RFB953400-01 - Drawings.pdf
PDF 24 MB Posted
- Attached to
- ATOD Will Call Ramp Replacement
- Solicitation number
- RFB953400-01
- Issued by
- Polk County, Iowa
About this file
This bidding document package is for the ATOD Will Call Ramp Replacement project issued by the Iowa Department of Administrative Services for a facility located at 1918 SE Hulsizer Road, Ankeny, Iowa 50021. The project involves the removal and replacement of an existing will call ramp, its accessories, and surrounding concrete infrastructure. The scope of work includes demolition of the existing ramp concrete slab, concrete panels, retaining walls, and guardrails; construction of a new vehicular ramp with a 1:10 (10 percent) slope designed to accommodate a 26,000-pound capacity box truck; new concrete landing and stoop areas with minimum cross-slopes of 1/4 inch per 12 inches for drainage; new reinforced concrete retaining walls and footings; new galvanized steel guardrails and handrails painted safety yellow; a new concrete threshold curb; concrete stairs with appropriate nosing bars; and restriping of lane and access aisle markings. The structural design is based on the 2015 International Building Code with specific design parameters including a ground snow load of 30 pounds per square foot, basic wind speed of 115 miles per hour, and seismic design category A. The project documents specify detailed foundation requirements, concrete reinforcement schedules, steel framing specifications, and a comprehensive special inspection program for structural elements.
The drawings include detailed footing plans, layout plans and elevations, ramp details, and specifications for concrete mix designs of 4,000 pounds per square inch for footings, slabs on grade, and walls. All reinforcing steel must conform to ASTM A615 Grade 60, and welding must follow AWS codes with certified welders. The documents establish specific requirements for shop drawing submittals, field verification of existing conditions, and coordination with mechanical and electrical systems. Exposed concrete surfaces require architectural-grade finishes, and all exposed steel permanently exposed to weather must be hot-dip galvanized. The general contractor is responsible for all temporary bracing systems, structural stability during construction, and maintaining Bay 8 in operation during construction activities. Special inspection requirements include continuous and periodic inspections of concrete reinforcement placement, steel welding and bolting operations, and concrete curing in accordance with Chapter 17 of the International Building Code. The construction sequencing must accommodate existing utility systems, including an 18-inch drain line approximately 8 feet 8 inches below finish floor and a storm sewer manhole that require protection during construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB953400-01 - Addendum #01.pdf | ||
| RFB953400-01 - Notice to Bidders.pdf | ||
| RFB953400-01 - Bid Form.pdf | ||
| RFB953400-01 - Project Manual.pdf | ||
| 1408146-event.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EARTH
PLYWOOD
GYPSUM WALLBOARD
CONCRETE BLOCK
CONCRETE
RIGID INSULATION
BATT INSULATION
DIMENSION LUMBER
WOOD
SAND & GRAVEL
EXPANSION JOINT
DOOR IDENTIFICATION
NOTE REFERENCE
ROOM IDENTIFICATION
BUILDING SECTION
WINDOW IDENTIFICATION
ROOM NAME
DETAIL NUMBER
DRAWING SHEET NUMBER
ELEVATION REFERENCE
ELEVATION NUMBER
DRAWING SHEET NUMBER
A1 A1.1
MATCHLINE
STRUCTURAL GRIDLINE
WALL SECTION
DETAIL NUMBER
DRAWING SHEET NUMBER
A1
A1.1
A1.1
DETAIL SECTION/ DETAIL CALLOUT
DETAIL NUMBER
DRAWING SHEET NUMBER
A1
A1.1
ROOM NAME
ROOM NUMBER
A1
CEILING IDENTIFICATION1
WALL IDENTIFICATION1
LEVELLEVEL 1
SPOT ELEVATION
0'-0"
0'-0"
LEVEL IDENTIFICATION
ELEVATION
FLOORING FINISH TRANSITION
CORNER GUARDS, TYP.
CG
CASEWORK IDENTIFICATION
WIDTH
HEIGHT (INCLUDES COUNTERTOP)
DEPTH
MODEL NUMBER ('M' DENOTES MODIFICATION
100M
EXTRA SHELF MODIFICATION DESCRIPTION
PROJECT LOCATION
PROJECT LAYDOWN AREA
PROJECT WORK AREA
BAY 8 TO REMAIN IN
OPERATION DURING
CONSTRUCTION
EXCAVATED FILL STORAGE - USE
ONLY IF EXISTING REMOVED SOIL IS
ADEQUATE FOR RECOMPACTION PER
GEOTECHNICAL ENGINEER'S
DETERMINATION; AREA TO BE
SEEDED PER SUDAS 9010 WHEN
WORK IS COMPLETE
CHAIN LINK CONSTRUCTION
FENCE TO BE WITHIN 1'-0" OF
EDGE OF CUT CONCRETE TO
MAINTAIN BAY 8 ACCESS
B A
Y
B A
Y
W
IL
L C
A
LL
R A
M P
W A
LK
D
O O
R
ADDITIONAL CONCRETE
PANEL W/ MANHOLE TO BE
DEMOLISHED & REPOURED
PROJECT NUMBER:
DATE:
DRAWING INDEX:
BIDDING DOCUMENTS
06/22/2026
ATOD Will Call Ramp Replacement
1918 SE Hulsizer Rd., Ankeny, IA 50021
State of Iowa - Department of Administrative Services
9534.00
.0
A T
O D
W ill
C a ll
R a m p R e p la c e m e n t
B
ID
D
IN
G D
O C
U M
E N
T S
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly registered architect under the laws of the State of Iowa.
Registration Expires
Reg. #
Signature
Date issued
O L
N AE
ROF
N S
C E
E
WOI A
I D
L P
T C
E C
TI
H
A R
SS I
Melissa S. Goodwin 08372
ARCHITECT
06/30/2028
Melissa S.
Goodwin
08372
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed
Professional Engineer under the laws of the State of Iowa.
My license renewal date is:
IA Reg. # Date
O
L
NA
E
ROF
N S
C E
E
WOI A
I D
L
P
G E
R E
NI
E
N
SS I
12/31/2027
Eric E. Vermeer P19938
STRUCTURAL ENGINEER
Eric E. Vermeer
P19938
GENERAL
G0.0 COVER
STRUCTURAL
S1.1 DEMO & FOOTING PLAN
S1.2 LAYOUT PLAN & ELEVATIONS
S1.0 STRUCTURAL NOTES & DETAILS
S1.3 RAMP DETAILS
MATERIALS LEGEND
SYMBOLS LEGEND
ABBREVIATIONS
ACT Acoustical Ceiling Tile
AFF After Finish Floor
ALUM Aluminum
ADA Americans with Disabilities Act
& And
L Angle
@ At
BCS Baby Changing Station
BOL Bollard
CIP Cast In Place
CBB Cement Backer Board
CL Center Line
CLR Clear
CONC Concrete
CONF Conference
CJ Construction Joint
CONT Continuous
CLJ Control Joint
CG Corner Guard
DIA Diameter
DS Downspout
EA Each
EHD Electric Hand Dryer
EWC Electric Water Cooler
EL Elevation
ELEV Elevation
ENG Engineered
EQ Equal
ETC Etcetera
EPDM Ethylene Propylene DieneTerpolymer
EXP Expansion
EJ Expansion Joint
EXT Exterior
EIFS Exterior Insulation Finish System
FRP Fiberglass Reinforced Panel
FF Finish Floor
FE Fire Extinguisher
FEC Fire Extinguisher Cabinet
FD Floor Drain
FT Foot or Feet
GA Gage
GT Glazing Type
GB Grab Bar
GYP Gypsum
GYP BD Gypsum Board
HM Hollow Metal
HSS Hollow Structural Sections
IR Impact Resistant
IT Information Technology
IMP Insulated Metal Panel
INSUL Insulation
INT Interior
JT Joint
MFR Manufacturer
MAX Maximum
MECH Mechanical
MEPT Mechanical/ Electrical/ Plumbing/ Technology
MTL Metal
MIN Minimum
MIR Mirror
NIC Not In Contract
OC On Center
OHS Overhead Sectional Door
PT Paint
PTD Paper Towel Dispenser
PLAM Plastic Laminate
PVC Polyvinyl Chloride
LB Pound
RCP Reflected Ceiling Plan
REQD Required
REV Reversed
RTU Roof Top Unit
SNR Sanitary Napkin Receptacle
SJ Saw Joint
SIM Similar
SDS Soap Dispenser
STL Steel
STRUCT Structure
TKSP Tack Strip
MIL Thousands of an Inch
TP Toilet Paper Dispenser
TOW Top of Wall
TYP Typical
VERT Vertical w/ With
WD Wood
AERIAL VIEW - VICINITY MAP SITE STAGING PLAN
RFB 953400-01
06/22/2026
06/22/2026
EXTEND INTERIOR
HOOKS TO EXTERIOR
FACE OF WALL, TYP.
CORNER BARS:
MATCH SIZE & SPACING
OF HORIZONTAL BARS
FOR EACH LAYER OF
REINFORCING
STANDARD HOOK
ALTERNATE ENDS
TYPICAL
CLASS B LAP
TYPICAL
CLASS B LAP
HORIZONTAL BARS: SEE WALL
& FOUNDATION SECTIONS
FOR REQ'D SIZE & SPACING
NOTES:
1. PROVIDE REINFORCING AS SHOWN ABOVE @ CORNERS OF FOUNDATION WALLS, GRADE
BEAMS, AND TRENCH FOOTINGS.
2. REINFORCING SHOWN ABOVE NOT REQUIRED @ POURED FOOTINGS. CONTINUE
TRANSVERSE FOOTING REINFORCEMENT TO EXTERIOR EDGE AT CORNERS. SEE
FOOTING DETAILS.
SURROUND PIPE WITH
2" RIGIN INSULATION.
FOUNDATION WALL
CONT. REINFORCING.
FOOTING STIRRUPS.
(4) PAIRS OF #5 BARS.
1' -0
M
IN
(2) ADDITIONAL TIES AT
SLEEVE LOCATION, 6” MAX
FROM EDGE OF OPENING
FOOTING CONT.
REINFORCING.
NOTES:
1) SEE FOUNDATION PLAN FOR SLAB THICKNESS AND REINFORCING
2) SEE PLANS FOR JOINT LOCATIONS
3) SEE SOILS REPORT FOR EXCAVATION/REWORKING OF EXISTING
FILL REQUIREMENTS
REINF. CONCRETE SLAB
ON GRADE OVER
GRANULAR FILL
1/2" DIA.x1'-4" SMOOTH BAR W/
ONE END GREASED @ 12" O.C.
LOCATED @ MID-HEIGHT OF SLAB
& PERPENDICULAR TO JOINT
COMPACTED GRANULAR
FILL - SEE NOTES
COMPACTED SUBGRADE -
SEE NOTES
REINF - SEE PLAN
1/8" TOOLED RADIUS EDGE
8" 6"
EXISTING PAVING
NOTES:
1) SEE FOUNDATION PLAN FOR SLAB THICKNESS AND REINFORCING
2) SEE PLANS FOR JOINT LOCATIONS
3) SEE SOILS REPORT FOR EXCAVATION/REWORKING OF EXISTING FILL
REQUIREMENTS
SAWCUT JOINT WITHIN 12
HOURS OF POUR, SEE PLAN
FOR LOCATIONS. DEPTH OF
JOINT TO BE THE SMALLER OF
1/4 THE SLAB THICKNESS OR 2".
REINF - SEE PLAN
COMPACTED GRANULAR
FILL - SEE NOTES
COMPACTED SUBGRADE -
SEE NOTES
REINF. CONCRETE SLAB
ON GRADE OVER
GRANULAR FILL
8" 6"
NOTES:
1) SEE FOUNDATION PLAN FOR SLAB THICKNESS AND REINFORCING
2) SEE PLANS FOR JOINT LOCATIONS
3) SEE SOILS REPORT FOR EXCAVATION/REWORKING OF EXISTING
FILL REQUIREMENTS
REINF. CONCRETE SLAB
ON GRADE OVER
GRANULAR FILL
REINF- SEE PLAN
COMPACTED GRANULAR
FILL - SEE NOTES
COMPACTED SUBGRADE -
SEE NOTES
8" 6"
CONDITION A CONDITION B
TRENCH FOOTING
PROVIDE SLEEVE - REF
MECH/ELEC DRAWINGS
SITE UTILITY - REF
MECH/ELEC DRAWINGS
1' -0
PIPE SLEEVE AT
FLOWABLE FILL
FLOWABLE FILL
NOTES:
1. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR ALL LOCATIONS,
ELEVATIONS, ETC., OF SITE UTILITIES.
2. DETAIL REQUIRED AT ALL UTILITIES HAVING A PLAN WIDTH UP TO 3'-0". FOR WIDTHS
GREATER THAN 3'-0", REFERENCE PLAN FOR REQUIRED DETAIL.
3. CONDITION B DOES NOT APPLY AT SPREAD FOOTING SITUATIONS. GENERAL
CONTRACTOR SHALL NOTIFY ENGINEER SHOULD SUCH A CONDITION ARISE AND AWAIT
FURTHER INSTRUCTIONS.
4. SEE DETAIL C2/S3.00 FOR LOCATIONS OF UTILITIES AT BOTOM OF TRENCH FOOTINGS
1' -0
M
IN
N O
T E
1' -0
M
IN
B ACDE
F
B ACDEF
S T
R U
C T
U R
A L
E N
G
IN
E E
R
F O
LD
K el lo gg
A ve
A m es , I
A
P h on e:
.2
.0
F a x:
.2
.0
A R
C H
IT
E
C T
F
O
LD
K el lo gg ve m es , I
A
P h on e:
.2
.0
F a x:
-2
2-
©2026REVISIONS:
PROJECT NUMBER
PROJECT ISSUE DATE
REV DATE DESCRIPTION
S1.0
STRUCTURAL NOTES &
DETAILS
A T
O D
W ill
C al l R am p R ep la ce m en t
S ta te o f I ow a
D ep ar tm en t o f A dm in is tr at iv e
S er vi ce s
S E
H ul si ze r R d.
, A nk en y, IA
06/22/2026 9534.00
BIDDING DOCUMENTS
MARK
CF18
FOOTING SCHEDULE
WIDTH
1'-6" CONT.
THICKNESS
1'-3"
FOOTING REINFORCING
(2) #5 CONTINUOUS WITH #5 @ 12" O.C.
TRANSVERSE
WALL REINFORCING
10" THICK FOUNDATION WALL TO HAVE #5 @ 12" O.C. EACH
WAY. TERMINATE WITH 6" 90 DEGREE HOOKS SPLICED TO
BOTTOM MAT OF REINFORCING IN FOOTING.
CF52 4'-4" CONT. 1'-3" 1'-0" THICK FOUNDATION WALL TO HAVE #5 @ 12" O.C.
EACH WAY ON SIDE OF WALL WITH HIGH GRADE AND #4
@ 12" O.C. EACH WAY ON SIDE OF WALL WITH LOW
GRADE. TERMINATE #5'S WITH 22" LONG AND #4 WITH 6"
LONG, 90 DEGREE HOOKS SPLICED TO BOTTOM MAT OF
REINFORCING IN FOOTING. PROVIDE #5 @ 12"
CONTINOUS IN WALLS.
(5) #5 TOP CONTINUOUS
(5) #5 BOTTOM CONTINUOUS
#5 @ 12" O.C. TRANSVERSE SETTING ON TOP
ROW OF CONTINUOUS REINFORCING
SF70 5'-8" CONT 1'-3" 1'-0" THICK FOUNDATION WALL TO HAVE #5 @ 12" O.C.
EACH WAY ON SIDE OF WALL WITH HIGH GRADE AND #4
@ 12" O.C. EACH WAY ON SIDE OF WALL WITH LOW
GRADE. TERMINATE #5'S WITH 22" LONG AND #4 WITH 6"
LONG, 90 DEGREE HOOKS SPLICED TO BOTTOM MAT OF
REINFORCING IN FOOTING. PROVIDE #5 @ 12"
CONTINOUS IN WALLS.
(6) #5 TOP CONTINUOUS
(6) #5 BOTTOM CONTINUOUS
#5 @ 12" O.C. TRANSVERSE SETTING ON TOP
ROW OF CONTINUOUS REINFORCING
NOTES:
1. EXTEND CONTINUOUS REINFORCING THROUGH ISOLATED FOOTINGS AND PIERS.
GENERAL STRUCTURAL NOTES
1 THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE REQUIREMENTS FROM THESE DRAWINGS
INTO THEIR SHOP DRAWINGS AND WORK.
2 VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO FABRICATION OF ANY ITEMS.
3 DRAWINGS SHALL BE COORDINATED WITH ELECTRICAL COMPONENTS. NOT SHOWN ON DRAWINGS.
COORDINATE LOCATION, SIZE AND REINFORCEMENT OF ALL OPENINGS WITH RESPECTIVE TRADES BEFORE FABRICATION. REPORT ANY DISCREPANCIES AND/OR INTERFERENCE PROBLEMS TO THE ARCHITECT AND
STRUCTURAL ENGINEER OF RECORD.
4 THESE GENERAL NOTES SUPPLEMENT THE PROJECT SPECIFICATIONS. REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER THE GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE
PROVIDED, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
5 THE BUILDING IS NOT STRUCTURALLY STABLE UNTIL ALL CONNECTIONS, FRAMING AND WALLS ARE COMPLETE AND HAVE ACHIEVED FINAL DESIGN STRENGTH. CONTRACTOR IS SOLELY RESPONSIBLE TO MAINTAIN STRUCTURAL STABILITY DURING ERECTION AND CONSTRUCTION. TEMPORARY BRACING SYSTEMS
ARE NOT TO BE REMOVED UNTIL STRUCTURAL WORK IS COMPLETE.
6 CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL RECOGNIZE AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.
7 THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL MEANS, METHODS, TECHNIQUES, SEQUENCING, AND
PROCEDURES NECESSARY FOR CONSTRUCTING, OVERSEEING, AND COORDINATING THE WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ALL APPLICABLE HEALTH AND SAFETY STANDARDS.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR JOB SITE SAFETY.
DESIGN PARAMETERS
1 THE STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE ICC INTERNATIONAL BUILDING CODE, 2015
EDITION.
2 RAMP LANDING FROST SLAB DESIGN BASED ON ACCOMODATING A 26,000 LBS CAPACITY BOXTRUCK.
4 SNOW DESIGN PARAMETERS:
GROUND SNOW LOAD (Pg) 30 PSF FLAT ROOF SNOW LOAD (Pf) 23 PSF
SNOW EXPOSURE FACTOR (C/E) 1.0
SNOW LOAD IMPORTANCE FACTOR (I) 1.0
SNOW LOAD THERMAL FACTOR (Ct) 1.0
EARTHQUAKE DESIGN PARAMETERS:
SEISMIC IMPORTANCE FACTOR (I/E) 1.0
Ss 0.064g S1 0.046g
SEISMIC SITE CLASS D
Sds 0.068g Sd1 0.073g SHORT-PERIOD SITE COEFFICIENT (Fa) 1.6 LONG-PERIOD SITE COEFFICIENT (Fv) 2.4
SEISMIC DESIGN CATEGORY A
SEISMIC-FORCE-RESISTING SYSTEM:
ORDINARY REINFORCED CONCRETE WALLS
SEISMIC BASE SHEAR (V),CLASSROOM ADDITION 0.70K
SEISMIC RESPONSE COEFFICIENT (Cs) N-S 0.01 SEISMIC RESPONSE COEFFICIENT (Cs) E-W 0.01
RESPONSE MODIFICATION FACTOR (R) N-S 2
RESPONSE MODIFICATION FACTOR (R) E-W 2
REDUNDANCY FACTOR (ρ) N-S 1.0 REDUNDANCY FACTOR (ρ) E-W 1.0
SEISMIC ANALYSIS PROCEDURE:
EQUIVALENT LATERAL FORCE ANALYSIS (WIND LOAD GOVERNS DESIGN)
6 WIND DESIGN PARAMETERS:
BASIC WIND SPEED (V) (3 SECOND GUST) 115 MPH
RISK CATEGORY II
WIND EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFFICIENT +/-.18
BASIC DESIGN PRESSURE @ WALL 18 PSF (SERVICE)
7 ALLOWABLE WALL DEFLECTIONS:
EXTERIOR (CLADDING DESIGN) L/360
8 ASSUMED FUTURE CONSTRUCTION:
VERTICAL NONE
HORIZONTAL NONE
9 ASSUMED FUTURE CONSTRUCTION:
NONE.
FOUNDATION PARAMETERS
1 SIZE AND BOTTOM ELEVATIONS OF FOOTINGS HAVE BEEN DETERMINED BASED ON SITE OBSERVATIONS, UNANTICIPATED SOIL CONDITIONS MAY REQUIRE CHANGES. OWNER IS TO EMPLOY A GEOTECHNICAL ENGINEER TO REVIEW SOIL CONDITIONS AT NEW FOOTINGS PRIOR TO CONCRETE PLACEMENT. AS EXCAVATION PROGRESSES, UNANTICIPATED SOIL CONDITIONS MAY REQUIRE CHANGES. CONTACT
STRUCTURAL ENGINEER OF RECORD FOR EVALUATION OF THESE CHANGES.
2 ALLOWABLE SOIL BEARING PRESSURE
SPREAD AND ISOLATED FOOTINGS 2000 PSF (ASSUMED)
RETAINING FOOTINGS (AT FOOTING TOE) 2000 PSF (ASSUMED)
3 MINIMUM FOOTING DEPTH FOR FROST PROTECTION
(BELOW FINISHED GRADE) 42 IN.
4 DESIGN EARTH PRESSURES:
ACTIVE 35 PCF
PASSIVE 400 PCF
AT REST 60 PCF
6 GEOTECHNICAL ENGINEER IS SOLE JUDGE OF THE SUITABILITY OF UNDERLYING MATERIAL TO SUPPORT
FOUNDATIONS. BEARING MATERIAL SHALL BE APPROVED BY GEOTECHNICAL ENGINEER BEFORE
FOUNDATION INSTALLATION. DO NOT PROCEED WITHOUT APPROVAL.
SUBMITTALS
1 GENERAL CONTRACTOR TO PROVIDE A SHOP DRAWING SUBMITTAL LOG ITEMIZING ALL PROPOSED
SUBMITTALS FOR APPROVAL BY STRUCTURAL ENGINEER OF RECORD.
2 ALL SHOP DRAWINGS SHALL BE CHECKED BY THE FABRICATOR AND APPROVED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER OF RECORD. SHOP DRAWING REVIEW BY ENGINEER IS LIMITED TO VERIFYING GENERAL CONFORMANCE TO THE CONTRACT DOCUMENTS.
CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES FROM THE CONTRACT DOCUMENTS, DIMENSIONAL
ERRORS, COORDINATION ERRORS, OR OMISSIONS IN SHOP DRAWINGS.
3 SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION
REGARDING ALL STRUCTURAL ITEMS, INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
● CONCRETE MIX DESIGNS (5 DAYS BEFORE POUR, MIN.)
● CONCRETE REINFORCEMENT
● EMBEDDED STEEL ITEMS
● CONCRETE CURING
● STEEL GUARDRAILS
4 SHOP DRAWINGS SHALL INCLUDE CONNECTIONS AS WELL AS SIZE, SPACING, AND GRADE OF ALL MEMBERS. PLANS AND ANY DETAILING NECESSARY FOR DETERMINING FIT AND PLACEMENT SHALL ALSO BE
INCLUDED.
5 IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEY SHALL BEAR THE SEAL AND SIGNATURE OF AN ENGINEER REGISTERED IN THE APPROPRIATE STATE. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT AND ARE SUBJECT TO
REVIEW AND APPROVAL OF THE STRUCTURAL ENGINEER
6 DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN AND FABRICATION OF ITEMS
THAT ARE DESIGNED BY THE CONTRACTOR, INCLUDE:
● TEMPORARY SHORING
● CONCRETE FORMWORK
SHALL BEAR THE SEAL AND SIGNATURE OF AN ENGINEER REGISTERED IN THE APPROPRIATE STATE AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION. CALCULATIONS SHALL BE INCLUDED FOR ALL CONNECTIONS TO THE STRUCTURE, CONSIDERING LOCALIZED EFFECTS ON
STRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS.
7 ITEMS THAT ARE DESIGNED BY THE CONTRACTOR SHALL BE DESIGNED TO RESIST THE LIVE LOADS INDICATED IN STRUCTURAL NOTES, DEAD LOAD, SELF WEIGHT, ANY ADDITIONAL LOADING INDICATED ON
PLANS AND DETAILS, SNOW DRIFT, AND A NET WIND UPLIFT.
8 ITEMS THAT ARE DESIGNED BY THE CONTRACTOR SHALL INCLUDE ANY RELEVANT TECHNICAL
LITERATURE FROM MANUFACTURER. ALSO PROVIDE A CERTIFICATION FROM THE MANUFACTURER
SHOWING THE PRODUCT IS IN COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS.
9 FIELD ENGINEERED DETAILS DEVELOPED BY THE CONTRACTOR THAT DIFFER FROM OR ADD TO THE STRUCTURAL DRAWINGS SHALL BEAR THE SEAL AND SIGNATURE OF AN ENGINEER REGISTERED IN THE
APPROPRIATE STATE AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO CONSTRUCTION.
10 ALL SHOP DRAWINGS SHALL BE CHECKED BY THE FABRICATOR AND APPROVED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL TO THE ARCHITECT, WHOSE REVIEW OF THE SHOP DRAWINGS IS LIMITED TO VERIFYING GENERAL CONFORMANCE TO THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR ANY CHANGES FROM CONTRACT DOCUMENTS, DIMENSIONAL ERRORS, COORDINATION
ERRORS, OR OMISSIONS IN SHOP DRAWINGS.
11 VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO FABRICATION OF ANY ITEMS. DRAWINGS SHALL BE COORDINATED WITH MECHANICAL/ELECTRICAL COMPONENTS NOT SHOWN ON DRAWINGS. COORDINATE LOCATION, SIZE, AND REINFORCING OF ALL OPENINGS WITH RESPECTIVE TRADES BEFORE FABRICATION.
12 FIELD VERIFY EXISTING DIMENSIONS, MEMBER SIZES AND ELEVATIONS SHOWN ON THE DRAWINGS PRIOR TO STARTING CONSTRUCTION. ALL DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION
OF THE ARCHITECT.
CONCRETE NOTES
1 CONCRETE WORK SHALL CONFORM TO CHAPTER 19 OF THE IBC.
2 WHERE NEW CONCRETE IS PLACED DIRECTLY AGAINST EXISTING CONCRETE, THE EXISTING CONCRETE SURFACE SHALL BE CLEANED AND ROUGHENED TO A MINIMUM OF 1/4" AMPLITUDE. SEE PLAN FOR
DOWELING REQUIREMENTS.
3 ALL EXPOSED EDGES OF CONCRETE MEMBERS SHALL BE CHAMFERED 1/2" U.N.O.
4 CONCRETE FORMWORK:
4.1 SLEEVES, OPENINGS, CONDUIT, AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL
DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER PRIOR TO POURING CONCRETE.
CONDUITS EMBEDDED IN SLABS SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN ONE THIRD OF THE THICKNESS OF THE SLAB AND SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS ON CENTER.
4.2 VERIFY ALL BLOCK OUTS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING
REQUIREMENTS PRIOR TO POURING.
5 CONCRETE REINFORCEMENT:
5.1 DETAILING, FABRICATION, AND PLACEMENT OR REINFORCEMENT SHALL CONFORM TO ACI-315.
5.2 ALL REINFORCEMENT TO BE ASTM A615 GRADE 60 U.N.O. REINFORCING STEEL SHALL BE SECURELY TIED IN PLACE USING #16 ANNEALED IRON WIRE. REINFORCEMENT SHALL BE CONTINUOUS THROUGH ALL
CONSTRUCTION JOINTS UNLESS NOTED OTHERWISE.
5.3 ALL CONTINUOUS REINFORCING SHALL BE SPLICED USING CLASS B TENSION SPLICES, U.N.O.
5.4 BARS IN BEAMS AND SLABS SHALL BE SUPPORTED ON WELL-CURED CONCRETE BLOCKS OR
APPROVED METAL CHAIRS, AS SPECIFIED BY THE CRSI MANUAL OF STANDARD PRACTICE, MSP-1.
5.5 CONTINUE HORIZONTAL WALL BARS THROUGH PILASTERS, COLUMNS, AND INTERSECTING WALLS.
REFER TO TYPICAL DETAILS FOR LAYOUT OF CORNER BARS AND BARS IN SMALL WALL SECTIONS. SLAB
BARS SHALL BE HOOKED INTO WALLS OR HOOKED DOWELS SHALL BE PROVIDED TO MATCH SLAB
REINFORCING. PROVIDE HOOKED DOWELS FROM FOOTINGS TO MATCH VERTICAL WALL REINFORCING.
5.6 ADD TWO DIAGONAL #5 BARS, FOUR FEET LONG, CENTERED, AT EACH CORNER OF FOUNDATION OR
SLAB OPENING, U.N.O.
5.7 ALL SLAB REINFORCEMNET IS TO BE FULLY CHAIRED AT THE INDICATED ELEVATION PER ACI-315 REQUIREMENTS PRIOR TO CONCRETE PLACEMENT. LIFTING SLAB MAT REINFORCEMENT INTO PLACE
DURING CONCRETE PLACEMENT IS NOT PERMITTED.
6 COVERAGE FOR REINFORCEMENT:
6.1 CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
6.2 CONCRETE EXPOSED TO EARTH AND WEATHER:
#6 THRU #18 BARS 2"
#5 BAR 1 1/2"
6.3 CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
SLABS, WALLS, JOISTS:
#11 BAR AND SMALLER ...................................................................................3/4"
PIERS:
PRIMARY REINFORCEMENT,
TIES, STIRRUPS, SPIRALS ..............................................................................1 1/2"
7 CONCRETE COMPRESSIVE STRENGTHS SHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER
ASTM C39 AND SHALL BE AS FOLLOWS:
FOOTINGS............................................................................................................. f'c = 4,000 PSI SLABS ON GRADE ............................................................................................... f'c = 4,000 PSI WALLS AND PIERS ............................................................................................... f'c = 4,000 PSI
8 SPECIAL INSPECTOR SHALL BE NOTIFIED IF ANY WATER IS TO BE ADDED IN FIELD.
9 CONCRETE FOUNDATIONS:
9.1 ALL FOUNDATION EXCAVATIONS MUST BE REVIEWED AND APPROVED BY THE GEOTECHNICAL
ENGINEER TO BE OF SUITABLE BEARING CAPACITY PRIOR TO PLACEMENT OF CONCRETE.
9.2 ACCURATELY SET AND SECURELY SUPPORT REINFORCING, DOWELS, AND ANCHOR BOLTS PRIOR TO PLACEMENT OF CONCRETE. WET-STICKING OR FLOATING OF REINFORCING, DOWELS, AND ANCHOR RODS
IS NOT ALLOWED.
9.3 PROVIDE CONSTRUCTION JOINTS, INSERTS, SLEEVES, DOWELS, ANCHORS, ETC., AS SHOWN. ITEMS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS AND ACCORDING TO USUAL ACCEPTED
STANDARDS OF THE TRADE. ANCHOR RODS PER ASTM F1554 AS SHOWN.
9.4 ALL FOUNDATION COLD JOINTS SHALL BE KEYED. CONTINUOUS REINFORCING SHALL EXTEND ONE
DEVELOPMENT LENGTH PLUS 6".
9.5 REINFORCING SHOWN ON DETAILS IS THE REQUIRED MINIMUM. AT CONTRACTOR'S OPTION AND EXPENSE, ADDITIONAL REINFORCING MAY BE PERMITTED TO ASSIST IN EASE OF CONSTRUCTABILITY.
ADDITIONAL REINFORCING MUST BE SUBMITTED FOR REVIEW ON SHOP DRAWINGS.
10 PROVIDE MINIMUM 7000 PSI NON-SHRINK, NON-METALLIC GROUT. GROUT SHALL NOT CONTAIN GYPSUM.
ENSURE ALL VOIDS ARE FILLED WITH GROUT.
11 NOT USED
12 PROVIDE CONTROL JOINTS AS FOLLOWS, U.N.O.:
12.1 SLABS (ON GRID LINE WHERE PRACTICAL) AND:
SLAB-ON-GRADE ................................. 10' ± 2'
12.2 CONTROL JOINT LAYOUT SHOULD MAINTAIN AN APPROXIMATE ASPECT RATIO OF 1:1
13 EXPOSED SLAB ON GRADE:
13.1 ALL SLAB ON GRADE CONTROL JOINTS & COLD JOINTS SHALL BE COORDINATED WITH THE
ARCHITECT WHERE THE SLAB IS EXPOSED.
13.2 CONTRACTOR SHALL PARTICIPATE IN A PRE-CONSTRUCTION MEETING PRIOR TO ANY EXPOSED CONCRETE SLAB ON GRADE POUR. CONTRACTOR SHALL PROVIDE ENGINEER WITH ANTICIPATED EXPOSED SLAB ON GRADE CONTROL AND COLD JOINT LOCATIONS. ENGINEER MUST APPROVE CONTROL AND COLD
JOINT LOCATIONS PRIOR TO ANY EXPOSED CONCRETE SLAB POUR.
13.3 SLABS SHALL BE SUPPORTED BY REWORKED ENGINEERED COMPACTED FILL IN THICKNESS AS
NOTED ABOVE. SLABS ON GRADE SHALL BE AS INDICATED ON DRAWINGS. WHERE REQUIRED BY
GEOTECHNICAL ENGINEER, OVER-EXCAVATE AND RECOMPACT USING STRUCTURAL FILL. SEE SOILS REPORT FOR SPECIFIC REQUIREMENTS. PROVIDE 98% PROCTOR DENSITY ON COMPACTED STRUCTURAL
FILL. PROVIDE NO MORE THAN 15% FLY ASH FOR ALL FLOOR SLABS.
13.4 SAWN CONTROL JOINTS IN SLABS ON GRADE SHALL BE 1/8" WIDE AND 1/4 OF THE SLAB THICKNESS DEEP. CUTTING OPERATIONS SHALL BE FROM 4 TO 12 HOURS AFTER PLACING CONCRETE. MAXIMUM SPACING OF JOINTS SHALL BE 30 TIMES THE SLAB THICKNESS OR AS SHOWN ON THE DRAWINGS. SEE SPECIFICATION REGARDING CUTTING REQUIREMENTS AND EDGE RAVELING. CONTRACTOR TO SUBMIT
SAWN JOINT LAYOUT TO ENGINEER FOR APPROVAL PRIOR TO POURING SLABS.
14 CONCRETE ACCESSORIES:
14.1 U.N.O., EXPANSION BOLTS TO BE HILTI KWIK BOLT III, SIMPSON STRONG-BOLT, OR APPROVED EQUIVALENT WITH EQUAL ICC TENSION AND SHEAR VALUES. EXPANSION ANCHORS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. DO NOT CUT REINFORCING IN NEW OR
EXISTING CONCRETE DURING INSTALLATION.
14.2 U.N.O., EPOXY ANCHORS TO BE HILTI HIT-RE 500-SD, SIMPSON SET-XP, OR APPROVED EQUIVALENT WITH EQUAL ICC TENSION AND SHEAR VALUES. EPOXY ANCHORS SHALL BE INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. DO NOT CUT REINFORCING IN NEW OR
EXISTING CONCRETE DURING INSTALLATION.
15 PERMANENTLY EXPOSED PLATES AND GUARDRAILS TO BE HOT-DIP GALVANIZED.
16 EPOXY REPAIR ADHESIVE SHALL CONFORM TO ASTM C881 AND SHALL BE A TWO-COMPONENT, LIQUID EPOXY WITH NON-SAG CONSISTENCY AND A LONG POT LIFE. THE EPOXY ADHESIVE SHALL BE SUITABLE FOR USE IN DRY OR DAMP CONDITIONS. MINIMUM SHEAR STRENGTH SHALL BE 5,000 PSI; MINIMUM TENSILE STRENGTH SHALL BE 4,000 PSI. HOLE SIZES AND INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH THE APPROVED ICC REQUIREMENTS. DO NOT CUT REINFORCING IN NEW OR EXISTING CONCRETE DURING
PLACEMENT.
17 COLD WEATHER PROTECTION
17.1 DURING COLD WEATHER CONSTRUCTION, CONTRACTOR IS RESPONSIBLE FOR PROTECTING CURING
CONCRETE PER THE RQMTS. OF ACI 306.
17.2 DURING COLD WEATHER CONSTRUCTION, CONTRACTOR IS RESPONSIBLE FOR PROTECTING
FOUNDATIONS THAT DO NOT EXTEND TO FROST DEPTH FROM HEAVING. AT CONTRACTOR'S OPTION, BOTTOM OF FOOTINGS MAY BE EXTENDED BEYOND THE FROST ZONE, IN LIEU OF SURFACE PROTECTION METHODS. NO ADD'L REINFORCING WILL BE REQ'D AT EXTENDED FOUNDATIONS. ALL MITIGATION WORK
SHALL BE PART OF THE CONTRACTOR BID AND NOT COMPENSIBLE BY CHANGE ORDER.
18.3 CONTRACTOR TO PROVIDE A FROST STOOP PER TYP. STOOP DETAIL @ ALL EXTERIOR DOORS, SEE
ARCH. FOR DOOR LOCATIONS.
STEEL FRAMING NOTES
1 STEEL FRAMING WORK SHALL COMPLY WITH CHAPTER 22 OF THE IBC.
2 STEEL FRAMING MATERIALS:
2.1 W/WT-SECTIONS ASTM A992 FY=50,000 PSI
2.2 TUBULAR STEEL ASTM A500 GR B FY=46,000 PSI
2.3 CHANNELS, ANGLES, BARS ASTM A36 FY=36,000 PSI
2.4 PLATES (NON-MOMENT CONNECTIONS) ASTM A36 FY=36,000 PSI
2.5 PLATES (MOMENT CONNECTIONS) ASTM A572 FY=50,000 PSI
2.6 WELDING ELECTRODES E70XX
3 STEEL ERECTION SHALL COMPLY WITH ALL OSHA, STATE, LOCAL, AND UNION REGULATIONS. IN ADDITION, AT THE END OF THE WORK DAY, ALL COLUMNS MUST BE FRAMED WITH BEAMS AND/OR GIRDERS IN ALL DIRECTIONS, OR ADEQUATELY GUYED OR BRACED IN ALL DIRECTIONS. TEMPORARY GUYING/BRACING IS
THE RESPONSIBILITY OF THE ERECTOR (DESIGN AND INSTALLATION).
4 DESIGN, FABRICATION, AND ERECTION SHALL BE IN ACCORDANCE WITH THE AISC STEEL CONSTRUCTION
MANUAL, AISC 360-10 INCLUDING COMMENTARY, AND THE AISC 303-10.
5 ALL BOLTS FOR STRUCTURAL STEEL CONNECTIONS PER ASTM A325-N U.N.O. AND SHALL CONFORM TO THE RCSC SPECIFICATION. BOLTS FOR STEEL JOISTS MAY BE A307. BOLTS AND SHALL BE SNUG-TIGHT U.N.O.
6 WELDING SHALL CONFORM TO THE AWS CODES FOR ARC AND GAS WELDING IN BUILDING
CONSTRUCTION. WELDING SHALL BE PERFORMED IN ACCORDANCE WITH A WELDED PROCEDURE
SPECIFICATION (WPS) AS REQUIRED IN AWS D1.1 AND APPROVED BY THE STRUCTURAL ENGINEER. THE WPS VARIABLES SHALL BE WITHIN THE PARAMETERS ESTABLISHED BY THE FILLER-METAL MANUFACTURER.
7 WELDS SHALL BE MADE USING E70XX ELECTRODES AND SHALL BE 3/16" MINIMUM, U.N.O. ALL WELDING FOR STRUCTURAL STEEL CONNECTIONS TO BE PERFORMED BY CERTIFIED WELDERS IN ACCORDANCE WITH
AWS D1.1. PROTECT ALL SURFACES SURROUNDING WELDING OPERATIONS.
8 NOT USED
9 NOT USED
10 NOT USED
11 HOT-DIP GALVANIZE STEEL FOR THE FOLLOWING CONDITIONS:
11.1 STEEL ELEMENTS PERMANENTLY EXPOSED TO WEATHER.
11.2 STEEL ELEMENTS LOCATED OUTSIDE THE BUILDING THERMAL ENVELOPE.
11.3 STEEL ELEMENTS LOCATED IN AREAS WITH HIGH HUMIDITY.
11.4 WHERE PIECES REQUIRING GALVANIZATION ARE PART OF A LARGER ASSEMBLY, THE HOT-DIPPING
PROCESS IS TO OCCUR AFTER COMPLETE FABRICATION OF THE ASSEMBLY.
12 CONNECTIONS:
12.1 WHERE CONNECTIONS ARE NOT SHOWN, THE CONNECTIONS SHALL BE DESIGNED AND DETAILED IN
ACCORDANCE WITH THE REQUIREMENTS OF AISC SPECIFICATIONS FOR THE SHEAR CAPACITIES
SHOWN BELOW:
12.2 ALL CONNECTIONS SHALL SATISFY THE REQUIREMENTS OF AISC AND OSHA.
12.3 AT STEEL CONNECTIONS WITH POST INSTALLED ANCHORS, THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT THE HOLE DIAMETERS COMPLY WITH THE MANUFACTURER'S RECOMMENDED DRILL
BIT DIAMETER.
13 (+###'-#") CALLOUT ON PLANS AT BEAM LOCATIONS INDICATES TOP OF BEAM U.N.O.
SPECIAL INSPECTION SCHEDULE
1 SPECIAL INSPECTION PROGRAM SHALL CONFORM TO CHAPTER 17 OF THE IBC.
2 THE OWNER SHALL EMPLOY A SPECIAL INSPECTOR TO PERFORM THE REQUIRED TESTS AND SPECIAL INSPECTIONS WITH QUALIFICATIONS DESCRIBED PER IBC CHAPTER 17 AND THE PROJECT SPECIFICATIONS.
3 SPECIAL INSPECTION REPORTS SHALL BE FURNISHED TO BUILDING OFFICIAL, OWNER, ARCHITECT, STRUCTURAL ENGINEER, AND CONTRACTOR.
4 SPECIAL INSPECTOR SHALL SUBMIT A FINAL REPORT STATING THAT THE STRUCTURAL WORK WAS, TO
THE BEST OF THE SPECIAL INSPECTOR'S KNOWLEDGE, PERFORMED IN ACCORDANCE WITH THE
CONSTRUCTION DOCUMENTS.
5 SPECIAL INSPECTION PROGRAM:
VERIFICATION AND INSPECTION FREQ/TASK
STEEL
1. INSPECTION TASKS PRIOR TO WELDING:
A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE. PERFORM
B. MANUFACTURER'S CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE. PERFORM
C. MATERIAL IDENTIFICATION (TYPE/GRADE). OBSERVE
D. WELDER IDENTIFICATION SYSTEM. OBSERVE
E. CONFIGURATION & FINISH OF ACCESS HOLES. OBSERVE
F. FIT-UP OF FILLET WELDS:
• DIMS. (ALIGNMENT, GAPS AT ROOT) OBSERVE
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY & LOCATION)
2. INSPECTION TASKS DURING WELDING:
A. USE OF QUALIFIED WELDERS. OBSERVE
B. CONTROL & HANDLING OF WELDING CONSUMABLES: OBSERVE
• EXPOSURE CONTROL • PACKAGING
C. NO WELDING OVER CRACKED TACK WELDS. OBSERVE
D. ENVIRONMENTAL CONDITIONS: OBSERVE
• WIND SPEED WITHIN LIMITS • PRECIPITATION & TEMP.
E. WPS FOLLOWED:
• SETTINGS ON WELDING EQPT. • TRAVEL SPEED
• SELECTED WELDING MATERIALS • PREHEAT APPLIED OBSERVE
• SHIELDING GAS TYPE/FLOW RATE • PROPER POSITION (F, V, H, OH)
• INTERPASS TEMP. MAINTAINED (MIN / MAX)
F. WELDING TECHNIQUES:
• INTERPASS & FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS OBSERVE
• EACH PASS MEETS QUALITY REQUIREMENTS
3. INSPECTION TASKS AFTER WELDING.
A. WELDS CLEANED. OBSERVE
B. SIZE, LENGTH, & LOCATION OF WELDS. PERFORM
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA:
• CRACK PROHIBITION • WELD SIZE
• WELD / BASE-METAL FUSION • UNDERCUT PERFORM
• CRATER CROSS SECTION • POROSITY
• WELD PROFILES
D. ARC STRIKES. PERFORM
E. k-AREA. PERFORM
F. BACKING & WELD TABS REMOVED (IF REQ'D.). PERFORM
G. REPAIR ACTIVITIES. PERFORM
H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER. PERFORM
4. INSPECTION TASKS PRIOR TO BOLTING:
A. MFR. CERTS. AVAILABLE FOR FASTENER MATERIALS. PERFORM
B. FASTENERS MARKED IN ACCORDANCE w/ ASTM RQMTS. OBSERVE
C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, OBSERVE
BOLT LENGTH, EXCLUDED THREADS).
D. PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL. OBSERVE
E. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE OBSERVE
CONDITION & HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE RQMTS.
F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION OBSERVE
PERSONNEL OBSERVED & DOCUMENTED FOR FASTENER
ASSEMBLIES & METHODS USED.
G. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS & OTHER OBSERVE
FASTENER COMPONENTS.
5. INSPECTION TASKS DURING BOLTING:
A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES OBSERVE
& WASHERS (IF REQ'D) ARE POSITIONED AS REQ'D.
B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE OBSERVE
PRETENSIONING OPERATION.
C. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED OBSERVE
FROM ROTATING.
D. FASTENERS ARE PRETENSIONED IN ACCORDANCE w/ THE RCSC OBSERVE
SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID
POINT TOWARD THE FREE EDGES.
6. INSPECTION TASKS AFTER BOLTING:
A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNS. PERFORM
7. INSPECTION OF STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL:
A. INSPECTION OF WELDING:
1) VERIFICATION OF WELDABILITY OF REINF. STEEL OTHER THAN ASTM A706. PERIODIC
2) REINFORCING STEEL RESISTING FLEXURAL & AXIAL FORCES IN
INTERMEDIATE & SPECIAL MOMENT FRAMES, & BOUNDARY ELEMENTS OF CONT.
SPECIAL STRUCTURAL WALLS OF CONCRETE & SHEAR REINFORCEMENT.
4) SHEAR REINFORCING STEEL. CONT.
5) OTHER REINFORCING STEEL. PERIODIC
CONCRETE
1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, PERIODIC
& PLACEMENT.
2. INSPECTION OF REINFORCING STEEL WELDING IN ACCORDANCE w/ IBC _________ TABLE 1705.2.2, ITEM 2b.
3. INSPECTION OF ANCHORS TO BE INSTALLED IN CONCRETE WHERE ALLOWABLE PERIODIC
LOADS HAVE BEEN INCREASED OR WHERE STRENGTH DESIGN IS USED.
4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS. PERIODIC
5. VERIFYING USE OF REQUIRED DESIGN MIX. PERIODIC
6. AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP & AIR CONTENT TESTS, & DETERMINE THE CONT.
TEMPERATURE OF THE CONCRETE.
7. INSPECTION OF CONCRETE & SHOTCRETE PLACEMENT FOR PROPER CONT.
APPLICATION TECHNIQUES.
8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMP. & TECHNIQUES. PERIODIC
9. INSPECTION OF PRESTRESSED CONCRETE: CONT.
A. APPLICATION OF PRESTRESSING FORCES. CONT.
B. GROUTING OF BONDED PRESTRESSING TENDONS IN THE SEISMIC-FORCE- CONT.
RESISTING SYSTEM.
10. ERECTION OF PRECAST CONCRETE MEMBERS. PERIODIC
11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST TENSIONED CONCRETE & PRIOR TO REMOVAL OF PERIODIC
SHORES & FORMS FROM BEAMS & STRUCTURAL SLABS.
12. INSPECT FORMWORK FOR SHAPE, LOCATION & DIMENSIONS OF THE PERIODIC
CONCRETE MEMBER BEING FORMED.
PROGRAM FOOTNOTES
1. THE ITEMS INDICATED ABOVE SHALL BE INSPECTED IN ACCORDANCE WITH CHAPTER 17 OF THE IBC BY A CERTIFIED SPECIAL INSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING REQUIREMENTS, REFER TO THE PROJECT SPECIFICATIONS & THE SPECIFIC STRUCTURAL NOTES SECTIONS. THE TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING & INSPECTION REPORTS DIRECTLY TO THE ARCHITECT, STRUCTURAL ENGINEER, CONTRACTOR, & BUILDING OFFICIAL. ANY MATERIALS WHICH FAIL TO MEET THE PROJECT SPECIFICATIONS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL
BIDDER DESIGNED COMPONENTS.
2. CONT. - CONTINUOUS SPECIAL INSPECTION. SPECIAL INSPECTOR IS PRESENT WHEN & WHERE THE
WORK TO BE INSPECTED IS BEING PERFORMED. (IBC SECTION 1702).
3. PERIODIC - PERIODIC SPECIAL INSPECTION. SPECIAL INSPECTOR IS INTERMITTENTLY PRESENT WHERE
THE WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED.
4. OBSERVE - SPECIAL INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS
NEED NOT BE DELAYED PENDING THESE INSPECTIONS (AISC 360 SECTION N5).
5. PERFORM - SPECIAL INSPECTOR SHALL PERFORM THESE TASKS FOR EACH JOINT, CONNECTION, ELEMENT OR MEMBER (AISC 360 SECTION N5).
6. SPECIAL INSPECTION IS NOT REQUIRED FOR WORK PERFORMED BY AN APPROVED FABRICATOR (IBC
SECTION 1704.2.2).
7. ALL WELDS SHALL BE VISUALLY INSPECTED.
8. ALL COMPLETE PENETRATION WELDS SHALL BE TESTED ULTRASONICALLY OR BY USE OF A
COMPARABLE APPROVED METHOD.
9. INSPECTION FOR PREFABRICATED CONSTRUCTION SHALL BE THE SAME AS IF THE MATERIAL USED IN THE CONSTRUCTION TOOK PLACE ON SITE. CONTINUOUS INSPECTION WILL NOT BE REQUIRED DURING PREFABRICATION IF THE APPROVED AGENCY CERTIFIES THE CONSTRUCTION AND FURNISHES EVIDENCE OF
COMPLIANCE.
SCALE: 1/2" = 1'-0"A3 TYPICAL CORNER REINFORCEMENT
SCALE: 3/4" = 1'-0"B2 TYPICAL PIPE SLEEVE
SCALE: 3/4" = 1'-0"A2 SLAB AT CONSTRUCTION JOINT
SCALE: 3/4" = 1'-0"B1 SLAB AT CONTROL JOINT
SCALE: 3/4" = 1'-0"A1 SLAB AT GRADE
SCALE: 1/2" = 1'-0"B3 UTILITIES AT FTG
CF24 2'-0" CONT. 1'-3" (3) #5 CONTINUOUS WITH #5 @ 12" O.C.
TRANSVERSE
8" THICK FOUNDATION WALL TO HAVE #5 @ 12" O.C. EACH
WAY. TERMINATE WITH 6" 90 DEGREE HOOKS SPLICED TO
BOTTOM MAT OF REINFORCING IN FOOTING.
CF08 0'-8" CONT. 3'-4" #5 @ 12" O.C. VERTICAL AND HORIZONTAL
UP
D1 S1.2
D1 S1.2
S1.2 D2
C F
(8 '-0
CF52 -(8'-0")
C F
(8 '-0
C F
(8 '-0
EXISTING CONC FTG
EXISTING CONC FTG
C F
(8 '-0
C F
(8 '-0
C F
(8 '-0
111111
D1 S1.3
C1 S1.3
A3 S1.3
D1 S1.3
A1 S1.3
B3 S1.3
F1 S1.3
C F
(8 '-0
CF08 -(4'-0")
S1.3 C3
2' -0
1'
-5
0' -3
1'
-4
0' -8
/2
3'
-0
/2
2' -8
/2
± 8'-8" 15'-8" ± 12'-3"
'-0
'-6
6' -6
/2
'-0
'-0
/2
9' -1
1/
2"
3 3 3
35 5
3" ± 2'-1"
1'-0" MAX ±6'-0", V.I.F.
EXISTING WILL CALL BAY BAY #9 BAY #8
± 7'-6" V.I.F.
1'-0" ± 11'-2" 8" 11'-10" 8" ± 12'-3" 1'-0"
'-0
/2
0' -1
7'
-0
4' -0
1'
-1 0"
1' -5
1'
-0
'-2
/2
'-4
5' -0
'-0
/2
± 36'-7"
9' -4
/2
1' -0
2'
-0
1' -5
0'
-3
1' -4
1'
-3
0' -0
5'
-2
/2
2' -5
/2
1'-0" ± 12'-3" 1'-0"
8'-0"
38'-7"
A. FIELD VERIFY ALL EXISTING DIMENSIONS, SITE CONDITIONS, AND BUILDING
CONDITIONS PRIOR TO WORK.
B. THESE DEMOLITION DRAWINGS REPRESENT THE LAYOUT OF EXISTING CONDITIONS
& MAJOR COMPONENTS. THEY ARE NOT TO BE CONSTRUED AS A COMPLETE
REPRESENTATION OF MATERIALS & INCIDENTAL CONSTRUCTION.
C. DEMOLISH AND/OR REMOVE ALL COMPONENTS AS NOTED ON THE DRAWINGS AND
AS NECESSARY TO ACHIEVE NEW WORK IF NOT EXPLICITLY SHOWN AS
DEMOLISHED. PATCH AND REPAIR ADJACENT SURFACES TO ACCOMMODATE NEW
WORK. MAINTAIN ADJACENT SURFACES TO ORIGINAL CONDITIONS. ANY DAMAGE OF
EXISTING CONDITIONS SHALL BE REPAIRED TO ORIGINAL OR BETTER CONDITION.
D. ALL MATERIALS THAT HAVE BEEN DEMOLISHED SHALL BE REMOVED AND DISPOSED
OF PROPERLY. NO DEMOLISHED MATERIALS SHALL BE STOCKPILED ON SITE.
E. PROTECT OWNER'S PROPERTY AND PERSONS AT ALL TIMES. THIS INCLUDES ALL
ITEMS AND SERVICES NECESSARY TO DEMOLISH OR DISMANTLE AND REMOVE ALL
WALLS, EQUIPMENT, PIPING, AND APPURTENANCES WHICH WILL INTERFERE WITH
NEW CONSTRUCTION. ALL ITEMS TO BE REMOVED SHALL BE COORDINATED WITH
NEW CONSTRUCTION.
F. ANY ITEMS NOT SHOWN TO BE DEMOLISHED THAT ARE DAMAGED DURING THE
COURSE OF DEMOLITION OR CONSTRUCTION SHALL BE REPAIRED/REPLACED BY
THE CONTRACTOR AT THE CONTRACTOR'S EXPENSE.
G. COORDINATE ANY SYSTEMS SHUTDOWNS WHICH MAY BE REQUIRED WITH THE
OWNER.
H. PROVIDE APPROPRIATE TEMPORARY OR PERMANENT SUPPORT WHEREVER
OPENINGS ARE CREATED IN EXISTING CONSTRUCTION AS REQUIRED.
I. EXISTING CONSTRUCTION SHALL BE PROTECTED.
J. BUILDING FINISH FLOOR ELEVATION = 0'-0"
SCALE: 1/4" = 1'-0"F1 SELECTIVE DEMOLITION PLAN
B ACDE
F
B ACDEF
S T
R U
C T
U R
A L
E N
G
IN
E E
R
F O
LD
K el lo gg
A ve
A m es , I
A
P h on e:
.2
.0
F a x:
.2
.0
A R
C H
IT
E
C T
F
O
LD
K el lo gg es , I
A
P h on e:
.2
.0
F a x:
-2
2-
©2026REVISIONS:
PROJECT NUMBER
PROJECT ISSUE DATE
REV DATE DESCRIPTION
S1.1
DEMO & FOOTING PLAN
A T
O D
W ill
C al l R am p R ep la ce m en t
S ta te o f I ow a
D ep ar tm en t o f A dm in is tr at iv e
S er vi ce s
S E
H ul si ze r R d.
, A nk en y, IA
06/22/2026 9534.00
BIDDING DOCUMENTS
SCALE: 1/4" = 1'-0"D1 FOOTING PLAN
FOOTING PLAN NOTES
1 EXISTING FOUNDATION WALL EXTENSION
2 8" CONCRETE SLAB W/ #5 AT 1'-0" O.C. BOTH WAYS OVER 6" DRAINAGE FILL OVER
COMPACTED SUBGRADE.
3 6" CONCRETE SLAB WITH TOP AND BOTTOM MAT OF #5 @ 1'-0" O.C. EACH WAY
OVER VOID FORMS OVER COMPACTED STRUCTURAL FILL. SPLICE ALL BARS TO
BENT VERTICAL REINFORCEMENT IN PERIMETER WALLS. NORTH-SOUTH
REINFORCEMENT TO BE ON THE BOTTOM OF REINFORCEMENT MATS.
4 PIN SLAB TO FROST SLAB WITH SMOOTH, GREASED 2'-0" LONG #5 DOWELS AT 2'-0"
O.C. PROVIDE 6" MIN. DRILL DOWEL AND EPOXY WITH 6" MIN. EMBEDMENT.
5 EXISTING CONCRETE FOUNDATION WALL
6 8" CONCRETE WALL- SEE SCHEDULE FOR REINFORCING
7 DRILL, DOWEL, AND EPOXY ALL PERPENDICULAR REINFORCEMENT BARS INTO
EXISTING FOOTING, 6" EMBEDMENT. CLEAN AND SCARIFY FACE OF EXISTING
FOOTING ACCORDING TO REQUIREMENTS IN GENERAL STRUCTURAL NOTES.
8 SEE DETAILS FOR REQUIRED SPLICING AT ALL FOUNDATION WALL AND FOOTING
INTERSECTIONS, TYP.
9 SLAB CONTROL JOINT - SEE DETAILS.
10 6" CONCRETE-FILLED STEEL PIPE BOLLARD. EXTEND DOWN TO FOOTING.
11 EXISTING FOOTING DEPTH AND THICKNESS BASED ON SITE INVESTIGATION
PERFORMED BY CONTRACTOR. ALERT STRUCTURAL ENGINEER IF DIMENSIONS
DISCOVERED DURING EXCAVATION DIFFER THAN THOSE SHOWN. DO NOT
UNDERMINE EXISTING FOOTINGS, EITHER DIRECTLY OR WITHIN THE ANGLE OF
INCIDENCE OF THE BEARING LOAD ON THE SOIL. CONTACT STRUCTURAL
ENGINEER IF ANY UNDERMINING IS SUSPECTED.
13 GALVANIZED STEEL GUARDRAIL WITH HORIZONTALS AT +42" AND +21" FROM
FINISHED SLAB ELEVATION.
14 PROVIDE EXPANSION JOINT WITH NO POSITIVE MECHANICAL ANCHORAGE
BETWEEN SLAB AND WALL.
15 12" CONCRETE WALL - SEE SCHEDULE FOR REINFORCING
16 CUT HSS12x0.375 WITH 1/2" EXPANSION ANCHOR AT 2'-0" O.C., FULLY GROUTED
AND FULL HEIGHT OF CONCRETE WALL
17 SEE DETAILS FOR REQUIRED SMOOTH BAR DOWELS AT JOINT BETWEEN NEW AND
EXISTING CONCRETE SLABS.
18 CHAIN LINK CONSTRUCTION FENCE - SEE SELECTIVE DEMOLITION PLAN
DEMO PLAN NOTES
1 REMOVE RAMP CONCRETE SLAB
2 REMOVE CONCRETE SLAB
3 REMOVE CONCRETE PANEL TO INDICATED JOINT LINE
4 SAWCUT AND REMOVE CONCRETE PANEL; EXTEND SAW CUT LINE TO FOUNDATION
5 REMOVE RETAINING WALL AND ASSOCIATED FOOTING
6 REMOVE GUARDRAILS
7 REMOVE EXISTING THRESHOLD CURB DOWN TO TOP OF FOUNDATION WALL; PREP FOR
NEW THRESHOLD CURB
8 REMOVE EXISTING DRAIN INLET AND SALVAGE FOR REINSTALLATION
9 EXISTING 18" DRAIN LINE, APPROXIMATELY 8'-8" BELOW FINISH FLOOR; PROTECT FOR
DURATION OF CONSTRUCTION; ENSURE SLOPE IS MAINTAINED TO PROVIDE POSITIVE
DRAINAGE TO COLLECTOR LINE TO SOUTH
10 EXISTING STORM SEWER MANHOLE - PROTECT DURING CONSTRUCTION
11 EXISTING HOSE BIBB IN EXTERIOR WALL, ±8" AFF - PROTECT DURING CONSTRUCTION
12 GRIND FLUTED FINISH OF PRECAST FLUSH TO CREATE SMOOTH SURFACE FOR NEW
STOOP SLAB
13 MIN. 8-FT HIGH CHAIN LINK CONSTRUCTION FENCE LOCATED WITHIN 1'-0" OF CUT EDGE
OF PAVING
14 REMOVE EXISTING CRACKED CONCRETE PANEL TO INDICATED JOINT LINES; PROTECT
AND MAINTAIN LOCATION OF MANHOLE DURING CONSTRUCTION
GENERAL NOTES
UP
D1 S1.2
D1 S1.2
S1.2 D2
1/
4"
3'-0" MIN.
-4'-0"
-1 1/4"
0" (E) FF SLAB
-3'-9 11/16"
6 3/4"
6 3/4" -1 1/4"
3'-2" 10" 4'-0" 10"
'-1
1/
2"
'-1
3'-3" 4'-0" OPENING 1'-7" 4'-5" 8'-0" OPENING 1'-7" 10"
3" MIN CLR
-4'-0"
8'-10" 14'-0" 10"
1/
2"
7'-0"
-4'-3 1/2"
-4'-6"
-4'-6"
-4'-2"
-4'-0"
-4'-5"
-4'-8"
-4'-2"
-3'-11"
-4'-3 1/2"
-4'-2 1/2"
-4'-0 1/2"
-4'-0"
-4'-2 1/8"
-4'-0"
-4'-4"
-4'-5 1/2"
-4'-4 1/2"
-4'-1"
-3'-10 1/2"
-3'-8 1/2"
-4'-0 1/2"
4 4 4
1:
-4'-6"
-1 1/4"
-4'-6"
-4'-8 1/2"
-4'-6"
-4'-6"
-4'-3 5/8"
MAX 150 OCC.
3'-9"
'-0
/2
'-0
3' -1
0" 1'
-2
6' -5
'-0
4'-10"
15 15
-1 1/4" -1 1/4"
-7 7/8"
T.O. FF SLAB
0"
B.O. RAMP
-4'-0"
T.O. SLAB
-1 1/4"
1:10
3' -0
3' -6
9'-5 3/4" 47'-4 1/2"
1' -4
1'
-9
5"
T.O. FF SLAB
0"
B.O. RAMP
-4'-0"
T.O. FOOTING
-8'-0"
1:10
3' -0
T.O. SLAB
-1 1/4"
EXISTING BUILDING
FOUNDATION WALL
S1.3 B3
57'-4 1/2"
BUILDING INFORMATION
• OCCUPANCY: S-1, MODERATE-HAZARD STORAGE
• TYPE IIB
• SPRINKLERED
• OCCUPANT LOAD: 61
• EXISTING BUILDING HEIGHT, AREA, NUMBER OF STORIES, AND EXTERIOR WALL
RATING SHALL BE ACCEPTED.
• NO INTERNAL COMPONENTS OF THE BUILDING WILL BE AFFECTED BY PROJECT.
IMPACT IS ONLY TO THE EXIT DISCHARGE PORTION OF THE MEANS OF EGRESS.
IBC 2024
CHAPTER 10 - MEANS OF EGRESS
1003.1 General Means of Egress - Applicability. The general requirements specified in Sections 1003 through 1015 shall apply to all three elements of the means of egress system, in addition to those specific requirements for the exit access, the exit, and the exit discharge details elsewhere in this chapter.
Table 1006.2.1 Spaces with One Exit or Exit Access Doorway. For Group S occupancies with greater than 29 occupants or a common path of egress travel distance greater than 100 feet, two exits or exit access doorways shall be provided.
1006.2.2.5. Egress Based on Use – Vehicular Ramps. Vehicular ramps shall not be considered as an exit access ramp unless pedestrian facilities are provided.
1011.2 Stairways – Width and Capacity. The required capacity of stairways shall be determined as specified in Section 1005.1, but the minimum width shall be not less than 44 inches.
1011.11 Stairways – Handrails. Flights of stairways shall have handrails on each side and shall comply with Section 1014. […]
1028.2 Exit Discharge. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide a direct path of egress travel to grade. The exit discharge shall not reenter a building. [...]
1028.5 Exit Discharge - Access to a Public Way. The exit discharge shall provide a direct and unobstructed access to a public way.
IEBC 2024
CHAPTER 3 - PROVISIONS FOR ALL COMPLIANCE METHODS
306.7.2 Alterations - Accessible Means of Egress. Accessible means of egress required by Chapter 10 of the International Building Code are not required to be added in existing facilities.
CODE PLAN GENERAL NOTES
B ACDE
F
B ACDEF
S T
R U
C T
U R
A L
E N
G
IN
E E
R
F O
LD
K el lo gg
A ve
A m es , I
A
P h on e:
.2
.0
F a x:
.2
.0
A R
C H
IT
E
C T
F
O
LD
K el lo gg es , I
A
P h on e:
.2
.0
F a x:
-2
2-
©2026REVISIONS:
PROJECT NUMBER
PROJECT ISSUE DATE
REV DATE DESCRIPTION
S1.2
LAYOUT PLAN &
ELEVATIONS
A T
O D
W ill
C al l R am p R ep la ce m en t
S ta te o f I ow a
D ep ar tm en t o f A dm in is tr at iv e
S er vi ce s
S E
H ul si ze r R d.
, A nk en y, IA
06/22/2026 9534.00
BIDDING DOCUMENTS
SCALE: 1/4" = 1'-0"F1 LAYOUT PLAN
SCALE: 1/4" = 1'-0"D2 WEST ELEVATION
SCALE: 1/4" = 1'-0"D1 LONGITUDINAL SECTION THROUGH RAMP
LAYOUT PLAN NOTES
1 NEW CONCRETE VEHICULAR RAMP; SLOPE = 1:10 (10%); SEE STRUCTURAL DRAWINGS
FOR DETAILS
2 NEW CONCRETE VEHICULAR RAMP LANDING; MIN. CROSS-SLOPE = 1/4" : 12" FOR
PROPER DRAINAGE; SEE STRUCTURAL DRAWINGS FOR DETAILS
3 NEW CONCRETE STOOP; MIN. CROSS-SLOPE = 1/4" : 12" FOR PROPER DRAINAGE; SEE
STRUCTURAL DRAWINGS FOR DETAILS
4 NEW CONCRETE PANEL - SEE STRUCTURAL DRAWINGS FOR DETAILS
5 NEW CONCRETE STAIR - SEE STRUCTURAL DRAWINGS FOR DETAILS
6 NEW CONCRETE STAIR LANDING - SEE STRUCTURAL DRAWINGS FOR DETAILS
7 NEW CONCRETE RETAINING WALL AND FOOTING - SEE STRUCTURAL DRAWINGS FOR
DETAILS
8 NEW SURFACE MOUNTED GALVANIZED STEEL GUARDRAIL; PAINT WITH HIGH
PERFORMANCE COATING; COLOR: SAFETY YELLOW
9 NEW SURFACE MOUNTED GALVANIZED STEEL HANDRAIL; PAINT WITH HIGH
PERFORMANCE COATING; COLOR: SAFETY YELLOW
10 NEW CONCRETE THRESHOLD CURB INSTALLED ON TOP OF EXISTING BUILDING
FOUNDATION WALL; SLOPE TOP OF CURB 1":12" TO THE EXTERIOR TO PROMOTE
POSITIVE DRAINAGE; SEE STRUCTURAL DRAWINGS FOR DETAILS
11 REINSTALL SALVAGED DRAIN INLET
12 EXISTING 18" DRAIN LINE, APPROXIMATELY 8'-8" BELOW FINISH FLOOR; PROTECT FOR
DURATION OF CONSTRUCTION; ENSURE SLOPE IS MAINTAINED TO PROVIDE POSITIVE
DRAINAGE TO COLLECTOR LINE TO SOUTH
13 EXISTING STORM SEWER MANHOLE - PROTECT DURING CONSTRUCTION
14 EXISTING HOSE BIBB IN EXTERIOR WALL, ±8" AFF - PROTECT DURING CONSTRUCTION;
PROVIDE A MINIMUM OF 3" CLEAR BETWEEN HOSE BIBB AND NEW RETAINING WALL
15 STEEL WALL CAP - SEE STRUCTURAL DETAILS; PAINT WITH HIGH PERFORMANCE
COATING; COLOR: YELLOW
16 NEW CONCRETE PANEL - SEE STRUCTURAL DRAWINGS FOR DETAILS; PROTECT AND
MAINTAIN LOCATION OF MANHOLE DURING CONSTRUCTION
17 PAINT CONCRETE AS NEEDED TO RESTRIPE LANE AND ACCESS AISLE MARKINGS AT
BAYS 9 AND 8 - COORDINATE WITH OWNER FOR EXACT LOCATIONS
18 MATCH EXISTING TOP OF CONCRETE GRADES
19 CHAIN LINK CONSTRUCTION FENCE - SEE SELECTIVE DEMOLITION PLAN
T.O. FOOTING
-8'-0"
PCC SLAB OVER COMPACTED
STRUCTURAL FILL - SEE PLAN
1/2" EXPANSION JOINT. NO
POSITIVE MECHANICAL
CONNECTION.
REINFORCED CONCRETE WALL.-
SEE PLAN
REINFORCED CONCRETE
FOOTING - SEE PLAN
GALVANIZED GUARDRAIL.
SEE SCHEDULE
S E
E S
C H
E D
1'-6"
CLR
2"
3" C
LR
3" CLR
PCC SLAB OVER COMPACTED
STRUCTURAL FILL - SEE PLAN
1/2"x6"x6" STEEL PLATE W/
(4) 1/2"x4" HILTI KWIK BOLT
III ANCHORS.
1/2" EXPANSION JOINT. NO
POSITIVE MECHANICAL
CONNECTION.
2x6 KEYWAY
VERTICAL DOWELS WITH 1'-9" LEG -
MATCH WALL REINFORCING SIZE
AND SPACING
2" CLR
ARCHITECTURAL-GRADE
CONCRETE FINISH REQUIRED ON
ALL EXPOSED FACES OF
CONCRETE, TYP. SEE
SPECIFICATIONS FOR MORE
REQUIREMENTS
REINFORCED CONCRETE
SLAB - SEE PLAN
VOID FORM - SEE PLAN
REINFORCED CONCRETE WALL.-
SEE PLAN
REINFORCED CONCRETE
FOOTING - SEE PLAN
GALVANIZED GUARDRAIL.
PCC SLAB OVER COMPACTED
STRUCTURAL FILL - SEE PLAN
1/2"x6"x6" STEEL PLATE W/
(4) 1/2"x4" HILTI KWIK BOLT
III ANCHORS.
1/2" EXPANSION JOINT. NO
POSITIVE MECHANICAL
CONNECTION.
VERTICAL DOWELS WITH 1'-6" LEG -
MATCH WALL REINFORCING SIZE
AND SPACING
1' -4
1'
-9
1/
4"
2" CLR
SEE SCHEDULE
S E
E S
C H
E D
1'-0"
3" CLR
3" C
LR
ADDITIONAL #4 REBAR AT
PERIMETER
DOWEL W/ 3'-0" LEGS -
MATCH SLAB REINFORCING
SIZE AND SPACING
SLAB REINFORCING -
PLACE BARS RUNNING
EAST-WEST ON BOTTOM.
1 1/2"
SEE SCHEDULE
3" C
LR
REINFORCED CONCRETE
SLAB - SEE PLAN
VOID FORM - SEE PLAN
DOWEL W/ 3'-0" LEGS -
MATCH SLAB REINFORCING
SIZE AND SPACING
SLAB REINFORCING -
PLACE BARS RUNNING
EAST-WEST ON BOTTOM.
REINFORCED CONCRETE WALL.-
SEE PLAN
REINFORCED CONCRETE
FOOTING - SEE PLAN
VERTICAL DOWELS WITH 1'-6" LEG -
MATCH WALL REINFORCING SIZE
AND SPACING. ALTERNATE LIEG
DIRECTION
S E
E S
C H
E D
PCC SLAB OVER COMPACTED
STRUCTURAL FILL - SEE PLAN
3/4"DIAx1'-0" DOWEL AT 1'-0" O.C.
REINFORCED CONCRETE
SLAB - SEE PLAN
VOID FORM - SEE PLAN
SLAB REINFORCING -
PLACE BARS RUNNING
EAST-WEST ON BOTTOM.
1/2" EXPANSION JOINT
MATERIAL
EXISTING CONCRETE WALL
EXISTING CONC SLAB
REINFORCED CONCRETE
SLAB - SEE PLAN
#4 DOWEL W/ 7" LEGS AT
1'-0" O.C.. DRILL AND EPOXY
INTO EXISTING CONC WALL
W/ 4" EMBED
1/2" EXPANSION JOINT
MATERIAL
EXISTING CONCRETE WALL
EXISTING CONC SLAB
EXISTING OVER HEAD DOOR
SLOPE THRESHOLD 1"
REINFORCED CONCRETE
THRESHOLD CURB - SEE PLAN
REINFORCED CONCRETE WALL.-
SEE PLAN
REINFORCED CONCRETE
FOOTING - SEE PLAN
PCC SLAB OVER COMPACTED
STRUCTURAL FILL - SEE PLAN
1/2" EXPANSION JOINT. NO
POSITIVE MECHANICAL
CONNECTION.
2x6 KEYWAY
VERTICAL DOWELS WITH 1'-9" LEG -
MATCH WALL REINFORCING SIZE
AND SPACING
DOWEL W/ 3'-0" LEGS - MATCH
SLAB/STAIR REINFORCING SIZE
AND SPACING
VOID FORM - SEE PLAN
SLAB REINFORCING -
PLACE BARS RUNNING
EAST-WEST ON BOTTOM.
#4 NOSING BAR, TYPICAL
CONCRETE STEPS W/ #5 BARS AT 1'-0" O.C.
BOTH DIRECTIONS. PLACE BARS RUNNING
NORTH-SOUTH ON BOTTOM.
ACCEPTABLE FOR CONTRACTOR
TO ABANDON FORMING IN PLACE
CONCRETE WALL -
SEE PLAN
SET EDGE OF PIPE 1/4"
FROM EDGE OF CONCRETE
WALL; ENSURE THAT
NEITHER SIDE OF PIPE
EXTENDS PAST FACE OF
CONCRETE
WALL - REINFORCING -
SEE SCHEDULE
FULLY INFILL W/
GROUT AND ROUND
TOP TO SHED WATER
1/2" DIA.x8" HILTI -KWIK BOLT
3 ANCHORS AT 2'-0" O.C.
5" 1'
-9
1' -4
3' -6
T Y
P
4"
9'-5 3/4" 3'-4 1/2"
EQ. EQ.
7'-10 1/4"
EQ. EQ.
3' -6
2' -1
0"
1' -6
1'
-4
8'-4"
5 3/4" 3'-8 3/4" 4'-1 1/2"
2' -1
0" 1' -4
1'
-6
3" 57'-4 1/2" 5" 3'
-6
8" 2'
-1 0"
1' -6
1'
-4
EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ.
5" 47'-4 1/2" 3"
EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ.
3' -0
2'
-1 0"
GUARDRAIL
HANDRAIL
3' -0
2'
-1 0"
1' -4
1'
-6 " 2' -1
0" 8"
3' -6
LANDING WEST & SOUTH GUARDRAIL STAIR
EAST HANDRAIL
STAIR
WEST GUARD/HANDRAIL
RAMP WEST RETAINING WALL GUARDRAIL
RAMP EAST RETAINING WALL GUARDRAIL
1'-0"
1'-0"
11" 11"
B ACDE
F
B ACDEF
S T
R U
C T
U R
A L
E N
G
IN
E E
R
F O
LD
K el lo gg
A ve
A m es , I
A
P h on e:
.2
.0
F a x:
.2
.0
A R
C H
IT
E
C T
F
O
LD
K el lo gg es , I
A
P h on e:
.2
.0
F a x:
-2
2-
©2026REVISIONS:
PROJECT NUMBER
PROJECT ISSUE DATE
REV DATE DESCRIPTION
S1.3
RAMP DETAILS
A T
O D
W ill
C al l R am p R ep la ce m en t
S ta te o f I ow a
D ep ar tm en t o f A dm in is tr at iv e
S er vi ce s
S E
H ul si ze r R d.
, A nk en y, IA
06/22/2026 9534.00
BIDDING DOCUMENTS
SCALE: 3/4" = 1'-0"D1 RETAINING WALL AT RAMP
SCALE: 3/4" = 1'-0"C1 RETAINING WALL AT STOOP
SCALE: 3/4" = 1'-0"A1 FOUNDATION WALL AT TRANSITION
SCALE: 3/4" = 1'-0"A3 STOOP AT (E) WALL
SCALE: 3/4" = 1'-0"B3 THRESHOLD AT OVERHEAD DOOR
SCALE: 3/4" = 1'-0"F1 SECTION AT STAIRS
SCALE: 1 1/2" = 1'-0"C3 STEEL CAP AT WALL
SCALE: 1/4" = 1'-0"F3 RAILING DETAILS
| Sheets |
| G0.0 - COVER |
| S1.0 - STRUCTURAL NOTES & DETAILS |
| S1.1 - DEMO & FOOTING PLAN |
| S1.2 - LAYOUT PLAN & ELEVATIONS |
| S1.3 - RAMP DETAILS |
File details come from the government source that posted it. Updated .