Site Visit Questions & Responses – Set #3
FA6633-15-R-0002/QJKL 11-0014
Repair Door Heating Track, Bldg 821, Minneapolis ARS, MN
SET #3 – 29 April 2015
1. QUESTION: Is there any in floor heating in the existing hanger concrete?
RESPONSE: There is existing track heating at the doors that is to be removed per the drawings, but there is not floor heating anywhere else in the hangar.
2. QUESTION: Can we install temporary anchors in the existing floor to support the temporary tarp?
RESPONSE: Anchoring directly to the floor will not be allowed. Placing concrete jersey barriers on the hangar floor and anchoring to them will be allowed. Other forms of anchoring will also be considered as long as they do not damage the floor or interfere with operations.