RFC_004_Wood_Treatment_ANS.docx
DOCX document 18 KB Posted
- Attached to
- CVN Camels Federal contract opportunity
- Solicitation number
- N4523A-1-R-0033
About this file
Wood Treatment
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_2_-_CVN_CAMELS_5-Way_Breakdown_-_Corrected_DEC2016.xls | XLS spreadsheet | |
| Amendment_3.docx | DOCX document | |
| Amendment_2.docx | DOCX document | |
| Amendment_1.docx | DOCX document | |
| RFC_011_Material_List_ANS.docx | DOCX document | |
| RFC_011.docx | DOCX document | |
| Wooden_Fender_PSNS.docx | DOCX document | |
| RFC_009_revision_Wood_Fenders_ANS.docx | DOCX document | |
| RFC_009_(2).docx | DOCX document | |
| RFC_008_Drawings_4_ANS.docx | DOCX document | |
| RFC_007_Drawings_3_ANS.docx | DOCX document | |
| RFC_005_Drawings_ANS.docx | DOCX document | |
| RFC_006_Drawings_2_ANS.docx | DOCX document | |
| RFC_002_Draft_ANS.docx | DOCX document | |
| RFC_001_Blocking_Plan_ANS.docx | DOCX document | |
| RFC_003_Vessel_Delivery_ANS.docx | DOCX document | |
| Attachment_2_-_CVN_CAMELS_5-Way_Breakdown_-_B.xls | XLS spreadsheet | |
| N4523A17R0002.pdf | ||
| Attachment_3_-_CDRLs_and_DIDs_-_C.pdf | ||
| Attachment_1_-_Request_for_Clarification_-_A.docx | DOCX document | |
| SOW_Everett_Camels.docx | DOCX document |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR SPECIFICATION CLARIFICATION
| DATE OF REQUEST: 10-25-2016 |
| QUESTION NO: 004 |
| REQUIREMENT: Wooden Fender Repairs |
| REQUISITION NO.: N4523A-17-R-0002 |
ITEM NO: 3.3.3
TITLE: Pressure Treatment Blocking Plan
ISSUING OFFICE POC(CODE 446):
LeAundria Shaheed: (360) 476-4053 LeAundria Shaheed@navy.mil
| PARA. NO: 3.3.3 |
| PAGE NO: 23 |
| CONTRACTOR: |
| PLANNER’S NAME: |
| ATTACH. NO: |
| CONTRACTOR POC & PHONE: |
CONTRACTOR QUESTION:
Paragraph 3.3.3. calls for pressure treatment to a CCA, 2.5 retention level standard, using a category 5A of the American Wood Protection Association 2001 Book of Standards (AWPA).
Apparently this standard was discontinued in the early 2000’s due to EPA standards/regulations.
We believe that the present standards are ACQ.
Please specify what level of treatment is required under these standards as no vendor we have talked to follows the CCA standards.
DO NOT WRITE BELOW THIS LINE
| SPEC CHG: N |
| DWG/REF CHG. N |
| RQMTS CHG: N |
| MAT'L CHG: N |
| TECHNICAL REVIEW: C/411.1JT |
| SERIAL NO: 004 |
Accomplish the requirements of SOW paragraph 3.3.3.
Known source of CCA 2.5 retention level pressure treated lumber is: http://www.buildingproductsplus.com/
ALL REQUESTS FOR CLARIFICATION MUST BE RECEIVED BY THE ISSUING
OFFICE POC NO LATER THAN THE DATE & TIME IDENTIFIED IN THE REQUEST
FOR PROPOSAL.