Amendment_4_to_GS11P16MKC7003.pdf

PDF 421 KB Posted

Attached to
General Construction for Perimeter Security Improvements Project Federal contract opportunity
Solicitation number
GS11P16MKC7003
Issued by
General Services Administration Public Buildings Service National Capital Region

View the file

Other files for this federal contract opportunity

Other files attached to General Construction for Perimeter Security Improvements Project, newest first.
File Type Posted
Amendment_5_to_GS11P16MKC7003.pdf PDF
Site_Visit__2_Sign_In_Sheet.pdf PDF
Amendment_3_to_GS11P16MKC7003.pdf PDF
Revised_Spec_Section_321413_(Unit_Paving)_dated_3_June_2016.pdf PDF
Revised_DWG_DETAILS_L503_dated_3_June_2016.pdf PDF
GC_Past_Performance_Reference_Form.pdf PDF
Amendment_1_to_GS11P16MKC7003.pdf PDF
Revised_Spec_Section_334100_(Storm_Piping)_dated_3_June_2016.pdf PDF
The_Solicitation_dated_9June16_Revised.pdf PDF
Attachment_A_-_SITE_VISIT_Info_Sheet_Revised.pdf PDF
Revised_Pricing_Sheet_dated_9_June_2016.pdf PDF
Attachment 8_USMSContractor Security clearance request.pdf PDF
Attachment_11_EnvironmentalAssessment_Jan_2012.pdf PDF
GSA527-15.pdf PDF
Attachment 7_Davis Bacon Wage Rate VA160083.pdf PDF
Attachment 12B_Traffic Impact Study.pdf PDF
Attachment_1_Statement_of_Work.pdf PDF
Attachment 9_Geotechnical Engineering Report 3 March 2015.pdf PDF
Attachment_3__Final_Drawing_Mylar_Submission.pdf PDF
Attachment_12B_Traffic_Impact_Study.pdf PDF
Pricing_Sheet.pdf PDF
Attachment_6B_C D-Waste-Monthly-Report.PerimeterSecurity_(1).xlsx XLSX spreadsheet
Attachment 6B_C D-Waste-Monthly-Report.PerimeterSecurity —
Attachment_5_Safety__and_Health_Specification_Section_01546.pdf PDF
The_Agreement_Small_Business_Set-Aside_GC_FINAL.pdf PDF
Attachment 6A_C D-Waste-Monthly-Report.PerimeterSecurity —
Attachment 2_Project Specifications Manual 6 March 2015.pdf PDF
Attachment_2_Project_Specifications_Manual_6_March_2015.pdf PDF
Attachment 1_Statement of Work.pdf PDF
Attachment_4_ConstructionWasteMgmt_and_Disposal_Spec.pdf PDF
Attachment_12A_Traffic_Impact_Study_Jan_2012.pdf PDF
Attachment_9_Geotechnical_Engineering_Report_3_March_2015.pdf PDF
Attachment 5_Safety and Health Specification Section 01546.pdf PDF
The_Solicitation_Small_Business_Set_Aside_GC_LPTA__FINAL.pdf PDF
Attachment 11_EnvironmentalAssessment Jan 2012.pdf PDF
Attachment_8_USMSContractor_Security_clearance_request.pdf PDF
Attachment 3_ Final Drawing Mylar Submission.pdf PDF
Attachment 12A_Traffic Impact Study Jan 2012.pdf PDF
Attachment 11_EnvironmentalAssessment Jan 2012.pdf PDF
Attachment 8_USMSContractor Security clearance request.pdf PDF
Attachment 3_ Final Drawing Mylar Submission.pdf PDF
Attachment 5_Safety and Health Specification Section 01546.pdf PDF
Attachment 1_Statement of Work.pdf PDF
Attachment 10_ALTA-ACSM Final Survey 06-24-15 —
Attachment 6B_C D-Waste-Monthly-Report.PerimeterSecurity —
Attachment 7_Davis Bacon Wage Rate VA160083.pdf PDF
SF1442_Form_(GS-11-P-16-MK-C-7003).pdf PDF
C301_GC_Reps_ _Certs.pdf PDF
Attachment 9_Geotechnical Engineering Report 3 March 2015.pdf PDF
Attachment 2_Project Specifications Manual 6 March 2015.pdf PDF
Show all 50

General Construction for Perimeter Security Improvements Project has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

GS11P16MKC7003

PAGE OF

PAGES

2. AMENDMENT/MODIFICATION NO.

Amendment 04

3. EFFECTIVE DATE

6/27/2016

REQUISITION/PURCHASE REQ. NO.

PROJECT NO. (If applicable)

6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE

GSA, NCR, PBS,

Office of Acquisition, Capital Construction 301 7th Street, SW Room 6651 Washington, DC 20407

GSA, NCR, PBS,

Office of Acquisition, Capital Construction 301 7th Street, SW Room 6651 Washington, DC 20407

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

9.A. AMENDMENT OF SOLICITATION NO.

(X)

GS11P16MKC7003

To All Prospective Offerors

9B. DATED (SEE ITEM 11)

6/3/2016

TOTAL SMALL BUSINESS SET-ASIDE 10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing Items 8 and 15, and returning. copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegraph which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS

IT MODIFIES THE CONTRACT/ORDER NO. DESCRIBED IN ITEM 14.

(x) A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

c. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not is required to sign this document and return ________ copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible).

The solicitation is hereby amended as follows:

The following changes, clarifications, additions and supplements are hereby incorporated into this

SOLICITATION in their entirety as submitted. Continued on Page 2 of this Amendment Except as provided herein, all terms and conditions of the document reference in item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

Jane Facchina, Contracting Officer

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA

BY Jane Facchina .

(Signature of Contracting Officer)

16C. DATE SIGNED

6/27/2016

NSN 7540-01-152-8070

PREVIOUS EDITION UNUSABLE

30-105 STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA

FAR (48 CFR) 53.243

CONTINUATION OF SF 30: AMENDMENT OF

SOLICITATION/MODIFICATION OF CONTRACT

GS11P16MKC7003

Amendment No. 4

GS11P16MKC7003, General Construction Services for Perimeter Security Improvements at the

Bryan Courthouse, Alexandria, VA

ITEM A: INSERT the attached “Responses to RFI Questions” dated 27 June 2016.

ITEM B: Offerors must acknowledge receipt of this amendment on offer form, giving number and date.

END OF AMENDMENT NO. FOUR (4)

A.V. Bryan Courthouse Perimeter Security Improvement Project

RFP AMENDMENT 004 dated 27 June 2016

ATTACHMENT #1

Pre-Award (RFI) Questions and Answers (Questions 9 through 33)

9. QUESTION:

Per the RFP the project is listed as set-aside for small business. If the equipment manufacturer is a large business due to the manufacturing requirements. Will it be acceptable that the manufacturer is large business as long as the equipment is furnished and installed by the small business contractor.

RESPONSE:

Yes. It is acceptable to purchase from a large manufacturer as long as the equipment is furnished and installed by the small business contractor.

10. QUESTION:

Will it be acceptable for the contractor to relocate and modify the temporary concrete barriers during construction as temporary force protection?

The existing concrete barriers can be relocated during construction however the concrete barriers (or another equal temporary barrier type) must be in place once the GC’s crews have completed work for each day.

11. QUESTION: Is there a concrete slab under the existing brick pavers.

RESPONSE: It is believed that the brick paved areas most recently re-paved (approx.

2002) are set on a thin mortar base with sand between each paver.

12. QUESTION: Please verify the operable bollards will be controlled from the guard’s booth and the control room.

Yes, “master” control is from control room inside the building, with “slave” control at the guard booths.

13. QUESTION: It is our understanding that the new vehicular barrier's are provided under a separate contract. When the units are manufactured can the relay's for the connection under our contract be installed.

The GSA is managing two (2) separate projects that will enhance vehicle security. One project primarily focuses on the replacement of the existing delta wedge barriers directly in front of each garage entrance. The other project focuses on the collective perimeter security for the Courthouse and creates the first layer of vehicular defense on Jamieson via the installation of active bollards. The successful GC for this solicitation (perimeter security improvement project) shall be responsible for all needed relays and controls related to the perimeter security improvement project.

14. QUESTION: Section 347513 2.2 M calls for a UPS sized to allow for 100 cycles. This would be a large UPS for this style of system. Please request whether or not a smaller UPS will be allowable.

Proceed with providing pricing for the UPS as required within the project specifications however please provide an alternate price for the installation of a smaller UPS that will accommodate the system being presented.

15. QUESTION: Will the due date be extended due to the additional information required.

The due date will not be extended.

16. QUESTION: Reference Drawing L 501 states bollard foundation shall be designed to meet the threat level of the project, can the government clarify whether an engineered crash rating is acceptable or ifRef certified crash test is required?

Engineered crash rating is not acceptable. GC must provide crash test data for any pre-tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test

Method. For the custom cable fence systems the GC shall provide LS Dyna virtual crash test (FEA model) analysis, signed and sealed by PE.

17. QUESTION: Reference Drawing L 502 – (3) Decorative Bollard Sheath / Can the government provide tolerances and dimension for orthogonal design?

Drawings show aesthetic intent, provide shop drawings based on plans for acceptance by the government.

18. QUESTION: Reference Drawing L 502 – (3) Decorative Bollard Sheath / Denotes a 1” x 2” Steel attachment tab for fence panel, if the attachment tab is to be reinforced to bollard core the decorative sheath cannot be a continuous form or sleeve as it will not slide over the bollard core. Can the government clarify the design intent.

Decorative panels can be attached to decorative sheath if attachment can provide a secure connection for the fence panel. Panels at cable stay system will need to be coordinated with delegated design of cable stay system.

19. QUESTION: Reference Drawing L 502 – (3) & (1) Decorative Bollard Sheath / Can the government clarify and define “eased edges at top”

Eased edges signifies rounding edges, change note to say “provide a ¼” round edge at top.”

20. QUESTION: Reference Drawing L 502 – (2) Section B-B / Shows the cable stay portion above the height of the bollard core. Can the government confirm that the bollard core height should be adjusted throughout site based upon location?

Yes, adjust as necessary for delegated design of cable-stay system.

21. QUESTION: Reference Drawing L 503 – (1) Fence Panel Cable System / Drawing shows a traditional terminal post cable system however represents the application in on drawing 502 in a round bollard configuration. Can the government clarify the design intent?

Drawings show aesthetic intent/requirement for sheaths and infill panels. Delegated design cable-stay structure and supports to be within decorative sheath and panel system.

22. QUESTION: Reference Drawing L 503 - (1) Fence Panel Cable System / Drawing denotes a cable configuration where the bottom weld and cable system due to the interior location on a round bollard would add substantial fabrication costs. Can the government confirm the design as shown is required or can contractors propose different core and cable design that fits within the current exterior sheath design?

Drawings show aesthetic intent/requirement. Contractors can propose different core and cable design as long as it fits within the aesthetic intent. Cable-stay structure and supports is delegated design.

23. QUESTION: Can the government provide further dimensions, close up detail and tolerances for fence panel design? Since the government has requested LPTA we would strongly encourage further design details to ensure proper interpretation of fabrication requirements.

Drawings & specifications show aesthetic intent. Provide as shown on drawings. See

2/L0502 for design intent.

24. QUESTION: Reference Drawing S 101 – Note 1 / Details requirements for signed and sealed drawings by Professional Engineer, are PE Stamped drawings required for all crash rated foundations through entire site or will a single stamped drawing for each foundation type be acceptable (stand alone bollard, cable stay bollard and hydraulic bollard)?

At a minimum, provide signed and sealed delegated design drawings for each foundation type showing “worst” case scenario. If foundation type has multiple shapes, provide separate drawing for each shape.

25. QUESTION: Reference Drawing S 101 – Note 1 / If foundations are to be engineered then crash test data would not be applicable. Can the government clarify?

tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test

26. QUESTION: Reference Drawing S 001 – Note IV B / If foundations are to be engineered there will be no crash test data available the meets DOS crash testing requirements, can the government clarify?

tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test

27. QUESTION: SECTION 34 71 13 VEHICLE BARRIERS – 1.6 Performance / Requires crash test certification, however directly above states custom design for cable stay system. There will be no certified crash test in accordance with DOS on a custom engineered system. Can the government either remove the performance criteria or provide clarification on the conflicting statements?

tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test

28. QUESTION: SECTION 34 71 13 VEHICLE BARRIERS – 2.1 A 3 / Stated diameter core is 8” however drawings denote 10” can the government clarify?

8” is a minimum and 10” is representational, as noted in detail 4/L501. Either are acceptable if they provide required rating.

29. QUESTION: SECTION 34 71 13 VEHICLE BARRIERS – 2.2 A 1 / Can the government change impact “certified” to impact “engineered” as the system will not be crash test certified unless the government would like the contractor to include the cost of crash testing the custom system to receive applicable certification?

tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test test (FEA model) analysis, signed and sealed by PE..

30. QUESTION: SECTION 34 71 13 VEHICLE BARRIERS – High Security Vehicle Barricade / Active bollards are typically crash test in groups of three, can the government confirm that per drawings a set of two bollards will be acceptable even though it does not meet the manufacturer’s crash test data requirements?

Since there are fixed bollards on each side of the groups of two, if the fixed bollard meets

K-4 and the retractable bollards meet k-4, it is acceptable to assume a cluster of bollards with two retractable and one fixed each with K-4 rating is equivalent to that of 3 retractable group if they have the same distances in between them as the crashed test conducted for 3 retractable ones.

31. QUESTION: Please confirm that a LS Dyna virtual crash test (FEA model) will be required for all cable fence and bollard scenarios depicted on the drawings. There are several locations with slightly different spacing requirements and foundation restrictions. Please confirm that an analysis would be required for each location.

tested systems. GC must also provide manufactures certification that the barrier design has been tested by an approved, independent testing agency. For a K4 rating, the test vehicle at the moment of impact will stop and disable a 15,000-lb (6,818-kg) truck, moving at 30mph (48 kph). Pre-tested systems shall follow the ASTM F2656, Standard Test

Provide documentation showing compliance for each type of system and foundation combination. Where spacing requirements vary, showing approved range is acceptable.

32. QUESTION: Being that the site is active, does the perimeter security need to be maintained at the end of each day (ie: will the jersey barriers or completed bollard/fence system need to be in place at the end of each day)?

The existing concrete barriers can be relocated during construction however the concrete barriers (or another equal temporary barrier type) must be in place once the GC’s crews have completed work for each day.

33. QUESTION: For the conduit for the controls of the bollards, will it need to be concealed (ie: below ground) for all locations outside the building?

Yes, all conduit will need to be concealed for all locations outside the building.