Attachment 3A - ACM Report Bldg. 5 MERs.pdf
PDF 9 KB Posted
- Attached to
- Z1DA--695-22-107 Replace Building 5 AHUs Federal contract opportunity
- Solicitation number
- 36C25223B0010
About this file
This analytical report details asbestos testing results for floor tiles and mastic samples collected from the first and third floors of Building 5 at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. Analysis was conducted using polarized light microscopy and dispersion staining to identify the presence of asbestos fibers. One sample of floor tile contained 1% chrysotile asbestos, while mastic samples contained either 10% or no detectable asbestos. The report provides results for five samples and identifies the laboratory and methodology used for testing in accordance with EPA standards.
The related federal contract opportunity is a solicitation to replace air handling units in Building 5 at the Clement J. Zablocki VA Medical Center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 is listed as the contracting agency. No further details are provided on response dates, award timing, pricing terms, or set-asides.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BULK ASBESTOS ANALYTICAL REPORT
Utilizing PLM and Dispersion Stain Technique
Clement J Zablocki VA Med Ctr
Facility Mgmt
5000 W. National Ave.
Milwaukee , WI 53295
Bldg 5 - MER 1st & 3rd FloorsJob ID:
15-Feb-22Received:
23-Feb-2022Analyzed:
211224Report #:Customer:
MICRO ANALYTICAL, INC.
11521 West North Avenue
Milwaukee, WI 53226
(414) 771-0855
Non-Asbestos
Fibrous
Components% AsbestosSample ID
Non-Fibrous
Components Color Texture
Floortile001 None Detected 1% Cellulose 99% Gray
Mastic001 II 10% Chrysotile 90% Black
Compact001 III None Detected 100% White
Compressed002 None Detected 60% Cellulose 40% Black
Mastic002 II None Detected 100% Gray
Test method: EPA/600/R-93/116 and EPA - Appendix E to Subpart E of 40 CFR Part 763. Quantitation is done by Calibrated Visual Estimation which has an accepted Relative Percent Difference of 35. This report may not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government. This test report relates only to the items tested and shall not be reproduced except in full, without the written approval of MICRO
ANALYTICAL, INC.
NVLAP Lab Code 101247-0
Analyzed By: Jon Yakish