Technical Exhibit 10

View the file

Other files

File Type Posted
TIRNO10R00006-A0006 1 .rtf RTF text file
TIRNO10R00006-A0005 1 .rtf RTF text file
TIRNO10R00006-A0004 1 .rtf RTF text file
TIRNO10R00006-A0003 1 .rtf RTF text file
TE-5 Revision 1.xls XLS spreadsheet
TIRNO10R00006-A0002 1 .rtf RTF text file
TIRNO10R00006-A0001 1 .rtf RTF text file
TE - 2 Revision 1.doc DOC document
TE-6 Revision 1.doc DOC document
QASP.xls XLS spreadsheet
TE-8.doc DOC document
Wage Determination DC.doc DOC document
TE-1.doc DOC document
TE-5.xls XLS spreadsheet
TE-11.doc DOC document
TE-9.doc DOC document
CBA Wash DC.pdf PDF
TE-2.doc DOC document
TIRNO10R00006 1 SF1449.rtf RTF text file
TE-6.doc DOC document
TE-4.doc DOC document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IRS Building Delegations Performance Work Statement

TECHNICAL EXHIBIT TE -10

Infrared Testing Requirements

IRS PM

CHECK

DESCRIPTION
FREQUENCY
E-26
Molded Case Breakers Less than 600 Volts and Greater than 400 amps
One time in three years
E-28
Motor Starters Less Than 100 Hp
One time in three years
E-30A
Switchboards, Medium Voltage, (per cubicle)
One time in three years
E-30B
Switchboards Low Voltage, (per cubicle),
One time in three years
E-34A
Disconnects or Isolating Switch, Per Switch, Under 200 amps >600 VOLTS
Annual
E-34B
Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - 200 To 500 Amps
Annual
E-34C
Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - Over 500 Amps
Annual
E-59
Uninterruptible Power System, Static
Annual
E-35A
Motor Control Center (MCC), under 100 hp - - 5 or fewer starters
Annual
E-35B
Motor Control Center (MCC), under 100 hp - - Each additional motor starter
Annual
E-58
Power Distribution Unit
Annual