Example Report for SCBAs.PDF

PDF 183 KB Posted

Attached to
Yaquina Overhaul FY27
Solicitation number
W9127N26BA029_
Issued by

About this file

This document is a Complete SCBA (Self-Contained Breathing Apparatus) test report for a Drager PSS5000 unit (Serial Number: BRCE-1638 11) deployed on the Dredge Yaquina. The test was conducted on February 16, 2023, by Jeramy Griffith at Alexander Gow Fire Equipment in Seattle, Washington, using a Posi3 USB testing device (Serial Number: U07336) with current calibration. The equipment passed all functional tests, including exhalation pressure (5.7" H2O), facepiece leakage (0.4" H2O), static facepiece pressure (0.8" H2O), high pressure leakage (20 PSI), alarm activation at 4500 PSI whistle pressure (1104 PSI), and gauge accuracy across three pressure points (630 PSI, 1850 PSI, and 3090 PSI ±225 PSI each). Visual inspections passed for the facepiece, backframe/harness, low pressure warning system, and hoses, with the cylinder inspection not performed. Breathing resistance testing confirmed acceptable parameters, with facepiece pressure ranging from 0.5" to 2.7" H2O at both standard and maximum breathing rates.

View the file

Other files

File Type Posted
Bid Roster_YAQ FY27 Overhaul_8.24.2026.pdf PDF
Formal Abstract of Offers_Final.pdf PDF
New Door Hinge Design 5.11.5.pdf PDF
Bidder inquiries completed_8.13.2026.pdf PDF
527 000 00 03 S4K Geislinger Coupling Gear.pdf PDF
SCA WD_2015-5623_Alameda CA.pdf PDF
SCA WD 2015-5563_Multnomah County OR.pdf PDF
SCA WD 2015-5535_Snohomish County WA.pdf PDF
Performance Work Statment_amend1_10AUG2026_FINAL.pdf PDF
Solicitation Amendment W9127N26BA0290002 SF 30.pdf PDF
Performance Work Statement_YAQ OH_Amend1_7.24.26.pdf PDF
DT50-55 Tech Manual.pdf PDF
USACE Drawing 353-E330-024 Gear Foundation Mods.pdf PDF
Hundested Dwg 1-022-020409 Installation Unit.pdf PDF
New England Trawler Equipment Co Capstan-Windlass Manual.pdf PDF
MTU Series 60 Service Manual.pdf PDF
Red Hawk FA-000 - Fire Alarm System Dredge YAQUINA General Notes Information.pdf PDF
Maintenance Manual for SCBAs - Drager Servicing.pdf PDF
VD-TM-91721 incl drawings (OM) Manual.pdf PDF
NORSHIPCO Y-2232-18 Revision C Sheets 1 to 2 Arrangement Details of Bow Thruster.pdf PDF
NORSHIPCO Y-2494-3 Revision E Sheets 1 to 2 Hopper Plating.pdf PDF
Hundested 0-002-020932-2 MP700 Propeller Hoved Samling.pdf PDF
NORSHIPCO Y-2232-9 Revision F Sheets 1 to 2 Tank Top Plating.pdf PDF
NORSHIPCO Y-1032-16 Revision K Sheets 1 to 6 General Arrangement.pdf PDF
NORSHIPCO Y-2274-2 Arrangement-Details of Rudder Stock Tiller-Tiebar.pdf PDF
NORSHIPCO Y-1032-16 General Arrangement.pdf PDF
NORSHIPCO Y-2274-1 Rudders.pdf PDF
NORSHIPCO Y-2636-1 Shaft Struts.pdf PDF
Y-2496-2 Door Operating Gear.pdf PDF
NORSHIPCO Y-1034-2 Alum Doors.pdf PDF
Y-2496-2 Arrgt and Details Hopper Doors Operating Gear.pdf PDF
MTU 8V4000 Service Manual.pdf PDF
Red Hawk FA-101- Fire Alarm System Dredge YAQUINA FAS Layout.pdf PDF
D-1441-1 Revision G- CO2 Fire Extinguishing Smoke Detection Systems.PDF PDF
NORSHIPCO Y-2272-1 Revision C Sheets 1 to 2 Chain Locker Details.pdf PDF
LIPS-A004654.pdf PDF
Y-1034-1 Top of Hopper.pdf PDF
NORSHIPCO Y-2494-1 Revision C Sheets 1 to 2 Hopper Door Frames.pdf PDF
NORSHIPCO Y-2496-1 Revision C Sheets 1 to 2 Hopper Door- Frames.pdf PDF
DTC 5241115 Trunnion.pdf PDF
MDC 353-E507-2012-01 Revision A Dredge Pipe Arrangement.pdf PDF
MDC 353-A640-01 Revision B Sheets 1 to 3 Engine Cooling System.pdf PDF
NORSHIPCO Y-2232-42 Revision B Sheets 1 to 5 Miscellaneous Tanks.pdf PDF
Grid Cooler Installation and Maintenance Manual Form 185.pdf PDF
D-1441-2- Layout Smoke Detection System.PDF PDF
NORSHIPCO Y-3878-18 HVAC - Upper DK Deck House.pdf PDF
MDC 353-E507-2012-05 Dredge Pipe Flanges Gaskets.pdf PDF
FY27 Yaquina Overhaul PWS Final.pdf PDF
Solicitation - W9127N26BA029.pdf PDF
Attachment A_Price Schedule.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Posi3 USB Test Results 2/16/2023 8:07:45 AM

Complete SCBA Test

Drager

PSS5000

S/N: BRCE-1638 11

Dredge Yaquina

Posi3 USB serial # U07336 - Calibration was up to date when the test was performed

Tested by : Jeramy Griffith

Alexander Gow Fire Equipment EP

1436 NW 53rd St Seattle, WA 98107 Page 1 Version 4.1.1.109

Functional Tests

Exhalation Pressure 5.7 " H 2 O

Facepiece Leakage Pass 0.4 " H 2 O

Static Facepiece Pressure Pass 0.8 " H 2 O

1st Breath Activation -2.6 " H 2 O

High Pressure Leakage Pass 20 P S I

Bypass Flow 50 L / m i n

Alarm Activation Pressure

4500 PSI Whistle Pass 1104 P S I

Gauge Accuracy

4500 PSI Digital Pass

630 PSI ±225 PSI 1850 PSI ±225 PSI 3090 PSI ±225 PSI

Pass 543 Pass 1838 Pass 3068

Auxiliary IDs

Facepiece

Second Stage BRDE00378P

First Stage/Reducer

Low Pressure Alarm

Cyl Connector

Airline Attachment

Harness BRCE-1638 11

Visual Inspection

Facepiece Pass

Backframe/Harness Pass

Cylinder Not Perform

Low Pressure Warning Pass

Hoses Pass

Manifold Volume: 0.062

Minimum Maximum Breathing Results Minimum Maximum

0.3 " H 2 O 2.3 " H 2 O Pass Facepiece Pressure 0.5 " H 2 O 2.7 " H 2 O Pass