RACEWAY
DESIGNATION
FROM TO
CONDUIT
CONDUCTORS/
MAX CURRENT LENGTH NOTES
SWITCHBOARD "F"
SWITCHBOARD "F"
INPUT XFMR
9315-225
CABLE TRAY
1-#1/0AWG G.
6-500kcmil 800A@208V
750KVA XFMR CABLE TRAY
1-#4/0AWG G.
16-500kcmil 1600A@208V
SWITCHBOARD "F" SBM CABLE TRAY 800A@208V
1-#1/0AWG G.
8-500kcmil
SWITCHBOARD "F" CABLE TRAY
INPUT XFMR
9315-225
1-#2AWG G.
3-350kcmil
800A@208V
INPUT XFMR
UPS
9315-225
CABLE TRAY
1-#1/0AWG G.
6-500kcmil
RECTIFIER INPUT
BYPASS INPUT800A@208V
1-#1/0AWG G.
8-500kcmil
CABLE TRAY
UPS
9315-225
SBM
SBM
UPS
9315-225
1-#1/0AWG G.
8-500kcmil
CABLE TRAY 800A@208V BYPASS INPUT
INPUT XFMR
UPS
9315-225
CABLE TRAY RECTIFIER INPUT
CABINET 2-B
J37 BATTERY
UPS
9315-225
CABLE TRAY
1-350kcmil(-)
1-350kcmil(+)
DC INPUT
CABINET 2-A
J37 BATTERY
UPS
9315-225
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET 1-A
J37 BATTERY
CABINET 1-B
J37 BATTERY
UPS
9315-225
UPS
9315-225
1-350kcmil(-)
1-350kcmil(+)
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY
CABLE TRAY
DC INPUT
DC INPUT
TIE CABINET
PARALLEL
1-#1/0AWG G.
8-500kcmil
CABLE TRAY 800A@208V
UPS
9315-225
UPS OUTPUT
TIE CABINET
PARALLEL
SBM CABLE TRAY
1-#1/0AWG G.
8-500kcmil 800A@208V
UPS
9315-225
TIE CABINET
PARALLEL
1-#1/0AWG G.
8-500kcmil
CABLE TRAY 800A@208V UPS OUTPUT
SBM
OUTPUT PANEL
208V CRITICAL
CABLE TRAY
1-#1/0AWG G.
8-500kcmil 800A@208V
OUTPUT PANEL
208V CRITICAL
WPAC CRITICAL
1-#1/0AWG G.
8-500kcmil
800A@208VCABLE TRAY
OUTPUT PANEL
208V CRITICAL
I/O CRITICAL
1-#1/0AWG G.
8-500kcmil
CABLE TRAY 800A@208V
40FT
40FT
25FT
30FT
25FT
40FT
40FT
60FT
35FT
30FT
50FT
40FT
30FT
30FT
35FT
30FT
30FT
25FT
300A@208V
300A@208V
300A@480VDC
1-#2AWG G.
3-350kcmil
300A@480VDC
300A@480VDC
300A@480VDC
1.
NOTES:
UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE TO BE TYPE THHN.
CABLE & CONDUIT SCHEDULE - POWER
E006
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
AS NOTED
CAGE CODE:
SCALE:
SIZE:
B
DATE OF ISSUE:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
OF:
SHT:
REV:
ORDER NUMBER:
CONTRACT NUMBER:
CUSTOM NUMBER:
A
B
C
D
ZONE REV
3 2
E
F
G
APPROVEDDESCRIPTION DATE
REVISIONS
H
OKINAWA, JAPAN
2004-07-30 C. NYCE
G. PARKS
G. PARKS A
A 2004-07-30INITIAL DESIGN GP
E006
CABLE & CONDUIT SCHEDULE - POWER
NO SCALE
310.17, 75° COLUMN,
CABLE TRAY CONDUCTOR AMPACITIES BASED ON 65% OF NEC TABLE 2.
SEPARATE REDUNDANT CABLES AS MUCH AS PRACTICABLE.3.
REFER TO SHEET E006 SHT. 2of2 FOR CONTINUATION OF THIS SCHEDULE.4.
22321
196930
Attachment 2 Drawings FA5270-17-Q-0007
RACEWAY
DESIGNATION
FROM TO
CONDUIT
CONDUCTORS/
MAX CURRENT LENGTH NOTES
SWITCHBOARD "G" CABLE TRAY
1-#1/0AWG G.
6-500kcmil
800A@480V750KVA XFMR
CABLE TRAY
MBM CABLE TRAY
DISCONNECT
VIA 800A FUSED
SWITCHBOARD "G"
UPS
9315-500
RECTIFIER INPUT
SWITCHBOARD "G"
800A@480V
800A@480V
1-#1/0AWG G.
6-500kcmil
1-#1/0AWG G.
6-500kcmil
EXTERNAL BYPASS
SWITCHBOARD "G" MBM
1-#1/0AWG G.
6-500kcmil
CABLE TRAY 800A@480V
MBM
UPS
9315-500
CABLE TRAY
CABLE TRAY
CABLE TRAY
1-#1/0AWG G.
6-500kcmil
800A@480V BYPASS INPUT
MBM
UPS
9315-500
1-#1/0AWG G.
6-500kcmil 800A@480V
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
CABINET
J47 BATTERY
UPS
9315-500
1-350kcmil(-)
1-350kcmil(+)
CABLE TRAY DC INPUT
UPS
9315-500
TIE CABINET
PARALLEL
1-#1/0AWG G.
8-500kcmil
4W FOR PARRALLEL OPERATION
UPS OUTPUT,
UPS
9315-500
TIE CABINET
PARRALLEL
1-#1/0AWG G.
8-500kcmil
TIE CABINET
PARALLEL
MBM
CABLE TRAY
CABLE TRAY
CABLE TRAY
CABLE TRAY
1-#1/0AWG G.
6-500kcmil
MBM
OUTPUT PANEL
480V CRITICAL
1-#1/0AWG G.
6-500kcmil
OUTPUT PANEL
480V CRITICAL
TRANSFORMER
75KVA
1-1/4" GRC
1-#6AWG G.
3-#1AWG
125A@480V
800A@480V
800A@480V
800A@480V
800A@480V
OUTSIDE OF BUILDING.
RUN RIGID CONDUIT ON
TRANSFORMER
75KVA
DISTRIBUTION PANEL
CRITICAL
2" FLEX
1-#2 AWG G.
4-#4/0 AWG
225A@208V
DISTRIBUTION PANEL
CRITICAL
PANEL TPE 1-1/4" EMT
1-#8AWG G.
4-#3AWG
100A@208V
WALL BELOW CEILING.
RUN EMT CONDUIT ON
WALL BELOW CEILING.
RUN EMT CONDUIT ON
WALL BELOW CEILING.
RUN EMT CONDUIT ON
PANEL TPJ 2" EMT
1-#6AWG G.
4-#3/0AWG
200A@208V
DISTRIBUTION PANEL
CRITICAL
DISTRIBUTION PANEL
CRITICAL
PANEL TPF 1" EMT
1-#10AWG G.
4-#6AWG
70A@208V
90FT
40FT
30FT
30FT
35FT
45FT
30FT
35FT
40FT
45FT
30FT
40FT
30FT
30FT
400FT
15FT
120FT
130FT
90FT
40FT
40FT
40FT
40FT
300A@480VDC
300A@480VDC
300A@480VDC
300A@480VDC
300A@480VDC
300A@480VDC
300A@480VDC
300A@480VDC
4W FOR PARRALLEL OPERATION
UPS OUTPUT,
1.
NOTES:
UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE TO BE TYPE THHN.
CABLE & CONDUIT SCHEDULE - POWER
E006
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
AS NOTED
CAGE CODE:
SCALE:
SIZE:
B
DATE OF ISSUE:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
OF:
SHT:
REV:
ORDER NUMBER:
CONTRACT NUMBER:
CUSTOM NUMBER:
A
B
C
D
ZONE REV
3 2
E
F
G
APPROVEDDESCRIPTION DATE
REVISIONS
G. PARKS A
A 2004-07-30INITIAL DESIGN GP
E006
CABLE & CONDUIT SCHEDULE - POWER
NO SCALE
310.17, 75° COLUMN,
CABLE TRAY CONDUCTOR AMPACITIES BASED ON 65% OF NEC TABLE 2.
SEPARATE REDUNDANT CABLES AS MUCH AS PRACTICABLE.3.
REFER TO SHEET E006 SHT. 1of2 FOR CONTINUATION OF THIS SCHEDULE.4.
FROM
UPS SYSTEM
9315-225
[C4]
[C3]
[C2]
[C1]
DESIGNATION
1-3/4"CBATTERY BREAKERS
1-1/2"C <24VDC
120VAC
TWISTED PAIR
4-#14 AWG
TWISTED PAIR
2-#14 AWG
20 FT
30 FT
DUAL RMP
TO
1-1/2"C
1-3/4"C
RACEWAY
<24VDC
<24VDC
VOLTAGE
NOMINAL
TWISTED PAIR
#14 AWG
TWISTED PAIRS
2-#14 AWG
CONDUCTORS
100 FT
400 FT
LENGTH
ESTIMATED
CABINETS AND MAIN BATTERY DISCONNECTS
SHUNT TRIPS & AUXILLARY CONTACTS FOR J47 BATTERY
CABLE TO TO RMP. ( 2 RUNS TO RMP).
RS485 COMMUNICATIONS - EACH MODULE REQUIRES A
CONTROL WIRINING
NOTES
PARALLEL TIE CABINET AUXILLARY CONTACTS
CABINET
PARALLEL TIE
MODULE
SYSTEM BYPASS
UPS SYSTEM
9315-225
UPS SYSTEM
9315-225
UPS SYSTEM
9315-225
[C5]
SBM
9315-225
CABINET
PARALLEL TIE
TWISTED PAIR
1-#14 AWG3/4"C <24VDC
[C6]
UPS SYSTEM
9315-500
TWISTED PAIR
2-#14 AWG
<24VDCDUAL RMP 1-3/4"C 400 FT CABLE TO TO RMP. ( 2 RUNS TO RMP).
RS485 COMMUNICATIONS - EACH MODULE REQUIRES A
[C7]
MODULE
MAINTENANCE BYPASS
1-1/2"C
TWISTED PAIR
#14 AWG
<24VDC 100 FT
CONTROL WIRINING
BATTERY BREAKERS[C8] 1-3/4"C
TWISTED PAIR
2-#14 AWG
120VAC 30 FT CABINETS AND MAIN BATTERY DISCONNECTS
SHUNT TRIPS & AUXILLARY CONTACTS FOR J47 BATTERY
[C9]
CABINET
PARALLEL TIE
TWISTED PAIR
4-#14 AWG1-1/2"C <24VDC 20 FT
PARALLEL TIE CABINET AUXILLARY CONTACTS
UPS SYSTEM
9315-500
UPS SYSTEM
9315-500
UPS SYSTEM
9315-500
[C10]
UPS SYSTEM
9315-500
CABINET
PARALLEL TIE 3/4"C
TWISTED PAIR
4-#14 AWG
<24VDC
CABLE & CONDUIT SCHEDULE - CONTROL
E007
E007
CABLE & CONDUIT SCHEDULE - CONTROL
NO SCALE
NONE.
NOTES:
1.
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
AS NOTED
CAGE CODE:
SCALE:
SIZE:
B
DATE OF ISSUE:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
OF:
SHT:
REV:
ORDER NUMBER:
CONTRACT NUMBER:
CUSTOM NUMBER:
A
B
C
D
ZONE REV
3 2
E
F
G
APPROVEDDESCRIPTION DATE
REVISIONS
G. PARKS A
A 2004-07-30INITIAL DESIGN GP