Revised - Exhibit _6_-Generator_Repair_Item 3-19-26SS.xlsx
XLSX spreadsheet 17 KB Posted
- Solicitation number
- BPM055828
- Issued by
- Carroll County, Maryland
About this file
This is a generator repair specification document for the Maryland Department of Health's Springfield Hospital Center (SHC), a Joint Commission accredited mental health facility located in Sykesville, Maryland. The document details repair requirements for eleven (11) emergency generators distributed across multiple facility locations that provide backup power during outages. The repair services encompass inspection, troubleshooting, load testing, and corrective maintenance to restore reliable generator operation. The generators requiring repair are located at Administration, Geriatrics, Salomon, Food Services, Mckeldin, Maintenance Shops, Canteen, Store Room, M&S, Muncie Barn, and C4 locations. Equipment specifications include Cummins and Kohler generators ranging from 35 kilowatts to 215 kilowatts, manufactured between 2003 and 2016, with varying serial and engine modification numbers documented for each unit.
The repairs needed across all eleven generators include common maintenance tasks such as water pump replacement, oil cooler and hose replacement, thermostat replacement, block heater and hose replacement, cooling system flushing and antifreeze replacement, transfer switch replacement, gas valve replacement, engine block heater hose replacement, vacuum harness replacement, and radiator hose replacement. Several units require more complex work including turbocharger oil drain repair, engine tune-ups, spark plug and wire replacement, gas piping re-sealing, seal and gasket replacement, governor system and controller replacement, and one unit requires a complete controls upgrade including a Deep Sea controller kit with new wiring harness, voltage regulator, speed controller, and sensor installation with load bank programming and adjustment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Location | Make/Model | S/N (#KW) - Year | Eng mod/Serial # |
| Administration | Cummins/GGHE-5656823 | A0593995 (60KW) 2003 | WSG1068/042520574 |
| Repairs Needed | Replace Cummins Water pump | ||
| Repairs Needed | Replace Cummins Oil cooler and hoses | ||
| Repairs Needed | Replace Thermostat and Hoses | ||
| Repairs Needed | Replace Block Heater and Hoses | ||
| Repairs Needed | Flush Cooling System and Replace Antifreeze |
| Location | Make/Model | S/N (#KW) - Year | Eng Mod/Serial # |
| Geriatrics (Big G) | Cummins GGHE-5656836 | A040593403 (60KW) - 2005 | WSG10681-6005A/04-01-076645 |
| Repairs Needed | Replace Thermostat | ||
| Repairs Needed | Replace Cooling System Hoses | ||
| Repairs Needed | Flush Coolant System and Replace Antifreeze | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Salomon | Kohler/180REZXB | SGM32GL9 (180KW) - 2016 | GM99499-GA1/SGM32GML9 |
| Repairs Needed | Repair LeakingTurbo Charger Oil Drain | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Food Services | Cummins/GTA 855 | KM044063760 (215KW) - 2005 | GTA85562/25297022 |
| Repairs Needed | Engine Tune up | ||
| Repairs Needed | Replace Spark Plugs and Wires | ||
| Repairs Needed | Re-seal Gas Piping in Unit | ||
| Repairs Needed | Replace Seals and Gaskets in Oil Cooler | ||
| Repairs Needed | Replace engine govenor system due to existing parts being obsolete | ||
| Repairs Needed | Install new govenor controller and actuator | ||
| Repairs Needed | Install conversion kit and set and adjust unit with load. |
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Mckeldin | Cummins/GGKB-5656842 | A040593402 (125 KW) - 2003 | GTA83G1/46357342 |
| Repairs Needed | Replaice Oil Cooler | ||
| Repairs Needed | Replace Thermostat | ||
| Repairs Needed | Replace Water Pump | ||
| Repairs Needed | Replace Radiator and Oil Cooler Hoses | ||
| Repairs Needed | Flush coolant system and replace Antifreeze | ||
| Repairs Needed | Replace 2 Transfer Switches | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Maintenance Shops | Kohler/60R26 | 2101538 (60KW) - 2006 | -------- |
| Repairs Needed | Replace Block Heater and Block Heater Hose | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Canteen | Cummins/GGHE - 5656835 | A040593396 (60KW) - 2003 | WSG-10681-6005- A/04-01-076632 |
| Repairs Needed | Replace Engine Block Heater | ||
| Repairs Needed | Replace Heater Block Hoses | ||
| Repairs Needed | Replace Gas Valve at the Gas Supply | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Store Room | Cummins/GGFD-5656827 | A040593399 (35KW) - 2003 | ESG642/042K21820 |
| Repairs Needed | Replace Gas Valve at Gas Supply | ||
| Repairs Needed | Replace Engine Block Heater | ||
| Repairs Needed | Replace Engine Block Heater Hose | ||
| Repairs Needed | Replace Engine Vacuum Harness | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| M&S | Cummins/GGKB-5656831 | A040593398 (125KW) - 2003 | GTA8361/46358374 |
| Repairs Needed | Replace Water Pump | ||
| Repairs Needed | Replace Radiator Hoses | ||
| Repairs Needed | Replace Block Heater | ||
| Repairs Needed | Replace Block Heater Hoses | ||
| Repairs Needed | Replace Thermostat | ||
| Repairs Needed | Flush Coolant System and Replace Antifreeze | ||
| Location | Make/Model | S/N (#KW) | Eng Mod/Serial # |
| Muncie Barn | Kohler/60RZG | 2093568(60kw) - 2007 | |
| Repairs Needed | Replace Engine Block Heater | ||
| Repairs Needed | Replace Engine Bock Heater Hoses | ||
| Repairs Needed | Flush Coolant System and Replace Antifreeze |
| Location | Make/Model | S/N (#KW) Year | Eng Mod/Serial # |
| C4 | Cummins/GGKB-5656830 | A040593400 (125KW)-2003 | GTA83G1/46358431 |
| Repairs Needed | Complete Controls Upgrade: Deep sea controller kit with new wiring harness, voltage regulator, speed controller, throttle body, CTS and sensors. | ||
| Repairs Needed | Program and adjust as needed with a load bank |