RFI 2 Before Award HVAC.pdf

PDF 164 KB Posted

Attached to
Repair HVAC Federal contract opportunity
Solicitation number
M2638220MPT1860
Issued by
Department of the Air Force Reserve Command

About this file

This document contains a Request for Information report and a pre-solicitation notice for a federal contract opportunity. The Request for Information report relates to a potential contract to repair HVAC systems and seeks clarification on equipment specifications, noting that condensing units of the specified size are not available with VFDs or an 18 SEER rating. It provides responses allowing for modulated capacity control via alternative means and a minimum 10 EER rating for condensing units. The related pre-solicitation notice is for the Repair HVAC project at the Marine Reserve Facility in Westover Air Reserve Base. The opportunity will use sealed bid procedures and be set aside for total small businesses. The solicitation will be issued on or about May 26th, 2020 with a bid opening date of July 7th, 2020. The single award firm fixed-price contract will have a 150-day performance period from notice to proceed. The project scope involves replacing HVAC units and equipment. The magnitude of construction is estimated between $250,000 to $500,000.

View the file

Other files for this federal contract opportunity

Other files attached to Repair HVAC, newest first.
File Type Posted
Abstract of Offers KTR 7.8.2020.pdf PDF
Abstract of Offers KTR.pdf PDF
RFI Before Award HVAC.pdf PDF
H.1.3.pdf PDF
Solicitation - FA660620B0004 Issued.pdf PDF
Wage Determinations 3.13.2020.pdf PDF
H.1.5.pdf PDF
H.3.1.pdf PDF
Submittal Register - Final 1.31.2020.xls XLS spreadsheet
H.2.1.pdf PDF
H.1.1.pdf PDF
SOW HVAC 4.6.20.docx DOCX document
Special Standards of Responsibility.pdf PDF
H.3.3.pdf PDF
15951a HVAC SOO.pdf PDF
H.1.2.pdf PDF
04--BID SCHEDULE (Draft for Contractor Estimate).docx DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION REPORT (RFI)

RFI NO. PAGE NO.

CONTRACT NO. CONTRACT TITLE

Repair HVAC YTPM 19-0005

PRIME CONTRACTOR

Contractor's Request for Information

REQUESTED BY: DATE REQUESTED Potential Cost Impact

[No] Potential Schedule

Impact [No]SUBCONTRACTOR

RFI

SUBJECT:

DRAWINGS

INFORMATION REQUESTED:

ATTACHMENTS FROM CONTRACTOR: (1 attachment)

Question:

Response:

NOTE: THE RFI SYSTEM IS INTENDED TO PROVIDE AN EFFICIENT MECHANISM FOR RESPONDING TO CONTRACTOR'S REQUESTS FOR

INFORMATION. IT DOES NOT PROVIDE AUTHORITY TO PROCEED WITH ADDITIONAL WORK. IF THE CONTRACTOR CONSIDERS

THE RFI RESPONSE A CHANGED CONDITION, PROVIDE WRITTEN NOTICE TO THE CONTRACTING OFFICER'S REPRESENTATIVE

IN ACCORDANCE WITH CONTRACT PROVISIONS.

QA REVIEWER'S SIGNATURE DATE

RFI FORM

FA6606-20-B-0004

Please clarify this line item requirement from the SOW -

2.9 Provide Trane (Model TTA18024DDA-AE) or equivalent, 15 ton cooling capacity unit with VFD to maintain discharge air temperature and Trane (Model RAUJC404E) or equivalent, 40 ton cooling capacity unit with VFD to maintain discharge air temperature. Provide unit with minimum SEER of 18

1.) The condensing units are not available with VFD’s.

2.) Condensing units this size are not available with an 18 SEER rating.

25 June 2020

1.) Provide means to modulate capacity from 10% to 100% rated unit capacity utilizing compressor unloading ...(i.e. VFD, VAV...)

2.) Minimum EER of 10 required on condensing units.

William Makowiec 6/25/2020