Plans_and_Drawings_-_Event_4234.pdf
PDF 6 MB Posted
- Attached to
- Bid-PW Hawthorne Fire Alarm Replacement
- Solicitation number
- 0000004234
- Issued by
- Hennepin County, Minnesota
About this file
This document is a set of construction plans and drawings for the Hawthorne Municipal Parking Ramp Fire Alarm System Replacement project for the City of Minneapolis, Division of Traffic and Parking Services. The project involves the complete replacement of the fire alarm system at the Hawthorne Parking Ramp located at 31 North 9th Street, Minneapolis, Minnesota (Project Number 23978.000). The scope of work includes disconnecting and removing all existing fire alarm devices and wiring, installing a new Notifier Inspire Series addressable fire alarm system with notification appliances (horn/strobes only), providing conduit and conductors for system wiring, installing addressable modules for flow and tamper switches on existing riser piping, providing duct smoke detectors with control relays for HVAC integration, coordinating elevator fire alarm controls with an elevator contractor, and providing monitor modules for fire pump and fire smoke damper connections. The project encompasses multiple floors including the basement, first through seventh floors, and penthouse areas, with device locations shown across multiple area plans (Areas A and B for most floors).
The construction documents include comprehensive specifications requiring all work to comply with NFPA standards and state and local fire codes, with fire-rated wall penetrations to be sealed using listed fire stop systems. All fire alarm conduit must be color-coded red, with specific installation requirements for concealed versus exposed routing. The contractor must provide temporary wiring and generators to maintain power to operational areas during construction, include contractor premium time for scheduled interruptions, field-verify all existing conditions before rough-in, provide updated panelboard schedules, coordinate with the Building Automation System (BAS) contractor for system integration, and deliver as-built red-line marked drawings and a complete program download on flash drive upon project completion. The existing fire pump control panel, fire alarm network node panel, flow and tamper switches, and fire smoke dampers are to remain operational, with new monitoring and interface connections provided for integration with the new fire alarm control panel.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
G000
TITLE SHEET
DANIEL COLVIN
PROJECT MANAGER
PHONE: (612) 673-2788
E-MAIL: DANIEL.COLVIN@MINNEAPOLISMN.GOV
OWNER REPRESENTATIVE
TODD VOLKMEIER
PROJECT MANAGER
TKDA
3311 E. OLD SHAKOPEE RD., SUITE 300
BLOOMINGTON, MN 55425
PHONE: (651) 292-4404
E-MAIL: TODD.VOLKMEIER@TKDA.COM
CONTACT INFORMATION
TKDA REPRESENTATIVES
SITE LOCATION MAP
ELECTRICAL
SHEET INDEX
SHEET NO. DESCRIPTION
G000 TITLE SHEET
ED000 SYMBOLS & ABBREVIATIONS DEMO
E000 SYMBOLS & ABBREVIATIONS
ED100 FIRE ALARM - SE OFFICE BASEMENT - DEMO PLAN
ED101 FIRE ALARM - FIRST FLOOR - DEMO PLAN
ED103 FIRE ALARM - THIRD FLOOR - DEMO PLAN
ED104 FIRE ALARM - FOURTH FLOOR - DEMO PLAN
ED105 FIRE ALARM - FIFTH FLOOR - DEMO PLAN
ED106 FIRE ALARM - SIXTH FLOOR - DEMO PLAN
ED107 FIRE ALARM - SEVENTH FLOOR & PENTHOUSE FLOOR DEMO PLAN
E100 FIRE ALARM - SE OFFICE BASEMENT - PLAN
E101A FIRE ALARM - FIRST FLOOR - AREA A PLAN
E101B FIRE ALARM - FIRST FLOOR - AREA B PLAN
E103A FIRE ALARM - THIRD FLOOR - AREA A PLAN
E103B FIRE ALARM - THIRD FLOOR - AREA B PLAN
E104A FIRE ALARM - FOURTH FLOOR - AREA A PLAN
E104B FIRE ALARM - FOURTH FLOOR - AREA B PLAN
E105A FIRE ALARM - FIFTH FLOOR - AREA A PLAN
E105B FIRE ALARM - FIFTH FLOOR - AREA B PLAN
E106A FIRE ALARM - SIXTH FLOOR - AREA A PLAN
E106B FIRE ALARM - SIXTH FLOOR - AREA B PLAN
E107A FIRE ALARM - SEVENTH FLOOR & PENTHOUSE - AREA A PLAN
E107B FIRE ALARM - SEVENTH FLOOR & PENTHOUSE - AREA B PLAN
E200 FIRE ALARM RISER DIAGRAM
E201 FIRE ALARM SEQUENCE OF OPERATION
NGHI TRAN
ELECTRICAL ENGINEER
TKDA
3311 E. OLD SHAKOPEE RD., SUITE 300
BLOOMINGTON, MN 55425
PHONE: (651) 726-7974
E-MAIL: NGHI.TRAN@TKDA.COM
CONSTRUCTION DOCUMENTS
CITY OF MINNEAPOLIS
HAWTHORNE PARKING RAMP
FIRE ALARM SYSTEM REPLACEMENT
CITY OF MINNEAPOLIS -
TRAFFIC AND PARKING SERVICES
33 NORTH 9TH STREET
MINNEAPOLIS, MINNESOTA 55403
PROJECT LOCATION
HAWTHORNE MUNICIPAL PARKING RAMP
31 NORTH 9TH STREET
MINNEAPOLIS, MN 55403
PROJECT NUMBER: 23978.000
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED000
SYMBOLS &
ABBREVIATIONS
DEMO
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E000
SYMBOLS &
ABBREVIATIONS
EQUIPMENT
DEVICES
LIGHTINGFIRE ALARM
COMMUNICATION
T
JP
M
S
S
TV
S
J-BOX, 4-1/16"x4-1/16"x2-1/2" DEEP WITH 2 GANG RING
JACK, DATA
JACK, DATA/VOICE
JACK, TELEPHONE (VOICE)
JACK, TELEVISION
WIRELESS MICROPHONE RECEIVER
PROJECTOR
P.A. SYSTEM SPEAKER, CEILING MOUNTED SPEAKER
HORN TYPE SOUND
RE-INFORCEMENT SPEAKER MOUNTED ON 4" SQUARE JUNCTION BOX.
WI/FI ACCESS POINT CONTROL MODULE
DISCONNECT SWITCH
EQUIPMENT
KEYED SWITCH
MOTOR
MOTOR STARTER, COMBINATION
MOTOR STARTER, MAGNETIC
MOTOR STARTER, MANUAL
PANEL, ANNUNCIATOR/ALARM
PANEL, AS DESIGNATED
PANEL, POWER PANEL
PANEL, POWER (FLUSH)
PANEL, TERMINAL CABINET
TIME SWITCH
TRANSFORMERT
TS
s
CONTROL DEVICE (PL- PILOT
LIGHT, PC PHOTOCELL, PB- PUSHBUTTON,MS-MOTION
SENSOR,)
RECEPTACLE, CEILING DUPLEX
RECEPTACLE, DOUBLE DUPLEX
RECEPTACLE, DUPLEX, T - TAMPERPROOF
RECEPTACLE, SINGLE
RECEPTACLE, SPECIAL, NEMA# AS NOTED
RECEPTACLE, SPLIT WIRED
J-BOX, 4"X4"X2-1/2" DEEP
WITH 2 GANG RING
NO.
MTR
EQP
NO.
PB
CM
K
J s
M
NOTE:
ITEMS SHOWN ON THIS SHEET ARE STANDARD SYMBOLS AND ABBREVIATIONS AND MAY NOT ALL APPEAR ON THE PROJECT
DRAWINGS.
SYMBOLS GENERAL NOTESABBREVIATIONS
T a b
WI/FI
COMMON WORK
1. PROVIDE CONDUIT, CABLES OR CONDUCTORS TO MAINTAIN CIRCUIT
CONTINUITY FOR RELOCATED AND EXISTING TO REMAIN EQUIPMENT.
2. FIELD VERIFY ALL EXISTING CONDUIT AND WIRE SIZES. NOT ALL
CONDUIT IS SHOWN.
3. FIELD VERIFY CIRCUIT NUMBERS ON EXISTING EQUIPMENT.
4. FIELD VERIFY ROUTING OF PROPOSED RACEWAY. ROUTING SHOWN IS
SCHEMATIC AND INTENDED TO INDICATE INTENT.
5. CONSULT ENGINEER WHERE CONFLICTS OCCUR BETWEEN DRAWINGS
AND SPECIFICATIONS.
6. PROVIDE DEDICATED NEUTRALS FOR ALL CIRCUITS SUPPLYING LINE
TO NEUTRAL LOADS, BOTH 120V AND 277V.
7. PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS.
8. INCREASE ALL CIRCUIT CONDUCTOR SIZING TO ACCOUNT FOR
TEMPERATURE. ASSUME THE FOLLOWING NOMINAL AMBIENT
TEMPERATURES:
INDOOR CONDITIONED SPACES 80F
INDOOR UNCONDITIONED SPACES100F
OUTDOOR CONCEALED/SHADED 105F
OUTDOOR EXPOSED TO SUN 125F
OUTDOOR BELOW GRADE 80F
9. INCREASE ALL CIRCUIT CONDUCTOR SIZING TO ACCOUNT FOR
VOLTAGE DROP. LIMIT THE VOLTAGE DROP TO 3% PER SEGMENT AND
5% OVERALL IN ALL BRANCH CIRCUIT AND FEEDER WIRING. 20A
CIRCUIT CONDUCTORS AT A MINIMUM SHALL BE SIZED AS
FOLLOWS(CIRCUIT THAT DROP LOAD ALONG THE LENGTH MAY BE A
GREATER DISTANCE FOR THE WIRE GAUGE):
LENGTH LENGTH
AWG 120V 277V
#12 <65' <150' #10 65'-110' 150'-250' #8 110'-160' 250'-390' #6 >160' >390'
10. PROVIDE TEMPORARY WIRING AND/OR GENERATOR(S) TO MAINTAIN
POWER TO AREA OF THE BUILDING THAT MUST REMAIN OPERATIONAL
DURING CONSTRUCTION UNLESS SCHEDULED OUTAGES ARE
PRE-APPROVED BY THE OWNER.
11. BID TO INCLUDE CONTRACTOR PREMIUM TIME DUE TO SCHEDULING
OF POWER/COMMUNICATIONS INTERRUPTIONS.
12. PROVIDE A COMPLETE RED LINE MARKED UP SET OF AS-BUILT
DRAWINGS TO THE ENGINEER AT COMPLETION OF CONSTRUCTION.
13. DO NOT PENETRATE STAIR ENCLOSURES WITH RACEWAY UNLESS IT
IS SERVING DEVICES/LIGHTS/EQUIPMENT LOCATED WITHIN THE STAIR
ENCLOSURE.
14. COORDINATE MOUNTING HEIGHT OF RECESS BOXES TO ALIGN WITH
MASONRY JOINTS AND CASEWORK.
15. POWER, CONTROL, SIGNAL, AND COMMUNICATION WIRING SHALL NOT
BE RUN IN THE SAME CONDUIT.
DEMOLITION
1. FIELD VERIFY EXISTING EQUIPMENT AND CONDUIT. LOCATIONS,
QUANTITIES, AND SIZES SHOWN ARE SCHEMATIC, APPROXIMATE, AND
FOR REFERENCE ONLY.
2. REMOVE WIRING BACK TO LAST ACTIVE SOURCE OR EXISTING DEVICE
TO REMAIN. EXTEND CIRCUITS TO EXISTING DEVICES/EQUIPMENT
THAT ARE TO REMAIN.
3. UPDATE PANEL DIRECTORIES AND NAMEPLATES TO REFLECT
DEMOLITION AND NEW WORK. LABEL AND TURN OFF ALL CIRCUIT
BREAKERS MADE SPARE BY DEMOLITION.
4. REMOVE EXPOSED JUNCTION BOXES, CONDUIT AND WIRING NOT
REUSED. NO ABANDONED IN PLACE EXPOSED RACEWAY IS ALLOWED.
PROVIDE COVERPLATE ON EXISTING RECESSED JUNCTION BOXES.
PROVIDE NEW COVERPLATES AS REQUIRED FOR NEW/REVISED
RECEPTACLES OR SWITCHES.
5. COORDINATE WITH OWNER FOR ANY REMOVED ITEMS THAT SHALL BE
SALVAGED FOR THEIR USE.
6. DISPOSE OF ALL REMOVED EQUIPMENT NOT ACCEPTED BY THE
OWNER. ITEMS CONTAINING HAZARDOUS MATERIALS SHALL FOLLOW
LOCAL AND STATE DISPOSAL REQUIREMENT.
7. PATCH ALL OPENINGS IN WALLS RESULTING FROM REMOVAL WORK.
PAINT TO MATCH SURROUNDING SURFACES.
8. PROVIDE KNOCKOUT PLUGS IN ALL BOX OPENINGS NOT REUSED.
9. VISIT THE SITE TO VERIFY THE EXTENT OF DEMOLITION AND
REMODELING PRIOR TO BID.
10. EXISTING TO REMAIN ELECTRICAL SYSTEMS MUST STAY
OPERATIONAL AND BE PROTECTED FROM ANY PHYSICAL DAMAGE OR
CONTAMINATION FROM DUST DURING CONSTRUCTION.
POWER
1. COORDINATE LOCATION OF ELECTRICAL DEVICES SUCH AS WIRING
DEVICES WITH EXISTING CONDITIONS PRIOR TO ROUGH IN.
2. UPDATE PANELBOARD SCHEDULES (TYPEWRITTEN AND DATED) TO
REFLECT CHANGES. UNUSED CIRCUIT BREAKERS SHALL BE LABELED
"SPARE". PANELBOARD SCHEDULE CIRCUIT DESCRIPTION TO BE
UNIQUE PER NEC.
3. LABEL ALL JUNCTION BOXES AND RECEPTACLE COVERS WITHIN THE
AREA OF WORK WITH SOURCE PANELBOARD NAME(S) AND BRANCH
CIRCUIT NUMBER(S).
4. PROVIDE GFCI PROTECTED RECEPTACLES IN WET LOCATIONS,
WITHIN 6' OF A SINK, OR OUTDOORS.
5. PROVIDE WHILE-IN-USE WEATHER PROTECTED COVERS FOR ALL
OUTDOOR RECEPTACLES.
FIRE ALARM AND LOW-VOLTAGE SYSTEMS
1. LABEL ALL PROJECT AREA SIGNAL OUTLET COVERS WITH SOURCE
EQUIPMENT NAME AND CABLE DESIGNATOR AS APPROPRIATE.
2. PROVIDE CONDUIT FOR FIRE ALARM AND LOW-VOLTAGE SYSTEMS
CABLING. FIRE ALARM CONDUIT SHALL BE RED
3. PROVIDE CONDUIT TO ACCESSIBLE CEILINGS FOR FIRE ALARM AND
LOW-VOLTAGE SYSTEMS. PROVIDE J-HOOKS, D-RINGS, OR CABLE
TRAY (WHERE SHOWN) FOR ROUTING ABOVE ACCESSIBLE CEILINGS.
4. PROVIDE COVERPLATES, CABLES, AND CABLE SUPPORTS FOR
CABLES SUPPORTED FROM ABOVE CEILING STRUCTURE (IE.
J-HOOKS). PROVIDE IDENTIFICATION AND TESTING FOR SYSTEM
CABLING.
5. PROVIDE ROUGH INCLUDING BUT NOT LIMITED TO HAND HOLES,
JUNCTION BOXES, AND CONDUIT TO HALLWAY ACCESSIBLE CEILING
SPACES AND EXTERIOR WALL MOUNTED FIRE ALARM DEVICES.
PROVIDE CONNECTION TO FIRE ALARM SYSTEM.
6. PROVIDE A NOTIFIER ADDRESSABLE FIRE ALARM SYSTEM TO COVER
THE ENTIRE BUILDING, INCLUDING FIRE ALARM DEVICES LOCATED
OUTSIDE OF THE BUILDING. THE SYSTEM SHALL CONSIST BUT NOT
LIMIT TO NOTIFICATION APPLIANCES, INITIATING, AND ALL EQUIPMENT
REQUIRED FOR A COMPLETE AND OPERATIONAL FIRE ALARM SYSTEM.
NOTIFICATION APPLIANCES SHALL BE HORN/STROBES ONLY; VOICE
EVACUATION SYSTEM IS NOT INCLUDED. PROVIDE PROPER
CONNECTIONS FROM FIRE ALARM DEVICES TO THE FIRE ALARM
CONTROL PANEL. ALL DEVICES SHALL BE OF THE SAME
MANUFACTURER AND COMPATIBLE WITH THE SITE-WIDE FIRE ALARM
SYSTEM.
7. DEVICE LOCATIONS SHOWN ON DRAWINGS ARE APPROXIMATE.
VERIFY DEVICE LOCATIONS IN FIELD AND ENSURE ADEQUATE SPACE
AND CLEARANCES FOR PROPER ACCESS AND OPERATION PRIOR TO
INSTALLATION.
8. ALL SYSTEM DESIGN AND INSTALLATION SHALL BE IN STRICT AND
ACCORDANCE WITH THE LATEST APPLICABLE CODES AND
STANDARDS RELATED TO THE SYSTEM. ALL SYSTEM INSPECTIONS
AND TESTING SHALL BE COORDINATED WITH THE FIRE DEPARTMENT.
AB ABOVE COUNTER
AC ALTERNATING CURRENT
AF AMPS FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AL ALARM
AM AMMETER
AO ANALOG OUTPUT
APPROX APPROXIMATE
AT AMPS TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY SWITCH
AV AUDIO VISUAL
BESS BATTERY ELECTRIC STORAGE SYSTEM
BFG BELOW FINISHED GRADE
BLDG BUILDING
BSMT BASEMENT
C CONDUIT
CAB CABINET
CB CIRCUIT BREAKER
CBL CABLE
CKT CIRCUIT
CLG CEILING
CONC CONCRETE
COOL COOLING
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CR CONTROL RELAY
CS CONTROL STATION
CT CURRENT TRANSFORMER
CTR COUNTER
DB DISTRIBUTION BLOCK
DC DIRECT CURRENT
DI DIGITAL INPUT
DIM DIMENSION
DISP DISPOSAL
DIV DIVISION
DN DOWN
DO DIGITAL OUTPUT
DP DISTRIBUTION PANEL
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EA EACH
ELECT ELECTRICAL
EPC EMERGENCY PULL CORD
EQUIP EQUIPMENT
E-STOP EMERGENCY STOP
ETM ELAPSED TIME METER
EV ELECTRIC VEHICLE
EVSE ELECTIC VEHICAL SUPPLY EQUIPMENT
EWC ELECTRIC WATER COOLER
F FAN
FI FAULT INTERRUPTER
FLR FLOOR
FO FIBER OPTIC CABLE
FRACT FRACTIONAL
FT FEET
FTP FIBER TERMINATION PANEL
FU FUSE
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G GROUND, GROUNDED
GEN GENERATOR
GFEP GROUND FAULT EQUIPMENT PROTECTION
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HH HAND HOLE
HMI HUMAN MACHINE INTERFACE
HOA HAND-OFF-AUTO
HP HORSE POWER
HT HEAT TRACE
HTG HEATING
HTR HEATER
HZ HERTZ
I/P CURRENT TO PRESSURE
ID INSIDE DIAMETER
ILPB ILLUMINATED PUSHBUTTON
IN INCHES
INSTR INSTRUMENT
ISB INTRINSIC SAFETY BARRIER
JB JUNCTION BOX OR PULL BOX
KCMIL THOUSANDS OF CIRCULAR MILS
KIT KITCHEN
KS KEY SWITCH
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LA LIGHTNING ARRESTOR
LC LIGHTING CONTACTOR
LCP LIGHTING CONTROL PANEL
LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT
LI LOAD INTERRUPTER
LR LINE OR LOAD REACTOR
LTG LIGHTING
MA MOTOR ALARM CONTACT
MAX MAXIMUM
MCB MAIN BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MECH MECHANICAL
MH MANHOLE
MICR MICROWAVE
MIN MINIMUM
MISC MISCELLANEOUS
MPZ MINI POWER-ZONE
MRS MOTOR RATED SWITCH
MS MOTOR STARTER
MSS MOTOR STARTER SWITCH
MT EMPTY
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MV MOTORIZED VALVE
N NEUTRAL
NC NORMALLY CLOSED
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NON NONCOINCIDENTAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD RELAY
OPG OPENING
P POLE
P/I PRESSURE TO CURRENT
PB PUSH BUTTON
PBS PUSH BUTTON STATION
PEC PHOTO ELECTRIC CELL
PER PHOTO ELECTRIC RELAY
PH PHASE
PI PULSE INPUT
PL PILOT LIGHT
PLC PROGRAMMABLE LOGIC CONTROLLER
PM POWER METER
PO PULSE OUTPUT
POT POTENTIOMETER
PPE PERSONAL PROTECTIVE EQUIPMENT
PRI PRIMARY
PVC POLYVINYL CHLORIDE
PWS POWER SUPPLY
REC RECEPTACLE
REFG REFRIGERATOR
REQD REQUIRED
RMC RIGID METAL CONDUIT
RT RAIN TIGHT
RTD RESISTANCE TEMPERATURE DETECTOR
SCADA SUPERVISORY CNTRL AND DATA ACQUISITION
SCCR SHORT CIRCUIT CURRENT RATING
SEC SECONDARY
SFS SOFT START MOTOR STARTER
SP SINGLE POLE
SPD SURGE PROTECTION DEVICE
SS SELECTOR SWITCH
ST SINGLE THROW
SV SOLENOID VALVE
SW SWITCH
SWGR SWITCHGEAR
T TRANSFORMER
TB TERMINAL BOARD
TD TIME DELAY
TEL TELEPHONE TERMINAL
TYP TYPICAL
UH UNIT HEATER
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VM VOLT METER
VT VAPOR TIGHT
W WATTS
W WIRE
W/ WITH
WELD WELDING
WHM WATT HOUR METER
WP WEATHER PROOF
XFMR TRANSFORMER
CF CEILING FLUSH MOUNT
CS SURFACE CEILING MOUNT
XC EXTERIOR CEILING MOUNT
WF WALL FLUSH MOUNT
W SURFACE WALL MOUNT
XW EXTERIOR WALL MOUNT
P POLE MOUNT
XP EXTERIOR POLE MOUNT
PD PENDANT MOUNT
PP PARAPET MOUNT
CM CORNER MOUNT
B BEAM MOUNT
XB EXTERIOR BEAM MOUNT
C
C
CAM
360 FISHEYE DOME CAMERA
360 MULTI-LENS DOME
EXISTING CAMERA
C
C 5M
FIXED DOME CAMERA WITH SIZE
PANORAMIC MULTI-LENS DOME
MISCELLANEOUS
FLOOR BOX
HAND HOLE
JUNCTION BOX
NOTE, REFERRAL
NOTE, REVISION
POWER POLE
PULL BOX
CONDUIT UNDERGROUND OR
UNDERFLOOR
CONDUIT EXPOSED
CONDUIT UP
CONDUIT DOWN
HH
J
PB
PP
SECURITY/ACCESS CONTROL
SS
REX
EH
ET
ES
JB
ADO
ML
CR
DO
ACP
EM
EL
DEL
MD
D
ELECTRIFIED MORTICE LOCK
ELECTRIC LATCH RETRACTION
ELECTROMAGNETIC LOCK
ELECTRIC HINGE
ELECTRIC (POWER) TRANSFER
ELECTRIC STRIKE
DELAYED EGRESS LOCK
DOOR OPERATOR
AUTOMATIC DOOR OPERATOR
JUNCTION BOX
ACCESS CONTROL PANEL
PANIC BUTTON / PUSH BUTTON
REQUEST-TO-EXIT
CARD READER
KEYPAD
DOOR CONTACT / DOOR SWITCH POSITION
MOTION DETECTOR
PS POWER SUPPLY
HC HANDICAP PUSH PLATE / PANEL
KS KEY SWITCH
DH
GB
DOOR HOLDER
GLASS BREAK DETECTOR
CTRL DOOR CONTROLLER
GO
EP
CHIME
GATE OPERATOR
SECURITY SIREN
EMERGENCY PHONE
CYPHER LOCK
SURGE SUPPRESSION
INTERCOMIC
KEY
CYPL
SECURITY CAMERA
DAYLIGHT SENSOR
EXIT LIGHT, CEILING
EXIT LIGHT, WALL MNT w/EM
LUMINAIRE TYPE
CIRCUIT NUMBER
SWITCH IDENTIFICATION
LUMINAIRE, CEILING
LUMINAIRE, NIGHTLIGHT/EMERGENCY LIGHT (12 SHADING)
LUMINAIRE, POLE MOUNTED
LUMINAIRE, FLUORESCENT
LUMINAIRE, WALL MOUNT
LUMINAIRE TYPE AND CIRCUIT #
OCCUPANCY SENSOR
- EQUAL TO WATTSTOPPER SERIES
SWITCH, DIMMER
SWITCH, SINGLE GANG (b-SWITCH IDENTIFICATION, SWITCH, LOW VOLTAGE (WATTSTOPPER OR
APPROVED EQUAL) a,b - SWITCH
IDENTIFICATION AND INDICATES TWO
BUTTON SWITCH
SWITCH, SINGLE GANG SP (DUAL RELAY)
(OS-OCCUPANCY SENSOR EQUAL TO WATTSTOPPER,
b-SWITCH IDENTIFICATION)
PHOTOSENSOR
SWITCH WITH PILOT
OS
D s
AA
b A
DS
b
PS
s
OS s b s
LV
a,b
DETECTOR, SMOKE / HEAT
(S- SMOKE, H- HEAT, B- BEAM, D-DUCT, F- FIXED, RR-RATE/RISE,
CO- CARBON MONOXIDE)
CONVENTIONAL HEAT DETECTOR
DETECTOR SMOKE/CO WITH SOUNDER BASE
STROBE - WITH CANDELA RATING
SPEAKER
SPEAKER/STROBE
LOW FREQUENCY HORN/STROBE
INDIVIDUAL ADDRESSABLE MODULE
MAGNETIC DOOR HOLDER
MANUAL PULL STATION
SWITCH, PRESSURE
SWITCH, FLOW
SWITCH, TAMPER
FIRE/SMOKE DAMPER W/ POWER CONNECTION FROM FACP TO
ACTUATOR AND DUCT DETECTOR.
REMOTE TEST SWITCH FOR DUCT DETECTORS
RELAY MODULE
FIRE DEPARTMENT PHONE
KNOXBOX
F
F S
F
F
D F
IAM
F F
F
T F
F
SD
F
S/CO
RTS
R
F
F K
F
LF
H
P F
PUSH
TO OPEN
48" MAX
42" MIN
1'-6"
6'-8" MIN
8'-0" MAX
WALL-MOUNTED PHONE
CARD ACCESS READER
FIRE ALARM NOTIFICATION DEVICE
DOOR CONTROL PUSH PLATE
FIRE ALARM PULL STATION
JUNCTION BOX
RECEPTACLE
DATA/TELECOM OUTLET
LIGHT SWITCH
FINISHED CEILING
FINISHED FLOOR
WALL-MOUNT SENSOR
12"
FACP
6'-6"
MAX
NAC
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED100
FIRE ALARM
OFFICE - BASEMENT
DEMO PLAN
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE PUMP AND CONTROL PANEL TO REMAIN.
EXISTING FIRE SMOKE DAMPER TO REMAIN.
EXISTING FIRE ALARM NETWORK NODE PANEL TO
REMAIN.
EXISTING ELEVATORS HAVE FIRE ALARM CONTROLS
HARDWIRED TO THE FACP. COORDINATE WITH AN
ELEVATOR CONTRACTOR TO IDENTIFY CIRCUITS AND
PREPARE TO INTERCEPT WIRING FOR NEW SYSTEM.
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
TYP.
TYP.
EXISTING FIRELARM
NETWORK NODE PANEL
EXISTING FIRE PUMP
CONTROL PANEL
TYP.
TYP.
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED101
FIRE ALARM
FIRST FLOOR
DEMO PLAN
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.
REMOVE POWER CIRCUIT BACK TO SOURCE. UPDATE
PANELBOARD SCHEDULE.
EXISTING ELEVATORS HAVE FIRE ALARM CONTROLS
HARDWIRED TO THE FACP. COORDINATE WITH AN
ELEVATOR CONTRACTOR TO IDENTIFY CIRCUITS AND
PREPARE TO INTERCEPT WIRING FOR NEW SYSTEM.
REMOVE CONVENTIONAL HEAT DETECTOR.
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
TYP.
TYP.
TYP.
5 5 5 5
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED103
FIRE ALARM
THIRD FLOOR - SKYWAY
DEMO PLAN
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.2
TYP. 2
TYP.
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED104
FIRE ALARM
FOURTH FLOOR
DEMO PLAN
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.2
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED105
FIRE ALARM
FIFTH FLOOR
DEMO PLAN
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.2
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED106
FIRE ALARM
SIXTH FLOOR
DEMO PLAN
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.2
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
ED107
FIRE ALARM
SEVENTH FLOOR
DEMO PLAN
REMOVAL GENERAL NOTES
A. DISCONNECT AND REMOVE ALL EXISTING FIRE ALARM
DEVICES.
B. DISCONNECT AND REMOVE ALL WIRING FROM FIRE
ALARM DEVICES BACK TO THE FIRE ALARM CONTROL
PANEL.
C. EXISTING CONCEALED RACEWAY MAY BE REUTILIZE FOR
NEW DEVICES.
D. ALL ABANDONED RACEWAYS FOR FIRE ALARM SYSTEM
SHALL BE REMOVED. PATCH AND REPAIR / PAINT ALL
SURFACES TO MATCH EXISTING ADJACENT FINISHES.
E. FIRE ALARM CONTROL PANELS TO BE DEMOLISHED
COMPLETE, ONLY AFTER STARTUP OF NEW PANEL.
BUILDING MUST HAVE OPERATIONAL FIRE ALARM
CONTROL PANEL DURING CONSTRUCTION AND CUT
OVER.
F. BLOCK WALL: PROVIDE STAINLESS STEEL PLATE FOR
CONCEALED BACKBOX AND PAINT AS NEEDED WHERE
DEVICE WAS REMOVED.
G. GYPSUM WALL / CEILING: PATCH AND REPAIR / PAINT
SURFACES WHERE DEVICE AND RACEWAY WERE
REMOVED
H. ACT CEILING: REPLACE TILE WHERE DEVICE WAS
REMOVED.
TYP.
KEYED NOTES
1 EXISTING FLOW AND TAMPER SWITCHES TO REMAIN.
REPLACE MONITOR MODULE AND CONDUCTORS.
EXISTING FIRE SMOKE DAMPER TO REMAIN.
EXISTING ELEVATORS HAVE FIRE ALARM CONTROLS
HARDWIRED TO THE FACP. COORDINATE WITH AN
ELEVATOR CONTRACTOR TO IDENTIFY CIRCUITS AND
PREPARE TO INTERCEPT WIRING FOR NEW SYSTEM.
F S
F
F
IAM F
T
F F
IAM
F
F
F
F
F
F
F
F S
F T
F F
F
F F
F F
FPCP
IAM
FIRE PUMP
CONTROL PANEL
IAM
IAM (X16)
FLOW SWITCH (X12)
TAMPER SWITCH (X4)
F F
FIRE ALARM
NETWORK NODE
PANEL
FSD
FSD
FSD
FSD
FAAP
FAAP-01
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E100
FIRE ALARM
SE OFFICE
BASEMENT PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM SE OFFICE BASEMENT PLAN1
E100
KEYED NOTES
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
FIRE PUMP AND CONTROL PANEL ARE EXISTING. PROVIDE MONITOR MODULES FOR FIRE PUMP
FAIL, PHASE REVERSAL, PUMP RUNNING AND POWER FAILURE.
FIRE ALARM NETWORK NODE PANEL IS EXISTING. PROVIDE INTERFACE / CONNECTION TO NEW
FIRE ALARM CONTROL PANEL (FACP).
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
IAM
T
F F
IAM
F S
F
F S
F
F
FF
F
F
F
F
F
F
FA
CPF
S
F
F
F F
F F
F F
FSD
FSD
FSD
F
F
F
F
FSD
F F
F F
F D
R
FSD
FSD
FSD
IAM
IAM (X3)
ELEVATOR EQUIPMENT
- LOSS OF POWER INDICATION
- PRIMARY RECALL
- SECONDARY RECALL
F S
F F
F
FSD
FSD
FIRE ALARM
CONTROL
PANEL
FDC
FDC
FDC
F
WP
FAAP
FAAP-02
F
IAM
BASEMENT 1ST FLOOR
OPERATIONS OFFICE
SKYWAY DRY SYST’S
FLOORS 4,5,6,7
PENTHOUSE
DRY STANDPIPE
STAIRS – A, C, & D DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E101A
FIRE ALARM
FIRST FLOOR
AREA A PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FIRST FLOOR - AREA A PLAN1
E101A
SEE DRAWING E101B
KEYED NOTES
FIRE DEPT CONNECTION (FDC). PROVIDE ELECTRICAL CONNECTIONS TO SPRINKLER WATER
FLOW SYSTEM.
PROVIDE WEATHER PROOF HORN/STROBE AT LOCATION SHOWN.
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
PROVIDE ADDRESSABLE MODULES FOR LOSS OF ELEVATOR POWER, PRIMARY RECALL, AND
SECONDARY ELEVATOR RECALL. COORDINATE WITH ELEVATOR CONTRACTOR AND VERIFY
PROPER OPERATION.
PROVIDE AN ADDRESSABLE PHOTOELECTRIC DUCT SMOKE DETECTOR FOR THE FIRE SMOKE
DAMPER. PROVIDE ADDRESSABLE CONTROL RELAY, AND REMOTE INDICATOR LIGHT. MOUNT
REMOTE INDICATOR LIGHT IN AN ACCESSIBLE LOCATION. PROVIDE CONNECTIONS TO THE FIRE
SMOKE DAMPER TO CLOSE ON DETECTION OF SMOKE.
PROVIDE NOTIFIER INSPIRE SERIES FIRE ALARM PANEL (FACP). THE PANEL SHALL INCLUDE
NETWORK COMMUNICATION GATEWAY FOR SYSTEM INTEGRATION, AND ALL REQUIRED
MODULES TO SUPPORT NAC AND SLC CIRCUITS. PROVIDE DIGITAL COMMUNICATION
TRANSMITTER FOR IP SYSTEM WITH CELL BACKUP. INSTALL NEW FACP ADJACENT TO EXISTING
PANEL TO ALLOW BOTH SYSTEMS TO REMAIN OPERATIONAL DURING CONSTRUCTION.
COORDINATE WITH EXISTING FIRE ALARM SYSTEM AND PHASING REQUIREMENTS.
PROVIDE 120V - 30A -1P DEDICATED BRANCH CIRCUIT AND LINE VOLTAGE CONNECTIONS TO
FACP. CIRCUIT BREAKER SHALL MATCH BY TYPE / STYLE/ AIC RATING. PROVIDE LOCK-ON
DEVICE TO CIRCUIT BREAKER HANDLE WITH RED MARKING, ACCESSIBLE ONLY TO AUTHORIZED
PERSONNEL. UPDATE PANEL BOARD SCHEDULE TO LABEL FIRE ALARM.
PROVIDE ADDRESSABLE MODULE FROM FACP TO BAS FOR FIRE ALARM STATUS. COORDINATE
WITH BAS CONTRACTOR.
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
F
F
F
F
F
F
F S
F
F
F
F
F F
F F
F
F F
F F
F T
F F
IAM
F F
F
F
F
F F
F F
F
F
F
F
F
FSD
FSD
FSD
FSD
HHHHH
H
H
IAM
IAM
IAM (X3)
ELEVATOR EQUIPMENT
- LOSS OF POWER INDICATION
- PRIMARY RECALL
- SECONDARY RECALL
F S
F F
AHU-1
F D
R
RETURNFSD
FSD
FSD
FSD
FSD
FSD
FDC
F
WP
IAM (X5)
FLOW SWITCH (X2)
TAMPER SWITCH (X3)
IAM
DN
OPEN OFFICE
OPEN OFFICE3
RECEIVING
MECHANICAL/
ELECTRICAL
CONF/TRAINING
CONF
FOCUS FOCUS
VESTIBULE
CONF.
IT ROOM
COPY CENTER
OFFICE
136 BREAK
OUTSIDE STORAGE
TRASH/ LOADING
OPEN PATIO
MENS
WOMEN'S
CONF
LOCKER ROOM
MOTHER'S ROOM
UNISEX
RESTROOM
TRASH/STORAGE
VESTIBULE
ELEV.
CONF
OFFICE
FOCUS
FOCUS
BREAK ROOM
E1
CONF.
OFFICE
CONF.
MECHANICAL
STAIR D
D1
ELEV.
EQUIP.
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E101B
FIRE ALARM
FIRST FLOOR
AREA B PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FIRST FLOOR - AREA B PLAN1
E101B
SEE DRAWING E101A
KEYED NOTES
FIRE DEPT CONNECTION (FDC). PROVIDE ELECTRICAL CONNECTIONS TO SPRINKLER WATER
FLOW SYSTEM.
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
PROVIDE ADDRESSABLE MODULES FOR LOSS OF ELEVATOR POWER, PRIMARY RECALL, AND
SECONDARY ELEVATOR RECALL. COORDINATE WITH ELEVATOR CONTRACTOR AND VERIFY
PROPER OPERATION.
PROVIDE AN ADDRESSABLE PHOTOELECTRIC DUCT SMOKE DETECTOR WITHIN THE DUCT.
PROVIDE ADDRESSABLE CONTROL RELAY, AND REMOTE INDICATOR LIGHT. MOUNT REMOTE
INDICATOR LIGHT IN AN ACCESSIBLE LOCATION. PROVIDE CONNECTIONS TO AHU FOR
SHUTDOWN ON DETECTION OF SMOKE.
PROVIDE ADDRESSABLE MONITOR MODULE TO INITIATE ALARM SIGNAL TO FIRE ALARM CONTROL
PANEL.
PROVIDE HEAVY-DUTY, WATERPROOF FIXED-TEMPERATURE CONVENTIONAL HEAT DETECTOR.
PROVIDE CONNECTIONS TO THE FIRE ALARM SYSTEM MONITOR MODULE.
2 3
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
6 6 6 6
T
F F
IAM
F S
F
AHU-5
AHU-4F
D
IAM
R
F D
R
SUPPLY
RETURN
F D
R
SUPPLY
F D
R
RETURN
F S
F S
FSD
FSD
F
F
F F
F F
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
F S
F S
F S
F S
F S
F S
F S
F S
F S
F
F
F
F
F
F
F
F
F F
F S
F S
F S
F S
F S
F S
F S
F S
F S
FSD
FSD
FSD
FSD
IAM
IAM IAM
IN ELEVETOR PIT
D F
DF
DF
D F
F S
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E103A
FIRE ALARM
THIRD FLOOR & SKYWAY
AREA A PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - THIRD FLOOR & SKYWAY - AREA A PLAN1
E103A
SEE DRAWING E103B
KEYED NOTES
PROVIDE AN ADDRESSABLE PHOTOELECTRIC DUCT SMOKE DETECTOR WITHIN THE DUCT.
PROVIDE ADDRESSABLE CONTROL RELAY, AND REMOTE INDICATOR LIGHT. MOUNT REMOTE
INDICATOR LIGHT IN AN ACCESSIBLE LOCATION. PROVIDE CONNECTIONS TO AHU FOR
SHUTDOWN ON DETECTION OF SMOKE.
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
PROVIDE NEW ELECTROMAGNETIC DOOR HOLDERS. PROVIDE ADDRESSABLE CONTROL MODULE
AND CONNECTIONS TO MAGNETIC DOOR HOLDERS. PROVIDE POWER FOR MAGNETIC DOOR
HOLDERS. UPON ACTIVATION OF THE SMOKE DETECTOR, RELEASE THE MAGNETIC DOOR
HOLDERS TO CLOSE THE DOORS.
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
AHU-2
F D
R
SUPPLY
F D
R
RETURN
F S
F
FSD
FSD
FSD
FSD
F S
F S
F S
FSD
F
F
FSD
FSD
FSD
IAM
IAM
FSD
F
F
F F
F S
F S
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E103B
FIRE ALARM
THIRD FLOOR & SKYWAY
AREA B PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - THIRD FLOOR & SKYWAY - AREA B PLAN1
E103B
SEE DRAWING E103A
KEYED NOTES
PROVIDE AN ADDRESSABLE PHOTOELECTRIC DUCT SMOKE DETECTOR WITHIN THE DUCT.
PROVIDE ADDRESSABLE CONTROL RELAY, AND REMOTE INDICATOR LIGHT. MOUNT REMOTE
INDICATOR LIGHT IN AN ACCESSIBLE LOCATION. PROVIDE CONNECTIONS TO AHU FOR
SHUTDOWN ON DETECTION OF SMOKE.
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
T
F F
IAM
F S
F
F
FSD
FSD
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E104A
FIRE ALARM
FOURTH FLOOR
AREA A PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FOURTH FLOOR - AREA A PLAN1
E104A
SEE DRAWING E104B
KEYED NOTES
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E104B
FIRE ALARM
FOURTH FLOOR
AREA B PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FOURTH FLOOR - AREA B PLAN1
E104B
SEE DRAWING E104A
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
T
F F
IAM
F S
F
F
FSD
FSD
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E105A
FIRE ALARM
FIFTH FLOOR
AREA A PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FIFTH FLOOR - AREA A PLAN1
E105A
SEE DRAWING E105B
KEYED NOTES
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
SYSTEM. DOWNLOAD A COPY OF FINAL PROGRAM ONTO FLASH DRIVE AND PROVIDE TO OWNER.
GENERAL NOTES
FLOW AND TAMPER SWITCHES ON RISER PIPING ARE EXISTING. PROVIDE MONITOR MODULES
FOR FLOW AND TAMPER SWITCHES. PROVIDE CONDUIT AND CONDUCTORS TO EXISTING
SWITCHES.
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHORNE
KEY PLAN
HAWTHORNE
FIRE ALARM SYSTEM
REPLACEMENTS
CITY OF MINNEAPOLIS
DIVISION OF TRAFFIC
AND PARKING
E105B
FIRE ALARM
FIFTH FLOOR
AREA B PLAN
0 16' 32' Scale: 1/16" = 1'-0"
FIRE ALARM - FIFTH FLOOR - AREA B PLAN1
E105B
SEE DRAWING E105A
A. THE FIRE ALARM SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH STATE AND LOCAL CODE REQUIREMENTS AND IN ACCORDANCE WITH THE LATEST APPLICABLE EDITION OF NFPA STANDARDS.
B. THE CONTRACTOR SHALL COORDINATE INSTALLATION WITH EXISTING BUILDING SYSTEMS TO AVOID CONFLICTS AND MAINTAIN REQUIRED ACCESS AND CLEARANCES. ANY DISCREPANCIES OR CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, CODES, OR EXISTING CONDITIONS SHALL BE REPORTED TO THE OWNER SITE REPRESENTATIVE FOR
RESOLUTION PRIOR TO INSTALLATION.
C. ALL PENETRATIONS THROUGH FIRE-RATED WALLS SHALL BE FIRE SEALED WITH A LISTED FIRE STOP SYSTEM TO MEET
OR EXCEED THE REQUIRED RATING.
D. ALL CONDUIT, CONDUCTORS AND CONDUIT BOXES TO FIRE ALARM DEVICES SHALL BE IDENTIFIED BY RED COLOR.
WIRING TO FIRE ALARM DEVICES INSTALLED ON MASONRY WALLS (FINISHED OR UN-FINISHED AREAS) SHALL BE WITH IN
EXISTING CONCEALED CONDUIT OR SURFACE MOUNTED RED EMT CONDUIT.
E. WIRING TO FLOW SWITCHES AND TAMPER SWITCHES SHALL BE INSTALLED IN RED EMT CONDUIT. THE LAST 3 FEET MAY
BE INSTALLED IN LIQUIDTIGHT CONDUIT.
F. WIRING TO FIRE ALARM DEVICES INSTALLED ABOVE ACOUSTICAL CEILINGS SHALL BE INDEPENDENTLY SUPPORTED BY APPROVED CABLE SUPPORTS EVERY 3 FEET, INSTALLED IN THE CABLE TRAY, OR INSTALLED IN EMT RED CONDUIT.
CEILING SUPPORTS ARE NOT ALLOWED.
G. CEILING MOUNTED NOTIFICATION DEVICES ARE PREFERRED IN ROOMS WITH ACOUSTICAL (ACT) CEILINGS.
H. PROVIDE 4" SQUARE (RED) BACK BOX FOR ALL CONTROL MODULES AND MONITOR MODULES.
I. PROVIDE FIRE ALARM SYSTEM DEVICES AS SHOWN ON PLANS. PROVIDE FINAL TERMINATIONS AT THE HEAD-END AND AT ALL FIELD DEVICES. PROVIDE PROGRAMMING, TESTING, AND TRAINING FOR A COMPLETE AND OPERATIONAL
T
F F
IAM
F S
F
F
FSD
FSD
DESIGNED DRAWN CHECKED
SIGNATURE:
PRINTED NAME:
LIC. NO.: DATE:
DATENO. ISSUE RECORD
BA
R
IS
O
N E
IN
C
H O
N O
R
IG
IN
AL
D R
AW
IN
G
IF
N
O T
O N
E
IN
C H
O N
T H
IS
D
R
AW
IN
G
A D
JU
ST
S C
AL
ES
A C
C O
R D
IN
G
LY
23978.000
RAMP C
RAMP B
RAMP A
HAWTHO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .