E-501
2CAT 6 RJ-45 JACK
1"C WITH TWO 4-UTP CAT 6 CABLES
LABEL
LABEL
NEW VIOP SUB
CABINET 31A
EXISTING
FRONT OF
STORE PHONES
CASH
OFFICES
CASH
REGISTERS
TO MAIN
GROUND
BUSS
#3/0 GROUND
EXISTING
PHONES
EXISTING TELEPHONE BOARD
IN MECHANICAL MEZZANINE STAIR
(ROUTE FIBER AND COPPER TO
SUB HUB 31B AS DIRECTED BY
DECA IT)
NEW PHONES
NEW VOIP FULL-SIZE CABINET IN NEW DATA CLOSET
KEYED NOTES:
CONTRACTOR TO PROVIDE PUNCH DOWN BLOCKS (PD), PATCH PANELS (PP), AND LIGHT INTERFACE UNITS (LIU). PROVIDE POWER AS INDICATED, AND FURNISH AND TERMINATE ALL TELECOMM DATA CABLES UNLESS OTHERWISE DIRECTED. PROVIDE NEW HALF-SIZE ENCLOSED SUB-HUB CABINETS (48"H X 22.75"W X 20"D). SUB-HUB CABINET SHALL INCLUDE: POWER STRIP, LOCKING ACRYLIC FRONT DOOR, ADJUSTABLE RAILS (2 PR), VENTED OR WEBBED THREE QUARTER SHELF, EQUIPMENT
MOUNTING BOLTS (30 EA), TWO 4" DIA. INSULATED - BUSHED OPENING IN TOP.
RECONNECT TO EXISTING SECURITY SYSTEM AND NEW PA/MUSIC/PAGING CABINET
CONTRACTOR TO PROVIDE 100 PR COPPER IN 3” CONDUIT AND 3-4 PR CAT 6 IN 2" C.
MAINTAIN INTERCOM AND PAGING SERVICES TO NEW AND EXISTING PHONE LOCATIONS. CONTRACTOR SHALL WORK CLOSELY
WITH STORE MANAGEMENT AND DECA HQ IT SERVICES (RICKY ROSSER 804734-8000 EXT 48467) TO MAINTAIN TELEPHONE SERVICE TO COMMISSARY WITH MINIMAL DISRUPTION DURING SWITCH
OVER TO NEW LINES – BOTH INTERNAL AND EXTERNAL. CONTRACTOR TO PROVIDE DETAILED SWITCH OVER STAGING PLAN FOR APPROVAL BY DECA AND STORE MANAGEMENT. ADDITIONAL CONTRACT MODS FOR OUTAGES AND/OR
OTHER UNANTICIPATED CIRCUMSTANCES WILL NOTE BE ALLOWED.
ROUTE NEW CAT 6 CABLES TO NEAREST HUB. SPLICE COPPER PAIRS AS DIRECTED BY RICKY ROSSER - DECA IT (SEE NOTE 4)
CONTRACTOR TO PROVIDE PUNCH DOWN BLOCKS (PD), PATCH PANELS (PP), AND LIGHT INTERFACE UNITS (LIU). PROVIDE POWER AS INDICATED, AND FURNISH AND TERMINATE ALL TELECOMM DATA CABLES UNLESS OTHERWISE DIRECTED. PROVIDE NEW FULL-SIZE ENCLOSED CABINETS (78"H X 22.75"W X 20"D). DATA CABINET SHALL INCLUDE: POWER STRIP, LOCKING ACRYLIC FRONT DOOR, ADJUSTABLE RAILS (2 PR), VENTED OR WEBBED THREE QUARTER SHELF, EQUIPMENT MOUNTING BOLTS (30 EA), TWO 4" DIA. INSULATED - BUSHED OPENING IN TOP.
PROVIDE 12 STRAND
MULTIMODE FIBER IN 2"
CONDUIT
TO PA SYSTEM
(PAGING) 31A
EXISTING TELEPHONE BOARD
IN OLD RECEIVING MANAGER
OFFICE (ROUTE TO PP'S)
TO ROOM 4
EXISTING
AND NEW
DATA
NEW HALF-SIZE
DATA SUB CABINET
IN DATA CLOSET
EXISTING
PHONES
(ROUTE TO
NEW COMM SUB
HUB CLOSET
31B)
EXISTING
AND NEW
DATA
POS
EXISTING
AND NEW
POS
NEW POS
CABINET
NEW
PC-LAN
CABINET
3-4 PR
CAT 6 IN 2"
PP
PP
L
IU
PP
PP
LIU
PP
LIU
PP
LIU
PP
LIU
PP
LIU
PP
2 6
1/4-TURN PADLOCKABLE
DOOR CATCH
GROUND NEUTRAL Ao Bo Co
LOCKING LIFT CATCH
MOUNTING EARS
PROVISION ONLY ON FRONT
AND BOTTOM DOORS FOR
KIRK KEY INTERLOCK
3" I.D. RUBBER BUSHINGS
FOR TEMPORARY CABLE ENTRY.
1,200 AMP
FUSED OUTDOOR
DISCONNECT
4 SETS OF 4 #350, #3/0 GROUND IN 3"C
OUTDOOR GENERATOR CONNECTION CABINET
BERTHOLD CATALOG #W12-5S-S28W9 (OR EQUAL)
1200A, 480/277V, 2PH, 4W, 35KAIC
(EDIT)
EXISTING
POS DATA CABLING
1 2 3 4 5 6 7 8
G R E E N
W H
IT
E
O R A N G E
W H
IT
E
B
LU
E
W H
IT
E
B R O W N
W H
IT
E
G R E E N
W H
IT
E
B
LU
E
W H
IT
E
O R A N G E
W H
IT
E
B R O W N
W H
IT
E
P A
IR
P A
IR
P A
IR
P A
IR
WIRING SCHEMATIC
RJ - 45 MODULAR CONNECTOR
MALE RJ-45 VIEW
OF BACKSIDE
CAT. 6 CABLE (4 PAIR)
(BELDON #1874 A)
TRACER
COLOR CODING
IS 568 B
STANDARD
WIRE
COLOR
AMPLIFIER(S),
BACKGROUND
MUSIC, AND P.A.
SYSTEM.
4 PR. CAT 6
TO TELE. PATCH PANEL
WITH PAGING CONNECTION
TO TELEPHONE SYSTEM.
TERMINATE IN RJ45
TELE. JACK.
LOCATE SALES FLOOR VOLUME CONTROL WITH HEAD-END EQUIPMENT IN CISIC ROOM 31A.
PA TO BE MUTED BY SIGNAL FROM MASS NOTIFICATION SYSTEM.
1" RIGID STUBBED 2' ABOVE ROOF
WITH WEATHERHEAD AND PULL
CORD FOR FUTURE SATELLITE ANTENNA.
FROM MASS NOTIFICATION SYSTEM
GENERAL NOTES :
1. VOLUME CONTROL FOR SPEAKERS IN
OFFICES IS TO BE WALL MOUNTED WHERE
INDICATED ON PLANS.
2. DEVICES IN COOLER BOXES AND
PREPERATION AREAS TO BE DESIGNED
FOR WET LOCATION.
3. QUANTITIES TO BE AS INDICATED ON
THE PLANS.
4. MUSIC SYSTEM SHALL INCLUDE AM/FM
RADIO, CD PLAYER,
AND AUXILIARY INPUTS FOR THE
"IN-STORE RADIO" SERVICE AND THE
PRERECORDED ANNOUNCEMENT UNIT. ALL
EQUIPMENT TO BE PROVIDED BY
CONTRACTOR EXCEPT FOR "IN-STORE"
RADIO WHICH IS PROVIDED BY
GOVERNMENT OR GOVERNMENT
CONTRACTOR.
5. INTEGRATE PAGING/MUSIC SYSTEM
WITH GF/GI TELEPHONE SYSTEM.
6. ALL CONDUCTORS SHALL BE IN CONDUIT.
TO NEW AND EXISTING SPEAKERS
120V
KEYED NOTES
MICROPHONE
COORDINATE
LOCATION WITH
STORE
OPERATIONS
6B
M
VERIFY CONDUCTOR CONFIGURATION BEFORE
INSTALLATION (SPECIFICALLY, VERIFY IF NEUTRAL
HAS BEEN INSTALLED) SEE E-601
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
101 south spring street little rock, ar 72201
501.372.2900 cromwell.com
SEQUENCE
NO.
SHEET NO.
OF
DATE:SOL. NO.
PROJECT NO.
DRAWING NUMBER
SUBMITTED BY:
ENGINEER:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
TO THE BEST OF OUR KNOWLEDGE,
INFORMATION AND BELIEF, BASED
ON AND LIMITED TO OUR NORMAL
FUNCTIONS PERFORMED UNDER OUR
CONTRACT WITH THE GOVERNMENT,
IT IS OUR PROFESSIONAL OPINION
THAT THIS PROJECT IS DESIGNED
IN ACCORDANCE WITH APPLICABLE
DOD REGULATIONS.
ALLAN FULLER
DEFENSE COMMISSARY AGENCY
LACKLAND AFB, TEXAS
FORT LEE, VIRGINIA
DIRECTORATE OF ENGINEERING
30-MAY-2018
EA16MI05
NAVAL AIR STATION
PENSACOLA, FLORIDA
PENSACOLA COMMISSARY FACILITY
ADDITION /ALTERATION
A/E: 2016-001
RTA SOLICITATION ISSUE
SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION
1 5-30-2018 RTA SOLICITATION ISSUE
E-501
WAF
JRD
PSM
ELECTRICAL DETAILS
05/30/18
N.T.S.
1 VOICE, DATA, OR INTERCOM OUTLET
N.T.S.
3 TELEPHONE / DATA SINGLE-LINE DIAGRAM
N.T.S.
4 MOBILE GENERATOR CONNECTION BOX AND FUSED DISCONNECT
N.T.S.
2 POS/COM DATA CABLING RJ-45 MODULAR CONNECTOR
N.T.S.
5 BACKGROUND MUSIC & P.A. SCHEMATIC
3 7-24-2018 REVISIONS TO BID DOCUMENTS
HDEC03-18-R-0007
AMENDMENT 0006
ATTACHMENT 05
(DELIVERIES SIGNAL SIMILAR)
CUSTOMER, PRODUCE OR MEAT SERVICE
SWITCH LOCATED IN
MGR. OFFICE
EDWARDS #598
OR EQUAL
120/24V 30VA
EDWARDS #852 OR EQUAL PUSH
BUTTON. LOCATE AS INDICATED.
LABEL WITH "RING FOR CUSTOMER
SERVICE" OR "RING FOR (PRODUCE
/MEAT) DELIVERIES" AS INDICATED.
NUMBER OF PUSHBUTTONS AND
BUZZERS AS INDICATED ON PLANS
EDWARDS #340A-G5
OR EQUAL
24VAC
NL
120V
FUSE AT 0.5 AMP
J
J
J
STAND
CHECKOUT
LC
CHECK WRITING
STAND & CARD
READER
SCANNER-
SCALE
OPERATOR
TERMINAL
PRINTER STAND
TELE/POWER
POLE (GF/GI)
MERCHANDISER
CONDUIT & J-BOX
CABLE TRAY
MOUNTED ON TELE-POWER
POLE FOR MERCHANDISER
(GF/GI)
GENERAL NOTES:
1. COORDINATE CABLE TRAY AND POWER
POLE LOCATIONS WITH GF/GI CHECKOUT
STAND CONFIGURATION.
32 1
FINISHED
FLOOR
DUPLEX CONVENIENCE
OUTLET FOR
MERCHANDISER
(GF/GI)
DATA OUTLET (GF/GI)
KEYED NOTES :
4-CONDUCTOR MC CABLE FOR "CLEAN" POWER JUNCTION BOX AT CHECKOUT STAND.
3-CONDUCTOR MC CABLE FOR "DIRTY" POWER JUNCTION BOX AT CHECKOUT STAND.
3-CONDUCTOR MC CABLE FOR DUPLEX CONVENIENCE OUTLET AND CHECKOUT SIGNAL
LIGHT AT CHECKOUT STAND.
FOUR CAT 6 CABLES FROM POS (CISIC) ROOM. TERMINATE EACH CABLE WITH ONE
RJ-45 (CAT 6) JACK.
DURESS ALARM CABLE FROM SECURITY PANEL IN CISIC RM. TERMINATE CABLE WITH
DURESS PUSHBUTTON.
QUEUING CABLE - TERMINATE CABLE WITH PUSHBUTTON.
LANE
LIGHT
(GF/GI)
J-BOX & MC CABLE
TELE/POWER POLE (GF/GI)
ROOF STRUCTURE
DOUBLE CHANNEL
STRUT TRAPEZE
12" CABLE TRAY
GENERAL NOTES:
1. AT EACH CHECKOUT STAND LOCATION, COIL ALL
CABLES AS SHOWN. EACH COIL LENGTH SHALL BE
EQUAL TO THE MOUNTING HEIGHT OF THE J-BOX OR
CABLE TRAY ABOVE FINISHED FLOOR PLUS 10 FEET.
LABEL AND NEATLY SECURE COILS TO RACEWAY,
CABLE TRAY OR DOUBLE CHANNEL STRUT TRAPEZE.
EXTRA CABLE IS PROVIDED FOR FUTURE RELOCATION
OF CHECKSTANDS.
2. THE GOVERNMENT SHALL TERMINATE ALL TYPE MC
CABLES (KEYED NOTES 1, 2, AND 3) AT CHECKOUT
STANDS.
3. AFTER TERMINATION OF THE CABLES WITH JACKS
OR PUSHBUTTONS (KEYED NOTES 4, 5, AND 6) BY THE
CONTRACTOR, THE GOVERNMENT SHALL INSTALL
JACKS AND PUSHBUTTONS AT THE CHECKOUT STANDS.
CONTRACTOR SHALL THEN TERMINATE AND INSTALL DURESS
ALARM BUTTONS.
4. IN AREAS NOT ADJACENT TO CABLE TRAY
(SELF-SERVICE CHECKSTANDS, ETC.), PROVIDE
APPROPRIATE RACEWAYS TO REACH CABLE TRAY.
VERIFY HEIGHT WITH
TELEPHONE / POWER POLE
PROVIDER (GF/GI). INSTALL
CABLE TRAY AT OR ABOVE
24'-0"AFF TO AVOID AIR
FROM DUCTS AND THE
RESULTING
CONDENSATION. AND TO
PROVIDE ADEQUATE
CLEARANCE OVER
MEZZANINE.
CEILING
EL. =
EL. =
0' - 0"
T / FLOOR SLAB
INSTALL CONDUIT FROM TOP OF GONDOLA
UPRIGHT, THROUGH FACTORY PRE-SET
OPENINGS IN UPPER, CENTER, AND LOWER
SPANNERS, AND CONNECT TO JUNCTION BOX
AT BASE OF GONDOLA UPRIGHT FRAME
RUN CONDUIT BENEATH BASE
SHELVES THROUGH FACTORY
PRE_SET OPENINGS WITHIN GONDOLA
BASE SUPPORT
INSTALL 48" LONG LIQUID TIGHT
FLEXIBLE CONDUIT AT ELECTRICAL
RECEPTACLE LOCATIONS
ELECTRICAL TWO-CELL POWER POLE ATTACHED TO TOP
OF GONDOLA UPRIGHT FRAME AND SECURED TO THE
CABLE TRAY ABOVE.
ATTACH ELECTRICAL RECEPTACLE
TO GONDOLA KICKPLATE AT
CENTER OF LAST GONDOLA IN
ROW
INSTALL 48" LONG LIQUID
TIGHT FLEXIBLE CONDUIT AT
ELECTRICAL RECEPTACLE
LOCATIONS
CABLE TRAY SHALL HAVE SOLID
NON-VENTILATED BOTTOM W/ VENTILATED
COVER THAT IS PRE-TREATED FOR FIELD
PAINTING.
PROVIDE CABLE TRAY WITH
A TRAPEZE SUPPORT
BRACKET.
PROVIDE STEEL C-CLAMPS
TO SECURE CABLE TRAY
TRAPEZE TO THE ROOF
STRUCTURE .
POWER POLE SHALL THE
STRAPPED AND BRACED
TO THE CABLE TRAY .
PROVIDE 3/4" CONDUIT FOR
POWER, AND 1" CONDUIT FOR
TELECOMM, IF REQUIRED. POWER
POLE SHALL HAVE A KNOCK OUT
TO FEED POWER FROM THE
CABLE TRAY TO THE POWER POLE.
ATTACH ELECTRICAL RECEPTACLE
TO GONDOLA KICKPLATE AT
CENTER OF LAST GONDOLA IN
ROW
BOTTOM OF ROOF VARIES SEE
STRUCTURAL FOR BOTTOM OF STEEL
ELEVATIONS. (VERIFY IN FIELD)
7' -6
22' - 0" AFF
B / CABLE TRAY
CEILING CEILING
PROVIDE 6" TO 8" CLEARANCE
ABOVE CEILING (MORE OVER
LIGHT FIXTURES)
NEW 1" CONDUIT
NEW 1" CONDUIT
JUNCTION BOX
HEAVY-DUTY COVER
18 1/2" x 11 1/2" x 3/4"
BOX WITH
SOLID BASE
20 1/2" x 13 1/2" x 18 1/2"
NOTE:
1. ENCLOSURE AND COVER SHALL BE RATED FOR NO LESS
THAN 8,000 LBS OVER A 10"x10" AREA AND DESIGNATED AND
TESTED TO A TEMPERATURE OF -50 DEGREES FAHRENHEIT.
MATERIAL COMPRESSIVE STRENGTH SHALL BE NO LESS THAN
11,000 PSI. COVERS SHALL HAVE A MINIMUM COEFFICIENT OF
FRICTION OF .5.
HANDHOLE
(SEE NOTE)
BACKFILL
FINISH GRADE
CONCRETE
4-4"PVC
SPARE (WITH
PULL CORD)
24"MIN. BACKFILL
4" TYP.
BOTH ENDS
4" TYP.
4" TYP.
BOTH ENDS
4" TYP.
MARKER TAPE
3000 PSI
12"
NOTES:
1. DUCT BANKS OTHER THAN 4-4" SHALL HAVE SIMILAR
CONFIGURATION AND CONCRETE COVERAGE.
COORDINATE CONFIGURATION WITH PENSACOLA BCO
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
101 south spring street little rock, ar 72201
501.372.2900 cromwell.com
SEQUENCE
NO.
SHEET NO.
OF
DATE:SOL. NO.
PROJECT NO.
DRAWING NUMBER
SUBMITTED BY:
ENGINEER:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
TO THE BEST OF OUR KNOWLEDGE,
INFORMATION AND BELIEF, BASED
ON AND LIMITED TO OUR NORMAL
FUNCTIONS PERFORMED UNDER OUR
CONTRACT WITH THE GOVERNMENT,
IT IS OUR PROFESSIONAL OPINION
THAT THIS PROJECT IS DESIGNED
IN ACCORDANCE WITH APPLICABLE
DOD REGULATIONS.
ALLAN FULLER
DEFENSE COMMISSARY AGENCY
LACKLAND AFB, TEXAS
FORT LEE, VIRGINIA
DIRECTORATE OF ENGINEERING
30-MAY-2018
EA16MI05
NAVAL AIR STATION
PENSACOLA, FLORIDA
PENSACOLA COMMISSARY FACILITY
ADDITION /ALTERATION
A/E: 2016-001
RTA SOLICITATION ISSUE
SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION
1 5-30-2018 RTA SOLICITATION ISSUE
E-503
WAF
JRD
PSM
ELECTRICAL DETAILS
05/30/18
N.T.S.
2 SERVICE SIGNAL SCHEMATIC
N.T.S.
3 CHECKOUT STAND WIREWAYS
N.T.S.
4 SECTION @ CHECKOUT STAND
N.T.S.
5 POWER POLE GONDOLA MOUNTING DETAIL
3 7-24-2018 REVISIONS TO BID DOCUMENTS
N.T.S.
1 HANDHOLE DETAIL
N.T.S.
6 COMMUNICATIONS DUCT BANK DETAIL
HDEC03-18-R-0007
CB
CB
CB
N
G
4#6
FUSE
RECEIVING AISLE
SPACE
METERING & MAIN
SWITCH SECTION
SELECTOR
SWITCH
WH
GFI
V
A
2000 A.S.
F2000
KRP-C
F200
FRS
F100
FRS
F120
FRS
F100
FRS F200
FRS
200 A.S.100 A.S.100 A.S.200 A.S.100 A.S.200 A.S.
PNL
'HA'
PNL
'HB'
MISC.
ADMIN.LTG. SALES
& STOR.
TRANSFORMER 'TA'
480-120/208V/3 , 4W
30KVA
PNL
'LA'
PNL
'HC'
PNL
'LM'
PNL
'LC'
DRY
STO.
PNL
'NCR'
125KW GENERATOR,480V, 3 PH.,
AND OVERLOAD PROTECTION
INSULATED/
ISOLATED
GROUND
EQUIPMENT
GROUND
200 A.S.
F125
FRS
PNL
'LD'
PNL
'LE'
MECH.
EQUIP.
RM. 83
MECH.
RM. 83
2-200A 2-100A 2-60A
FEEDER TO REFRIGERATION SUBDISTRIBUTION PNL 'CP' 277/480V,3 ,4W
F100
FRS
100A F90
100A.T.
KA
100A.T.
KA
300A.T.
KA
TRANSFORMER 'TM'
480-120/208V/3
4W, 30KVA
PNL
'EM'
CASHIERS
OFFICE
TRANSFORMER 'TE'
480-120/208V/3
4W, 30KVA
SHIELDED
TRANSFORMER 'TB'
480-120/208V/3 , 4W
150KVA
BAKERY
MISC.
ADMIN.
PNL
'HD'
100A
ADP RM/
CASH REG.
PNL
'LB'
PNL
LB1
PNL
'LF'
1200 A.S.
F1200
KTU
SPACE
(1-200A) (2-100A)
WIRE TROUGH
500 A.T.
(TYPE MA)
I-LINE SUBDISTRIBUTION
PANELBOARD "SDP1"
600A BUS, 208V,3 ,4W.
250A.T.
KA
PROC./STO.
& BATTERY
CHARGERS
PNL
'EH'
#6
ELECTROSTATIC SHIELD
4#1/0,#4G, 2"C
3"-4#350 MCM + #4GND
MAIN DISTRIBUTION PANEL 'MDP': 277/480V, 3 ,
4W, 2000 AMP BUS. RATING OF 'MDP' PANEL TO BE
100,000 A.I.C. SYM MINIMUM.
1200A DISCONNECT FUSED AT 1200A, ON EXTERIOR WALL
BY STAIR 31 TO CONNECT PORTABLE GENERATOR.
AUTOMATIC
TRANSFER SWITCH
'ATS
NON-AUTOMATIC TRANSFER SWITCH
"MTS,"1200 AMP.
50K A.I.C RATING MINIMUM
NEW
PNL
'LC1'
NEW
PNL
'HC1'
NEW
PNL
'NCR1'
60A 3P
NEW GENERATOR
CONNECTION BOX
NEW
TRANSFORMER
TE1
4W
30KVA
SHIELDED
NEW
PNL
'EM1'
NEW
PNL
'EH1'
NEW
PNL
'HB1'
NEW
PNL
'LA1'
TA1
75KVA
480-120/208V, 3PH,4W
NEW
MHE
CHARGING
BUSSWAY
(SEE EP101)
TRANSFORMER TM1
480-120/208V 3PH
4W 30KVA
110A 3P
80A 3P
45A 3P
3#4,#4G,1.25"C
#6
3#1,#300N,#4G, #4IG,2.5"C
PNL
'NCR'
SUB
4#1,#4G,2"C
4#2,#6G,1.5"C
100A.T.
KA
4#1/0,#4G, 2"C
NEW
PNL
'LH'
100A.T.
KA
4#1/0,#4G, 2"C
NEW
PNL
'LG'
100A.T.
KA
NEW
PNL
'LA2'
4#1,#6G,2"C
60A 3P
3#6,#10G,1"C
#8
#2
4#300,#4G,3"C
3#2,#6G,1.25"C
4#3/0, #6G, 2.5"C
200 A.S.
F200
FRS
100 A.S.
F100
FRS
F225
FRS
225 A.S.
3#4/0,#4G,2"C
DHU-1DHU-1
X
X
X
X
MATCH CONDUCTORS IN DISCONNECT
4#1,#6G,2"C
4#3/0, #6G, 2.5"C
200 A.S.
F200
FRS
3 3
E-504
E-502
5 5
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
PROFESSIONAL
REGISTERED
ARKANSAS
S T
A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E R
101 south spring street little rock, ar 72201
501.372.2900 cromwell.com
SEQUENCE
NO.
SHEET NO.
OF
DATE:SOL. NO.
PROJECT NO.
DRAWING NUMBER
SUBMITTED BY:
ENGINEER:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
TO THE BEST OF OUR KNOWLEDGE,
INFORMATION AND BELIEF, BASED
ON AND LIMITED TO OUR NORMAL
FUNCTIONS PERFORMED UNDER OUR
CONTRACT WITH THE GOVERNMENT,
IT IS OUR PROFESSIONAL OPINION
THAT THIS PROJECT IS DESIGNED
IN ACCORDANCE WITH APPLICABLE
DOD REGULATIONS.
ALLAN FULLER
DEFENSE COMMISSARY AGENCY
LACKLAND AFB, TEXAS
FORT LEE, VIRGINIA
DIRECTORATE OF ENGINEERING
30-MAY-2018
EA16MI05
NAVAL AIR STATION
PENSACOLA, FLORIDA
PENSACOLA COMMISSARY FACILITY
ADDITION /ALTERATION
A/E: 2016-001
RTA SOLICITATION ISSUE
SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION
1 5-30-2018 RTA SOLICITATION ISSUE
E-601
WAF
JRD
PSM
ELECTRICAL SINGLE-LINE DIAGRAM
05/30/18
GENERAL NOTES:
1. PROVIDE ARC FLASH CALCULATIONS AND ARC FLASH LABELS ON ALL NEW AND EXISTING EQUIPMENT, INCLUDING ALL PANELBOARDS, TRANSFER SWITCHES, DISTRIBUTION GEAR, ETC.
2. VERIFY THAT KAIC RATINGS MATCH EXISTING ON ALL EQUIPMENT.
3. LIGHT SOLID LINES INDICATE EXISTING TO REMAIN.
HEAVY SOLID LINES INDICATE NEW WORK.
4. EXISTING PANELS NCR / NCR SUB, EM, LC AND HC WILL BE REPLACED WITH NEW PANELS NCR1, EM1, LC1, AND HC1 RESPECTIVELY. THE EXISTING PANELS WILL REMAIN IN SERVICE UNTIL PHASING PLANS ALLOW EXISTING REMAINING CIRCUITS TO BE TRANSFERRED FROM EXISTING PANELS TO NEW PANELS.
CONTRACTOR TO PROVIDE ACCESSIBLE SPLICE POINTS (J-BOXES, ETC.), CONDUITS AND CONDUCTORS, TO EXTEND ALL REMAINING EXISTING CIRCUITS TO NEW PANEL BOARDS. RE-ARRANGE NEW AND EXISTING CIRCUITS IN NEW PANEL BOARDS USING NEW AND EXISTING CONDUCTORS AND CONDUITS. SEE GENERAL NOTE 26 ON E-001 CONCERNING TRACING AND LABELING ALL EXISTING PANEL CIRCUITS. PANELS HB, LA, LD, LE, LF, AND LM AND ASSOCIATED EXISTING CIRCUITS TO REMAIN WITH BREAKERS HAVING CIRCUITS
REMOVED OR MOVED TO NEW PANELS BECOMING “SPARE”.
KEYED NOTES:
PROVIDE TEMPORARY WIRING AT AUTOMATIC TRANSFER SWITCH AND TEMPORARY CIRCUIT BREAKER PROTECTION SO THAT TOTAL LOAD ON TRANSFER SWITCH DOES NOT EXCEED 125 AMPS. ADJUST PROTECTION AS NEEDED DURING
PHASING AS LOADS ARE MOVED FROM PANEL TO PANEL.
THESE EQUIPMENT ITEMS TO BE REMOVED AFTER ALL PHASING IS COMPLETED AND ALL CIRCUITS HAVE BEEN TRANSFERRED FROM NCR/NCR SUB TO NCR1, FROM EM TO EM1, FROM LC TO LC1, AND FROM HC TO HC1.
PROVIDE NEW FUSED SWITCH(S) IN BLANK SPACE(S) IN EXISTING MDP.
DISCONNECT OLD AH1 CONDUCTORS AND CONDUIT BACK TO PANEL. EXISTING FUSE AND SWITCH BECOME SPACE.
PROVIDE NEW 225A FUSED SWITCH FOR NEW AHU-1. COORDINATE WITH MECHANICAL.
PROVIDE NEW BREAKERS IN EXISTING PANEL BLANK SPACES. MATCH KAIC RATINGS OF PANELS.
NEW 100A 480/277V MHE BUSSWAY WITH 8 PLUG IN 30A FUSED DISCONNECT SWITCHES. COORDINATE WITH MHE
CHARGING EQUIPMENT.
N.T.S.
1 ELECTRICAL SINGLE LINE DIAGRAM
3 7-24-2018 REVISIONS TO BID DOCUMENTS
HDEC03-18-R-0007
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER VOLTS LAMPS DESCRIPTION NOTES
A COOPER METALUX 24EN-LD1-54-UNV-L835 277 LED
2'X4' RECESSED LED TROFFER
(5400 LUMENS)
B COOPER METALUX 24EN-LD1-67-UNV-L836 277 LED
2'X4' RECESSED LED TROFFER
(6700 LUMENS)
C COOPER METALUX 24EN-LD1-45-UNV-L837 277 LED
2'X4' RECESSED LED TROFFER
(4500 LUMENS)
E GOTHAM EVO-35-30-6WR-MD-LSS-277 277 LED 6" DOWNLIGHT, 3000 LUMENS
F GOTHAM EVO-SQ-35-15-6WR-MD-LSS-278 277 LED 6" SQUARE, 1500 LUMENS
F1 LIGHTOLIER C4L15NUVBZ10V / C4L10DL35KCCDWVB 277 LED
1500 LUMEN, 4" RECESSED
DOWNLIGHT
G LIGHTING SCIENCE FLB LOWBAY-V2-CW-CLC-SRF-WHT 277 LED INCLUDED
SURFACE MOUNT LED FREEZER
LIGHT
H3 NEO-RAY S123-DW-2-35-0048-1-C-U-ED-1-W 277 LED
4' OVER MIRROR WALL MOUNT
LED FIXTURE
H4 NEO-RAY S123-DW-2-35-0024-1-C-U-ED-1-W 277 LED
2' OVER MIRROR WALL MOUNT
LED FIXTURE
I1 COOPER METALUX 8VT2-LD4-12-DR-UNV-L835-CD1-WL 277 LED
8' LED COOLER FIXTURE (12,000
LUMEN)
I2 COOPER METALUX 8VT2-LD4-9-DR-UNV-L835-CD1-WL 277 LED
8' LED COOLER FIXTURE (9,000
LUMEN)
J COLUMBIA CSR240-8-EB8 277 2-F32T8SPR35
MATCHING 8' FIXTURE OVER
WAREHOUSE OR EQUAL
K PARAMOUNT SC1-1-L-8-2-35K-120-277V 277 LED 8' LED PROCESSING FIXTURE
M COOPER METALUX 24GR6435D 277 LED
2'X4' LENSED LED TROFFER (6400
LUMENS)
N ENERGY SOLUTIONS
F-18VX-N4H-35-RS
277 LED 1'X8' LED SALES TROFFER 1
N ZOOM
QRM-44-D-SNW-LED1650-35K-8’-G-WH
277 LED 1'X8' LED SALES TROFFER 1,5
P COLUMBIA LCL-4-35-ML-U 277 LED 4' LED STRIPLIGHT
R1 SURE-LITES 12-X-25-WH, BATTERY CC-7-LESS- 12 1-12V 25W INC. REMOTE SINGLE HEAD
R2 SURE-LITES 12-X-25-D-WH 12 2-12V 25W INC. REMOTE DOUBLE HEAD
R3 LIGHTGUARD B200G H1212B OT, BATTERY LEC-361 277 REMOTE ONLY
170W REMOTE BATTERY UNIT.
MOUNT AT 10'-0" AFF. USE #10
WIRE FOR REMOTE HEADS
CONNECTIONS.
U5 BETA SEC-EDG-2M-WM-04-D-27-BZ-350-40K-F 277 LED INCLUDED
WALL MOUNTED AREA LIGHT,
MOUNT AT 12' ABOVE FINISHED
GRADE.
V PHOENIX DLP-FLEX-LED 120 LED INCLUDED
DOCK LIGHT WITH 42.5"
ADJUSTABLEARM-MOUNT AT
6'-0" AFF
SURE-LITES LPX70*-WH 277 LED INCLUDED
POLYCARB EXIT SIGN - ARROWS,
MOUNTING, FACES PER PLANS,
BATTERY INCL.
SURE-LITES EEX7*** 277 LED INCLUDED
EDGE-LIT EXIT SIGN - ARROWS,
MOUNTING, FACES PER PLANS,
BATTERY INCL.
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
1. PROVIDE FLANGE KIT AS REQUIRED
2. ALL FLUORESCENT BALLASTS SHALL BE ELECTRONIC RAPID PROGRAMMED START. ALL FIXTURES ARE TO BE FUSED PER SPECIFICATIONS.
3. PROVIDE 1100 LUMEN OUTPUT EMERGENCY BATTERY PACK BALLASTS AS REQUIRED.
4. NOT USED
5. EQUIVALENT FIXTURES ARE ACCEPTABLE, EQUIVALENT IS BASED ON LAMP TYPE, NUMBER OF LAMPS, FIXTURE TYPE, FIXTURE SIZE, FIXTURE APPEARANCE, AND FIXTURE EFFICIENCY.
6. LER = LUMINAIRE EFFICIENCY RATING PER NEMA LE 5
LIGHTING FIXTURE SCHEDULE NOTES (SOME NOTES MAY NOT BE USED):
1. CONTACT MALSTROM WHITE (501-224-2775) FOR ENERGY SOLUTIONS FIXTURE INFORMATION OR ATLANTIC LIGHTING REPRESENTATIVE FOR "ZOOM" FIXTURE.
2. MOUNT REMOTE BALLAST OR EMERGENCY BATTERY PACK ON OPPOSITE SIDE OF WALL AT +10'-0" AFF, OR ABOVE LAY-IN CEILING WHERE APPLICABLE, MOUNT TEST SWITCH NEXT TO BALLAST.
3. COORDIANTE LETTER COLOR WITH OWNER.
4. SINGLE FACE SHALL BE CLEAR, DOUBLE FACE SHALL BE MIRROR.
5. ALTERNATE "N" TYPE LIGHTING FIXTURE
6. SEE PLANS FOR LOCATIONS OF FIXTURES REQUIRING LAMPS WITH TUBE GUARDS.
7. MOUNT ABOVE MIRROR
GENERAL NOTES FOR ALL PLANS:
1. THE COMMISSARY WILL CONTINUE TO OPERATE DURING CONSTRUCTION. THE FOLLOWING NOTES ARE TO BE IMPLEMENTED IN THE CONTRACTOR'S PLAN FOR
ACCOMPLISHING THE CONSTRUCTION WITHIN THE EXISTING FACILITY AND THE ADDITION.
2. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
3. CONTRACTOR SHALL INCLUDE IN HIS (OR HER) BID THE TRANSPORT AND DISPOSAL OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH
ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE.
A. LAMPS, BALLASTS AND OTHER MATERIALS SHALL BE TRANSPORTED AND
DISPOSED OF IN ACCORDANCE WITH ALL D.E.P. AND E.P.A. GUIDELINES.
B. THE CONTRACTOR SHALL PROVIDE WRITTEN CERTIFICATION THAT ALL
MATERIALS WERE RECYCLED OR DISPOSED OF PROPERLY PER THE
GUIDELINES NOTED ABOVE.
4. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD-LOCATED EXACTLY AS SHOWN ON THE DRAWINGS.
COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS, AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT / ENGINEER, MAY BE NECESSARY AND IT IS INTENDED THAT SUCH RENOVATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES ETC. PRIOR TO BID AND IS TO INCLUDE ANY DEVIATIONS IN
THE CONTRACT.
5. LOCATE ALL EXISTING UTILITIES AND PROTECT THEM FROM DAMAGE.
6. REMOVE EXISTING POWER, LIGHTING, SYSTEMS MATERIALS AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY
FUNCTIONAL.
7. ALL RECEPTACLES, DEVICES, LIGHTING, SYSTEMS AND EQUIPMENT NOT SHOWN AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS NOTED OTHERWISE. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO
RECEPTACLES, DEVICES, LIGHTING, SYSTEMS AND EQUIPMENT.
8. CONCEAL ALL CONDUITS BELOW SLAB, ABOVE CEILINGS OR WITHIN WALLS AND COUNTERS UNLESS IMPOSSIBLE TO DO SO DUE TO EXISTING CONDITIONS (i.e.
EXPOSED STRUCTURAL CEILINGS, BUILDING EXTERIOR WALLS OR EXPOSED STRUCTURAL COLUMNS). PROVIDE CUTTING AND PATCHING AND NEW FINISHED
SURFACES.
9. ALL DECA TAGGED EQUIPMENT AND FIXTURES REMOVED AND NOT REUSED SHALL BE TURNED OVER TO THE GOVERNMENT. DISCARD ALL OTHER COMPLETE ITEMS
WHICH THE GOVERNMENT ELECTS TO REFUSE.
10. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON
ENERGIZED EQUIPMENT OR CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS.
11. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR SERVICE. DISABLE SYSTEM ONLY TO MAKE THE SWITCHOVER AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER AT LEAST 24 (TWENTY-FOUR) HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING
SYSTEM. MINIMIZE DURATION OF THE OUTAGE.
12. EXISTING FIRE ALARM SYSTEM: MAINTAIN EXISTING SYSTEM IN SERVICE.
13. REMOVE EXPOSED OR ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES
14. DISCONNECT ABANDONED OUTLETS AND REMOVE DEVICES. REMOVE ABANDONED OUTLETS IF CONDUIT SERVICING THEM IS ABANDONED AND REMOVED.
PROVIDE BLANK COVER FOR ABANDONED OUTLETS WHICH ARE NOT REMOVED.
15. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND/OR DISTRIBUTION EQUIPMENT.
16. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND/OR EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN REMOVED.
17. CLEAN AND REPAIR EXISTING MATERIAL AND/OR EQUIPMENT WHICH REMAINS OR ARE TO BE REUSED.
18. PANELBOARDS: CLEAN EXPOSED SURFACES AND CHECK TIGHTNESS OF ELECTRICAL CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR VACANT POSITIONS. PROVIDE TYPED CIRCUIT DIRECTORY, SHOWING REVISED CIRCUITING ARRANGEMENT.
19. ALL NEW CIRCUIT BREAKERS WITHIN EXISTING PANELBOARD SHALL BE THE SAME MANUFACTURER TYPE, STYLE AND A.I.C. RATING OF EXISTING PANELBOARD.
20. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR CHANGED, REMOVE ALL BRANCH CONDUITS THAT ARE NO LONGER IN SERVICE. IF, IN THE COURSE OF THE WORK, OUTLETS ARE COVERED UP OR OTHERWISE RENDERED INACCESSIBLE, REMOVE ALL WIRING TO SAME OUTLETS TO THE SOURCE. IF A CIRCUIT THAT MUST REMAIN IN SERVICE IS THEREBY INTERRUPTED, RECONNECT IT BY THE MOST INCONSPICUOUS MEANS, SO AS TO REMAIN OPERATIONAL, WITH THE SAME CAPACITY AS BEFORE. REPAIR ALL BUILDING SURFACES DAMAGED AND OPENINGS LEFT BY REMOVAL OF BOXES, PIPING, OR OTHER EQUIPMENT. CLOSE ALL HOLES
LEFT IN JUNCTION BOXES, SWITCHES, PANELS, ETC.
21. WHERE NEW OPENINGS ARE CUT IN EXISTING WALLS, FLOORS OR CEILINGS AND CONCEALED CONDUITS ARE ENCOUNTERED, REMOVE OR RELOCATE CONDUIT AS REQUIRED. WHERE CONDUIT TO BE REMOVED STUBS THROUGH FLOORS, WALLS, AND/OR CEILINGS, REMOVE SUCH CONDUIT TO THE POINT WHERE THE FINISH SURFACES CAN BE PATCHED ADEQUATELY SO THAT NO EVIDENCE OF THE FORMER INSTALLATION REMAINS.
22. REMOVE ALL OUTLET BOXES AT LOCATIONS IN WHICH FIXTURES OR DEVICES WERE REMOVED. PATCH THE CEILING OR WALL TO MATCH EXISTING OR NEW FINISH.
IF OUTLET BOX MUST REMAIN TO MAINTAIN CONTINUITY OF CIRCUITRY, INSTALL AN APPROPRIATELY ACCESSIBLE BLANK PLATE WITH THE FINISH TO MATCH EXISTING OR NEW, WHERE APPLICABLE. PATCH ALL CEILING PLATES AND PATCHES AS DIRECTED BY THE ARCHITECT.
23. RELOCATE ALL OUTLET BOXES WHICH MUST BE REMOVED DUE TO REMOVAL OF WALL, AND WHICH MUST REMAIN ACTIVE IN ORDER TO MAINTAIN CIRCUIT CONTINUITY, IN CEILING OR FLOOR. THESE OUTLET BOXES MUST REMAIN ACCESSIBLE AND MUST HAVE BLANK COVERPLATES AS DESCRIBED ABOVE.
24. DASHED DEVICES (LIGHTING FIXTURES, SPEAKERS, ETC.) INDICATE DEVICES TO BE REMOVED.
25. (NOT USED)
26. IN ADDITION TO CLEANING AND REPLACING DAMAGED DISTRIBUTION PANEL COVERS, TRACE AND LABEL ALL EXISTING PANEL CIRCUITS - PROVIDE NEW TYPED CIRCUIT DIRECTORIES FOR ALL EXISTING AND NEW PANELS. MEASURE AND VERIFY LOADS ON ALL PANEL BOARDS USING AMP CLAMP AND TAKING AT LEAST 3 READINGS ON EACH PANEL AT DIFFERENT TIMES DURING STORE OPERATION. REPORT ANY OVERLOAD CONDITIONS TO CONTRACTING OFFICER. EXERCISE CAUTION WHILE TRACING CIRCUITS AS SEVERAL REMODELS AND ADDITIONS HAVE OCCURRED WITHOUT CIRCUIT DOCUMENTATION.
27. ALL REFRIGERATION ELECTRICAL WORK - BOTH NEW AND DEMOLITION - IS TO BE PROVIDED BY REFRIGERATION CONTRACTOR. IN ADDITION TO MAIN COMPRESSORS THIS INCLUDES REMOTE CASE POWER, LIGHTING, RECEPTACLES AND OUTSIDE TEMPORARY TRAILER HOOKUPS AS INDICATED. REFRIGERATION CONTRACTOR MAY CHOOSE TO HAVE SOME ITEMS DONE BY ELECTRICAL CONTRACTOR, BUT THIS WORK MUST BE COORDINATED BETWEEN THE 2 CONTRACTORS. SEE R-503 DETAIL 5.
28. WHERE ROOF TOP LIGHTING PROTECTION SYSTEMS EXIST, RECONNECT NEW / REPLACED ROOFTOP EQUIPMENT TO LIGHTNING PROTECTION SYSTEM. LIGHTNING PROTECTION CONTRACTOR SHALL DESIGN AND RE-CERTIFY ALL WORK SO AS TO PROVIDE A COMPLETE SYSTEM WITH U L MASTER LABEL CERTIFICATION. MATERIALS MUST BE COMPATIBLE WITH EXISTING LIGHTNING PROTECTION MATERIALS AND ALL MATERIALS IN CONTACT WITH ROOF.
,L
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
101 south spring street little rock, ar 72201
501.372.2900 cromwell.com
SEQUENCE
NO.
SHEET NO.
OF
DATE:SOL. NO.
PROJECT NO.
DRAWING NUMBER
SUBMITTED BY:
ENGINEER:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
TO THE BEST OF OUR KNOWLEDGE,
INFORMATION AND BELIEF, BASED
ON AND LIMITED TO OUR NORMAL
FUNCTIONS PERFORMED UNDER OUR
CONTRACT WITH THE GOVERNMENT,
IT IS OUR PROFESSIONAL OPINION
THAT THIS PROJECT IS DESIGNED
IN ACCORDANCE WITH APPLICABLE
DOD REGULATIONS.
ALLAN FULLER
DEFENSE COMMISSARY AGENCY
LACKLAND AFB, TEXAS
FORT LEE, VIRGINIA
DIRECTORATE OF ENGINEERING
30-MAY-2018
EA16MI05
NAVAL AIR STATION
PENSACOLA, FLORIDA
PENSACOLA COMMISSARY FACILITY
ADDITION /ALTERATION
A/E: 2016-001
RTA SOLICITATION ISSUE
SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION
1 5-30-2018 RTA SOLICITATION ISSUE
E-602
WAF
JRD
PSM
LIGHTING FIXTURE SCHEDULE & GENERAL NOTES FOR ALL
PLANS
05/30/18
3 7-24-2018 REVISIONS TO BID DOCUMENTS
HDEC03-18-R-0007
U
OS
S S
S
P
OS
OP
S
P
OS
U
OS
D S
X S
LV
S
OU
S
S
M S
K S
P S a S
S
S
WH
V
A
SS
V S
V S
S V
S V
V S
C
TV
T
J
CB
R
SPD
G
D
KS
MD
M
#8, 1"C
1GL1-1,3,5
F30 FRS
GFI
60A
F20
CONDUIT SIZE
WIRE SIZE
PHASE CONDUCTOR(S)
HOMERUN DESIGNATION
CIRCUIT DESIGNATION
NEUTRAL
ELECTRICAL SYMBOLS ELECTRICAL SYMBOLS
LIGHT FIXTURES
LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED.
LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED ON EMERGENCY CIRCUIT.
LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED WITH EMERGENCY SELF CONTAINED
BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.
LIGHT FIXTURE, FLUORESCENT OR LED, WALL MOUNTED.
LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED.
LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED ON
EMERGENCY CIRCUIT.
LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED WITH
EMERGENCY SELF CONTAINED BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.
LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, CEILING MOUNTED. (REFER TO
FIXTURE SCHEDULE FOR TYPE).
LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D.,OR LED, CEILING MOUNTED ON EMERGENCY
CIRCUIT.
LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, CEILING MOUNTED WITH EMERGENCY
SELF CONTAINED BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.
LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, WALL MOUNTED. (REFER TO FIXTURE
SCHEDULE FOR TYPE).
EMERGENCY BATTERY POWERED LIGHTING UNIT, WITH SELF CONTAINED BATTERY, CHARGER,
ETC. (REFER TO FIXTURE SCHEDULE FOR BATTERY TYPE, VOLTAGE, LAMP TYPE, WATTAGE,
ETC.) TRIANGLES DEPICT QUANTITY AND AIMING OF LAMP HEADS.
EXIT SIGN, LIGHTED, CEILING MOUNTED. SHADED AREA INDICATES FACE. ARROW DEPICTS
DIRECTIONAL ARROW ON SIGN. WHEN REQUIRED BY THE FIXTURE SCHEDULE, AN EMERGENCY
SELF-CONTAINED BATTERY PACK IS TO REMAIN UNSWITCHED.
EXIT SIGN, LIGHTED, WALL MOUNTED AT 7'-0" AFF UNLESS INDICATED OTHERWISE. WHEN
REQUIRED BY THE FIXTURE SCHEDULE, AN EMERGENCY SELF-CONTAINED BATTERY PACK IS TO
REMAIN UNSWITCHED.
FLOOD LIGHT. ARROW INDICATES DIRECTION OF BEAM.
DOCK LIGHT
PARKING AREA LIGHT FIXTURE (POLE MOUNTED)
SINGLE LINE
CIRCUIT BREAKER, TRIP RATING AS INDICATED, 3 POLE OR AS
INDICATED.
DISCONNECT SWITCH OR LOAD INTERRUPTER SWITCH, CURRENT
RATING AS INDICATED, 3 POLE OR AS INDICATED.
SWITCH WITH GROUND FAULT INTERRUPTER
FUSE, CURRENT RATING AND TYPE WHEN INDICATED.
TRANSFORMER, DESCRIPTION AS NOTED OR PER SCHEDULE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
PHASE SELECTOR SWITCH
AMMETER
VOLT METER
WATT-HOUR METER
SURGE PROTECTIVE DEVICE
AUTOMATIC TRANSFER SWITCH
GENERATOR
SWITCHES (MOUNTED AT 46", UNLESS INDICATED OTHERWISE) (LOWER CASE
LETTER INDICATES DEVICES CONTROLLED)
SWITCH, SINGLE POLE, 20A
SWITCH, DOUBLE POLE, 20A SWITCH
3-WAY, 20A SWITCH
4-WAY, 20A SWITCH
KEY OPERATED
SINGLE POLE SWITCH, WITH PILOT LIGHT
SINGLE POLE MANUAL MOTOR STARTING SWITCH, WITH THERMAL OVERLOAD
ELEMENT AND PROVISIONS FOR LOCKING OPEN
SWITCH, DIMMING (ON FLUORESCENT FIXTURES, COORDINATE WITH BALLAST
MANUFACTURER)
SWITCH, MULLION SWITCH
LOW VOLTAGE WITH MOMENTARY CONTACTS SWITCH
OCCUPANCY SENSOR, ULTRASONIC SWITCH
OCCUPANCY SENSOR, PASSIVE INFRARED
OCCUPANCY SENSOR, PASSIVE INFRARED, CEILING MOUNTED
OCCUPANCY SENSOR, PASSIVE INFRARED, WALL MOUNTED
OCCUPANCY SENSOR, ULTRASONIC, CEILING MOUNTED
OCCUPANCY SENSOR, ULTRASONIC, WALL MOUNTED
MULTIPLE DEVICES LOCATED SIDE BY SIDE (OR ABOVE AND BELOW, IF DIFFERENT
ELEVATIONS ARE SHOWN) AT THE LOCATION INDICATED).
SWITCHGEAR
MAGNETIC MOTOR STARTER (FURNISHED BY DIVISION 15, UNLESS NOTED OTHERWISE)
ELECTRICAL PANELBOARD, FLUSH MOUNTED
ELECTRICAL PANELBOARD, SURFACE MOUNTED
SAFETY SWITCH; 30A CURRENT RATING UNLESS NOTED OTHERWISE. +4'-0" TO HANDLE
FUSIBLE SAFETY SWITCH; CURRENT RATING AND FUSE RATING NOTED. +4'-0" TO
HANDLE.
CIRCUIT BREAKER IN WALL MOUNTED ENCLOSURE
ELECTRICAL TRANSFORMER. FLOOR MOUNTED UNLESS INDICATED OTHERWISE.
MISCELLANEOUS
JUNCTION BOX. WALL MOUNT AS INDICATED. FINAL CONNECTION TO BE MADE BY
ELECTRICAL CONTRACTOR.
CLOCK OUTLET. WALL MOUNTED 7'-6" AFF
MOTOR
10' BARE #6 COILED & EXOTHERMICALLY WELDED TO COLUMN
CABLE TELEVISION OUTLET BOX MOUNTED 18" AFF WITH CONDUIT STUBBED
ABOVE CEILING. PROVIDE PULL CORD.
CONDUIT RUN, EXPOSED
CONDUIT RUN, CONCEALED
FLEXIBLE CONDUIT
CIRCUIT DESIGNATION INDICATES PANELBOARD AND CIRCUIT(S) TO WHICH
HOMERUN IS CONNECTED.
WIRE SIZE SHALL BE NO. 12, UNLESS INDICATED OTHERWISE.
CONDUIT SIZE SHALL BE MINIMUM ALLOWED BY SPECIFICATIONS FOR NO. 12 SIZE
WIRE, 3/4" FOR NO. 10, UNLESS INDICATED OTHERWISE.
CIRCUIT INFORMATION PROVIDED AT THE HOMERUN SYMBOL SHALL APPLY THE
ENTIRE LENGTH OF THE CIRCUIT (FROM PANELBOARD TO LAST LOAD).
WHEN NO PHASE CONDUCTOR OR NEUTRAL IS INDICATED AT THE HOMERUN
SYMBOL, PROVIDE ONE PHASE CONDUCTOR AND ONE NEUTRAL, BOTH NO. 12.
SWITCHING CONDUCTORS, CONDUCTORS FOR NIGHT LIGHT CIRCUITS
(UNSWITCHED), ETC. ARE NOT SHOWN, BUT SHALL BE PROVIDED AS
NECESSARY.
WIRE SIZE INDICATED ON THESE DOCUMENTS AS INDICATED BY "NO." OR "#" HAS
THE SAME MEANING AS "AWG" (N.E.C. NOMENCLATURE). (i.e. "NO. 12" OR "#12"
MEANS "12AWG" IN N.E.C. NOMENCLATURE.)
PAGING DEVICES
LOUDSPEAKER OUTLET, CEILING MOUNTED, DIRECTIONAL.
SUBSCRIPT "V" DENOTES VOLUME CONTROL.
LOUDSPEAKER OUTLET, WALL MOUNTED, DIRECTIONAL. SUBSCRIPT
"V" DENOTES VOLUME CONTROL.
LOUDSPEAKER OUTLET, CEILING MOUNTED, BI-DIRECTIONAL.
SUBSCRIPT "V" DENOTES VOLUME CONTROL.
LOUDSPEAKER OUTLET, CEILING MOUNTED. SUBSCRIPT "V" DENOTES
VOLUME CONTROL.
SPEAKER VOLUME CONTROL
EQUIPMENT GROUND (EQUIPMENT GROUND SHALL BE
PROVIDED IN ALL CIRCUITS AND FEEDERS, WHETHER SHOWN OR
NOT)
CIRCUIT
INFORMATION
ELECTRICAL SYMBOLS
RECEPTACLES (MOUNTED 18" AFF UNLESS INDICATED OTHERWISE)
DUPLEX RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)
DUPLEX RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)
MOUNT 4" ABOVE COUNTER TOP, SINK, OR BACKSPLASH (IF PRESENT).
SINGLE RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)
FLOOR RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)
SINGLE RECEPTACLE OUTLET (50A, 250V, 3 POLE, 3 WIRE, NEMA 10-50R)
SINGLE RECEPTACLE OUTLET (20A, 250V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 6-20R)
SINGLE RECEPTACLE OUTLET (30A, 250V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 6-30R)
SINGLE RECEPTACLE OUTLET (30A, 250V, 3 POLE, 4 WIRE, TWIST-LOCK, GROUNDING TYPE,
NEMA L15-30R)
SINGLE SPECIAL-PURPOSE RECEPTACLE OUTLET; NUMBER CORRESPONDS TO THE
SPECIAL-PURPOSE RECEPTACLE SCHEDULE.
SINGLE RECEPTACLE FOR ELECTRIC RANGE (50A, 125/250V, 3 POLE, 4 WIRE GROUNDING
TYPE NEMA 14-50R)
DUPLEX RECEPTACLE MOUNTED IN CEILING (20A, 125V, 2 POLE, 3 WIRE GROUNDING TYPE
NEMA 5-20R)
TWO (2) DUPLEX RECEPTACLES MOUNTED IN DOUBLE GANG BACKBOX (20A, 125V, 2 POLE, 3
WIRE GROUNDING TYPE NEMA 5-20R)
TWO (2) DUPLEX RECEPTACLES FLOOR MOUNTED IN DOUBLE GANG BACKBOX (20A, 125V, 2
POLE, 3 WIRE GROUNDING TYPE NEMA 5-20R)
+6'
AFF
LIGHT FIXTURE IDENTIFICATION
A a
LOWER CASE LETTER BESIDE FIXTURE DENOTES
SWITCH CONTROL (WHERE APPLICABLE)
UPPER CASE LETTER BESIDE EACH FIXTURE
DENOTES FIXTURE TYPE.
ELECTRICAL SYMBOLS
CD
ES
GENERAL SYMBOLS NOTES :
1. ALL SYMBOLS MAY NOT BE USED.
2. MOUNTING HEIGHTS ARE ABOVE FINISHED
FLOOR OR GRADE TO THE CENTER LINE OF THE
OUTLET, DEVICE, ETC. UNLESS INDICATED
OTHERWISE.
3. LARGE AMPACITY CIRCUIT DESIGNATION
EXAMPLE: "4 SETS OF 3#500, #250N, #1/0G, 4"C
MEANS IN EACH OF FOUR 4" CONDUITS INSTALL
THREE 500 kCM CONDUCTORS, ONE 250 kCM
NEUTRAL AND ONE #1/0 GROUND.
ABBREVIATIONS:
AFF = ABOVE FINISHED FLOOR
AFL = ABOVE FINISHED LANDING
GFI = GROUND FAULT INTERRUPTER
IG = ISOLATED GROUND
UIO = UNLESS INDICATED OTHERWISE
WP = WEATHERPROOF CONSTRUCTION
OF/OI = OWNER FURNISHED / OWNER INSTALLED
CF/CI = CONTRACTOR FURNISHED / CONTRACTOR INSTALLED
SECURITY
MAGNETIC ALARM SWITCH
DURESS ALARM SWITCH
MOTION DETECTOR
CAPACITIVE DETECTOR
CCTV CAMERA LOCATION, CEILING MOUNTED UNLESS INDICATED OTHERWISE
KEYPAD ACCESS ALARM OVERRIDE CONTROL
ELECTRIC PUSH-BUTTON
CARD READER
ELECTRIC STRIKE
SIGNALING DEVICES
PUSHBUTTON
BELL
TYP = TYPICAL
DOOR ALARM (LOCAL). PROVIDE 120V CIRCUIT.DA
TELEPHONE/COMMUNICATIONS/DATA (OUTLETS SHALL BE MOUNTED 18" AFF UNLESS INDICATED
OTHERWISE)
TELEPHONE OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM. SUBSCRIPT: W - WALL MOUNTED AT 54" AFF.
TELEPHONE OUTLET MOUNTED AT 54" AFF.. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN
3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
TELEPHONE FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C
TERMINATED TO PUNCH DOWN BLOCK IN NEAREST COMMUNICATIONS ROOM.
DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C TERMINATED TO PATCH
PANEL IN NEAREST COMMUNICATIONS ROOM.
DATA OUTLET MOUNTED AT 54" AFF. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C
TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
POS DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 BLUE JACKETED CABLES IN 3/4" C TERMINATED TO
PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
WIRELESS ACCESS POINT DATA OUTLET MOUNTED AT 10'-0" AFF OR 1'-0" BELOW CEILING. OUTLET BOX WITH , (2) CAT. 6 YELLOW JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST
COMMUNICATIONS ROOM.
AIR DEFENSE DATA OUTLET MOUNTED 10'-0" AFF OR 1'-0" BELOW CEILING. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
SCALE DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 WHITE JACKETED CABLES IN 3/4" C TERMINATED TO
PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
WOMEN INFANT CHILDREN DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN
3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C TERMINATED TO
PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
POS DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 BLUE JACKETED CABLES IN 3/4" C TERMINATED
TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
SCALE DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 WHITE JACKETED CABLES IN 3/4" C
TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.
COMBO VOICE/DATA OUTLET. QUAD OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES AND (2) CAT.
6 GREEN JACKETED CABLES IN 1" C. TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATION
ROOM.
COMBO VOICE/DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES AND (2) CAT.
6 GREEN JACKETED CABLES IN 1" C. TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATION
ROOM.
4'-0" HIGH x 3/4" THICK VARNISHED TYPE A-C FIRE RATED PLYWOOD BACKBOARD. SEE PLANS FOR
LENGTH. FIRE RETARDANT PAINT IS NOT PREFERRED. SEE 13A TECH GUIDE.
REMOTE ANTENNA OUTLET, 9'-0" AFF. REMOTE ANTENNA LOCATION REQUIRES INSTALLATION OF A 4"
WEATHERPROOF JUNCTION BOX WITH A BLANK COVER PLATE MOUNTED 1" FROM THE CEILING
CENTERED ON THE WALL WITH 3/4" CONDUIT (WEATHERPROOF INSULATED WALL PENETRATIONS) EXTENDING FROM THE JUNCTION BOX TO THE CLOSEST WIRELESS DATA OUTLET; CONDUIT WILL HOUSE CABLE WITH RP-TNC JACK CONNECTOR (IN JUNCTION BOX) TO RP-TNC PLUG CONNECTOR (AT
WIRELESS DATA OUTLET), SEE DESIGN CRITERIA 27 20 00 FOR PHOTOS.
OUTSIDE BUILDING REMOTE ANTENNA OUTLET, REMOTE OUTSIDE ANTENNA LOCATION AT 10'-0"
GROUND LEVEL, REQUIRES WEATHERHEAD AND 3/4" CONDUIT EXTENDING FROM THE OUTSIDE
LOCATION TO THE CLOSEST WIRELESS DATA OUTLET; THIS CONDUIT WILL HOUSE CONSTRUCTION CONTRACTOR PROVIDED LMR SERIES 400 LOW LOSS COAX CABLE WITH N-TYPE MALE CONNECTOR (AT EXTERIOR LOCATION) TO RP-TNC PLUG CONNECTOR (AT WIRELESS DATA OUTLET), SEE DESIGN
CRITERIA 27 20 00.
LIGHTGUIDE INTERCONNECTION UNIT
PUNCHDOWN BLOCK
CAT6 PATCH PANEL
W
W
P
AP
AD
S
P
S
A
A
WP
LIU
PD
PP
WIC
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
PROFESSIONAL
REGISTERED
ARKANSAS
S T A T E O F
ENGINEER
No. 7509
W I L
L I A M A . F U L
L E
R
101 south spring street little rock, ar 72201
501.372.2900 cromwell.com
SEQUENCE
NO.
SHEET NO.
OF
DATE:SOL. NO.
PROJECT NO.
DRAWING NUMBER
SUBMITTED BY:
ENGINEER:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
TO THE BEST OF OUR KNOWLEDGE,
INFORMATION AND BELIEF, BASED
ON AND LIMITED TO OUR NORMAL
FUNCTIONS PERFORMED UNDER OUR
CONTRACT WITH THE GOVERNMENT,
IT IS OUR PROFESSIONAL OPINION
THAT THIS PROJECT IS DESIGNED
IN ACCORDANCE WITH APPLICABLE
DOD REGULATIONS.
ALLAN FULLER
DEFENSE COMMISSARY AGENCY
LACKLAND AFB, TEXAS
FORT LEE, VIRGINIA
DIRECTORATE OF ENGINEERING
30-MAY-2018
EA16MI05
NAVAL AIR STATION
PENSACOLA, FLORIDA
PENSACOLA COMMISSARY FACILITY
ADDITION /ALTERATION
A/E: 2016-001
RTA SOLICITATION ISSUE
SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION
1 5-30-2018 RTA SOLICITATION ISSUE
E-001
WAF
JRD
PSM
ELECTRICAL LEGEND
05/30/18
3 7-24-2018 REVISIONS TO BID DOCUMENTS
HDEC03-18-R-0007
PANEL EH(EXIST) MOUNTING SURFACE LOCATION BAG STO MAIN BUS RATING 250 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 480Y/277 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 25KAIC
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30 EXISTING 1 20
20 1 EXISTING 31 32 EXISTING 1 20
20 1 EXISTING 33 34 EXISTING 1 20
20 1 EXISTING 35 36 EXISTING 1 20
20 1 EXISTING 37 38 EXISTING 1 20
20 1 EXISTING 39 40 EXISTING 1 20
20 1 EXISTING 41 42 EXISTING 1 20
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
EXISTING CONNECTED 105729 VA 0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL NCR(EXIST) MOUNTING SURFACE LOCATION ADP RM MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND+IG
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 SPACE 1 20
20 1 EXISTING 27 28 SPACE 1 20
20 1 SPACE 29 30 EXISTING 1 20
20 1 EXISTING 31 32 EXISTING 1 20
20 1 EXISTING 33 34 EXISTING 1 20
20 1 EXISTING 35 36 EXISTING 1 20
20 1 SPACE 37 38 EXISTING 1 20
20 1 SPACE 39 40 EXISTING 1 20
20 1 SPACE 41 42 EXISTING 1 20
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL NCR1 MOUNTING SURFACE LOCATION NEW COMM MAIN BUS RATING 225 AMPS
MAIN CB POLES 3 FRAME 225 TRIP 110
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND+IG
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 R CHECK OUT 1 500 1 1000 2 500 CHECK OUT 2 R 1 20
20 1 R CHECK OUT 3 500 3 1000 4 500 CHECK OUT 4 R 1 20
20 1 R CHECK OUT 5 500 5 1000 6 500 CHECK OUT 6 R 1 20
20 1 R CHECK OUT 7 500 7 1000 8 500 CHECK OUT 8 R 1 20
20 1 R CHECK OUT 9 500 9 1000 10 500 CHECK OUT 10 R 1 20
20 1 R CHECK OUT 11 500 11 1000 12 500 CHECK OUT 12 R 1 20
20 1 R CHECK OUT 13 500 13 1000 14 500 CHECK OUT 14 R 1 20
20 1 R SCO 15 500 15 1000 16 500 SCO 16 R 1 20
20 1 R SCO 17 500 17 1000 18 500 SCO 18 R 1 20
20 1 R SCO MONITOR 500 19 1000 20 500 SCO MONITOR R 1 20
20 1 R TRAINING ROOM 360 21 720 22 360 COMM ROOM R 1 20
20 1 R BACK DATA CLOSET 1000 23 1360 24 360 COMM ROOM R 1 20
20 3 R POS CABINET 1000 25 1180 26 180 COMM ROOM R 1 20
R 1000 27 1000 28 SPARE 1 20
R 1000 29 1000 30 SPARE 1 20
20 1 R BACK DATA CLOSET VOIP 1000 31 1000 32 SPARE 1 20
20 1 SPARE 33 34 SPARE 1 20
20 1 SPARE 35 36 SPARE 1 20
20 1 SPARE 37 38 SPARE 1 20
20 1 SPARE 39 40 SPARE 1 20
20 1 SPARE 41 42 SPARE 1 20
TOTAL 6180 4720 5360 16 KVA (CONNECTED) 45 AMPS (CONNECTED)
EXISTING CONNECTED -VERIFY- 13 KVA (DEMAND) 36 AMPS (DEMAND)
PANEL EM(EXIST) MOUNTING SURFACE LOCATION CASH MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 SPACE
SPACE 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
SPACE 15 16 EXISTING 1 20
SPACE 17 18 EXISTING 1 20
SPACE 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30 EXISTING 1 20
20 1 EXISTING 31 32 EXISTING 1 20
20 1 EXISTING 33 34 EXISTING 1 20
20 1 EXISTING 35 36 SPACE
SPACE 37 38 SPACE
SPACE 39 40 SPACE
SPACE 41 42 SPACE
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL LA(EXIST) MOUNTING SURFACE LOCATION MHE CHG MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 2 20
20 1 EXISTING 3 4 EXISTING
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30 EXISTING 1 20
20 1 EXISTING 31 32 EXISTING 1 20
20 1 EXISTING 33 34 EXISTING 1 20
20 1 EXISTING 35 36 EXISTING 1 20
20 1 EXISTING 37 38 EXISTING 1 20
20 1 EXISTING 39 40 EXISTING 1 20
20 1 EXISTING 41 42 EXISTING 1 20
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL LB(EXIST) MOUNTING SURFACE LOCATION DELI/BKRY MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30 EXISTING 1 20
20 1 EXISTING 31 32 EXISTING 1 20
20 1 EXISTING 33 34 EXISTING 1 20
20 1 EXISTING 35 36 EXISTING 1 20
20 1 EXISTING 37 38 EXISTING 1 20
20 1 EXISTING 39 40 EXISTING 1 20
20 1 EXISTING 41 42 EXISTING 1 20
30 2 R PANNI 500 43 44 EXISTING 1 20
500 45 46 EXISTING 1 20
30 2 R PANNI 500 47 48 EXISTING 1 20
500 49 50 SPACE
SPACE 51 52 SPACE 2 20
SPACE 53 54 SPACE
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL LB1(EXIST) MOUNTING SURFACE LOCATION DELI/BKRY MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
SPACE 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30 EXISTING 1 20
20 1 EXISTING 31 32 SPACE
20 1 EXISTING 33 34 SPACE
20 1 EXISTING 35 36 SPACE
20 1 EXISTING 37 38 EXISTING 1 20
20 1 EXISTING 39 40 EXISTING 1 20
20 1 EXISTING 41 42 EXISTING 1 20
TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)
0 KVA (DEMAND) 0 AMPS (DEMAND)
PANEL LC(EXIST) MOUNTING SURFACE LOCATION RCVG MAIN BUS RATING 225 AMPS
MAIN POLES FRAME TRIP
VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA
ACCESSORIES SN + EQP GND
DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE
AMPS
POLES TYPE
VOLT
NO
VOLT AMPS
NO
VOLT
TYPE POLES
AMPS
TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP
20 1 EXISTING 1 2 EXISTING 1 20
20 1 EXISTING 3 4 EXISTING 1 20
20 1 EXISTING 5 6 EXISTING 1 20
20 1 EXISTING 7 8 EXISTING 1 20
20 1 EXISTING 9 10 EXISTING 1 20
20 1 EXISTING 11 12 EXISTING 1 20
20 1 EXISTING 13 14 EXISTING 1 20
20 1 EXISTING 15 16 EXISTING 1 20
20 1 EXISTING 17 18 EXISTING 1 20
20 1 EXISTING 19 20 EXISTING 1 20
20 1 EXISTING 21 22 EXISTING 1 20
20 1 EXISTING 23 24 EXISTING 1 20
20 1 EXISTING 25 26 EXISTING 1 20
20 1 EXISTING 27 28 EXISTING 1 20
20 1 EXISTING 29 30…