What is the approximate thickness of the existing concrete floor?

Answer: 8 Inches

Will the Government be removing any existing fixtures, shelving tools etcetera from the crane installation area?

Answer: Yes

Will we be able to laterally brace the new columns to the existing building/concrete columns or must the new columns be free standing?

Answer: New structure MUST be free standing. NO tying back to the building columns.

Is the maximum width of 23’-0” shown in your description the out to out of the system?

Answer: The overall width of the crane system including the bridge overhang CANNOT be wider than 23’-0”.

Upon completion of the installation & start-up will RRAD be preforming a load test and if so will the contractor be required to witness the load test?

Answer: The contractor shall perform the appropriate load testing.