SECTION 09 29 00
GYPSUM BOARD
05/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992; Reaffirmed 2005) Specifications for
Interior Installation of Cementitious Backer Units
ASTM INTERNATIONAL (ASTM)
ASTM C 1002 (2007) Standard Specification for Steel Self-
Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1047 (2010a) Standard Specification for
Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C 1177/C 1177M (2008) Standard Specification for Glass Mat
Gypsum Substrate for Use as Sheathing
ASTM C 1178/C 1178M (2008) Standard Specification for Glass Mat
Water-Resistant Gypsum Backing Panel
ASTM C 1396/C 1396M (2009a) Standard Specification for Gypsum
Board
ASTM C 475/C 475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C 514 (2004; R 2009e1) Standard Specification for
Nails for the Application of Gypsum Board
ASTM C 557 (2003; R 2009e1) Adhesives for Fastening
Gypsum Wallboard to Wood Framing
ASTM C 840 (2008) Application and Finishing of Gypsum
Board
ASTM C 954 (2010) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
ASTM C1629/C1629M (2006) Standard Classification for Abuse- Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels
ASTM D 1037 (2006a) Evaluating Properties of Wood-Base
Fiber and Particle Panel Materials
ASTM D 1149 (2007) Standard Test Method for Rubber
Deterioration - Surface Ozone Cracking in a Chamber
ASTM D 226/D 226M (2009) Standard Specification for Asphalt-
Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D 2394 (2005; R 2011) Simulated Service Testing of
Wood and Wood-Base Finish Flooring
ASTM D 412 (2006ae2) Standard Test Methods for
Vulcanized Rubber and Thermoplastic Elastomers - Tension
ASTM D 5420 (2010) Impact Resistance of Flat, Rigid
Plastic Specimen by Means of a Strike Impacted by a Falling Weight (Gardner Impact)
ASTM D 624 (2000; R 2007) Tear Strength of Conventional
Vulcanized Rubber and Thermoplastic Elastomers
ASTM E 2129 (2005) Standard Practice for Data Collection for Sustainability Assessment of Building Products
ASTM E 695 (2003; R 2009) Measuring Relative Resistance of Wall, Floor, and Roof Construction to Impact Loading
ASTM E 84 (2010b) Standard Test Method for Surface
Burning Characteristics of Building Materials
GREENGUARD ENVIRONMENTAL INSTITUTE (GEI)
GEI Greenguard Standards for Low Emitting
Products
GYPSUM ASSOCIATION (GA)
GA 214 (2007) Recommended Levels of Gypsum Board
Finish
GA 216 (2010) Application and Finishing of Gypsum
Panel Products
GA 224 (2008) Installation of Predecorated Gypsum
Board
GA 253 (2007) Application of Gypsum Sheathing
GA 600 (2009) Fire Resistance Design Manual
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS Scientific Certification Systems (SCS)Indoor
Advantage
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED (2002; R 2005) Leadership in Energy and
Environmental Design(tm) Green Building Rating System for New Construction (LEED-NC)
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2011) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-03 Product Data
Submit for each type of gypsum board and for cementitious backer units.
Submit manufacturer's product data, indicating VOC content.]
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.3.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range.
Gypsum wallboard shall not be stored with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives.
1.3.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
file://HSTFS01.AREA52.AFNOAPPS.USAF.MIL/INFOBASE/MSG/BCE/CEC/AUTO%20CAD/Gis_Cad/Projects/KY%202011%20Projects/11-9024,%2025%20&%2026%20Repair%20Buildings%20246,%20248%20&%20253%20(TFI)/4.%20Design%20Phases/100%25%20Design%20Analysis,%20Drawings%20&%20Specs%20Re-Submittal/01%2033%2000.doc
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Temperature
Maintain a uniform temperature of not less than 10 degrees C( 50 degrees F) in the structure for at least 48 hours prior to, during, and following the application of gypsum board, cementitious backer units, and joint treatment materials, or the bonding of adhesives.
1.4.2 Exposure to Weather
Protect gypsum board and cementitious backer unit products from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
1.4.3 Temporary Ventilation
Provide temporary ventilation for work of this section.
1.5 SCHEDULING
The gypsum wallboard shall be taped, spackled and primed before the installation of the highly-emitting materials.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only.
Submit Material Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Gypsum Board
ASTM C 1396/C 1396M.
2.1.1.1 Regular
1200 mm (48 inch) wide, 15.9 mm (5/8 inch) thick, tapered edges.
2.1.1.2 Type X (Special Fire-Resistant)
1200 mm (48 inch) wide15.9 mm( 5/8 inch) thick, tapered edges.
2.1.2 Regular Water-Resistant Gypsum Backing Board
ASTM C 1396/C 1396M
2.1.2.1 Regular
1200 mm ( 48 inch )wide, 15.9 mm( 5/8 inch) thick, tapered edges.
2.1.2.2 Type X (Special Fire-Resistant)
1200 mm ( 48 inch )wide, 15.9 mm(5/8 inch) thick, tapered edges.
2.1.3 Impact Resistant Gypsum Board
1200 mm( 48 inch)wide, 15.9 mm( 5/8 inch) thick, tapered edges.
Reinforced gypsum panel with imbedded fiber mesh or lexan backing testing in accordance with the following tests. Hard body impact test must attain a Level 2 performance in accordance with ASTM C1629/C1629M. Provide fasteners that meet manufacturer requirements and specifications stated within this section. Impact resistant gypsum board, when tested in accordance with ASTM E 84, have a flame spread rating of 25 or less and a smoke developed rating of 50.
2.1.3.1 Structural Failure Test
ASTM E 695 or ASTM D 2394 for structural failure (drop penetration). ASTM E 695 using a 27.2 kg( 60 lb) sand filled leather bag, resisting no less than 407 N-m( 300 ft. lb.) cumulative impact energy before failure or ASTM D 2394 using 139.7 mm( 5.5 inch) hemispherical projectile resisting no less than 357 N-m( 264 ft. lb.) before failure. Provide test specimen stud spacing a minimum 406 mm( 16 inch) on center.
2.1.3.2 Indentation Test
ASTM D 5420 or ASTM D 1037 for indentation resistance. ASTM D 5420 using a .907 kg( 32 oz) weight with a 16 mm( 5/8 inch) hemispherical impacting head dropped once 915 mm( 3 feet) creating not more than 3.5 mm( 0.137 inch) indentation or ASTM D 1037 using no less than 213 kg( 470 lb) weight applied to the 11.13 mm( 0.438 inch) diameter ball to create not more than a 0.5 mm(
0.0197 inch) indentation depth.
2.1.4 Cementitious Backer Units
In accordance with the Tile Council of America (TCA) Handbook.
2.1.5 Joint Treatment Materials
ASTM C 475/C 475M.
2.1.5.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.5.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.5.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
2.1.5.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.5.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
2.1.6 Fasteners
2.1.6.1 Screws
ASTM C 1002, Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.84 mm( 0.033 inch) thick. ASTM C 954 steel drill screws for fastening gypsum board to steel framing members 0.84 to 2.84 mm( 0.033 to
0.112 inch) thick. Provide cementitious backer unit screws with a polymer coating.
2.1.7 Adhesives
Do not use adhesive containing benzene, carbon tetrachloride, or trichloroethylene. Adhesive shall contain a maximum VOC content of 50 grams per liter.
2.1.7.1 Adhesive for Fastening Gypsum Board to Metal Framing
Type recommended by gypsum board manufacturer.
2.1.7.2 Adhesive for Fastening Gypsum Board to Wood Framing
ASTM C 557.
2.1.7.3 Adhesive for Laminating
Adhesive attachment is not permitted for multi-layer gypsum boards. For laminating gypsum studs to face panels, provide adhesive recommended by gypsum board manufacturer.
2.1.8 Accessories
ASTM C 1047. Fabricate from corrosion protected steel or plastic designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment.
2.1.9 Asphalt Impregnated Building Felt
Provide a 6.7 kg( 15 lb) asphalt moisture barrier over gypsum sheathing.
Conforming to ASTM D 226/D 226M Type 1 (No. 15) for asphalt impregnated building felt.
2.1.10 Water
Provide clean, fresh, and potable water.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Gypsum Board and Framing
Verify that surfaces of gypsum board and framing to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Masonry and Concrete Walls
Verify that surfaces of masonry and concrete walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C 840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints. Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible.
Surfaces of gypsum board and substrate members may be bonded together with an adhesive, except where prohibited by fire rating(s). Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer. Minimize framing by floating corners with single studs and drywall clips. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Application of Single-Ply Gypsum Board to Wood Framing
Apply in accordance with ASTM C 840, System I or GA 216.
3.2.2 Application of Two-Ply Gypsum Board to Wood Framing
Apply in accordance with ASTM C 840, System II or GA 216.
3.2.3 Adhesive Nail-On Application to Wood Framing
Apply in accordance with ASTM C 840, System III or GA 216. This method may be used in lieu of ASTM C 840, System I at the option of the Contractor.
3.2.4 Solid Gypsum Board Partitions
Provide in accordance with ASTM C 840, System V or GA 216.
3.2.5 Adhesive Application to Interior Masonry or Concrete Walls
Apply in accordance with ASTM C 840, System VI or GA 216.
3.2.6 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C 840, System VIII or GA 216.
3.2.7 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
In dry areas (areas other than tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply glass mat water-resistant gypsum tile backing board or water-resistant gypsum backing board in accordance with ASTM C 840, System X or GA 216.
3.2.8 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C 840, System XIII or GA 216. Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.
3.2.9 Application of Impact Resistant Gypsum Board
Apply in accordance with applicable system of ASTM C 840 as specified or GA
216. Follow manufacturers written instructions on how to cut, drill and attach board.
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
In wet areas (tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply cementitious backer units in accordance with ANSI A108.11.
Place a 7.6 kg( 15 lb) asphalt impregnated, continuous felt paper membrane behind cementitious backer units, between backer units and studs or base layer of gypsum board. Place membrane with a minimum 150 mm( 6 inch) overlap of sheets laid shingle style.
3.3.2 Joint Treatment
ANSI A108.11
3.4 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C 840, GA 214 and GA
216. Finish plenum areas above ceilings to Level 1 in accordance with GA
214. Finish water resistant gypsum backing board, ASTM C 1396/C 1396M, to receive ceramic tile to Level 2 in accordance with GA 214. Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214. Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with GA 214. Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214. Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.4.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semi-gloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.5 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.6 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and ceiling framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated. Joints of fire-rated gypsum board enclosures shall be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.7 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
3.8 WASTE MANAGEMENT
As specified in Waste Management Plan and as follows. Separate clean waste gypsum products from contaminants. Do not include wood, plastic, metal, asphalt-impregnated gypsum board, or any gypsum board coated with glass fiber, vinyl, decorative paper, or other finish. Place in designated area and protect from moisture and contamination.
End of Section 09 29 00 file://HSTFS01.AREA52.AFNOAPPS.USAF.MIL/INFOBASE/MSG/BCE/CEC/AUTO%20CAD/Gis_Cad/Projects/KY%202011%20Projects/11-9024,%2025%20&%2026%20Repair%20Buildings%20246,%20248%20&%20253%20(TFI)/4.%20Design%20Phases/100%25%20Design%20Analysis,%20Drawings%20&%20Specs%20Re-Submittal/07%2092%2000.doc
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 DELIVERY, STORAGE, AND HANDLING |
| 1.3.1 Delivery |
| 1.3.2 Storage |
| 1.3.3 Handling |
| 1.4 ENVIRONMENTAL CONDITIONS |
| 1.4.1 Temperature |
| 1.4.2 Exposure to Weather |
| 1.4.3 Temporary Ventilation |
1.5 SCHEDULING
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.1.1 Gypsum Board |
| 2.1.1.1 Regular |
| 2.1.1.2 Type X (Special Fire-Resistant) |
| 2.1.2 Regular Water-Resistant Gypsum Backing Board |
| 2.1.2.1 Regular |
| 2.1.2.2 Type X (Special Fire-Resistant) |
| 2.1.3 Impact Resistant Gypsum Board |
| 2.1.3.1 Structural Failure Test |
| 2.1.3.2 Indentation Test |
| 2.1.4 Cementitious Backer Units |
| 2.1.5 Joint Treatment Materials |
| 2.1.5.1 Embedding Compound |
| 2.1.5.2 Finishing or Topping Compound |
| 2.1.5.3 All-Purpose Compound |
| 2.1.5.4 Setting or Hardening Type Compound |
| 2.1.5.5 Joint Tape |
| 2.1.6 Fasteners |
| 2.1.6.1 Screws |
| 2.1.7 Adhesives |
| 2.1.7.1 Adhesive for Fastening Gypsum Board to Metal Framing |
| 2.1.7.2 Adhesive for Fastening Gypsum Board to Wood Framing |
| 2.1.7.3 Adhesive for Laminating |
| 2.1.8 Accessories |
| 2.1.9 Asphalt Impregnated Building Felt |
| 2.1.10 Water |
| PART 3 EXECUTION |
| 3.1 EXAMINATION |
| 3.1.1 Framing and Furring |
| 3.1.2 Gypsum Board and Framing |
| 3.1.3 Masonry and Concrete Walls |
| 3.2 APPLICATION OF GYPSUM BOARD |
| 3.2.1 Application of Single-Ply Gypsum Board to Wood Framing |
| 3.2.2 Application of Two-Ply Gypsum Board to Wood Framing |
| 3.2.3 Adhesive Nail-On Application to Wood Framing |
| 3.2.4 Solid Gypsum Board Partitions |
| 3.2.5 Adhesive Application to Interior Masonry or Concrete Walls |
| 3.2.6 Application of Gypsum Board to Steel Framing and Furring |
| 3.2.7 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive |
| 3.2.8 Control Joints |
| 3.2.9 Application of Impact Resistant Gypsum Board |
| 3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS |
| 3.3.1 Application |
| 3.3.2 Joint Treatment |
| 3.4 FINISHING OF GYPSUM BOARD |
| 3.4.1 Uniform Surface |
| 3.5 SEALING |
| 3.6 FIRE-RESISTANT ASSEMBLIES |
| 3.7 PATCHING |
| 3.8 WASTE MANAGEMENT |