National Consolidated Risk Management Survey
FIRE PROTECTION
RAC Summary
Survey Area RAC Score Means of Egress Fire Detection and Alarm Fire Suppresion Smoke Control Other
Fire Protection Survey Overall RAC Score:
Building Information
Questions Response Findings/Observations
Building Profile Region GSA Building Number GSA Building Name Building Street Address Building City Building State Date(s) of Onsite Survey Surveyor Type of Occupancies Building Point(s) of Contact for Surveys Date of Building Construction Date of Last Major Building Renovation Has any work been done since the last survey (e.g., any tenant fit-outs, changes in occupancy, etc.)? If yes, please describe in the findings section.
Property Type What is the tenant breakdown?
Primary Tenants
Is there a law enforcement tenant in this facility?
Name of O&M or Facilities Management Services Contractor Name of Custodial Services Contractor
Building Information
Questions Response Findings/Observations Identify any Unique Space Type(s). If "other" is chosen, please describe the "other" unique space in the comments section.
Building Size (GSF) Building Size (RSF) Total Number of Floors Above Grade Total Number of Floors Below Grade Is the building a highrise according to Rexus?
Is the building a highrise according to FPE?
What is the building construction classification (IBC Code)?
What is the pitch of roof?
Are there photovoltaic (PV) cells on the roof?
Type of Roof Anchoring System Are there antennas?
How many elevators are there?
Identify Fuel Fired Equipment What are the fuel types?
How many confined spaces are there?
What type of confined spaces are there?
How many permit-required confined spaces are there?
What is the potable water source?
Is there asbestos containing material(s)?
Is there lead paint or other lead material(s)?
Is there PCB containing material(s)?
Building Information
Questions Response Findings/Observations What energy sources are used onsite? (select all that apply) Above-Ground Storage Tanks (ASTs) Are there any ASTs?
If yes, how many are there?
What is their total value?
Tank Size (gallons) Type Tank Location Fuel Type Installation Date Underground Storage Tanks (USTs) Are there any USTs?
If yes, how many are there?
What is their total value?
Tank Size (gallons) Type Tank Location Fuel Type Installation Date Occupant Emergency Plan (OEP) Is there an OEP?
Date of plan Are persons in plan current?
Is there OEP training for designated persons?
Building Information
Questions Response Findings/Observations Are there procedures for evacuation of disabled persons?
Are there procedures for after-hours emergencies?Is there a fire department pre-fire plan?
Means of Egress
# Questions Response Findings/Observations
Means of Egress Components
Are doors in compliance? If no, identify and describe the circumstances in the findings section.
Are stairs in compliance? If no, identify and describe the circumstances in the findings section.
Are handrail/guards in compliance? If no, identify and describe the circumstances in the findings section.
Are ramps in compliance? If no, identify and describe the circumstances in the findings section.
Are horizontal exits in compliance? If no, identify and describe the circumstances in the findings section.
Are exit passageways in compliance? If no, identify and describe the circumstances in the findings section.
Other means of egress elements noted? If no, identify and describe the circumstances in the findings section.
Capacity of Means of Egress
Is the means of egress capacity based on occupant load for floor and area adequate?
Is egrees capacity adequate at convergence points?
Means of Egress Minimum Width
Is the means of egress minimum width maintained (i.e. 44" or 36" where permitted)?
Number of Exits
Are the required number of exits provided for floor or area?
Are there interlocking or scissor stairs present (if yes, counts as 1 exit)?
Arrangement of Means of Egress
Are exits readily accessible? If no, identify and describe the circumstances in the findings section.
Are common path of travel and dead end arrangements in compliance? If no, identify and describe the circumstances in the findings section.
Are exits arranged to be remote per code?
If no, identify and describe the circumstances in the findings section.
Are travel distances in compliance? If no, identify and describe the circumstances in the findings section.
Discharge of Means of Egress
Is the exit discharge in compliance? If no, identify and describe the circumstances in the findings section.
Regulatory Citation Risk Assessment Code (RAC) Recommended Corrective Actions
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
National Consolidated Risk Management Survey
FIRE PROTECTION
Means of Egress
Means of Egress Components
Capacity of Means of Egress
Means of Egress Minimum Width
Number of Exits
Arrangement of Means of Egress
Discharge of Means of Egress
Means of Egress
# Questions Response Findings/Observations
Illumination of Means of Egress
If emergency lighting is provided, is there adequate coverage? If no, identify and describe the circumstances in the findings section.
Is there a current emergency lighting testing and maintenance report? If yes, please identify the date and any findings in the findings section.
Marking Means of Egress
Are adequate markings of means of egress provided? If no, identify and describe the circumstances in the findings section.
Is the illumination of the markings of means of egress in compliance? If no, identify and describe the circumstances in the findings section.
Elevators
22 How many elevators are in the building?
What is the installation date(s) of the elevator(s)?
Do elevators have firemans recall phase I or II?
Are any of the elevators used as a required means of egress?
Other Findings
Overall Means of Egress RAC
Once the surveyor has reviewed the Means of Egress findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
User Adjusted Means of Egress RAC
Explanation of User Adjusted RAC
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
Illumination of Means of Egress
Marking Means of Egress
Elevators
Other Findings
Once the surveyor has reviewed the Means of Egress findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Fire Detection and Alarm
# Questions Response Findings/Observations
Fire Detection and Alarm
Is there a fire alarm system installed? If no, please explain in the findings section.
If there is a fire alarm system installed, is the system operational and functioning correctly?
29 What is the fire alarm system type?
Is there a current (NFPA 72) test and maintenance report? If yes, please identify the date and any findings in the findings section.
Is there off-site notification? If yes, please describe notification in the findings section.
Fire Alarm Control Panel 32 What is the age of the control panel?
33 Where is the fire alarm control panel located?
34 Identify the fire alarm manufacturer (type/model).
Is there a fire command station or emergency control center? If yes, please identify in the findings section.
Initiating Devices
Are there manual pull station issues? If yes, please describe in the findings section.
Are there smoke detectors issues? If yes, please describe in the findings section.
Are there duct detectors issues? If yes, please describe in the findings section.
Are there heat detectors issues? If yes, please describe in the findings section.
Are there water flow switches issues? If yes, please describe in the findings section.
Are there valve supervision issues? If yes, please describe in the findings section.
Are there any other initiating devices with issues? If yes, please describe in the findings section.
Notification Devices
Are there any visual device problems? If yes, please describe problems and date of test and maintenance report in the findings section.
Are there any audibility problems? If yes, please describe in the findings section.
Other Findings
Overall Fire Detection and Alarm RAC
Once the surveyor has reviewed the Fire Detection and Alarm findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
User Adjusted Fire Detection and Alarm RAC
Regulatory Citation
Risk Assessment Code (RAC) Recommended Corrective Actions
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
National Consolidated Risk Management Survey
FIRE PROTECTION
Fire Detection and Alarm
Fire Detection and Alarm
Fire Alarm Control Panel
Initiating Devices
Notification Devices
Once the surveyor has reviewed the Fire Detection and Alarm findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Fire Detection and Alarm
# Questions Response Findings/Observations
Fire Suppression
# Questions Response Findings/Observations
Automatic Sprinklers
Is there a fire sprinkler system installed? If no, please explain in the findings section. If yes, please complete the questions below.
47 What is type of fire sprinkler system?
48 What is the age of the oldest sprinkler?
What percentage of the facility has a fire protection system?
Is there a current (NFPA 25) maintenance report?
If yes, please identify the date and any findings in the findings section.
Are there any identified fire sprinkler issues? If yes, please explain in the findings section.
Standpipes 52 What are the types of standpipes?
Is there current (NFPA 25) maintenance record?
If yes, please identify the date and any findings in the findings section.
Are there any standpipe issues? If yes, please explain in the findings section.
Fire Pumps
Are there any fire pump(s)? If yes, please complete the questions below.
56 What is the location of the fire pump(s)?
What is the size of the fire pump, ___gpm at ___psi?
Is there a current (NFPA 25) maintenance record? If yes, please identify the date and any findings in the findings section.
Are there any fire pump issues? If yes, please explain in the findings section.
What is the power source? If diesel, identify any fuel storage issues in the findings section.
Fire Extinguishers
Are there fire extinguishers? If yes, please complete the questions below.
Have the fire extinguishers been maintained per NFPA 10? If no, identify issues in the findings section.
Are the fire extinguishers properly located and sized in compliance with NFPA 10? If no, please explain in the findings section.
Other Suppression Systems
Are there other suppression systems? If yes, please describe location and type in the findings section.
Are there current maintenance records? What is the date of the last test?
Are there identified issues? If yes, please explain in the findings section.
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
National Consolidated Risk Management Survey
FIRE PROTECTION
Fire Suppression
Automatic Sprinklers
Standpipes
Fire Pumps
Fire Extinguishers
Other Suppression Systems
Fire Suppression
# Questions Response Findings/Observations
Overall Fire Suppression RAC
Once the surveyor has reviewed the Fire Suppression findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
User Adjusted Fire Suppression RAC
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
Once the surveyor has reviewed the Fire Suppression findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Smoke Control
# Questions Response Findings/Observations
Smoke Control 68 Is there a smoke control system present?
What is the application of the smoke control system? Please provide the location in the findings section.
Is there a current maintenance record? If yes, please identify the date and any findings in the findings section.
Are there any smoke control issues? If yes, please explain in the findings section.
Other Findings
Overall Smoke Control RAC
Once the surveyor has reviewed the Smoke Control findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
User Adjusted Smoke Control RAC
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
National Consolidated Risk Management Survey
FIRE PROTECTION
Smoke Control
Smoke Control
Once the surveyor has reviewed the Smoke Control findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Smoke Control
Other
# Questions Response Findings/Observations
Fire and Smoke Barriers
Are vertical applications (i.e. stairwell, HVAC shafts) properly maintained? If no, please describe in the comments section.
Are horizontal applications (i.e. floors, corridors, special hazard areas) properly maintained? If no, please describe in the comments section.
Are special use areas (i.e. laboratories, firing range) properly maintained? If no, please describe in the comments section.
Are penetrations properly maintained? If no, please describe in the comments section.
Are opening protective's properly maintained? If no, please describe in the comments section.
Are all other fire barriers properly maintained? If no, please describe in the comments section.
Are there fire dampers, smoke dampers, or combination dampers? If yes, provide where they are located in the findings section.
Is there a current maintenance record (NFPA 80)? If yes, please identify the date and any findings in the findings section.
On-Site Power Generation
Is there on-site power generation? If yes, please select the appropriate type from the drop down menu.
82 Identify on-site power generation location.
83 Are firefighter provisions in place?
On-Site Fuel Storage
Is there on-site fuel storage? If yes, please select the appropriate type from the drop down menu and provide the location and size in the findings section.
85 What is the intended use of on-site fuel?
Are there any maintenance records and associated identified issues or concerns? If yes, please explain in the findings section.
Emergency Power 87 Are there emergency generator(s)?
Is there a current maintenance record (NFPA 110)? If yes, please identify the date and any findings in the findings section.
Are there any identified issues? If yes, please explain in the findings section.
Kitchen Use
Is there commercial cooking equipment present?
If yes, identify equipment and related fire protection features (i.e. ventilation hoods) in the findings section.
Are there any current (NFPA 96) maintenance records? If yes, please identify the date and any findings in the findings section.
Are there any identified kitchen issues? If yes, please explain in the findings section.
Interior Finishes
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
National Consolidated Risk Management Survey
FIRE PROTECTION
Other
Fire and Smoke Barriers
On-Site Power Generation
On-Site Fuel Storage
Emergency Power
Kitchen Use
Interior Finishes
Other
# Questions Response Findings/Observations
Are interior finishes compliant with the occupancy use? If no, please describe in the findings section.
Fire Planning and Prevention
Is the fire rating being maintained? If no, then note areas not maintained in the findings section.
95 Is there a fire command room?
Are there any other overall fire prevention issues?
If yes, please describe in the findings section.
Other Findings
Overall Other RAC
Once the surveyor has reviewed the Other findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
User Adjusted Other RAC
Probability Severity RAC Is there a recommended corrective action associated with this item? Location Recommended Action
Fire Planning and Prevention
Once the surveyor has reviewed the Other findings and Overall RAC provided above, if the RAC does not represent the risk associated with the findings as a whole, please provide an adjusted RAC and explanation below.
Other
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location
M ea ns o f E gr es s
Means of Egress
Capacity of Means of Egress
Means of Egress Minimum Width
Number of Exits
Arrangement of Means of Egress
Discharge of Means of Egress
Illumination of Means of Egress
Marking Means of Egress
Elevators
Other Findings - Means of Egress
Action Taken Completion Date
FIRE PROTECTION
Work Item Summary and Tracking Sheet
Means of Egress
Capacity of Means of Egress
Means of Egress Minimum Width
Number of Exits
Arrangement of Means of Egress
Discharge of Means of Egress
Illumination of Means of Egress
Marking Means of Egress
Elevators
Other Findings - Means of Egress
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location
M ea ns o f E gr es s
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location
Fi re
D et ec tio n an d A la rm
Fire Detection and Alarm
Fire Alarm Control Panel
Initiating Devices
Notification Devices
Other Findings - Fire Detection and Alarm
Fi re
S up pr es si on
Automatic Sprinklers
Standpipes
Fire Pumps
Fire Detection and Alarm
Fire Alarm Control Panel
Initiating Devices
Notification Devices
Other Findings - Fire Detection and Alarm
Automatic Sprinklers
Standpipes
Fire Pumps
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location 60Fi re S up pr es si on
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location Fire Extinguishers
Other Suppression Systems
Other Findings - Fire Suppression
Sm ok e C on tr ol
Smoke Control
Other Findings - Smoke Control
O th er
Fire and Smoke Barriers
On-Site Power Generation
On-Site Fuel Storage
Fi re
S up pr es si on
Fire Extinguishers
Other Suppression Systems
Other Findings - Fire Suppression
Smoke Control
Other Findings - Smoke Control
Fire and Smoke Barriers
On-Site Power Generation
On-Site Fuel Storage
Work Item Summary and Tracking Sheet
# Findings/Observations Recommended Action Location Emergency Power
Kitchen Use
Interior Finishes
Fire Planning and Prevention
Other Findings - Other
O th er
Emergency Power
Kitchen Use
Interior Finishes
Fire Planning and Prevention
Other Findings - Other
Severity and Probability Assessment Guidance
SEVERITY ASSESSMENT GUIDANCE
SCOPE and APPLICABILITY
Environmental Risk Fire Protection Risk Safety & Health Risk
Contamination of air, water soil, and biota or non-compliance with environmental regulations
Effects to occupants or facility as a result of a condition or potential event.
Adverse health effects or injury to facility occupants, contractors or visitors in response to a condition or event
SEVERITY LEVEL DEFINITIONS
CATASTROPHIC Irreversible long-term impacts.
(1) Death, permanent disability or irreversible health effect to occupants or (2) a loss of an entire facility.
Permanent disability, irreversible health effect or death.
SEVERE
Reversible long-term damage (5+ years to remediate).
(1) Severe injury, potential long-term health effect or
(2) major loss or impact to a facility.
Potential long-term health effect or severe injury.
SIGNIFICANT
Reversible medium-term damage (1-5 years to remediate).
(1) Minor injury or reversible health effect or
(2) damage to a portion of a facility requiring an extended period of time to repair.
Reversible health effect or minor injury.
MODERATE
Reversible short-term impact (<1 year to remediate).
(1) First aid, no lost time or
(2) damage to a facility requiring a minimal amount of time to repair.
First aid or no lost time.
MINOR De minimis regulatory violation. De minimis code violation. De minimis code violation.
NO IMPACT No risk of impact. No risk of impact to the occupants or facility. No risk of impact.
MODERATE
Reversible short-term impact (<1 year to remediate).
(1) First aid, no lost time or
(2) damage to a facility requiring a minimal amount of time to repair.
First aid or no lost time.
PROBABILITY ASSESSMENT GUIDANCE
PROBABILITY LEVEL DEFINITIONS
Likely Imminent or 1 in 10
Probable Probable or 1 in 100
Possible Possible or 1 in 1000
Remote Remote or 1 in 10,000
Unlikely Unlikely or 1 in 100,000
Not Possible Non-existent