Appendix J - SRG Testing Report 2012.pdf

PDF 491 KB Posted

Attached to
Raised Floor Upgrade Federal contract opportunity
Solicitation number
HC102821R0012
Issued by
Defense Information Systems Agency

About this file

This solicitation requests proposals to upgrade the raised access floor in computer rooms. The work includes replacing all access floor panels with concrete core panels, upgrading the access flooring structure with new stringers, lifting existing racks during floor replacement, and cleaning the structural floor. Proposals are due by a unspecified date. The Defense Information Systems Agency is the contracting agency. The upgraded floor must support a static design load of 2,500 pounds and a rolling load of 2,000 pounds with a basket weave stringer configuration, in accordance with DoD Core Data Center engineering standards.

View the file

Other files for this federal contract opportunity

Other files attached to Raised Floor Upgrade, newest first.
File Type Posted
Solicitation Q and A Rounds1-4 (21June2021).xlsx XLSX spreadsheet
HC102821R00120009.pdf PDF
Solicitation Q and A Rounds1-3 (26May2021).xlsx XLSX spreadsheet
HC102821R00120008.pdf PDF
HC102821R00180007.pdf PDF
Revised Solicitation Q and A Round 2 Date 4.12.21.xlsx XLSX spreadsheet
Appendix I - SRG Drawing.pdf PDF
Appendix B - Raised Grid Access Flooring.docx DOCX document
Appendix C - Signal Reference Grid for Grounding.docx DOCX document
HC102821R00120006.pdf PDF
HC102821R00120005.pdf PDF
DISA - Raised Floor System Report San Antonio TX -Revised 20180206.pdf PDF
MECH-DATA CENTER SAN ANTONIO.pdf PDF
HC102821R00120004.pdf PDF
ELEC-DATA CENTER SAN ANTONIO.pdf PDF
SAT Raised Floor Pre-Proposal Site Visit Sign-in.pdf PDF
Solicitation Q and A Rounds 1 and 2 (23Mar2021).xlsx XLSX spreadsheet
HC102821R0012-0003.pdf PDF
Solicitation Q and A Round 1.xlsx XLSX spreadsheet
HC102821R0012-0002.pdf PDF
HC102821R0012-0001.pdf PDF
encl 4_final qasp - SAT Raised Floor Upgrade.pdf PDF
HC102821R0012-CLIN Pricing Worksheet (2).xlsx XLSX spreadsheet
Appendix G - SEC Inventory Format (excel spreadshhet).xlsx XLSX spreadsheet
Appendix E - MIL-STD-188.pdf PDF
Appendix F - Contractor NDA.docx DOCX document
SCA WD 2015-5253 Rev 12.pdf PDF
Appendix H - Electrical Safety Program.pdf PDF
encl 4_qasp - SAT CW Filtration and Upgrades.docx DOCX document
Appendix A - Raised Floor Upgrade Drawing.pdf PDF
Appendix C - Signal Reference Grid for Grounding.docx DOCX document
Appendix B - Raised Grid Access Flooring.pdf PDF
HC102821R0012-Raised Floor Upgrade RFP.pdf PDF
Appendix D - SRG Grounding System Commissioning.docx DOCX document
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Electrical Reliability Services, Inc.

Houston Area Office

1455 East Sam Houston Parkway South Suite 190 Pasadena, TX 77503

T (281) 241-2800 F (281) 241-2801

August 30, 2012

Emerald Standard Services Inc 520 Preston AVE Pasadena, TX 77503

Attention: Mr. Roger Pombrol

Subject: Grounding-acceptance Testing Reference No. 3149368

Dear Mr. Pombrol:

Enclosed, is the test report prepared by our lead field engineer. It was our pleasure to be of service to you on this project. If you have any questions, or if we can be of further assistance, please do not hesitate to call.

Sincerely, Electrical Reliability Services, Inc

Heath Deville Supervising Engineer

Enclosures hdeville A Signiture

Electrical Reliability Services, Inc Houston Area Office

1455 East Sam Houston Parkway South Suite 190 Pasadena, TX 77503

T (281) 241-2800

Grounding-acceptance Testing

At

3326 GENERAL HUDNELL DR BLDG

San Antonio, TX

For

Emerald Standard Services Inc 520 Preston AVE

Pasadena, TX 77503

Attention: Mr. Roger Pombrol Order No: 3435-11-024

Reference No. 3149368 Submitted By: Richard Carrera Senior Technician

Reviewed By:

Heath Deville Supervising

Engineer

TABLE OF CONTENTS

1 Purpose

2 Summary

3 Equipment Tested and Inspected

4 Procedures

5 Results And Recommendations

Reference No.3149368 Page 1

1 PURPOSE

1.1 The new electrical equipment and components as defined in Section 3.0 of this report have been inspected and tested to help assure that each component meets manufacturer's and industry standards.

1.2 Evaluating the performance of new equipment prior to energization is considered the most important test the equipment ever receives. These tests often reveal hidden defects, design or installation errors or in-transit damage, which can lead to serious system malfunction and down time.

1.3 This initial testing provides a database for future maintenance system analysis and equipment modification. These test results, when compared with the results from future periodic maintenance tests, can be indicative of life expectancy and thus provide a continuing monitor of reliability throughout the life of the equipment.

2 SUMMARY

This project was initiated by Mr. Roger Pombrol with Emerald Standard Services Inc. All testing was performed by Electrical Reliability Services Field Engineer Richard Carrera, Travis Keck between Tuesday, July 10, 2012 and Saturday, August 25, 2012.

Please refer to Section 5 “Results and Recommendations” for complete details of the testing.

3 EQUIPMENT TESTED AND INSPECTED

1. Ground wells at corners of building, switchgear A and B.

2. Crawl space ground loop-to ground plate connections.

3. Crawl space ground loop-to outside counterpoise loop connections.

4. Sub-floor ground plate and inter-loop connections as per drawings

E201-E204.

4 PROCEDURES

Grounding Systems

Visual and Mechanical Inspection

Reference No.3149368 Page 2

Inspected ground system connections for completeness and proper termination in accordance with design drawings, if available.

Electrical Tests

Performed "fall-of-potential" method test on the main grounding electrode per IEEE Standard No. 81. If suitable locations for test rods were not available, a low resistance dead earth or reference ground was utilized.

Performed "two-point" method test per IEEE Standard No. 81, to determine the ground resistance between the main grounding system and all major electrical equipment frames, system neutral and/or derived neutral points.

5 RESULTS AND RECOMMENDATIONS

5.1 The equipment listed in Section 3 was found to be satisfactory, as indicated by the attached field data sheets.

Results from the forms:

907 Billy Mitchell BLVD

Port Authority Of San Antonio

EMERALD STANDARD SERVICES INCCustomer

Location/Plant

Table of Contents Job #3149368

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

REVISED 4/23/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

PAGE

Owner

PAGE

EQUIPMENT LOCATION

SUBSTATION DATA TEST FORM

POSITION

AIR TERMINALS FOR OUTSIDE AREA

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR

BUILDING 200

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

COUNTERPOISE TO OUTER LOOP CONNECTIONS

BUILDING 200

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

CRAWL SPACE UNDER BUILDING (CONT.)

BUILDING 200

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

CRAWL SPACE UNDER BUILDING

ROOM CR1

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

GROUNDS CONNECTIONS AND PLATES

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL 1

ROOM CR2A

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

GROUNDS CONNECTIONS AND LPLATES

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL 2

ROOM CR2B

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

GROUNDS AND PLATES

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST (2)

TEST WELL 2 (TEST 2)

ROOM CR3

907 BILLY MITCHELL BLVD

24210 - GROUND RESISTANCE TWO TERMINAL

GROUNDS CONNECTIONS AND PLATES

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL 3

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL 4

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL SG A

BUILDING 200

3326 GENERAL HUDNELL DR

24021 - FALL OF POTENTIAL GROUND TEST

TEST WELL SG B

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION AIR TERMINALS FOR OUTSIDE AREA OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR

7/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD33 °C 65

EQUIPMENT I.D.

DET 4TCCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E202 AND E203 MARK UP.

UNCORRECTED CORRECTED RESISTANCE RESULT

GENERATOR # 3 GROUND POINT #21

GENERATOR # 3 AIR TERMINAL #22

GENERATOR # 3 AIR TERMINAL #23

GENERATOR # 2 GROUND POINT #24

GENERATOR # 2 AIR TERMINAL #25

GENERATOR # 2 AIR TERMINAL #26

GENERATOR # 1 GROUND POINT #27

GENERATOR #1 AIR TERMINAL #28

GENERATOR #1 AIR TERMINAL #29

SWITCHGEAR WALK-IN ENCLOSURE #30

SWITCHGEAR WALK-IN ENCLOSURE AIR TERMINAL #31

SWITCHGEAR WALK-IN ENCLOSURE AIR TERMINAL #32

UTILITY BUS "B"

UTILITY BUS "A"

FUEL TANK VENT PIPING GROUND POINT #35

FUEL TANK VENT PIPING AIR TERMINAL #36

DX CHILLER AIR TERMINAL #37

DX CHILLER AIR TERMINAL #38

2.5

2.5

2.5

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

OUTSIDE BURIED GROUND LOOPFROM

COMMENTS: Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

REFER BACK TO DRAWINGS FOR IDENTIFICATION POINTS AND GROUND PLATE NUMBERS.

DEFICIENCIES:

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 COUNTERPOISE TO OUTER LOOP CONNECTIONS

7/18/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD33 °C 72

EQUIPMENT I.D.

AEMC 4620 Ground test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E203 AND E204 MARK UP.

UNCORRECTED CORRECTED RESISTANCE RESULT

COUNTERPOISE CONNECTPOINT-1

COUNTERPOISE CONNECTPOINT-2

COUNTERPOISE CONNECTPOINT-3

COUNTERPOISE CONNECTPOINT-4

COUNTERPOISE CONNECTPOINT-5

COUNTERPOISE CONNECTPOINT-6

COUNTERPOISE CONNECTPOINT-7

COUNTERPOISE CONNECTPOINT-8

COUNTERPOISE CONNECTPOINT-9

COUNTERPOISE CONNECTPOINT-10

COUNTERPOISE CONNECTPOINT-11

COUNTERPOISE CONNECTPOINT-12

COUNTERPOISE CONNECTPOINT-13

COUNTERPOISE CONNECTPOINT-14

COUNTERPOISE CONNECTPOINT-15

COUNTERPOISE CONNECTPOINT-16

COUNTERPOISE CONNECTPOINT-17

COUNTERPOISE CONNECTPOINT-18

COUNTERPOISE CONNECTPOINT-19

COUNTERPOISE CONNECTPOINT-20

COUNTERPOISE CONNECTPOINT-21

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

OUTER GROUND LOOPFROM

COMMENTS: Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NEW

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 CRAWL SPACE UNDER BUILDING (CONT.)

8/20/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E-201 AND E-202

UNCORRECTED CORRECTED RESISTANCE RESULT

POINT 54

GP-10

GP-11

GP-12

GP-13

POINT 66

GP-1

GP-13

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

COMMENTS: GP-13 TO POINT 66 TESTED THRU 3 CONNECTIONS. THE RESISTANCE OF EACH OF THE THREE CONNECTIONS COMBINE TO 80 MoHMS.

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 CRAWL SPACE UNDER BUILDING

8/20/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E-201 AND E-202

UNCORRECTED CORRECTED RESISTANCE RESULT

POINT 7

POINT 7

POINT 9

GP-2

POINT 11

POINT 12

GP-3

POINT 15

POINT 17

POINT 18

GP-4

POINT 20

POINT 24

POINT 25

GP-5

POINT 27

POINT 28

GP-6

POINT 33

POINT 34

GP-7

POINT 36

POINT 39

GP-8

POINT 46

GP-9

POINT 49

GP-1

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

COMMENTS: TESTED SATISFACTORY

REFERENCE POINT FROM 2.5 (DX CHILLER) TO GP-1 WAS 10 MILLI-OHMS

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION ROOM CR1 GROUNDS CONNECTIONS AND PLATES

8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E203 AND E204

UNCORRECTED CORRECTED RESISTANCE RESULT

GPCR1-5

GPCR1-1

POINT 7

GPCR1-2

POINT 8

GPCR1-3

POINT 9 (WIRE TO RM CR2B)

WIRE TO TOP GND LOOP

WIRE TO BOTTOM GND LOOP

GPCR1-4

WIRE TO TOP GND LOOP

WIRE TO BOTTOM GND LOOP

WIRE TO BOTTOM GND LOOP

POINT 18

GPCR1-7

POINT 17 (WIRE TO CRAWL SPACE)

GPCR1-6

POINT 13 (WIRE TO RM CR2B)

POINT 14 (WIRE TO RM CR2A)

GPCR1-6

GPCR1-5

GPCR1-1

GPCR1-1

GPCR1-1

GPCR1-2

GPCR1-3

GPCR1-3

GPCR1-3

GPCR1-3

GPCR1-4

GPCR1-4

GPCR1-8

GPCR1-8

GPCR1-8

GPCR1-7

GPCR1-7

GPCR1-4

GPCR1-4

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

COMMENTS: TESTED SATISFACTORY

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION ROOM CR2A GROUNDS CONNECTIONS AND LPLATES

8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E203 AND E204

UNCORRECTED CORRECTED RESISTANCE RESULT

POINT 1 (WIRE TO CRAWL SPACE)

POINT 14

GPCR2A-4

GPCR2A-5

GPCR2A-6

POINT 5 (WIRE TO CRAWL SPACE)

POINT 6 (WIRE TO RM CR3)

GPCR2A-3

WIRE TO BOTTOM GND LOOP

WIRE TO TOP GND LOOP

GPCR2A-2

GPCR2A-1

POINT 15 (WIRE TO RM CR3)

POINT 7 (WIRE TO RM CR1)

WIRE TO TOP GND LOOP

WIRE TO BOTTOM GND LOOP

GPCR2A-4

GPCR2A-5

GPCR2A-6

GPCR2A-6

GPCR2A-6

GPCR2A-3

GPCR2A-3

GPCR2A-3

GPCR2A-2

GPCR2A-4

GPCR2A-3

GPCR2A-6

GPCR2A-6

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION ROOM CR2B GROUNDS AND PLATES

8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E203 AND E204

UNCORRECTED CORRECTED RESISTANCE RESULT

GPCR2B-6

POINT 1 (WIRE TO RM CR2A)

GPCR2B-4

WIRE TO TOP GND LOOP

WIRE TO BOTTOM GND LOOP

GPCR2B-2

GPCR2B-1

POINT 8 (WIRE TO CRAWL SPACE)

POINT 9

GPCR2B-3

POINT 11 (WIRE TO CRAWL SPACE)

GPCR2B-5

GPCR2B-6

GPCR2B-4

GPCR2B-4

GPCR2B-4

GPCR2B-2

GPCR2B-1

GPCR2B-1

GPCR2B-1

GPCR2B-3

GPCR2B-3

GPCR2B-5

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

OWNER

ADDRESS

CUSTOMER

JOB #

GROUND RESISTANCE

TWO TERMINAL METHOD

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION ROOM CR3 GROUNDS CONNECTIONS AND PLATES

8/21/2012 TEMPERATURE HUMIDITY % 907 BILLY MITCHELL BLVD25 °C 40

EQUIPMENT I.D.

DET4TCR2 RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24210, REVISED 4/22/2009COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

DRAWING REFERENCE NUMBER E203 AND E204

UNCORRECTED CORRECTED RESISTANCE RESULT

WIRE TO BOTTOM GND LOOP

WIRE TO TOP GND LOOP

GPCR3-3

POINT 3 (WIRE TO CRAWL SPACE)

GPCR3-8

POINT 12 (WIRE TO CRAWL SPACE)

WIRE TO BOTTOM GND LOOP

WIRE TO TOP GND LOOP

GPCR3-9

GPCR3-4

POINT 3

POINT 6 (WIRE TO CRAWL SPACE)

POINT 9 (WIRE TO CRAWL SPACE)

POINT 9

GPCR3-5

POINT 19 (WIRE TO CRAWL SPACE)

GPCR3-1

GPCR3-6

GPCR3-7

POINT 14

GPCR3-3

GPCR3-3

GPCR3-8

GPCR3-8

GPCR3-8

GPCR3-8

GPCR3-9

GPCR3-4

GPCR3-10

GPCR3-2

GPCR3-2

GPCR3-1

GPCR3-6

GPCR3-6

TEST # TO

OHMSMILLI-OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

MILLI-OHMS OHMS

POINT TO POINTFROM

BARECONNECTING CONDUCTOR INSULATED

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL SG B

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.02

0.06

0.11

0.02

32 0.02

52 0.04

72 0.06

92 0.44

DISTANCE IN FEET

1/2 soil and sand

FALL OF POTENTIAL

OHMS0.06

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The ground electrode is located at the north side of the gear.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

No soil was available nearby. All ground surface was paved as a parking lot.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 1

7/23/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

3.08

3.22

3.31

3.19

60 3.09

240 3.19

260 3.26

280 3.34

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS3.15

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

Test well located at the east corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 300 FEET

61.8% OF TOTAL TEST DISTANCE = 185 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.

Satisfactory.

directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 2

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

17.5

17.7

18.95

17.57

32 17.56

52 17.65

72 18.7

92 19.3

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS17.70

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

DEFICIENCIES & RECOMMENDATIONS :

The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.

directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 2 (TEST 2)

8/21/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 65

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

5.35

5.54

5.64

5.44

32 5.4

52 5.5

72 5.56

92 5.76

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS5.54

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 3

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.16

0.3

0.55

0.23

32 0.16

52 0.26

72 0.36

92 2.3

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS0.30

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the west corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 4

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

8.59

8.91

9.45

8.74

32 8.69

52 8.9

72 9.4

92 9.54

DISTANCE IN FEET

1/2 soil and sand

FALL OF POTENTIAL

OHMS8.91

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the north corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL SG A

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.2

0.24

0.32

0.21

32 0.2

52 0.21

72 0.24

92 0.48

DISTANCE IN FEET

1/2 rock over top soil

FALL OF POTENTIAL

OHMS0.24

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The ground electrode for the switchgear is located adjacent to the gear on the north side of the gear.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

No soil was available nearby. All ground surface was paved as a parking lot.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set Deville, HeathEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 1

7/23/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

3.08

3.22

3.31

3.19

60 3.09

240 3.19

260 3.26

280 3.34

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS3.15

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

Test well located at the east corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 300 FEET

61.8% OF TOTAL TEST DISTANCE = 185 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.

Satisfactory.

directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 2

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

17.5

17.7

18.95

17.57

32 17.56

52 17.65

72 18.7

92 19.3

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS17.70

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.

directions to the boundary of the property. The ground electrode was driven into the elevated soil next to the building.

WETDAMPDRY

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set RCARRERA,TKECKEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 1, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 2 (TEST 2)

8/21/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 65

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

5.35

5.54

5.64

5.44

32 5.4

52 5.5

72 5.56

92 5.76

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS5.54

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the South corner of the facility. The soil adjacent to this point extended approximately 20-25 feet away from the building and then covered in concrete in all

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 3

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.16

0.3

0.55

0.23

32 0.16

52 0.26

72 0.36

92 2.3

DISTANCE IN FEET

1/2 sod

FALL OF POTENTIAL

OHMS0.30

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the west corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL 4

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

8.59

8.91

9.45

8.74

32 8.69

52 8.9

72 9.4

92 9.54

DISTANCE IN FEET

1/2 soil and sand

FALL OF POTENTIAL

OHMS8.91

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The test well is located at the north corner of the building.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL SG A

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.2

0.24

0.32

0.21

32 0.2

52 0.21

72 0.24

92 0.48

DISTANCE IN FEET

1/2 rock over top soil

FALL OF POTENTIAL

OHMS0.24

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The ground electrode for the switchgear is located adjacent to the gear on the north side of the gear.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

LENGTH OF GROUND RODS

NUMBER OF RODS

SOIL TYPE

DIAMETER OF GROUND ROD

TYPE OF GROUND ROD

four point fall of potential test set H DevilleEQPT. INVENTORY NO. TESTED BY:

24021, Page 1 of 2, REVISED 11/29/2011COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

EQPT. LOCATION

PAGE

OWNER

ADDRESS

CUSTOMER

JOB #

FALL OF POTENTIAL

GROUND TEST

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

NA

3149368

DATE LAST INSPECTION

EMERALD STANDARD SERVICES INC

529 PRESTON AVE; PASADENA TX 77503

PORT AUTHORITY OF SAN ANTONIO; 907 BILLY MITCHELL BLVD; SAN ANTONIO TX 78226

907 BILLY MITCHELL BLVDLOCATION/PLANT

DATE

SUBSTATION BUILDING 200 TEST WELL SG B

7/18/2012 TEMPERATURE HUMIDITY % 3326 GENERAL HUDNELL DR33 °C 72

EQUIPMENT I.D.

RESISTANCE IN OHMS

TWO-POINT

Copper

SOIL CONDITION:

TEST TYPE:

0.02

0.06

0.11

0.02

32 0.02

52 0.04

72 0.06

92 0.44

DISTANCE IN FEET

1/2 soil and sand

FALL OF POTENTIAL

OHMS0.06

FEET10

AWG2/0CONNECTING CONDUCTOR SIZE

The ground electrode is located at the north side of the gear.

DESCRIPTION OF GROUND SYSTEM UNDER TEST

INDUCED FREQUENCY

AUXILIARY POTENTIAL ELECTRODE

DISTANCE C1 - C2 = 100 FEET

61.8% OF TOTAL TEST DISTANCE = 62 FEET

GROUND RESISTANCE @ 61.8% OF DISTANCE

COMMENTS:

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.

Comment Summary Job #3149368

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

Owner

Customer EMERALD STANDARD SERVICES INC

Port Authority Of San Antonio

Location/Plant: 907 Billy Mitchell BLVD

Substation: AIR TERMINALS FOR OUTSIDE AREA Date: 7/21/2012

Equipment I.D.: OUTSIDE GENERATOR ,CHILLER UNITS AND SW.GEAR

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

REFER BACK TO DRAWINGS FOR IDENTIFICATION POINTS AND GROUND PLATE NUMBERS.

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: COUNTERPOISE TO OUTER LOOP CONNECTIONS

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 8/20/2012

Equipment I.D.: CRAWL SPACE UNDER BUILDING (CONT.)

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

GP-13 TO POINT 66 TESTED THRU 3 CONNECTIONS. THE RESISTANCE OF EACH OF THE THREE CONNECTIONS COMBINE TO 80 MoHMS.Comments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 8/20/2012

Equipment I.D.: CRAWL SPACE UNDER BUILDING

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

TESTED SATISFACTORYComments:

REFERENCE POINT FROM 2.5 (DX CHILLER) TO GP-1 WAS 10 MILLI-OHMS

Job #3149368

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

Location/Plant: 907 Billy Mitchell BLVD

Substation: ROOM CR1 Date: 8/21/2012

Equipment I.D.: GROUNDS CONNECTIONS AND PLATES

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

TESTED SATISFACTORYComments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/23/2012

Equipment I.D.: TEST WELL 1

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

Concrete surface surrounding the test well. There was bare soil adjacent and up to 60 feet away, then accross the parking lot, then accross a street.Comments:

Satisfactory.

Location/Plant: 907 Billy Mitchell BLVD

Substation: ROOM CR2A Date: 8/21/2012

Equipment I.D.: GROUNDS CONNECTIONS AND LPLATES

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

TESTED SATISFACTORYComments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: ROOM CR2B Date: 8/21/2012

Equipment I.D.: GROUNDS AND PLATES

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

TESTED SATISFACTORYComments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 8/21/2012

Equipment I.D.: TEST WELL 2 (TEST 2)

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST (2)

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Job #3149368

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

Location/Plant: 907 Billy Mitchell BLVD

Substation: ROOM CR3 Date: 8/21/2012

Equipment I.D.: GROUNDS CONNECTIONS AND PLATES

Equipment: 24210 - GROUND RESISTANCE TWO TERMINAL

TESTED SATISFACTORYComments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: TEST WELL 3

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: TEST WELL 4

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: TEST WELL SG A

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: TEST WELL SG B

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

Based on the inspections, maintenance, calibration, and test results performed, this equipment was found to meet applicable NETA standards.Comments:

Deficiency Summary Job #3149368

Electrical Reliability Services Inc.

Houston Area Service Center

1455 E. Sam Houston Pkwy S Suite 190

Pasadena, TX 77503 Phone 281-241-2800

REVISED 4/26/2010COPYRIGHT © 2002-2008 POWERDB, INC. www.powerdb.com

Owner

Customer EMERALD STANDARD SERVICES INC

Port Authority Of San Antonio

Location/Plant: 907 Billy Mitchell BLVD

Substation: BUILDING 200 Date: 7/18/2012

Equipment I.D.: TEST WELL 2

Equipment: 24021 - FALL OF POTENTIAL GROUND TEST

The results do not meet the specificed requirement. Suggest corrective action such as additional/ deeper ground rod installation and retest.Deficiencies:

3149368.pdf
PowerDb Combine.pdf
3149368 PDB.pdf
TEST WELL SG B.pdf
PowerDB (Emerson).pdf
TEST WELL 1.pdf
TEST WELL 2 TEST 2.pdf
TEST WELL 2.pdf
TEST WELL 3 .pdf
TEST WELL 4 .pdf
TEST WELL SG A .pdf
TEST WELL 1.pdf
TEST WELL 2.pdf
TEST WELL 2 TEST 2.pdf
TEST WELL 3 .pdf
TEST WELL 4 .pdf
TEST WELL SG A .pdf
TEST WELL SG B.pdf

File details come from the government source that posted it. Updated .