This solicitation requests proposals to upgrade the raised access floor in computer rooms. The work includes replacing all access floor panels with concrete core panels, upgrading the access flooring structure with new stringers, lifting existing racks during floor replacement, and cleaning the structural floor. Proposals are due by a unspecified date. The Defense Information Systems Agency is the contracting agency. The upgraded floor must support a static design load of 2,500 pounds and a rolling load of 2,000 pounds with a basket weave stringer configuration, in accordance with DoD Core Data Center engineering standards.
View the file
Other files for this federal contract opportunity
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Electrical Reliability Services, Inc.
Houston Area Office
1455 East Sam Houston Parkway South Suite 190 Pasadena, TX 77503
T (281) 241-2800 F (281) 241-2801
August 30, 2012
Emerald Standard Services Inc 520 Preston AVE Pasadena, TX 77503
Attention: Mr. Roger Pombrol
Subject: Grounding-acceptance Testing Reference No. 3149368
Dear Mr. Pombrol:
Enclosed, is the test report prepared by our lead field engineer. It was our pleasure to be of service to you on this project. If you have any questions, or if we can be of further assistance, please do not hesitate to call.
Sincerely, Electrical Reliability Services, Inc
Heath Deville Supervising Engineer
Enclosures hdeville A Signiture
Electrical Reliability Services, Inc Houston Area Office
1455 East Sam Houston Parkway South Suite 190 Pasadena, TX 77503
T (281) 241-2800
Grounding-acceptance Testing
At
3326 GENERAL HUDNELL DR BLDG
San Antonio, TX
For
Emerald Standard Services Inc 520 Preston AVE
Pasadena, TX 77503
Attention: Mr. Roger Pombrol Order No: 3435-11-024
Reference No. 3149368 Submitted By: Richard Carrera Senior Technician
Reviewed By:
Heath Deville Supervising
Engineer
TABLE OF CONTENTS
1 Purpose
2 Summary
3 Equipment Tested and Inspected
4 Procedures
5 Results And Recommendations
Reference No.3149368 Page 1
1 PURPOSE
1.1 The new electrical equipment and components as defined in Section 3.0 of this report have been inspected and tested to help assure that each component meets manufacturer's and industry standards.
1.2 Evaluating the performance of new equipment prior to energization is considered the most important test the equipment ever receives. These tests often reveal hidden defects, design or installation errors or in-transit damage, which can lead to serious system malfunction and down time.
1.3 This initial testing provides a database for future maintenance system analysis and equipment modification. These test results, when compared with the results from future periodic maintenance tests, can be indicative of life expectancy and thus provide a continuing monitor of reliability throughout the life of the equipment.
2 SUMMARY
This project was initiated by Mr. Roger Pombrol with Emerald Standard Services Inc. All testing was performed by Electrical Reliability Services Field Engineer Richard Carrera, Travis Keck between Tuesday, July 10, 2012 and Saturday, August 25, 2012.
Please refer to Section 5 “Results and Recommendations” for complete details of the testing.
3 EQUIPMENT TESTED AND INSPECTED
1. Ground wells at corners of building, switchgear A and B.
2. Crawl space ground loop-to ground plate connections.
3. Crawl space ground loop-to outside counterpoise loop connections.
4. Sub-floor ground plate and inter-loop connections as per drawings
E201-E204.
4 PROCEDURES
Grounding Systems
Visual and Mechanical Inspection
Reference No.3149368 Page 2
Inspected ground system connections for completeness and proper termination in accordance with design drawings, if available.
Electrical Tests
Performed "fall-of-potential" method test on the main grounding electrode per IEEE Standard No. 81. If suitable locations for test rods were not available, a low resistance dead earth or reference ground was utilized.
Performed "two-point" method test per IEEE Standard No. 81, to determine the ground resistance between the main grounding system and all major electrical equipment frames, system neutral and/or derived neutral points.
5 RESULTS AND RECOMMENDATIONS
5.1 The equipment listed in Section 3 was found to be satisfactory, as indicated by the attached field data sheets.
Results from the forms:
907 Billy Mitchell BLVD
Port Authority Of San Antonio
EMERALD STANDARD SERVICES INCCustomer
Location/Plant
Table of Contents Job #3149368
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
REVISED 4/23/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
PAGE
Owner
PAGE
EQUIPMENT LOCATION
SUBSTATION DATA TEST FORM
POSITION
AIR TERMINALS FOR OUTSIDE AREA
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR
BUILDING 200
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
COUNTERPOISE TO OUTER LOOP CONNECTIONS
BUILDING 200
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
CRAWL SPACE UNDER BUILDING (CONT.)
BUILDING 200
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
CRAWL SPACE UNDER BUILDING
ROOM CR1
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
GROUNDS CONNECTIONS AND PLATES
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL 1
ROOM CR2A
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
GROUNDS CONNECTIONS AND LPLATES
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL 2
ROOM CR2B
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
GROUNDS AND PLATES
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST (2)
TEST WELL 2 (TEST 2)
ROOM CR3
907 BILLY MITCHELL BLVD
24210 - GROUND RESISTANCE TWO TERMINAL
GROUNDS CONNECTIONS AND PLATES
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL 3
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL 4
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL SG A
BUILDING 200
3326 GENERAL HUDNELL DR
24021 - FALL OF POTENTIAL GROUND TEST
TEST WELL SG B
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION AIR TERMINALS FOR OUTSIDE AREA OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR
7/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD33 °C 65
EQUIPMENT I.D.
DET 4TCCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E202 AND E203 MARK UP.
UNCORRECTED CORRECTED RESISTANCE RESULT
GENERATOR # 3 GROUND POINT #21
GENERATOR # 3 AIR TERMINAL #22
GENERATOR # 3 AIR TERMINAL #23
GENERATOR # 2 GROUND POINT #24
GENERATOR # 2 AIR TERMINAL #25
GENERATOR # 2 AIR TERMINAL #26
GENERATOR # 1 GROUND POINT #27
GENERATOR #1 AIR TERMINAL #28
GENERATOR #1 AIR TERMINAL #29
SWITCHGEAR WALK-IN ENCLOSURE #30
SWITCHGEAR WALK-IN ENCLOSURE AIR TERMINAL #31
SWITCHGEAR WALK-IN ENCLOSURE AIR TERMINAL #32
UTILITY BUS "B"
UTILITY BUS "A"
FUEL TANK VENT PIPING GROUND POINT #35
FUEL TANK VENT PIPING AIR TERMINAL #36
DX CHILLER AIR TERMINAL #37
DX CHILLER AIR TERMINAL #38
2.5
2.5
2.5
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
OUTSIDE BURIED GROUND LOOPFROM
COMMENTS: Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
REFER BACK TO DRAWINGS FOR IDENTIFICATION POINTS AND GROUND PLATE NUMBERS.
DEFICIENCIES:
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 COUNTERPOISE TO OUTER LOOP CONNECTIONS
7/18/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD33 °C 72
EQUIPMENT I.D.
AEMC 4620 Ground test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E203 AND E204 MARK UP.
UNCORRECTED CORRECTED RESISTANCE RESULT
COUNTERPOISE CONNECTPOINT-1
COUNTERPOISE CONNECTPOINT-2
COUNTERPOISE CONNECTPOINT-3
COUNTERPOISE CONNECTPOINT-4
COUNTERPOISE CONNECTPOINT-5
COUNTERPOISE CONNECTPOINT-6
COUNTERPOISE CONNECTPOINT-7
COUNTERPOISE CONNECTPOINT-8
COUNTERPOISE CONNECTPOINT-9
COUNTERPOISE CONNECTPOINT-10
COUNTERPOISE CONNECTPOINT-11
COUNTERPOISE CONNECTPOINT-12
COUNTERPOISE CONNECTPOINT-13
COUNTERPOISE CONNECTPOINT-14
COUNTERPOISE CONNECTPOINT-15
COUNTERPOISE CONNECTPOINT-16
COUNTERPOISE CONNECTPOINT-17
COUNTERPOISE CONNECTPOINT-18
COUNTERPOISE CONNECTPOINT-19
COUNTERPOISE CONNECTPOINT-20
COUNTERPOISE CONNECTPOINT-21
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
OUTER GROUND LOOPFROM
COMMENTS: Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NEW
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 CRAWL SPACE UNDER BUILDING (CONT.)
8/20/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E-201 AND E-202
UNCORRECTED CORRECTED RESISTANCE RESULT
POINT 54
GP-10
GP-11
GP-12
GP-13
POINT 66
GP-1
GP-13
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
COMMENTS: GP-13 TO POINT 66 TESTED THRU 3 CONNECTIONS. THE RESISTANCE OF EACH OF THE THREE CONNECTIONS COMBINE TO 80 MoHMS.
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 CRAWL SPACE UNDER BUILDING
8/20/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E-201 AND E-202
UNCORRECTED CORRECTED RESISTANCE RESULT
POINT 7
POINT 7
POINT 9
GP-2
POINT 11
POINT 12
GP-3
POINT 15
POINT 17
POINT 18
GP-4
POINT 20
POINT 24
POINT 25
GP-5
POINT 27
POINT 28
GP-6
POINT 33
POINT 34
GP-7
POINT 36
POINT 39
GP-8
POINT 46
GP-9
POINT 49
GP-1
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
COMMENTS: TESTED SATISFACTORY
REFERENCE POINT FROM 2.5 (DX CHILLER) TO GP-1 WAS 10 MILLI-OHMS
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION ROOM CR1 GROUNDS CONNECTIONS AND PLATES
8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E203 AND E204
UNCORRECTED CORRECTED RESISTANCE RESULT
GPCR1-5
GPCR1-1
POINT 7
GPCR1-2
POINT 8
GPCR1-3
POINT 9 (WIRE TO RM CR2B)
WIRE TO TOP GND LOOP
WIRE TO BOTTOM GND LOOP
GPCR1-4
WIRE TO TOP GND LOOP
WIRE TO BOTTOM GND LOOP
WIRE TO BOTTOM GND LOOP
POINT 18
GPCR1-7
POINT 17 (WIRE TO CRAWL SPACE)
GPCR1-6
POINT 13 (WIRE TO RM CR2B)
POINT 14 (WIRE TO RM CR2A)
GPCR1-6
GPCR1-5
GPCR1-1
GPCR1-1
GPCR1-1
GPCR1-2
GPCR1-3
GPCR1-3
GPCR1-3
GPCR1-3
GPCR1-4
GPCR1-4
GPCR1-8
GPCR1-8
GPCR1-8
GPCR1-7
GPCR1-7
GPCR1-4
GPCR1-4
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
COMMENTS: TESTED SATISFACTORY
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION ROOM CR2A GROUNDS CONNECTIONS AND LPLATES
8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E203 AND E204
UNCORRECTED CORRECTED RESISTANCE RESULT
POINT 1 (WIRE TO CRAWL SPACE)
POINT 14
GPCR2A-4
GPCR2A-5
GPCR2A-6
POINT 5 (WIRE TO CRAWL SPACE)
POINT 6 (WIRE TO RM CR3)
GPCR2A-3
WIRE TO BOTTOM GND LOOP
WIRE TO TOP GND LOOP
GPCR2A-2
GPCR2A-1
POINT 15 (WIRE TO RM CR3)
POINT 7 (WIRE TO RM CR1)
WIRE TO TOP GND LOOP
WIRE TO BOTTOM GND LOOP
GPCR2A-4
GPCR2A-5
GPCR2A-6
GPCR2A-6
GPCR2A-6
GPCR2A-3
GPCR2A-3
GPCR2A-3
GPCR2A-2
GPCR2A-4
GPCR2A-3
GPCR2A-6
GPCR2A-6
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION ROOM CR2B GROUNDS AND PLATES
8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E203 AND E204
UNCORRECTED CORRECTED RESISTANCE RESULT
GPCR2B-6
POINT 1 (WIRE TO RM CR2A)
GPCR2B-4
WIRE TO TOP GND LOOP
WIRE TO BOTTOM GND LOOP
GPCR2B-2
GPCR2B-1
POINT 8 (WIRE TO CRAWL SPACE)
POINT 9
GPCR2B-3
POINT 11 (WIRE TO CRAWL SPACE)
GPCR2B-5
GPCR2B-6
GPCR2B-4
GPCR2B-4
GPCR2B-4
GPCR2B-2
GPCR2B-1
GPCR2B-1
GPCR2B-1
GPCR2B-3
GPCR2B-3
GPCR2B-5
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
OWNER
ADDRESS
CUSTOMER
JOB #
GROUND RESISTANCE
TWO TERMINAL METHOD
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION ROOM CR3 GROUNDS CONNECTIONS AND PLATES
8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40
EQUIPMENT I.D.
DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
DRAWING REFERENCE NUMBER E203 AND E204
UNCORRECTED CORRECTED RESISTANCE RESULT
WIRE TO BOTTOM GND LOOP
WIRE TO TOP GND LOOP
GPCR3-3
POINT 3 (WIRE TO CRAWL SPACE)
GPCR3-8
POINT 12 (WIRE TO CRAWL SPACE)
WIRE TO BOTTOM GND LOOP
WIRE TO TOP GND LOOP
GPCR3-9
GPCR3-4
POINT 3
POINT 6 (WIRE TO CRAWL SPACE)
POINT 9 (WIRE TO CRAWL SPACE)
POINT 9
GPCR3-5
POINT 19 (WIRE TO CRAWL SPACE)
GPCR3-1
GPCR3-6
GPCR3-7
POINT 14
GPCR3-3
GPCR3-3
GPCR3-8
GPCR3-8
GPCR3-8
GPCR3-8
GPCR3-9
GPCR3-4
GPCR3-10
GPCR3-2
GPCR3-2
GPCR3-1
GPCR3-6
GPCR3-6
TEST # TO
OHMSMILLI-OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
MILLI-OHMS OHMS
POINT TO POINTFROM
BARECONNECTING CONDUCTOR INSULATED
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL SG B
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.02
0.06
0.11
0.02
32 0.02
52 0.04
72 0.06
92 0.44
DISTANCE IN FEET
1/2 soil and sand
FALL OF POTENTIAL
OHMS0.06
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The ground electrode is located at the north side of the gear.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
No soil was available nearby. All ground surface was paved as a parking lot.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 1
7/23/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
3.08
3.22
3.31
3.19
60 3.09
240 3.19
260 3.26
280 3.34
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS3.15
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
Test well located at the east corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 300 FEET
61.8% OF TOTAL TEST DISTANCE = 185 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.
Satisfactory.
directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 2
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
17.5
17.7
18.95
17.57
32 17.56
52 17.65
72 18.7
92 19.3
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS17.70
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
DEFICIENCIES & RECOMMENDATIONS :
The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.
directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 2 (TEST 2)
8/21/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 65
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
5.35
5.54
5.64
5.44
32 5.4
52 5.5
72 5.56
92 5.76
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS5.54
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 3
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.16
0.3
0.55
0.23
32 0.16
52 0.26
72 0.36
92 2.3
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS0.30
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the west corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 4
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
8.59
8.91
9.45
8.74
32 8.69
52 8.9
72 9.4
92 9.54
DISTANCE IN FEET
1/2 soil and sand
FALL OF POTENTIAL
OHMS8.91
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the north corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL SG A
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.2
0.24
0.32
0.21
32 0.2
52 0.21
72 0.24
92 0.48
DISTANCE IN FEET
1/2 rock over top soil
FALL OF POTENTIAL
OHMS0.24
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The ground electrode for the switchgear is located adjacent to the gear on the north side of the gear.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
No soil was available nearby. All ground surface was paved as a parking lot.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 1
7/23/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
3.08
3.22
3.31
3.19
60 3.09
240 3.19
260 3.26
280 3.34
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS3.15
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
Test well located at the east corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 300 FEET
61.8% OF TOTAL TEST DISTANCE = 185 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.
Satisfactory.
directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 2
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
17.5
17.7
18.95
17.57
32 17.56
52 17.65
72 18.7
92 19.3
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS17.70
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.
directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.
WETDAMPDRY
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 2 (TEST 2)
8/21/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 65
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
5.35
5.54
5.64
5.44
32 5.4
52 5.5
72 5.56
92 5.76
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS5.54
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 3
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.16
0.3
0.55
0.23
32 0.16
52 0.26
72 0.36
92 2.3
DISTANCE IN FEET
1/2 sod
FALL OF POTENTIAL
OHMS0.30
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the west corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL 4
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
8.59
8.91
9.45
8.74
32 8.69
52 8.9
72 9.4
92 9.54
DISTANCE IN FEET
1/2 soil and sand
FALL OF POTENTIAL
OHMS8.91
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The test well is located at the north corner of the building.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL SG A
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.2
0.24
0.32
0.21
32 0.2
52 0.21
72 0.24
92 0.48
DISTANCE IN FEET
1/2 rock over top soil
FALL OF POTENTIAL
OHMS0.24
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The ground electrode for the switchgear is located adjacent to the gear on the north side of the gear.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
LENGTH OF GROUND RODS
NUMBER OF RODS
SOIL TYPE
DIAMETER OF GROUND ROD
TYPE OF GROUND ROD
four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:
24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
EQPT. LOCATION
PAGE
OWNER
ADDRESS
CUSTOMER
JOB #
FALL OF POTENTIAL
GROUND TEST
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
NA
3149368
DATE LAST INSPECTION
EMERALD STANDARD SERVICES INC
529 PRESTON AVE; PASADENA TX 77503
PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226
907 BILLY MITCHELL BLVDLOCATION/PLANT
DATE
SUBSTATION BUILDING 200 TEST WELL SG B
7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72
EQUIPMENT I.D.
RESISTANCE IN OHMS
TWO-POINT
Copper
SOIL CONDITION:
TEST TYPE:
0.02
0.06
0.11
0.02
32 0.02
52 0.04
72 0.06
92 0.44
DISTANCE IN FEET
1/2 soil and sand
FALL OF POTENTIAL
OHMS0.06
FEET10
AWG2/0CONNECTING CONDUCTOR SIZE
The ground electrode is located at the north side of the gear.
DESCRIPTION OF GROUND SYSTEM UNDER TEST
INDUCED FREQUENCY
AUXILIARY POTENTIAL ELECTRODE
DISTANCE C1 - C2 = 100 FEET
61.8% OF TOTAL TEST DISTANCE = 62 FEET
GROUND RESISTANCE @ 61.8% OF DISTANCE
COMMENTS:
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.
Comment Summary Job #3149368
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
Owner
Customer EMERALD STANDARD SERVICES INC
Port Authority Of San Antonio
Location/Plant: 907 Billy Mitchell BLVD
Substation: AIR TERMINALS FOR OUTSIDE AREA Date: 7/21/2012
Equipment I.D.: OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
REFER BACK TO DRAWINGS FOR IDENTIFICATION POINTS AND GROUND PLATE NUMBERS.
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: COUNTERPOISE TO OUTER LOOP CONNECTIONS
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 8/20/2012
Equipment I.D.: CRAWL SPACE UNDER BUILDING (CONT.)
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
GP-13 TO POINT 66 TESTED THRU 3 CONNECTIONS. THE RESISTANCE OF EACH OF THE THREE CONNECTIONS COMBINE TO 80 MoHMS.Comments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 8/20/2012
Equipment I.D.: CRAWL SPACE UNDER BUILDING
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
TESTED SATISFACTORYComments:
REFERENCE POINT FROM 2.5 (DX CHILLER) TO GP-1 WAS 10 MILLI-OHMS
Job #3149368
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
Location/Plant: 907 Billy Mitchell BLVD
Substation: ROOM CR1 Date: 8/21/2012
Equipment I.D.: GROUNDS CONNECTIONS AND PLATES
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
TESTED SATISFACTORYComments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/23/2012
Equipment I.D.: TEST WELL 1
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.Comments:
Satisfactory.
Location/Plant: 907 Billy Mitchell BLVD
Substation: ROOM CR2A Date: 8/21/2012
Equipment I.D.: GROUNDS CONNECTIONS AND LPLATES
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
TESTED SATISFACTORYComments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: ROOM CR2B Date: 8/21/2012
Equipment I.D.: GROUNDS AND PLATES
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
TESTED SATISFACTORYComments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 8/21/2012
Equipment I.D.: TEST WELL 2 (TEST 2)
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST (2)
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Job #3149368
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
Location/Plant: 907 Billy Mitchell BLVD
Substation: ROOM CR3 Date: 8/21/2012
Equipment I.D.: GROUNDS CONNECTIONS AND PLATES
Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL
TESTED SATISFACTORYComments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: TEST WELL 3
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: TEST WELL 4
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: TEST WELL SG A
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: TEST WELL SG B
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:
Deficiency Summary Job #3149368
Electrical Reliability Services Inc.
Houston Area Service Center
1455 E. Sam Houston Pkwy S Suite 190
Pasadena, TX 77503 Phone 281-241-2800
REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com
Owner
Customer EMERALD STANDARD SERVICES INC
Port Authority Of San Antonio
Location/Plant: 907 Billy Mitchell BLVD
Substation: BUILDING 200 Date: 7/18/2012
Equipment I.D.: TEST WELL 2
Equipment: 24021 - FALL OF POTENTIAL GROUND TEST
The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.Deficiencies:
| 3149368.pdf |
| PowerDb Combine.pdf |
| 3149368 PDB.pdf |
| TEST WELL SG B.pdf |
| PowerDB (Emerson).pdf |
| TEST WELL 1.pdf |
| TEST WELL 2 TEST 2.pdf |
| TEST WELL 2.pdf |
| TEST WELL 3 .pdf |
| TEST WELL 4 .pdf |
| TEST WELL SG A .pdf |
| TEST WELL 1.pdf |
| TEST WELL 2.pdf |
| TEST WELL 2 TEST 2.pdf |
| TEST WELL 3 .pdf |
| TEST WELL 4 .pdf |
| TEST WELL SG A .pdf |
| TEST WELL SG B.pdf |