SSUMRR2504_100_CD_250521.pdf

PDF 3 MB Posted

Attached to
Colston Elevator Replacement
Solicitation number
PE-54800-RFQ-2025-000000027
Issued by
Chatham County, Georgia

About this file

Colston Administration Building Elevator Replacement - Construction Documents

This set of construction documents pertains to a state and local contract opportunity for the Board of Regents of the University System of Georgia at Savannah State University located at 3219 College Street, Savannah, Georgia. The project scope consists of the removal and replacement of an existing elevator and associated systems in the Colston Administration Building, along with upgrades to fire alarm systems serving the elevator. The project is identified as Owner's Project No. SSUMRR2504 and Architect's Project No. 2431, with construction documents prepared by Cogdell & Mendrala Architects, PC as the architect and Method Engineering Group as the MEP engineers. The documents are dated May 2025 and marked "Not for Construction." The building is classified as Business occupancy under NFPA 101, with existing construction type IIB and is unsprinklered. The facility will remain occupied during construction per NFPA 101 4.6.10.1, 2018 Edition, with renovation work required to maintain existing means of egress to exits and all fire protection features.

The construction documents include comprehensive specifications, demolition plans, HVAC plans showing a ductless heat pump system (DHP-1/DAH-1 with 12 MBH cooling capacity), and electrical plans detailing a new 175-amp three-phase 208-volt elevator disconnect with associated wiring and a new 200-amp fusible safety switch with 125-amp time delay fuses. The electrical work includes new smoke detectors at elevator landings connected to the existing Simplex 4010 fire alarm control panel, fire alarm relays for elevator equipment, and GFCI receptacles. All work must comply with the International Building Code (2018 Edition with Georgia Amendments), International Mechanical Code (2018 Edition), National Electrical Code (2023 Edition), Life Safety Code NFPA 101 (2018 Edition), and ASME A17.1/CSA B44 Safety Code for Elevators and Escalators (2022). The contractor is responsible for coordinating with all trades, maintaining building operations during construction, and providing one-year warranties on all workmanship and materials upon final acceptance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COGDELL & MENDRALA ARCHITECTS, PC

COLSTON ADMINISTRATION BUILDING

ELEVATOR REPLACEMENT

ARCHITECT'S PROJECT NO.: 2431

SAVANNAH STATE UNIVERSITY

ARCHITECTS

OWNER

SAVANNAH STATE UNIVERSITY

3219 COLLEGE ST. SAVANNAH, GEORGIA 31404

517 E CONGRESS ST. SAVANNAH, GEORGIA, 31401

912.234.6318

CONSULTANTS

MEP ENGINEERS

LOCATION MAP

SHEET

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101, SAVANNAH, GA 31401

912.963.1611

BOARD OF REGENTS OF THE UNIVERSITY SYSTEM OF GEORGIA

OWNER'S PROJECT NO.: SSUMRR2504

/2

/2

:3 :3

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

CONSTRUCTION DOCUMENTS

3219 COLLEGE ST. SAVANNAH, GEORGIA 31404

MAY 2025

T1.0

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

/2

/2

:3 :3

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

G0.01

SHEET LIST

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

SHEET LIST - ARCHITECTURAL

SHEET

NUMBER SHEET NAME REV. DATE REV.

A0.02 INTERIOR CONSTRUCTION SYSTEMS

A2.01 COMPOSITE FLOOR PLANS

A2.02 ROOF PLAN

A4.01 ENLARGED ELEVATOR PLANS

A5.01 INTERIOR ELEVATIONS

SHEET LIST - LIFE SAFETY

SHEET

NUMBER SHEET NAME REV. DATE REV.

LS1.01 LIFE SAFETY - COMPOSITE FLOOR PLANS

SHEET LIST - GENERAL

SHEET

NUMBER SHEET NAME REV. DATE REV.

G0.01 SHEET LIST

G0.02 GENERAL PROJECT INFORMATION

SHEET LIST - DEMOLITION

SHEET

NUMBER SHEET NAME REV. DATE REV.

D2.01 DEMOLITION - COMPOSITE FLOOR PLANS

D2.02 DEMOLITION - COMPOSITE SECOND FLOOR PLAN

D2.03 DEMOLITION - ROOF PLAN

SHEET LIST - MECHANICAL

SHEET

NUMBER SHEET NAME REV. DATE REV.

M0.00 HVAC TITLE SHEET, SCHEDULE, & SPECIFICATIONS

M1.01 HVAC PLAN

SHEET LIST - ELECTRICAL

SHEET

NUMBER SHEET NAME REV. DATE REV.

E0.00 ELECTRICAL TITLE SHEET

E1.01 ELECTRICAL DEMOLITION PLAN

E2.01 ELECTRICAL PLANS

REVISION SCHEDULE

NO DATE DESCRIPTION

DRAWING

TITLE TITLE OF DRAWING1

A0.1 1/8" = 1'-0"

100A

LOBBY

H100

A0.1 SHEET NO. WHERE

DWG NO.

SHEET NO. WHERE

ELEV. IS DRAWN

SHEET NO. WHERE

DRAWING NO.

SECT. LINESECT. IS DRAWN

SECT. IS DRAWN

DET. IS DRAWN

AREA

AROUND

DASHES

DETAILED

ROOM NAME

ROOM NO.

DOOR NO.

SHEET NO. WHERE

DWG NO.

DWG NO.

DWG NO.

CENTER LINE

DOOR TAG

EXTERIOR WALL TAG

SEE A0.03

MATCH LINE

BREAK LINE

REVISION TAG

DIMENSION

INDICATOR

X.X

16'-0"

BUILDING

SECTION

WALL

SECTION

PLAN OR

SECTION

DETAIL

ROOM TAG

EXTERIOR

ELEVATION

N O

R T H

NORTH

ARROW

A0.1

A0.1

SECT. LINE

A0.1

S1

R1

FLOOR TAG

SEE A0.03

A0.1 A0.1

REVISION CLOUD

REVISION NUMBER

ROOF TAG

SEE A0.03

WINDOW TAG

SEE A8.X SERIES

C1

STOREFRONT TAG

SEE A8.X SERIES

CURTAIN WALL TAG

SEE A8.X SERIES

S1

W1

ROOF TYPE

FLOOR TYPE

EXTERIOR

WALL TYPE

VERTICAL HEIGHT

SPOT ELEVATION

MAIN LEVEL PLAN

0' - 0"

0' - 0"

TOILET & BATH

ACCESSORY TAG

TBA-1

KEYNOTE TAG 03 30 00.A CAST-IN-PLACE CONCRETE

SPECIFICATION SECTION

DESCRIPTION OF CONSTRUCTION

COMPONENT

CONSTRUCTION COMPONENT AS

LISTED IN LEGEND

PLAN NOTE TAG REFERS TO CORRESPONDING

NOTES ON SHEET

ELEV. IS DRAWN

SHEET NO. WHERE

DRAWING NO.INTERIOR

ELEVATION

A0.1 A0.1

INTERIOR PARTITION TAG

SEE A0.04

X.X.X

INTERIOR

WALL TYPE

X.X

X X

REFERS TO CORRESPONDING

ITEM AS SCHEDULED

AIR CONDITION(ING)

ADMINISTRATION

ABOVE FINISHED FLOOR

ALTERNATE

ALUMINUM

APPROXIMATE(LY)

ARCHITECT(URAL)

AUTOMATIC

AUXILIARY

AUDIOVISUAL

BITUMINOUS

BUILDING LINE

BUILDING

BOTTOM OF STEEL

BOTTOM

CABINET

CONTROL JOINT

CENTER LINE

CEILING

CEILING HEIGHT

CLOSET

CLEAR(ANCE)

CONCRETE MASONRY UNIT

COLUMN

CONCRETE

CONFERENCE

CONTINUE, CONTINUOUS

CORRIDOR

CUBIC FOOT

CUBIC YARD

DEMOLISH

DEPARTMENT

DETAIL

DRINKING FOUNTAIN

DIAMETER

DIAGONAL

DIMENSION

DIVISION

DOWN SPOUT

EAST

EACH

ELEVATION

ELECTRIC(AL)

ELEVATOR

EXPANSION JOINT

ENCLOSE(D)

EDGE OF SLAB

EQUAL

EQUIPMENT

ELECTRIC WATER COOLER

EXISTING

JT EXPANSION JOINT

EXTERIOR

FLOOR DRAIN

FIRE EXTINGUISHER

FIRE EXTINGUISHER ON BRACKET

FIRE EXTINGUISHER CABINET

FACE TO FACE

FINISH FLOOR ELEVATION

FIRE HOSE CABINET

FINISHED FLOOR

FLOOR, FILLER

FACE OF CURB

FACE OF FINISH

FACE OF MASONRY

FACE OF SLAB

FACE OF WALL

FOOT, FEET

FOOTING

FURNISH, FURNITURE

GAGE

GALVANIZED

GENERAL CONTRACTOR

GYPSUM BOARD

GYPSUM PLASTER

HANDICAP

HEAVY DUTY

HARDWARE

HARDWOOD

HOLLOW METAL

HORIZONTAL

HEIGHT

HEATING, VENTILATION &

AIR CONDITIONING

INSIDE DIAMETER

INFORMATION

INCLUDE(D), (ING)

INSULATION

INTERIOR

JANITOR CLOSET

KITCHEN

KNOCKOUT

LABORATORY

LAMINATE

LAUNDRY

LAV LAVATORY

LF LINEAR FEET

LVR LOUVER

MAINTENANCE

MATERIAL

MAXIMUM

MECHANICAL

MEZZANINE

MANUFACTURING

MANUFACTURER

MINIMUM

MISCELLANEOUS

MASONRY OPENING

MOISTURE RESISTANT

MOUNTED

MOUNTING

METAL

NORTH

NOT IN CONTRACT

NON-COMBUSTIBLE

NOMINAL

NOT TO SCALE

ON CENTER

OUTSIDE DIAMETER

OPTION(AL)

OPPOSITE

POUNDS PER CUBIC FEET

PLASTIC LAMINATE

POUNDS PER LINEAR FOOT

PLYWOOD

PANEL

PAIR

PREFABRICATED

PREFINISH

PARKING

POUNDS PER SQUARE FOOT

POUNDS PER SQUARE INCH

PAINT, POST-TENSIONED,

PRE-TREATED

POLYVINYL CHLORIDE

(PLASTIC)

QUARTER

QUANTITY

RADIUS, RISER

REFLECTED CEILING PLAN,

REINFORCED CONCRETE

PIPE

ROOF DRAIN

REFRIGERATOR, REFERENCE

REQUIRED

ROOF LEADER

ROOM

ROUGH OPENING

RIGHT OF WAY

S SOUTH

SC SOLID CORE

SD STORM DRAIN

SECT SECTION

SF SQUARE FEET

SIM SIMILAR

SPEC SPECIFICATION

SPKR SPEAKER

SQ SQUARE

SS STAINLESS STEEL

STANDARD

STORAGE

SUSPENDED

SYSTEM

TREAD

TELEPHONE

TEMPORARY

TOP OF FINISH FLOOR

THICKNESS

THROUGH

TOP OF BEAM

TOP OF CONCRETE, TOP OF CURB

TOP OF FOOTING

TOP OF JOIST

TOP OF MASONRY

TOP OF PARAPET

TOS TOP OF SLAB

TOW TOP OF WALL

TREATED

TELEVISION

TYPICAL

UNDERWRITERS LABORATORIES

UNLESS NOTED OTHERWISE

VERTICAL

VESTIBULE

VERIFY IN FIELD

WEST, WIDE

WITH

WITHOUT

WATER CLOSET

WOOD

WORKING POINT, WATERPROOFING

WATER REPELLENT

WEIGHT

WALL TO WALL

WELDED WIRE FABRIC

YARD

A/C

ADMIN

AFF

ALT

ALUM

APPROX

ARCH

AUTO

AUX

AV

BITUM

BL

BLDG

BOS

BOT

CAB

CJ

CL

CLG

CLG HT

CLO

CLR

CMU

COL

CONC

CONF

CONT

CORR

CU FT

CU YD

DEMO

DEPT

DET

DF

DIA

DIAG

DIM

DIV

DS

E

EA

EL

ELEC

ELEV

EJ

ENCL

EOS

EQ

EQUIP

EWC

EXIST

EXP JT

EXT

FD

FE

FEB

FEC

F/F

FF EL

FHC

FIN FLR

FLR

FOC

FOF

FOM

FOS

FOW

FT

FTG

FURN

GA

GALV

GC

GYP BD

GYP PLAS

HC

HD

HDWR

HDWD

HM

HORIZ

HT

HVAC

ID

INFO

INCL

INSUL

INT

JAN CLO

KIT

KO

LAB

LAM

LAU

LAV

LF

LVR

MAINT

MATL

MAX

MECH

MEZZ

MFG

MFR

MIN

MISC

MO

MR

MTD

MTG

MTL

N

NIC

NON

NOM

NTS

OC

OD

OPT

OPP

PCF

PLAM

PLF

PLYWD

PNL

PR

PREFAB

PREFIN

PRKG

PSF

PSI

PT

PVC

QTR

QTY

R

RCP

RD

REF

REQD

RL

RM

RO

ROW

S

SC

SD

SECT

SF

SIM

SPEC

SPKR

SQ

SS

STD

STOR

SUSP

SYS

T

TEL

TEMP

TFF

THK

THRU

TOB

TOC

TOF

TOJ

TOM

TOP

TOS

TOW

TRTD

TV

TYP

UL

UNO

VERT

VEST

VIF

W W/ W/O

WC

WD

WP

WR

WT

W/W

WWF

YD

EARTH/COMPACT FILL

POROUS FILL

CONCRETE

SAND, GYPSUM BOARD

MORTAR, PLASTER

CONCRETE MASONRY

ROUGH WOOD

WOOD BLOCKING

PLAN LEGEND

SECTION

BATT INSULATION

RIGID INSULATION

BRICK VENEER

STEEL/OTHER METALS

PLYWOOD

GYPSUM BOARD

ACOUSTICAL CLG. TILE

FINISH WOOD

NOT IN CONTRACT

AREA NOT IN SCOPE

METAL STUD

PARTITION

CONCRETE MASONRY

PARTITION

EXISTING

CONSTRUCTION

CONSTRUCTION TO BE

REMOVED

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :3

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

G0.02

GENERAL

PROJECT

INFORMATION

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

KEYNOTE LEGEND - MASTER

NO. NOTE

03 30 00.B CAST-IN-PLACE CONCRETE SEE STRUCT.

03 30 00.G WELDED WIRE MESH SEE STRUCT.

03 30 00.H VAPOR BARRIER

03 30 00.S4 4" DRAINABLE FILL SEE STRUCT.

03 51 16.A3 3" CEMENTITIOUS WOOD-FIBER PLANK ROOF DECK

03 52 16 LIGHTWEIGHT INSULATING CONCRETE

04 20 00.A1 HORIZ. JOINT REINF. (@ 16" O.C. U.N.O)

04 20 00.A2 REINF. BAR SEE STRUCT.

04 20 00.C CONCRETE UNIT MASONRY

05 22 00 STEEL JOIST SEE STRUCT.

05 31 00.A STEEL DECKING SEE STRUCT.

07 41 13.16 STANDING-SEAM METAL ROOF PANELS

07 41 13.G THERMAL INSULATION

07 42 43.A2 SELF-ADHERING UNDERLAYMENT

07 54 19 POLYVINYL CHLORIDE ROOFING

07 84 43 JOINT FIRESTOPPING

09 22 16 NON-STRUCTURAL METAL FRAMING

09 22 16.D2 3 5/8" METAL STUDS @ 16" O.C.

09 29 00.A5 5/8" GYPSUM BOARD

09 29 00.H6 THERMAL INSULATION (SOUND ATTENUATION)

09 51 13.A APC 2 X 2

09 51 13.C GRID SYSTEM

10 11 00.B1 MARKER BOARD

10 11 00.C1 TACKBOARD

10 14 26 PANEL SIGNAGE

12 21 13.B HORIZONTAL LOUVER BLINDS (HLB)

02300.E SUBGRADE

GRAPHIC SYMBOLS

ABBREVIATIONS

GENERAL NOTES

1 REFERENCE THE CODE INFORMATION ON SHEET LS1.01 FOR LIFE SAFETY REQUIREMENTS.

2 REFER TO SHEET G0.01 FOR SYMBOL LEGEND.

3 FRAME WALL DIMENSIONS ARE TO FACE OF STUD (UNO)

4 MASONRY WALL DIMENSIONS ARE TO FACE OF CMU (UNO)

5 OFFSET DOOR FRAMES IN STUD PARTITIONS 4" FROM ADJACENT WALL UNLESS INDICATED

OTHERWISE.

6 ALL LUMBER AND PLYWOOD INSTALLED THROUGHOUT THE BUILDING SHALL BE FIRE-RETARDANT

TREATED. STANDING AND RUNNING TRIM DO NOT REQUIRE TREATMENT.

7 LOCATE CONTROLS FOR MECHANICAL, ELECTRICAL, & LIFE SAFETY SYSTEMS (SWITCHES,

THERMOSTATS, PULL STATIONS, ETC) WITHIN 12" OF NEAREST CORNER OR OPENING. DO NOT

CENTER ITEM ON WALL. COORDINATE WITH ARCHITECT IF QUESTIONS ARISE.

8 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS, UNLESS NOTED OTHERWISE.

9 REFER TO PLANS AND/OR SECTIONS FOR SUBSYSTEM TYPE

10 ALL EXPOSED, UNFINISHED EXTERIOR METAL SURFACES SHALL BE PAINTED.

11 INSTALL WOOD BLOCKING BEHIND ALL WALL-MOUNTED EQUIPMENT AT STUD PARTITIONS AND

FURRING.

12 NEW FINISHES SHALL BE INSTALLED FLUSH WITH EXISTING FINISHES.

MATERIAL LEGEND

UP

DN

NUMBER IN DIAMOND INDICATES NUMBER OF OCCUPANTS IN

ANY SPACE CALCULATED FROM LOAD FACTORS (LSC/IBC)

SPACE CONSIDERED AS BEING UNOCCUPIED AND NOT

INCLUDED WITH IN CALCULATIONS

SPACE CONSIDERED AS BEING OCCUPIED AND INCLUDED IN

CALCULATIONS

NUMBER IN OCTAGON INDICATES NUMBER OF ACTUAL

OCCUPANTS IN SPACE

NUMBER IN CIRCLE INDICATES EGRESS CAPACITY OF OPENING

20-MINUTE FIRE-RATED DOOR ASSEMBLY

45-MINUTE FIRE-RATED DOOR ASSEMBLY

1-HOUR FIRE-RATED DOOR ASSEMBLY

1-1/2 HOUR FIRE-RATED DOOR ASSEMBLY

EXIT

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER BRACKET

FEC

C

B1

B2

FEB

X

X

PROPERTY ADDRESS: COLSTON ADMINISTRATION BUILDING

SAVANNAH STATE UNIVERSITY

3219 COLLEGE STREET

SAVANNAH, GEORGIA 31404

APPLICABLE BUILDING CODES WITH GEORGIA AMENDMENTS:

(LIST IS NOT INCLUSIVE)

1. INTERNATIONAL BUILDING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS

(2020), (2022), (2024), (2025)

2. INTERNATIONAL FIRE CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS (2020)

3. INTERNATIONAL PLUMBING CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS

(2020), (2022), (2023), (2024)

4. INTERNATIONAL MECHANICAL CODE, 2018 EDITION, WITH GEORGIA

AMENDMENTS (2020), (2024)

5. INTERNATIONAL FUEL GAS CODE, 2018 EDITION, WITH GEORGIA AMENDMENTS

(2020), (2022)

6. NATIONAL ELECTRICAL CODE, 2023 EDITION

7. INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION, WITH GEORGIA

SUPPLEMENTS AND AMENDMENTS (2020), (2022), (2023)

8. LIFE SAFETY CODE, NFPA 101, 2018 EDITION WITH GEORGIA AMENDMENTS

(2020)

9. NFPA 70 NATIONAL ELECTRICAL CODE (2020)

10. NFPA 72 NATIONAL FIRE ALARM & SIGNALING CODE (2019) WITH GA

AMENDMENTS (2020)

11. NFPA 13 (2019) WITH GEORGIA AMENDMENTS (2020)

12. DOJ 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, WITH GEORGIA

ACCESSIBILITY CODE 120-3-20

13. ASME A17.1/CSA B44 - SAFETY CODE FOR ELEVATORS AND ESCALATORS (2022)

CORR.

FINANCIAL AID OFFICE

133A

WORK ROOM

EQUIPMENT

CREDIT UNION

101A

CORR.

LOBBY

SECRETARIAL OFFICE

VENDING

ENTRY

B2

B1

GALLERY

DEAN'S OFFICE

VESTIBULE

CORR.

PRES. SECURITY & RECEPTION

CORR.

CONFERENCE ROOM

OPEN TO BELOW

DATA

CONFERENCE ROOM

B1

PROJECT SCOPE CONSISTS OF THE REMOVAL AND REPLACEMENT OF

THE EXISTING ELEVATOR (AND ASSOCIATED SYSTEMS) IN THE COLSTON

BUILDING ON THE SAVANNAH STATE UNIVERSITY CAMPUS. FIRE ALARM

SYSTEMS FOR THE ELEVATOR WILL ALSO BE UPGRADED.

OCCUPANCY CLASSIFICATION:

NFPA 101: BUSINESS, EXISTING

CONSTRUCTION TYPE (EXISTING):

IBC: TYPE IIB

SPRINKLERED: NO

PROTECTION: REQUIRED: PROVIDED:

ELEVATOR SHAFT (NFPA 101): 1-HOUR 1-HR, EXISTING

EQUIPMENT ROOM (IBC 3005.4): 2-HOUR 2-HR, EXISTING

GEORGIA STATE MINIMUM STANDARD ELECTRICAL CODE, 620.37

PERMITTED USES IN EQUIPMENT ROOM ARE RESTRICTED TO

THOSE ASSOCIATED WITH ELEVATOR ONLY.

EXISTING ELEVATOR ROOM HAS ELEVATOR EQUIPMENT AND

ELECTRICAL PANELS FOR THE BUILDING.

EXIT PATH THROUGH LOBBY TO EXIT DOORS SHALL BE KEPT

CLEAR AT ALL TIMES. DO NOT BLOCK WITH EQUIPMENT OR

CONSTRUCTION DEBRIS. MAINTAIN EGRESS PATH CONSISTENT

WITH NFPA 101 7.5 AND 15.2.5 WHILE BUILDING IS OCCUPIED.

EXIT PATH IN CORRIDOR LEADING TO STAIRS SHALL BE KEPT

CLEAR AT ALL TIMES. DO NOT BLOCK WITH EQUIPMENT OR

CONSTRUCTION DEBRIS.MAINTAIN EGRESS PATH CONSISTENT

WITH NFPA 101 7.5 AND 15.2.5 WHILE BUILDING IS OCCUPIED.

TEMPORARY, LOCKABLE, CONSTRUCTION EQUIPMENT STAGING

AREA. SEE NOTE 11/A4.01. BOUNDARY SHOWN IS FULL EXTENT OF

AREA TO BE USED.

UL-RATED ONE-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

NOTE: ALL ARE SHOWN IN COLOR ON ALL

LIFE SAFETY DRAWINGS. LIFE SAFETY DRAWINGS ARE NOT VALID UNLESS

DEPICTED IN COLOR.

WALL AND PARTITION RATINGS

UL-RATED THREE-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

NON-RATED SMOKE-RESISTIVE

SEPARATION ASSEMBLY OR PARTITION,

UNLESS OTHERWISE NOTED

UL-RATED TWO-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

DESIGNATED ONE-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

DESIGNATED TWO-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

DESIGNATED THREE-HOUR SEPARATION

ASSEMBLY OR FIRE PARTITION, UNLESS

OTHERWISE NOTED

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :3

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

LS1.01

LIFE SAFETY -

COMPOSITE

FLOOR PLANS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

LIFE SAFETY LEGENDGENERAL INFORMATION GENERAL LIFE SAFETY NOTES

1 REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL LIFE SAFETY INFORMATION.

2 ALL RATED WALLS OR SMOKE BARRIERS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH STENCILING ABOVE DECORATIVE CEILING OR CONCEALED SPACES WITH LETTERS A MINIMUM OF 3" HIGH ON A CONTRASTING BACKGROUND SPACED A MAXIMUM OF 12'-0" O.C. WITH A MINIMUM OF ONE PER WALL OR BARRIER IN ACCORDANCE WITH MODIFICATIONS OF THE 2012 INTERNATIONAL

FIRE CODE, 120-3-3-04, CHAPTER 7 OF THE RULES AND REGULATIONS OF THE FIRE SAFETY

COMMISSIONER. THE HOURLY RATING SHALL BE INCLUDED ON ALL RATED BARRIERS OR WALLS.

WORDING SHALL BE AS FOLLOWS AS APPLICABLE: " '--' HOUR FIRE (AND SMOKE BARRIER) PROTECT

ALL OPENINGS."

3 ALL RATED AND RESISTIVE PARTITIONS/BARRIERS SHALL BE INSPECTED BY CONTRACTOR FOR

CONSTRUCTION COMPLIANCE. ANY VOIDS OR NONCOMPLIANT ITEMS SHALL BE CORRECTED TO

COMPLY WITH INDICTATED CLASSIFICATION.

4 ALL WALL AND PARTITION RATINGS ARE SHOWN IN COLOR ON ALL LIFE SAFETY DRAWINGS. LIFE

SAFETY DRAWINGS ARE NOT VALID UNLESS DEPICTED IN COLOR.

5 BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION PER NFPA 101 4.6.10.1, 2018 EDITION.

RENOVATION WORK SHALL NOT DIMINISH OR REDUCE EXISTING MEANS OF EGRESS TO EXITS. ALL FIRE PROTECTION FEATURES SHALL REMAIN IN PLACE AND BE CONTINUOUSLY MAINTAINED FOR THE

PORTION OF FACILITY THAT IS OCCUPIED.

6 MAINTAIN BARRIERS (INTERIOR & EXTERIOR) AS REQUIRED TO PREVENT PUBLIC ACCESS TO AREAS

IN WHICH DEMOLITION AND NEW CONSTRUCTION ACTIVITIES ARE UNDERWAY. PRIOR TO

COMMENCEMENT OF WORK, COORDINATE WITH USING AGENT TO MINIMIZE IMPACT ON CAMPUS

OPERATIONS.

7 IT SHOULD BE NOTED DUE TO LIMITED AREA FOR BUILDING ACCESS/EGRESS, MATERIAL AND

EQUIPMENT DELIVERIES AND MATERIAL MOVEMENTS WILL REQUIRE CARE AND COORDINATION.

8 CONTRACTOR SHALL AVOID DISABLING THE FACILITIES FIRE ALARM SYSTEM DURING CONSTRUCTION.

SHOULD FOR ANY REASON THIS SYSTEM BECOMES INACTIVE THE CONTRACTOR SHOULD CONTACT

THE CAMPUS AND FD TO PLACE THE FACILITY ON FIRE WATCH.

1/8" = 1'-0"LS1.01

COMPOSITE LIFE SAFETY PLAN - FIRST FLOOR1

1/8" = 1'-0"LS1.01

COMPOSITE LIFE SAFETY PLAN - SECOND FLOOR2

PROJECT SUMMARY

CODE REQUIREMENTS

LIFE SAFETY PLAN NOTES LIFE SAFETY WALL RATINGS

REVISION SCHEDULE

LIFE SAFETY WALL RATINGS (EXISTING)

CORR.

FINANCIAL AID OFFICE

133A

WORK ROOM

EQUIPMENT

CREDIT UNION

101A

CORR.

LOBBY

SECRETARIAL OFFICE

VENDING

ENTRY

D2.01

REMOVE AND REINSTALL CEILING GRID AND PANELS AS

NEEDED FOR ELECTRICAL WORK.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

C E

IL

IN

G S

W A

L L

S

O P

E N

IN

G

S F

L O

O R

S

M

IS

C

O T

H E

R

REMOVE EXISTING WALL PARTITION TO EXTENTS SHOWN.

SEE NOTE 3/A2.01 FOR ADDITIONAL INFORMATION.

REMOVE AND REINSTALL DEFIBULATOR AND OTHER WALL-

MOUNTED ITEMS AT NEW DOOR LOCATION. DO NOT

DISTURB FA DEVICE.

REMOVE AND REINSTALL DOOR. REMOVE FRAME. REMOVE

AND REINSTALL DOOR HARDWARE EXCEPT FOR CLOSER.

DISCARD CLOSER.

REMOVE WALL BASE THIS WALL.

REMOVE EXISTING PLYWOOD BACKER BOARD THIS WALL.

NOT USED.

INSTALL PROTECTION TO PROTECT EXISTING FLOORING.

REMOVE FLOORING IN ELEVATOR CAB.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

REMOVE ELEVATOR COMPONENTS AS REQUIRED FOR

SPECIFIED REPLACEMENTS INCLUDING INTERIOR WALL

PANELS, FLOORING, CEILING AND LIGHTS. SEE ELECTRICAL

SHEETS FOR ADDITIONAL INFORMATION.

REMOVE WALL-MOUNTED ELEVATOR CALL SIGNALS, POSITION

INDICATORS AND RELATED ITEMS AT CORRIDORS. SEE

ELECTRICAL FOR MORE INFORMATION.

SEE ELECTRICAL FOR DEMOLITION IN THIS ROOM.

REMOVE ELEVATOR VENT AND SHAFT EXHAUST FAN DOWN TO

CURB.

REMOVE WALL-MOUNTED SECURITY ENCLOSURE BOX.

COORDINATE WITH ELECTRICAL. SEE ELECTRICAL SHEETS FOR

ADDITIONAL INFORMATION.

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED

EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED;

SALVAGE FOR REUSE AS REQUIRED. REFER TO DOOR

SCHEDULE FOR ADDITIONAL INFORMATION.

AREA NOT IN SCOPE

CORR.

VENDING

LOBBY

CREDIT UNION133A

WORK ROOM

EQUIPMENT

101A

CORR.

10 910

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :3

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

D2.01

DEMOLITION -

COMPOSITE

FLOOR PLANS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

1/8" = 1'-0"D2.01

DEMOLITION - COMPOSITE FIRST FLOOR PLAN1

GENERAL DEMOLITION NOTES

1 DEMOLITION PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 241, 2022 EDITION

"STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS".

2 REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING (MEP) DRAWINGS FOR SPECIFIC DEMOLITION

OF MEP EQUIPMENT AND CONSTRUCTION. MEP DEMOLITION SHOWN ON THE ARCHITECTURAL

DRAWINGS IS GENERAL.

3 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

4 EXCEPT WHERE SPECIFICALLY INDICATED, EXTENT OF SLAB REMOVAL REQUIRED TO INSTALL

CONDUIT AND/OR PIPING IS NOT SHOWN. GENERAL CONTRACTOR IS RESPONSIBLE FOR

COORDINATION OF CUTTING AND PATCHING REQUIRED TO INSTALL MEP LINES BELOW THE SLAB, AND

PENETRATING WALLS AND PARTITIONS.

5 ANY EQUIPMENT REMOVED FOR RE-INSTALLATION SHALL BE PROTECTED AND STORED BY THE

CONTRACTOR.

6 REMOVE ALL MISCELLANEOUS EQUIPMENT MOUNTED WALLS AND FLOOR AS INDICATED.

7 REMOVE AND REPLACE PORTION(S) OF CONCRETE SLAB AS REQUIRED TO INSTALL OR REMOVE

EQUIPMENT AND/OR MATERIAL BELOW. COORDINATE WITH MEP DRAWINGS.

8 WHERE A NOTE IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

9 WHERE MATERIALS ARE REMOVED OR DEMOLISHED, INFIL OR PATCH TO MATCH EXISTING ADJACENT

FINISH AND/OR STRUCTURAL MEMBER.

10 ALL RENOVATION WORK IS TO BE PERFORMED IN COMPLIANCE WITH IFC 2012, SECTION 3304.2 WASTE

DISPOSAL. ALL COMBUSTIBLE DEBRIS AND WASTE MATERIAL SHALL BE REMOVED FROM THE

BUILDING AT THE END OF EACH SHIFT OF WORK.

DEMOLITION NOTE LEGENDDEMOLITION LEGEND

1/4" = 1'-0"D2.01

DEMOLITION - ENLARGED FIRST FLOOR PLAN2

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED

EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED;

SALVAGE FOR REUSE AS REQUIRED. REFER TO DOOR

SCHEDULE FOR ADDITIONAL INFORMATION.

AREA NOT IN SCOPE

REMOVE AND REINSTALL CEILING GRID AND PANELS AS

NEEDED FOR ELECTRICAL WORK.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

C E

IL

IN

G S

W A

L L

S

O P

E N

IN

G

S F

L O

O R

S

M

IS

C

O T

H E

R

REMOVE EXISTING WALL PARTITION TO EXTENTS SHOWN.

SEE NOTE 3/A2.01 FOR ADDITIONAL INFORMATION.

REMOVE AND REINSTALL DEFIBULATOR AND OTHER WALL-

MOUNTED ITEMS AT NEW DOOR LOCATION. DO NOT

DISTURB FA DEVICE.

REMOVE AND REINSTALL DOOR. REMOVE FRAME. REMOVE

AND REINSTALL DOOR HARDWARE EXCEPT FOR CLOSER.

DISCARD CLOSER.

REMOVE WALL BASE THIS WALL.

REMOVE EXISTING PLYWOOD BACKER BOARD THIS WALL.

NOT USED.

INSTALL PROTECTION TO PROTECT EXISTING FLOORING.

REMOVE FLOORING IN ELEVATOR CAB.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

REMOVE ELEVATOR COMPONENTS AS REQUIRED FOR

SPECIFIED REPLACEMENTS INCLUDING INTERIOR WALL

PANELS, FLOORING, CEILING AND LIGHTS. SEE ELECTRICAL

SHEETS FOR ADDITIONAL INFORMATION.

REMOVE WALL-MOUNTED ELEVATOR CALL SIGNALS, POSITION

INDICATORS AND RELATED ITEMS AT CORRIDORS. SEE

ELECTRICAL FOR MORE INFORMATION.

SEE ELECTRICAL FOR DEMOLITION IN THIS ROOM.

REMOVE ELEVATOR VENT AND SHAFT EXHAUST FAN DOWN TO

CURB.

REMOVE WALL-MOUNTED SECURITY ENCLOSURE BOX.

COORDINATE WITH ELECTRICAL. SEE ELECTRICAL SHEETS FOR

ADDITIONAL INFORMATION.

GALLERY

DEAN'S OFFICE

VESTIBULE

CORR.

PRES. SECURITY & RECEPTION

CONFERENCE ROOM

CORR.

OPEN TO BELOW

DATA

CONFERENCE ROOM

1/8" = 1'-0"D2.02

DEMOLITION - COMPOSITE SECOND FLOOR PLAN1

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

1/8" = 1'-0"

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

D2.02

DEMOLITION -

COMPOSITE

SECOND FLOOR

PLAN

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

GENERAL DEMOLITION NOTES

1 DEMOLITION PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 241, 2022 EDITION

"STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS".

2 REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING (MEP) DRAWINGS FOR SPECIFIC DEMOLITION

OF MEP EQUIPMENT AND CONSTRUCTION. MEP DEMOLITION SHOWN ON THE ARCHITECTURAL

DRAWINGS IS GENERAL.

3 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

4 EXCEPT WHERE SPECIFICALLY INDICATED, EXTENT OF SLAB REMOVAL REQUIRED TO INSTALL

CONDUIT AND/OR PIPING IS NOT SHOWN. GENERAL CONTRACTOR IS RESPONSIBLE FOR

COORDINATION OF CUTTING AND PATCHING REQUIRED TO INSTALL MEP LINES BELOW THE SLAB, AND

PENETRATING WALLS AND PARTITIONS.

5 ANY EQUIPMENT REMOVED FOR RE-INSTALLATION SHALL BE PROTECTED AND STORED BY THE

CONTRACTOR.

6 REMOVE ALL MISCELLANEOUS EQUIPMENT MOUNTED WALLS AND FLOOR AS INDICATED.

7 REMOVE AND REPLACE PORTION(S) OF CONCRETE SLAB AS REQUIRED TO INSTALL OR REMOVE

EQUIPMENT AND/OR MATERIAL BELOW. COORDINATE WITH MEP DRAWINGS.

8 WHERE A NOTE IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

9 WHERE MATERIALS ARE REMOVED OR DEMOLISHED, INFIL OR PATCH TO MATCH EXISTING ADJACENT

FINISH AND/OR STRUCTURAL MEMBER.

10 ALL RENOVATION WORK IS TO BE PERFORMED IN COMPLIANCE WITH IFC 2012, SECTION 3304.2 WASTE

DISPOSAL. ALL COMBUSTIBLE DEBRIS AND WASTE MATERIAL SHALL BE REMOVED FROM THE

BUILDING AT THE END OF EACH SHIFT OF WORK.

DEMOLITION LEGEND DEMOLITION NOTE LEGEND

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE REMOVED

EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED;

SALVAGE FOR REUSE AS REQUIRED. REFER TO DOOR

SCHEDULE FOR ADDITIONAL INFORMATION.

AREA NOT IN SCOPE

REMOVE AND REINSTALL CEILING GRID AND PANELS AS

NEEDED FOR ELECTRICAL WORK.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

C E

IL

IN

G S

W A

L L

S

O P

E N

IN

G

S F

L O

O R

S M

IS

C

O

T H

E R

REMOVE EXISTING WALL PARTITION TO EXTENTS SHOWN.

SEE NOTE 3/A2.01 FOR ADDITIONAL INFORMATION.

REMOVE AND REINSTALL DEFIBULATOR AND OTHER WALL-

MOUNTED ITEMS AT NEW DOOR LOCATION. DO NOT

DISTURB FA DEVICE.

REMOVE AND REINSTALL DOOR. REMOVE FRAME. REMOVE

AND REINSTALL DOOR HARDWARE EXCEPT FOR CLOSER.

DISCARD CLOSER.

REMOVE WALL BASE THIS WALL.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

NOT USED.

REMOVE ELEVATOR COMPONENTS INCLUDING DOORS,

INTERIOR WALL PANELS, FLOORING, CEILING AND LIGHTS. SEE

ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION.

REMOVE WALL-MOUNTED ELEVATOR CALL SIGNALS, POSITION

INDICATORS AND RELATED ITEMS AT CORRIDORS. SEE

ELECTRICAL FOR MORE INFORMATION.

SEE ELECTRICAL FOR DEMOLITION IN THIS ROOM.

REMOVE ELEVATOR VENT AND SHAFT EXHAUST FAN. CURB AND

FLASHING TO REMAIN.

REMOVE WALL-MOUNTED SECURITY ENCLOSURE BOX.

COORDINATE WITH ELECTRICAL. SEE ELECTRICAL SHEETS FOR

ADDITIONAL INFORMATION.

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

1/8" = 1'-0"

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

D2.03

DEMOLITION -

ROOF PLAN

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

GENERAL DEMOLITION NOTES

1 DEMOLITION PROCEDURES SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 241, 2022 EDITION

"STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS".

2 REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING (MEP) DRAWINGS FOR SPECIFIC DEMOLITION

OF MEP EQUIPMENT AND CONSTRUCTION. MEP DEMOLITION SHOWN ON THE ARCHITECTURAL

DRAWINGS IS GENERAL.

3 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

4 EXCEPT WHERE SPECIFICALLY INDICATED, EXTENT OF SLAB REMOVAL REQUIRED TO INSTALL

CONDUIT AND/OR PIPING IS NOT SHOWN. GENERAL CONTRACTOR IS RESPONSIBLE FOR

COORDINATION OF CUTTING AND PATCHING REQUIRED TO INSTALL MEP LINES BELOW THE SLAB, AND

PENETRATING WALLS AND PARTITIONS.

5 ANY EQUIPMENT REMOVED FOR RE-INSTALLATION SHALL BE PROTECTED AND STORED BY THE

CONTRACTOR.

6 REMOVE ALL MISCELLANEOUS EQUIPMENT MOUNTED WALLS AND FLOOR AS INDICATED.

7 REMOVE AND REPLACE PORTION(S) OF CONCRETE SLAB AS REQUIRED TO INSTALL OR REMOVE

EQUIPMENT AND/OR MATERIAL BELOW. COORDINATE WITH MEP DRAWINGS.

8 WHERE A NOTE IS SHOWN FOR ONE CONDITION, IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS.

9 WHERE MATERIALS ARE REMOVED OR DEMOLISHED, INFIL OR PATCH TO MATCH EXISTING ADJACENT

FINISH AND/OR STRUCTURAL MEMBER.

10 ALL RENOVATION WORK IS TO BE PERFORMED IN COMPLIANCE WITH IFC 2012, SECTION 3304.2 WASTE

DISPOSAL. ALL COMBUSTIBLE DEBRIS AND WASTE MATERIAL SHALL BE REMOVED FROM THE

BUILDING AT THE END OF EACH SHIFT OF WORK.

DEMOLITION LEGEND

1/8" = 1'-0"D2.03

DEMOLITION - ROOF PLAN1

DEMOLITION NOTE LEGEND

1ST CHARACTER:

CORE MATERIAL CODE, PER WALL MATERIAL

CODE AND SIZE LEGEND

NOTE: "EX" REFERS TO EXISTING SUBSTRATE

2ND CHARACTER:

NOMINAL CORE SIZE, PER WALL MATERIAL

CODE AND SIZE LEGEND

4TH CHARACTER:

HEAD CONDITION PER NOTES

DESIGNATED WITH LOWER CASE LETTER

3RD CHARACTER:

MODIFIER PER SCHEDULE

DESIGNATED WITH UPPER CASE LETTER

FIRE RATING DESIGNATION:

-- = NO RATING

S=SMOKE

1= 1 HOUR RATING

2= 2 HR RATING

3= 3 HR RATING

4= 4 HR RATING

SOUND TRANSMISSION CLASS (STC) RATING:

-- = NO RATING

A= STC 40

B= STC 50

C= STC 60

MODIFIER

MARK DESCRIPTION

A. 5/8" GYPSUM WALL BOARD ONE SIDE OF PARTITION.

B. 5/8" GYPSUM WALL BOARD BOTH SIDES OF PARTITION.

C. MULTI LAYER GYPSUM BOARD PER FIRE RATING ASSEMBLY.

D. TILE ON 5/8" CEMENT BOARD ONE SIDE OF PARTITION, 5/8" GYPSUM ON OPP. SIDE.

E. TILE ON 5/8" CEMENT BOARD, BOTH SIDES OF PARTITION.

F. TILE ON 5/8" CEMENT BOARD ONE SIDE OF PARTION, NO FINISH ON OPP. SIDE.

G. RESERVED.

H. RESERVED.

I. 5/8" GYPSUM WALL BOARD ONE SIDE OF PARTITION, PROVIDE SOUND ATTENUATION.

J. 5/8" GYPSUM WALL BOARD BOTH SIDES OF PARTITION, PROVIDE SOUND

ATTENUATION.

K. MULTI LAYER GYPSUM BOARD PER FIRE RATING ASSEMBLY, WITH SOUND

ATTENUATION.

L. TILE ON 5/8" CEMENT BOARD ONE SIDE OF PARTITION, 5/8" GYPSUM WALL BOARD ON

OPP. SIDE. PROVIDE SOUND ATTENUATION.

M. TILE ON 5/8" CEMENT BOARD, BITH SIDES OF PARTITION. PROVIDE SOUND ATTENUATION.

N. TILE ON 5/8" CEMENT BOARD, ONE SIDE OF PARTION, NO FINISH ON OPP. SIDE. PROVIDE

SOUND ATTENUATION.

O. RESERVED.

P. RESERVED.

Q. LAMINATED TILE ONE SIDE.

R. LAMINATED TILE EACH SIDE.

S. RESERVED.

T. RESERVED.

U. 5/8" GYPSUM BOARD EACH SIDE, PROVIDE SHEATHING PER STRUCTURAL.

V. SUBSTITUTE SINGLE LAYER OF GYPSUM BOARD WITH (2) 1/4" LAYERS OF GYPSUM

BOARD AT CURVE.

W. RESERVED.

X. RESERVED.

Y. RESERVED.

Z. RESERVED.

AA. RESERVED.

BB. RESERVED.

XX.X.X

X X

09 22 16NON-STRUCTURAL METAL FRAMING

09 29 00.H6

THERMAL INSULATION (SOUND

ATTENUATION)

M6

FINISH/MODIFIER PER WALL TAG

M4

M3

M2

M8

WHERE SCHEDULED PER

WALL TAG

@ 16" O.C. U.N.O.

2 HR

UL DES

#U419 W/ 2

LAYERS

EA SIDE

M1

M10

M12

1. UL ASSEMBLY LISTINGS AS SHOWN ARE PROVIDED FOR CONVENIENCE ONLY. REFER TO APPROPRIATE UL

OR GA PUBLICATIONS FOR COMPLETE LISTINGS.

2. COGDELL MENDRALA ARCHITECTS, PC IS NOT RESPONSIBLE FOR ANY ADDITIONS OR OMISSIONS TO

ASSEMBLIES LISTED IN THIS DOCUMENT.

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

A0.02

INTERIOR

CONSTRUCTION

SYSTEMS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

KEYNOTE LEGEND - BY SHEET

NO. NOTE

09 22 16 NON-STRUCTURAL METAL FRAMING

09 29 00.H6 THERMAL INSULATION (SOUND ATTENUATION)

GENERAL WALL TYPE NOTES

1 THE CONSTRUCTION SUBSYSTEMS AND PARTITION TYPES SHOWN INDICATE THE GENERAL

CONSTRUCTION FEATURES OF THE MAJORITY OF THE CONSTRUCTION SYSTEMS TO BE PROVIDED. THEY

ARE NOT INTENDED TO REPRESENT A COMPLETE LISTING OF SYSTEMS REQUIRED AND DO NOT

NECESSARILY INDICATE ALL OF THE CONSTRUCTION REQUIREMENTS TO BE PROVIDED BY THE

CONTRACT DOCUMENTS

2 REFERENCE FOR FIRE RESISTANCE AND SOUND RATINGS:

CONCRETE MASONRY HANDBOOK, SOUND CONTROL GYPSUM

ASSOCIATION, FIRE RESISTANCE DESIGN MANUAL, ELEVENTH EDITION.

NCMA: NATIONAL CONCRETE MASONRY ASSOCIATION,TEK NOTES.

SA: SHINER AND ASSOCIATES.

UL: UNDERWRITERS LABORATORIES, INC., FIRE RESISTANCE

3 REFER TO PLANS AND SECTIONS FOR CONSTRUCTION SYSTEMS, AND FOR LOCATIONS AND REQUIRED FIRE RATINGS OF THE RATED SYSTEMS. HORIZONTAL RATINGS SHALL EQUAL THAT SHOWN FOR THE

WALLS ON THE FLOOR PLANS.

4 PROVIDE SEALANT AT PERIMETER OF ALL SMOKE RESISTIVE PARTITIONS AND AT ALL PARTITIONS PENETRATIONS. PROVIDE ACOUSTICAL SEALANT AT PERIMETER OF ALL SOUND RATED PARTITIONS AND AT ALL PARTITION PENETRATIONS. IF PARTITIONS IS FIRE RATED, PROVIDE UL LABELED FIRESTOPPING IN PLACE OF ACOUSTICAL SEALANT. AT PARTITIONS THAT ARE SOUND AND FIRE RATED, PROVIDE ACOUSTICAL SEALANT AT PARTITION PENETRATIONS THAT DO NOT REQUIRE FIRESTOPPING (EXAMPLE:

DUCT PENETRATIONS WITH FIRE DAMPERS)

5 RATED AND SMOKE RESISTIVE INTERIOR PARTITIONS SHALL EXTEND TO UNDERSIDE OF DECK, PARTITIONS ENCLOSING RESTROOMS & CLASSROOMS SHALL EXTEND TO UNDERSIDE OF DECK, UNLESS

NOTED OTHERWISE; NON-RATED INTERIOR PARTITIONS SHALL EXTEND TO 4" MINIMUM ABOVE ANY ADJACENT CEILING, UNLESS NOTED OTHERWISE. SMOKE RESISTIVE PARTITIONS MAY HAVE GYP BD ON ONE SIDE ONLY FROM 4" MIN ABOVE ANY ADJACENT CEILING TO THE DECK ABOVE, UNLESS NOTED

OTHERWISE..

6 WHERE METAL/WOOD PARTITION IS INDICATED TO BE FIRE RATED, PROVIDE MANUFACTURER'S

PROPRIETARY GYPSUM BOARD (MEETING THE DESIGNATED FIRE REFERENCE LISTED). RATED

PARTITION TO MEET CONSTRUCTION REQUIREMENTS OF RATING REFERENCE LISTED.

7 PROVIDE DEFLECTION TRACK AT HEAD OF ALL METAL STUD PARTITIONS ATTACHED TO STRUCTURE

ABOVE.

8 AT UNRATED STUD PARTITIONS NOTED TO EXTEND TO DECK, WHERE A GYPSUM BOARD WALL FINISH ABUTS A GYPSUM BOARD CEILING FINISH, THE WALL FINISH IS NOT REQUIRED TO EXTEND BEYOND THE CEILING. AT PARTITIONS WITH INSULATION, INSTALL INSULATION NETTING ON UNFINISHED FACE OF

STUD ABOVE CEILING.

INTERIOR PARTITION TAG LEGEND

INTERIOR METAL STUD PARTITIONS

FIRE RATING REFERENCETAGDESCRIPTION

UL ASSEMBLY NOTES

A4.01

CORR.

FINANCIAL AID OFFICE

133A

WORK ROOM

EQUIPMENT

CREDIT UNION

101A

CORR.

LOBBY

SECRETARIAL OFFICE

VENDING

ENTRY

A4.01

GALLERY

DEAN'S OFFICE

VESTIBULE

CORR.

PRES. SECURITY & RECEPTION

CORR.

CONFERENCE ROOM

OPEN TO BELOW

DATA

EXIT PATH THROUGH LOBBY TO EXIT DOORS SHALL BE KEPT CLEAR AT

ALL TIMES. DO NOT BLOCK WITH EQUIPMENT OR CONSTRUCTION DEBRIS.

EXIT PATH AT STAIR SHALL BE KEPT CLEAR AT ALL TIMES. DO NOT BLOCK

WITH EQUIPMENT OR CONSTRUCTION DEBRIS.

NEW DOOR OPENING SHALL BE LOCATED TO AVOID DISTURBING

EXISTING FIRE ALARM DEVICE. OTHER WALL-MOUNTED ITEMS SHALL BE

REMOVED AND REINSTALLED IF THEIR EXISTING LOCATION IS IN

CONFLICT WITH NEW DOOR OPENING.

REPAIR ADJACENT WALL SURFACES AT NEW FRAME.

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

A2.01

COMPOSITE

FLOOR PLANS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

1/8" = 1'-0"A2.01

COMPOSITE FIRST FLOOR PLAN1

1/8" = 1'-0"A2.01

COMPOSITE SECOND FLOOR PLAN2

KEYNOTE LEGEND - BY SHEET

NO. NOTE

GENERAL PLAN NOTES

1 REFER TO LIFE SAFETY PLANS FOR LOCATIONS OF WALLS AND PARTITIONS PROVIDING FIRE OR

SMOKE RESISTIVE SEPARATION.

2 REFER TO SHEET G0.02 FOR GENERAL PROJECT NOTES, GRAPHIC SYMBOLS, AND EQUIPMENT

MOUNTING DIMENSIONS.

3 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS, UNLESS NOTED OTHERWISE.

4 WHERE MATERIALS ARE REMOVE OR DEMOLISHED, INFILL AND/OR PATCH TO MATCH EXISTING

ADJACENT FINISH AND/OR STRUCTURAL MEMBER.

5 OFFSET DOOR FRAMES IN STUD PARTITIONS 4" FROM ADJACENT WALL UNLESS INDICATED

OTHERWISE.

6 NEW FINISHES SHALL BE INSTALLED FLUSH WITH EXISTING FINISHES.

7 INSTALL WOOD BLOCKING BEHIND ALL WALL-MOUNTED EQUIPMENT AT STUD PARTITIONS AND

FURRING.

PLAN NOTES

NEW CAPS ON EXISTING CURBS. SEE DETAIL 2/A2.02. FIELD MEASURE EXISTING CURBS PRIOR

TO SHOP DRAWINGS. PROVIDE DIMENSIONED SHOP DRAWINGS INCLUDING PLAN, SECTION

AND MOUNTING/FASTENERS.

PROVIDE 16 GA. MIN. KYNAR COATED BRAKE METAL.

FORM CAP TO A CENTER PEAK FOR POSITIVE DRAINAGE.

GYPSUM SHEATHING: GLASS-MAT GYPSUM SHEATHING, ASTM C 1177/1177M. THICKNESS: 5/8".

ACCEPTABLE PRODUCTS: GLASROC BY CERTAINTEED CORP., SECUREROCK BY USG, GOLD

BOND EXP EXTENDED EXPOSURE SHEATHING BY NATIONAL GYPSUM CO.

MINERAL-WOOL INSULATION: ASTM C612, MINERAL FIBER BLOCK AND BOARD THERMAL

INSULATION, TYPES IA, IB, II, III, IVA, IVB.

BASIS OF DESIGN: THERMAFIBER RAINBARRIER DARK BY OWENS CORNING.

PRODUCTS MEETING OR EXCEEDING THE PROPERTIES OF THE BASIS OF DESIGN PRODUCT

BY THE FOLLOWING MANUFACTURERS ARE ACCEPTABLE: THERMAFIBER INC., FIBREX

INSULATIONS INC., KNAUF.

SIZE AND THICKNESS AS NEEDED TO FILL CAVITY.

EXTERIOR NON-LOAD-BEARING METAL STUDS. AISI S100, AISI S240.

FASTENERS:

ANCHOR BOLTS: ASTM F1554, GRADE 36, THREADED CARBON-STEEL HEX-HEADED BOLTS,

CARBON-STEEL NUTS. ZINC COATED BY HOT-DIP PROCESS (ASTM A153/A153M, CLASS C).

MECHANICAL FASTENERS: ASTM C1513, CORROSION-RESISTANT-COATED, SELF-DRILLING,

SELF-TAPPING, STEEL DRILL SCREWS.

4" M

IN

BRAKE METAL CAP

MINERAL WOOL INSULATION

2-1/2" x 2-1/2" METAL STUDS AT

PERIMETER OF OPENING AND AT

16" O.C. ONE WAY.

5/8" TYPE X GYPSUM SHEATHING.

OVERLAP OPENING 1" MIN. SEALANT

AROUND PERIMETER OF SHEATHING.

07 84 43JOINT FIRESTOPPING

AT PERIMETER OF

SHEATHING.

EXISTING VENT/EF CURB.

DO NOT DISTURB CURB, FLASHING

OR ROOF SYSTEM.

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

A2.02

ROOF PLAN

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

KEYNOTE LEGEND - BY SHEET

NO. NOTE

07 84 43 JOINT FIRESTOPPING

GENERAL ROOF PLAN NOTES

1 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS, UNLESS NOTED OTHERWISE.

1/8" = 1'-0"A2.02

ROOF PLAN1

ROOF PLAN & DETAIL NOTES

1" = 1'-0"A2.02

INFILL AT CURBS2

A5.01

CORR.

FINANCIAL AID OFFICE

133A

WORK ROOM

EQUIPMENT

CREDIT UNION

101A

CORR.

LOBBY

VENDING

ENTRY

TEMPORARY

CONSTRUCTION AND

EQUIPMENT

STAGING AREA

623 4

3 4

M4.C

2 --

A5.01

GALLERY

DEAN'S OFFICE

CORR.

PRES. SECURITY & RECEPTION

CORR.

OPEN TO BELOW

PAINT ELEVATOR CASED OPENING HM FRAME & EXT. DOOR.

FILL HOLES AND VOIDS AT PENETRATIONS IN EXISTING 2-HOUR EQUIPMENT ROOM WALLS. COMPLY

WITH RATED CONSTRUCTION REQUIREMENTS.

PATCH WALL FLUSH WHERE WALL-MOUNTED ITEMS HAVE BEEN REMOVED. PAINT WALL, CORNER

TO CORNER. MATCH EXISTING WALL PAINT IN COLOR AND SHEEN.

NEW WALL BASE THIS WALL, CORNER TO CORNER. MATCH EXISTING ADJACENT WALL BASE IN

STYLE, HEIGHT AND COLOR.

EXISTING BRACKET-MOUNTED FIRE EXTINGUISHER TO REMAIN.

REPLACE CEILING GRID AND PANELS DAMAGED DURING WORK. MATCH EXISTING GRID AND PANELS.

PROVIDE NEW HM 90-MIN RATED FRAME. REINSTALL 90-MIN DOOR. PROVIDE NEW HARDWARE. SEE

HARDWARE SET #1 THIS SHEET.

PAINT HM FRAME. MATCH ADJACENT DOOR FRAME COLOR AND SHEEN.

HM FRAME: MEET ANSISDI A250.8, ANSI/NFPA 80.

MANUFACTURERS: CECO DOOR PROCDUCTS, CURRIES COMPANY OR STEELCRAFT.

INTERIOR STANDARD-DUTY DOOR FRAME: FABRICATED FROM COLD-ROLLED STEEL SHEET

COMPLYING WITH ASTM A1008/A1008M. FABRICATE WITH MITERED CORNERS. MINIMUM 16 GA THICK

STEEL SHEET.

CONTRACTOR'S OPTION FOR CONSTRUCTION TYPE (KNOCKDOWN ETC).

SEAL AND COVER EDGES OF EXISTING PLYWOOD BACKER BOARDS WITH FIRE CAULK.

REINSTALL DEFIBULATOR AND OTHER WALL-MOUNTED ITEMS. COORDINATE FINAL LOCATION WITH

OWNER.

PROVIDE NEW RESILIENT TILE AT JOINT BETWEEN DISSIMILAR FLOORING. FASOLPLUS BY TOLI INTERNATIONAL, COLOR: 2040 (BLACK). COMPARABLE PRODUCTS BY ARMSTRONG FLOORING INC., SHAW CONTRACT, MOHAWK GROUP, OR TARKETT. PREP SUBSTRATE PER MANUFACTURER'S

INSTALLATION GUIDELINES.

TEMPORARY CONSTRUCTION EQUIPMENT STAGING AREA:

INSTALL TEMPORARY STAGING AREA PRIOR TO START OF CONSTRUCTION. WALLS OF STAGING

AREA TO BE SELF-SUPPORTING. DO NOT CONNECT OR FASTEN TO LOBBY WALLS OR FLOOR.

INSTALLATION AND REMOVAL OF TEMPORARY CONSTRUCTION FOR STAGING AREA AND FINISHES

PROTECTION SHALL NOT DAMAGE EXISTING LOBBY FINISHES. DAMAGED FINISHES WILL BE

REPLACED (TO MATCH) AT THE CONTRACTOR'S EXPENSE.

BOUNDARY SHOWN IS FULL EXTENT OF AREA TO BE USED. DO NOT EXCEED BOUNDARY. DO NOT

BLOCK EXIT PATH WITH EQUIPMENT, DEBRIS OR CONSTRUCTION MATERIALS. PROVIDE TEMPORARY

FLOOR COVERING PROTECTION IN STAGING AREA.

INSTALL NEW FIRE-RETARDENT PLYWOOD BACKER BOARD AS INDICATED ON ELECTRICAL SHEETS.

PROVIDE FIRE-RETARDENT TREATED BLOCKING IN WALL AS NEEDED.

PAINT ELEVATOR SHAFT WALLS, FLOOR TO CEILING. MATCH EXISTING PAINT IN COLOR AND SHEEN.

SEE SPECIFICATIONS FOR WORK AT/IN ELEVATOR.14

3 HINGE, FULL MORTISE FBB191NRP 5" x 4-1/2" US32D ST

1 STOREROOM LOCK 45H7D 14H LESS CORE 626 BE

1 PERMANENT CORE PROVIDE PERM CORE KEYED 626 BE

INTO EXISTING SYSTEM

1 SURFACE CLOSER HD8016 SDS SNDTPK80 689 BE

1 GASKETING S88BL LAR PE

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

A4.01

ENLARGED

ELEVATOR PLANS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

KEYNOTE LEGEND - BY SHEET

NO. NOTE

GENERAL ENLARGED PLAN NOTES

1 SEE SHEET LS1.01 FOR LOCATION OF WALLS AND PARTITIONS TO PROVIDE FIRE OR SMOKE

RESISTIVE SEPARATION.

2 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS, UNLESS NOTED OTHERWISE.

3/8" = 1'-0"A4.01

FIRST FLOOR ELEVATOR PLAN1

3/8" = 1'-0"A4.01

SECOND FLOOR ELEVATOR PLAN2

ENLARGED PLAN NOTES

REVISION SCHEDULE

HARDWARE SET #1

4'

0" M

A X

ELEVATOR CALL BUTTON

ELEVATOR HALL SIGNALS

4'

0" M

A X

FIRE SAFETY SIGNAGE

ELEVATOR CALL BUTTON

ELEVATOR HALL SIGNALS

5'

0" M

A X

5'

0"

M A

X

FLOOR DESIGNATION NUMBERS ON

BOTH SIDES OF DOOR JAMB

FLOOR DESIGNATION NUMBERS ON

BOTH SIDES OF DOOR JAMB

FIRST FLOOR ELEVATOR ENTRY

SECOND FLOOR ELEVATOR ENTRY

IN CASE OF

FIRE

ELEVATORS ARE OUT

OF SERVICE

USE EXIT STAIRS

FIRE SAFETY SIGNAGE

FLOOR DESIGNATIONS

2" M

IN

2" MIN.

4"

4"

1/ 2"

1/ 2"

1/ 2"

1'

2"

8 3/4"

BRAILLE IDENTIFICATION TYPICAL

517 EAST CONGRESS STREET

SAVANNAH, GEORGIA 31401

tel 912.234.6318 fax 912.236.8414 cogdellmendrala.com

SEAL

SHEET TITLE

PROJECT NO:

DRAWN BY:

DATE:

SCALE:

SHEET

KEY PLAN

CogdellMendralaArchitects

NOT FOR

CONSTRUCTIO

N

M.E.P. ENGINEERS

TRUE NORTH PROJECT NORTHSCALE

COPYRIGHT © 2025 COGDELL & MENDRALA ARCHITECTS, PC

100'50'0

OWNER NO:

METHOD ENGINEERING GROUP

1020 DRAYTON STREET, SUITE 101,

SAVANNAH, GA 31401

As indicated

/2

/2

:3 :4

P

M C

U s e rs

\j ja m e s \D o c u m e n ts

\2

C u ls o n

E le v a to r_

R

J J a m e s V

Y .r v t

A5.01

INTERIOR

ELEVATIONS

JMJ

MAY 2025

CONSTRUCTION

DOCUMENTS

COLSTON

ADMINISTRATION

BUILDING

ELEVATOR

REPLACEMENT

3219 COLLEGE ST.

SAVANNAH, GEORGIA

31404

SAVANNAH STATE UNIVERSITY

COLSTON ADMINISTRATION

BUILDING

SSUMRR2504

KEYNOTE LEGEND - BY SHEET

NO. NOTE

1/2" = 1'-0"A5.01

FIRST FLOOR ELEVATOR ENTRY1

1/2" = 1'-0"A5.01

SECOND FLOOR ELEVATOR ENTRANCE2

1/2" = 1'-0"A5.01

ELEVATOR DOOR JAMB3

SIGNAGE SCHEDULE

REVISION SCHEDULE

NO DATE DESCRIPTION

GENERAL INTERIOR ELEVATION NOTES

1 WHERE A NOTE/DETAIL IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE

CONDITIONS, UNLESS NOTED OTHERWISE.

2 INSTALL NEW ELEVATOR SIGNAL DEVICES (HALL CALL BUTTONS, ETC) IN ORIGINAL DEVICE LOCATIONS.

B M D Ƨ

Ƨ

C3H3

CH4

CO2

CO

H2

H2S

HZG

NO2

HS

TC

TH

TS

T

H

O2

M

S

S

M

CHWS

CD

CDR

CWR

CWS

HWR

HWS

G

STM

(E)

CHWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE DRAINAGE

CONDENSATE RETURN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

NATURAL GAS

STEAM

R REFRIGERANT

2"

2"

4"

4"

PIPING SYMBOLS

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING PIPE TAG

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPING BEING DEMOLISHED

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

PIPE RISE

PIPE DROP

PIPE TEE REDUCING 45

DEGREE TEE

45 DEGREE TEE

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN

THIS SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE

USED IN THIS SET OF DRAWINGS.

PG PROPANE GAS

Room

INVERT: -105' - 1"

1/8" / 12" SLOPE

18"x12"

18"/12"

(E)

18"Ø

EXHAUST AIR

OUTSIDE AIR

RELIEF AIR

RETURN AIR

SUPPLY AIR

TRANSFER AIR

GRILLES, REGISTERS & DIFFUSERS TAG

CFM

THROW-150FPM/ 100FPM/ 50FPM

NECK SIZE / MODULE SIZE

EXISTING DUCT TAG

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

HVAC SYMBOLS

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT TAGS

ROUND DUCT SIZE TAG (DIAMETER)

LINEAR DIFFUSER TAG

CFM

TYPE (SEE SCHEDULE) NUMBER OF SLOTS /

ACTIVE SLOT LENGTH (PLENUM LENGTH) /

NECK SIZE

DUCT BEING DEMOLISHED

ELEVATION (CENTER OF FACE)

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

DROP

DROP

DROP

DROP

DROP

DROP

GREASE EXHAUST AIR

EQUIPMENT BY OTHERS

(REFER TO OTHER DISCIPLINE

FOR ADDITIONAL INFORMATION)

EXISTING EQUIPMENT

TO REMAIN

COMBUSTION AIR

CONDITIONED OUTSIDE AIR

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

AD AREA DRAIN

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

ALT ALTERNATE

AP ACCESS PANEL

ARCH ARCHITECT/ARCHITECTURAL

BFF BELOW FINISHED FLOOR

BLW BELOW

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CB CATCH BASIN

CFM CUBIC FEET PER MINUTE

CLG CEILING

CO CLEAN OUT

CW COLD WATER

D DEGREE

DB DRY BULB

DIA DIAMETER

DN DOWN

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

ELEC ELECTRICAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EXIST EXISTING

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FD/SD COMBINATION FIRE / SMOKE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FL FLOOR

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

GAL GALLON

GF GAS-FIRED

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GW GREASE WASTE

HB HOSE BIB

HP HORSE POWER

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INV INVERT

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LV LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

RH RELATIVE HUMIDITY

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SF SQUARE FOOT

SD SMOKE DAMPER

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

STM STEAM

T THERMOSTAT

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VENT VENTILATION

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

48"x2 1/2"

SLB3 400

10" / 24x24

SD3 300

12" / ---

SD9 400

LINEAR BAR GRILLE

LINEAR SLOT

DIFFUSER

PERFORATED

DIFFUSER WITH

DEFLECTORS

ROUND DIFFUSER

WITH ADJUSTABLE

PATTERNS

LOUVERED DOUBLE

DEFLECTION GRILLE 12"x10"

SG5 500

TYPE (SEE SCHEDULE)

10" / 24x24 H-5/7/1422

SD1 400

3-CONE DIFFUSER

THROW PATTERN

MAX NC RATING

1 / 4' - 0" / 8"

LSD1 200

8' - 0"AFF

1 / 4' - 0" / 8"

LSD1 200

6' - 0"

1 / 4' - 0" / 8"

LSD1 200

SECTION TOTAL TRACK LENGTH

12"x10" / 24x12

RG11 500

LOUVERED GRILLE

22"x22" / 24x24

RG2 500

EGGCRATE RETURN

GRILLE

BOTTOM OF EQUIPMENT

ELEVATION

OPERATING WEIGHT

NOT INCLUDING CURB

FUEL INPUT

GAS PIPE FLOW

NOMINAL COOLING

CAPACITY

DATA DEVICE TAGS

CAP

PLUG

GWR

GWS

GEOTHERMAL WATER RETURN

GEOTHERMAL WATER SUPPLY

EXISTING RELOCATED

EQUIPMENTAC AIR CONDITIONOR

AH AIR HANDLER

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CH CHILLER

CT COOLING TOWER

CUH CABINET UNIT HEATER

CHWP CHILLED WATER PUMP

DAH DUCTLESS AIR HANDLER

DHP DUCTLESS HEAT PUMP

DOAS DEDICATED OUTDOOR AIR SYSTEM

EF EXHAUST FAN

EH ELECTRIC HEATER

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

FCU FAN COIL UNIT

FF FLY FAN

GRV GRAVITY ROOF VENTILATOR

HP HEAT PUMP

HWP HEATING WATER PUMP

HRC HEAT RECOVERY CONTROLLER

KEF KITCHEN EXHAUST FAN

MAU MAKEUP AIR UNIT

RAC ROOFTOP AIR CONDITIONER

RHP ROOFTOP HEAT PUMP

SF SUPPLY FAN

TF TRANSFER FAN

UH UNIT HEATER

VAH VRF AIR HANDLER

VHP VRF HEAT PUMP

VRF VARIABLE REFRIGERANT FLOW

EQUIPMENT ABBREVIATIONS

DAMPER TAGS

MOTORIZED DAMPER

BACKDRAFT DAMPER

MANUAL BALANCING DAMPER

12"x12" S/A

18"x18" S/A

18"x18" S-O/A

18"x18" O/A

18"x18" R/A

18"x18" T/A

18"x18" E/A

18"x18" L/A

18"x18" GE/A

6"Ø C/A

COMB. FIRE/SMOKE DAMPER

FIRE DAMPER

SMOKE DAMPER

12"x12" S/A

EQUIPMENT ID SYMBOL

C3H3 DETECTOR

CH4 DETECTOR

CO2 DETECTOR

CO DETECTOR

H2 DETECTOR

H2S DETECTOR

HAZARDOUS GAS DETECTOR

NO2 DETECTOR

HUMIDITY SENSOR

TEMPERATURE & CO2 SENSOR

TEMPERATURE & HUMIDITY SENSOR

TEMPERATURE SENSOR

THERMOSTAT

HUMIDISTAT

O2 DETECTOR

RAC-XX

PIPE ACCESSORY TAGS

2" CHECK

2" BALANCING

BALANCING VALVE

2" CIRC

CIRCUIT SETTER

2" GATE

GATE VALVE

2" PRV

PRESS REDUCING

2" STRAINER

2" M-CNTRL

ELEC. CONTROL

2" SHUTOFF

BALL VALVE

1" GAS-CNTRL

EMERG. GAS SHUTOFF

(ALTERNATE CHECK

VALVE SYMBOL)

CHECK VALVE

1" REG

PRESS REGULATOR

1" GAS COCK

GAS SHUTOFF COCK

1" PLUG

PLUG VALVE

2" BUTTERFLY

BUTTERFLY VALVE

2" GLOBE

GLOBE VALVE

2" LOCKED

LOCK SHIELD VALVE

4" 3-WAY CNTRL

3-WAY ELEC. CONTROL

2" QUICK

QUICK OPENING

VAV-XX

10' - 0"

VAH-XX

590 lb

RTU-XX

4.0 ton

RTU-XX

115 CFH

RTU-XX

CONCEALED DUCTED

ROOFTOP UNIT

(R)VAV-XX

DOUBLE WALL SPIRAL DUCT

EXTERIOR DUCT

LINED DUCT

FABRIC DUCT

EXHAUST GAS FLUE6"Ø FLUE

(E)VAH-XX

GENERAL PROVISIONS

IMPOSED REGULATIONS: APPLICABLE PROVISIONS OF THE STATE AND LOCAL CODES AND OF THE FOLLOWING CODES AND…