RACEWAY

DESIGNATION

FROM TO

CONDUIT

CONDUCTORS/

MAX CURRENT LENGTH NOTES

SWITCHBOARD "F"

SWITCHBOARD "F"

INPUT XFMR

9315-225

CABLE TRAY

1-#1/0AWG G.

6-500kcmil 800A@208V

750KVA XFMR CABLE TRAY

1-#4/0AWG G.

16-500kcmil 1600A@208V

SWITCHBOARD "F" SBM CABLE TRAY 800A@208V

1-#1/0AWG G.

8-500kcmil

SWITCHBOARD "F" CABLE TRAY

INPUT XFMR

9315-225

1-#2AWG G.

3-350kcmil

800A@208V

INPUT XFMR

UPS

9315-225

CABLE TRAY

1-#1/0AWG G.

6-500kcmil

RECTIFIER INPUT

BYPASS INPUT800A@208V

1-#1/0AWG G.

8-500kcmil

CABLE TRAY

UPS

9315-225

SBM

SBM

UPS

9315-225

1-#1/0AWG G.

8-500kcmil

CABLE TRAY 800A@208V BYPASS INPUT

INPUT XFMR

UPS

9315-225

CABLE TRAY RECTIFIER INPUT

CABINET 2-B

J37 BATTERY

UPS

9315-225

CABLE TRAY

1-350kcmil(-)

1-350kcmil(+)

DC INPUT

CABINET 2-A

J37 BATTERY

UPS

9315-225

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET 1-A

J37 BATTERY

CABINET 1-B

J37 BATTERY

UPS

9315-225

UPS

9315-225

1-350kcmil(-)

1-350kcmil(+)

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY

CABLE TRAY

DC INPUT

DC INPUT

TIE CABINET

PARALLEL

1-#1/0AWG G.

8-500kcmil

CABLE TRAY 800A@208V

UPS

9315-225

UPS OUTPUT

TIE CABINET

PARALLEL

SBM CABLE TRAY

1-#1/0AWG G.

8-500kcmil 800A@208V

UPS

9315-225

TIE CABINET

PARALLEL

1-#1/0AWG G.

8-500kcmil

CABLE TRAY 800A@208V UPS OUTPUT

SBM

OUTPUT PANEL

208V CRITICAL

CABLE TRAY

1-#1/0AWG G.

8-500kcmil 800A@208V

OUTPUT PANEL

208V CRITICAL

WPAC CRITICAL

1-#1/0AWG G.

8-500kcmil

800A@208VCABLE TRAY

OUTPUT PANEL

208V CRITICAL

I/O CRITICAL

1-#1/0AWG G.

8-500kcmil

CABLE TRAY 800A@208V

40FT

40FT

25FT

30FT

25FT

40FT

40FT

60FT

35FT

30FT

50FT

40FT

30FT

30FT

35FT

30FT

30FT

25FT

300A@208V

300A@208V

300A@480VDC

1-#2AWG G.

3-350kcmil

300A@480VDC

300A@480VDC

300A@480VDC

1.

NOTES:

UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE TO BE TYPE THHN.

CABLE & CONDUIT SCHEDULE - POWER

E006

A

B

C

D

7 6 5

E

F

G

H

8 7 6 5

RIGHTS" IN DFAR 252.227-7013

IN THE DEFINITION OF "LIMITED

THE RESTRICTIONS AS SET FORTH

THE GOVERNMENT IS SUBJECT TO

DUPLICATION OR DISCLOSURE BY

4 3 2

AS NOTED

CAGE CODE:

SCALE:

SIZE:

B

DATE OF ISSUE:

APPROVED BY:

DESIGNED BY:

DRAWN BY:

OF:

SHT:

REV:

ORDER NUMBER:

CONTRACT NUMBER:

CUSTOM NUMBER:

A

B

C

D

ZONE REV

3 2

E

F

G

APPROVEDDESCRIPTION DATE

REVISIONS

H

OKINAWA, JAPAN

2004-07-30 C. NYCE

G. PARKS

G. PARKS A

A 2004-07-30INITIAL DESIGN GP

E006

CABLE & CONDUIT SCHEDULE - POWER

NO SCALE

310.17, 75° COLUMN,

CABLE TRAY CONDUCTOR AMPACITIES BASED ON 65% OF NEC TABLE 2.

SEPARATE REDUNDANT CABLES AS MUCH AS PRACTICABLE.3.

REFER TO SHEET E006 SHT. 2of2 FOR CONTINUATION OF THIS SCHEDULE.4.

22321

196930

Attachment 2 Drawings FA5270-17-Q-0007

RACEWAY

DESIGNATION

FROM TO

CONDUIT

CONDUCTORS/

MAX CURRENT LENGTH NOTES

SWITCHBOARD "G" CABLE TRAY

1-#1/0AWG G.

6-500kcmil

800A@480V750KVA XFMR

CABLE TRAY

MBM CABLE TRAY

DISCONNECT

VIA 800A FUSED

SWITCHBOARD "G"

UPS

9315-500

RECTIFIER INPUT

SWITCHBOARD "G"

800A@480V

800A@480V

1-#1/0AWG G.

6-500kcmil

1-#1/0AWG G.

6-500kcmil

EXTERNAL BYPASS

SWITCHBOARD "G" MBM

1-#1/0AWG G.

6-500kcmil

CABLE TRAY 800A@480V

MBM

UPS

9315-500

CABLE TRAY

CABLE TRAY

CABLE TRAY

1-#1/0AWG G.

6-500kcmil

800A@480V BYPASS INPUT

MBM

UPS

9315-500

1-#1/0AWG G.

6-500kcmil 800A@480V

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

CABINET

J47 BATTERY

UPS

9315-500

1-350kcmil(-)

1-350kcmil(+)

CABLE TRAY DC INPUT

UPS

9315-500

TIE CABINET

PARALLEL

1-#1/0AWG G.

8-500kcmil

4W FOR PARRALLEL OPERATION

UPS OUTPUT,

UPS

9315-500

TIE CABINET

PARRALLEL

1-#1/0AWG G.

8-500kcmil

TIE CABINET

PARALLEL

MBM

CABLE TRAY

CABLE TRAY

CABLE TRAY

CABLE TRAY

1-#1/0AWG G.

6-500kcmil

MBM

OUTPUT PANEL

480V CRITICAL

1-#1/0AWG G.

6-500kcmil

OUTPUT PANEL

480V CRITICAL

TRANSFORMER

75KVA

1-1/4" GRC

1-#6AWG G.

3-#1AWG

125A@480V

800A@480V

800A@480V

800A@480V

800A@480V

OUTSIDE OF BUILDING.

RUN RIGID CONDUIT ON

TRANSFORMER

75KVA

DISTRIBUTION PANEL

CRITICAL

2" FLEX

1-#2 AWG G.

4-#4/0 AWG

225A@208V

DISTRIBUTION PANEL

CRITICAL

PANEL TPE 1-1/4" EMT

1-#8AWG G.

4-#3AWG

100A@208V

WALL BELOW CEILING.

RUN EMT CONDUIT ON

WALL BELOW CEILING.

RUN EMT CONDUIT ON

WALL BELOW CEILING.

RUN EMT CONDUIT ON

PANEL TPJ 2" EMT

1-#6AWG G.

4-#3/0AWG

200A@208V

DISTRIBUTION PANEL

CRITICAL

DISTRIBUTION PANEL

CRITICAL

PANEL TPF 1" EMT

1-#10AWG G.

4-#6AWG

70A@208V

90FT

40FT

30FT

30FT

35FT

45FT

30FT

35FT

40FT

45FT

30FT

40FT

30FT

30FT

400FT

15FT

120FT

130FT

90FT

40FT

40FT

40FT

40FT

300A@480VDC

300A@480VDC

300A@480VDC

300A@480VDC

300A@480VDC

300A@480VDC

300A@480VDC

300A@480VDC

4W FOR PARRALLEL OPERATION

UPS OUTPUT,

1.

NOTES:

UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE TO BE TYPE THHN.

CABLE & CONDUIT SCHEDULE - POWER

E006

A

B

C

D

7 6 5

E

F

G

H

8 7 6 5

RIGHTS" IN DFAR 252.227-7013

IN THE DEFINITION OF "LIMITED

THE RESTRICTIONS AS SET FORTH

THE GOVERNMENT IS SUBJECT TO

DUPLICATION OR DISCLOSURE BY

4 3 2

AS NOTED

CAGE CODE:

SCALE:

SIZE:

B

DATE OF ISSUE:

APPROVED BY:

DESIGNED BY:

DRAWN BY:

OF:

SHT:

REV:

ORDER NUMBER:

CONTRACT NUMBER:

CUSTOM NUMBER:

A

B

C

D

ZONE REV

3 2

E

F

G

APPROVEDDESCRIPTION DATE

REVISIONS

G. PARKS A

A 2004-07-30INITIAL DESIGN GP

E006

CABLE & CONDUIT SCHEDULE - POWER

NO SCALE

310.17, 75° COLUMN,

CABLE TRAY CONDUCTOR AMPACITIES BASED ON 65% OF NEC TABLE 2.

SEPARATE REDUNDANT CABLES AS MUCH AS PRACTICABLE.3.

REFER TO SHEET E006 SHT. 1of2 FOR CONTINUATION OF THIS SCHEDULE.4.

FROM

UPS SYSTEM

9315-225

[C4]

[C3]

[C2]

[C1]

DESIGNATION

1-3/4"CBATTERY BREAKERS

1-1/2"C <24VDC

120VAC

TWISTED PAIR

4-#14 AWG

TWISTED PAIR

2-#14 AWG

20 FT

30 FT

DUAL RMP

TO

1-1/2"C

1-3/4"C

RACEWAY

<24VDC

<24VDC

VOLTAGE

NOMINAL

TWISTED PAIR

#14 AWG

TWISTED PAIRS

2-#14 AWG

CONDUCTORS

100 FT

400 FT

LENGTH

ESTIMATED

CABINETS AND MAIN BATTERY DISCONNECTS

SHUNT TRIPS & AUXILLARY CONTACTS FOR J47 BATTERY

CABLE TO TO RMP. ( 2 RUNS TO RMP).

RS485 COMMUNICATIONS - EACH MODULE REQUIRES A

CONTROL WIRINING

NOTES

PARALLEL TIE CABINET AUXILLARY CONTACTS

CABINET

PARALLEL TIE

MODULE

SYSTEM BYPASS

UPS SYSTEM

9315-225

UPS SYSTEM

9315-225

UPS SYSTEM

9315-225

[C5]

SBM

9315-225

CABINET

PARALLEL TIE

TWISTED PAIR

1-#14 AWG3/4"C <24VDC

[C6]

UPS SYSTEM

9315-500

TWISTED PAIR

2-#14 AWG

<24VDCDUAL RMP 1-3/4"C 400 FT CABLE TO TO RMP. ( 2 RUNS TO RMP).

RS485 COMMUNICATIONS - EACH MODULE REQUIRES A

[C7]

MODULE

MAINTENANCE BYPASS

1-1/2"C

TWISTED PAIR

#14 AWG

<24VDC 100 FT

CONTROL WIRINING

BATTERY BREAKERS[C8] 1-3/4"C

TWISTED PAIR

2-#14 AWG

120VAC 30 FT CABINETS AND MAIN BATTERY DISCONNECTS

SHUNT TRIPS & AUXILLARY CONTACTS FOR J47 BATTERY

[C9]

CABINET

PARALLEL TIE

TWISTED PAIR

4-#14 AWG1-1/2"C <24VDC 20 FT

PARALLEL TIE CABINET AUXILLARY CONTACTS

UPS SYSTEM

9315-500

UPS SYSTEM

9315-500

UPS SYSTEM

9315-500

[C10]

UPS SYSTEM

9315-500

CABINET

PARALLEL TIE 3/4"C

TWISTED PAIR

4-#14 AWG

<24VDC

CABLE & CONDUIT SCHEDULE - CONTROL

E007

E007

CABLE & CONDUIT SCHEDULE - CONTROL

NO SCALE

NONE.

NOTES:

1.

A

B

C

D

7 6 5

E

F

G

H

8 7 6 5

RIGHTS" IN DFAR 252.227-7013

IN THE DEFINITION OF "LIMITED

THE RESTRICTIONS AS SET FORTH

THE GOVERNMENT IS SUBJECT TO

DUPLICATION OR DISCLOSURE BY

4 3 2

AS NOTED

CAGE CODE:

SCALE:

SIZE:

B

DATE OF ISSUE:

APPROVED BY:

DESIGNED BY:

DRAWN BY:

OF:

SHT:

REV:

ORDER NUMBER:

CONTRACT NUMBER:

CUSTOM NUMBER:

A

B

C

D

ZONE REV

3 2

E

F

G

APPROVEDDESCRIPTION DATE

REVISIONS

G. PARKS A

A 2004-07-30INITIAL DESIGN GP