E-501

2CAT 6 RJ-45 JACK

1"C WITH TWO 4-UTP CAT 6 CABLES

LABEL

LABEL

NEW VIOP SUB

CABINET 31A

EXISTING

FRONT OF

STORE PHONES

CASH

OFFICES

CASH

REGISTERS

TO MAIN

GROUND

BUSS

#3/0 GROUND

EXISTING

PHONES

EXISTING TELEPHONE BOARD

IN MECHANICAL MEZZANINE STAIR

(ROUTE FIBER AND COPPER TO

SUB HUB 31B AS DIRECTED BY

DECA IT)

NEW PHONES

NEW VOIP FULL-SIZE CABINET IN NEW DATA CLOSET

KEYED NOTES:

CONTRACTOR TO PROVIDE PUNCH DOWN BLOCKS (PD), PATCH PANELS (PP), AND LIGHT INTERFACE UNITS (LIU). PROVIDE POWER AS INDICATED, AND FURNISH AND TERMINATE ALL TELECOMM DATA CABLES UNLESS OTHERWISE DIRECTED. PROVIDE NEW HALF-SIZE ENCLOSED SUB-HUB CABINETS (48"H X 22.75"W X 20"D). SUB-HUB CABINET SHALL INCLUDE: POWER STRIP, LOCKING ACRYLIC FRONT DOOR, ADJUSTABLE RAILS (2 PR), VENTED OR WEBBED THREE QUARTER SHELF, EQUIPMENT

MOUNTING BOLTS (30 EA), TWO 4" DIA. INSULATED - BUSHED OPENING IN TOP.

RECONNECT TO EXISTING SECURITY SYSTEM AND NEW PA/MUSIC/PAGING CABINET

CONTRACTOR TO PROVIDE 100 PR COPPER IN 3” CONDUIT AND 3-4 PR CAT 6 IN 2" C.

MAINTAIN INTERCOM AND PAGING SERVICES TO NEW AND EXISTING PHONE LOCATIONS. CONTRACTOR SHALL WORK CLOSELY

WITH STORE MANAGEMENT AND DECA HQ IT SERVICES (RICKY ROSSER 804734-8000 EXT 48467) TO MAINTAIN TELEPHONE SERVICE TO COMMISSARY WITH MINIMAL DISRUPTION DURING SWITCH

OVER TO NEW LINES – BOTH INTERNAL AND EXTERNAL. CONTRACTOR TO PROVIDE DETAILED SWITCH OVER STAGING PLAN FOR APPROVAL BY DECA AND STORE MANAGEMENT. ADDITIONAL CONTRACT MODS FOR OUTAGES AND/OR

OTHER UNANTICIPATED CIRCUMSTANCES WILL NOTE BE ALLOWED.

ROUTE NEW CAT 6 CABLES TO NEAREST HUB. SPLICE COPPER PAIRS AS DIRECTED BY RICKY ROSSER - DECA IT (SEE NOTE 4)

CONTRACTOR TO PROVIDE PUNCH DOWN BLOCKS (PD), PATCH PANELS (PP), AND LIGHT INTERFACE UNITS (LIU). PROVIDE POWER AS INDICATED, AND FURNISH AND TERMINATE ALL TELECOMM DATA CABLES UNLESS OTHERWISE DIRECTED. PROVIDE NEW FULL-SIZE ENCLOSED CABINETS (78"H X 22.75"W X 20"D). DATA CABINET SHALL INCLUDE: POWER STRIP, LOCKING ACRYLIC FRONT DOOR, ADJUSTABLE RAILS (2 PR), VENTED OR WEBBED THREE QUARTER SHELF, EQUIPMENT MOUNTING BOLTS (30 EA), TWO 4" DIA. INSULATED - BUSHED OPENING IN TOP.

PROVIDE 12 STRAND

MULTIMODE FIBER IN 2"

CONDUIT

TO PA SYSTEM

(PAGING) 31A

EXISTING TELEPHONE BOARD

IN OLD RECEIVING MANAGER

OFFICE (ROUTE TO PP'S)

TO ROOM 4

EXISTING

AND NEW

DATA

NEW HALF-SIZE

DATA SUB CABINET

IN DATA CLOSET

EXISTING

PHONES

(ROUTE TO

NEW COMM SUB

HUB CLOSET

31B)

EXISTING

AND NEW

DATA

POS

EXISTING

AND NEW

POS

NEW POS

CABINET

NEW

PC-LAN

CABINET

3-4 PR

CAT 6 IN 2"

PP

PP

L

IU

PP

PP

LIU

PP

LIU

PP

LIU

PP

LIU

PP

LIU

PP

2 6

1/4-TURN PADLOCKABLE

DOOR CATCH

GROUND NEUTRAL Ao Bo Co

LOCKING LIFT CATCH

MOUNTING EARS

PROVISION ONLY ON FRONT

AND BOTTOM DOORS FOR

KIRK KEY INTERLOCK

3" I.D. RUBBER BUSHINGS

FOR TEMPORARY CABLE ENTRY.

1,200 AMP

FUSED OUTDOOR

DISCONNECT

4 SETS OF 4 #350, #3/0 GROUND IN 3"C

OUTDOOR GENERATOR CONNECTION CABINET

BERTHOLD CATALOG #W12-5S-S28W9 (OR EQUAL)

1200A, 480/277V, 2PH, 4W, 35KAIC

(EDIT)

EXISTING

POS DATA CABLING

1 2 3 4 5 6 7 8

G R E E N

W H

IT

E

O R A N G E

W H

IT

E

B

LU

E

W H

IT

E

B R O W N

W H

IT

E

G R E E N

W H

IT

E

B

LU

E

W H

IT

E

O R A N G E

W H

IT

E

B R O W N

W H

IT

E

P A

IR

P A

IR

P A

IR

P A

IR

WIRING SCHEMATIC

RJ - 45 MODULAR CONNECTOR

MALE RJ-45 VIEW

OF BACKSIDE

CAT. 6 CABLE (4 PAIR)

(BELDON #1874 A)

TRACER

COLOR CODING

IS 568 B

STANDARD

WIRE

COLOR

AMPLIFIER(S),

BACKGROUND

MUSIC, AND P.A.

SYSTEM.

4 PR. CAT 6

TO TELE. PATCH PANEL

WITH PAGING CONNECTION

TO TELEPHONE SYSTEM.

TERMINATE IN RJ45

TELE. JACK.

LOCATE SALES FLOOR VOLUME CONTROL WITH HEAD-END EQUIPMENT IN CISIC ROOM 31A.

PA TO BE MUTED BY SIGNAL FROM MASS NOTIFICATION SYSTEM.

1" RIGID STUBBED 2' ABOVE ROOF

WITH WEATHERHEAD AND PULL

CORD FOR FUTURE SATELLITE ANTENNA.

FROM MASS NOTIFICATION SYSTEM

GENERAL NOTES :

1. VOLUME CONTROL FOR SPEAKERS IN

OFFICES IS TO BE WALL MOUNTED WHERE

INDICATED ON PLANS.

2. DEVICES IN COOLER BOXES AND

PREPERATION AREAS TO BE DESIGNED

FOR WET LOCATION.

3. QUANTITIES TO BE AS INDICATED ON

THE PLANS.

4. MUSIC SYSTEM SHALL INCLUDE AM/FM

RADIO, CD PLAYER,

AND AUXILIARY INPUTS FOR THE

"IN-STORE RADIO" SERVICE AND THE

PRERECORDED ANNOUNCEMENT UNIT. ALL

EQUIPMENT TO BE PROVIDED BY

CONTRACTOR EXCEPT FOR "IN-STORE"

RADIO WHICH IS PROVIDED BY

GOVERNMENT OR GOVERNMENT

CONTRACTOR.

5. INTEGRATE PAGING/MUSIC SYSTEM

WITH GF/GI TELEPHONE SYSTEM.

6. ALL CONDUCTORS SHALL BE IN CONDUIT.

TO NEW AND EXISTING SPEAKERS

120V

KEYED NOTES

MICROPHONE

COORDINATE

LOCATION WITH

STORE

OPERATIONS

6B

M

VERIFY CONDUCTOR CONFIGURATION BEFORE

INSTALLATION (SPECIFICALLY, VERIFY IF NEUTRAL

HAS BEEN INSTALLED) SEE E-601

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

101 south spring street little rock, ar 72201

501.372.2900 cromwell.com

SEQUENCE

NO.

SHEET NO.

OF

DATE:SOL. NO.

PROJECT NO.

DRAWING NUMBER

SUBMITTED BY:

ENGINEER:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

TO THE BEST OF OUR KNOWLEDGE,

INFORMATION AND BELIEF, BASED

ON AND LIMITED TO OUR NORMAL

FUNCTIONS PERFORMED UNDER OUR

CONTRACT WITH THE GOVERNMENT,

IT IS OUR PROFESSIONAL OPINION

THAT THIS PROJECT IS DESIGNED

IN ACCORDANCE WITH APPLICABLE

DOD REGULATIONS.

ALLAN FULLER

DEFENSE COMMISSARY AGENCY

LACKLAND AFB, TEXAS

FORT LEE, VIRGINIA

DIRECTORATE OF ENGINEERING

30-MAY-2018

EA16MI05

NAVAL AIR STATION

PENSACOLA, FLORIDA

PENSACOLA COMMISSARY FACILITY

ADDITION /ALTERATION

A/E: 2016-001

RTA SOLICITATION ISSUE

SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION

1 5-30-2018 RTA SOLICITATION ISSUE

E-501

WAF

JRD

PSM

ELECTRICAL DETAILS

05/30/18

N.T.S.

1 VOICE, DATA, OR INTERCOM OUTLET

N.T.S.

3 TELEPHONE / DATA SINGLE-LINE DIAGRAM

N.T.S.

4 MOBILE GENERATOR CONNECTION BOX AND FUSED DISCONNECT

N.T.S.

2 POS/COM DATA CABLING RJ-45 MODULAR CONNECTOR

N.T.S.

5 BACKGROUND MUSIC & P.A. SCHEMATIC

3 7-24-2018 REVISIONS TO BID DOCUMENTS

HDEC03-18-R-0007

AMENDMENT 0006

ATTACHMENT 05

(DELIVERIES SIGNAL SIMILAR)

CUSTOMER, PRODUCE OR MEAT SERVICE

SWITCH LOCATED IN

MGR. OFFICE

EDWARDS #598

OR EQUAL

120/24V 30VA

EDWARDS #852 OR EQUAL PUSH

BUTTON. LOCATE AS INDICATED.

LABEL WITH "RING FOR CUSTOMER

SERVICE" OR "RING FOR (PRODUCE

/MEAT) DELIVERIES" AS INDICATED.

NUMBER OF PUSHBUTTONS AND

BUZZERS AS INDICATED ON PLANS

EDWARDS #340A-G5

OR EQUAL

24VAC

NL

120V

FUSE AT 0.5 AMP

J

J

J

STAND

CHECKOUT

LC

CHECK WRITING

STAND & CARD

READER

SCANNER-

SCALE

OPERATOR

TERMINAL

PRINTER STAND

TELE/POWER

POLE (GF/GI)

MERCHANDISER

CONDUIT & J-BOX

CABLE TRAY

MOUNTED ON TELE-POWER

POLE FOR MERCHANDISER

(GF/GI)

GENERAL NOTES:

1. COORDINATE CABLE TRAY AND POWER

POLE LOCATIONS WITH GF/GI CHECKOUT

STAND CONFIGURATION.

32 1

FINISHED

FLOOR

DUPLEX CONVENIENCE

OUTLET FOR

MERCHANDISER

(GF/GI)

DATA OUTLET (GF/GI)

KEYED NOTES :

4-CONDUCTOR MC CABLE FOR "CLEAN" POWER JUNCTION BOX AT CHECKOUT STAND.

3-CONDUCTOR MC CABLE FOR "DIRTY" POWER JUNCTION BOX AT CHECKOUT STAND.

3-CONDUCTOR MC CABLE FOR DUPLEX CONVENIENCE OUTLET AND CHECKOUT SIGNAL

LIGHT AT CHECKOUT STAND.

FOUR CAT 6 CABLES FROM POS (CISIC) ROOM. TERMINATE EACH CABLE WITH ONE

RJ-45 (CAT 6) JACK.

DURESS ALARM CABLE FROM SECURITY PANEL IN CISIC RM. TERMINATE CABLE WITH

DURESS PUSHBUTTON.

QUEUING CABLE - TERMINATE CABLE WITH PUSHBUTTON.

LANE

LIGHT

(GF/GI)

J-BOX & MC CABLE

TELE/POWER POLE (GF/GI)

ROOF STRUCTURE

DOUBLE CHANNEL

STRUT TRAPEZE

12" CABLE TRAY

GENERAL NOTES:

1. AT EACH CHECKOUT STAND LOCATION, COIL ALL

CABLES AS SHOWN. EACH COIL LENGTH SHALL BE

EQUAL TO THE MOUNTING HEIGHT OF THE J-BOX OR

CABLE TRAY ABOVE FINISHED FLOOR PLUS 10 FEET.

LABEL AND NEATLY SECURE COILS TO RACEWAY,

CABLE TRAY OR DOUBLE CHANNEL STRUT TRAPEZE.

EXTRA CABLE IS PROVIDED FOR FUTURE RELOCATION

OF CHECKSTANDS.

2. THE GOVERNMENT SHALL TERMINATE ALL TYPE MC

CABLES (KEYED NOTES 1, 2, AND 3) AT CHECKOUT

STANDS.

3. AFTER TERMINATION OF THE CABLES WITH JACKS

OR PUSHBUTTONS (KEYED NOTES 4, 5, AND 6) BY THE

CONTRACTOR, THE GOVERNMENT SHALL INSTALL

JACKS AND PUSHBUTTONS AT THE CHECKOUT STANDS.

CONTRACTOR SHALL THEN TERMINATE AND INSTALL DURESS

ALARM BUTTONS.

4. IN AREAS NOT ADJACENT TO CABLE TRAY

(SELF-SERVICE CHECKSTANDS, ETC.), PROVIDE

APPROPRIATE RACEWAYS TO REACH CABLE TRAY.

VERIFY HEIGHT WITH

TELEPHONE / POWER POLE

PROVIDER (GF/GI). INSTALL

CABLE TRAY AT OR ABOVE

24'-0"AFF TO AVOID AIR

FROM DUCTS AND THE

RESULTING

CONDENSATION. AND TO

PROVIDE ADEQUATE

CLEARANCE OVER

MEZZANINE.

CEILING

EL. =

EL. =

0' - 0"

T / FLOOR SLAB

INSTALL CONDUIT FROM TOP OF GONDOLA

UPRIGHT, THROUGH FACTORY PRE-SET

OPENINGS IN UPPER, CENTER, AND LOWER

SPANNERS, AND CONNECT TO JUNCTION BOX

AT BASE OF GONDOLA UPRIGHT FRAME

RUN CONDUIT BENEATH BASE

SHELVES THROUGH FACTORY

PRE_SET OPENINGS WITHIN GONDOLA

BASE SUPPORT

INSTALL 48" LONG LIQUID TIGHT

FLEXIBLE CONDUIT AT ELECTRICAL

RECEPTACLE LOCATIONS

ELECTRICAL TWO-CELL POWER POLE ATTACHED TO TOP

OF GONDOLA UPRIGHT FRAME AND SECURED TO THE

CABLE TRAY ABOVE.

ATTACH ELECTRICAL RECEPTACLE

TO GONDOLA KICKPLATE AT

CENTER OF LAST GONDOLA IN

ROW

INSTALL 48" LONG LIQUID

TIGHT FLEXIBLE CONDUIT AT

ELECTRICAL RECEPTACLE

LOCATIONS

CABLE TRAY SHALL HAVE SOLID

NON-VENTILATED BOTTOM W/ VENTILATED

COVER THAT IS PRE-TREATED FOR FIELD

PAINTING.

PROVIDE CABLE TRAY WITH

A TRAPEZE SUPPORT

BRACKET.

PROVIDE STEEL C-CLAMPS

TO SECURE CABLE TRAY

TRAPEZE TO THE ROOF

STRUCTURE .

POWER POLE SHALL THE

STRAPPED AND BRACED

TO THE CABLE TRAY .

PROVIDE 3/4" CONDUIT FOR

POWER, AND 1" CONDUIT FOR

TELECOMM, IF REQUIRED. POWER

POLE SHALL HAVE A KNOCK OUT

TO FEED POWER FROM THE

CABLE TRAY TO THE POWER POLE.

ATTACH ELECTRICAL RECEPTACLE

TO GONDOLA KICKPLATE AT

CENTER OF LAST GONDOLA IN

ROW

BOTTOM OF ROOF VARIES SEE

STRUCTURAL FOR BOTTOM OF STEEL

ELEVATIONS. (VERIFY IN FIELD)

7' -6

22' - 0" AFF

B / CABLE TRAY

CEILING CEILING

PROVIDE 6" TO 8" CLEARANCE

ABOVE CEILING (MORE OVER

LIGHT FIXTURES)

NEW 1" CONDUIT

NEW 1" CONDUIT

JUNCTION BOX

HEAVY-DUTY COVER

18 1/2" x 11 1/2" x 3/4"

BOX WITH

SOLID BASE

20 1/2" x 13 1/2" x 18 1/2"

NOTE:

1. ENCLOSURE AND COVER SHALL BE RATED FOR NO LESS

THAN 8,000 LBS OVER A 10"x10" AREA AND DESIGNATED AND

TESTED TO A TEMPERATURE OF -50 DEGREES FAHRENHEIT.

MATERIAL COMPRESSIVE STRENGTH SHALL BE NO LESS THAN

11,000 PSI. COVERS SHALL HAVE A MINIMUM COEFFICIENT OF

FRICTION OF .5.

HANDHOLE

(SEE NOTE)

BACKFILL

FINISH GRADE

CONCRETE

4-4"PVC

SPARE (WITH

PULL CORD)

24"MIN. BACKFILL

4" TYP.

BOTH ENDS

4" TYP.

4" TYP.

BOTH ENDS

4" TYP.

MARKER TAPE

3000 PSI

12"

NOTES:

1. DUCT BANKS OTHER THAN 4-4" SHALL HAVE SIMILAR

CONFIGURATION AND CONCRETE COVERAGE.

COORDINATE CONFIGURATION WITH PENSACOLA BCO

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

101 south spring street little rock, ar 72201

501.372.2900 cromwell.com

SEQUENCE

NO.

SHEET NO.

OF

DATE:SOL. NO.

PROJECT NO.

DRAWING NUMBER

SUBMITTED BY:

ENGINEER:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

TO THE BEST OF OUR KNOWLEDGE,

INFORMATION AND BELIEF, BASED

ON AND LIMITED TO OUR NORMAL

FUNCTIONS PERFORMED UNDER OUR

CONTRACT WITH THE GOVERNMENT,

IT IS OUR PROFESSIONAL OPINION

THAT THIS PROJECT IS DESIGNED

IN ACCORDANCE WITH APPLICABLE

DOD REGULATIONS.

ALLAN FULLER

DEFENSE COMMISSARY AGENCY

LACKLAND AFB, TEXAS

FORT LEE, VIRGINIA

DIRECTORATE OF ENGINEERING

30-MAY-2018

EA16MI05

NAVAL AIR STATION

PENSACOLA, FLORIDA

PENSACOLA COMMISSARY FACILITY

ADDITION /ALTERATION

A/E: 2016-001

RTA SOLICITATION ISSUE

SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION

1 5-30-2018 RTA SOLICITATION ISSUE

E-503

WAF

JRD

PSM

ELECTRICAL DETAILS

05/30/18

N.T.S.

2 SERVICE SIGNAL SCHEMATIC

N.T.S.

3 CHECKOUT STAND WIREWAYS

N.T.S.

4 SECTION @ CHECKOUT STAND

N.T.S.

5 POWER POLE GONDOLA MOUNTING DETAIL

3 7-24-2018 REVISIONS TO BID DOCUMENTS

N.T.S.

1 HANDHOLE DETAIL

N.T.S.

6 COMMUNICATIONS DUCT BANK DETAIL

HDEC03-18-R-0007

CB

CB

CB

N

G

4#6

FUSE

RECEIVING AISLE

SPACE

METERING & MAIN

SWITCH SECTION

SELECTOR

SWITCH

WH

GFI

V

A

2000 A.S.

F2000

KRP-C

F200

FRS

F100

FRS

F120

FRS

F100

FRS F200

FRS

200 A.S.100 A.S.100 A.S.200 A.S.100 A.S.200 A.S.

PNL

'HA'

PNL

'HB'

MISC.

ADMIN.LTG. SALES

& STOR.

TRANSFORMER 'TA'

480-120/208V/3 , 4W

30KVA

PNL

'LA'

PNL

'HC'

PNL

'LM'

PNL

'LC'

DRY

STO.

PNL

'NCR'

125KW GENERATOR,480V, 3 PH.,

AND OVERLOAD PROTECTION

INSULATED/

ISOLATED

GROUND

EQUIPMENT

GROUND

200 A.S.

F125

FRS

PNL

'LD'

PNL

'LE'

MECH.

EQUIP.

RM. 83

MECH.

RM. 83

2-200A 2-100A 2-60A

FEEDER TO REFRIGERATION SUBDISTRIBUTION PNL 'CP' 277/480V,3 ,4W

F100

FRS

100A F90

100A.T.

KA

100A.T.

KA

300A.T.

KA

TRANSFORMER 'TM'

480-120/208V/3

4W, 30KVA

PNL

'EM'

CASHIERS

OFFICE

TRANSFORMER 'TE'

480-120/208V/3

4W, 30KVA

SHIELDED

TRANSFORMER 'TB'

480-120/208V/3 , 4W

150KVA

BAKERY

MISC.

ADMIN.

PNL

'HD'

100A

ADP RM/

CASH REG.

PNL

'LB'

PNL

LB1

PNL

'LF'

1200 A.S.

F1200

KTU

SPACE

(1-200A) (2-100A)

WIRE TROUGH

500 A.T.

(TYPE MA)

I-LINE SUBDISTRIBUTION

PANELBOARD "SDP1"

600A BUS, 208V,3 ,4W.

250A.T.

KA

PROC./STO.

& BATTERY

CHARGERS

PNL

'EH'

#6

ELECTROSTATIC SHIELD

4#1/0,#4G, 2"C

3"-4#350 MCM + #4GND

MAIN DISTRIBUTION PANEL 'MDP': 277/480V, 3 ,

4W, 2000 AMP BUS. RATING OF 'MDP' PANEL TO BE

100,000 A.I.C. SYM MINIMUM.

1200A DISCONNECT FUSED AT 1200A, ON EXTERIOR WALL

BY STAIR 31 TO CONNECT PORTABLE GENERATOR.

AUTOMATIC

TRANSFER SWITCH

'ATS

NON-AUTOMATIC TRANSFER SWITCH

"MTS,"1200 AMP.

50K A.I.C RATING MINIMUM

NEW

PNL

'LC1'

NEW

PNL

'HC1'

NEW

PNL

'NCR1'

60A 3P

NEW GENERATOR

CONNECTION BOX

NEW

TRANSFORMER

TE1

4W

30KVA

SHIELDED

NEW

PNL

'EM1'

NEW

PNL

'EH1'

NEW

PNL

'HB1'

NEW

PNL

'LA1'

TA1

75KVA

480-120/208V, 3PH,4W

NEW

MHE

CHARGING

BUSSWAY

(SEE EP101)

TRANSFORMER TM1

480-120/208V 3PH

4W 30KVA

110A 3P

80A 3P

45A 3P

3#4,#4G,1.25"C

#6

3#1,#300N,#4G, #4IG,2.5"C

PNL

'NCR'

SUB

4#1,#4G,2"C

4#2,#6G,1.5"C

100A.T.

KA

4#1/0,#4G, 2"C

NEW

PNL

'LH'

100A.T.

KA

4#1/0,#4G, 2"C

NEW

PNL

'LG'

100A.T.

KA

NEW

PNL

'LA2'

4#1,#6G,2"C

60A 3P

3#6,#10G,1"C

#8

#2

4#300,#4G,3"C

3#2,#6G,1.25"C

4#3/0, #6G, 2.5"C

200 A.S.

F200

FRS

100 A.S.

F100

FRS

F225

FRS

225 A.S.

3#4/0,#4G,2"C

DHU-1DHU-1

X

X

X

X

MATCH CONDUCTORS IN DISCONNECT

4#1,#6G,2"C

4#3/0, #6G, 2.5"C

200 A.S.

F200

FRS

3 3

E-504

E-502

5 5

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

PROFESSIONAL

REGISTERED

ARKANSAS

S T

A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E R

101 south spring street little rock, ar 72201

501.372.2900 cromwell.com

SEQUENCE

NO.

SHEET NO.

OF

DATE:SOL. NO.

PROJECT NO.

DRAWING NUMBER

SUBMITTED BY:

ENGINEER:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

TO THE BEST OF OUR KNOWLEDGE,

INFORMATION AND BELIEF, BASED

ON AND LIMITED TO OUR NORMAL

FUNCTIONS PERFORMED UNDER OUR

CONTRACT WITH THE GOVERNMENT,

IT IS OUR PROFESSIONAL OPINION

THAT THIS PROJECT IS DESIGNED

IN ACCORDANCE WITH APPLICABLE

DOD REGULATIONS.

ALLAN FULLER

DEFENSE COMMISSARY AGENCY

LACKLAND AFB, TEXAS

FORT LEE, VIRGINIA

DIRECTORATE OF ENGINEERING

30-MAY-2018

EA16MI05

NAVAL AIR STATION

PENSACOLA, FLORIDA

PENSACOLA COMMISSARY FACILITY

ADDITION /ALTERATION

A/E: 2016-001

RTA SOLICITATION ISSUE

SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION

1 5-30-2018 RTA SOLICITATION ISSUE

E-601

WAF

JRD

PSM

ELECTRICAL SINGLE-LINE DIAGRAM

05/30/18

GENERAL NOTES:

1. PROVIDE ARC FLASH CALCULATIONS AND ARC FLASH LABELS ON ALL NEW AND EXISTING EQUIPMENT, INCLUDING ALL PANELBOARDS, TRANSFER SWITCHES, DISTRIBUTION GEAR, ETC.

2. VERIFY THAT KAIC RATINGS MATCH EXISTING ON ALL EQUIPMENT.

3. LIGHT SOLID LINES INDICATE EXISTING TO REMAIN.

HEAVY SOLID LINES INDICATE NEW WORK.

4. EXISTING PANELS NCR / NCR SUB, EM, LC AND HC WILL BE REPLACED WITH NEW PANELS NCR1, EM1, LC1, AND HC1 RESPECTIVELY. THE EXISTING PANELS WILL REMAIN IN SERVICE UNTIL PHASING PLANS ALLOW EXISTING REMAINING CIRCUITS TO BE TRANSFERRED FROM EXISTING PANELS TO NEW PANELS.

CONTRACTOR TO PROVIDE ACCESSIBLE SPLICE POINTS (J-BOXES, ETC.), CONDUITS AND CONDUCTORS, TO EXTEND ALL REMAINING EXISTING CIRCUITS TO NEW PANEL BOARDS. RE-ARRANGE NEW AND EXISTING CIRCUITS IN NEW PANEL BOARDS USING NEW AND EXISTING CONDUCTORS AND CONDUITS. SEE GENERAL NOTE 26 ON E-001 CONCERNING TRACING AND LABELING ALL EXISTING PANEL CIRCUITS. PANELS HB, LA, LD, LE, LF, AND LM AND ASSOCIATED EXISTING CIRCUITS TO REMAIN WITH BREAKERS HAVING CIRCUITS

REMOVED OR MOVED TO NEW PANELS BECOMING “SPARE”.

KEYED NOTES:

PROVIDE TEMPORARY WIRING AT AUTOMATIC TRANSFER SWITCH AND TEMPORARY CIRCUIT BREAKER PROTECTION SO THAT TOTAL LOAD ON TRANSFER SWITCH DOES NOT EXCEED 125 AMPS. ADJUST PROTECTION AS NEEDED DURING

PHASING AS LOADS ARE MOVED FROM PANEL TO PANEL.

THESE EQUIPMENT ITEMS TO BE REMOVED AFTER ALL PHASING IS COMPLETED AND ALL CIRCUITS HAVE BEEN TRANSFERRED FROM NCR/NCR SUB TO NCR1, FROM EM TO EM1, FROM LC TO LC1, AND FROM HC TO HC1.

PROVIDE NEW FUSED SWITCH(S) IN BLANK SPACE(S) IN EXISTING MDP.

DISCONNECT OLD AH1 CONDUCTORS AND CONDUIT BACK TO PANEL. EXISTING FUSE AND SWITCH BECOME SPACE.

PROVIDE NEW 225A FUSED SWITCH FOR NEW AHU-1. COORDINATE WITH MECHANICAL.

PROVIDE NEW BREAKERS IN EXISTING PANEL BLANK SPACES. MATCH KAIC RATINGS OF PANELS.

NEW 100A 480/277V MHE BUSSWAY WITH 8 PLUG IN 30A FUSED DISCONNECT SWITCHES. COORDINATE WITH MHE

CHARGING EQUIPMENT.

N.T.S.

1 ELECTRICAL SINGLE LINE DIAGRAM

3 7-24-2018 REVISIONS TO BID DOCUMENTS

HDEC03-18-R-0007

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NUMBER VOLTS LAMPS DESCRIPTION NOTES

A COOPER METALUX 24EN-LD1-54-UNV-L835 277 LED

2'X4' RECESSED LED TROFFER

(5400 LUMENS)

B COOPER METALUX 24EN-LD1-67-UNV-L836 277 LED

2'X4' RECESSED LED TROFFER

(6700 LUMENS)

C COOPER METALUX 24EN-LD1-45-UNV-L837 277 LED

2'X4' RECESSED LED TROFFER

(4500 LUMENS)

E GOTHAM EVO-35-30-6WR-MD-LSS-277 277 LED 6" DOWNLIGHT, 3000 LUMENS

F GOTHAM EVO-SQ-35-15-6WR-MD-LSS-278 277 LED 6" SQUARE, 1500 LUMENS

F1 LIGHTOLIER C4L15NUVBZ10V / C4L10DL35KCCDWVB 277 LED

1500 LUMEN, 4" RECESSED

DOWNLIGHT

G LIGHTING SCIENCE FLB LOWBAY-V2-CW-CLC-SRF-WHT 277 LED INCLUDED

SURFACE MOUNT LED FREEZER

LIGHT

H3 NEO-RAY S123-DW-2-35-0048-1-C-U-ED-1-W 277 LED

4' OVER MIRROR WALL MOUNT

LED FIXTURE

H4 NEO-RAY S123-DW-2-35-0024-1-C-U-ED-1-W 277 LED

2' OVER MIRROR WALL MOUNT

LED FIXTURE

I1 COOPER METALUX 8VT2-LD4-12-DR-UNV-L835-CD1-WL 277 LED

8' LED COOLER FIXTURE (12,000

LUMEN)

I2 COOPER METALUX 8VT2-LD4-9-DR-UNV-L835-CD1-WL 277 LED

8' LED COOLER FIXTURE (9,000

LUMEN)

J COLUMBIA CSR240-8-EB8 277 2-F32T8SPR35

MATCHING 8' FIXTURE OVER

WAREHOUSE OR EQUAL

K PARAMOUNT SC1-1-L-8-2-35K-120-277V 277 LED 8' LED PROCESSING FIXTURE

M COOPER METALUX 24GR6435D 277 LED

2'X4' LENSED LED TROFFER (6400

LUMENS)

N ENERGY SOLUTIONS

F-18VX-N4H-35-RS

277 LED 1'X8' LED SALES TROFFER 1

N ZOOM

QRM-44-D-SNW-LED1650-35K-8’-G-WH

277 LED 1'X8' LED SALES TROFFER 1,5

P COLUMBIA LCL-4-35-ML-U 277 LED 4' LED STRIPLIGHT

R1 SURE-LITES 12-X-25-WH, BATTERY CC-7-LESS- 12 1-12V 25W INC. REMOTE SINGLE HEAD

R2 SURE-LITES 12-X-25-D-WH 12 2-12V 25W INC. REMOTE DOUBLE HEAD

R3 LIGHTGUARD B200G H1212B OT, BATTERY LEC-361 277 REMOTE ONLY

170W REMOTE BATTERY UNIT.

MOUNT AT 10'-0" AFF. USE #10

WIRE FOR REMOTE HEADS

CONNECTIONS.

U5 BETA SEC-EDG-2M-WM-04-D-27-BZ-350-40K-F 277 LED INCLUDED

WALL MOUNTED AREA LIGHT,

MOUNT AT 12' ABOVE FINISHED

GRADE.

V PHOENIX DLP-FLEX-LED 120 LED INCLUDED

DOCK LIGHT WITH 42.5"

ADJUSTABLEARM-MOUNT AT

6'-0" AFF

SURE-LITES LPX70*-WH 277 LED INCLUDED

POLYCARB EXIT SIGN - ARROWS,

MOUNTING, FACES PER PLANS,

BATTERY INCL.

SURE-LITES EEX7*** 277 LED INCLUDED

EDGE-LIT EXIT SIGN - ARROWS,

MOUNTING, FACES PER PLANS,

BATTERY INCL.

LIGHTING FIXTURE SCHEDULE GENERAL NOTES:

1. PROVIDE FLANGE KIT AS REQUIRED

2. ALL FLUORESCENT BALLASTS SHALL BE ELECTRONIC RAPID PROGRAMMED START. ALL FIXTURES ARE TO BE FUSED PER SPECIFICATIONS.

3. PROVIDE 1100 LUMEN OUTPUT EMERGENCY BATTERY PACK BALLASTS AS REQUIRED.

4. NOT USED

5. EQUIVALENT FIXTURES ARE ACCEPTABLE, EQUIVALENT IS BASED ON LAMP TYPE, NUMBER OF LAMPS, FIXTURE TYPE, FIXTURE SIZE, FIXTURE APPEARANCE, AND FIXTURE EFFICIENCY.

6. LER = LUMINAIRE EFFICIENCY RATING PER NEMA LE 5

LIGHTING FIXTURE SCHEDULE NOTES (SOME NOTES MAY NOT BE USED):

1. CONTACT MALSTROM WHITE (501-224-2775) FOR ENERGY SOLUTIONS FIXTURE INFORMATION OR ATLANTIC LIGHTING REPRESENTATIVE FOR "ZOOM" FIXTURE.

2. MOUNT REMOTE BALLAST OR EMERGENCY BATTERY PACK ON OPPOSITE SIDE OF WALL AT +10'-0" AFF, OR ABOVE LAY-IN CEILING WHERE APPLICABLE, MOUNT TEST SWITCH NEXT TO BALLAST.

3. COORDIANTE LETTER COLOR WITH OWNER.

4. SINGLE FACE SHALL BE CLEAR, DOUBLE FACE SHALL BE MIRROR.

5. ALTERNATE "N" TYPE LIGHTING FIXTURE

6. SEE PLANS FOR LOCATIONS OF FIXTURES REQUIRING LAMPS WITH TUBE GUARDS.

7. MOUNT ABOVE MIRROR

GENERAL NOTES FOR ALL PLANS:

1. THE COMMISSARY WILL CONTINUE TO OPERATE DURING CONSTRUCTION. THE FOLLOWING NOTES ARE TO BE IMPLEMENTED IN THE CONTRACTOR'S PLAN FOR

ACCOMPLISHING THE CONSTRUCTION WITHIN THE EXISTING FACILITY AND THE ADDITION.

2. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

3. CONTRACTOR SHALL INCLUDE IN HIS (OR HER) BID THE TRANSPORT AND DISPOSAL OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH

ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE.

A. LAMPS, BALLASTS AND OTHER MATERIALS SHALL BE TRANSPORTED AND

DISPOSED OF IN ACCORDANCE WITH ALL D.E.P. AND E.P.A. GUIDELINES.

B. THE CONTRACTOR SHALL PROVIDE WRITTEN CERTIFICATION THAT ALL

MATERIALS WERE RECYCLED OR DISPOSED OF PROPERLY PER THE

GUIDELINES NOTED ABOVE.

4. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD-LOCATED EXACTLY AS SHOWN ON THE DRAWINGS.

COOPERATION WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS, AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT / ENGINEER, MAY BE NECESSARY AND IT IS INTENDED THAT SUCH RENOVATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES ETC. PRIOR TO BID AND IS TO INCLUDE ANY DEVIATIONS IN

THE CONTRACT.

5. LOCATE ALL EXISTING UTILITIES AND PROTECT THEM FROM DAMAGE.

6. REMOVE EXISTING POWER, LIGHTING, SYSTEMS MATERIALS AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY

FUNCTIONAL.

7. ALL RECEPTACLES, DEVICES, LIGHTING, SYSTEMS AND EQUIPMENT NOT SHOWN AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS NOTED OTHERWISE. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO

RECEPTACLES, DEVICES, LIGHTING, SYSTEMS AND EQUIPMENT.

8. CONCEAL ALL CONDUITS BELOW SLAB, ABOVE CEILINGS OR WITHIN WALLS AND COUNTERS UNLESS IMPOSSIBLE TO DO SO DUE TO EXISTING CONDITIONS (i.e.

EXPOSED STRUCTURAL CEILINGS, BUILDING EXTERIOR WALLS OR EXPOSED STRUCTURAL COLUMNS). PROVIDE CUTTING AND PATCHING AND NEW FINISHED

SURFACES.

9. ALL DECA TAGGED EQUIPMENT AND FIXTURES REMOVED AND NOT REUSED SHALL BE TURNED OVER TO THE GOVERNMENT. DISCARD ALL OTHER COMPLETE ITEMS

WHICH THE GOVERNMENT ELECTS TO REFUSE.

10. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON

ENERGIZED EQUIPMENT OR CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS.

11. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR SERVICE. DISABLE SYSTEM ONLY TO MAKE THE SWITCHOVER AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER AT LEAST 24 (TWENTY-FOUR) HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING

SYSTEM. MINIMIZE DURATION OF THE OUTAGE.

12. EXISTING FIRE ALARM SYSTEM: MAINTAIN EXISTING SYSTEM IN SERVICE.

13. REMOVE EXPOSED OR ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES

14. DISCONNECT ABANDONED OUTLETS AND REMOVE DEVICES. REMOVE ABANDONED OUTLETS IF CONDUIT SERVICING THEM IS ABANDONED AND REMOVED.

PROVIDE BLANK COVER FOR ABANDONED OUTLETS WHICH ARE NOT REMOVED.

15. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND/OR DISTRIBUTION EQUIPMENT.

16. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND/OR EQUIPMENT SERVING UTILIZATION EQUIPMENT THAT HAS BEEN REMOVED.

17. CLEAN AND REPAIR EXISTING MATERIAL AND/OR EQUIPMENT WHICH REMAINS OR ARE TO BE REUSED.

18. PANELBOARDS: CLEAN EXPOSED SURFACES AND CHECK TIGHTNESS OF ELECTRICAL CONNECTIONS. REPLACE DAMAGED CIRCUIT BREAKERS AND PROVIDE CLOSURE PLATES FOR VACANT POSITIONS. PROVIDE TYPED CIRCUIT DIRECTORY, SHOWING REVISED CIRCUITING ARRANGEMENT.

19. ALL NEW CIRCUIT BREAKERS WITHIN EXISTING PANELBOARD SHALL BE THE SAME MANUFACTURER TYPE, STYLE AND A.I.C. RATING OF EXISTING PANELBOARD.

20. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR CHANGED, REMOVE ALL BRANCH CONDUITS THAT ARE NO LONGER IN SERVICE. IF, IN THE COURSE OF THE WORK, OUTLETS ARE COVERED UP OR OTHERWISE RENDERED INACCESSIBLE, REMOVE ALL WIRING TO SAME OUTLETS TO THE SOURCE. IF A CIRCUIT THAT MUST REMAIN IN SERVICE IS THEREBY INTERRUPTED, RECONNECT IT BY THE MOST INCONSPICUOUS MEANS, SO AS TO REMAIN OPERATIONAL, WITH THE SAME CAPACITY AS BEFORE. REPAIR ALL BUILDING SURFACES DAMAGED AND OPENINGS LEFT BY REMOVAL OF BOXES, PIPING, OR OTHER EQUIPMENT. CLOSE ALL HOLES

LEFT IN JUNCTION BOXES, SWITCHES, PANELS, ETC.

21. WHERE NEW OPENINGS ARE CUT IN EXISTING WALLS, FLOORS OR CEILINGS AND CONCEALED CONDUITS ARE ENCOUNTERED, REMOVE OR RELOCATE CONDUIT AS REQUIRED. WHERE CONDUIT TO BE REMOVED STUBS THROUGH FLOORS, WALLS, AND/OR CEILINGS, REMOVE SUCH CONDUIT TO THE POINT WHERE THE FINISH SURFACES CAN BE PATCHED ADEQUATELY SO THAT NO EVIDENCE OF THE FORMER INSTALLATION REMAINS.

22. REMOVE ALL OUTLET BOXES AT LOCATIONS IN WHICH FIXTURES OR DEVICES WERE REMOVED. PATCH THE CEILING OR WALL TO MATCH EXISTING OR NEW FINISH.

IF OUTLET BOX MUST REMAIN TO MAINTAIN CONTINUITY OF CIRCUITRY, INSTALL AN APPROPRIATELY ACCESSIBLE BLANK PLATE WITH THE FINISH TO MATCH EXISTING OR NEW, WHERE APPLICABLE. PATCH ALL CEILING PLATES AND PATCHES AS DIRECTED BY THE ARCHITECT.

23. RELOCATE ALL OUTLET BOXES WHICH MUST BE REMOVED DUE TO REMOVAL OF WALL, AND WHICH MUST REMAIN ACTIVE IN ORDER TO MAINTAIN CIRCUIT CONTINUITY, IN CEILING OR FLOOR. THESE OUTLET BOXES MUST REMAIN ACCESSIBLE AND MUST HAVE BLANK COVERPLATES AS DESCRIBED ABOVE.

24. DASHED DEVICES (LIGHTING FIXTURES, SPEAKERS, ETC.) INDICATE DEVICES TO BE REMOVED.

25. (NOT USED)

26. IN ADDITION TO CLEANING AND REPLACING DAMAGED DISTRIBUTION PANEL COVERS, TRACE AND LABEL ALL EXISTING PANEL CIRCUITS - PROVIDE NEW TYPED CIRCUIT DIRECTORIES FOR ALL EXISTING AND NEW PANELS. MEASURE AND VERIFY LOADS ON ALL PANEL BOARDS USING AMP CLAMP AND TAKING AT LEAST 3 READINGS ON EACH PANEL AT DIFFERENT TIMES DURING STORE OPERATION. REPORT ANY OVERLOAD CONDITIONS TO CONTRACTING OFFICER. EXERCISE CAUTION WHILE TRACING CIRCUITS AS SEVERAL REMODELS AND ADDITIONS HAVE OCCURRED WITHOUT CIRCUIT DOCUMENTATION.

27. ALL REFRIGERATION ELECTRICAL WORK - BOTH NEW AND DEMOLITION - IS TO BE PROVIDED BY REFRIGERATION CONTRACTOR. IN ADDITION TO MAIN COMPRESSORS THIS INCLUDES REMOTE CASE POWER, LIGHTING, RECEPTACLES AND OUTSIDE TEMPORARY TRAILER HOOKUPS AS INDICATED. REFRIGERATION CONTRACTOR MAY CHOOSE TO HAVE SOME ITEMS DONE BY ELECTRICAL CONTRACTOR, BUT THIS WORK MUST BE COORDINATED BETWEEN THE 2 CONTRACTORS. SEE R-503 DETAIL 5.

28. WHERE ROOF TOP LIGHTING PROTECTION SYSTEMS EXIST, RECONNECT NEW / REPLACED ROOFTOP EQUIPMENT TO LIGHTNING PROTECTION SYSTEM. LIGHTNING PROTECTION CONTRACTOR SHALL DESIGN AND RE-CERTIFY ALL WORK SO AS TO PROVIDE A COMPLETE SYSTEM WITH U L MASTER LABEL CERTIFICATION. MATERIALS MUST BE COMPATIBLE WITH EXISTING LIGHTNING PROTECTION MATERIALS AND ALL MATERIALS IN CONTACT WITH ROOF.

,L

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

101 south spring street little rock, ar 72201

501.372.2900 cromwell.com

SEQUENCE

NO.

SHEET NO.

OF

DATE:SOL. NO.

PROJECT NO.

DRAWING NUMBER

SUBMITTED BY:

ENGINEER:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

TO THE BEST OF OUR KNOWLEDGE,

INFORMATION AND BELIEF, BASED

ON AND LIMITED TO OUR NORMAL

FUNCTIONS PERFORMED UNDER OUR

CONTRACT WITH THE GOVERNMENT,

IT IS OUR PROFESSIONAL OPINION

THAT THIS PROJECT IS DESIGNED

IN ACCORDANCE WITH APPLICABLE

DOD REGULATIONS.

ALLAN FULLER

DEFENSE COMMISSARY AGENCY

LACKLAND AFB, TEXAS

FORT LEE, VIRGINIA

DIRECTORATE OF ENGINEERING

30-MAY-2018

EA16MI05

NAVAL AIR STATION

PENSACOLA, FLORIDA

PENSACOLA COMMISSARY FACILITY

ADDITION /ALTERATION

A/E: 2016-001

RTA SOLICITATION ISSUE

SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION

1 5-30-2018 RTA SOLICITATION ISSUE

E-602

WAF

JRD

PSM

LIGHTING FIXTURE SCHEDULE & GENERAL NOTES FOR ALL

PLANS

05/30/18

3 7-24-2018 REVISIONS TO BID DOCUMENTS

HDEC03-18-R-0007

U

OS

S S

S

P

OS

OP

S

P

OS

U

OS

D S

X S

LV

S

OU

S

S

M S

K S

P S a S

S

S

WH

V

A

SS

V S

V S

S V

S V

V S

C

TV

T

J

CB

R

SPD

G

D

KS

MD

M

#8, 1"C

1GL1-1,3,5

F30 FRS

GFI

60A

F20

CONDUIT SIZE

WIRE SIZE

PHASE CONDUCTOR(S)

HOMERUN DESIGNATION

CIRCUIT DESIGNATION

NEUTRAL

ELECTRICAL SYMBOLS ELECTRICAL SYMBOLS

LIGHT FIXTURES

LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED.

LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED ON EMERGENCY CIRCUIT.

LIGHT FIXTURE, FLUORESCENT OR LED, CEILING MOUNTED WITH EMERGENCY SELF CONTAINED

BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.

LIGHT FIXTURE, FLUORESCENT OR LED, WALL MOUNTED.

LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED.

LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED ON

EMERGENCY CIRCUIT.

LIGHT FIXTURE, FLUORESCENT OR LED, INDUSTRIAL STRIP, SURFACE OR PENDANT MOUNTED WITH

EMERGENCY SELF CONTAINED BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.

LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, CEILING MOUNTED. (REFER TO

FIXTURE SCHEDULE FOR TYPE).

LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D.,OR LED, CEILING MOUNTED ON EMERGENCY

CIRCUIT.

LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, CEILING MOUNTED WITH EMERGENCY

SELF CONTAINED BATTERY PACK. BATTERY PACK IS TO REMAIN UNSWITCHED.

LIGHT FIXTURE, INCANDESCENT, FLUORESCENT, H.I.D., OR LED, WALL MOUNTED. (REFER TO FIXTURE

SCHEDULE FOR TYPE).

EMERGENCY BATTERY POWERED LIGHTING UNIT, WITH SELF CONTAINED BATTERY, CHARGER,

ETC. (REFER TO FIXTURE SCHEDULE FOR BATTERY TYPE, VOLTAGE, LAMP TYPE, WATTAGE,

ETC.) TRIANGLES DEPICT QUANTITY AND AIMING OF LAMP HEADS.

EXIT SIGN, LIGHTED, CEILING MOUNTED. SHADED AREA INDICATES FACE. ARROW DEPICTS

DIRECTIONAL ARROW ON SIGN. WHEN REQUIRED BY THE FIXTURE SCHEDULE, AN EMERGENCY

SELF-CONTAINED BATTERY PACK IS TO REMAIN UNSWITCHED.

EXIT SIGN, LIGHTED, WALL MOUNTED AT 7'-0" AFF UNLESS INDICATED OTHERWISE. WHEN

REQUIRED BY THE FIXTURE SCHEDULE, AN EMERGENCY SELF-CONTAINED BATTERY PACK IS TO

REMAIN UNSWITCHED.

FLOOD LIGHT. ARROW INDICATES DIRECTION OF BEAM.

DOCK LIGHT

PARKING AREA LIGHT FIXTURE (POLE MOUNTED)

SINGLE LINE

CIRCUIT BREAKER, TRIP RATING AS INDICATED, 3 POLE OR AS

INDICATED.

DISCONNECT SWITCH OR LOAD INTERRUPTER SWITCH, CURRENT

RATING AS INDICATED, 3 POLE OR AS INDICATED.

SWITCH WITH GROUND FAULT INTERRUPTER

FUSE, CURRENT RATING AND TYPE WHEN INDICATED.

TRANSFORMER, DESCRIPTION AS NOTED OR PER SCHEDULE

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

PHASE SELECTOR SWITCH

AMMETER

VOLT METER

WATT-HOUR METER

SURGE PROTECTIVE DEVICE

AUTOMATIC TRANSFER SWITCH

GENERATOR

SWITCHES (MOUNTED AT 46", UNLESS INDICATED OTHERWISE) (LOWER CASE

LETTER INDICATES DEVICES CONTROLLED)

SWITCH, SINGLE POLE, 20A

SWITCH, DOUBLE POLE, 20A SWITCH

3-WAY, 20A SWITCH

4-WAY, 20A SWITCH

KEY OPERATED

SINGLE POLE SWITCH, WITH PILOT LIGHT

SINGLE POLE MANUAL MOTOR STARTING SWITCH, WITH THERMAL OVERLOAD

ELEMENT AND PROVISIONS FOR LOCKING OPEN

SWITCH, DIMMING (ON FLUORESCENT FIXTURES, COORDINATE WITH BALLAST

MANUFACTURER)

SWITCH, MULLION SWITCH

LOW VOLTAGE WITH MOMENTARY CONTACTS SWITCH

OCCUPANCY SENSOR, ULTRASONIC SWITCH

OCCUPANCY SENSOR, PASSIVE INFRARED

OCCUPANCY SENSOR, PASSIVE INFRARED, CEILING MOUNTED

OCCUPANCY SENSOR, PASSIVE INFRARED, WALL MOUNTED

OCCUPANCY SENSOR, ULTRASONIC, CEILING MOUNTED

OCCUPANCY SENSOR, ULTRASONIC, WALL MOUNTED

MULTIPLE DEVICES LOCATED SIDE BY SIDE (OR ABOVE AND BELOW, IF DIFFERENT

ELEVATIONS ARE SHOWN) AT THE LOCATION INDICATED).

SWITCHGEAR

MAGNETIC MOTOR STARTER (FURNISHED BY DIVISION 15, UNLESS NOTED OTHERWISE)

ELECTRICAL PANELBOARD, FLUSH MOUNTED

ELECTRICAL PANELBOARD, SURFACE MOUNTED

SAFETY SWITCH; 30A CURRENT RATING UNLESS NOTED OTHERWISE. +4'-0" TO HANDLE

FUSIBLE SAFETY SWITCH; CURRENT RATING AND FUSE RATING NOTED. +4'-0" TO

HANDLE.

CIRCUIT BREAKER IN WALL MOUNTED ENCLOSURE

ELECTRICAL TRANSFORMER. FLOOR MOUNTED UNLESS INDICATED OTHERWISE.

MISCELLANEOUS

JUNCTION BOX. WALL MOUNT AS INDICATED. FINAL CONNECTION TO BE MADE BY

ELECTRICAL CONTRACTOR.

CLOCK OUTLET. WALL MOUNTED 7'-6" AFF

MOTOR

10' BARE #6 COILED & EXOTHERMICALLY WELDED TO COLUMN

CABLE TELEVISION OUTLET BOX MOUNTED 18" AFF WITH CONDUIT STUBBED

ABOVE CEILING. PROVIDE PULL CORD.

CONDUIT RUN, EXPOSED

CONDUIT RUN, CONCEALED

FLEXIBLE CONDUIT

CIRCUIT DESIGNATION INDICATES PANELBOARD AND CIRCUIT(S) TO WHICH

HOMERUN IS CONNECTED.

WIRE SIZE SHALL BE NO. 12, UNLESS INDICATED OTHERWISE.

CONDUIT SIZE SHALL BE MINIMUM ALLOWED BY SPECIFICATIONS FOR NO. 12 SIZE

WIRE, 3/4" FOR NO. 10, UNLESS INDICATED OTHERWISE.

CIRCUIT INFORMATION PROVIDED AT THE HOMERUN SYMBOL SHALL APPLY THE

ENTIRE LENGTH OF THE CIRCUIT (FROM PANELBOARD TO LAST LOAD).

WHEN NO PHASE CONDUCTOR OR NEUTRAL IS INDICATED AT THE HOMERUN

SYMBOL, PROVIDE ONE PHASE CONDUCTOR AND ONE NEUTRAL, BOTH NO. 12.

SWITCHING CONDUCTORS, CONDUCTORS FOR NIGHT LIGHT CIRCUITS

(UNSWITCHED), ETC. ARE NOT SHOWN, BUT SHALL BE PROVIDED AS

NECESSARY.

WIRE SIZE INDICATED ON THESE DOCUMENTS AS INDICATED BY "NO." OR "#" HAS

THE SAME MEANING AS "AWG" (N.E.C. NOMENCLATURE). (i.e. "NO. 12" OR "#12"

MEANS "12AWG" IN N.E.C. NOMENCLATURE.)

PAGING DEVICES

LOUDSPEAKER OUTLET, CEILING MOUNTED, DIRECTIONAL.

SUBSCRIPT "V" DENOTES VOLUME CONTROL.

LOUDSPEAKER OUTLET, WALL MOUNTED, DIRECTIONAL. SUBSCRIPT

"V" DENOTES VOLUME CONTROL.

LOUDSPEAKER OUTLET, CEILING MOUNTED, BI-DIRECTIONAL.

SUBSCRIPT "V" DENOTES VOLUME CONTROL.

LOUDSPEAKER OUTLET, CEILING MOUNTED. SUBSCRIPT "V" DENOTES

VOLUME CONTROL.

SPEAKER VOLUME CONTROL

EQUIPMENT GROUND (EQUIPMENT GROUND SHALL BE

PROVIDED IN ALL CIRCUITS AND FEEDERS, WHETHER SHOWN OR

NOT)

CIRCUIT

INFORMATION

ELECTRICAL SYMBOLS

RECEPTACLES (MOUNTED 18" AFF UNLESS INDICATED OTHERWISE)

DUPLEX RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)

DUPLEX RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)

MOUNT 4" ABOVE COUNTER TOP, SINK, OR BACKSPLASH (IF PRESENT).

SINGLE RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)

FLOOR RECEPTACLE OUTLET (20A, 125V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 5-20R)

SINGLE RECEPTACLE OUTLET (50A, 250V, 3 POLE, 3 WIRE, NEMA 10-50R)

SINGLE RECEPTACLE OUTLET (20A, 250V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 6-20R)

SINGLE RECEPTACLE OUTLET (30A, 250V, 2 POLE, 3 WIRE, GROUNDING TYPE, NEMA 6-30R)

SINGLE RECEPTACLE OUTLET (30A, 250V, 3 POLE, 4 WIRE, TWIST-LOCK, GROUNDING TYPE,

NEMA L15-30R)

SINGLE SPECIAL-PURPOSE RECEPTACLE OUTLET; NUMBER CORRESPONDS TO THE

SPECIAL-PURPOSE RECEPTACLE SCHEDULE.

SINGLE RECEPTACLE FOR ELECTRIC RANGE (50A, 125/250V, 3 POLE, 4 WIRE GROUNDING

TYPE NEMA 14-50R)

DUPLEX RECEPTACLE MOUNTED IN CEILING (20A, 125V, 2 POLE, 3 WIRE GROUNDING TYPE

NEMA 5-20R)

TWO (2) DUPLEX RECEPTACLES MOUNTED IN DOUBLE GANG BACKBOX (20A, 125V, 2 POLE, 3

WIRE GROUNDING TYPE NEMA 5-20R)

TWO (2) DUPLEX RECEPTACLES FLOOR MOUNTED IN DOUBLE GANG BACKBOX (20A, 125V, 2

POLE, 3 WIRE GROUNDING TYPE NEMA 5-20R)

+6'

AFF

LIGHT FIXTURE IDENTIFICATION

A a

LOWER CASE LETTER BESIDE FIXTURE DENOTES

SWITCH CONTROL (WHERE APPLICABLE)

UPPER CASE LETTER BESIDE EACH FIXTURE

DENOTES FIXTURE TYPE.

ELECTRICAL SYMBOLS

CD

ES

GENERAL SYMBOLS NOTES :

1. ALL SYMBOLS MAY NOT BE USED.

2. MOUNTING HEIGHTS ARE ABOVE FINISHED

FLOOR OR GRADE TO THE CENTER LINE OF THE

OUTLET, DEVICE, ETC. UNLESS INDICATED

OTHERWISE.

3. LARGE AMPACITY CIRCUIT DESIGNATION

EXAMPLE: "4 SETS OF 3#500, #250N, #1/0G, 4"C

MEANS IN EACH OF FOUR 4" CONDUITS INSTALL

THREE 500 kCM CONDUCTORS, ONE 250 kCM

NEUTRAL AND ONE #1/0 GROUND.

ABBREVIATIONS:

AFF = ABOVE FINISHED FLOOR

AFL = ABOVE FINISHED LANDING

GFI = GROUND FAULT INTERRUPTER

IG = ISOLATED GROUND

UIO = UNLESS INDICATED OTHERWISE

WP = WEATHERPROOF CONSTRUCTION

OF/OI = OWNER FURNISHED / OWNER INSTALLED

CF/CI = CONTRACTOR FURNISHED / CONTRACTOR INSTALLED

SECURITY

MAGNETIC ALARM SWITCH

DURESS ALARM SWITCH

MOTION DETECTOR

CAPACITIVE DETECTOR

CCTV CAMERA LOCATION, CEILING MOUNTED UNLESS INDICATED OTHERWISE

KEYPAD ACCESS ALARM OVERRIDE CONTROL

ELECTRIC PUSH-BUTTON

CARD READER

ELECTRIC STRIKE

SIGNALING DEVICES

PUSHBUTTON

BELL

TYP = TYPICAL

DOOR ALARM (LOCAL). PROVIDE 120V CIRCUIT.DA

TELEPHONE/COMMUNICATIONS/DATA (OUTLETS SHALL BE MOUNTED 18" AFF UNLESS INDICATED

OTHERWISE)

TELEPHONE OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM. SUBSCRIPT: W - WALL MOUNTED AT 54" AFF.

TELEPHONE OUTLET MOUNTED AT 54" AFF.. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN

3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

TELEPHONE FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C

TERMINATED TO PUNCH DOWN BLOCK IN NEAREST COMMUNICATIONS ROOM.

DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C TERMINATED TO PATCH

PANEL IN NEAREST COMMUNICATIONS ROOM.

DATA OUTLET MOUNTED AT 54" AFF. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C

TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

POS DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 BLUE JACKETED CABLES IN 3/4" C TERMINATED TO

PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

WIRELESS ACCESS POINT DATA OUTLET MOUNTED AT 10'-0" AFF OR 1'-0" BELOW CEILING. OUTLET BOX WITH , (2) CAT. 6 YELLOW JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST

COMMUNICATIONS ROOM.

AIR DEFENSE DATA OUTLET MOUNTED 10'-0" AFF OR 1'-0" BELOW CEILING. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES IN 3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

SCALE DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 WHITE JACKETED CABLES IN 3/4" C TERMINATED TO

PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

WOMEN INFANT CHILDREN DATA OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN

3/4" C TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GREEN JACKETED CABLES IN 3/4" C TERMINATED TO

PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

POS DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 BLUE JACKETED CABLES IN 3/4" C TERMINATED

TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

SCALE DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 WHITE JACKETED CABLES IN 3/4" C

TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATIONS ROOM.

COMBO VOICE/DATA OUTLET. QUAD OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES AND (2) CAT.

6 GREEN JACKETED CABLES IN 1" C. TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATION

ROOM.

COMBO VOICE/DATA FLOOR OUTLET. OUTLET BOX WITH (2) CAT. 6 GRAY JACKETED CABLES AND (2) CAT.

6 GREEN JACKETED CABLES IN 1" C. TERMINATED TO PATCH PANEL IN NEAREST COMMUNICATION

ROOM.

4'-0" HIGH x 3/4" THICK VARNISHED TYPE A-C FIRE RATED PLYWOOD BACKBOARD. SEE PLANS FOR

LENGTH. FIRE RETARDANT PAINT IS NOT PREFERRED. SEE 13A TECH GUIDE.

REMOTE ANTENNA OUTLET, 9'-0" AFF. REMOTE ANTENNA LOCATION REQUIRES INSTALLATION OF A 4"

WEATHERPROOF JUNCTION BOX WITH A BLANK COVER PLATE MOUNTED 1" FROM THE CEILING

CENTERED ON THE WALL WITH 3/4" CONDUIT (WEATHERPROOF INSULATED WALL PENETRATIONS) EXTENDING FROM THE JUNCTION BOX TO THE CLOSEST WIRELESS DATA OUTLET; CONDUIT WILL HOUSE CABLE WITH RP-TNC JACK CONNECTOR (IN JUNCTION BOX) TO RP-TNC PLUG CONNECTOR (AT

WIRELESS DATA OUTLET), SEE DESIGN CRITERIA 27 20 00 FOR PHOTOS.

OUTSIDE BUILDING REMOTE ANTENNA OUTLET, REMOTE OUTSIDE ANTENNA LOCATION AT 10'-0"

GROUND LEVEL, REQUIRES WEATHERHEAD AND 3/4" CONDUIT EXTENDING FROM THE OUTSIDE

LOCATION TO THE CLOSEST WIRELESS DATA OUTLET; THIS CONDUIT WILL HOUSE CONSTRUCTION CONTRACTOR PROVIDED LMR SERIES 400 LOW LOSS COAX CABLE WITH N-TYPE MALE CONNECTOR (AT EXTERIOR LOCATION) TO RP-TNC PLUG CONNECTOR (AT WIRELESS DATA OUTLET), SEE DESIGN

CRITERIA 27 20 00.

LIGHTGUIDE INTERCONNECTION UNIT

PUNCHDOWN BLOCK

CAT6 PATCH PANEL

W

W

P

AP

AD

S

P

S

A

A

WP

LIU

PD

PP

WIC

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

PROFESSIONAL

REGISTERED

ARKANSAS

S T A T E O F

ENGINEER

No. 7509

W I L

L I A M A . F U L

L E

R

101 south spring street little rock, ar 72201

501.372.2900 cromwell.com

SEQUENCE

NO.

SHEET NO.

OF

DATE:SOL. NO.

PROJECT NO.

DRAWING NUMBER

SUBMITTED BY:

ENGINEER:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

TO THE BEST OF OUR KNOWLEDGE,

INFORMATION AND BELIEF, BASED

ON AND LIMITED TO OUR NORMAL

FUNCTIONS PERFORMED UNDER OUR

CONTRACT WITH THE GOVERNMENT,

IT IS OUR PROFESSIONAL OPINION

THAT THIS PROJECT IS DESIGNED

IN ACCORDANCE WITH APPLICABLE

DOD REGULATIONS.

ALLAN FULLER

DEFENSE COMMISSARY AGENCY

LACKLAND AFB, TEXAS

FORT LEE, VIRGINIA

DIRECTORATE OF ENGINEERING

30-MAY-2018

EA16MI05

NAVAL AIR STATION

PENSACOLA, FLORIDA

PENSACOLA COMMISSARY FACILITY

ADDITION /ALTERATION

A/E: 2016-001

RTA SOLICITATION ISSUE

SYM. D.O. NO. ACTION DATE DESCRIPTION OF REVISION

1 5-30-2018 RTA SOLICITATION ISSUE

E-001

WAF

JRD

PSM

ELECTRICAL LEGEND

05/30/18

3 7-24-2018 REVISIONS TO BID DOCUMENTS

HDEC03-18-R-0007

PANEL EH(EXIST) MOUNTING SURFACE LOCATION BAG STO MAIN BUS RATING 250 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 480Y/277 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 25KAIC

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30 EXISTING 1 20

20 1 EXISTING 31 32 EXISTING 1 20

20 1 EXISTING 33 34 EXISTING 1 20

20 1 EXISTING 35 36 EXISTING 1 20

20 1 EXISTING 37 38 EXISTING 1 20

20 1 EXISTING 39 40 EXISTING 1 20

20 1 EXISTING 41 42 EXISTING 1 20

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

EXISTING CONNECTED 105729 VA 0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL NCR(EXIST) MOUNTING SURFACE LOCATION ADP RM MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND+IG

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 SPACE 1 20

20 1 EXISTING 27 28 SPACE 1 20

20 1 SPACE 29 30 EXISTING 1 20

20 1 EXISTING 31 32 EXISTING 1 20

20 1 EXISTING 33 34 EXISTING 1 20

20 1 EXISTING 35 36 EXISTING 1 20

20 1 SPACE 37 38 EXISTING 1 20

20 1 SPACE 39 40 EXISTING 1 20

20 1 SPACE 41 42 EXISTING 1 20

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL NCR1 MOUNTING SURFACE LOCATION NEW COMM MAIN BUS RATING 225 AMPS

MAIN CB POLES 3 FRAME 225 TRIP 110

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND+IG

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 R CHECK OUT 1 500 1 1000 2 500 CHECK OUT 2 R 1 20

20 1 R CHECK OUT 3 500 3 1000 4 500 CHECK OUT 4 R 1 20

20 1 R CHECK OUT 5 500 5 1000 6 500 CHECK OUT 6 R 1 20

20 1 R CHECK OUT 7 500 7 1000 8 500 CHECK OUT 8 R 1 20

20 1 R CHECK OUT 9 500 9 1000 10 500 CHECK OUT 10 R 1 20

20 1 R CHECK OUT 11 500 11 1000 12 500 CHECK OUT 12 R 1 20

20 1 R CHECK OUT 13 500 13 1000 14 500 CHECK OUT 14 R 1 20

20 1 R SCO 15 500 15 1000 16 500 SCO 16 R 1 20

20 1 R SCO 17 500 17 1000 18 500 SCO 18 R 1 20

20 1 R SCO MONITOR 500 19 1000 20 500 SCO MONITOR R 1 20

20 1 R TRAINING ROOM 360 21 720 22 360 COMM ROOM R 1 20

20 1 R BACK DATA CLOSET 1000 23 1360 24 360 COMM ROOM R 1 20

20 3 R POS CABINET 1000 25 1180 26 180 COMM ROOM R 1 20

R 1000 27 1000 28 SPARE 1 20

R 1000 29 1000 30 SPARE 1 20

20 1 R BACK DATA CLOSET VOIP 1000 31 1000 32 SPARE 1 20

20 1 SPARE 33 34 SPARE 1 20

20 1 SPARE 35 36 SPARE 1 20

20 1 SPARE 37 38 SPARE 1 20

20 1 SPARE 39 40 SPARE 1 20

20 1 SPARE 41 42 SPARE 1 20

TOTAL 6180 4720 5360 16 KVA (CONNECTED) 45 AMPS (CONNECTED)

EXISTING CONNECTED -VERIFY- 13 KVA (DEMAND) 36 AMPS (DEMAND)

PANEL EM(EXIST) MOUNTING SURFACE LOCATION CASH MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 SPACE

SPACE 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

SPACE 15 16 EXISTING 1 20

SPACE 17 18 EXISTING 1 20

SPACE 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30 EXISTING 1 20

20 1 EXISTING 31 32 EXISTING 1 20

20 1 EXISTING 33 34 EXISTING 1 20

20 1 EXISTING 35 36 SPACE

SPACE 37 38 SPACE

SPACE 39 40 SPACE

SPACE 41 42 SPACE

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL LA(EXIST) MOUNTING SURFACE LOCATION MHE CHG MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 2 20

20 1 EXISTING 3 4 EXISTING

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30 EXISTING 1 20

20 1 EXISTING 31 32 EXISTING 1 20

20 1 EXISTING 33 34 EXISTING 1 20

20 1 EXISTING 35 36 EXISTING 1 20

20 1 EXISTING 37 38 EXISTING 1 20

20 1 EXISTING 39 40 EXISTING 1 20

20 1 EXISTING 41 42 EXISTING 1 20

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL LB(EXIST) MOUNTING SURFACE LOCATION DELI/BKRY MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30 EXISTING 1 20

20 1 EXISTING 31 32 EXISTING 1 20

20 1 EXISTING 33 34 EXISTING 1 20

20 1 EXISTING 35 36 EXISTING 1 20

20 1 EXISTING 37 38 EXISTING 1 20

20 1 EXISTING 39 40 EXISTING 1 20

20 1 EXISTING 41 42 EXISTING 1 20

30 2 R PANNI 500 43 44 EXISTING 1 20

500 45 46 EXISTING 1 20

30 2 R PANNI 500 47 48 EXISTING 1 20

500 49 50 SPACE

SPACE 51 52 SPACE 2 20

SPACE 53 54 SPACE

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

EXISTING CONNECTED -VERIFY- 0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL LB1(EXIST) MOUNTING SURFACE LOCATION DELI/BKRY MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

SPACE 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30 EXISTING 1 20

20 1 EXISTING 31 32 SPACE

20 1 EXISTING 33 34 SPACE

20 1 EXISTING 35 36 SPACE

20 1 EXISTING 37 38 EXISTING 1 20

20 1 EXISTING 39 40 EXISTING 1 20

20 1 EXISTING 41 42 EXISTING 1 20

TOTAL 0 0 0 0 KVA (CONNECTED) 0 AMPS (CONNECTED)

0 KVA (DEMAND) 0 AMPS (DEMAND)

PANEL LC(EXIST) MOUNTING SURFACE LOCATION RCVG MAIN BUS RATING 225 AMPS

MAIN POLES FRAME TRIP

VOLTAGE 208Y/120 PHASE 3 MINIMUM BREAKER INTERRUPTING CAPACITY 10KA

ACCESSORIES SN + EQP GND

DEVICE BRANCH CIRCUIT PHASE LOAD BRANCH CIRCUIT DEVICE

AMPS

POLES TYPE

VOLT

NO

VOLT AMPS

NO

VOLT

TYPE POLES

AMPS

TRIP LOAD DESCRIPTION AMPS A B C AMPS DESCRIPTION LOAD TRIP

20 1 EXISTING 1 2 EXISTING 1 20

20 1 EXISTING 3 4 EXISTING 1 20

20 1 EXISTING 5 6 EXISTING 1 20

20 1 EXISTING 7 8 EXISTING 1 20

20 1 EXISTING 9 10 EXISTING 1 20

20 1 EXISTING 11 12 EXISTING 1 20

20 1 EXISTING 13 14 EXISTING 1 20

20 1 EXISTING 15 16 EXISTING 1 20

20 1 EXISTING 17 18 EXISTING 1 20

20 1 EXISTING 19 20 EXISTING 1 20

20 1 EXISTING 21 22 EXISTING 1 20

20 1 EXISTING 23 24 EXISTING 1 20

20 1 EXISTING 25 26 EXISTING 1 20

20 1 EXISTING 27 28 EXISTING 1 20

20 1 EXISTING 29 30…