This document contains test results from a pre-construction commissioning of air handling units and related systems in Building 5 of the Milwaukee VA Medical Center. Key details include measurements of airflow and velocity taken at supply and return air diffusers and grilles throughout the building basement, first, second, and third floors served by air handling units AHU-1 and SF-1. Exhaust fan readings and outdoor air intake measurements were also recorded. Accompanying the test results is a federal contract opportunity to replace the existing Building 5 air handling units under solicitation number 36C25223B0010 for the Department of Veterans Affairs VISN 12.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--695-22-107 Replace Building 5 AHUs, newest first.
File Type Posted
36C25223B0010 0006.docx DOCX document
S06 - 695-22-107 Amend 0006 Questions 02.27.23.pdf PDF
S06 - 695-22-107 Amend 0005 Questions 02.24.23.pdf PDF
36C25223B0010 0005.docx DOCX document
Attachment 2D - VA Temp AC Unit Photo 4.pdf PDF
Attachment 2C - VA Temp AC Unit Photo 3.pdf PDF
Attachment 2B - VA Temp AC Unit Photo 2.pdf PDF
Attachment 2G - VA Temp AC Unit Photo 7.pdf PDF
Attachment 2F - VA Temp AC Unit Photo 6.pdf PDF
Attachment 2E - VA Temp AC Unit Photo 5.pdf PDF
Attachment 2A - VA Temp AC Unit Photo 1.pdf PDF
Attachment 1 - VA Temp AC Unit Cutsheets and O_M.pdf PDF
S06 - 695-22-107 Amend 0004 Specifications.pdf PDF
Attachment 3B - ACM Report Bldg. 5 Basement.pdf PDF
S06 - 695-22-107 Amend 0004 Questions 02.21.23.pdf PDF
36C25223B0010 0004.docx DOCX document
Attachment 3A - ACM Report Bldg. 5 MERs.pdf PDF
36C25223B0010 0003.docx DOCX document
36C25223B0010 0002.docx DOCX document
S06 - Site Visit Attendance Sheet_695-22-107 01.11.23.pdf PDF
36C25223B0010 0001.docx DOCX document
S02 - Drawings Part 4.pdf PDF
S02 - Firestop_SingleSourceJustification_MPT-SAT_SIGNED.pdf PDF
S02 - Specifications.pdf PDF
36C25223B0010.docx DOCX document
S02 - Drawings Part 2.pdf PDF
S02 - Wage Determination_11_11_22.pdf PDF
S02 - HVAC_BAS_Controls_SingleSourceJustification_MPT-SAT_SIGNED.pdf PDF
S02 - Drawings Part 3.pdf PDF
S02 - Drawings Part 1.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Diffuser and Grille Sheet

FPM VEL. C.F.M. FPM VEL. C.F.M. % DESIGN

AHU-1 N/A

1 B01 SG 21X21 1.00 452 N/A

2 B02 SG 24X6 0.56 201 113 N/A

3 B02 SG 24X6 0.56 188 105 N/A

4 B03 SG 18X18 1.00 27 N/A

5 B01 SG 18X18 1.00 23 N/A

6 101 SG 16X16 1.00 158 N/A

7 101 SG 16X16 1.00 59 N/A

8 101 SG 16X16 1.00 173 N/A

9 101 SG 12X12 1.00 150 N/A

10 101 SG 12X12 1.00 222 N/A

11 105 SG 12X12 1.00 58 N/A

1ST

OFFICE SG 12X12 1.00 101 N/A

13 SG (1) 0 N/A

14 101 SG 12X12 1.00 216 N/A

15 101 SG 12X12 1.00 123 N/A

16 101 SG 12X12 1.00 217 N/A

17 101 SG 12X12 1.00 145 N/A

18 101 SG 12X12 1.00 69 N/A

19 101 SG 12X12 1.00 112 N/A

20 SG (1) 0 N/A

21 101 SG 12X12 1.00 45 N/A

WOMEN

BATH SG 24X24 1.00 116 N/A

23 109 SG 24X24 1.00 257 N/A

24 101 SG 16X16 1.00 243 N/A

25 101 SG 16X16 1.00 54 N/A

26 101 SG 16X16 1.00 279 N/A

27 201 SG 24X24 1.00 124 N/A

28 201 SG 24X24 1.00 99 N/A

NOTES: *Testing done with all VAV's are 100% open 3770

(1) Grills not installed

FACTOR

TEST RESULTSTERMINAL

NUMBER

ROOM

NUMBER TYPE SIZE

REQUIRED

2ND FLOOR

1ST FLOOR

BASEMENT

JOB NAME: Milwaukee VA Building #5 SYSTEM NO: AHU-1 Supply (Pre- Testing) FAN NO:

ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295

BUILDING NO: #5

29 201 SG 24X24 1.00 105 N/A

30 202 SG 24X24 1.00 68 N/A

31 203 SG 24X24 1.00 65 N/A

32 203 SG 24X24 1.00 45 N/A

33 203 SG 24X24 1.00 54 N/A

34 201 SG 24X24 1.00 114 N/A

35 201 SG 24X24 1.00 138 N/A

36 204 SG 24X24 1.00 118 N/A

37 204 SG 6" 0 1.00 0 N/A

38 207B SG 24X24 1.00 49 N/A

39 207A SG 24X24 1.00 61 N/A

40 206 SG 24X24 1.00 131 N/A

41 206 SG 24X24 1.00 98 N/A

42 208 SG 24X24 1.00 75 N/A

43 206 SG 24X24 1.00 134 N/A

44 206 SG 24X24 1.00 123 N/A

45 206 SG 24X24 1.00 106 N/A

46 206 SG 24X24 1.00 98 N/A

47 206 SG 24X24 1.00 117 N/A

48 206 SG 24X24 1.00 102 N/A

49 303 SG 24X24 1.00 96 N/A

50 306 SG 24X24 1.00 155 N/A

51 305 SG 24X24 1.00 62 N/A

52 304 SG 24X24 1.00 190 N/A

53 301 SG 24X24 1.00 152 N/A

54 301 SG 24X24 1.00 143 N/A

55 301 SG 24X24 1.00 144 N/A

56 301 SG 24X24 1.00 119 N/A

57 301 SG 24X24 1.00 126 N/A

2ND FLOOR

3RD FLOOR

REQUIRED TEST RESULTS

NOTES: 2988

TERMINAL

NUMBER

ROOM

NUMBER

TYPE SIZE FACTOR

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295 SYSTEM NO: AHU-1 Supply (Pre- Testing)

FAN NO: BUILDING NO: #5

58 301 SG 24X24 1.00 134 N/A

59 301 SG 24X24 1.00 223 N/A

60 301 SG 24X24 1.00 262 N/A

61 307 SG 24X24 1.00 27 N/A

62 309 SG 24X24 1.00 59 N/A

63 308 SG 24X24 1.00 54 N/A

64 308 SG 24X24 1.00 43 N/A

65 308 SG 24X24 1.00 39 N/A

66 308 SG 24X24 1.00 63 N/A

67 308 SG 24X24 1.00 65 N/A

68 308 SG 24X24 1.00 53 N/A

69 308 SG 24X24 1.00 59 N/A

70 308 SG 24X24 1.00 50 N/A

71 308 SG 24X24 1.00 49 N/A

72 308 SG 24X24 1.00 47 N/A

73 308 SG 24X24 1.00 49 N/A

74 308 SG 24X24 1.00 56 N/A

75 308 SG 24X24 1.00 52 N/A

76 310 SG 24X24 1.00 59 N/A

ADDED

N/A

3RD

CORRIDOR SG 24X24 1.00 38 N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

3RD FLOOR

REQUIRED TEST RESULTS

NOTES: 1481

TERMINAL

NUMBER

ROOM

NUMBER

TYPE SIZE

FACTOR

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295 SYSTEM NO: AHU-1 Supply (Pre- Testing)

AHU-1

N/A

1 B02 RG 12X6 433 454 N/A

2 B01 RG 12X12 255 268 N/A

3 B01 RG 12X12 247 259 N/A

4 B03 RG 12X12 431 453 N/A

5 101 RG 12X12 279 293 N/A

6 101 RG 8X8 155 163 N/A

7 105 VELGRID 8X8 413 182 N/A

8 101 RG 12X12 229 240 N/A

9 101 RG 8X8 168 176 N/A

10 101 RG 8X8 179 188 N/A

11 101 RG 12X12 246 258 N/A

12 101 RG 12X12 246 258 N/A

13 101 RG 8X8 93 98 N/A

14 101 RG 12X12 291 306 N/A

15 RG (1)

N/A

16 109 RG 12X12 83 87 N/A

17 101 RG 12X12 546 573 N/A

1ST

OFFICE RG 12X12 263 276 N/A

19 204 RG 12X12 57 60 N/A

20 201 RG 12X12 0 0 N/A

21 201 RG 12X12 0 0 N/A

22 201 RG 12X12 0 0 N/A

23 202 RG 12X12 0 0 N/A

24 205 RG 12X12 0 0 N/A

25 205 RG 12X12 0 0 N/A

26 208 RG 12X12 0 0 N/A

27 206 RG 12X12 0 0 N/A

28 206 RG 12X12 31 33 N/A

29 206 RG 12X12 0 0 N/A

BASEMENT

1ST FLOOR

2ND FLOOR

REQUIRED TEST RESULTS

NOTES: (1) Grill not installed. 4627

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295 SYSTEM NO: AHU-1 Return (Pre- Testing)

FAN NO: BUILDING NO: #5

TERMINAL

NUMBER ROOM

NUMBER

TYPE SIZE

FACTOR

30 206 RG 12X12 1.05 0 0 N/A

31 206 RG 12X12 1.05 0 0 N/A

32 303 RG 14X10 1.05 152 160 N/A

33 306 RG 14X10 1.05 51 54 N/A

34 301 RG 24X24 1.05 176 185 N/A

35 301 RG 24X24 1.05 112 118 N/A

36 307 RG 14X10 1.05 101 106 N/A

37 301 RG 14X14 1.05 268 281 N/A

38 302 RG 12X12 1.05 98 103 N/A

39 308 RG 24X24 1.05 119 125 N/A

40 309 RG 14X10 1.05 52 55 N/A

41 308 RG 24X24 1.05 152 160 N/A

42 308 RG 14X10 1.05 100 105 N/A

43 308 RG 24X24 1.05 140 147 N/A

44 310 RG 14X10 1.05 45 47 N/A

45 301 RG 24X24 1.05 167 175 N/A

46 305 RG 14X10 1.05 107 112 N/A

47 304 RG 14X10 1.05 114 120 N/A

N/A

4A B02 RG 12X12 1.05 301 316 N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

2ND FLOOR

3RD FLOOR

REQUIRED TEST RESULTS

NOTES: 2359

TERMINAL

NUMBER

ROOM

NUMBER

TYPE SIZE

FACTOR

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295 SYSTEM NO: AHU-1 Return (Pre- Testing)

SUPPLY 1039 N/A

1 114 SG 24X6 1.00 96 N/A

2 114 SG 24X6 1.00 119 N/A

3 115 SG 24X6 1.00 163 N/A

4 122 SG 24X6 1.00 124 N/A

5 118 SG 24X6 1.00 136 N/A

6 119 SG 24X6 1.00 146 N/A

7 113 SG 24X6 1.00 60 N/A

8 113 SG 24X6 1.00 103 N/A

9 120 SG 24X6 1.00 92 N/A

N/A

N/A

N/A

RETURN 881 N/A

1 113 RG 24X24 1.05 513 539 N/A

2 114 RG 10X10 1.05 0 0 N/A

3 113 RG 24X24 1.05 326 342 N/A

4 119 RG 10X10 1.05 0 0 N/A

N/A

N/A

ADDED

N/A

117 117 RG 24X12 1.05 498 523 N/A

117 117 SG 24X24 1.00 972 N/A

N/A

N/A

N/A

N/A

N/A

N/A

REQUIRED TEST RESULTS

NOTES:

TERMINAL

NUMBER ROOM

NUMBER

TYPE SIZE

FACTOR

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295

SYSTEM NO: SF-1 FAN NO: BUILDING NO: #5

EF-38 174 N/A

1 207A EG 12X12 1.05 86 90 N/A

2 207B EG 12X12 1.05 80 84 N/A

3 311 EG 10X10 1.05 0 N/A

N/A

N/A

1ST FLOOR WOMAN'S EG 10X10 1.05 585 614 N/A

BATHROOM

(1)

N/A

N/A

5-EF-1

N/A

1 114 EG 14X14 122 128 N/A

2 TOILET EG 6X6 0 0 N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

REQUIRED TEST RESULTS

NOTES:

TERMINAL

NUMBER ROOM

NUMBER

TYPE SIZE

FACTOR

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295

SYSTEM NO: Exhausts (Pre-Testing) FAN NO: BUILDING NO: #5

EF-52

3RD

FLOOR PITOT 9X6 0.38 1779 676 N/A

N/A

N/A

N/A

EF-38

2ND

FLOOR

(4) 174 N/A

N/A

N/A

N/A

AHU-1

2ND

FLOOR

N/A

SUPPLY (2) 8239 N/A

RETURN BRANCH #1 PITOT 46X38 12.14 626 7600 N/A

BRANCH #2 PITOT 22X20 3.06 73 223 N/A

OA 416 N/A

EF-4

2ND

FLOOR

(1) (1) N/A

N/A

N/A

N/A

S-EF-1 1ST FLOOR 227 N/A

BRANCH #1 MECH PITOT 8X6 0.33 108 36 N/A

BRANCH #2 MECH PITOT 16X8 0.89 215 191 N/A

N/A

SF-1 1ST FLOOR N/A

SUPPLY MECH PITOT 24X12 2.00 529 1058 N/A

RETURN MECH PITOT 29X12 2.42 57 138 N/A

OA MECH 920 N/A

N/A

N/A

N/A

N/A

(3) Unit was at 100% OA during testing. (4) No good spot for total pitot. Used grill total.

BY SUBTRACTION

BY SUBTRACTION

SUPPLY STATIC +0.36

SUPPLY STATIC +0.08

REQUIRED TEST RESULTS

NOTES: (1) Fan won't run, could not test louvers.

(2) No good spot to get accurate louver reading. Unit supply branches to all 3 floors so not able to get total suppy pitot to subtract from total return potot. Used grill total for subtraction.

JOB NAME: Milwaukee VA Building #5 ADDRESS: 5000 W. National Avenue, Milwaukee, WI 53295

SYSTEM NO: Louver Readings FAN NO: BUILDING NO: #5

TERMINAL

NUMBER

ROOM

NUMBER

TYPE SIZE

FACTOR

File details come from the government source that posted it. Updated .