Installation and operating instructions
T M
No contact
Overvoltage
Undervoltage
Dry running
Speed reduction
Overtemperature
Overload
Sensor alarm
We GRUNDFOS declare under our sole responsibility that the product CU 300, to which this declaration relates, is in conformity with the Council Directives on the approximation of the laws of the EEC Member States relating to
— Electromagnetic compatibility (89/336/EEC).
Standards used: EN 55 014 and EN 55 014-2.
— Electrical equipment designed for use within certain voltage limits (73/23/EEC).
Standard used: EN 60 335-1.
Bjerringbro, 1st August 2000
Kenth Hvid Nielsen Technical Manager
CONTENTS
Page
1. General 5
1.1 Expansion possibilities 5
1.2 On/Off button 5
2. CU 300 as an alarm unit 6
2.1 Description 6
2.2 Installation 6
2.3 Location 6
2.4 Mounting the CU 300 6
2.5 Electrical connection 7
2.5.1 Mains supply 7
2.5.2 Pump supply 7
2.5.3 Alarm signal relay 7
2.5.4 Digital input 7
2.6 Description of dry-running protection 8
2.6.1 Function 8
2.7 Settings 8
2.7.1 Required R100 settings 8
2.8 Description of the dewatering function 8
2.8.1 Applications 8
2.8.2 Function 9
2.9 Settings 9
2.9.1 Required R100 settings 9
2.9.2 Run/stop times 9
3. CU 300 with constant pressure control - 0 to 6 bar 10
3.1 Description 10
3.2 Function 10
3.3 Positioning the pressure sensor 11
3.4 System sizing 12
3.5 Installation 12
3.6 Location 12
3.7 Mounting the CU 300 12
3.8 Electrical connection 13
3.8.1 Mains supply 13
3.8.2 Pump supply 13
3.8.3 Alarm signal relay 14
3.9 Settings 14
3.9.1 Required R100 settings 14
3.10 Start-up 14
4. CU 300 with constant pressure control - 0 to 10 bar 15
4.1 Description 15
4.2 Function 15
4.3 Positioning the pressure sensor 15
4.4 System sizing 16
4.5 Installation 16
4.6 Location 16
4.7 Mounting the CU 300 16
4.8 Electrical connection 17
4.8.1 Mains supply 17
4.8.2 Pump supply 18
4.8.3 Alarm signal relay 18
4.9 Settings 18
4.9.1 Required R100 settings 18
4.10 Start-up 18
5. CU 300 with constant pressure control - two-pump operation 19
5.1 Description 19
5.2 Function 19
5.3 Positioning the pressure sensor 20
5.4 System sizing 20
5.5 Installation 20
5.6 Location 20
5.7 Mounting the CU 300 20
5.8 Electrical connection 21
5.8.1 Auxiliary relay 21
5.8.2 Mains supply 21
5.8.3 Pump supply 22
5.8.4 Alarm signal relay 22
5.8.5 Flow switch and pressure sensor 22
5.9 Settings 22
5.9.1 Required R100 settings 22
5.10 Start-up 22
6. CU 300 with sensors 23
6.1 General 23
6.2 Sensor functioning 23
6.2.1 Alarm limits 23
6.2.2 Warning limits 23
6.2.3 Start/stop limits 23
6.3 Installation 24
6.4 Location 24
6.5 Mounting the CU 300 24
6.6 Electrical connection 25
6.6.1 Mains supply 25
6.6.2 Pump supply 26
6.6.3 Alarm signal relay 26
6.6.4 Sensors 26
6.7 Settings 26
6.7.1 Required R100 settings 26
7. CU 300 connected to potentiometer 27
7.1 Description 27
7.2 Installation 27
7.3 Location 27
7.4 Mounting the CU 300 27
7.5 Electrical connection 28
7.5.1 Mains supply 28
7.5.2 Pump supply 29
7.5.3 Alarm signal relay 29
7.5.4 Potentiometer SPP 1 29
7.6 Settings 29
7.6.1 Required R100 settings 29
8. CU 300 connected to water meter 30
8.1 Description 30
8.2 Installation 30
8.3 Location 30
8.4 Mounting the CU 300 30
8.5 Electrical connection 31
8.5.1 Mains supply 31
8.5.2 Pump supply 31
8.5.3 Alarm signal relay 31
8.5.4 Water meter (pulse flow meter) 32
8.6 Settings 32
8.6.1 Required R100 settings 32
9. Constant water level 33
9.1 Description 33
9.2 Function 33
9.3 Installation 33
9.4 Location 33
9.5 Mounting the CU 300 33
9.6 Electrical connection 34
9.6.1 Mains supply 34
9.6.2 Pump supply 35
9.6.3 Alarm signal relay 35
9.6.4 Level sensor 35
9.7 Settings 35
9.7.1 Required R100 settings 35
10. CU 300 connected to RS-232, RS-485 36
10.1 Description 36
10.2 CU 300 connected to a PC directly 36
10.3 Installation 37
10.4 Location 37
10.5 Mounting the CU 300 37
10.6 Electrical connection 38
10.6.1 Mains supply 38
10.6.2 Pump supply 38
10.6.3 Alarm signal relay 39
10.6.4 RS-485 input 39
10.6.5 RS-232 input 39
10.6.6 Modem 39
10.6.7 PC Tool CU 300 39
11. Alarm functions 40
11.1 No contact 40
11.2 Overvoltage 40
11.3 Undervoltage 40
11.4 Dry running 41
11.5 Speed reduction 41
11.6 Overtemperature 41
11.7 Overload 42
11.8 Sensor alarm 42
12. CU 300 with R100 43
12.1 Menu OPERATION 47
12.1.1 Setpoint 47
12.1.2 Operating mode 47
12.1.3 Alarm 47
12.2 Menu STATUS 48
12.2.1 Operating mode 48
12.2.2 Actual setpoint and external setpoint 48
12.2.3 Temperature 49
12.2.4 Speed 49
12.2.5 Power input and power consumption 49
12.2.6 Operating hours and number of starts 49
12.2.7 Sensor 1 and sensor 2 49
12.2.8 Digital input 49
12.2.9 Accumulated flow and energy per m³ 50
12.3 Menu LIMITS 50
12.3.1 Sensor 1 50
12.3.2 Stop, sensor 1 50
12.3.3 Warning, sensor 1 50
12.3.4 Alarm, sensor 1 50
12.3.5 Sensor 2 51
12.3.6 Stop, sensor 2 51
12.3.7 Warning, sensor 2 51
12.3.8 Alarm, sensor 2 51
12.3.9 Stop type 51
12.3.10 Digital input 52
12.3.11 Accumulated flow 52
12.3.12 Warning, temperature 52
12.4 Menu INSTALLATION 52
12.4.1 Controller 52
12.4.2 External setpoint 53
12.4.3 Automatic restart 53
12.4.4 Start delay 54
12.4.5 Run/Stop 54
12.4.6 Dry-running stop 54
12.4.7 Dry-running protection 54
12.4.8 Maximum speed 55
12.4.9 Button on CU 300 55
12.4.10 Number 55
13. Technical data 56
14. Disposal 57
1. General The control unit CU 300 is developed for the SQE submersible pumps.
The CU 300 covers the voltage range:
1 x 100-240 V –10%/+6%, 50/60 Hz, PE.
The CU 300 enables:
• control of the pump on the basis of sensor signals,
• setting of operating parameters, and
• monitoring of operation and alarm indication, if any.
The CU 300 indicates the following alarms:
• No contact,
• Overvoltage,
• Undervoltage,
• Dry running,
• Speed reduction,
• Overtemperature,
• Overload,
• Sensor alarm.
The individual alarms are described in detail in sec-tion 11. Alarm functions.
The CU 300 receives alarm signals from the motor for the following parameters:
• Dry running.
• Incipient pump/motor defect.
• Too high temperature in motor electronics.
• Supply failure.
As standard, the CU 300 incorporates an alarm sig-nal relay.
1.1 Expansion possibilities
The CU 300 enables the use of:
• Remote control R100:
Wireless infra-red remote control by means of the R100 enables change of factory settings and mon-itoring of the installation by calling up actual oper-ating data, e.g. speed, operating hours and power consumption.
• External sensors:
Reception of data from external sensors and con-trol according to the data received, e.g. flow rate, pressure, water level and conductivity.
• External potentiometer SPP 1:
Manual speed control.
1.2 On/Off button
By means of the On/Off button on the CU 300, it is possible to
• start/stop the pump and
• reset possible alarms.
Fig. 1
The green and red indicator lights in the On/Off but-ton indicate pump operating condition as follows:
* If the On/Off button has been used to stop the pump, this button must also be used for restarting.
If the On/Off button is pressed for minimum 5 sec-onds, the pump is started, irrespective of any active fault/alarm indications. When the On/Off button is released, the pump will stop.
Before beginning installation procedures, these installation and operating instruc-tions should be studied carefully. The in-stallation and operation should also be in accordance with local regulations and ac-cepted codes of good practice.
T M
Indication Description
Green indicator light permanently on. Pump is operating.
Green indicator light flashing.
Pump has been stopped by either:
• a sensor,
• an external on/off switch or
• a stop command from the
R100.
Red indicator light permanently on.
Pump has been stopped by means of the On/Off button.*
Red indicator light flashing.
The CU 300 is communicat-ing with the R100.
Green
Red
2. CU 300 as an alarm unit
2.1 Description
When the CU 300 is connected to an SQE pump, any alarm will be indicated by one of the eight red indicator lights on the CU 300.
The indications are based on signals from the motor and from sensors, if installed. The individual alarms are described in detail in section 11. Alarm functions.
It is possible to connect an external alarm signal transmitter and an external on/off switch, see section
2.5 Electrical connection concerning connection, etc.
Fig. 2 shows an example of an installation with the CU 300 as an alarm unit.
Fig. 2
The CU 300 functions as an alarm unit for the pump.
Furthermore, it is possible to communicate with the pump via the remote control R100, see also section
12. CU 300 with R100.
2.2 Installation
2.3 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
2.4 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 3 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 3) to allow condensed water, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 3
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
T M
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
T M
104.5104.5
.5
2.5 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 4
Legend:
2.5.1 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con-nected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
2.5.2 Pump supply
PUMP, terminals 3, 4 and PE:
Connect terminals 3 and 4 to the phase and neutral leads of the pump. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
2.5.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7:
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay is activated when the alarm and warning limits are exceeded.
Manual or automatic restarting can be selected in the R100 display 12.4.3 Automatic restart.
Manual restarting is carried out by means of the On/Off button on the CU 300.
2.5.4 Digital input
DIG IN, terminals 11, 12 and 13:
In fig. 4, the digital input is used to start and stop the pump.
The function of the digital input can be selected by means of the R100 in display 12.3.10 Digital input.
Never make any connections in the CU 300 unit unless the electricity supply has been switched off. The CU 300 must be connected in accordance with the rules and standards in force for the application in question.
T M
K1
POWER
PE
PUMP
RELAY
ALARM
C O
M N
C
N O
N O
N C
C O
M
AUX
RELAY IN
DIG
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
SENSOR
1 2
SENSOR
IN+2
4V
D C
G N
D
RS
RS
B G N
D A R
I D
TR
R
X D
G N
D
5 6 7
1 2
3 4
111213 161514 171819
PE
TX
D
LNL N
H S1
Pos. Description
S1 On/off switch for start/stop of pump.
H Alarm signal transmitter (optional).
K1 Internal alarm signal relay.
Relay data: 250 VAC, 8 A, AC1.
2.6 Description of dry-running protection
When the pump sucks air, the pump power input decreases.
If the pump power input falls below the dry-running power limit set in the R100 display 12.4.6 Dry-run-ning stop, the pump will stop and the CU 300 will indicate the dry-running alarm.
2.6.1 Function
The dry-running protection applies only if the motor speed lies within the “maximum speed” range (i.e.
maximum speed less 1,000 min-1), see fig. 5.
Normally, “maximum speed” is 10,700 min-1. How-ever, it can be reduced in the R100 display 12.4.8 Maximum speed. The dry-running power limit set in display 12.4.6 Dry-running stop must match the speed.
Changing the setpoint:
If the setpoint is changed by means of the R100 dis-play 12.1.1 Setpoint or 12.4.2 External setpoint, the pump can be forced to run at a reduced speed in relation to the “maximum speed”. The dry-running protection will not protect the pump if the reduced speed lies outside the “maximum speed” range (i.e.
maximum speed less 1,000 min-1), see fig. 5.
Constant pressure control:
In constant pressure control mode, the dry-running protection is active, as the motor will operate at “maximum speed” in connection with dry running.
Pump power input curve:
The curve shows the pump power input in relation to the pump speed.
Fig. 5
2.7 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
2.7.1 Required R100 settings
If the maximum speed of the pump has been re-duced by more than 1,000 min-1, the dry-running stop value must be changed. In order to change the dry-running protection function, the following R100 settings must be made:
Setting of dry-running power limit (dry-running stop):
1. Start the pump against a closed discharge pipe.
2. Read the input power (P1) in the R100 display
12.2.5 Power input and power consumption.
3. Calculate the dry-running power limit, P1 x 0.9 [W].
4. Set this value in the R100 display 12.4.6 Dry-run-ning stop.
2.8 Description of the dewatering function
When the pump sucks air, the pump power input decreases.
If the pump power input falls below the dry-running power limit set in the R100 display 12.4.6 Dry-run-ning stop, the pump will stop.
During dewatering, the green indicator light in the On/Off button on the CU 300 is flashing to indicate that the pump has stopped.
2.8.1 Applications
The dewatering function can be used in applications where the pump often runs dry, e.g.:
• in boreholes with a low yield.
• in boreholes and building sites where the water table should be lowered.
T M
Max. speed as set in display 12.4.8
Max. speed -1,000 min-1
Motor speed
Pump power input
Pump power curve
Dry-running power limit set
7,000 min-1
Watt
10,700 min-1
Display R100 setting
12.4.7 Dry-running
protection
Set “Dry-running protection” to “Active”.
Note: In certain installations, it may be necessary to dis-able the dry-running protec-tion. This is done in this display. The disabling applies to the dry-running power limit set in display 12.4.6 Dry-run-ning stop.
See fig. 5.
12.4.6 Dry-running
stop Set the dry-running power limit, i.e. dry-running stop.
See “Setting of dry-running power limit (dry-running stop)” below and section 13.
Technical data.
2.8.2 Function
The dewatering function works as follows:
1. The pump is operating.
2. The pump sucks air due to a drop in the water level.
3. The load decreases, and consequently the pump power input does as well.
4. The pump stops when the power input falls to the dry-running power limit set in the R100 display
12.4.6 Dry-running stop in the INSTALLATION
menu.
Note: The length of the stop time depends on the length of the run time according to a setting made in the R100 display 12.4.5 Run/Stop in the IN- STALLATION menu.
2.9 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
2.9.1 Required R100 settings
In order to activate the dewatering function, the fol-lowing R100 settings must be made:
Setting of dry-running power limit (dry-running stop):
1. Start the pump against a closed discharge pipe.
2. Read the input power (P1) in the R100 display
12.2.5 Power input and power consumption.
3. Calculate the dry-running power limit, P1 x 0.9 [W].
4. Set this value in the R100 display 12.4.6 Dry-run-ning stop.
2.9.2 Run/stop times
The dewatering function means that there is a de-pendence between the period of time during which the pump is running, the run time, and the period of time during which the pump is stopped, the stop time.
Fig. 6 shows an example of run/stop times set in the R100 display 12.4.5 Run/Stop.
Fig. 6
Explanation:
The run and stop times were set to 60 min. each.
The pump has been running for 25 min. when dry running occurs. The pump will be stopped for 35 min.
If the pump had been running for e.g. 2 hours (120 min.), the stop time would be 1 min.
Display R100 setting
12.4.7 Dry-running
protection
Set “Dry-running protection” to “Active”.
12.4.6 Dry-running
stop Set the dry-running power limit, i.e. dry-running stop.
See “Setting of dry-running power limit (dry-running stop)” below.
12.4.5 Run/Stop
Set the relation between run and stop times.
Indication of operation:
The dry-running alarm indica-tion on the CU 300 is auto-matically disabled, when the setting is made in display
12.4.5 Run/Stop.
To disable the dewatering function and return to dry-running protection, simply set the Run/Stop fields to “–” (not active).
T M
3. CU 300 with constant pressure control - 0 to 6 bar
3.1 Description
Using constant pressure control enables automatic adjustment of the pump performance according to consumption. The system maintains a constant pres-sure within the maximum pump performance in spite of a varying water consumption.
Fig. 7 shows an example of an installation with con-stant pressure control within the range from 0 to 6 bar.
Fig. 7
3.2 Function
The pressure is registered by means of the pressure sensor, which transmits a signal to the CU 300. The CU 300 adjusts the pump performance accordingly by changing the pump speed.
Mains borne signalling:
The communication between the CU 300 and the pump is effected via the power supply cable.
This communication principle is called mains borne signalling (or power line communication). Using this principle means that no additional cables to the pump are required.
The communication of data is effected by means of a high-frequency signal transmitted to the power sup-ply cable and led into the electronics unit by means of signal coils incorporated in the motor and the CU 300 respectively.
When does the pump start?
The pump starts as a consequence of...
• a high flow or
• a low pressure or
• a combination of both.
To ensure that the pump is started when water is consumed, a flow detection is required. The flow is detected via pressure changes in the system. When water is consumed, the pressure will drop according-ly depending on the size of the diaphragm tank and the water flow:
• at a low flow, the pressure will drop slowly.
• at a high flow, the pressure will drop quickly.
See fig. 8.
Fig. 8
Note: When the pressure is dropping 0.1 bar/s or faster, the pump will start immediately.
If a diaphragm tank of 8 litres is used, the pump will start at a flow rate of approx. 0.18 m³/h.
Note: If a larger tank is used, the flow must be higher before the pump starts.
Consumption up to 0.18 m³/h:
The pump will start when the pressure has dropped to 0.5 bar below the pressure setting.
The pump will run until the pressure is 0.5 bar above the pressure set.
Flow detection:
During pump operation, i.e. when water is con-sumed, the CU 300 will adjust the pump speed to maintain a constant pressure. In order to stop the pump when no water is consumed, the CU 300 per-forms flow detection every 10 seconds.
The pump speed is reduced until a small pressure drop is registered. This pressure drop indicates that water is consumed and the pump speed is resumed, see fig. 9.
If the pump speed can be reduced without any pres-sure drop being registered, this indicates that no water is consumed. The diaphragm tank will be filled with water and the pump will be stopped.
T M
Pos. Description
1 CU 300.
2 Diaphragm tank.
Absorbs pressure variations.
Pressure sensor.
The required pressure is set using the R100.
T M
Pressure
Time
Low flow
H ig h flo w
Fig. 9
System limits:
Even though the CU 300 is controlling the pressure within ±0.2 bar, bigger pressure variations may occur in the system.
If the consumption is suddenly changed, e.g. if a tap is opened, the water must start flowing before the pressure can be made constant again. Such dynam-ic variations depend on the pipework, but, typically, they will lie between 0.5 and 1 bar.
If the desired consumption is higher than the quantity the pump is able to deliver at the desired pressure, the pressure follows the pump curve as illustrated in fig. 10.
Fig. 10
A = Required pressure
3.3 Positioning the pressure sensor
Pressure loss often causes inconvenience to the user. The CU 300 keeps the pressure constant in the place where the pressure sensor is positioned, see fig. 11.
Fig. 11
In fig. 11, tap 1 is placed close to the pressure sen-sor. Therefore, the pressure will be kept nearly con-stant at tap 1, as the friction loss is small. At the shower and tap 2, the friction loss is bigger. This, of course, depends on the piping. However, old and furred-up piping may cause inconvenience due to friction loss.
Therefore, it is recommended that the pressure sen-sor be positioned as close to the places of consump-tion as possible.
T M
T
M
Pressure
Time
Flow detection
10 s10 s
Controlling ±0.2 bar
Dynamic variations ±0.5 bar
Pressure
Start -0.5 bar
A
Stop +0.5 bar m³/h0.18
Flow Flow
T M
Shower
Tap 1 Tap 2
CU 300
8 l
3.4 System sizing
In normal installations with the CU 300 and an SQE pump set to constant pressure control, the required tank size is 8 litres. Bigger tanks can be used without causing any problems.
3.5 Installation
3.6 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
3.7 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 12 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 12) to allow condensed wa-ter, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 12
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
The installation must be designed for the maximum pump pressure.
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
T M
104.5104.5
3.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 13
Legend: 3.8.1 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con-nected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
3.8.2 Pump supply
PUMP, terminals 3, 4 and PE:
Connect terminals 3 and 4 to the phase and neutral leads of the pump. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Never make any connections in the CU 300 unit unless the electricity supply has been switched off. The CU 300 must be connected in accordance with the rules and standards in force for the application in question.
T M
K1
POWER
PE
PUMP
RELAY
ALARM
C O
M N
C
N O
N O
N C
C O
M
AUX
RELAY IN
DIG
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
SENSOR
1 2
SENSOR
IN+2
4V
D C
G N
D
RS
RS
B G N
D A R
I D
TR
R
X D
G N
D
5 6 7
1 2
3 4
111213 161514 171819
PE
TX
D
LNL N
H 1
Pos. Description
1 Pressure sensor, brown lead, terminal 14.
2 Pressure sensor, black lead, terminal 15.
3 Pressure sensor, screen, terminal GND.
4 Pressure sensor.
Must be connected to sensor input 1.
H Alarm signal transmitter (optional).
3.8.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7:
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning lim-its are exceeded.
Manual or automatic restarting can be selected in the R100 display 12.4.3 Automatic restart.
Manual restarting is carried out by means of the On/Off button on the CU 300.
3.9 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
3.9.1 Required R100 settings
The following R100 settings must be made:
3.10 Start-up
Prior to start-up, the precharge pressure of the dia-phragm tank must be set to 70% of the setpoint set in the R100 display 12.1.1 Setpoint.
Display R100 setting
12.4.1 Controller
Select “Closed loop”.
12.3.1 Sensor 1
Set the sensor type.
Example:
• Sensor output signal
(4-20 mA),
• setting range unit (m),
• setting range - head
(0-40 m).
12.3.9 Stop type
Set the stop type.
• Sensor 1: “Fill”.
• Sensor 2: “–” (not active).
12.3.10 Digital in-
put
Set
• Type to “–” (not active) and
• l/pulse to “–” (not active).
12.1.1 Setpoint
Set the desired head (m).
Example: 35 m.
Rule: The maximum setting of the setpoint corresponds to the maximum value set in dis-play 12.3.1 Sensor 1 less 5 m.
In this case, 40 less 5 = 35 m.
4. CU 300 with constant pressure control - 0 to 10 bar
4.1 Description
Using constant pressure control enables automatic adjustment of the pump performance according to consumption. The system maintains a constant pres-sure within the maximum pump performance in spite of a varying water consumption.
Fig. 14 shows an example of an installation with con-stant pressure control within the range from 0 to 10 bar.
Fig. 14
4.2 Function
The pressure is registered by means of the pressure sensor and transmitted to the CU 300. The CU 300 adjusts the pump performance accordingly. To en-sure that the pump is started when water is con-sumed, a flow switch must be included in the system.
The required pressure (setpoint) is set in the R100 display 12.1.1 Setpoint.
• Consumption up to 0.18 m³/h.
The flow switch contact is open.
The pump starts when the pressure is equal to the setpoint less 0.5 bar. The pump will fill the tank and stop when the pressure is equal to the set-point plus 0.5 bar. Consequently, the pump runs on/off operation.
• Consumption above 0.18 m³/h.
The flow switch contact is closed.
The pump starts when the flow switch contact closes and the speed control ensures that the pressure is kept constant. If the flow is below
0.18 m³/h and the flow switch contact is opened, the tank is filled to a pressure equal to the setpoint plus 0.5 bar. When this pressure is reached, the pump stops. Stopping is a combination of the flow switch contact opening and the pressure being equal to the setpoint plus 0.5 bar.
If the flow is larger than the quantity the pump is able to deliver at the desired pressure, the pressure fol-lows the pump curve as illustrated in fig. 15.
Fig. 15
A = Required pressure
4.3 Positioning the pressure sensor
Pressure loss often causes inconvenience to the user. The CU 300 keeps the pressure constant in the place where the pressure sensor is positioned, see fig. 16.
Fig. 16
In fig. 16, tap 1 is placed close to the pressure sen-sor. Therefore, the pressure will be kept nearly con-stant at tap 1, as the friction loss is small. At the shower and tap 2, the friction loss is bigger. This, of course, depends on the piping. However, old and furred-up piping may cause inconvenience due to friction loss.
T M
Pos. Description
1 CU 300.
2 Diaphragm tank.
Absorbs pressure variations.
Flow switch.
The pump starts at once when water is consumed at the taps.
Pressure sensor.
The required pressure is set using the R100.
T M
T
M
A
Tap 1 Tap 2
CU 300
Shower
8 l
Therefore, it is recommended that the pressure sen-sor be positioned as close to the places of consump-tion as possible.
4.4 System sizing
In normal installations with the CU 300 and an SQE pump set to constant pressure control, the required tank size is 8 litres. Bigger tanks can be used without causing any problems.
4.5 Installation
4.6 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
4.7 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 17 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 17) to allow condensed wa-ter, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 17
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
The installation must be designed for the maximum pump pressure.
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
T M
104.5104.5
4.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 18
Legend: 4.8.1 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con-nected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
Never make any connections in the CU 300 unit unless the electricity supply has been switched off. The CU 300 must be connected in accordance with the rules and standards in force for the application in question.
T M
5 6
K1
POWER
PE
PUMP
RELAY
ALARM
C O
M N
C
N O
N O
N C
C O
M
AUX
RELAY IN
DIG
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
SENSOR
1 2
SENSOR
IN+2
4V
D C
G N
D
RS
RS
B G N
D A R
I D
TR
R
X D
G N
D
5 6 7
1 2
3 4
111213 161514 171819
PE
TX
D
LNL N
H 1
Pos. Description
1 Pressure sensor, brown lead, terminal 14.
2 Pressure sensor, black lead, terminal 15.
3 Pressure sensor, screen, terminal GND.
4 Pressure sensor.
Must be connected to sensor input 1.
5 Diaphragm tank connection.
Flow switch.
Must be connected to the digital input, terminals 12 and 13. Cannot be con-nected wrongly.
H Alarm signal transmitter (optional).
4.8.2 Pump supply
PUMP, terminals 3, 4 and PE:
Connect terminals 3 and 4 to the phase and neutral leads of the pump. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
4.8.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7:
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning lim-its are exceeded.
Manual or automatic restarting can be selected in the R100 display 12.4.3 Automatic restart.
Manual restarting is carried out by means of the On/Off button on the CU 300.
4.9 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
4.9.1 Required R100 settings
The following R100 settings must be made:
4.10 Start-up
Prior to start-up, the precharge pressure of the dia-phragm tank must be set to 70% of the setpoint set in the R100 display 12.1.1 Setpoint.
Display R100 setting
12.4.1 Controller
Select “Closed loop”.
12.3.1 Sensor 1
Set the sensor type.
Example:
• Sensor output signal
(4-20 mA),
• setting range unit (m),
• setting range - head
(0-40 m).
12.3.9 Stop type
Set the stop type.
• Sensor 1: “Fill”.
• Sensor 2: “–” (not active).
12.3.10 Digital in-
put
Set
• Type to “Start” and
• l/pulse to “–” (not active).
12.1.1 Setpoint
Set the desired head (m).
Example: 35 m.
Rule: The maximum setting of the setpoint corresponds to the maximum value set in dis-play 12.3.1 Sensor 1 less 5 m.
In this case, 40 less 5 = 35 m.
5. CU 300 with constant pressure control - two-pump operation
5.1 Description
Using constant pressure control in connection with two-pump operation enables automatic adjustment of the pump performance according to the consump-tion in systems where a high flow is required. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption.
Note: During two-pump operation, the two pumps must have the same nominal flow, e.g. two SQE 2.
Fig. 19 shows an example of a two-pump installation with constant pressure control.
Fig. 19
5.2 Function
The pressure is registered by means of the pressure sensor and transmitted to the CU 300 (master). The CU 300 adjusts the pump speed to ensure that the pressure is kept constant. To ensure that the pump connected to the CU 300 (master) is started when water is consumed, a flow switch must be included in the system.
Set the CU 300 (master) to the desired pressure (setpoint) in the R100 display 12.1.1 Setpoint.
• Consumption up to 0.18 m³/h.
The flow switch contact is open.
The pump connected to the CU 300 (master) starts when the pressure is equal to the setpoint less 0.5 bar. The pump will fill the tank and stop when the pressure is equal to the setpoint plus
0.5 bar. Consequently, the pump runs on/off oper-ation.
• Consumption above 0.18 m³/h.
The flow switch contact is closed.
The pump connected to the CU 300 (master) starts when the flow switch contact closes and the speed control ensures that the pressure is kept constant.
If the flow is lower than 0.18 m³/h and the flow switch contact is opened, the tank is filled to a pressure equal to the setpoint plus 0.5 bar. When this pressure is reached, the pump stops. Stop-ping is a combination of the flow switch contact opening and the pressure being equal to the set-point plus 0.5 bar.
If the consumption exceeds the quantity the pump connected to the CU 300 (master) is able to de-liver, the pressure in the diaphragm tank will fall.
The pump connected to the CU 300 (slave) will be started in the two following situations:
1. If the pressure in the diaphragm tank falls to 1 bar below the setpoint or
2. if the pump connected to the CU 300 (master) has been operating at maximum performance for more than 5 seconds and the water requirement has increased.
The pump connected to the CU 300 (slave) will be stopped in the three following situations:
1. If the system pressure is 1 bar higher than the setpoint or
2. if the pump connected to the CU 300 (master) has been operating at minimum performance for more than 5 seconds and the water requirement has fallen or
3. if the flow switch indicates “no flow" and the sys-tem pressure is 0.5 bar higher than the setpoint.
If the flow is larger than the quantity the pumps are able to deliver at the desired pressure, the pressure follows the pump curve as illustrated in fig. 20.
Fig. 20
A = Required pressure
T M
Pos. Description
1A, 1B 1A = CU 300 (master), 1B = CU 300 (slave).
2 Diaphragm tank, minimum 24 litres.
Absorbs pressure variations.
Flow switch.
The pump starts at once when water is consumed at the taps.
Pressure sensor.
The required pressure is set using the R100.
1A 1B
T M
A
Pressure
±1.0 bar±0.2 bar -0.5 bar
5.3 Positioning the pressure sensor
See section 4.3 Positioning the pressure sensor.
5.4 System sizing
In two-pump installations set to constant pressure control, the required tank size is 24 litres. Bigger tanks can be used without causing any problems.
5.5 Installation
5.6 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
5.7 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 21 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 21) to allow condensed wa-ter, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 21
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
The installation must be designed for the maximum pump pressure.
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
T M
104.5104.5
5.8 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 22
Legend: 5.8.1 Auxiliary relay Connect the CU 300 (master) to the CU 300 (slave) as follows:
See fig. 22.
5.8.2 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply, see fig. 22. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
Never make any connections in the CU 300 unit unless the electricity supply has been switched off. The CU 300 must be connected in accordance with the rules and standards in force for the application in question.
T M
K1
POWER
PE
PUMP
RELAY
ALARM
C O
M N
C
N O
N O
N C
C O
M
AUX
RELAY IN
DIG
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
SENSOR
1 2
SENSOR
IN+2
4V
D C
G N
D
RS
RS
B G N
D A R
I D
TR
R
X D
G N
D
5 6 7
1 2
3 4
111213 161514 171819
PE
TX
D
LNL N
NL N L
TX
D
PE
191817141516131211
8 9 10
G N
D R
X D
D
TR
R I
AG
N
D B
RS
RS
G N
D
+2 4V
D C
IN
SENSOR
SENSOR
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
DIG
INRELAY
AUX
C O
M N
C
N O
N O
N C
C O
M
ALARM
RELAY
PUMP
PE
POWER
A B
5 6
DC
Pos. Description
A CU 300 (master).
B CU 300 (slave).
C Installation for Q < 5 m³/h.
D Installation for Q > 5 m³/h.
1 Pressure sensor, brown lead, terminal 14.
2 Pressure sensor, black lead, terminal 15.
3 Pressure sensor, screen, terminal GND.
4 Pressure sensor.
Must be connected to sensor input 1.
5 Diaphragm tank connection.
Flow switch (Q < 5 m³/h).
Must be connected to the digital input, terminals 12 and 13. Cannot be con-nected wrongly.
Flow switch (Q > 5 m³/h).
Must be connected to the digital input, terminals 12 and 13. Cannot be con-nected wrongly.
K1 Internal alarm signal relay.
Relay data: 250 VAC, 8 A, AC1.
Connections
CU 300 (master) CU 300 (slave)
Terminal 9 (COM) Terminal 12 (IN)
Terminal 10 (NO) Terminal 13 (GND)
5.8.3 Pump supply
PUMP, terminals 3, 4 and PE:
Connect terminals 3 and 4 to the phase and neutral leads of the pump, see fig. 22. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
5.8.4 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7:
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning lim-its are exceeded.
Manual or automatic restarting can be selected in the R100 display 12.4.3 Automatic restart.
Manual restarting is carried out by means of the On/Off button on the CU 300.
5.8.5 Flow switch and pressure sensor
Connect the flow switch and the pressure sensor to the CU 300 (A = master) as illustrated in fig. 22.
5.9 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
5.9.1 Required R100 settings
The following R100 settings must be made on the CU 300 (master):
The following R100 setting must be made on the CU 300 (slave):
5.10 Start-up
Prior to start-up, the precharge pressure of the dia-phragm tank must be set to 70% of the setpoint set in the R100 display 12.1.1 Setpoint.
Flow switch
Pump type Product number
SQE 1 96 03 73 32
SQE 2, SQE 3, SQE 5, SQE 7 96 03 75 59
Display R100 setting
12.4.1 Controller
Select “Closed loop”.
12.3.1 Sensor 1
Set the sensor type.
Example:
• Sensor output signal
(4-20 mA),
• setting range unit (m),
• setting range - head
(0-40 m).
12.3.9 Stop type
Set the stop type.
• Sensor 1: “Fill”.
• Sensor 2: “–” (not active).
12.3.10 Digital in-
put
Set
• Type to “Start” and
• l/pulse to “–” (not active).
12.1.1 Setpoint
Set the desired head (m).
Example: 35 m.
Rule: The maximum setting of the setpoint corresponds to the maximum value set in dis-play 12.3.1 Sensor 1 less 5 m.
In this case, 40 less 5 = 35 m.
Display R100 setting
12.3.10 Digital in-
put
Set
• Type to “Start” and
• l/pulse to “–” (not active).
6. CU 300 with sensors
6.1 General
The CU 300 can be used in systems with 1 to 3 sen-sors connected.
Fig. 23 shows an example of an installation incorpo-rating sensors.
Fig. 23
The alarm, warning and stop limits can be set indi-vidually for all sensors connected. The limit settings do not influence each other, and each setting offers its own functioning.
Fig. 24 shows a schematic presentation of the set-ting of maximum and minimum limits for alarm, warn-ing and stop respectively.
Fig. 24
It is necessary to set only the limits applying to the sensor selected. Where “–” is selected, the setting is automatically “not active”.
These settings are made in the R100 displays
12.3.1 to 12.3.9.
6.2 Sensor functioning
6.2.1 Alarm limits
When an alarm limit is exceeded, the following takes place:
1. The pump is stopped.
2. The alarm signal relay operates.
3. The “Sensor alarm” indicator light on the CU 300 is on.
4. The alarm appears in the R100 display
12.1.3 Alarm.
If the pump has stopped already or if the alarm sig-nal relay has operated, this condition is maintained.
6.2.2 Warning limits
When a warning limit is exceeded, the following takes place:
1. The alarm signal relay operates.
2. Pump operation is continued. No “Sensor alarm” indication.
3. The warning appears in the R100 display
12.1.3 Alarm.
6.2.3 Start/stop limits
Start/stop limits should be used in connection with the emptying/filling of e.g. water tanks.
The start/stop function depends on the application, i.e. emptying or filling.
• Emptying means that the pump must start at a given maximum water level and stop at a given minimum water level, see fig. 25.
Fig. 25
T M
Pos. Description
1 CU 300.
2 pH sensor.
Detects the water quality.
3 Pulse flow meter.
Detects the water quantity.
4 Level sensor.
T M pH 100%
Alarm
Warning
Warning
Max. (start)
Min. (stop) Warning
Max. Max. Max.
Min. Min. Min.
Status
100%
Sensor signal
StopWarningAlarm
T M
Max. (start)
Min. (stop)
• Filling means that the pump must start at a given minimum water level and stop at a given maximum water level, see fig. 26.
Fig. 26
6.3 Installation
6.4 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
6.5 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 27 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 27) to allow condensed wa-ter, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 27
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
T M
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
T M
Max. (stop) Min. (start)
104.5104.5
6.6 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 28
Legend: 6.6.1 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con-nected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
Never make any connections in the CU 300 unit unless the electricity supply has been switched off. The CU 300 must be connected in accordance with the rules and standards in force for the application in question.
T M
K1
POWER
PE
PUMP
RELAY
ALARM
C O
M N
C
N O
N O
N C
C O
M
AUX
RELAY IN
DIG
IN+2
4V
D C
G N
D
G N
D
+2 4V
D C
IN
SENSOR
1 2
SENSOR
IN+2
4V
D C
G N
D
RS
RS
B G N
D A R
I D
TR
R
X D
G N
D
5 6 7
1 2
3 4
111213 161514 171819
PE
TX
D
LNL N
H
D1
4-20 mA
D1
A1
A2
0-20 mA
0-10V/2-10V
A3
Pos. Description
A1 Analog sensor, output signal 4-20 mA.
A2 Analog sensor, output signal 0-20 mA.
A3 Analog sensor, output signal 0-10/2-10 V.
D1 Digital sensor, NO (normally open).
D2 Digital sensor, NC (normally closed).
H Alarm signal transmitter (optional).
6.6.2 Pump supply
PUMP, terminals 3, 4 and PE:
Connect terminals 3 and 4 to the phase and neutral leads of the pump. Each terminal can be connected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
6.6.3 Alarm signal relay
ALARM RELAY, terminals 5, 6 and 7:
Connect terminals 5, 6 and 7 to the internal alarm signal relay as follows:
• Terminal 5 NC (normally closed).
• Terminal 6 COM (common).
• Terminal 7 NO (normally open).
The relay operates when the alarm and warning lim-its are exceeded.
Manual or automatic restarting can be selected in the R100 display 12.4.3 Automatic restart.
Manual restarting is carried out by means of the On/Off button on the CU 300.
6.6.4 Sensors
SENSOR 1 and SENSOR 2, terminals 14, 15, 16, 17, 18 and 19:
Terminals 14, 15 and 16 (SENSOR 1) and terminals 17, 18 and 19 (SENSOR 2) are used for external sensors, e.g. a pressure gauge, a flow meter or another type of sensor.
Limits for the signal from an external sensor are set by means of the R100 in the LIMITS menu.
The signal can be used
• to start and stop the motor and
• to operate the alarm signal relay, without stopping the motor.
The sensors must give signals within the ranges 0-20 or 4-20 mA, 0-10 or 2-10 VDC. Changeover between current and voltage signals is carried out by means of the R100.
The total load of terminals 11, 14 and 17 (+24 VDC) must not exceed 100 mA.
6.7 Settings
In the following section, the relevant R100 displays and settings are shown and described.
For a detailed description of the R100 displays, see section 12. CU 300 with R100. Each individual dis-play has a number which refers to the section in which it is described in detail.
6.7.1 Required R100 settings
The following R100 settings must be made:
It is necessary to set only the limits applying to the sensor selected. Where “–” is selected, the setting is automatically “not active”.
Display R100 setting
12.3.1 Sensor 1
12.3.5 Sensor 2
Set the
• sensor output signal
(4-20 mA),
• setting range unit
(m), and
• setting range (0-50) for sensor 1 and sensor 2 respectively.
Sensor 2 is set to “not active”.
12.3.2 Stop, sensor 1
12.3.6 Stop, sensor 2
Set the
• maximum stop limit and
• minimum stop limit for sensor 1 and sensor 2 respectively.
12.3.3 Warning, sensor 1
12.3.7 Warning, sensor 2
Set the
• maximum warning limit and
• minimum warning limit for sensor 1 and sensor 2 respectively.
12.3.4 Alarm, sensor 1
12.3.8 Alarm, sensor 2
Set the
• maximum alarm limit and
• minimum alarm limit for sensor 1 and sensor 2 respectively.
12.3.9 Stop type Set the desired stop
type.
Example:
• Sensor 1: “Fill”.
• Sensor 2: “–” (not active).
7. CU 300 connected to potentiometer
7.1 Description
Using an external potentiometer enables:
• manual control of the motor speed, and thereby of pump performance.
• manual starting/stopping of the pump.
Note: To stop the pump, turn the potentiometer (SPP 1) to “STOP”.
Fig. 29 shows an example of an installation incorpo-rating a potentiometer.
Fig. 29
7.2 Installation
7.3 Location
The CU 300 can be placed both indoors and out-doors. It must not be exposed to direct sunlight.
7.4 Mounting the CU 300
The CU 300 is designed for wall mounting.
The box has six mounting holes (ø4), see fig. 30 (dimensions stated in mm).
The CU 300 must be mounted:
• horizontally (see fig. 30) to allow condensed wa-ter, if any, to escape.
• on a plane surface to avoid deformation of the box.
Fig. 30
The CU 300 is supplied with a set of gaskets for the Pg screwed connections.
The gaskets are to be used for the connection of cables/wires to ensure tight connections (IP 55) and cable relief.
T M
Pos. Description
1 CU 300.
External GRUNDFOS potentiometer, SPP 1.
The required flow is obtained by chang-ing the motor speed manually using the external potentiometer.
3 Water tank.
Before starting any work on the CU 300, make sure that the electricity supply has been switched off and that it cannot be ac-cidentally switched on.
1 2
T M
104.5104.5
7.5 Electrical connection The supply voltage and frequency are marked on the nameplate. Make sure that the CU 300 is suitable for the electricity supply on which it will be used.
Fig. 31
Legend: 7.5.1 Mains supply
POWER, terminals 1, 2 and PE:
Connect terminals 1 and 2 to the phase and neutral leads of the mains supply. Each terminal can be con-nected to any of the two leads.
Connect the PE terminal to the green/yellow earth lead. Each PE terminal must be connected to an earth lead of its own.
Maximum cross-section of the leads to be connected is 6 mm².
Back-up fuse: Maximum 16 A.
Note: The leads of the mains supply must not be connected to terminals 3 and 4 (PUMP).
Never make any connections in the CU 300 unit unless the electricity supply has been switched off.