed. Si gnal s shal l be pr ovi ded t o i ndi cat e by zone any al ar m, super vi sor y or t r oubl e condi t i on on t he syst em. Upon r est or at i on of power , st ar t up shal l be aut omat i c, and shal l not r equi r e any manual oper at i on. The l oss of pr i mar y power or t he sequence of appl y i ng pr i mar y or emer gency power shal l not af f ect t he t r ansmi ssi on of al ar m, super vi sor y or t r oubl e s i gnal s. Dual hazar d capabl e cont r ol and r el ease panel s ar e t he
SECTI ON 21 13 18. 00 10 Page 12 basi s of desi gn f or t hi s pr oj ect as shown on dr awi ngs and i n not es. The basi s of desi gn f or t hi s pr oj ect i s t he FI RELI TE MRP 200, Dual Hazar d Cont r ol Rel ease Panel or t he Vi k i ng VFR- 400 Hazar d Rel ease Cont r ol Panel .
2. 9. 1 Zone Annunci at or
Revi s i on 1
Zones and exact devi ces wi l l be annunci at ed on l cd t ext scr een f or al l addr essabl e devi ces and non-addressable devi ces moni t or ed by addr essabl e modul es or relays .
Revi s i on 1
2. 9. 2 Pr i mar y Power Suppl y
Revi s i on 1
Pr i mar y power and t r oubl e al ar m power t o t he Cont r ol Panel shal l be suppl i ed f r om t wo 120 VAC ci r cui t s. Power t o t he cont r ol panel shal l be on dedi cat ed 20 amp 120 VAC c i r cui t s. Panel shal l be equi pped wi t h one 20- amp ci r cui t br eaker s f or each cont r ol panel and wi t h key l ock. Ci r cui t shal l be per manent l y mar ked " PREACTI ON SPRI NKLER SYSTEM" .
Revi s i on 1
2. 9. 3 Emer gency Power Suppl y
Emer gency power shal l be pr ovi ded f or syst em oper at i on i n t he event of f ai l ur e of t he pr i mar y power suppl y and shal l consi st of r echar geabl e st or age bat t er y syst em. Tr ansf er f r om nor mal t o emer gency power or r est or at i on f r om emer gency t o nor mal power shal l be aut omat i c and shal l not cause t r ansmi ssi on of a f al se al ar m.
2. 9. 3. 1 St or age Bat t er i es
St or age Bat t er i es shal l be seal ed, Ni ckel - Cadmi um or l ead cal c i um r equi r i ng no addi t i onal wat er . Submi t cal cul at i ons t o subst ant i at e t he t ot al r equi r ement s f or super vi sor y and al ar m power . I nc l ude amper e- hour r equi r ement s f or each syst em component and each cont r ol panel component or modul e, under bot h nor mal and al ar m condi t i ons. The bat t er y r echar gi ng per i od shal l be i ncl uded wi t h t he cal cul at i ons. The bat t er i es shal l have ampl e capaci t y, wi t h pr i mar y power di sconnect ed, t o oper at e t he syst em f or a per i od of 48 hour s. Fol l owi ng t hi s per i od of oper at i on v i a bat t er i es, t he bat t er i es shal l have ampl e capaci t y t o oper at e al l al ar m i ndi cat i ng devi ces i n t he al ar m mode f or a mi ni mum per i od of 15 mi nut es. Bat t er y cabi net shal l be a separ at e compar t ment at t he bot t om of t he cont r ol panel or a separ at e cabi net i f necessar y. The bat t er y cabi net shal l have adequat e space f or spar e dupl i cat e st or age bat t er i es. Bat t er i es shal l be mount ed on a noncor r osi ve and nonconduct i ve base or pad.
2. 9. 3. 2 Bat t er y Char ger
Bat t er y char ger shal l be compl et el y aut omat i c, wi t h hi gh/ l ow char gi ng r at e, capabl e of r est or i ng t he bat t er i es f r om f ul l di schar ge t o f ul l char ge wi t hi n 48 usi ng t he hi gh char gi ng r at e. A separ at e ammet er shal l be pr ovi ded f or i ndi cat i ng r at e of char ge. A separ at e vol t met er shal l be pr ovi ded t o i ndi cat e t he st at e of t he bat t er y char ge. A pi l ot l i ght i ndi cat i ng when bat t er i es ar e manual l y pl aced on a hi gh r at e of char ge
SECTI ON 21 13 18. 00 10 Page 13 04 Sept ember 2018 e3enmrt3 Highlight shal l be pr ovi ded as par t of t he uni t assembl y. The char ger shal l be l ocat ed i n cont r ol panel cabi net .
2. 10 ALARM I NI TI ATI NG DEVI CES
2. 10. 1 I nci pi ent Smoke Det ect i on ( Ul t r a- Sensi t i ve Smoke Det ect i on)
Det ect or s shal l have a mi ni mum of 3 pr ogr ammabl e det ect i on t hr eshol ds or poi nt s i n addi t i on t o t he nor mal t r oubl e and super vi sor y condi t i on poi nt s.
Det ect i on t hr eshol d poi nt s shal l be f i el d pr ogr ammabl e wi t hi n sensi t i v i t y l i mi t s. The l east sensi t i ve det ect i on t hr eshol d s i gnal must cause t r ansmi ssi on of an al ar m t o t he bui l di ng f i r e al ar m cont r ol panel and t he r emot e cent r al s t at i on or Secur i t y oper at i ons cent er as wel l as i ni t i at i ng act i vat i on of t he bui l di ng al ar m and al l occupant not i f i cat i on devi ces. I n addi t i on t he al ar m shal l send si gnal s t o t he dual hazar d cont r ol and r el ease panel t o act i vat e t he appr opr i at e pr e- act i on val ve f or t he syst em i n t he zone i n al ar m. Ot her det ect i on t hr eshol ds shal l cause not i f i cat i ons/ f unct i ons as def i ned.
a. Range of Det ect i on: The smoke det ect or wi l l pr ovi de det ect i on wi t hi n a r ange of sensi t i v i t y . The accept abl e al er t det ect i on t hr eshol d s i gnal l evel wi t hi n t hi s r ange shoul d not be l ess t han one t ent h of an al ar m det ect i on t hr eshol d s i gnal l evel .
b. Al er t Det ect i on Thr eshol d Si gnal Level : The maxi mum sensi t i v i t y shoul d be no l ess t han 0. 003 per cent obscur at i on per f oot .
c. Al ar m Det ect i on Thr eshol d Si gnal Level : The mi ni mum sensi t i v i t y shoul d be not gr eat er t han 1/ 5 per cent per f oot .
Al l pi pi ng f or t he I nci pi ent smoke det ect i on shal l be manuf act ur er s r ecommendat i ons and be UL Li st ed f or such pur pose.
2. 10. 2 Manual Act uat i on St at i on
St at i on shal l be mount ed at 42 i nches above t he f l oor , unl ess ot her wi se shown. St at i on shal l be ar r anged t o act i vat e t he del uge syst em. St at i on shal l be dual - act i on t ype r equi r i ng t wo separ at e oper at i ons i n or der t o cause syst em di schar ge. St at i on shal l be col or ed a uni que col or di ssi mi l ar t o col or used f or manual f i r e al ar m syst em. St at i on shal l be pr ovi ded wi t h a posi t i ve v i s i bl e i ndi cat i on of oper at i on of t he st at i on. St at i on shal l be weat her pr oof t ype and shal l be pr ovi ded wi t h an engr aved l abel i ndi cat i ng DELUGE SYSTEM.
2. 10. 3 Spr i nkl er Pr essur e Al ar m Swi t ch
Pr essur e swi t ch shal l i ncl ude a met al housi ng wi t h a neopr ene di aphr agm, SPDT snap act i on swi t ches. The swi t ch shal l have a ser vi ce pr essur e r at i ng of 175 psi . Ther e shal l be t wo SPDT ( For m C) cont act s f act or y adj ust ed t o oper at e at 4 t o 8 psi . The swi t ch shal l be capabl e of bei ng mount ed i n any posi t i on i n t he al ar m l i ne t r i m pi pi ng of t he al ar m check val ve.
2. 10. 4 Wat er f l ow Al ar m
El ect r i cal l y oper at ed, ext er i or - mount ed, wat er f l ow al ar m bel l shal l be pr ovi ded and i nst al l ed i n accor dance wi t h NFPA 13. Wat er f l ow al ar m bel l shal l be r at ed 24 VDC and shal l be connect ed t o t he Fi r e Al ar m Cont r ol Panel ( FACP) i n accor dance wi t h Sect i on 28 31 64. 00 10 FI RE DETECTI ON AND
SECTI ON 21 13 18. 00 10 Page 14
ALARM SYSTEM, ADDRESSABLE.
2. 10. 5 Val ve Super vi sor y ( Tamper ) Swi t ch
Swi t ch shal l be sui t abl e f or mount i ng t o t he t ype of cont r ol val ve t o be super vi sed open. The swi t ch shal l be t amper r esi st ant and cont ai n one set of SPDT ( For m C) cont act s ar r anged t o t r ansf er upon r emoval of t he housi ng cover or c l osur e of t he val ve of mor e t han t wo r ot at i ons of t he val ve st em.
2. 11 NOTI FI CATI ON APPLI ANCES
Not i f i cat i on appl i ances shal l be sui t abl e f or connect i on t o super vi sed al ar m i ndi cat i ng c i r cui t s. Appl i ance shal l have a separ at e scr ew t er mi nal f or each conduct or . The sur f ace of t he appl i ance shal l be r ed i n col or .
Not i f i cat i on devi ces f or t he speci f i c annunci at i on of I SD condi t i ons shal l be by v i sual devi ces of a uni que col or t o al l ow f or i dent i f i cat i on wi t hi n comput er and Si mul at or r ooms.
2. 11. 1 Al ar m Hor n
Hor n shal l be sur f ace mount ed, wi t h t he mat chi ng mount i ng back box sur f ace mount ed v i br at i ng t ype sui t abl e f or use i n an el ect r i cal l y super vi sed c i r cui t . Hor ns shal l oper at e on nomi nal 24 VDC and have scr ew t er mi nal s f or i n- out wi r i ng connect i on. Sound out put shal l be a mi ni mum of 85 DBA at 10 f eet . Hor ns used i n ext er i or l ocat i ons shal l be speci f i cal l y l i s t ed or appr oved f or out door use and be pr ovi ded wi t h met al housi ng and pr ot ect i ve grills.
2. 12 WIRING
Revi s i on 1
Wi r i ng f or al t er nat i ng cur r ent ( AC) c i r cui t s shal l be 12 AWG mi ni mum.
Wi r i ng f or l ow vol t age di r ect cur r ent ( DC) c i r cui t s shal l be No. 16 or 14 AWG mi ni mum based on bat t er y calculations and necessar y f act or s of saf et y.
Power wi r i ng ( over 28 vol t s) and cont r ol wi r i ng shal l be i sol at ed. Wi r i ng shal l conf or m t o NFPA 70. Syst em f i el d wi r i ng shal l be sol i d copper and i nst al l ed i n el ect r i cal met al l i c t ubi ng or i n met al l i c condui t , except r i gi d pl ast i c condui t may be used under s l ab- on- gr ade. Conduct or s shal l be col or coded. Conduct or s used f or t he same f unct i on shal l be s i mi l ar l y col or coded. Wi r i ng col or code shal l r emai n uni f or m t hr oughout t he c i r cui t . Pi gt ai l or T- t ap connect i ons t o al ar m i ni t i at i ng, al ar m i ndi cat i ng, super vi sor y, and act uat i on c i r cui t s ar e pr ohi bi t ed.
Revi s i on 1
PART 3 EXECUTI ON
3. 1 EXAMINATION
Af t er becomi ng f ami l i ar wi t h al l det ai l s of t he wor k, ver i f y al l di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng t he wor k.
3. 2 I NSPECTI ON BY FI RE PROTECTI ON SPECI ALI ST
The Fi r e Pr ot ect i on Speci al i s t shal l i nspect t he spr i nkl er syst em per i odi cal l y dur i ng t he i nst al l at i on t o assur e t hat t he spr i nkl er syst em i nst al l ed i n accor dance wi t h t he cont r act r equi r ement s. The Fi r e
SECTI ON 21 13 18. 00 10 Page 15 04 Sept ember 2018
Pr ot ect i on Speci al i s t shal l wi t ness t he pr el i mi nar y and f i nal t est s and shal l s i gn t he t est r esul t s. The Fi r e Pr ot ect i on Speci al i s t , af t er compl et i on of t he syst em i nspect i ons and a successf ul f i nal t est , shal l cer t i f y i n wr i t i ng t hat t he syst em has been i nst al l ed i n accor dance wi t h t he cont r act r equi r ement s, i ncl udi ng s i gned appr oval of t he Pr el i mi nar y, Det ect i on and Cont r ol Syst ems, and Fi nal Accept ance Test Repor t s. Any di scr epancy shal l be br ought t o t he at t ent i on of t he Cont r act i ng Of f i cer i n wr i t i ng, no l at er t han t hr ee wor ki ng days af t er t he di scr epancy i s discovered.
3. 3 ABOVEGROUND PI PI NG I NSTALLATI ON
3. 3. 1 Pr ot ect i on of Pi pi ng Agai nst Ear t hquake Damage
Sei smi cal l y pr ot ect t he syst em pi pi ng agai nst damage f r om ear t hquakes.
Thi s r equi r ement i s not subj ect t o det er mi nat i on under NFPA 13. I nst al l t he sei smi c pr ot ect i on of t he syst em pi pi ng, i ncl udi ng sway br aci ng as r equi r ed, i n accor dance wi t h UFC 3- 310- 04, NFPA 13 and Annex A; submi t l oad cal cul at i ons f or s i z i ng of sway br aci ng f or syst ems t hat ar e r equi r ed t o be pr ot ect ed agai nst damage f r om ear t hquakes. I ncl ude t he r equi r ed f eat ur es i dent i f i ed t her ei n t hat ar e appl i cabl e t o t he speci f i c pi pi ng syst em.
3. 3. 2 Pi pi ng i n Exposed Ar eas
Exposed pi pi ng shal l be i nst al l ed so as not di mi ni sh exi t access wi dt hs, cor r i dor s, or equi pment access. Exposed hor i zont al pi pi ng, i ncl udi ng dr ai n pi pi ng, shal l be i nst al l ed t o pr ovi de maxi mum headr oom.
3. 3. 3 Pi pi ng i n Fi ni shed Ar eas
I n ar eas wi t h suspended or dr opped cei l i ngs and i n ar eas wi t h conceal ed spaces above t he cei l i ng, pi pi ng shal l be conceal ed above cei l i ngs. Pi pi ng shal l be i nspect ed, t est ed and appr oved bef or e bei ng conceal ed. Ri ser s and si mi l ar ver t i cal r uns of pi pi ng i n f i ni shed ar eas shal l be conceal ed.
3. 3. 4 Pendent Spr i nkl er s Locat i ons
Spr i nkl er s i nst al l ed i n t he pendent posi t i on shal l be of t he l i s t ed dr y pendent t ype, unl ess ot her wi se i ndi cat ed. Dr y pendent spr i nkl er s shal l be of t he r equi r ed l engt h t o per mi t t he spr i nkl er t o be t hr eaded di r ect l y i nt o a br anch l i ne t ee. Hanger s shal l be pr ovi ded on ar m- over s t o dr op ni ppl es suppl y i ng pendent spr i nkl er s when t he ar m- over exceeds 12 i nches f or st eel pi pe or 6 i nches f or copper t ubi ng. Dr y pendent spr i nkl er assembl i es shal l be such t hat spr i nkl er cei l i ng pl at es or escut cheons ar e of t he uni f or m dept h t hr oughout t he f i ni shed space. Pendent spr i nkl er s i n suspended cei l i ngs shal l be a mi ni mum of 6 i nches f r om cei l i ng gr i d. Recessed pendent spr i nkl er s shal l be i nst al l ed such t hat t he di st ance f r om t he spr i nkl er def l ect or t o t he under s i de of t he cei l i ng shal l not exceed t he manuf act ur er ' s l i s t ed r ange and shal l be of uni f or m dept h t hr oughout t he f i ni shed ar ea.
3. 3. 5 Upr i ght Spr i nkl er s
Ri ser ni ppl es or " spr i gs" t o upr i ght spr i nkl er s shal l cont ai n no f i t t i ngs bet ween t he br anch l i ne t ee and t he r educi ng coupl i ng at t he spr i nk l er .
Ri ser ni ppl es exceedi ng 30 i nches i n l engt h shal l be i ndi v i dual l y suppor t ed.
SECTI ON 21 13 18. 00 10 Page 16
3. 3. 6 Pendent Spr i nkl er s Locat i ons
Spr i nkl er s i nst al l ed i n t he pendent posi t i on shal l be of t he l i s t ed dr y pendent t ype, unl ess ot her wi se i ndi cat ed. Dr y pendent spr i nkl er s shal l be of t he r equi r ed l engt h t o per mi t t he spr i nkl er t o be t hr eaded di r ect l y i nt o a br anch l i ne t ee. Hanger s shal l be pr ovi ded on ar m- over s exceedi ng 12 i nches i n l engt h. Dr y pendent spr i nkl er assembl i es shal l be such t hat spr i nkl er cei l i ng pl at es or escut cheons ar e of t he uni f or m dept h t hr oughout t he f i ni shed space. Pendent spr i nkl er s i n suspended cei l i ngs shal l be a mi ni mum of 6 i nches f r om cei l i ng gr i d. Recessed pendent spr i nkl er s shal l be i nst al l ed such t hat t he di st ance f r om t he spr i nkl er def l ect or t o t he under si de of t he cei l i ng shal l not exceed t he manuf act ur er ' s l i s t ed r ange and shal l be of uni f or m dept h t hr oughout t he f i ni shed ar ea.
3. 3. 7 Pi pe Joi nt s
Pi pe j oi nt s shal l conf or m t o NFPA 13, except as modi f i ed her ei n. Not mor e t han f our t hr eads shal l show af t er j oi nt i s made up.