N.T.S.
FINAL DESIGN
VICINITY MAP
5555 E. MICHIGAN ST., SUITE 200 - ORLANDO, FL 32822-2779
www.avconinc.com
OFFICE: (407) 599-1122 - FAX: (407) 599-1133
12/04/2015
Sheet List Table
Sheet Number Sheet Title
North
L O C A T I O N M A P
DESIGN DRAWINGS FOR:
HOMESTEAD AIR RESERVE BASE, FLORIDA
INTERIOR RENOVATIONS TO
BUILDING 874
W9127810D0118
N.T.S.
ENGINEER:
CLIENT:
PROJECT LOCATION
PROJECT LOCATION
HOMESTEAD, FLORIDA
ENGINEERS & PLANNERS
AVCON, INC.
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
BRIEFING RM 2
BRIEFING RM 1
MAINTENANCE
215A
COMM CLOSET
PILOT AREA
HALL 2
HALL 1
SHEET
Sheet of
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
EXIT ACCESS TRAVEL DISTANCEXXX'
LOCATION OF EXIT SIGNS
(COORDINATE W/
ELECTRICAL DRAWINGS)
RECESSED FIRE EXTINGUISHER
CABINET. WRAP HOUSING WITH
INSULATION TO ENSURE STC
RATING IS MET.
TO SECOND MEANS OF EGRESS
LIFE SAFETY PLAN
SYMBOLS LEGEND
FE
OCCUPANT LOAD - RENOVATED AREA9
1 HOUR FIRE RATED WALL
DRAWING NO.
SYMBOLS LEGEND
SHEET NO.
DRAWING NO.
DRAWING TITLE
SECTION SYMBOL 1234
ROOM NUMBER
WINDOW TYPE
SPOT ELEVATION
DOOR NUMBER
ELEVATION SYMBOL
KEY NOTE
A-400
BUILDING AREA
NET HEATED AND COOLED: 865 SQUARE FEET
DRAWING
SCALE: 1/8" = 1'-0"
OCCUPANCY LOAD
EXTEND WALL TO UNDERSIDE
OF DECKING; SEAL ALL
PENTRATIONS WITH FIRE CAULK
DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
2 2' 0 2' 4'
DEMOLITION KEY NOTES
DEMOLISH EXISTING WALLS, DOORS AND DOOR FRAMES.
DEMOLISH EXISTING WINDOWS AND FRAMES.
DEMOLISH EXISTING DOOR AND FRAME.
DEMOLISH PORTION OF WALL TO ACCOMMODATE NEW DOOR AND
FRAME.
REMOVE ALL EXISTING CARPET, CEILING AND BASE BOARD FINISHES.
EXISTING PORTION OF RAISED FLOOR TO BE DEMOLISHED.
REMOVE GYPBPARD ON INTERIOR SIDE OF WALL TO ACCOMMODATE
NEW ELECTRICAL AND SOUND RATING REQUIREMENTS.
D1
D2
D3
D1D1D1
D2 D2
D4
CONTRACTOR TO VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS PRIOR TO FINAL
ACCEPTANCE OF DESIGN DOCUMENTS.
D5
D5 D5
LIFE SAFETY PLAN
LIFE SAFETY KEY NOTES
EXISTING FIRE EXTINGUISHER CABINET IN THIS VICINITY TO REMAIN IN
CURRENT LOCATION.
L1
D5 D5
D5 D5D5
D3
D3
D4
D4
D3D3
D3
36'
L1
FE
D6
D6
D7
D7 D7
D7 D7
D7 D7
D7
A1.01
BRIEFING RM 2
BRIEFING RM 1
MAINTENANCE
215A
COMM CLOSET
PILOT AREA
HALL 2
HALL 1
E
XI
S
TI
N G
0'
-0
E
XI
S
TI
N G
0'
-0
'-0
5'
-4
EXISTING 11'-2"
5' -1
0"
EXISTING 4'-6" EXISTING 11'-10"
13'-10"
REFLECTED CEILING PLAN
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
SHEET
Sheet of
FLOOR PLAN
SCALE: 1/4" = 1'-0"
2 2' 0 2' 4'
REFLECTED CEILING KEY NOTES
2'X2' FLOURESCENT LIGHT FIXTURES. SEE ELECTRICAL PLANS.
4' FLOURESCENT UTILITY FIXTURE. SEE ELECTRICAL PLANS.
2'X2' ACOUSTICAL CEILING TILE. USG MARS ClimaPlus - HIGH NRC OR
EQUAL.
PROVIDE DUPLEX OUTLET AND DATA DROP FOR CEILING MOUNTED
PROJECTOR. SEE ELECTRICAL PLANS.
ALL EXISTING SPRINKLER HEADS AND FIRE ALARM EQUIPMENT SHALL BE
RELOCATED AND/OR ADDED TO ACCOMOMDATE NEW LAYOUT.
SPRINKLERS AND ALARMS SHALL BE CENTERED ON CEILING TILES. SEE
ELECTRICAL AND FIRE PROTECTION PLANS.
R1
ARCHITECTURAL KEY NOTES
EXISTING PERIMETER WALL TO REMAIN. SEE WALL DETAIL 4/A1.10.
NEW 35
8" METAL STUD WALL TO EXTEND TO UNDERSIDE OF DECK. 1
LAYER OF 5 8" GYPBOARD ON EXTERIOR SIDE OF WALL, 2 LAYERS OF 5
8"
GYPBOARD w/ STAGGERED JOINTS ON THE INTERIOR SIDE OF THE WALL.
GYP BOARD TO EXTEND TO UNDERSIDE OF DECK WITH ACOUSTICAL
SEALANT AT TOP AND BOTTOM. SOUND ATTENUATION INSULATION
WITHIN NEW STUD CAVITY TO EXTEND TO UNDERSIDE OF DECK. SEE
WALL DETAIL 4/A1.10. PROVIDE STC 45 RATING FOR WALL.
NEW 3 5 8" METAL STUD WALL TO EXTEND TO UNDERSIDE OF DECK. 1
LAYER OF 5 8" GYPBOARD ON ONE SIDE OF WALL, 2 LAYERS OF 5
8" GYPBOARD ON OTHER w/ STAGGERED JOINTS . SOUND ATTENUATION
INSULATION WITHIN NEW STUD CAVITY TO EXTEND TO UNDERSIDE OF
DECK. SEE WALL DETAIL 1/A1.10. PROVIDE STC 45 RATING FOR WALL.
4" CORE DRILLED CHASE, ENCLOSED w/ 6" METAL STUD FRAMING AND 1
LAYER OF 5 8" GYP BOARD.
A1
A2
A3
CONTRACTOR TO VERIFY ALL EXISTING
CONDITIONS AND DIMENSIONS PRIOR TO FINAL
ACCEPTANCE OF DESIGN DOCUMENTS.
A1
A1
A1
A2
A2
A2
A2A2
A3
NEW 6" METAL STUD WALL w/ STUDS @ 16" O.C. TO EXTEND TO UNDERSIDE
OF DECK; 1 LAYER OF 5 8" GYPBOARD ON EXTERIOR SIDE OF WALL, 2
LAYERS OF 5 8" GYPBOARD w/ STAGGERED JOINTS w/ SOUND ATTENUATION INSULATION. JAMB STUDS FOR DOORS SHALL BE DOUBLED 16ga.& HORIZONTALLY BRACED WITH 16ga. METAL STUDS. IF ADJOINING WALLS
ARE FIRE RATED, RATING MUST BE CARRIED THROUGHOUT NEW WALL AND
DOOR. SEE WALL DETAIL 2/A1.10. PROVIDE STC 45 RATING FOR WALL.
INFILL EXTERIOR PLANE OF EXISTING WINDOW OPENING WITH MASONRY
MATCHING EXISTING EXTERIOR. MASONRY SHALL LINE UP w/ EXISTING PLANE. INTERIOR WALL SHALL RECEIVE 6" METAL STUD WALL w/ BATT INSULATOIN w/ 2 LAYERS OF 5 8" GYP BOARD AND SHALL LINE UP WITH
EXISTING SURROUNDING WALL PLANE. SEE WALL DETAIL 5/A1.10.
EXTEND EXISTING STUD WALL TO UNDERSIDE OF DECK w/ SOUND
ATTENUATION INSULATION AND 1 LAYER OF 5 8" GYPBOARD ON ONE SIDE
OF WALL, 2 LAYERS OF 5 8" GYPBOARD ON OTHER w/ STAGGERED JOINTS SEE WALL DETAIL 3/A1.10. REINFORCE DOOR JAMBS w/ 3 5
8"16ga NO-HOLE
STEEL STUDS. PROVIDE STC 45 RATING FOR WALL.
NEW 21 DOOR CELL PHONE LOCKER w/ MASTER ACCESS; MAILBOX WORKS
- 7X3 - 21 DOOR CELL PONE LOCKER (AFH1600XD73)
A5
A5
A5
A5
3'-0" x 7'-0"
SOUND
RATING
FRAME
MAT'L REMARKSJAMBHEADHDW SILLMAT'LSIZE TYPENO.
DOOR SCHEDULE
DOOR
3'-0" x 7'-0"
3'-0" x 7'-0"
3'-0" x 7'-0"
3'-0" x 7'-0"
3'-0" x 7'-0"102
3'-0" x 7'-0"101 C MTL HMHW-1
B WD
B WD
B WD
B WD
C MTL
A WD
HM
HM
HM
HM
HM
HM
7/A1.10 8/A1.10 9/A1.10
HW-2
HW-2
HW-3
HW-1
HW-3
HW-4
A6
A6 A6
- INTERIOR LATEX PAINTPNT
- 5/8" GYP BOARD; PRIMED & PAINTEDGYP
MTL - METAL DOOR; SEE SCHEDULE; PRIMED & PAINTED
DOORS
" TYPE "X" GYPSUM BOARD85-
CAR1 - COMMERCIAL GRADE CARPET TILE
GB
RB - 4" RESILIENT WALL BASE
CEILINGS
WALLS
BASE
FLOORING
ABBREVIATIONS
- LAY-IN ACOUSTICAL CEILING TILE 2'x2'-WHITEACT1
HM - HOLLOW METAL FRAME - WELDED
1 3/4" WOOD DOOR
TYPE B
w/ 45 STC RATING;
SOLID CORE BIRCH
TYPE A
1 3/4" WOOD DOOR
DOOR TYPES
SOLID CORE BIRCH
RB ACT1
REMARKSBASE
PNT
MAINTENANCE218
217 BRIEFING ROOM 1
GBCAR1
BRIEFING ROOM 2
COMM CLOSET
WALL
MAT'L HTFINISHFLOORNO.
215A
215 PILOT AREA
CEILING
FINISHROOM NAME
FINISH SCHEDULE
RBPNTGBSC
CAR1
CAR1
CAR1
RBPNTGB
RBPNTGB
RBPNTGB
ACT1
ACT1
8'-0"
EXPOSED
219 HALL 1
HALL 2
- EXPOSED CEILINGEXP
+ 8'-0" A.F.F.
EXPOSED
+ 8'-0" A.F.F.
+ 8'-0" A.F.F.
+ 8'-0" A.F.F.
+ 8'-0" A.F.F.
+ 8'-0" A.F.F.
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
ACT1
ACT1
ACT1
RB
RB
PNT
PNT
GB
GB
CAR1
CAR1
SOUND BATTS OVER ACT CEILING
SOUND BATTS OVER ACT CEILING
A7 A7
A7
A7
A7
A7
A1
R1
R1 R1
R1 R1
R1 R1
R1
R1
R1
R1
R1R1
R1
R1
R1
R1R1
R1R1
R1
R1 R1 R1
R1R1R1
R2
R2R2
R3
R3
R3
R3
R3
R3 R3
R3 R4
R4
R5
R5
R5
R5
R5
R5 R5
R5
A8
A8
HARDWARE SCHEDULE
HW-1
HW-2
HW-3
HW-4
A4
A4
FIELD RATED
PRE-CUT DOOR FOR CIPHER LOCK
WD - SOLID CORE WOOD DOOR; SEE SCHEDULE
STAINED TO MATCH EXISTING - RFI-0004
TYPE C
w/ 45 STC RATING;
METAL DOOR
FIELD RATED
7/A1.10 8/A1.10 9/A1.10
7/A1.10 8/A1.10 9/A1.10
7/A1.10 8/A1.10 9/A1.10
7/A1.10 8/A1.10 9/A1.10
7/A1.10 8/A1.10 9/A1.10
7/A1.10 8/A1.10 9/A1.10
STC 45
STC 45
STC 45
STC 45
STC 45
STC 45
STC 45
X-10 LOCKSET, BALANCED MAGNETIC SWITCH, LEVER
SET, ALARMED, NON-HOLD CLOSER, WALL STOP, SS
THRESHOLD, 3 CAM-LIFT HINGES, REMOVABLE
CYLINDER - RFI-0005
BALANCED MAGNETIC SWITCH, LEVER SET, ALARMED,
NON-HOLD CLOSER, 8" KICK PLATE, WALL STOP, SS
THRESHOLD, 3 CAM-LIFT HINGES, REMOVABLE
CYLINDER
LEVER SET, NON-HOLD CLOSER, 8" KICK PLATE, WALL
STOP, SS THRESHOLD, 3 CAM-LIFT HINGES,
REMOVABLE CYLINDER
LEVER SET, NON-HOLD CLOSER, WALL STOP, SS
THRESHOLD, REMOVABLE CYLINDER
*SCHEDULE TO BE FINALIZED IN SHOP DRAWINGS.
PROVIDED BY USER
A1.02
RFI-0010, EXISTING HOLES
TREATED & SEALED PER
IAWICD 705
1' -4
" A P
P R
O
XI
M A
TE
WALL DETAIL
SCALE: 1" = 1'-0"
SHEET
Sheet of
WALL DETAIL
SCALE: 1" = 1'-0"
WALL DETAIL
SCALE: 1" = 1'-0"
WALL DETAIL
SCALE: 1" = 1'-0"
WALL DETAIL
SCALE: 1" = 1'-0"
WALL DETAIL
SCALE: 3" = 1'-0"
EXISTING FLOOR
1/2" ACOUSTICAL SEALANT JOINT
4" RESILIENT BASE
FINISH PRIMED & PAINTED
2 LAYERS OF 5/8" TYPE X GYP BOARD
3 5/8" METAL STUDS @ 16" O.C.
SOUND BATTS CONTINUOUS
3 5/8" METAL STUDS @ 16" O.C. TO
EXISTING DECK
EXTEND TO UNDERSIDE OF DECK
1/2" ACOUSTICAL SEALANT JOINT
ACOUSTICAL CEILING TILE
EXISTING FLOOR
1/2" ACOUSTICAL SEALANT JOINT
4" RESILIENT BASE
FINISH PRIMED & PAINTED
1 LAYER OF 5/8" TYPE X GYP BOARD
6" METAL STUDS @ 16" O.C.
SOUND BATTS CONTINUOUS
6" METAL STUDS @ 16" O.C. TO
EXISTING DECK
EXTEND TO UNDERSIDE OF DECK
1/2" ACOUSTICAL SEALANT JOINT
EXISTING FLOOR
1/2" ACOUSTICAL SEALANT JOINT
4" RESILIENT BASE
FINISH PRIMED & PAINTED
2 NEW LAYERS OF 5/8" TYPE X GYP BOARD
EXISTING 3 5/8" METAL STUDS @ 16" O.C.
TO INSTALL NEW SOUND BATTS CONTINUOUS
3 5/8" METAL STUDS @ 16" O.C. TO
EXISTING DECK
EXTEND TO UNDERSIDE OF DECK
1/2" ACOUSTICAL SEALANT JOINT
ACOUSTICAL CEILING TILE
EXISTING 3 5/8" METAL STUD WALL
REMOVE EXISTING LAYER OF GYPBOARD
EXISTING FLOOR
1/2" ACOUSTICAL SEALANT JOINT
NEW 4" RESILIENT BASE
EXISTING 3 5/8" METAL STUDS @ 16" O.C.
3 5/8" METAL STUDS @ 16" O.C. TO
EXISTING DECK
EXTEND TO UNDERSIDE OF DECK
1/2" ACOUSTICAL SEALANT JOINT
ACOUSTICAL CEILING TILE
EXISTING 3 5/8" METAL STUD WALL
@ EXISTING GYP BOARD FINISH
NEW 3 5/8" METAL STUDS @ 16" O.C.
SOUND BATTS CONTINUOUS
FINISH PRIMED & PAINTED
NEW 2 LAYERS OF 5/8" TYPE X GYP BOARD
EXISTING EXTERIOR WALL
PRIMED & PAINTED
2 NEW LAYERS 5/8" GYP BOARD FINISH
NEW 6" METAL STUDS @ 16" O.C.
1/2" SEALANT JOINT
R-19 MIN. INSULATION
NEW CMU BLOCK INFILL
TO MATCH EXISTING
WEEPS AS REQUIRED
CONTINUOUS FLASHING
OVER DENSGLASS
EXISTING EXTERIOR WALL
PRIMED & PAINTED
2 NEW LAYERS 5/8" GYP BOARD FINISH
NEW 6" METAL STUDS @ 16" O.C.
1/2" SEALANT JOINT
R-19 MIN. INSULATION
NEW CMU BLOCK INFILL
TO MATCH EXISTING
WEATHER BARRIER
EXISTING WALL
6" METAL STUD FRAMING
PRIMED & PAINTED
5/8" GYP BOARD FINISH
4" CORE IN CONCRETE SLAB
FINISH PRIMED & PAINTED
2 NEW LAYERS OF 5/8" TYPE X GYP BOARD
ACOUSTICAL CEILING TILE
NOTE:
STAGGER JOINTS OF GYP BOARD SO SEAMS DO NOT
ALIGN.
STABILIZE SOUND BATT LOCATION
INTERMEDIATE BLOCKING TO
STABILIZE SOUND BATT LOCATION
INTERMEDIATE BLOCKING TO
STABILIZE SOUND BATT LOCATION
INTERMEDIATE BLOCKING TO
STABILIZE SOUND BATT LOCATION
INTERMEDIATE BLOCKING TO
OVER DENSGLASS
WEATHER BARRIER
FINISH PRIMED & PAINTED
1 LAYER OF 5/8" TYPE X GYP BOARD
FINISH PRIMED & PAINTED
1 LAYER OF 5/8" TYPE X GYP BOARD
FINISH PRIMED & PAINTED
1 LAYER OF 5/8" TYPE X GYP BOARD
FINISH PRIMED & PAINTED ON CONTROL SIDE
FASTENED TO EXISTING STUD WALL;
SILL DETAIL
SCALE: 3" = 1'-0"
JAMB DETAIL
SCALE: 3" = 1'-0"
HEAD DETAIL
SCALE: 3" = 1'-0"
BATT INSULATION
DOOR AS SCHEDULED
(NO-HOLE)
SEALANT
BOARD SHEATHING
DOOR AS SCHEDULED
DOOR FRAME BEYOND
2 LAYERS OF 5/8" GYP
BATT INSULATION
DOOR AS SCHEDULED
2x WOOD BUCK
16ga METAL STUD JAMB (NO-HOLE)
SEALANT
BOARD SHEATHING
METAL DOOR FRAME
2 LAYERS OF 5/8" GYP
REFERENCE SHOP DRAWINGS
REFERENCE SHOP DRAWINGS
FOR ACOUSTICAL THRESHOLD
FOR ACOUSTICAL TREATMENT
2x WOOD BUCK
METAL DOOR FRAME
REFERENCE SHOP DRAWINGS
FOR ACOUSTICAL TREATMENT
6" METAL STUD WALL
6" METAL STUD WALL
EXTEND FROM SLAB TO STRUCTURE
16ga METAL STUD HEADER
CONTROL SIDE CONTROL SIDE CONTROL SIDECONTROL SIDE
A1.10
MATCH EXISTING
ANCHORAGE TO
MATCH EXISTING
ANCHORAGE TO
1 LAYER OF 5/8" TYPE X GYP BOARD
WALL CONSTRUCTED PER RFI0014
EXISTING CARPET TO REMAIN BENEATH
ALL NEW METAL TRACK-RFI-0006
EXISTING CARPET TO REMAIN BENEATH
ALL NEW METAL TRACK-RFI-0006
EXISTING CARPET TO REMAIN BENEATH
ALL NEW METAL TRACK-RFI-0006
EXISTING CARPET TO REMAIN BENEATH
ALL NEW METAL TRACK-RFI-0006
MECHANICAL SYMBOLS
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
FLOOR PLAN
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
R
E V
I S
I O
N
DEMOLITION PLAN
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
R
E V
I S
I O
N
NOT TO SCALE
CONDENSER UNIT DETAIL
NOT TO SCALE
CEILING DIFFUSER DETAIL
NOT TO SCALE
BRANCH DUCT DETAILS
01 02 03
NOT TO SCALE
CONDENSATE DRAIN
NOT TO SCALE
FIRE DAMPER DETAIL
NOT TO SCALE
CONDENSER UNIT PAD DETAIL
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
NOT TO SCALE
CONDENSER UNIT TIE-DOWN DETAIL
NOT TO SCALE
DUCTWORK SUPPORT DETAILS
NOT TO SCALE
MINI SPLIT AIR HANDLER DETAIL
NOT TO SCALE
BOLLARD DETAIL
NOT TO SCALE
RETURN AIR GRILLE/BOOT DETAIL
NOT TO SCALE
PIPE HANGER DETAILS
NOT TO SCALE
TYPICAL LOW PRESSURE
"TEE" DUCT FITTING DETAIL
NOT TO SCALE
HVAC SECURE WALL PENETRATION DETAIL
NOT TO SCALE
VAV TERMINAL WITH ELECT. HEAT
NOT TO SCALE
TRANSFER AIR DETAIL
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
TYPICAL BLUE STROBE DETAIL
TYPICAL SECURITY ROUGH-IN DETAIL
NEW LUMINAIRE SCHEDULE
SECURE WALL/FOOR PENETRATION DETAIL TRANSFORMER CONNECTION DETAIL
System No. W-L-3026
F Ratings -1 and 2 Hr (see item 1)
L Rating - 1 and 2 Hr (see item 1)
Through-penetration Firestop
Wall Assembly
Studs
Gypsum Board *
Cables
Fill, Void of Cavity Material * - Caulk -
EGS NELSON FIRESTOP
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
L Rating At 400 F -less than I CFM/sq ft
L Rating At Ambient -less than 1 CFM/sq ft
T Ratings -0, 1,2,3, and 4 Hr (See Item 3)
F Ratings -1,2,3 and 4 Hr (See Items 2 and 3)
System No. W-L-1001
Through-penetration Firestop Systems
RatingRatingor Conduit
3M COMPANY
Diam In HrHr
Fill Void or Cavity Material* - Caulk
Max Pipe
WARD MFG INC
A BUNDY CO
TITEFLEX CORP
OMEGA FLEX INC
TF
Through Penetrating Product*
Copper Pipe
Copper Tubing
Conduit
Through-Penetrant
Iron Pipe
Steel Pipe
Wall Assembly
Gypsum Board*
Studs
FIRESTOP SYSTEM
MC TYPE CABLE
3M COMPANY
Nom PipeMin Floor
Tube or Conduit
Diam In.
or Wall
Thkns In.
Fill Void or Cavity Material* - Caulk,Sealant -
Rating Hr
Max Annular
Space In.
Mln Caulk
Thkns In.
F
Packing Material
Steel Pipe
Iron Pipe
Conduit
Conduit
Copper
Copper
Steel Sleeve
Through Penetrants
Precast Concrete UnIts
Floor or Wall Assembly -
Concrete Blocks
Concrete Blocks*
Precast Concrete UnIts*
System No. C-AJ-1044
F Ratings -2,3, and 4 Hr (See Items 2A and 4)
T Rating -0 Hr
L Rating At Ambient -2 CFM/sq ft
L Rating At 400 F -less than 1 CFM/sq ft
Through-penetration Firestop
W Rating - Class 1 (see item 4)
Forming Material* -
PARTIAL 1ST FLOOR PLAN
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
E1-0.2
DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
RENOVATED FLOOR PLAN
SCALE: 1/4" = 1'-0"
2 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
ENLARGED EXISTING ELECTRICAL ROOM PLAN
SCALE: 1/4" = 1'-0"
3 2' 0 2' 4'
ENLARGED COMMUNICATIONS ROOM PLAN
4 2' 0 2' 4'
DEMOLITION PLAN
1 2' 0 2' 4'
RENOVATED FLOOR PLAN
SCALE: 1/4" = 1'-0"
2 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
Luminaire Schedule
Scene: NORMAL
Symbol Qty Label Arrangement Total Lamp Lumens LLF Description
Calculation Summary
Scene: NORMAL
Label CalcType Units Avg Max Min Avg/Min Max/Min
Calculation Summary
Scene: EMEREGENCY
Label CalcType Units Max Min Avg/Min Max/Min
Luminaire Schedule
Scene: EMERGENCY
Symbol Qty Label Arrangement Total Lamp Lumens LLF Description
ELECTRICAL PHOTOMETRIC PLAN - NORMAL LIGHTING
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
ELECTRICAL PHOTOMETRIC PLAN - EMERGENCY LIGHTING
2 2' 0 2' 4'
E3-0.1
DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
1 2' 0 2' 4'
RENOVATED FLOOR PLAN
SCALE: 1/4" = 1'-0"
2 2' 0 2' 4'
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
ENLARGED COMMUNICATIONS CLOSET PLAN
3 2' 0 2' 4'
PARTIAL ELECTRICAL ONE LINE
SCALE: NTS
PARTIAL FIRE ALARM RISER
SCALE: NTS
SECURE DIGITAL PHONE RISER
SCALE: NTS
SPAWN RISER
SCALE: NTS
SIPRNET RISER
SCALE: NTS
NIPRNET RISER
SCALE: NTS
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
UNCLASSIFIED OUTLET DETAIL
SCALE: NTS
CCTV RISER
SCALE: NTS
CLASSIFIED OUTLET DETAIL
SCALE: NTS
PRINTER OUTLET DETAIL
SCALE: NTS
IDS AND ENTRY CONTROL RISER
BLUE LIGHT RISER
SHEET
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
CONSTRUCTION IN THE PROJECT AREA.
AS-BUILT DRAWINGS
BLUE STROBE LIGHT CONTROL SCHEMATIC
SCALE: NTS
4-POST RACK 4-POST RACK
C A
B L E
M
A N
A G
E M
E N
T
C A
B
N
A G
E M
E N
T
C A
B
N
A G
E M
E N
T
C A
B
N
A G
E M
E N
T
C-01 C-01
C-02 C-02
4-POST RACK
C A
B
N
A G
E M
E N
T C
A B
N
A G
E M
E N
T
C-01
C-02
COMMUNICATION SYSTEMS RACK ELEVATION DETAIL
SCALE: NTS
C-01
C-03
C-04
C-02
PATCH PANEL DETAILS
Sheet of
THESE AS-BUILT DRAWINGS ARE INTENDED TO DISPLAY
THE COMPLETED WORK SUBSTANTIALLY AS
CONSTRUCTED. THEY ARE BASED ON DATA FURNISHED BY
THE CONTRACTOR(S) TO THE ENGINEER. FIELD
VERIFICATION OF CONDITIONS AND LOCATIONS SHOULD
BE UNDERTAKEN PRIOR TO ALTERATIONS OR
| Cover Sheet As-Builts |
| A1.01 DEMOLITION PLAN |
| A1.02 FLOOR PLANS |
| A1.10 DETAILS |
| Mechanical As-Builts |
| Fire Protection As-Builts |
| Electrical As-Builts |