02510ARev1Pg5 6.pdf

PDF 24 KB Posted

Attached to
Revitalize Water Distribution System
Solicitation number
FA6670-08-R-0003
Issued by

View the file

Other files

File Type Posted
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Site Visit Sign in sheet.pdf PDF
Addendum 3.pdf PDF
Amendment 0001.pdf PDF
02081-02_C06.pdf PDF
02081-02_C21.pdf PDF
02081-02_C14.pdf PDF
02081-02_C23.pdf PDF
02081-02_C20.pdf PDF
02081-02_C12.pdf PDF
02081-02_C27.pdf PDF
02081-02_C31.pdf PDF
02081-02_C17.pdf PDF
02081-02_C19.pdf PDF
02081-02_C03.pdf PDF
02081-02_C01.pdf PDF
02081-02_C24.pdf PDF
02081-02_C22.pdf PDF
02081-02_C09.pdf PDF
02081-02_C07.pdf PDF
02081-02_C26.pdf PDF
02081-02_T02.pdf PDF
02081-02_C13.pdf PDF
02081-02_C11.pdf PDF
02921ARev1pg7.pdf PDF
02510ARev1Pg3.pdf PDF
ADDENDUM No.1.pdf PDF
Soil Boring Log.pdf PDF
SWP3-ES-Jun03 2.pdf PDF
FIGURE 2.pdf PDF
01330.pdf PDF
02770A.pdf PDF
01356A.pdf PDF
01670.pdf PDF
02302N.pdf PDF
swppp.pdf PDF
FIGURE 3.pdf PDF
01355A.pdf PDF
02510A.pdf PDF
AFF 3000.pdf PDF
02742N.pdf PDF
Ver2000_02081-02_C26.pdf PDF
01572.pdf PDF
01110N.pdf PDF
02081-02_C16.pdf PDF
SUBMITTAL LIST.pdf PDF
FA6670-08-R-0003.pdf PDF
Questionnaire Cover Letter.pdf PDF
Davis Bacon Wage Determination.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REVITALIZE WATER DISTRIBUTION SYSTEM 94-0466

SECTION 02510A Page 5

1.4.3 Plastic Pipe and Fittings

Polyvinyl Chloride (PVC), pipe and fittings shall be handled and stored in accordance with the manufacturer's recommendations. Storage facilities shall be classified and marked in accordance with NFPA 704, with classification as indicated in NFPA 49 and NFPA 325-1.

PART 2 PRODUCTS

2.1 PIPE

Pipe shall conform to the respective specifications and other requirements specified below.

2.1.1 Reinforced and Prestressed Concrete Pipe

Steel cylinder reinforced concrete pipe shall conform to AWWA C300, AWWA C301, or AWWA C303 and shall be designed to withstand a working pressure of not less than 150 psi unless otherwise shown or specified.

2.1.2 Plastic Pipe

2.1.2.1 PE Plastic Pipe

Pipe, tubing, and heat-fusion fittings shall conform to AWWA C901.

2.1.2.2 PVC Plastic Pipe

Pipe, couplings and fittings shall be manufactured of material conforming to ASTM D 1784, Class 12454B.

a. Pipe Less Than 4 inch Diameter:

(1) Elastomeric-Gasket Joint: Pipe shall conform to dimensional requirements of

ASTM D 1785 Schedule 40, with joints meeting the requirements of 150 psi working pressure, 200 psi hydrostatic test pressure, unless otherwise shown or specified.

b. Pipe 4 through 12 inch Diameter: Pipe, couplings and fittings shall conform to AWWA

C900, Class 150, CIOD pipe dimensions, elastomeric-gasket joint, unless otherwise shown or specified.

c. Pipe 14 through 36 inch Diameter: Pipe shall conform to AWWA C905 unless otherwise shown or specified.

2.1.2.3 Ductile-Iron Pipe

Ductile-iron pipe shall conform to AWWA C151, working pressure not less than 150 psi, unless otherwise shown or specified. Pipe shall be cement-mortar lined in accordance with AWWA C104. Linings shall be standard. When installed underground, pipe shall be encased in a polyethylene tubing in accordance with AWWA C105 with a minimum thickness of 8 mils.

Flanged ductile iron pipe with threaded flanges shall be in accordance with AWWA C115.

2.1.2.4 Steel Pipe

REVITALIZE WATER DISTRIBUTION SYSTEM 94-0466

SECTION 02510A Page 6

2.1.2.5 Galvanized Steel Pipe

Galvanized steel pipe shall conform to ASTM A 53, standard weight.

2.1.2.6 Protective Materials for Steel Pipe

Protective materials for steel pipe, except as otherwise specified, shall be mechanically applied in a factory or plant especially equipped for the purpose. The materials shall, unless otherwise indicated on the drawings, consist of the following for the indicated pipe material and size:

a. Pipe and fittings less than 3 inches in diameter shall be thoroughly cleaned of foreign material by wire brushing and solvent cleaning, and then given 1 coat of coal-tar primer and 2 coats of coal-tar enamel conforming to AWWA C203; threaded ends of pipe and fittings shall be adequately protected prior to coating.

2.1.2.7 Copper Tubing

Copper tubing shall conform to ASTM B 88, Type K, annealed.

2.2 FITTINGS AND SPECIALS

2.2.2 PVC Pipe System

a. For pipe less than 4 inch diameter, fittings for threaded pipe shall conform to requirements of ASTM D 2464, threaded to conform to the requirements of ASME B1.20.1 for use with Schedule 80 pipe and fittings; fittings for solvent cement jointing shall conform to ASTM D 2466 or ASTM D 2467; and fittings for elastomeric-gasket joint pipe shall be iron conforming to AWWA C110 or AWWA C111. Iron fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104.

b. For pipe 4 inch diameter and larger, fittings and specials shall be iron, bell end in accordance with AWWA C110, 150 psi pressure rating unless otherwise shown or specified, except that profile of bell may have special dimensions as required by the pipe manufacturer; or fittings and specials may be of the same material as the pipe with elastomeric gaskets, all in conformance with AWWA C900. Iron fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104. Fittings shall be bell and spigot or plain end pipe, or as applicable.

Ductile iron compact fittings shall be in accordance with AWWA C153.

2.2.3 Ductile-Iron Pipe System

Fittings and specials shall be suitable for 150 psi pressure rating, unless otherwise specified.

Fittings and specials for mechanical joint pipe shall conform to AWWA C153. Fittings and specials for use with push-on joint pipe shall conform to AWWA C153 and AWWA C111.

Fittings and specials shall be cement-mortar lined (standard thickness) in accordance with AWWA C104. Ductile iron compact fittings shall conform to AWWA C153.

2.2.4 Steel Pipe System

2.2.4.1 Galvanized Steel Piping

Steel fittings shall be galvanized. Screwed fittings shall conform to ASME B16.3. Flanged fittings shall conform to AWWA C207.

1.4.3 Plastic Pipe and Fittings
PART 2 PRODUCTS
2.1 PIPE
2.1.1 Reinforced and Prestressed Concrete Pipe
2.1.2 Plastic Pipe
2.1.2.1 PE Plastic Pipe
2.1.2.2 PVC Plastic Pipe
2.1.2.3 Ductile-Iron Pipe
2.1.2.4 Steel Pipe
2.1.2.5 Galvanized Steel Pipe
2.1.2.6 Protective Materials for Steel Pipe

2.1.2.7 Copper Tubing

2.2 FITTINGS AND SPECIALS
2.2.2 PVC Pipe System
2.2.3 Ductile-Iron Pipe System
2.2.4 Steel Pipe System
2.2.4.1 Galvanized Steel Piping