Sheet1
| DEPARTMENT OF THE AIR FORCE |
| 75 CIVIL ENGINEERING (CEOHA) |
| HILL AIR FORCE BASE, UTAH |
| LIMITED ASBESTOS INSPECTION REPORT, | HILL AFB BUILDING, 850 BAY G |
| REMODEL BAY FOR NEW WORKLOAD |
| Date Requested: | January 2016 | Inspection Date: | 24 February 2016 |
| Requester: | Cary Haws | Inspector: | Chase Johnson (Utah Certified Asbestos Inspector ASB#-5645) |
| Organization: | 309 MMXG | ||
| Location & Building: | HILL AFB BUILDING, 850 BAY G | ||
| Work Order: | 57154 |
| Affected Area: | South Section Bay G |
| Statement of Work: | Remodel South section of bay G to include 3,000 square feet of 100k cleanroom and 4,000 square feet of 300k cleanroom. |
| Design any necessary mechanical rooms, production space. |
This inspection was performed in accordance with the Utah Division of Air Quality (DAQ) requirements as found in the Utah Air Quality Rule R307-801-10. This inspection report is required to be on site during all abatement, renovation, and demolition activities. Samples referenced in this report were analyzed by polarized light microscopy (PLM) utilizing method 600R-93-116 by The Science and Engineering laboratory at Hill Air Force Base, Utah.
Civil Engineering personnel also reviewed previous asbestos inspection reports of suspect asbestos containing building materials (ACM) that could potentially be encountered in this area. The information gathered from all current and previous inspections is shown below by homogenous area.
SUMMARY OF ASBESTOS CONTAINING MATERIALS FOUND
| MATERIAL TYPE | ASBESTOS | FRIABILITY (During Removal)* | *RACM *Category I *Category II | QUANTITY | *LOCATIONS FOUND |
| Thermal System Hard Pipe Insulation | Assume | Friable | RACM | 200 Linear Feet | South Section Bay G |
| Thermal System Hard Pipe Fitting Insulation | Assume | Friable | RACM | 20 Linear Feet | South Section Bay G |
| *Per UDAQ definition. |
| RACM: Regulated Asbestos-Containing Material (RACM)" means friable ACM, Category I non-friable ACM that has become friable, Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation project operations. |
| Category I Non-Friable ACM: Asbestos-containing packings, gaskets, resilient floor coverings, or asphalt roofing products containing more than 1% asbestos as determined by using the method specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM). |
| Category II Non-Friable ACM: Any material, excluding Category I non- friable ACM, containing more than 1% asbestos as determined by using the methods specified in 40 CFR Part 763, Subpart E, Appendix E, Section 1, Polarized Light Microscopy (PLM) that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. |
| Locations found: Locations of building materials as described in this report indicate where they were found, but do not necessarily mean that these are the only locations where these materials may be encountered during the project. |
| Summary of materials containing ≤1% was identified via "Point Counting". ≤1% is not considered to be an asbestos containing material, but special handling/packaging requirements are necessary per OSHA 29CFR 1926.1101 and 29CFR 1910.1001 |
| MATERIAL TYPE | ASBESTOS | QUANTITY | *LOCATIONS FOUND |
| N/A | N/A | N/A | N/A |
The following is a list of the "Suspect Materials" that were sampled as part of this inspection:
Drywall/Joint Compound Wall System
| A total of | 3 | samples reference the | 1 | suspect materials assesses as part of the inspection. |
| The following table summarizes the sampling data. |
| Homogenous Building Material, Description, Location, Quantity. | Sample # | Sample Location | Results |
| Drywall/Joint Compound Wall System, Bay G, 200 Square Feet | GM160807 | East, Bay G | None Detected |
| GM160808 | Southeast, Bay G | None Detected | |
| GM160809 | Southwest, Outside Restrooms | None Detected |
Per EPA requirements, all materials analyzed as containing ≤10% asbestos are point counted utilizing EPA method 600/R-93/116.
| POTENTIAL FOR ADDITIONAL MATERIALS: |
| This inspection report only encompasses the areas/materials designated within this report. Should the scope of the project be altered in any way or any materials found that are not identified in this report shall require additional assessment. This report cannot be used for any other projects within the building. |
| This report was inspected by: |
| Chase Johnson (Utah Certified Asbestos Inspector ASB#-5645) |
| of the 75 CES/CEOHA Asbestos/LBP Shop. |
| Any questions or concerns regarding this inspection report or if any new suspect asbestos containing material (ACM) is encountered, stop work and contact the personnel listed below for further assistance. |
CONTACT INFORMATION
Asbetsos/LBP Shop 75 CES(CEOHA)
| Supervisor: Nickolas King: | DSN: (801)586-7094 | Asbestos/LBP Shop (801)777-8006 |
| Cell: (801)430-4785 |
Building: 850 Bay G
| Remodel South Section Bay G | WO#: 57154 |
| &P | 24 March 2016 |
1335 Hours
Sheet2
| Traver Andreasen (Utah Certified Asbestos Inspector ASB#-4397) |
| Chase Johnson (Utah Certified Asbestos Inspector ASB#-5645) |
| Nickolas King (Utah Certified Asbestos Inspector ASB#-2257) |
| Raudel Arteaga (Utah Certified Asbestos Inspector ASB#-5863) |