RFI 2 Before Award HVAC.pdf
PDF 164 KB Posted
- Attached to
- Repair HVAC Federal contract opportunity
- Solicitation number
- M2638220MPT1860
About this file
This document contains a Request for Information report and a pre-solicitation notice for a federal contract opportunity. The Request for Information report relates to a potential contract to repair HVAC systems and seeks clarification on equipment specifications, noting that condensing units of the specified size are not available with VFDs or an 18 SEER rating. It provides responses allowing for modulated capacity control via alternative means and a minimum 10 EER rating for condensing units. The related pre-solicitation notice is for the Repair HVAC project at the Marine Reserve Facility in Westover Air Reserve Base. The opportunity will use sealed bid procedures and be set aside for total small businesses. The solicitation will be issued on or about May 26th, 2020 with a bid opening date of July 7th, 2020. The single award firm fixed-price contract will have a 150-day performance period from notice to proceed. The project scope involves replacing HVAC units and equipment. The magnitude of construction is estimated between $250,000 to $500,000.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers KTR 7.8.2020.pdf | ||
| Abstract of Offers KTR.pdf | ||
| RFI Before Award HVAC.pdf | ||
| H.1.3.pdf | ||
| Solicitation - FA660620B0004 Issued.pdf | ||
| Wage Determinations 3.13.2020.pdf | ||
| H.1.5.pdf | ||
| H.3.1.pdf | ||
| Submittal Register - Final 1.31.2020.xls | XLS spreadsheet | |
| H.2.1.pdf | ||
| H.1.1.pdf | ||
| SOW HVAC 4.6.20.docx | DOCX document | |
| Special Standards of Responsibility.pdf | ||
| H.3.3.pdf | ||
| 15951a HVAC SOO.pdf | ||
| H.1.2.pdf | ||
| 04--BID SCHEDULE (Draft for Contractor Estimate).docx | DOCX document |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION REPORT (RFI)
RFI NO. PAGE NO.
CONTRACT NO. CONTRACT TITLE
Repair HVAC YTPM 19-0005
PRIME CONTRACTOR
Contractor's Request for Information
REQUESTED BY: DATE REQUESTED Potential Cost Impact
[No] Potential Schedule
Impact [No]SUBCONTRACTOR
RFI
SUBJECT:
DRAWINGS
INFORMATION REQUESTED:
ATTACHMENTS FROM CONTRACTOR: (1 attachment)
Question:
Response:
NOTE: THE RFI SYSTEM IS INTENDED TO PROVIDE AN EFFICIENT MECHANISM FOR RESPONDING TO CONTRACTOR'S REQUESTS FOR
INFORMATION. IT DOES NOT PROVIDE AUTHORITY TO PROCEED WITH ADDITIONAL WORK. IF THE CONTRACTOR CONSIDERS
THE RFI RESPONSE A CHANGED CONDITION, PROVIDE WRITTEN NOTICE TO THE CONTRACTING OFFICER'S REPRESENTATIVE
IN ACCORDANCE WITH CONTRACT PROVISIONS.
QA REVIEWER'S SIGNATURE DATE
RFI FORM
FA6606-20-B-0004
Please clarify this line item requirement from the SOW -
2.9 Provide Trane (Model TTA18024DDA-AE) or equivalent, 15 ton cooling capacity unit with VFD to maintain discharge air temperature and Trane (Model RAUJC404E) or equivalent, 40 ton cooling capacity unit with VFD to maintain discharge air temperature. Provide unit with minimum SEER of 18
1.) The condensing units are not available with VFD’s.
2.) Condensing units this size are not available with an 18 SEER rating.
25 June 2020
1.) Provide means to modulate capacity from 10% to 100% rated unit capacity utilizing compressor unloading ...(i.e. VFD, VAV...)
2.) Minimum EER of 10 required on condensing units.
William Makowiec 6/25/2020