REVITALIZE WATER DISTRIBUTION SYSTEM 94-0466
SECTION 02510A Page 5
1.4.3 Plastic Pipe and Fittings
Polyvinyl Chloride (PVC), pipe and fittings shall be handled and stored in accordance with the manufacturer's recommendations. Storage facilities shall be classified and marked in accordance with NFPA 704, with classification as indicated in NFPA 49 and NFPA 325-1.
PART 2 PRODUCTS
2.1 PIPE
Pipe shall conform to the respective specifications and other requirements specified below.
2.1.1 Reinforced and Prestressed Concrete Pipe
Steel cylinder reinforced concrete pipe shall conform to AWWA C300, AWWA C301, or AWWA C303 and shall be designed to withstand a working pressure of not less than 150 psi unless otherwise shown or specified.
2.1.2 Plastic Pipe
2.1.2.1 PE Plastic Pipe
Pipe, tubing, and heat-fusion fittings shall conform to AWWA C901.
2.1.2.2 PVC Plastic Pipe
Pipe, couplings and fittings shall be manufactured of material conforming to ASTM D 1784, Class 12454B.
a. Pipe Less Than 4 inch Diameter:
(1) Elastomeric-Gasket Joint: Pipe shall conform to dimensional requirements of
ASTM D 1785 Schedule 40, with joints meeting the requirements of 150 psi working pressure, 200 psi hydrostatic test pressure, unless otherwise shown or specified.
b. Pipe 4 through 12 inch Diameter: Pipe, couplings and fittings shall conform to AWWA
C900, Class 150, CIOD pipe dimensions, elastomeric-gasket joint, unless otherwise shown or specified.
c. Pipe 14 through 36 inch Diameter: Pipe shall conform to AWWA C905 unless otherwise shown or specified.
2.1.2.3 Ductile-Iron Pipe
Ductile-iron pipe shall conform to AWWA C151, working pressure not less than 150 psi, unless otherwise shown or specified. Pipe shall be cement-mortar lined in accordance with AWWA C104. Linings shall be standard. When installed underground, pipe shall be encased in a polyethylene tubing in accordance with AWWA C105 with a minimum thickness of 8 mils.
Flanged ductile iron pipe with threaded flanges shall be in accordance with AWWA C115.
2.1.2.4 Steel Pipe
REVITALIZE WATER DISTRIBUTION SYSTEM 94-0466
SECTION 02510A Page 6
2.1.2.5 Galvanized Steel Pipe
Galvanized steel pipe shall conform to ASTM A 53, standard weight.
2.1.2.6 Protective Materials for Steel Pipe
Protective materials for steel pipe, except as otherwise specified, shall be mechanically applied in a factory or plant especially equipped for the purpose. The materials shall, unless otherwise indicated on the drawings, consist of the following for the indicated pipe material and size:
a. Pipe and fittings less than 3 inches in diameter shall be thoroughly cleaned of foreign material by wire brushing and solvent cleaning, and then given 1 coat of coal-tar primer and 2 coats of coal-tar enamel conforming to AWWA C203; threaded ends of pipe and fittings shall be adequately protected prior to coating.
2.1.2.7 Copper Tubing
Copper tubing shall conform to ASTM B 88, Type K, annealed.
2.2 FITTINGS AND SPECIALS
2.2.2 PVC Pipe System
a. For pipe less than 4 inch diameter, fittings for threaded pipe shall conform to requirements of ASTM D 2464, threaded to conform to the requirements of ASME B1.20.1 for use with Schedule 80 pipe and fittings; fittings for solvent cement jointing shall conform to ASTM D 2466 or ASTM D 2467; and fittings for elastomeric-gasket joint pipe shall be iron conforming to AWWA C110 or AWWA C111. Iron fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104.
b. For pipe 4 inch diameter and larger, fittings and specials shall be iron, bell end in accordance with AWWA C110, 150 psi pressure rating unless otherwise shown or specified, except that profile of bell may have special dimensions as required by the pipe manufacturer; or fittings and specials may be of the same material as the pipe with elastomeric gaskets, all in conformance with AWWA C900. Iron fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104. Fittings shall be bell and spigot or plain end pipe, or as applicable.
Ductile iron compact fittings shall be in accordance with AWWA C153.
2.2.3 Ductile-Iron Pipe System
Fittings and specials shall be suitable for 150 psi pressure rating, unless otherwise specified.
Fittings and specials for mechanical joint pipe shall conform to AWWA C153. Fittings and specials for use with push-on joint pipe shall conform to AWWA C153 and AWWA C111.
Fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104. Ductile iron compact fittings shall conform to AWWA C153.
2.2.4 Steel Pipe System
2.2.4.1 Galvanized Steel Piping
Steel fittings shall be galvanized. Screwed fittings shall conform to ASME B16.3. Flanged fittings shall conform to AWWA C207.
| 1.4.3 Plastic Pipe and Fittings |
| PART 2 PRODUCTS |
| 2.1 PIPE |
| 2.1.1 Reinforced and Prestressed Concrete Pipe |
| 2.1.2 Plastic Pipe |
| 2.1.2.1 PE Plastic Pipe |
| 2.1.2.2 PVC Plastic Pipe |
| 2.1.2.3 Ductile-Iron Pipe |
| 2.1.2.4 Steel Pipe |
| 2.1.2.5 Galvanized Steel Pipe |
| 2.1.2.6 Protective Materials for Steel Pipe |
2.1.2.7 Copper Tubing
| 2.2 FITTINGS AND SPECIALS |
| 2.2.2 PVC Pipe System |
| 2.2.3 Ductile-Iron Pipe System |
| 2.2.4 Steel Pipe System |
| 2.2.4.1 Galvanized Steel Piping |