NEW ONE LINE
TITLE SHEET: OKINAWA PROJECT
EXISTING ONE LINE
EXISTING EQUIPMENT LAYOUT
ELECTRICAL NOTES/SPECIFICATIONS/ABBREVIATIONS/SYMBOLS LIST
INDEX OF DRAWINGS
DESIGN DRAWING PACKAGE
OKINAWA, JAPAN
UPS INSTALLATION PROJECT
58TH SIGNAL BATTALION, BUILDING 103
8 7 6 5
CUSTOM NO.
ORDER NO.
E004 1
E003
E002
E001
A
A
A
A
COVER
SHT.
NO. OF
REV
A
8 7 6 5
4 3 2
DRAWING TITLE
4 3 2 1
CABLE AND CONDUIT LAYOUT - POWER
E005
E006
A
A2
1-
NEW EQUIPMENT LAYOUT
E007
A
1-
CABLE AND CONDUIT LAYOUT - CONTROL
Attachment 2 Drawings FA5270-17-Q-0007
SINGLE PHASE
THREE PHASE
4.
NEUTRAL - WHITE
LINE 1 - BLACK
120 VOLTS
GENERAL NOTES/SPECIFICATIONS
NEUTRAL - WHITE
PHASE C - BLUE
PHASE B - RED
PHASE A - BLACK
120/208/240 VOLTS
SAFETY SWITCHES
NEUTRAL - GRAY
PHASE C - ORANGE
PHASE B - BROWN
PHASE A - YELLOW
277/480 VOLTS
NEUTRAL - WHITE
LINE 2 - RED
LINE 1 - BLACK
120/208/240 VOLTS
PHASE CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
SHALL BE QUIET TYPE WITH AVERAGE SOUND LEVEL BELOW 45 DECIBELS.
WITH MAXIMUM TEMPERATURE RISE OF 80°C ABOVE 40°C AMBIENT. TRANSFORMER
COPPER WIRING, DRY TYPE, NEMA 1 ENCLOSURE, K-13 RATED, CLASS H INSULATION
CRITICAL TRANSFORMER SPECIFICATIONS:2.
DISCONNECT ALL UNGROUNDED CONDUCTORS.
SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE 380. SWITCHES SHALL
CORROSION, PITTING AND OXIDATION. WHEN USED FOR MOTORS, A SAFETY SWITCH
SPECIFIED. SWITCH CONTACTS SHALL BE SILVER-TUNGSTEN OR PLATED TO MINIMIZE
CARRYING PARTS SHALL BE OF HIGH-CONDUCTIVITY COPPER UNLESS OTHERWISE
REPLACEMENT OF ANY PART FROM THE FRONT OF THE SWITCH. ALL CURRENT-
HOUSING. ALL PARTS SHALL BE MOUNTED ON INSULATING BASES TO PERMIT
QUICK-BREAK TYPE, EXCEPT FOR GROUND LUGS WHICH SHALL BE BONDED TO THE
CURRENT RATINGS INDICATED ON THE DRAWINGS. SWITCHES SHALL BE QUICK-MAKE,
MOUNTED IN NEMA TYPE 3R ENCLOSURES. SWITCHES SHALL BE OF THE VOLTAGE AND
ENCLOSURES. SWITCHES INSTALLED OUTDOORS, OT IN DAMP LOCATIONS SHALL BE
OTHERWISE INDICATED. SWITCHES MOUNTED IN DRY LOCATIONS SHALL BE NEMA 1
1. SAFETY SWITCHES SHALL BE TYPE "HD", HEAVY DUTY, LOCKING TYPE UNLESS
HOA
HOUR
INCHES
HERTZ
KILOVOLT
HR
IN
HZ
KV
KCMIL
KW
kVA
HP HORSEPOWER
HAND-OFF-AUTOMATIC
THOUSAND CIRCULAR MILS
KILO VOLT-AMPERE
WATTS, IN THOUSANDS
METER
MOTOR
MECHANICAL
MILLIMETERS
m
M.E.
MD
MECH
MHP
mm.
MTR
POLE
NOT APPLICABLE
NOT TO SCALE
NUMBER
PANEL
PHASE
TYPICAL
N/A
NO.
P
NTS
PNL
PH
TYP
PR
MECHANICAL EQUIPMENT
MOTORIZED DAMPER
MOTOR HORSEPOWER
PHASE FAILURE RELAY
OPNG OPENING
WATTS
VOLT
TRANSFORMER
WIRE
UPS
W
V
XFMR
w
UNINTERRUPTIBLE POWER SUPPLY
GENERAL:
CONDUCTORS:
3.
2.
1.
M
EP3-10
CONDUIT CONCEALED OR UNDERGROUND
HOME RUN-DESTINATION SHOWN
MOTOR CONNECTION
PANELBOARD
W
T
CONTACT - NORMALLY CLOSED
CONTACT - NORMALLY OPEN
THERMOSTAT
CONDUIT BODY
CONDUIT TURNING UP
CONDUIT TURNING DOWN
HORIZONTAL RUN OF WIRING IN WIREWAY
NA
100 NON
G
ATS
AUTOMATIC TRANSFER SWITCH
GENERATOR
SHIELDED TRANSFORMER
TRANSFORMER
GROUND, GROUNDING ELECTRODE
ST
G GROUND CONDUCTORS
FUSE, CURRENT RATING AND FUSE TYPE INDICATED
SWITCH SINGLE-THROW, CURRENT RATING INDICATED
CIRCUIT BREAKER, NON-AUTOMATIC, SIZE INDICATED
CIRCUIT BREAKER, SOLID STATE TRIP, SIZE INDICATED
CIRCUIT BREAKER, THERMAL MAGNETIC, SIZE INDICATED
DISCONNECT SWITCH, FUSE AND FRAME SIZE INDICATED
EXPOSED CONDUIT AND CONDUCTORS, CONCEALED IN CEILING
SYMBOLS LIST
AMPEREA, AMP
TRIP (AMPS)
ACU
A.F.F.
AF
ARCH
AT
AS
A.F.G.
A/C
SENSOR SIZE (AMPS)
ARCHITECT/ARCHITECTURAL
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
AMPERE FRAME, AMPERE FUSE
AIR-CONDITIONING UNITS
AIR-CONDITIONING UNIT
CONCRETE
CIRCUIT BREAKER
CONDUIT
DOWN
DISCONNECT
CONTROL RELAY
C
CONC
CB
CT
CR
DN
DISC
EXHAUST FAN
DRAWING
EXISTING
ELEC
DWG
E/G
EF
EPO
EUH
EXIST
EWH
EMERGENCY POWER OFF
ELECTRIC WALL HEATER
ELECTRIC UNIT HEATER
ENGINE GENERATOR, EMERGENCY GENERATOR
ELECTRIC, ELECTRICAL
CURRENT TRANSFORMER
ATS AUTOMATIC TRANSFER SWITCH
FLOOR
FULL LOAD AMPS
GROUND
FEET
FFL
FLR
FLA
GFE
G, GND, GR
FT
GOVERNMENT FURNISHED EQUIPMENT
FINISHED FLOOR LINE
J
SA
T
X
TERMINAL JUNCTION BOX
GROUND ROD ACCESS, HAND HOLE
GROUND ROD
CONNECTION POINT TO EQUIPMENT
COMBINATION MOTOR STARTER, MAGNETIC
SURGE ARRESTOR
TRANSFORMER
JUNCTION BOX
TERMINAL JUNCTION BOX
PROPOSED WIRING
INSTALLED WIRING AND TERMINATION OR CONNECTION OF
POINT OF DISCONNECTION OF EXISTING OR PREVIOUSLY
REQUIREMENTS FOR FACILITIES", DATED 8/28/90.
"LIGHTNING PROTECTION GROUNDING, GROUNDING, BONDING AND SHIELDING
8. ALL EQUIPMENT GROUNDING SHALL COMPLY WITH FAA SPECIFICATION FAA-STD-019a, "ELECTRICAL WORK, INTERIOR", DATED 1/25/91.
7. ALL ELECTRICAL WORK SHALL COMPLY WITH FAA SPECIFICATION FAA-C-1217e, RECEPTACLES AND LIGHTING FIXTURES.
6. PROVIDE CONDUITS, FITTINGS, PULLBOXES, JUNCTION BOXES, CABLE, CONTROL WIRING
BY MANUFACTURER OF THE BASE UNIT.
RECOMMENDATION. CONTROLS AND ACCESSORIES FOR EQUIPMENT SHALL BE PROVIDED
5. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S
4. ARRANGE FOR INSPECTIONS BY LOCAL AUTHORITIES HAVING JURISDICTION.
HAS BEEN RESOLVED.
IMMEDIATELY AND AFFECTED WORK SHALL NOT BE INSTALLED UNTIL THE CONFLICT
MAJOR CONFLICTS ARE APPARENT, THE RESIDENT ENGINEER SHALL BE ADVISED
DEVIATIONS FROM THE PLANS MAY BE MADE TO AVOID MINOR CONFLICTS. WHEN
WORK WITH EXISTING CONDITIONS AND THE WORK OF OTHER TRADES. MINOR
3. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ELECTRICAL
SUCH ENDS.
ELECTRICAL SYSTEMS. PROVIDE ALL LABOR AND MATERIALS NECESSARY TO ACHIEVE
2. THE INTENT OF THE DRAWINGS IS TO PROVIDE COMPLETE AND PROPERLY FUNCTIONING
HAVING JURISDICTION OVER THE FACILITY.
FEDERAL AVIATION ADMINISTRATION AND OTHER BUILDING OFFICIALS
EDITION OF THE NATIONAL ELECTRIC CODE, STANDARDS, DESIGN CRITERIA OF THE
1. ALL WORK IN THIS PROJECT SHALL BE IN ACCORDANCE WITH THE MOST CURRENT
MINIMUM CONTROL WIRE SIZE SHALL BE NO. 14 AWG.
MINIMUM BRANCH CIRCUIT CONDUCTOR SIZE SHALL BE NO. 12 AWG.
UNLESS OTHERWISE INDICATED, SHALL BE COPPER TYPE THHN.
ABBREVIATIONS
UNLESS OTHERWISE NOTED
MOUNTING HEIGHT +38" A.F.F.,
SINGLE POLE TOGGLE SWITCH,
PLASTER RING AND PULL STRING TO THE CEILING PLENUM.
+18" A.F.F. UNLESS OTHERWISE NOTED. PROVIDE 1" C WITH
DUPLEX COMMUNICATIONS WALL OUTLET, (DATA & TELEPHONE),
DRAWING NUMBER WHERE SHOWN
DRAWING NUMBER WHERE TAKEN
B
A
C
S
(NUMERAL) DESIGNATION
SECTION (LETTER) OR DETAIL
BATTERY PACK
TWINLAMP EMERGENCY
OVERLOAD
[C0] CONTROL
POWER
WIRING CALLOUT:
20A, 125V, 2P, 3W +18" A.F.F.
DUPLEX RECEPTACLE OUTLET
SURFACE MOUNTED
4 FT. INDUSTRIAL FIXTURE
ELECTRICAL NOTES/SPECIFICATIONS/ABBREVIATIONS/SYMBOLS LIST
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
AS NOTED
CAGE CODE:
SCALE:
DATE OF ISSUE:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
OF:
SHT:
REV:
ORDER NUMBER:
CONTRACT NUMBER:
CUSTOM NUMBER:
A
B
C
D
ZONE REV
3 2
E
F
G
APPROVEDDESCRIPTION DATE
REVISIONS
H
OKINAWA, JAPANC. NYCE
G. PARKS
G. PARKS A
A INITIAL DESIGN
LOADS
CRITICAL
WP AC
800AF
800AT
LVR
GE
800AT
800AF
CRITICAL
IO
800AF
800AT
NC
208/120V
XFMR
300KVA
DUMMY
BLDG 103
NON-CRITICAL
NO
700AT
1000AF
3P 1000A
NC
FA1
1600A 1000AT
1600AF
NC
NC
NO
1600A
FA2 FB2
1600A
NO
3200A
3200A
FAM
3200A
FBM
FB3
1600A800A
800A
NO
BLDG 103
RM NO.163
BUSWAY
UPS
NO.1
REMOTE
SWITCH
SWITCH
REMOTE
NO.2
UPS
J37
VRLA
BATTERY 2-B
J37
VRLA
BATTERY 2-A
9315-225
UPS-1
RECTIFIER
INVERTER
F63
F62
F61
FUSING
BATTERY
CB1
FILTER
INPUT
Y
D
(K3)
CONTACTOR
OUTPUT
SWITCH
STATIC
(K4)
CONTACTOR
BYPASS
TRANSFORMER
ISOLATION
OUTPUT
MODULE
BYPASS
MAINTENANCE
800A
800A
800A
800A
KK
J37
VRLA
BATTERY 1-B
J37
VRLA
BATTERY 1-A (K3)
CONTACTOR
OUTPUT
TRANSFORMER
ISOLATION
OUTPUT
FUSING
BATTERY
INVERTER
RECTIFIER
SWITCH
STATIC
(K4)
CONTACTOR
BYPASS
CB1
FILTER
INPUT
F63
F62
F61
9315-225
POWERWARE
UPS-2
XFMR
INPUT
XFMR
INPUT
208V/480
480/208V
SBM
TIE CABINET
PMC
3000A
SWITCHBOARD F
208V/480
B
A
C
D
7 6 5
E
F
G
H
8 7 6 5
OKINAWA PROPOSAL
22321
196930
2004 KH
DR
GREG PARKS A
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
APPROVED BY:
DESIGNED BY:
DRAWN BY:
AS NOTED
DATE OF ISSUE:
SCALE:
CAGE CODE:
SIZE:
B
B
OF:
SHT:CUSTOM NUMBER:ORDER NUMBER:
EXISTING ONE LINE DEMO DIAGRAM
E-002
CONTRACT NUMBER: REV:
A
C
D
4 3
REVZONE
E
F
G
APPROVED
REVISIONS
DESCRIPTION DATE
H
DISCONNECT AND REMOVE
TO BE REMOVED.
CROSS-HATCH INDICATES EQUIPMENT OR FEEDERS
NOTES:
1.
A DRAWING RELEASE 7/26/04 GP
EYEWASH
STATION
EYEWASH
GFI
CONTROL PNL
BATT RM VENT
BATT CAB 2
UPS2
BATT CAB 1
UPS2
BATT CAB 2
UPS1
BATT CAB 1
UPS1
DISC.
BATT.
600A
J-BOX)
(OVER
"MB"
PANEL
DOUBLE DOOR
AND
ROLL-UP
RAMP
"LH"
PANEL
"TRENCH"
DISC.
BATT.
600A
"PMC""SBM"
STEPS
A
V
F
G E
K
D
B
S W
B D
LOAD
DUMMY
MTS
SW
UPS2
REM.
SW
REMOTE
UPS1
X F
M R
K V
A
C A
B
IN
E T
REGULATOR
VOLTAGE
X F
M R
IN
P
U T
X F
M R
IN
P
U T
12x12 J-BOX
RAF CONTROLS
WESTINGHOUSE/HONEYWELL
WIREWAY
BOX
JUNCTION
RELOCATED BY SITE.
THERMOSTATS TO BE
600A BATT. DISCONNECTS.)
BY SITE. (TEMPORARILY SUPPORT
8" PARTITION TO BE REMOVED
CONCRETE COVERED TRENCH.
CONDUIT STUBS.
SITE TO CUT AND PATCH
BE REMOVED BY SITE.
EQUIPMENT PAD TO
SITE TO REMOVE METAL DOORS.
REMOVED BY SITE.
& VOLTAGE REGULATOR TO BE
EQUIPMENT PAD, SWGR,XFMR
TRENCH WITH CONCRETE.
SITE TO FILL/COVER
W E
N
CRITICAL
I O
CRITICAL
WP
RM 163
RM 172
RM 162
REMOVE
LEGEND:
RELOCATE
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
OKINAWA PROPOSAL
22321
196930
2004 KH
DR
G PARKS A
4 3 2
DRAWN BY:
DESIGNED BY:
APPROVED BY:
DATE OF ISSUE:
AS NOTED
CAGE CODE:
B
SIZE:
SCALE:
EXISTING EQUIPMENT LAYOUT
E003
CONTRACT NUMBER:
ORDER NUMBER: CUSTOM NUMBER:
REV:
OF:
SHT:
A
B
C
D
4 3
REVZONE
E
F
G
REVISIONS
DESCRIPTION
DATE APPROVED
H
A GPDEMO DRAWING 7/30/2004
E003
EXISTING EQUIPMENT LAYOUT
3/16"=1'-0"
CRITICAL
WPAC
800AF
800AT 800AT
800AF
CRITICAL
IO
NC
208/120V
BLDG 103
NON-CRITICAL
NC
700AT
1000AF
3P 1000A
NC
FA1
1600A 1600AT
1600AF
NC
NC
NO
1600A
FA2 FB2
1600A
NO
3200A
3200A
FAM
3200A
FBM
800AT
800AF
BLDG 103
RM NO.163
J37
VRLA
BATTERY 2-B
J37
VRLA
BATTERY 2-A
9315-225
UPS
RECTIFIER
INVERTER
F63
F62
F61
FUSING
FILTER
INPUT
Y
D
(K3)
CONTACTOR
OUTPUT
SWITCH
STATIC
(K4)
CONTACTOR
BYPASS
TRANSFORMER
ISOLATION
OUTPUT
MODULE
BYPASS
SYSTEM
800A
800A
800A
800A
KK
J37
VRLA
BATTERY 1-B
J37
VRLA
BATTERY 1-A (K3)
CONTACTOR
OUTPUT
TRANSFORMER
ISOLATION
OUTPUT
FUSING
BATTERY
INVERTER
RECTIFIER
SWITCH
STATIC
(K4)
CONTACTOR
BYPASS
CB1
FILTER
INPUT
F63
F62
F61
9315-225
UPS
XFMR
INPUT
XFMR
INPUT
SBM
TIE CABINET
F63
F62
F61
SWITCH
STATIC
800A
800A (K4)
CONTACTOR
BYPASS
MODULE
BYPASS
MAINTENANCE
480/480V
9315-500
UPS
TRANSFORMER
ISOLATION
OUTPUT
(K3)
CONTACTOR
OUTPUT
CB1
INVERTER
FUSING
BATTERY
RECTIFIER
FILTER
INPUT
KK
Y
D
480/480V
(K3)
CONTACTOR
OUTPUT
9315-500
UPS
FUSING
TRANSFORMER
ISOLATION
OUTPUT
INVERTER SWITCH
STATIC
(K4)
CONTACTOR
BYPASS
RECTIFIER
FILTER
INPUT
F63
F62
F61
J47
J47
J47
BATTERY
J47
BATTERY
J47
BATTERY
J47
BATTERY
J47
BATTERY
J47
BATTERY
NC NC
800A
NO
1600A
1600A
NC
1600A
NO
NC
RM NO.163
BLDG 103
TIE CABINET
NEMA-1
208/120-480/277V
750KVA
SPARESPARE
400A
800A
400A
800A
SPARE
800A
400A
K1 K1
K1
K2 K2
800A 800A 800A
1600A
1600A
800A
800A
800A
800A 800A
800A
NC
FUTURE
750KVA
XFMR
1600A
1200A
NC
1200A
1600A
NC SPARE
400A
800A
SPARE
400A400A
SPARE
800A 800A
NC
800A
800A
70a
175a
70a
175a
225a 225a
125a 125a
125a 125a
45a
45a
-a
45a
70a
-a
OUTPUT PANEL
100a
100a
225a
800A/208V
-a -a
208V CRITICAL
100a
100a
225a
400a
400a
NOTE 1
FUTURE
750KVA
XFMR
XFMR
75KVA
200a200a
100a
70a
100a
70a
-a-a
EXISTING
-a-a
-a -a
-a
-a
CRITICAL
DIST PANEL
225AMP/208/120V
75KVA
480-208/120V
SWITCHBOARD F
1600A
FA3
NC
K-13
SPACE SPACE
SWITCHBOARD G
PARALLEL
EXISTING
[C3]
Y
D
[C4]
[C4]
[C9] [C9]
[C3]
[C]
[C8]
Y
D
Y
Y
MODULE
BYPASS
SYSTEM
800A
800A
K3 K3K4 K4
104102101
[C2]
[C2]
[C1]
[C1]
PARALLEL
[C5]
141140139
TPE PANEL TPF PANELTPJ PANEL
EXISTING EXISTING
Y
D
133 134135
[C10]
127126125
[C7] [C7]
[C6]
131 132
DUAL RMP
DUAL RMP
OUTPUT PANEL
480V CRITICAL
800A/480V
B
A
C
D
7 6 5
E
F
G
H
8 7 6 5
OKINAWA PROPOSAL
22321
196930
2004-07-30 KH
DR
GPARKS A
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
APPROVED BY:
DESIGNED BY:
DRAWN BY:
AS NOTED
DATE OF ISSUE:
SCALE:
CAGE CODE:
SIZE:
B
B
OF:
SHT:CUSTOM NUMBER:ORDER NUMBER:
NEW ONE LINE DIAGRAM
E004
CONTRACT NUMBER: REV:
A
C
D
4 3
REVZONE
E
F
G
APPROVED
REVISIONS
DESCRIPTION DATE
H
NOTES:
1600A TRIP UNIT.
REPLACE 1000A TRIP UNIT WITH1.
IN BOLD.
NEW OR RELOCATED EQUIPMENT SHOWN2.
GROUND ALL TRANSFORMERS.3.
REV DESCRIPTION DATE APPROVED
EYEWASH
STATION
EYEWASH
GFI
CONTROL PNL
BATT RM VENT
J-BOX)
(OVER
"MB"
PANEL
DOUBLE DOOR
AND
ROLL-UP
RAMP
"LH"
PANEL
"PMC"
"SBM"
STEPS
V
F
G E
K
D
B
W
B D
9315 225XFMR
INPUT
W E
S
N
CRITICAL
I O
CRITICAL
WP
CAB
BATT
CAB
BATT
PANEL
OUTPUT
CRITICAL
208/120V
DISC.
FUSED
800A
480V
XFMR
750KVA
PANEL
OUTPUT
CRITICAL
480V
V
G
S W
B D
C
H
CAB
BATT
J47
9315 500
CAB
BATT
J47
CAB
BATT
J47
CAB
BATT
J47
CAB
TIE
9315 500
CAB
BATT
J47
CAB
BATT
J47
CAB
BATT
J47
CAB
BATT
J47 MBM
XFMR
INPUT CAB
BATT
9315 225
CAB
BATT
U P
U P
S
A
B
C
D
7 6 5
E
F
G
H
8 7 6 5
RIGHTS" IN DFAR 252.227-7013
IN THE DEFINITION OF "LIMITED
THE RESTRICTIONS AS SET FORTH
THE GOVERNMENT IS SUBJECT TO
DUPLICATION OR DISCLOSURE BY
4 3 2
AS NOTED
CAGE CODE:
SCALE:
SIZE:
B
DATE OF ISSUE:
APPROVED BY:
DESIGNED BY:
DRAWN BY:
OF:
SHT:
REV:
ORDER NUMBER:
CONTRACT NUMBER:
CUSTOM NUMBER:
A
B
C
D
ZONE REV
3 2
E
F
G
APPROVEDDESCRIPTION DATE
REVISIONS
H
OKINAWA, JAPAN
2004-07-30 C. NYCE
G. PARKS
G. PARKS A
A 2004-07-30INITIAL DESIGN GP
22321
196930
NEW EQUIPMENT LAYOUT
E005
E005
NEW EQUIPMENT LAYOUT
3/16"=1'-0"
File details come from the government source that posted it. Updated .