This document contains details of a federal solicitation and related technical file. The solicitation number 36C25223B0010 is for replacing air handling units in Building 5 at the Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 facility. The technical file S02 - Drawings Part 2.pdf provides supplementary drawings for the project, which involves replacing existing air handling units to service Building 5. Responses to the solicitation are due on or before the unspecified date. The solicitation is for a firm-fixed-price contract to supply the necessary labor, materials, equipment, and supervision to remove and replace the building's air handling units.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--695-22-107 Replace Building 5 AHUs, newest first.
File Type Posted
S06 - 695-22-107 Amend 0006 Questions 02.27.23.pdf PDF
36C25223B0010 0006.docx DOCX document
36C25223B0010 0005.docx DOCX document
S06 - 695-22-107 Amend 0005 Questions 02.24.23.pdf PDF
Attachment 3B - ACM Report Bldg. 5 Basement.pdf PDF
S06 - 695-22-107 Amend 0004 Questions 02.21.23.pdf PDF
36C25223B0010 0004.docx DOCX document
Attachment 4 - Bldg. 5 Tab Report.pdf PDF
Attachment 3A - ACM Report Bldg. 5 MERs.pdf PDF
Attachment 2G - VA Temp AC Unit Photo 7.pdf PDF
Attachment 2F - VA Temp AC Unit Photo 6.pdf PDF
Attachment 2E - VA Temp AC Unit Photo 5.pdf PDF
Attachment 2A - VA Temp AC Unit Photo 1.pdf PDF
Attachment 1 - VA Temp AC Unit Cutsheets and O_M.pdf PDF
S06 - 695-22-107 Amend 0004 Specifications.pdf PDF
Attachment 2D - VA Temp AC Unit Photo 4.pdf PDF
Attachment 2C - VA Temp AC Unit Photo 3.pdf PDF
Attachment 2B - VA Temp AC Unit Photo 2.pdf PDF
36C25223B0010 0003.docx DOCX document
36C25223B0010 0002.docx DOCX document
36C25223B0010 0001.docx DOCX document
S06 - Site Visit Attendance Sheet_695-22-107 01.11.23.pdf PDF
S02 - Wage Determination_11_11_22.pdf PDF
S02 - HVAC_BAS_Controls_SingleSourceJustification_MPT-SAT_SIGNED.pdf PDF
S02 - Drawings Part 3.pdf PDF
S02 - Drawings Part 1.pdf PDF
S02 - Firestop_SingleSourceJustification_MPT-SAT_SIGNED.pdf PDF
S02 - Specifications.pdf PDF
36C25223B0010.docx DOCX document
S02 - Drawings Part 4.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL

ROOM

OPEN OFFICES

WORKERS

COMP

OFFICE

CONFERENCE

COPY

RM

OFFICE

5-2-002

IT

UNISEX

TLT

207A

UNISEX

TLT

207B

KITCH

204A

UP

ST-2-05

STAIR

ST-2-04

STAIR

ST-2-03

STAIR

PORCH

213 PORCH

ELEVATOR

2-01

ST-2-07

VESTIBULE

EMPLOYEE

BENEFITS

5-1-SH-01

SHAFT

ROOF

SLOPE

UP

UPDN

DN

DF

XFEB

"NO EXIT" SIGN

ON DOOR

CAPACITYCLR

EXIT

33" 165

CAPACITYCLR

EXIT

33" 165

TRAVEL DISTANCE: 83'-4"

TRAVEL DISTANCE: 88'-2"

T R

A V

E L D

IS

T

XFEB

R

S

T U

V

XFEB

W

X

EVACUATION

PLAN

Q PB

1 2 3 4

A

C

EXIT ACCESS TRAVEL

(per NFPA 101, TABLE 39.26.2)

# OF MEANS OF

EGREES REQUIRED

(per NFPA 101, CHAPTER 7)

300'-00" MAXIMUM DISTANCE

(W/SPRINKLERED)

2 REQUIRED

OCCUPANT LOAD

(per NFPA 101, TABLE 7.3.1.2)

OCC. 3 = 5,184 GSF/150 = 35 PPL

OCC. 2 = 5,488 GSF/150 = 37 PPL

OCC. 1 = 5,608 GSF/150 = 38 PPL

OCC. B = 5,353 GSF/150 = 36 PPL

TOTAL OCCUPANCY = 146 PPL

GROSS BUILDING AREA

(OUTSIDE FACE WALLS)

LEVEL 3 - 5,184 SF

LEVEL 1 - 5,608 SF

REQUIRED # OF EXITS

(per NFPA 101, CHAPTER 7)

2 EXITS REQUIRED IF UNDER

49 TOTAL OCCUPANTS

# OF MEANS OF

EGRESS PROVIDED

2 MEANS OF EGRESS (EXISTING)

EGRESS INFORMATION

LEVEL 2 - 5,488 SF

BASEMENT - 5,353 SF

EXITS / EGRESS

ENCLOSURE (per NFPA

101, TABLE 7.1.3.2)

1 HR RATED ENCLOSURE

(EXISTING)

2 HR RATED ENCLOSURE

(EXISTING)

- 3 FLOORS OR FEWER

- 4 FLOORS

EGRESS PATH

EGRESS IDENTIFICATION

EXISTING FIRE EXTINGUISHER BRACKET

EXISTING FIRE EXTINGUISHER CABINET

EXISTING FDC

EXISTING AED CABINET

CONTROLLED ACCESS - ALWAYS

UNLOCKED IN DIRECTION OF EGRESS

EXIT SIGN

PHOTO REFERENCE - LETTER AND

DIRECTION

CA

XFEB

XFEC

FDC

XAED

CAPACITYCLR

EXTERIOR

EXIT

XX" ###

EXIT

IDENTIFICATION

EGRESS CLEAR

WIDTH

EGRESS

CAPACITY

K

ACCNT

ACCNT OFFICE

ACCNT MGR

OFFICE 308

KITCHEN

OFFICE

BUDGET OFFICE

OPEN OFFICE

302AEC

ELEC

CONFERENCE

DEPUTY

FINANCIAL MGR

OFFICE

MGMT ANALYST

OFFICE

OFFICE

IT

TLT

STAIR

3-04

STAIR

3-03

STAIR

3-05

3-01

ELEVATOR

PORCH

ROOF

SLOPE

ROOF

SLOPE

DF

DN

DN

XFEB

"NOT AN EXIT"

SIGN ON DOOR

CAPACITYCLR

EXIT

33" 165

CAPACITYCLR

EXIT

33" 165

TRAVEL DISTANCE: 102'-0"

TRAVEL DISTANCE: 88'-7"

BB

CC/NN

HH

JJ

XFEB

GG

EVACUATION PLAN

"NOT AN EXIT" SIGN ON

DOOR. DOOR ALSO

BOARDED ON THE

EXTERIOR AND BLOCKED

WITH A BAR ON THE

INTERIOR SIDE.

LL

EXISTING

GUARDRAIL

XFEB

OO

EVACUATION

PLAN

MM

XFEB

EVACUATION

PLAN

II

QQ

B

1 2 3 4

A

C

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2 /2

:5

:0

P M

C U s e rs

\d c o rd o n \D o c u m e n ts \R e v it l o c a l\ A

-3

M ilw a u k e e B

A

H U

R e p la c e m e n t_ d c o rd o n a c g

-p a

.c o m

.r v t

LS102

SECOND AND THIRD FLOOR LIFE

SAFETY PLANS

4 5DGC

REPLACE BUILDING 5 AHUS

CLEMENT J. ZABLOCKI VAMC

5000 WEST NATIONAL AVENUE

MILWAUKEE, WI 53295 NOVEMBER 23, 2022

100% CONSTRUCTION DOCUMENTS

695-22-10721-319-Q30

B5

HD

PROPOSED USE:

OWNED BY: FEDERAL GOVERNMENT

CODE ENFORCEMENT JURISDICTION: FEDERAL

APPLICABLE CODES:

GENERAL CODE INFORMATION:

RENOVATION (EXISTING BUILDING)

CONSTRUCTION TYPE:

PRIMARY OCCUPANCY:

PROJECT NAME:

PROJECT ADDRESS:

OWNER OR AGENT:

SPRINKLERED

2021 ENERGY CONSERVATION CODE

2021 INTERNATIONAL PLUMBING CODE

2021 INTERNATIONAL MECHANICAL CODE

2021 INTERNATIONAL FIRE CODE

OFFICE

2HH (PER NFPA 101)

BUSINESS

2020 NFPA 70 NATIONAL ELECTRIC CODE

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN CODE

2021 NFPA 101 LIFE SAFETY CODE

2017 PG 18-13 VA BARRIER FREE DESIGN STANDARDS

REPLACE BUILDING 5 AHUS

CLEMENT J. ZABLOCKI VAMC

5000 WEST NATIONAL AVENUE

MILWAUKEE, WI 53295

CLEMENT J. ZABLOCKI VAMC

CODE INFORMATION

NORTH

0 4 8 16

Scale: 1/8" = 1'-0"

EXISTING CONDITIONS - SECOND FLOOR LIFE SAFETY PLAN

LIFE SAFETY LEGEND

Scale: 1/8" = 1'-0"

EXISTING CONDITIONS - THIRD FLOOR LIFE SAFETY PLAN

NORTH

0 4 8 16

N

KEY PLAN

SCALE: NO SCALE

AREA OF WORK

SECOND FLOOR

THIRD FLOOR

P Q R

S T U

V W X

Y Z (LS101 - RM. ST-03) AA

BB CC (LS101 - RM. 117) DD (LS101 - RM. 5-1-CR-01)

THE INFORMATION CONTAINED IN THESE DRAWINGS

ARE NOT A VERIFIED LIFE SAFETY SURVEY NOR ARE

THEY TO BE USED AS OFFICIAL DOCUMENTATION IN

THE LIFE SAFETY NARRATIVE OF BUILDING 5.

A NON-DESTRUCTIVE VISUAL OBSERVATION OF

BUILDING 5 WAS PERFORMED ON 7/72022. THE

PHOTOGRAPHS ON THE LIFE SAFETY DRAWINGS ARE

THE BASIS FOR DESIGN ASSUMPTIONS CONTAINED

WITHIN THE DOCUMENT DRAWINGS.

WALL RATINGS SHOWN IN THESE PLANS ARE TO

SERVE AS THE BASIS OF DESIGN FOR ANY

REPLACEMENT, PATCHWORK OR PENETRATIONS FOR

FIRE RATED CONSTRUCTION REQUIRED TO

ADEQUATELY PERFORM THE SCOPE OF WORK.

EXISTING WALL RATINGS HAVE NOT BEEN VERIFIED.

WE NOTE THE PROBABLE LOCATIONS OF FIRE RATED

CONSTRUCTION BASED UPON PHOTOGRAPHS OF THE

EXISTING CONDITIONS. THE WALL RATINGS FOR

STAIRS AND SHAFTS DESIGNATE THE REQUIRED 2HR

RATING IN COMPLIANCE WITH NFPA 101, 2021 EDITION.

CONTRACTOR IS TO REPLACE, REPAIR, PATCH, AND

INSTALL PENETRATIONS IN ACCORDANCE WITH THE

FIRE RATED CONSTRUCTION DESIGNATED ON THESE

PLANS.

NO EVACUATION PLANS SHOWING EGRESS AND EXIT

FROM THE BUILDING WERE PRESENT ON THE WALLS

OF THE BUILDING 5.

PATHS OF TRAVEL ARE INTENDED TO FOLLOW THE

EXISTING EGRESS SIGNS AND SHOULD NOT BE

MODIFIED UNLESS IT IS REQUIRED TO DO SO DURING

CONSTRUCTION IN ORDER TO COMPLETE THE SCOPE

OF WORK.

CONTRACTOR IS TO NOTIFY THE COR AND ARCHITECT

IF ANY EXISTING EGRESS LIGHTS ARE REQUIRED TO

BE TEMPORARILY DISABLED DURING CONSTRUCTION.

TEMPORARY MODIFICATIONS TO THE PATH OF TRAVEL

ARE TO BE COMMUNICATED TO AND COORDINATED

WITH THE COR AND ARCHITECT.

ALL LIFE SAFETY CONDITIONS TEMPORARILY MODIFIED

DURING CONSTRUCTION WILL REVERT TO THEIR

ORIGINAL CONDITION ONCE THE WORK HAS BEEN

COMPLETED.

A SEPARATE PATH FOR REMOVAL OF CONSTRUCTION

WASTE WILL BE COORDINATED WITH THE COR AND

NOTATED ON LS103.

A SEPARATE PATH FOR THE REMOVAL OF ASBESTOS

AND OTHER HAZARDOUS MATERIALS WILL BE

COORDINATED WITH THE COR AND NOTATED ON

LS103.

FIG. 1 BELOW IS THE EMERGENCY PLAN USED

THROUGHOUT THE BUILDING. IT DOES NOT MEET

CURRENT LIFE SAFETY STANDARDS. PHOTO SHOWS

EXISTING CONDITIONS AND NOT TO BE TAKEN AS

CURRENT OR CORRECT EVACUATION PLAN.

FIG. 1 EXISTING EVACUATION PLAN

DocuSign Envelope ID: C7A11FCE-2DC0-4945-ADC2-185C2F86D091

11/22/2022

DN

UP

DN

DN

EXIT ACCESS TRAVEL

(per NFPA 101, TABLE 39.26.2)

# OF MEANS OF

EGREES REQUIRED

(per NFPA 101, CHAPTER 7)

300'-00" MAXIMUM DISTANCE

(W/SPRINKLERED)

2 REQUIRED

OCCUPANT LOAD

(per NFPA 101, TABLE 7.3.1.2)

OCC. 3 = 5,184 GSF/150 = 35 PPL

OCC. 2 = 5,488 GSF/150 = 37 PPL

OCC. 1 = 5,608 GSF/150 = 38 PPL

OCC. B = 5,353 GSF/150 = 36 PPL

TOTAL OCCUPANCY = 146 PPL

GROSS BUILDING AREA

(OUTSIDE FACE WALLS)

LEVEL 3 - 5,184 SF

LEVEL 1 - 5,608 SF

REQUIRED # OF EXITS

(per NFPA 101, CHAPTER 7)

2 EXITS REQUIRED IF UNDER

49 TOTAL OCCUPANTS

# OF MEANS OF

EGRESS PROVIDED

2 MEANS OF EGRESS (EXISTING)

EGRESS INFORMATION

LEVEL 2 - 5,488 SF

BASEMENT - 5,353 SF

EXITS / EGRESS

ENCLOSURE (per NFPA

101, TABLE 7.1.3.2)

1 HR RATED ENCLOSURE

(EXISTING)

2 HR RATED ENCLOSURE

(EXISTING)

- 3 FLOORS OR FEWER

- 4 FLOORS

EGRESS PATH

EGRESS IDENTIFICATION

EXISTING FIRE EXTINGUISHER BRACKET

EXISTING FIRE EXTINGUISHER CABINET

EXISTING FDC

EXISTING AED CABINET

CONTROLLED ACCESS - ALWAYS

UNLOCKED IN DIRECTION OF EGRESS

EXIT SIGN

PHOTO REFERENCE - LETTER AND

DIRECTION

CA

XFEB

XFEC

FDC

XAED

CAPACITYCLR

EXTERIOR

EXIT

XX" ###

EXIT

IDENTIFICATION

EGRESS CLEAR

WIDTH

EGRESS

CAPACITY

K

B06HC

HAC

B11

CORRIDOR

B04

AIR

COMPRESSOR/STORAGE

B14

EQUIP AND

POWER

B13EC

ELEC

B12

CORRIDOR

B08

PAYROLL

STORAGE

B10

ELEV LOBBY

B07

STORAGE

B13

ELEVATOR

EQUIP

B01

STORAGE

B02

COPY ROOM

(RICOH)

STAIR

B-04

STAIR

B-03

UP

P

IP

E T

U N

N E

L

TO TUNNEL

B-01

ELEVATOR

B03

DISTRIBUTION

D N

DN

WALKWAY

STAIRS

FDC

TEMPORARY

AHU LOCATION

ELECT. PANEL

FOR POWER

TO TEMP. AHU

TEMP.

TRANSF.

TEMP. PWR. TO GO

THRU EXIST WINDOW

UP

UPDN WALKWAY

LOADING

DOCK

MECHANICAL YARD

EXISTING TREE

CANOPY OUTLINE

LANDSCAPING

LANDSCAPING

EVACUATION PLAN

LANDSCAPING

EXISTING TREE

CANOPY OUTLINE

A-002

EXISTING HANDRAIL

EXISTING

BLDG. 7

EXISTING

PARKING

SPACE

TEMP. PWR. TO GO

THRU EXIST WALL

EXISTING TREE

CANOPY OUTLINE

B

1 2 3 4

A

C

MECHANICAL

ROOM 112

OFFICE

5-1-SH-01

SHAFT

OFFICE

STORAGE

109EC

ELEC

5-1-001

VESTIBULE

OFFICE

5-1-012

ELEV LOBBY

5-1-006

JAN

5-1-CR-01

CORRIDOR

5-1-010

RECEPTION

OFFICE

CONFERENCE

OFFICE

OFFICE

IT

5-1-CR-02

CORRIDOR

KITCHEN

OFFICE

5-1-007

TLT

CLOSET

CL

5-1-004

OFFICE

CL106

CL

ENTRY

UP

STAIR

ST-04

STAIR

ST-03

ST-05

STAIR

5-1-009

TOILET

5-1-EL-01

ELEV CAB

5-1-002

TOILET

DN

DN

DN

DN

UP

UPDN

DN DN

DN

T R

A V

E L D

IS

T

A N

C E

TRAVEL DISTANCE: 65'-9"

T R

A V

E L D

IS

T

A N

C E

XFEC

XAED

XFEB

B

1 2 3 4

A

C

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2 /2

:1

:2

A M

A

-3

M ilw a u k e e B

A

H U

R e p la c e m e n t_ d e ta c h e d .r v t

LS103

TEMPORARY CONSTRUCTION LIFE

SAFETY PLANS

5 5DGC

REPLACE BUILDING 5 AHUS

CLEMENT J. ZABLOCKI VAMC

5000 WEST NATIONAL AVENUE

MILWAUKEE, WI 53295 NOVEMBER 23, 2022

100% CONSTRUCTION DOCUMENTS

695-22-10721-319-Q30

B5

HD

PROPOSED USE:

OWNED BY: FEDERAL GOVERNMENT

CODE ENFORCEMENT JURISDICTION: FEDERAL

APPLICABLE CODES:

GENERAL CODE INFORMATION:

RENOVATION (EXISTING BUILDING)

CONSTRUCTION TYPE:

PRIMARY OCCUPANCY:

PROJECT NAME:

PROJECT ADDRESS:

OWNER OR AGENT:

SPRINKLERED

2021 ENERGY CONSERVATION CODE

2021 INTERNATIONAL PLUMBING CODE

2021 INTERNATIONAL MECHANICAL CODE

2021 INTERNATIONAL FIRE CODE

OFFICE

2HH (PER NFPA 101)

BUSINESS

2020 NFPA 70 NATIONAL ELECTRIC CODE

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN CODE

2021 NFPA 101 LIFE SAFETY CODE

2017 PG 18-13 VA BARRIER FREE DESIGN STANDARDS

REPLACE BUILDING 5 AHUS

CLEMENT J. ZABLOCKI VAMC

5000 WEST NATIONAL AVENUE

MILWAUKEE, WI 53295

CLEMENT J. ZABLOCKI VAMC

CODE INFORMATION

LIFE SAFETY LEGEND

Scale: 1/8" = 1'-0"

TEMPORARY CONDITIONS - BASEMENT FLOOR LIFE SAFETY PLAN

Scale: 1/8" = 1'-0"

TEMPORARY CONDITIONS - FIRST FLOOR LIFE SAFETY PLAN

NORTH

0 4 8 16

NORTH

0 4 8 16

N

KEY PLAN

SCALE: NO SCALE

AREA OF WORK

BASEMENT

FIRST FLOOR

EE (LS101 - RM. 101) FF GG

HH II JJ

KK LL MM

NN OO PP

QQ

DocuSign Envelope ID: C7A11FCE-2DC0-4945-ADC2-185C2F86D091

11/22/2022

File details come from the government source that posted it. Updated .