SSUMRR2504 Addendumn No_01.pdf
PDF 973 KB Posted
- Attached to
- Colston Elevator Replacement
- Solicitation number
- PE-54800-RFQ-2025-000000027
- Issued by
- Chatham County, Georgia
About this file
This is Addendum No. 01 to the construction documents for the Colston Administration Building Elevator Replacement project at Savannah State University in Savannah, Georgia, issued by Cogdell & Mendrala Architects on June 19, 2025. The project involves modifications to the existing hydraulic elevator and associated systems in the Colston Building, including upgrades to the fire alarm systems. A mandatory pre-bid conference was held on June 11, 2025, at 1:00 p.m. EST at the Evers Physical Plant on the Savannah State University campus, with the sign-in sheet attached to the addendum. Bids are due on July 1, 2025, at 1:00 p.m., with a project duration of 150 consecutive calendar days. The addendum indicates that all documents are available through Cogdell & Mendrala Architects and specifies that the construction area is limited to areas identified in the contract documents. The project scope includes three allowances and two unit prices to be included in the bid package. Important deadlines for bidders include June 20, 2025, for requests for approval of substitute products and June 24, 2025, for written questions; no addenda will be issued within five days of the bid date.
The project is governed by applicable building codes including the 2018 International Building Code with Georgia amendments, the 2018 International Fire Code, National Electrical Code 2023 Edition, NFPA 101 Life Safety Code 2018 Edition, and ASME A17.1/CSA B44 Safety Code for Elevators and Escalators. The Colston Administration Building is a two-floor structure with a total gross area of 27,576 square feet and a gross project area of 2,130 square feet, classified as business occupancy under NFPA 101 with existing construction type IIB per the IBC. Liquidated damages are set at $500 per day. The building and adjacent buildings will remain open during construction, requiring contractors to maintain all egress paths and fire protection features while keeping the facility occupied. The addendum's primary modification is the replacement of sheet LS1.01 (Life Safety Plan) in its entirety, with the revised drawing provided in color as required by code.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM No. 01 PAGE 1 OF 1
COLSTON ADMIN. BUILDING ELEVATOR REPLACEMENT CONSTRUCTION DOCUMENTS
SAVANNAH STATE UNIVERSITY
SAVANNAH, GEORGIA MAY 2025 (REV. 06/19/2025)
ADDENDUM No. 01
DATE: JUNE 19, 2025
PROJECT: SSUMRR2504: COLSTON ADMINISTRATION BUILDNG ELEVATOR REPLACEMENT
SAVANNAH STATE UNIVERSITY, SAVANNAH GA
BY: COGDELL & MENDRALA ARCHITECTS, PC (ARCHITECT)
517 EAST CONGRESS STREET
SAVANNAH, GA 31401
This Addendum forms a part of the Contract Documents and modifies the original Drawings and Project
Manual dated May 2025 and identified as (100% Construction Documents).
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. General Information
2. Substitution Requests
3. RFI Response
4. Project Manual
5. Drawings
1.2 GENERAL INFORMATION
A. Agenda and sign-in sheet from the Mandatory Pre-Bid Conference held at the Savannah State
University Campus on Wednesday, June 11, 2025, are attached as part of this addendum.
1. All items on the agenda were read aloud and the meeting was concluded with a tour of the project site.
2. The Contractor shall note if additional site meeting dates and times are needed the request should be made via the RFI process.
B. This addendum does not remove or release the contractor from any product requirements or required certifications. All products shall be required to meet the design intent of the basis of design product. If a substitute manufacturer or fabricator is accepted, they shall be required to modify the product as required to meet the design intent.
1.3 SUBSTITUTION REQUEST
A. Not applicable for Addendum No. 01.
ADDENDUM No. 01 PAGE 2 OF 1
COLSTON ADMIN. BUILDING ELEVATOR REPLACEMENT CONSTRUCTION DOCUMENTS
SAVANNAH STATE UNIVERSITY
SAVANNAH, GEORGIA MAY 2025 (REV. 06/19/2025)
1.4 RFI RESPONSE:
A. Not applicable for Addendum No. 01.
1.5 PROJECT MANUAL:
A. Not applicable for Addendum No. 01.
1.6 Drawings:
A. Architectural:
1. LS1.01 – LIFE SAFETY PLAN: Replace this sheet in its entirety.
PART 2 - (Not Used)
PART 3 - (Not Used)
END OF ADDENDUM No. 01
{ Mandatory Prebid & Site Visit Sign-in Sheet
State Entity Name: Savannah State University Solicitation Number: SSUMRR2504
Solicitation Name: Colston administration Building Elevator Replacement Date: June 11, 2025 @ 1:00 p.m. EST
COMPANY NAME REPRESENTATIVE NAME
SAVANNAH STATE UNIVERSITY RANDALL LOWERY
COGDELL & MENDRALA ARCHITECTS CASEY SMITH {JI~
COGDELL & MENDRALA ARCHITECTS SANDY SHERRILL ~
~fV\ek Cor ro r ~ t: ( () l' t)e.ff ~(.,~ ~lA\~i) j'l&'flLO(Tl ~\ us,, "1 -Z.l!.\C1l\lQ..
C ...I OD
6r•r,i, L:-r+ 5ot'--+: .... S 0,' l l O"'? b"fo..it,-
1Jf}~'7" , Wrwt-A~~ -&ikt> v1u.-l~ S
SAVANNAH
STATE UNIVERSITY
Phone & Email loweryr@savannahstate.edu
912-358-4370 csmith@cogdellmendrala.com 912-234-6318 ssherrill@cogdellmendrala.com 912-234-6318
Sa.'M~teorf, Go~
~ 7. E. \Gt lee.~ Gt~e8\itf CcNb'{'{lUt11o..J . C.o M.
b o yt r-.c, t, ~ \, c..u 1'.,.\ r \,\.c..,\ ~ ~"' \\ ~ ·'-°
- L.-\ l) -- G\ ln '? i Lf7i-.,~~-o'lf .l ~
°' L,·f+1ot""1,',,,s 4.,.4""",.,,. c•-..
C{f'- 5 ~\- so-i, bt\tr,µ (f, tioJ?tx--,,,\l ;~,. (C,._
CogdellMendralaArchitects A Woman ONned Small Business
MEETING AGENDA Cogdell & Mendrala Architects
51 7 East Congress Street
Savannah GA, 31401
Meeting Description: Savannah State University Colston Administration Building Elevator Replacement
Purpose: SSUMMR2504 - Pre-Bid Conference
Date· Wednesdav lune 11 025 Time· 1 ·00 PM Location· Evers Physi ca l Plant SSU
Items To Be Discussed
1 Introductions: I I
2 Bids Due: 1:00pm, July 1, 2025 I
3 All documents are ava ilab le via Cogdell Mendrala Architects I
4 Project Description: I
• Modifications to the ex isting Colston Building hydraulic elevator indicated in the contract documents .
5 Project Duration: 150 Consecutive Calendar days I
6 Liquidated Damages: $500 I
7 The building and adjacent buildings will be open during construction.
8 Construction area: Limited to areas identified in Contract Documents.
-9 AlteFAates
10 Allowances (Refer to specification 01 21 00 for more deta iled information)
• 00 43 21 Allowance Form to be included in the bid package
• Total of 3 Allowances
11 Unit Prices (Refer to specification section 01 22 00 for more detailed information)
• 00 43 22 Unit Prices Form to be included in the bid package
• Total of 2 Unit Prices
12 Instruction to Bidders - Important to read and understand.
• No Addenda will be issued within five days of the bid date Uune 26 th , 2025)
• Request for Approval of a substitute project must be received within ten days of the bid date Uune 20 th , 2025)
• Q uestions must be received in writing within six days prior to the bid date Uune 24 th , 2025)
• No oral interpretations will be made - questions must be in writing
13 The owner will only consider complete bids. Make sure that all required documentation is submitted.
Understand the Owner's Right Concerning Award. There are several requirements that must be met (including in the invitation to bid.)
15 Q uestions:
• I
I
CONTACTS FOR QUESTIONS - Cogdell Mendrala Architects: admin @/ cogdellmendrala.com
I
UP
DN
NUMBER IN DIAMOND INDICATES NUMBER OF OCCUPANTS IN
ANY SPACE CALCULATED FROM LOAD FACTORS (LSC/IBC)
SPACE CONSIDERED AS BEING UNOCCUPIED AND NOT
INCLUDED WITH IN CALCULATIONS
SPACE CONSIDERED AS BEING OCCUPIED AND INCLUDED IN
CALCULATIONS
NUMBER IN OCTAGON INDICATES NUMBER OF ACTUAL
OCCUPANTS IN SPACE
NUMBER IN CIRCLE INDICATES EGRESS CAPACITY OF OPENING
20-MINUTE FIRE-RATED DOOR ASSEMBLY
45-MINUTE FIRE-RATED DOOR ASSEMBLY
1-HOUR FIRE-RATED DOOR ASSEMBLY
1-1/2 HOUR FIRE-RATED DOOR ASSEMBLY
EXIT
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER BRACKET
FEC
C
B1
B2
FEB
X
X
PROPERTY ADDRESS: COLSTON ADMINISTRATION BUILDING
SAVANNAH STATE UNIVERSITY
3219 COLLEGE STREET
SAVANNAH, GEORGIA 31404
APPLICABLE BUILDING CODES WITH GEORGIA AMENDMENTS:
(LIST IS NOT INCLUSIVE)
1. INTERNATIONAL BUILDING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS
(2020), (2022), (2024), (2025)
2. INTERNATIONAL FIRE CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020)
3. INTERNATIONAL PLUMBING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS
(2020), (2022), (2023), (2024)
4. INTERNATIONAL MECHANICAL CODE, 2018 EDITION, WITH GEORGIA
AMENDMENTS (2020), (2024)
5. INTERNATIONAL FUEL GAS CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS
(2020), (2022)
6. NATIONAL ELECTRICAL CODE, 2023 EDITION
7. INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION, WITH GEORGIA
SUPPLEMENTS AND AMENDMENTS (2020), (2022), (2023)
8. LIFE SAFETY CODE, NFPA 101, 2018 EDITION WITH GEORGIA AMENDMENTS
(2020)
9. NFPA 70 NATIONAL ELECTRICAL CODE (2020)
10. NFPA 72 NATIONAL FIRE ALARM & SIGNALING CODE (2019) WITH GA
AMENDMENTS (2020)
11. NFPA 13 (2019) WITH GEORGIA AMENDMENTS (2020)
12. DOJ 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, WITH GEORGIA
ACCESSIBILITY CODE 120-3-20
13. ASME A17.1/CSA B44 - SAFETY CODE FOR ELEVATORS AND ESCALATORS (2022)
CORR.
FINANCIAL AID OFFICE
133A
WORK ROOM
EQUIPMENT
CREDIT UNION
101A
CORR.
LOBBY
SECRETARIAL OFFICE
VENDING
ENTRY
B2
B1
GALLERY
DEAN'S OFFICE
VESTIBULE
CORR.
PRES. SECURITY & RECEPTION
CORR.
CONFERENCE ROOM
OPEN TO BELOW
DATA
CONFERENCE ROOM
B1
PROJECT SCOPE CONSISTS OF MODIFICATIONS TO THE EXISTING ELEVATOR
(AND ASSOCIATED SYSTEMS) IN THE COLSTON BUILDING ON THE SAVANNAH
STATE UNIVERSITY CAMPUS. FIRE ALARM SYSTEMS FOR THE ELEVATOR WILL
ALSO BE UPGRADED.
OCCUPANCY CLASSIFICATION:
NFPA 101: BUSINESS, EXISTING
CONSTRUCTION TYPE (EXISTING):
IBC: TYPE IIB
SPRINKLERED: NO
BUILDING AREA:
13,788 X 2 FLOORS = 27,576 SF GROSS
PROJECT AREA:
1,065 X 2 FLOORS = 2,130 SF GROSS
OCCUPANCY LOAD:
27,576 SF / 150 SF/PERSON (BUSINESS OCC) = 184
PROTECTION: REQUIRED: PROVIDED:
ELEVATOR SHAFT (NFPA 101): 1-HOUR 1-HR, EXISTING
EQUIPMENT ROOM (IBC 3005.4): 2-HOUR 2-HR, EXISTING
GEORGIA STATE MINIMUM STANDARD ELECTRICAL CODE, 620.37
PERMITTED USES IN EQUIPMENT ROOM ARE RESTRICTED TO THOSE
ASSOCIATED WITH ELEVATOR ONLY.
EXISTING ELEVATOR ROOM HAS ELEVATOR EQUIPMENT AND ELECTRICAL
PANELS FOR THE BUILDING.
ELEVATOR WAS ORIGINALLY INSTALLED DURING A 1979 BUILDING
RENOVATION.
EXIT PATH THROUGH LOBBY TO EXIT DOORS SHALL BE KEPT
CLEAR AT ALL TIMES. DO NOT BLOCK WITH EQUIPMENT OR
CONSTRUCTION DEBRIS. MAINTAIN EGRESS PATH CONSISTENT
WITH NFPA 101 7.5 AND 15.2.5 WHILE BUILDING IS OCCUPIED.
EXIT PATH IN CORRIDOR LEADING TO STAIRS SHALL BE KEPT
CLEAR AT ALL TIMES. DO NOT BLOCK WITH EQUIPMENT OR
CONSTRUCTION DEBRIS.MAINTAIN EGRESS PATH CONSISTENT
WITH NFPA 101 7.5 AND 15.2.5 WHILE BUILDING IS OCCUPIED.
TEMPORARY, LOCKABLE, CONSTRUCTION EQUIPMENT STAGING
AREA. SEE NOTE 11/A4.01. BOUNDARY SHOWN IS FULL EXTENT OF
AREA TO BE USED.
UL-RATED ONE-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
NOTE: ALL ARE SHOWN IN COLOR ON ALL
LIFE SAFETY DRAWINGS. LIFE SAFETY DRAWINGS ARE NOT VALID UNLESS
DEPICTED IN COLOR.
WALL AND PARTITION RATINGS
UL-RATED THREE-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
NON-RATED SMOKE-RESISTIVE
SEPARATION ASSEMBLY OR PARTITION,
UNLESS OTHERWISE NOTED
UL-RATED TWO-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
DESIGNATED ONE-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
DESIGNATED TWO-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
DESIGNATED THREE-HOUR SEPARATION
ASSEMBLY OR FIRE PARTITION, UNLESS
OTHERWISE NOTED
517 EAST CONGRESS STREET
SAVANNAH, GEORGIA 31401
tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com
SEAL
SHEET TITLE
PROJECT NO:
DRAWN BY:
DATE:
SCALE:
SHEET
KEY PLAN
CogdellMendralaArchitects
NOT FOR
CONSTRUCTIO
N
M.E.P. ENGINEERS
TRUE NORTH PROJECT NORTHSCALE
COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC
100'50'0
OWNER NO:
METHOD ENGINEERING GROUP
1020 DRAYTON STREET, SUITE 101,
SAVANNAH, GA 31401
As indicated
/1
/2
:2
:2
P
M C
U s e rs
\j ja m e s \D o c u m e n ts
\2
C u ls o n
E le v a to r_
R
J J a m e s V
Y .r v t
LS1.01
LIFE SAFETY -
COMPOSITE
FLOOR PLANS
JMJ
MAY 2025
CONSTRUCTION
DOCUMENTS
COLSTON
ADMINISTRATION
BUILDING
ELEVATOR
REPLACEMENT
3219 COLLEGE ST.
SAVANNAH, GEORGIA
31404
SAVANNAH STATE UNIVERSITY
COLSTON ADMINISTRATION
BUILDING
SSUMRR2504
LIFE SAFETY LEGENDGENERAL INFORMATION GENERAL LIFE SAFETY NOTES
1 REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL LIFE SAFETY INFORMATION.
2 ALL RATED WALLS OR SMOKE BARRIERS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH STENCILING ABOVE DECORATIVE CEILING OR CONCEALED SPACES WITH LETTERS A MINIMUM OF 3" HIGH ON A CONTRASTING BACKGROUND SPACED A MAXIMUM OF 12'-0" O.C. WITH A MINIMUM OF ONE PER WALL OR BARRIER IN ACCORDANCE WITH MODIFICATIONS OF THE 2012 INTERNATIONAL
FIRE CODE, 120-3-3-04, CHAPTER 7 OF THE RULES AND REGULATIONS OF THE FIRE SAFETY
COMMISSIONER. THE HOURLY RATING SHALL BE INCLUDED ON ALL RATED BARRIERS OR WALLS.
WORDING SHALL BE AS FOLLOWS AS APPLICABLE: " '--' HOUR FIRE (AND SMOKE BARRIER) PROTECT
ALL OPENINGS."
3 ALL RATED AND RESISTIVE PARTITIONS/BARRIERS SHALL BE INSPECTED BY CONTRACTOR FOR
CONSTRUCTION COMPLIANCE. ANY VOIDS OR NONCOMPLIANT ITEMS SHALL BE CORRECTED TO
COMPLY WITH INDICTATED CLASSIFICATION.
4 ALL WALL AND PARTITION RATINGS ARE SHOWN IN COLOR ON ALL LIFE SAFETY DRAWINGS. LIFE
SAFETY DRAWINGS ARE NOT VALID UNLESS DEPICTED IN COLOR.
5 BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION PER NFPA 101 4.6.10.1, 2018 EDITION.
RENOVATION WORK SHALL NOT DIMINISH OR REDUCE EXISTING MEANS OF EGRESS TO EXITS. ALL FIRE PROTECTION FEATURES SHALL REMAIN IN PLACE AND BE CONTINUOUSLY MAINTAINED FOR THE
PORTION OF FACILITY THAT IS OCCUPIED.
6 MAINTAIN BARRIERS (INTERIOR & EXTERIOR) AS REQUIRED TO PREVENT PUBLIC ACCESS TO AREAS
IN WHICH DEMOLITION AND NEW CONSTRUCTION ACTIVITIES ARE UNDERWAY. PRIOR TO
COMMENCEMENT OF WORK, COORDINATE WITH USING AGENT TO MINIMIZE IMPACT ON CAMPUS
OPERATIONS.
7 IT SHOULD BE NOTED DUE TO LIMITED AREA FOR BUILDING ACCESS/EGRESS, MATERIAL AND
EQUIPMENT DELIVERIES AND MATERIAL MOVEMENTS WILL REQUIRE CARE AND COORDINATION.
8 CONTRACTOR SHALL AVOID DISABLING THE FACILITIES FIRE ALARM SYSTEM DURING CONSTRUCTION.
SHOULD FOR ANY REASON THIS SYSTEM BECOMES INACTIVE THE CONTRACTOR SHOULD CONTACT
THE CAMPUS AND FD TO PLACE THE FACILITY ON FIRE WATCH.
1/8" = 1'-0"LS1.01
COMPOSITE LIFE SAFETY PLAN - FIRST FLOOR1
1/8" = 1'-0"LS1.01
COMPOSITE LIFE SAFETY PLAN - SECOND FLOOR2
PROJECT SUMMARY
CODE REQUIREMENTS
LIFE SAFETY PLAN NOTES LIFE SAFETY WALL RATINGS
REVISION SCHEDULE
NO DATE DESCRIPTION
1 ADD. NO. 1
LIFE SAFETY WALL RATINGS (EXISTING)
06/16/2025