33 40 00.pdf
PDF 83 KB Posted
- Solicitation number
- W912DS-12-R-0002
About this file
Amendment 0001 Specs
View the file
Other files
| File | Type | Posted |
|---|---|---|
| St John's Interim Hospital Dv Lay.pdf | ||
| W912DS-12-R-0002 0008.pdf | ||
| W912DS-12-R-0002 0007.pdf | ||
| W912DS-12-R-0002 0006.pdf | ||
| W912DS-12-R-0002 0005.pdf | ||
| W912DS-12-R-0002 0004.pdf | ||
| W912DS-12-R-0002 0003.pdf | ||
| Site Visit - Sign-in Sheet - dtd 2011-10-25.pdf | ||
| W912DS-12-R-0002 0002.pdf | ||
| E505 ELECTRICAL DETAILS.pdf | ||
| 1980DR_E502.pdf | ||
| 1980DR_ES101.pdf | ||
| 1980DR_GI_CVR.pdf | ||
| 26 20 00.pdf | ||
| 63095_Site_Add01.pdf | ||
| 22 00 70.pdf | ||
| W912DS-12-R-0002 0001.pdf | ||
| 00902.pdf | ||
| 10 14 01.pdf | ||
| 00901.pdf | ||
| 33 70 02.00 10.pdf | ||
| 63095_Site_Final_Specs.pdf | ||
| 63095_Site_Final_Dwgs.pdf | ||
| W912DS-12-R-0002.pdf |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
St. John's Interim Hospital Site Design Joplin, MO
SECTION 33 40 00
STORM DRAINAGE UTILITIES
02/10
PART 1 GENERAL
1.1 MEASUREMENT AND PAYMENT
1.1.1 Pipe Culverts and Storm Drains
The length of pipe installed will be measured along the centerlines of the pipe from end to end of pipe without deductions for diameter of manholes.
Pipe will be paid for at the contract unit price for the number of linear feet of culverts or storm drains placed in the accepted work.
1.1.2 Storm Drainage Structures
The quantity of manholes and inlets will be measured as the total number of manholes and inlets of the various types of construction, complete with frames and gratings or covers and, where indicated, with fixed side-rail ladders, constructed to the depth of [_____] feet in the accepted work.
The depth of manholes and inlets will be measured from the top of grating or cover to invert of outlet pipe. Manholes and inlets constructed to depths greater than the depth specified above will be paid for as units at the contract unit price for manholes and inlets, plus an additional amount per linear foot for the measured depth beyond a depth of [_____] feet.
1.1.3 Walls and Headwalls
Walls and headwalls will be measured by the number of cubic yards of reinforced concrete, plain concrete, or masonry used in the construction of the walls and headwalls. Wall and headwalls will be paid for at the contract unit price for the number of walls and headwalls constructed in the completed work.
1.1.4 Flared End Sections
Flared end sections will be measured by the unit. Flared end sections will be paid for at the contract unit price for the various sizes in the accepted work.
1.1.5 Sheeting and Bracing
Payment will be made for that sheeting and bracing ordered to be left in place, based on the number of square feet of sheeting and bracing remaining below the surface of the ground.
1.1.6 Rock Excavation
Payment will be made for the number of cubic yards of material acceptably excavated, as specified and defined as rock excavation in Section 31 00 00 EARTHWORK, measured in the original position, and computed by allowing actual width of rock excavation with the following limitations: maximum rock excavation width, 30 inches for pipe of 12 inch or less nominal diameter; maximum rock excavation width, 16 inches greater than outside diameter of pipe of more than 12 inch nominal diameter. Measurement will
63095SITE SECTION 33 40 00 Page 1 include authorized overdepth excavation. Payment will also include all necessary drilling and blasting, and all incidentals necessary for satisfactory excavation and disposal of authorized rock excavation. No separate payment will be made for backfill material required to replace rock excavation; this cost shall be included in the Contractor's unit price bid per cubic yard for rock excavation. In rock excavation for manholes and other appurtenances, 1 foot will be allowed outside the wall lines of the structures.
1.1.7 Backfill Replacing Unstable Material
Payment will be made for the number of cubic yards of select granular material required to replace unstable material for foundations under pipes or drainage structures, which will constitute full compensation for this backfill material, including removal and disposal of unstable material and all excavating, hauling, placing, compacting, and all incidentals necessary to complete the construction of the foundation satisfactorily.
1.1.8 Pipe Placed by Jacking
Payment will be made for the number of linear feet of jacked pipe accepted in the completed work measured along the centerline of the pipe in place.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO M 294 (2010) Standard Specification for Corrugated Polyethylene Pipe, 300- to 1500-mm Diameter
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2009) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A48/A48M (2003; R 2008) Standard Specification for Gray Iron Castings
ASTM A536 (1984; R 2009) Standard Specification for Ductile Iron Castings
ASTM B26/B26M (2009) Standard Specification for Aluminum-Alloy Sand Castings
ASTM C 1103 (2003; R 2009) Standard Practice for Joint Acceptance Testing of Installed Precast Concrete Pipe Sewer Lines
ASTM C 270 (2010) Standard Specification for Mortar for Unit Masonry
ASTM C 478 (2009) Standard Specification for Precast
63095SITE SECTION 33 40 00 Page 2
Reinforced Concrete Manhole Sections
ASTM C 828 (2011) Low-Pressure Air Test of Vitrified Clay Pipe Lines
ASTM C 923 (2008) Standard Specification for Resilient Connectors Between Reinforced Concrete Manhole Structures, Pipes and Laterals
ASTM C 924 (2002; R 2009) Testing Concrete Pipe Sewer Lines by Low-Pressure Air Test Method
ASTM C231/C231M (2010) Standard Test Method for Air Content of Freshly Mixed Concrete by the Pressure Method
ASTM D 1751 (2004; R 2008) Standard Specification for Preformed Expansion Joint Filler for Concrete Paving and Structural Construction (Nonextruding and Resilient Bituminous Types)
ASTM D 1752 (2004a; R 2008) Standard Specification for Preformed Sponge Rubber Cork and Recycled PVC Expansion
ASTM D 2167 (2008) Density and Unit Weight of Soil in Place by the Rubber Balloon Method
ASTM D 2321 (2011) Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
ASTM D 2729 (2011) Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
ASTM D 3212 (2007) Standard Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals
ASTM D 3350 (2010a) Polyethylene Plastics Pipe and Fittings Materials
ASTM D 6938 (2010) Standard Test Method for In-Place Density and Water Content of Soil and Soil-Aggregate by Nuclear Methods (Shallow Depth)
ASTM D 698 (2007e1) Laboratory Compaction Characteristics of Soil Using Standard Effort (12,400 ft-lbf/cu. ft. (600 kN-m/cu. m.))
ASTM F 1417 (2011) Standard Test Method for Installation Acceptance of Plastic Gravity Sewer Lines Using Low Pressure Air
ASTM F 2648 High Density Polyethylene Pipe
63095SITE SECTION 33 40 00 Page 3
ASTM F 477 (2010) Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
ASTM F 714 (2010) Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside Diameter
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for [Contractor Quality Control approval.] [information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-03 Product Data
Placing Pipe
SD-04 Samples
Pipe for Culverts and Storm Drains
SD-07 Certificates
Resin Certification Pipeline Testing Hydrostatic Test on Watertight Joints Determination of Density Frame and Cover for Gratings
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery and Storage
Materials delivered to site shall be inspected for damage, unloaded, and stored with a minimum of handling. Materials shall not be stored directly on the ground. The inside of pipes and fittings shall be kept free of dirt and debris. Before, during, and after installation, plastic pipe and fittings shall be protected from any environment that would result in damage or deterioration to the material. Keep a copy of the manufacturer's instructions available at the construction site at all times and follow these instructions unless directed otherwise by the Contracting Officer.
Solvents, solvent compounds, lubricants, elastomeric gaskets, and any similar materials required to install plastic pipe shall be stored in accordance with the manufacturer's recommendations and shall be discarded if the storage period exceeds the recommended shelf life. Solvents in use shall be discarded when the recommended pot life is exceeded.
1.3.2 Handling
Materials shall be handled in a manner that ensures delivery to the trench in sound, undamaged condition. Pipe shall be carried to the trench, not dragged.
63095SITE SECTION 33 40 00 Page 4
PART 2 PRODUCTS
2.1 PIPE FOR CULVERTS AND STORM DRAINS
Pipe for culverts and storm drains shall be of the sizes indicated and shall conform to the requirements specified.
2.1.1 Concrete Pipe
Manufactured in accordance with and conforming to ASTM C 76, Class [I] [II] [III] [IV] [V], or ASTM C 655, [_____] D-Load.
2.1.1.1 Reinforced Arch Culvert and Storm Drainpipe
Manufactured in accordance with and conforming to ASTM C 506, Class [A-II]
[A-III] [A-IV].
2.1.1.2 Reinforced Elliptical Culvert and Storm Drainpipe
Manufactured in accordance with and conforming to ASTM C 507. Horizontal elliptical pipe shall be Class [HE-A] [HE-I] [HE-II] [HE-III] [HE-IV].
Vertical elliptical pipe shall be Class [VE-II] [VE-III] [VE-IV] [VE-V]
[VE-VI].
2.1.1.3 Nonreinforced Pipe
Manufactured in accordance with and conforming to ASTM C 14, Class [1] [2] [3].
2.1.1.4 Cast-In-Place Nonreinforced Conduit
ACI 346, except that testing shall be the responsibility of and at the expense of the Contractor. In the case of other conflicts between ACI 346 and project specifications, requirements of ACI 346 shall govern.
2.1.2 Clay Pipe
Standard or extra strength, as indicated, conforming to ASTM C 700.
2.1.3 Corrugated Steel Pipe
ASTM A760/A760M, zinc or aluminum (Type 2) coated pipe of either:
a. Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
b. Type [IR] [IIR] pipe with helical 3/4 by 3/4 by 7-1/2 inch corrugations.
2.1.3.1 Fully Bituminous Coated
AASHTO M 190 Type A and ASTM A760/A760M zinc or aluminum (Type 2) coated pipe of either:
a. Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
b. Type [IR] [IIR] pipe with helical 3/4 by 3/4 by 7-1/2 inch corrugations.
63095SITE SECTION 33 40 00 Page 5
2.1.3.2 Half Bituminous Coated, Part Paved
AASHTO M 190 Type B and ASTM A760/A760M zinc or aluminum (Type 2) coated Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
2.1.3.3 Fully Bituminous Coated, Part Paved
AASHTO M 190 Type C and ASTM A760/A760M zinc or aluminum (Type 2) coated Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
2.1.3.4 Fully Bituminous Coated, Fully Paved
AASHTO M 190 Type D and ASTM A760/A760M zinc or aluminum (Type 2) coated Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
2.1.3.5 Concrete-Lined
ASTM A760/A760M zinc coated Type I corrugated steel pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations and a concrete lining in accordance with ASTM A849.
2.1.3.6 Polymer Precoated
ASTM A762/A762M corrugated steel pipe fabricated from ASTM A742/A742M Grade 10/10 polymer precoated sheet of either:
a. Type [I] [II] pipe with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
b. Type [IR] [IIR] pipe with helical 3/4 by 3/4 by 7-1/2 inch corrugations.
2.1.3.7 Polymer Precoated, Part Paved
ASTM A762/A762M Type [I] [II] corrugated steel pipe and AASHTO M 190 Type B (modified), paved invert only, fabricated from ASTM A742/A742M Grade 10/10 polymer precoated sheet with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
2.1.3.8 Polymer Precoated, Fully Paved
ASTM A762/A762M Type [I] [II] corrugated steel pipe and AASHTO M 190 Type D (modified), fully paved only, fabricated from ASTM A742/A742M Grade 10/10 polymer precoated sheet with [annular] [helical] 2-2/3 by 1/2 inch corrugations.
2.1.4 Corrugated Aluminum Alloy Pipe
ASTM B745/B745M corrugated aluminum alloy pipe of either:
a. Type [I] [II] pipe with [annular] [helical] corrugations.
b. Type [IA] [IR] [IIA] [IIR] pipe with helical corrugations.
2.1.4.1 Aluminum Fully Bituminous Coated
Bituminous coating shall conform to ASTM A849 Type [_____]. Piping shall conform to AASHTO M 190 Type A and ASTM B745/B745M corrugated aluminum alloy pipe of either:
63095SITE SECTION 33 40 00 Page 6
a. Type [I] [II] pipe with [annular] [helical] corrugations.
b. Type [IA] [IR] [IIA] [IIR] pipe with helical corrugations.
2.1.4.2 Aluminum Fully Bituminous Coated, Part Paved
Bituminous coating shall conform to ASTM A849 Type [_____]. Piping shall conform to AASHTO M 190 Type C and ASTM B745/B745M corrugated aluminum alloy pipe of either:
a. Type [I] [II] pipe with [annular] [helical] corrugations.
b. Type [IR] [IIR] pipe with helical corrugations.
2.1.5 Structural Plate, Steel Pipe, Pipe Arches and Arches
Assembled with galvanized steel nuts and bolts, from galvanized corrugated steel plates conforming to AASHTO M 167M/M 167. Pipe coating, when required, shall conform to the requirements of [AASHTO M 190 Type A] [ AASHTO M 243]. Thickness of plates shall be as indicated.
2.1.6 Structural Plate, Aluminum Pipe, Pipe Arches and Arches
Assembled with either aluminum alloy, aluminum coated steel, stainless steel or zinc coated steel nuts and bolts. Nuts and bolts, and aluminum alloy plates shall conform to AASHTO M 219. Pipe coating, when required, shall conform to the requirements of [AASHTO M 190, Type A] [AASHTO M 243 ]. Thickness of plates shall be as indicated.
2.1.7 Ductile Iron Culvert Pipe
ASTM A716.
2.1.8 Cast-Iron Soil Piping
Cast-Iron Soil Pipe shall conform to ASTM A74, service-weight; gaskets shall be compression-type rubber conforming to ASTM C 564.
2.1.1 Perforated Piping
2.1.9.1 Clay Pipe
ASTM C 700, [standard] [extra] strength.
2.1.9.2 Concrete Pipe
Manufactured in accordance with and conforming to ASTM C 444, and applicable requirements of ASTM C 14, Class [_____].
2.1.9.3 Corrugated Steel Pipe
ASTM A760/A760M, Type III, zinc-coated.
2.1.9.4 Corrugated Aluminum Pipe
ASTM B745/B745M, Type III.
63095SITE SECTION 33 40 00 Page 7
2.1.1.1 PVC Pipe
ASTM D 2729.
2.1.10 PVC Pipe
Submit the pipe manufacturer's resin certification, indicating the cell classification of PVC used to manufacture the pipe, prior to installation of the pipe.
2.1.10.1 Type PSM PVC Pipe
ASTM D 3034, Type PSM, maximum SDR 35, produced from PVC certified by the compounder as meeting the requirements of ASTM D 1784, minimum cell class 12454-B.
2.1.10.2 Profile PVC Pipe
ASTM F 794, Series 46, produced from PVC certified by the compounder as meeting the requirements of ASTM D 1784, minimum cell class 12454-B.
2.1.10.3 Smooth Wall PVC Pipe
ASTM F 679 produced from PVC certified by the compounder as meeting the requirements of ASTM D 1784, minimum cell class 12454-B.
2.1.10.4 Corrugated PVC Pipe
ASTM F 949 produced from PVC certified by the compounder as meeting the requirements of ASTM D 1784, minimum cell class 12454-B.
2.1.2 HDPE Pipe
Submit the pipe manufacturer's resin certification, indicating the cell classification of HDPE used to manufacture the pipe, prior to installation of the pipe. The minimum cell classification for polyethylene plastic shall apply to each of the seven primary properties of the cell classification limits in accordance with ASTM D 3350.
2.1.2.1 Smooth Wall HDPE Pipe
ASTM F 714ASTM F 2648, maximum DR of 21 for pipes 3 to 24 inches in diameter and maximum DR of 26 for pipes 26 to 48 inches in diameter. Pipe shall be produced from HDPE certified by the resin producer as meeting the requirements of ASTM D 3350, minimum cell class 335434C.
2.1.11.2 Corrugated PE Pipe
AASHTO M 294, Type S or C. For slow crack growth resistance, acceptance of resins shall be determined by using the notched constant ligament-stress (NCLS) test meeting the requirements of AASHTO M 294. Pipe walls shall have the following properties:
63095SITE SECTION 33 40 00 Page 8
Minimum Moment Nominal Minimum of Inertia of Size Wall Area Wall Section (in.) (square in/ft) (in to the 4th/in)
12 1.50 0.024 15 1.91 0.053 18 2.34 0.062 24 3.14 0.116 30 3.92 0.163 36 4.50 0.222 42 4.69 0.543 48 5.15 0.543 54 5.67 0.800 60 6.45 0.800
2.1.11.3 Profile Wall PE Pipe
ASTM F 894, RSC 160, produced from PE certified by the resin producer as meeting the requirements of ASTM D 3350, minimum cell class 334433C. Pipe walls shall have the following properties:
Minimum Moment Of Inertia of Wall Section (in to the 4th/in)
Nominal Minimum Cell Cell Size Wall Area Class Class (in.) (square in/ft) 334433C 335434C
18 2.96 0.052 0.038 21 4.15 0.070 0.051 24 4.66 0.081 0.059 27 5.91 0.125 0.091 30 5.91 0.125 0.091 33 6.99 0.161 0.132 36 8.08 0.202 0.165 42 7.81 0.277 0.227 48 8.82 0.338 0.277
2.2 DRAINAGE STRUCTURES
2.2.1 Flared End Sections
Sections shall be of a standard design fabricated from zinc coated steel sheetspolyethylene meeting requirements of ASTM A929/A929MASTM D 3350 and ASTM F 714 or AASHTO M 294.
2.2.2 Precast Reinforced Concrete Box
Manufactured in accordance with and conforming to ASTM C 1433 Section
03 40 00.00 10 PLANT - PRECAST CONCRETE PRODUCTS FOR BELOW GRADE
CONSTRUCTION.
63095SITE SECTION 33 40 00 Page 9
2.2.3 PE Detention Chambers
Actual system shall be determined by a registered professional engineer in the state of Missouri responsible for design. Shop drawings of actual design shall be subject to approval by Owner's Engineer.
2.3 MISCELLANEOUS MATERIALS
2.3.1 Concrete
Unless otherwise specified, concrete and reinforced concrete shall conform to the requirements for [_____] psi concrete under Section [03 30 00.00 10
03 30 53 CAST-IN-PLACE CONCRETE]MISCELLANEOUS [03 30 00 CAST-IN-PLACE
CONCRETE]. The concrete mixture shall have air content by volume of concrete, based on measurements made immediately after discharge from the mixer, of 5 to 7 percent when maximum size of coarse aggregate exceeds 1-1/2 inches. Air content shall be determined in accordance with ASTM C231/C231M. The concrete covering over steel reinforcing shall not be less than 1 inch thick for covers and not less than 1-1/2 inches thick for walls and flooring. Concrete covering deposited directly against the ground shall have a thickness of at least 3 inches between steel and ground. Expansion-joint filler material shall conform to ASTM D 1751, or ASTM D 1752, or shall be resin-impregnated fiberboard conforming to the physical requirements of ASTM D 1752.
2.3.2 Mortar
Mortar for pipe joints, connections to other drainage structures, and brick or block construction shall conform to ASTM C 270, Type M, except that the maximum placement time shall be 1 hour. The quantity of water in the mixture shall be sufficient to produce a stiff workable mortar but in no case shall exceed [_____] gallons of water per sack of cement. Water shall be clean and free of harmful acids, alkalies, and organic impurities. The mortar shall be used within 30 minutes after the ingredients are mixed with water. The inside of the joint shall be wiped clean and finished smooth.
The mortar head on the outside shall be protected from air and sun with a proper covering until satisfactorily cured.
2.3.3 Precast Concrete Segmental Blocks
Precast concrete segmental block shall conform to ASTM C 139, not more than 8 inches thick, not less than 8 inches long, and of such shape that joints can be sealed effectively and bonded with cement mortar.
2.3.4 Brick
Brick shall conform to ASTM C 62, Grade SW; ASTM C 55, Grade S-I or S-II;
or ASTM C 32, Grade MS. Mortar for jointing and plastering shall consist of one part portland cement and two parts fine sand. Lime may be added to the mortar in a quantity not more than 25 percent of the volume of cement.
The joints shall be filled completely and shall be smooth and free from surplus mortar on the inside of the structure. Brick structures shall be plastered with 1/2 inch of mortar over the entire outside surface of the walls. For square or rectangular structures, brick shall be laid in stretcher courses with a header course every sixth course. For round structures, brick shall be laid radially with every sixth course a stretcher course.
63095SITE SECTION 33 40 00 Page 10
2.3.3 Precast Reinforced Concrete Manholes
Conform to ASTM C 478. Joints between precast concrete risers and tops shall be [full-bedded in cement mortar and shall be smoothed to a uniform surface on both interior and exterior of the structure] [made with flexible watertight, rubber-type gaskets meeting the requirements of paragraph JOINTS].Unless otherwise specified, manholes shall conform to the requirements under Section 03 40 00.00 10 PLANT-PRECAST CONCRETE PRODUCTS
FOR BELOW GRADE CONSTRUCTION.
2.3.6 Prefabricated Corrugated Metal Manholes
Manholes shall be of the type and design recommended by the manufacturer.
Manholes shall be complete with frames and cover, or frames and gratings.
2.3.4 Frame and Cover for Gratings
Submit certification on the ability of frame and cover or gratings to carry the imposed live load. Frame and cover for gratings shall be cast gray iron, ASTM A48/A48M, Class 35B; cast ductile iron, ASTM A536, Grade 65-45-12; or cast aluminum, ASTM B26/B26M, Alloy 356.OT6. Weight, shape, size, and waterway openings for grates and curb inlets shall be as indicated on the plans. The word "Storm Sewer" shall be stamped or cast into covers so that it is plainly visible.
2.3.5 Joints
2.3.8.1 Flexible Watertight Joints
a. Materials: Flexible watertight joints shall be made with plastic or rubber-type gaskets for concrete pipe and with factory-fabricated resilient materials for clay pipe. The design of joints and the physical requirements for plastic gaskets shall conform to AASHTO M 198, and rubber-type gaskets shall conform to ASTM C 443.
Factory-fabricated resilient joint materials shall conform to ASTM C 425.
Gaskets shall have not more than one factory-fabricated splice, except that two factory-fabricated splices of the rubber-type gasket are permitted if the nominal diameter of the pipe being gasketed exceeds 54 inches.
b. Test Requirements: Watertight joints shall be tested and shall meet test requirements of paragraph HYDROSTATIC TEST ON WATERTIGHT JOINTS.
Rubber gaskets shall comply with the oil resistant gasket requirements of ASTM C 443. Certified copies of test results shall be delivered to the Contracting Officer before gaskets or jointing materials are installed. Alternate types of watertight joint may be furnished, if specifically approved.
2.3.8.2 External Sealing Bands
Requirements for external sealing bands shall conform to ASTM C 877.
2.3.8.3 Flexible Watertight, Gasketed Joints
a. Gaskets: When infiltration or exfiltration is a concern for pipe lines, the couplings may be required to have gaskets. The closed-cell expanded rubber gaskets shall be a continuous band approximately 7 inches wide and approximately 3/8 inch thick, meeting the requirements of ASTM D 1056, Type 2 [A1] [B3] [_____], and shall have a quality
63095SITE SECTION 33 40 00 Page 11 retention rating of not less than 70 percent when tested for weather resistance by ozone chamber exposure, Method B of ASTM D 1171. Rubber O-ring gaskets shall be 13/16 inch in diameter for pipe diameters of 36 inches or smaller and 7/8 inch in diameter for larger pipe having 1/2 inch deep end corrugation. Rubber O-ring gaskets shall be 1-3/8 inches in diameter for pipe having 1 inch deep end corrugations. O-rings shall meet the requirements of AASHTO M 198 or ASTM C 443. Flexible plastic gaskets shall conform to requirements of AASHTO M 198, Type B.
b. Connecting Bands: Connecting bands shall be of the type, size and sheet thickness of band, and the size of angles, bolts, rods and lugs as indicated or where not indicated as specified in the applicable standards or specifications for the pipe. Exterior rivet heads in the longitudinal seam under the connecting band shall be countersunk or the rivets shall be omitted and the seam welded. Watertight joints shall be tested and shall meet the test requirements of paragraph HYDROSTATIC
TEST ON WATERTIGHT JOINTS.
2.3.5.1 PVC Plastic Pipes
Joints shall be solvent cement or elastomeric gasket type in accordance with the specification for the pipe and as recommended by the pipe manufacturer.
2.3.5.2 Smooth Wall PE Plastic Pipe
Pipe shall be joined using butt fusion method as recommended by the pipe manufacturer.
2.3.5.3 Corrugated PE Plastic Pipe
Pipe joints shall be [soil], [silt], and [water] tight and shall conform to the requirements in AASHTO M 294.[ Water tight joints shall be made using a PE coupling and rubber gaskets as recommended by the pipe manufacturer.
Rubber gaskets shall conform to ASTM F 477.]
2.3.8.7 Profile Wall PE Plastic Pipe
Joints shall be gasketed or thermal weld type with integral bell in accordance with ASTM F 894.
2.3.8.8 Ductile Iron Pipe
Couplings and fittings shall be as recommended by the pipe manufacturer.
2.3.9 Flap Gates
Flap Gates shall be [medium] [or] [heavy]-duty with [circular] [rectangular] opening and double-hinged. [Top pivot points shall be adjustable.] The seat shall be one-piece cast iron with a raised section around the perimeter of the waterway opening to provide the seating face.
The seating face of the seat shall be [cast iron] [bronze] [stainless steel] [neoprene]. The cover shall be one-piece cast iron with necessary reinforcing rib, lifting eye for manual operation, and bosses to provide a pivot point connection with the links. The seating face of the cover shall be [cast iron] [bronze] [stainless steel] [neoprene]. Links or hinge arms shall be cast or ductile iron. Holes of pivot points shall be bronze bushed. All fasteners shall be either galvanized steel, bronze or stainless steel.
63095SITE SECTION 33 40 00 Page 12
2.4 STEEL LADDER
Steel ladder shall be provided where the depth of the storm drainage structure exceeds 12 feet. These ladders shall be not less than 16 inches in width, with 3/4 inch diameter rungs spaced 12 inches apart. The two stringers shall be a minimum 3/8 inch thick and 2-1/2 inches wide. Ladders and inserts shall be galvanized after fabrication in conformance with
ASTM A123/A123M.
2.5 DOWNSPOUT BOOTS
Boots used to connect exterior downspouts to the storm-drainage system shall be of gray cast iron conforming to ASTM A48/A48M, Class 30B or 35BPVC material per the detail in the construction drawings. Shape and size shall be as indicated.
2.6 RESILIENT CONNECTORS
Flexible, watertight connectors used for connecting pipe to manholes and inlets shall conform to ASTM C 923.
2.7 HYDROSTATIC TEST ON WATERTIGHT JOINTS
2.7.1 Concrete, Clay, PVC and PE Pipe
A hydrostatic test shall be made on the watertight joint types as proposed. Only one sample joint of each type needs testing; however, if the sample joint fails because of faulty design or workmanship, an additional sample joint may be tested. During the test period, gaskets or other jointing material shall be protected from extreme temperatures which might adversely affect the performance of such materials. Performance requirements for joints in reinforced and nonreinforced concrete pipe shall conform to AASHTO M 198 or ASTM C 443. Test requirements for joints in clay pipe shall conform to ASTM C 425. Test requirements for joints in PVC and PE plastic pipe shall conform to ASTM D 3212.
2.7.2 Corrugated Steel and Aluminum Pipe
A hydrostatic test shall be made on the watertight joint system or coupling band type proposed. The moment strength required of the joint is expressed as 15 percent of the calculated moment capacity of the pipe on a transverse section remote from the joint by the AASHTO HB-17 (Division II, Section 26). The pipe shall be supported for the hydrostatic test with the joint located at the point which develops 15 percent of the moment capacity of the pipe based on the allowable span in feet for the pipe flowing full or 40,000 foot-pounds, whichever is less. Performance requirements shall be met at an internal hydrostatic pressure of 10 psi, for a 10 minute period for both annular corrugated metal pipe and helical corrugated metal pipe with factory reformed ends.
2.8 EROSION CONTROL RIPRAP
Provide nonerodible rock not exceeding 1512 inches in its greatest dimension and choked with sufficient small rocks exceeding 6 inches in its greatest dimension to provide a dense mass with a minimum thickness of [812 inches] [as indicated].
63095SITE SECTION 33 40 00 Page 13
PART 3 EXECUTION
3.1 EXCAVATION FOR PIPE CULVERTS, STORM DRAINS, AND DRAINAGE STRUCTURES
Excavation of trenches, and for appurtenances and backfilling for culverts and storm drains, shall be in accordance with the applicable portions of Section 31 00 00 EARTHWORK and the requirements specified below.
3.1.1 Trenching
The width of trenches at any point below the top of the pipe shall be not greater than twice the outside diameter of the pipe plus [_____] inches to permit satisfactory jointing and thorough tamping of the bedding material under and around the pipe. Sheeting and bracing, where required, shall be placed within the trench width as specified, without any overexcavation.
Where trench widths are exceeded, redesign with a resultant increase in cost of stronger pipe or special installation procedures will be necessary. Cost of this redesign and increased cost of pipe or installation shall be borne by the Contractor without additional cost to the Government.
3.1.2 Removal of Rock
Rock in either ledge or boulder formation shall be replaced with suitable materials in accordance with Section 31 00 00 EARTHWORK to provide a compacted earth cushion having a thickness between unremoved rock and the pipe of at least 8 inches or 1/2 inch for each foot of fill over the top of the pipe, whichever is greater, but not more than three-fourths the nominal diameter of the pipe. Where bell-and-spigot pipe is used, the cushion shall be maintained under the bell as well as under the straight portion of the pipe. Rock excavation shall be as specified and defined in Section
31 00 00 EARTHWORK.
3.1.3 Removal of Unstable Material
Where wet or otherwise unstable soil incapable of properly supporting the pipe, as determined by the Contracting Officer, is unexpectedly encountered in the bottom of a trench, such material shall be removed to the depth required and replaced to the proper grade with select granular material, compacted as provided in paragraph BACKFILLING. When removal of unstable material is due to the fault or neglect of the Contractor while performing shoring and sheeting, water removal, or other specified requirements, such removal and replacement shall be performed at no additional cost to the Government.
3.2 BEDDING
The bedding surface for the pipe shall provide a firm foundation of uniform density throughout the entire length of the pipe.
3.2.1 Concrete Pipe Requirements
When no bedding class is specified or detailed on the drawings, concrete pipe shall be bedded in granular material minimum 4 inch in depth in trenches with soil foundation. Depth of granular bedding in trenches with rock foundation shall be 1/2 inch in depth per foot of depth of fill, minimum depth of bedding shall be 8 inch up to maximum depth of 24 inches.
The middle third of the granular bedding shall be loosely placed. Bell holes and depressions for joints shall be removed and formed so entire
63095SITE SECTION 33 40 00 Page 14 barrel of pipe is uniformly supported. The bell hole and depressions for the joints shall be not more than the length, depth, and width required for properly making the particular type of joint.
3.2.2 Clay Pipe Requirements
Bedding for clay pipe shall be as specified by ASTM C 12.
3.2.3 Corrugated Metal Pipe
Bedding for corrugated metal pipe and pipe arch shall be in accordance with ASTM A798/A798M. It is not required to shape the bedding to the pipe geometry. However, for pipe arches, either shape the bedding to the relatively flat bottom arc or fine grade the foundation to a shallow v-shape. Bedding for corrugated structural plate pipe shall meet requirements of ASTM A807/A807M.
3.2.4 Ductile Iron and Cast-Iron Pipe
Bedding for ductile iron and cast-iron pipe shall be as shown on the drawings.
3.2.1 Plastic Pipe
Bedding for PVC and PE pipe shall meet the requirements of ASTM D 2321.
Bedding, haunching, and initial backfill shall be either Class IB or II material.
3.3 PLACING PIPE
Submit printed copies of the manufacturer's recommendations for installation procedures of the material being placed, prior to installation.
Each pipe shall be thoroughly examined before being laid; defective or damaged pipe shall not be used. Plastic pipe shall be protected from exposure to direct sunlight prior to laying, if necessary to maintain adequate pipe stiffness and meet installation deflection requirements.
Pipelines shall be laid to the grades and alignment indicated. Proper facilities shall be provided for lowering sections of pipe into trenches.
Lifting lugs in vertically elongated metal pipe shall be placed in the same vertical plane as the major axis of the pipe. Pipe shall not be laid in water, and pipe shall not be laid when trench conditions or weather are unsuitable for such work. Diversion of drainage or dewatering of trenches during construction shall be provided as necessary. Deflection of installed flexible pipe shall not exceed the following limits:
MAXIMUM ALLOWABLE
TYPE OF PIPE DEFLECTION (%)
Corrugated Steel and Aluminum Alloy 5
Concrete-Lined Corrugated Steel 3
Ductile Iron Culvert 3
Plastic (PVC & HDPE) 5
Note post installation requirements of paragraph 'Deflection Testing' in
63095SITE SECTION 33 40 00 Page 15
PART 3 of this specification for all pipe products including deflection testing requirements for flexible pipe.
3.3.1 Concrete, Clay, PVC, and Ribbed PVC, Ductile Iron and Cast-Iron Pipe Pipe
Laying shall proceed upgrade with spigot ends of bell-and-spigot pipe and tongue ends of tongue-and-groove pipe pointing in the direction of the flow.
3.3.2 Elliptical and Elliptical Reinforced Concrete Pipe
The manufacturer's reference lines, designating the top of the pipe, shall be within 5 degrees of a vertical plane through the longitudinal axis of the pipe, during placement. Damage to or misalignment of the pipe shall be prevented in all backfilling operations.
3.3.2 Corrugated PE Pipe
Laying shall be with the separate sections joined firmly on a bed shaped to line and grade and shall follow manufacturer's recommendations.
3.3.4 Corrugated Metal Pipe and Pipe Arch
Laying shall be with the separate sections joined firmly together, with the outside laps of circumferential joints pointing upstream, and with longitudinal laps on the sides. Part paved pipe shall be installed so that the centerline of bituminous pavement in the pipe, indicated by suitable markings on the top at each end of the pipe sections, coincides with the specified alignment of pipe. Fully paved steel pipe or pipe arch shall have a painted or otherwise applied label inside the pipe or pipe arch indicating sheet thickness of pipe or pipe arch. Any unprotected metal in the joints shall be coated with bituminous material as specified in AASHTO M 190 or AASHTO M 243. Interior coating shall be protected against damage from insertion or removal of struts or tie wires. Lifting lugs shall be used to facilitate moving pipe without damage to exterior or interior coatings. During transportation and installation, pipe or pipe arch and coupling bands shall be handled with care to preclude damage to the coating, paving or lining. Damaged coatings, pavings and linings shall be repaired in accordance with the manufacturer's recommendations prior to placing backfill. Pipe on which coating, paving or lining has been damaged to such an extent that satisfactory field repairs cannot be made shall be removed and replaced. Vertical elongation, where indicated, shall be accomplished by factory elongation. Suitable markings or properly placed lifting lugs shall be provided to ensure placement of factory elongated pipe in a vertical plane.
3.3.5 Structural-Plate Steel
Structural plate shall be installed in accordance with ASTM A807/A807M.
Structural plate shall be assembled in accordance with instructions furnished by the manufacturer. Instructions shall show the position of each plate and the order of assembly. Bolts shall be tightened progressively and uniformly, starting at one end of the structure after all plates are in place. The operation shall be repeated to ensure that all bolts are tightened to meet the torque requirements of 200 foot-pounds plus or minus 50 foot-pounds. Any power wrenches used shall be checked by the use of hand torque wrenches or long-handled socket or structural wrenches for amount of torque produced. Power wrenches shall be checked and adjusted frequently as needed, according to type or condition, to ensure
63095SITE SECTION 33 40 00 Page 16 proper adjustment to supply the required torque.
3.3.6 Structural-Plate Aluminum
Structural plate shall be assembled in accordance with instructions furnished by the manufacturer. Instructions shall show the position of each plate and the order of assembly. Bolts shall be tightened progressively and uniformly, starting at one end of the structure after all plates are in place. The operation shall be repeated to ensure that all bolts are torqued to a minimum of 100 foot-pounds on aluminum alloy bolts and a minimum of 150 foot-pounds on galvanized steel bolts. Any power wrenches used shall be checked by the use of hand torque wrenches or long-handled socket or structural wrenches for the amount of torque produced. Power wrenches shall be checked and adjusted as frequently as needed, according to type or condition, to ensure that they are in proper adjustment to supply the required torque.
3.3.3 Multiple Culverts
Where multiple lines of pipe are installed, adjacent sides of pipe shall be at least half the nominal pipe diameter or 3 feet12 inches apart, whichever is less.
3.3.8 Jacking Pipe Through Fills
Methods of operation and installation for jacking pipe through fills shall conform to requirements specified in Volume 1, Chapter 1, Part 4 of AREMA Eng Man.
3.4 JOINTING
3.4.1 Concrete and Clay Pipe
3.4.1.1 Cement-Mortar Bell-and-Spigot Joint
The first pipe shall be bedded to the established grade line, with the bell end placed upstream. The interior surface of the bell shall be thoroughly cleaned with a wet brush and the lower portion of the bell filled with mortar as required to bring inner surfaces of abutting pipes flush and even. The spigot end of each subsequent pipe shall be cleaned with a wet brush and uniformly matched into a bell so that sections are closely fitted. After each section is laid, the remainder of the joint shall be filled with mortar, and a bead shall be formed around the outside of the joint with sufficient additional mortar. If mortar is not sufficiently stiff to prevent appreciable slump before setting, the outside of the joint shall be wrapped or bandaged with cheesecloth to hold mortar in place.
3.4.1.2 Cement-Mortar Oakum Joint for Bell-and-Spigot Pipe
A closely twisted gasket shall be made of jute or oakum of the diameter required to support the spigot end of the pipe at the proper grade and to make the joint concentric. Joint packing shall be in one piece of sufficient length to pass around the pipe and lap at top. This gasket shall be thoroughly saturated with neat cement grout. The bell of the pipe shall be thoroughly cleaned with a wet brush, and the gasket shall be laid in the bell for the lower third of the circumference and covered with mortar. The spigot of the pipe shall be thoroughly cleaned with a wet brush, inserted in the bell, and carefully driven home. A small amount of mortar shall be inserted in the annular space for the upper two-thirds of
63095SITE SECTION 33 40 00 Page 17 the circumference. The gasket shall be lapped at the top of the pipe and driven home in the annular space with a caulking tool. The remainder of the annular space shall be filled completely with mortar and beveled at an angle of approximately 45 degrees with the outside of the bell. If mortar is not sufficiently stiff to prevent appreciable slump before setting, the outside of the joint thus made shall be wrapped with cheesecloth. Placing of this type of joint shall be kept at least five joints behind laying operations.
3.4.1.3 Cement-Mortar Diaper Joint for Bell-and-Spigot Pipe
The pipe shall be centered so that the annular space is uniform. The annular space shall be caulked with jute or oakum. Before caulking, the inside of the bell and the outside of the spigot shall be cleaned.
a. Diaper Bands: Diaper bands shall consist of heavy cloth fabric to hold grout in place at joints and shall be cut in lengths that extend one-eighth of the circumference of pipe above the spring line on one side of the pipe and up to the spring line on the other side of the pipe. Longitudinal edges of fabric bands shall be rolled and stitched around two pieces of wire. Width of fabric bands shall be such that after fabric has been securely stitched around both edges on wires, the wires will be uniformly spaced not less than 8 inches apart. Wires shall be cut into lengths to pass around pipe with sufficient extra length for the ends to be twisted at top of pipe to hold the band securely in place; bands shall be accurately centered around lower portion of joint.
b. Grout: Grout shall be poured between band and pipe from the high side of band only, until grout rises to the top of band at the spring line of pipe, or as nearly so as possible, on the opposite side of pipe, to ensure a thorough sealing of joint around the portion of pipe covered by the band. Silt, slush, water, or polluted mortar grout forced up on the lower side shall be forced out by pouring, and removed.
c. Remainder of Joint: The remaining unfilled upper portion of the joint shall be filled with mortar and a bead formed around the outside of this upper portion of the joint with a sufficient amount of additional mortar. The diaper shall be left in place. Placing of this type of joint shall be kept at least five joints behind actual laying of pipe.
No backfilling around joints shall be done until joints have been fully inspected and approved.
3.4.1.4 Cement-Mortar Tongue-and-Groove Joint
The first pipe shall be bedded carefully to the established grade line with the groove upstream. A shallow excavation shall be made underneath the pipe at the joint and filled with mortar to provide a bed for the pipe.
The grooved end of the first pipe shall be thoroughly cleaned with a wet brush, and a layer of soft mortar applied to the lower half of the groove.
The tongue of the second pipe shall be cleaned with a wet brush; while in horizontal position, a layer of soft mortar shall be applied to the upper half of the tongue. The tongue end of the second pipe shall be inserted in the grooved end of the first pipe until mortar is squeezed out on interior and exterior surfaces. Sufficient mortar shall be used to fill the joint completely and to form a bead on the outside.
63095SITE SECTION 33 40 00 Page 18
3.4.1.5 Cement-Mortar Diaper Joint for Tongue-and-Groove Pipe
The joint shall be of the type described for cement-mortar tongue-and-groove joint in this paragraph, except that the shallow excavation directly beneath the joint shall not be filled with mortar until after a gauze or cheesecloth band dipped in cement mortar has been wrapped around the outside of the joint. The cement-mortar bead at the joint shall be at least 1/2 inch, thick and the width of the diaper band shall be at least 8 inches. The diaper shall be left in place. Placing of this type of joint shall be kept at least five joints behind the actual laying of the pipe. Backfilling around the joints shall not be done until the joints have been fully inspected and approved.
3.4.1.6 Plastic Sealing Compound Joints for Tongue-and-Grooved Pipe
Sealing compounds shall follow the recommendation of the particular manufacturer in regard to special installation requirements. Surfaces to receive lubricants, primers, or adhesives shall be dry and clean. Sealing compounds shall be affixed to the pipe not more than 3 hours prior to installation of the pipe, and shall be protected from the sun, blowing dust, and other deleterious agents at all times. Sealing compounds shall be inspected before installation of the pipe, and any loose or improperly affixed sealing compound shall be removed and replaced. The pipe shall be aligned with the previously installed pipe, and the joint pulled together.
If, while making the joint with mastic-type sealant, a slight protrusion of the material is not visible along the entire inner and outer circumference of the joint when the joint is pulled up, the pipe shall be removed and the joint remade. After the joint is made, all inner protrusions shall be cut off flush with the inner surface of the pipe. If non-mastic-type sealant material is used, the "Squeeze-Out" requirement above will be waived.
3.4.1.7 Flexible Watertight Joints
Gaskets and jointing materials shall be as recommended by the particular manufacturer in regard to use of lubricants, cements, adhesives, and other special installation requirements. Surfaces to receive lubricants, cements, or adhesives shall be clean and dry. Gaskets and jointing materials shall be affixed to the pipe not more than 24 hours prior to the installation of the pipe, and shall be protected from the sun, blowing dust, and other deleterious agents at all times. Gaskets and jointing materials shall be inspected before installing the pipe; any loose or improperly affixed gaskets and jointing materials shall be removed and replaced. The pipe shall be aligned with the previously installed pipe, and the joint pushed home. If, while the joint is being made the gasket becomes visibly dislocated the pipe shall be removed and the joint remade.
3.4.1.8 External Sealing Band Joint for Noncircular Pipe
Surfaces to receive sealing bands shall be dry and clean. Bands shall be installed in accordance with manufacturer's recommendations.
3.4.2 Corrugated Metal Pipe
3.4.2.1 Field Joints
Transverse field joints shall be designed so that the successive connection of pipe sections will form a continuous line free of appreciable irregularities in the flow line. In addition, the joints shall meet the general performance requirements described in ASTM A798/A798M. Suitable
63095SITE SECTION 33 40 00 Page 19 transverse field joints which satisfy the requirements for one or more of the joint performance categories can be obtained with the following types of connecting bands furnished with suitable band-end fastening devices:
corrugated bands, bands with projections, flat bands, and bands of special design that engage factory reformed ends of corrugated pipe. The space between the pipe and connecting bands shall be kept free from dirt and grit so that corrugations fit snugly. The connecting band, while being tightened, shall be tapped with a soft-head mallet of wood, rubber or plastic, to take up slack and ensure a tight joint. [The annular space between abutting sections of part paved, and fully paved pipe and pipe arch, in sizes 30 inches or larger, shall be filled with a bituminous material after jointing.] Field joints for each type of corrugated metal pipe shall maintain pipe alignment during construction and prevent infiltration of fill material during the life of the installations. The type, size, and sheet thickness of the band and the size of angles or lugs and bolts shall be as indicated or where not indicated, shall be as specified in the applicable standards or specifications for the pipe.
3.4.2.2 Flexible Watertight, Gasketed Joints
Installation shall be as recommended by the gasket manufacturer for use of lubricants and cements and other special installation requirements. The gasket shall be placed over one end of a section of pipe for half the width of the gasket. The other half shall be doubled over the end of the same pipe. When the adjoining section of pipe is in place, the doubled-over half of the gasket shall then be rolled over the adjoining section. Any unevenness in overlap shall be corrected so that the gasket covers the end of pipe sections equally. Connecting bands shall be centered over adjoining sections of pipe, and rods or bolts placed in position and nuts tightened. Band Tightening: The band shall be tightened evenly, even tension being kept on the rods or bolts, and the gasket; the gasket shall seat properly in the corrugations. Watertight joints shall remain uncovered for a period of time designated, and before being covered, tightness of the nuts shall be measured with a torque wrench. If the nut has tended to loosen its grip on the bolts or rods, the nut shall be retightened with a torque wrench and remain uncovered until a tight, permanent joint is assured.
3.4 DRAINAGE STRUCTURES
3.4.1 Manholes and Inlets
Construction shall be of reinforced concrete, plain concrete, brick, or precast reinforced concrete, precast concrete segmental blocks, prefabricated corrugated metal, or bituminous coated corrugated metal;
complete with frames and covers or gratings; and with fixed galvanized steel ladders where indicated where the depth of the structure exceeds 12 feet. Pipe studs and junction chambers of prefabricated corrugated metal manholes shall be fully bituminous-coated and paved when the connecting branch lines are so treated. Pipe connections to concrete manholes and inlets shall be made with flexible, watertight connectors.
3.4.2 Walls and Headwalls
Construction shall be as indicated.
3.5 STEEL LADDER INSTALLATION
Ladder shall be adequately anchored to the wall by means of steel inserts
63095SITE SECTION 33 40 00 Page 20 spaced not more than 6 feet vertically, and shall be installed to provide at least 6 inches of space between the wall and the rungs. The wall along the line of the ladder shall be vertical for its entire length.
3.6 BACKFILLING
3.6.1 Backfilling Pipe in Trenches
After the pipe has been properly bedded, selected material from excavation or borrow, at a moisture content that will facilitate compaction, shall be placed along both sides of pipe in layers not exceeding 6 inches in compacted depth. The backfill shall be brought up evenly on both sides of pipe for the full length of pipe. The fill shall be thoroughly compacted under the haunches of the pipe.