SOUNDPROOF DIESEL GENERATING SETS
GENERAL CONSTRUCTION
The DCA Series generators are complete, stand alone generating sets. All models consist of a Denyo alternator which is directly coupled to a diesel engine. The alternator and engine are set on a common skid base. Special vibration isolators are used to minimise vibrations during operation.
The generator and electrical components are fully enclosed in a solid-steel,weatherproof bonnet.
Noise suppression is achieved using highly effective sound insulating materials.
DENYO POWER GENERATORS are partners of our civil life Denyo power generators are capable of generat-ing power in various situations where public power supply is not available. They contribute to build infrastructure of society and are highly appreciated by customers all over the world.In a variety of situa-tions like civil engineering works and construction works to build infrastructure of our society.
Denyo engine power generators are capable of pro-viding power at various sites where power is required like civil work and construction sites as well as are also employed in various facilities as emergency power source for critical equipment like medical equipment in hospital, bank online system and traffic signals etc.
As the power source in the areawhere electricity is unavaiable.
As the power source in the construction site. As the Emergency power source in the hospital.
The Denyo generating system guarantees the following levels of performance:
TEMPERATURE RISE : 100℃ tempera-ture rise at 40℃ ambient(JEC2130).
INSULATION : ClassF(JEC2130).
VOLTAGE REGULATION : Within±0.5% ( except DCA-400SP )
FREQUENCY REGULATION: Within 5.0% through noload to full-load.
VOLTAGE WAVEFORM : Deviation Factor of open-circuit terminal voltage does not exceed 0.06.
Telephone Influence Factor(TIF) is less than 50.
ELECTROMAGNETIC INTERFERENCE
LEVEL : Attenuated to meet most com-mercial requirements.
INSULATION RESISTANCE : Higher than 3 Me ga- ohms, measu re d be t we en a rmature wind ings and ear th, f ie ld windings and earth, field control circuit and earth.
●The innovative excitation system* fitted on all models, in conjunction with the AVR and advanced brushless generator, p rov ides fas t vo l tage regu la t ion in response to load variations, enabling use soon after start up. This system provides output stability during load variations.
*U.S.Patent No.4268788
●Synchronous brushless alternator for minimal wear.
●Designed to function in all climatic conditions.
●Easy starting and quick response.
●Utilising highly reliable diesel engines with low fuel consumption, manufactured by Japan's leading engine manufacturers.
●Uninterrupted generator operation for up to 12 hours under 75% load.
TRUE HEAVY-DUTY PERFORMANCE
For a particular job, you may need that extra power from your generator. With the DCA Series, the standby power rating(110% or 105% load except DCA- 610SPM) can be used continuously for 1 hour in ever y 8 hours of cont inuous operation. This extra power per for-mance of Denyo generators means you c a n g e t t h e j o b d o n e , w i t h o u t t h e inconvenience of using another generator.
PERFORMANCE
FEATURES
ECONOMICAL
PERFORMANCE
UNSURPASSED
FLEXIBILITY
HIGH-PERFORMANCE
●Will safely power the most sensitive loads, such as thyristors, invertors and computer systems, without the risk of damage to these loads, thanks to the high level electr ical character ist ics of the generator's output.
To meet today's varying needs successfully, your equipment must be as flexible as you are.
The Denyo DCA Series gene-rator range provides you with the flexibility to get the job done simply and economically, without any delays.
PARALLEL OPERATION FEATURE
( except for DCA-100 and below ) From time to time, at a construction site, mine site or in other situations, a large temporary power supply is required for a particular job. To meet this requirement Denyo's DCA Series generators incorpo-rate a built- in parallel operation drive system, allowing you to create a large-capacity generating plant on-site, without the need to procure any other equipment.
DUAL VOLTAGE SYSTEM
(optional for DCA-25USI2, 45ESH, 45USI2, 60ESH, 60USH)
Fo r c o m p a n i e s t h a t o p e r a te i n te r-nationally or have motors that require power at dif ferent voltages, a dif ferent generator is usually required for each voltage setting. However, the DCA Series generators are equipped with a dual voltage system, so one generator can be used to power motors wi th d i f fe rent voltage settings. An extremely convenient feature.
ALL MODELS CAN RUN AT 50Hz/60Hz Simply adjust the engine speed on the control panel to use a DCA Series gene-rator at either 50 Hz or 60 Hz.
EXTREMELY QUIET OPERATION
In urban areas and at the worksite, there is an ever increasing demand for reduced noise pol lut ion. In response to these c o n c e r n s , D e n y o h a s p i o n e e r e d a soundproof and super soundproof range of generators. The DCA Series generators are extremely quiet when operating at full load, even though all soundproof models are c o m p a c t l y d e s i g n e d . C h e c k t h e specifications for the sound level of each model.
DENYO GENERATORS:
DESIGNED TO BE
TOTALLY
USER-FRIENDLY
FULLY APPOINTED CONTROL PANELS
FOR EASE OF USE AND MONITORING GENERATOR PERFORMANCE.
①Tachometer ②AC Ammeter ③Voltmeter ④Pilot Lamp ⑤Panel Light ⑥Circuit Breaker ⑦Panel Light Switch ⑧Voltage Regulator ⑨ Frequency Meter
①
②③④⑥
⑩⑨
⑫ ⑬
⑰ ⑮
⑭
⑩Throttle Lever ⑪Preheat Lamp ⑫Emergency Stop Button ⑬ Starter Switch ⑭ Frequency Adjust Screw ⑮Warning Lamp(Oil Pressure) ⑯Warning Lamp(Water Temperature) ⑰Fuel Gauge
MAINTENANCE MADE SIMPLER
●Al l da i ly maintenance requi rements can be performed from one side of the machine. The large doors gives you full acces to the engine.
●External drain plugs for oil, fuel and water are fitted for convenience in performing routine maintenance.
● Large fuel gauge is fitted for simple viewing.
●For major engine overhauls, the bonnet can be simply unbolted, which allows full access to the engine.
TRANSPORTABILITY
●The new designs of the DCA Series range have achieved significant size and weight reductions over previously producted models, through improve-ments in coupling techniques and alternator design.
●The sturdy weatherproof s tee l bonnet on a heavy-duty steel skid base allows easy handling by a forklift.
●The balance point lifting hook (lug) fitted on the roof of each machine facilitates easy transportation using a crane.
●Al l mode ls a re modu la r des igned, so tha t generators can be stacked, thereby making the best use of your valuable storage area.
Provision of Various Protective Devices and Warning Lamps ●A circuit breaker is provided to protect the generator from shorting of the load circuit or an overload.
●An emergency stop device is provided to automatically detect an engine malfunction and shut down the unit, as well as a warning lamp.
Item
Operation Display
Low oil pressure
High water temperature
Over-current
Electric leakage
Insufficient charging
Low fuel level
Plugging of air cleaner
Rise in fuel filter level
Over-speed
Engine Stop
Load Interrupt
Malfunction Display
—(○*5)
*1
*2
*3
*4
*1 Only for 13 to 35. (Engine stopped/malfunction display not provided for 25ESI,45 – 150ES, US series.) *2 Excluding 13 – 20LS,25ESK.
*3 Only for 25ESI,45ESI,25USI2,45USI2.
*4 Only for 60ESI2,600SPK,800SPK,800SPM,1100SPM,1100SPC.
*5 Only for 60ESI2
O: Operates –:Does not operate
⑦ ⑧⑤
⑪
⑯
DCA-13LSK
DCA-20LSK DCA-25ESI DCA-45ESI
DCA-15LSK
SPECIFICATION TABLE(13kVA~45kVA CLASS SOUNDPROOF TYPE)
*1 Rated Voltage Classification
( ) indicates options.
50Hz 190~220V 190~220V 380~440V 380~440V 190~220V
(380~440V)
60Hz 200~240V 190~240V 380~480V 380~480V 200~240V
(380~480V)
10.5
13.7
10.5 11.5
12.5 13.8
16.5
18.7
27.5
27.5
38.9
47.3
31.5
36.75
DCA-13LSK DCA-13LSY
Kubota D1403-K3A
Inlined, Swirl Chambered
3-80×92.4 1.393
5.6 6.4
13.7/1500 10.2/1500
2.4
16.9/1800 12.4/1800
2.9
Yanmar
3TNV84-G
Inlined, Direct Injected
3-84×90 1.496
6.7 3.9
15.3/1500 11.3/1500
2.1
18.3/1800 13.5/1800
2.6
Isuzu
BB-4JG1T
4-95.4×107 3.059
10.9
46.5/1500 34.2/1500
6.3
56/1800 41.2/1800
7.8
Isuzu
AA-4LE2
Inlined, Direct Injected
4-85×96 2.179
8.5 6.6
26/1500 19.1/1500
3.3
32/1800 23.5/1800
4.2
0.8(Lagging) Within ±0.5
Brushless,Rotating Exciter(With A.V.R.)
②Dual Voltage①or③ Single Voltage
DCA-45ESIDCA-25ESIDCA-25ESKDCA-20LSK DCA-35SPKDCA-15LSK
Kubota
V2203-KB
4-87×92.4 2.197
7.6 7.9
ASTM No. 2 Diesel Fuel or Equivalent
Kubota D1703-K3A
3-87×92.4
1.647
5.6 6.4
Kubota V2203-K3A
4-87×92.4 2.197
7.6 7.9
Inlined,Swirl Chambered
Kubota
V3300-EB
Inlined, Swirl Chambered
4-98×110 3.318
13.2 10.5
16.9/1500 12.4/1500
2.8
20/1800 14.7/1800
3.4
23.1/1500 17.0/1500
3.6
27.1/1800 19.9/1800
4.3
58 61 61 62 60 63 61 64 6260636062 64 60 64
38.5/1500 28.3/1500
5.8
44.1/1800 32.4/1800
6.9
25/1500 18.4/1500
3.9
32.2/1800 23.71800
4.9
②Dual Voltage
*2 Fuel consumption is based on operation at 75% load.
*3 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.
*4 Depending on location and area,output voltage may differ from values listed in catalog.
②
③
④
①
①or③ Single Voltage
Class HClass F
Inlined,Direct Injected, Turbocharged
95D31R×1
3-Phase,4-Wire
*4
80D26R×1
SPECIFICATION TABLE(60kVA~125kVA CLASS SOUNDPROOF TYPE)
68.3
78.8
DCA-60ESI2 DCA-75SPI DCA-100ESI DCA-125ESM DCA-125SPK3
3-Phase,4-Wire
0.8(Lagging)
Within ±0.5
Brushless,Rotating Exciter(With A.V.R.)
Komatsu
SA6D102E-1-A
6-102×120
5.880
23.9
133/1500
97.8/1500
15.5
157/1800
115.5/1800
20.1
ASTM No. 2 Diesel Fuel or Equivalent
Isuzu
A-6BG1
Inlined,Direct Injected
6-105×125
6.494
65/1500
47.9/1500
8.7
13.2
15.4
120E41R×1
77/1800
57.1/1800
11.0
80/1500
58.8/1500
10.8
93/1800
68.4/1800
12.5
Isuzu
DD-6BG1T
Inlined,Direct Injected, Turbocharged
6-105×125
6.494
19.3
22.9
95E41R×2
22.4
22.0
95D31R×2
100/1500
73.6/1500
13.5
124/1800
91.3/1800
17.4
Mitsubishi
6D16-TLE2D
6-118×115
7.540
26.3
145/1500
107/1500
16.5
166/1800
122/1800
20.7
Inlined,Direct Injected, Turbocharged, Aftercooled
61 64 61 63 59 61 61 66 63 66
Hino
W04D-TG
4-104×118
4.009
16.5
12.2
80D26R×2
78/1800
57.4/1800
10.6
66/1500
48.5/1500
8.8
④Single Voltage (Dual Voltage is an option)
DCA-60ESH
Inlined,Direct Injected, Turbocharged
50Hz 190~220V 380~440V 190~220V
(380~440V)
60Hz 190~240V 380~480V 200~240V
(380~480V)
②
④
*1 Rated Voltage Classification
( ) indicates options.
*2 Fuel consumption is based on operation at 75% load.
*3 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.
*4 Depending on location and area,output voltage may differ from values listed in catalog.
DCA-150ESK
DCA-100ESI
DCA-125SPK3
Class H
Isuzu
BB-4BG1T
4-105×125
4.329
Class F
*4
Class F
②Dual Voltage
DCA-60ESI2
95E41R×2
SPECIFICATION TABLE(150kVA~500kVA CLASS SOUNDPROOF TYPE)
*1 Rated Voltage Classification
( ) indicates options.
50Hz 190~220V 380~440V
60Hz 190~240V 380~480V
*2 Fuel consumption is based on operation at 75% load.
*3 Shown unit lengths are with visor.(without visor) *4 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.
*5 Depending on location and area,output voltage may differ from values listed in catalog.②
5480(5000)*3
Within ±1.0
3-Phase,4-Wire
②Dual Voltage
0.8(Lagging)
Brushless,Rotating Exciter(With A.V.R.)
Class F
Within ±0.5
DCA-500SPK
Within ±0.5
DCA-220ESM DCA-220SPK3 DCA-300SPK3
ASTM No. 2 Diesel Fuel or Equivalent
Inlined,Direct Injected,Turbocharged,Aftercooled
Komatsu
SA6D170-B
6-170×170
23.150
92.5
520/1500
382/1500
69.5
580/1800
427/1800
83.1
Komatsu
SA6D140-A
6-140×165
15.240
421/1500
310/1500
52.1
485/1800
357/1800
60.8
190H52×2
6D24-TLE2B
6-130×150
11.940
246/1500
181/1500
33.7
270/1800
199/1800
38.1
Komatsu S6D125E-2-A
Inlined,Direct Injected, Turbocharged
6-125×150
11.040
242/1500
178/1500
31.5
277/1800
204/1800
35.7
Komatsu
SA6D125E-2-A
316/1500
232/1500
43.6
350/1800
257/1800
50.0
61 63 63 65 68 71 67 68 68 71
Inlined,Direct Injected, Turbocharged,Aftercooled
145G51×2
DCA-400SPK II DCA-500SPK
DCA-220ESM
*5
DCA-150ESK DCA-150ESM
6D16-TLE2D
6-118×115
7.540
153/1500
113/1500
19.8
183/1800
135/1800
24.0
Komatsu
SAA6D102E-2-D
6-102×120
5.880
28.4
153/1500
113/1500
20.6
183/1800
135/1800
25.0
62 65 62 67
DCA-400SPKII
95E41R×2
DCA-220SPK3
Within ±0.5
ASTM No. 2 Diesel Fuel or Equivalent
SPECIFICATION TABLE(600kVA~1100kVA CLASS SOUNDPROOF TYPE)
②
*1 Rated Voltage Classification
( ) indicates options.
5280(4800)*3
5580(5100)*3
DCA-610SPMDCA-600SPK
3-Phase,4-Wire
0.8(Lagging)
Within ±0.5
Brushless,Rotating Exciter(With A.V.R.)
Mitsubishi
S6R-PTA
6-170×180
24.500
768/1800 565/1800
96.4
762/1500 517/1500
82.0
Komatsu
SA6D170A
Inlined Direct InjectedTurbocharged,Aftercooled
6-170×170
23.150
190H52×2
639/1500 470/1500
81.8
698/1800 513/1800
93.7
DCA-600SPV
67 71 69 72
5180(4700)*3
Volvo
TAD1642GE
6-144×165
16.120
659/1500 485/1500
81.2
723/1800 532/1800
91.7
6110(5500)*3
11200
6210(5600)*3
11350
6610(6000)*3
14500
③Single Voltage
DCA-800SPK DCA-800SPM
1292/1800 950/1800
1209/1500 890/1500
Mitsubish
S12H-PTA
12-150×175
37.110
Mitsubishi
S12A2-PTA
12-150×160
33.93
830/1500 610/1500
920/1800 677/1800
Komatsu
SA12V140
12-140×165
30.480
1000/1800 736/1800
834/1500 613/1500
70 72 67 69 72 74
DCA-1100SPC
DCA-1100SPM DCA-1100SPC
1369/1800 1007/1800
1196/1500 880/1500
6610(6000)*3
12700
71 75
Cummins
QST30-G4
12-140×165
30.48
DCA-800SPM
DCA-600SPV
*2 Fuel consumption is based on operation at 75% load.
*3 Shown unit lengths are with visor.(without visor) *4 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.
*5 Depending on location and area,output voltage may differ from values listed in catalog.
V12 Direct InjectedTurbocharged,Aftercooled
190H52×4
50Hz 190~220V 380~440V 380~440V
60Hz 190~240V 380~480V 380~480V③
Class H
*5
Class F
②Dual Voltage
*1 Rated Voltage Classification *2 Fuel consumption is based on operation at 75% load.
*3 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.
*4 Depending on location and area,output voltage may differ from values listed in catalog.
27.5
38.9
47.3
4-85×96 2.179
8.5 6.4
80D26R×1
4-95.4×107 3.059
95D31R×1
6-102×120 5.880
22.4
95E41R×2
4-104×118 4.009
16.5 11.9
80D26R×2
95D31R×2
6-114×130 7.961
25.5 19.6
154/1500 113/1500
20.5
184/1800 135/1800
25.1
156/1800 115/1800
21.9
133/1500 97.8/1500
16.7
Komatsu
SAA6D102E-2-D
Inlined,Direct Injected, Turbocharged,Aftercooled
Hino
J08C-UP
Inlined,Direct Injected,Turbocharged
Isuzu
DD-6BG1T
Hino
W04D-TG
Isuzu
BB-4JG1T
Isuzu
AA-4LE2
Inlined, Direct Injected 126/1800 92.8/1800
17.1
101/1500 74.5/1500
13.4
6-105×125 6.494
22.4
ASTM No. 2 Diesel Fuel or Equivalent
78/1800 57.4/1800
10.2
66/1500 48.5/1500
8.3
56/1800 41.2/1800
8.4
46.5/1500 34.2/1500
6.7
32/1800 23.5/1800
3.9
26/1500 19.1/1500
3.2
3-Phase,4-Wire
0.8(Lagging) Within ±0.5
Brushless,Rotating Exciter(With A.V.R.) Class F
④Single Voltage(Dual Voltage is an option.) ②Dual Voltage
DCA-25USI2 DCA-45USI2 DCA-60USH2 DCA-100USI DCA-125USH DCA-150USK
52 52 51 53 52 55 55 57 53 56 55 58
NOTE 1 OUTPUT RATING
●Continuous output rating applies to operation under standard conditions as per JIS D0006*.
●Standby output rating applies to intermittant or emergency operation for approximately 1 hour as per JIS D0006.
●Kilowatts(kW) is calculated by multiplying output kVA by 0.8.
*JIS D0006:Standard air conditions Tenperature 25℃ Atmospheric pressure 100kPa Relative humidity 319%RH
NOTE 2 RATED VOLTAGE
●Line to neutral voltage is calcu- lated by dividing line to line voltage by √3.
●Besides the voltages shown on the specification table, other voltages are available upon request.
NOTE 3
Colours of products would be different from printed ones of catalogues.
50Hz 190~220V 380~440V 190~220V
(380~440V)
60Hz 190~240V 380~480V 200~240V
(380~480V)
( ) indicates options.
DCA-45USI2
DCA-60USH2
DCA-100USI
*4
SPECIFICATION TABLE(25kVA~150kVA CLASS SUPER SOUNDPROOF TYPE)
Operation
Method
Engine Starting / Stopping
Synchronization Verification/ Activation
Remarks
Manual Parallel Operation Device
Standard feature for DCA-125 to 1100
Load Sharing
Automatic Load Sharing Device For DCA-150 and above
Automatic Parallel Operation Device
Auto operation with pushbutton
For DCA-220 and above.
Standard feature for
DCA-1100SPM,1100SPC
Fully Automatic Parallel Operation Device (with GCP generator controller)
Semi-automatic Automatic
Refer to (4) below for applicable units.Automatic
Manual
Manual
Manual
Manual
Manual Automatic
Automatic
Automatic
Manual
Remote Control Devices The engine generator can be remotely changed from low speed to high speed operation, started and stopped, and otherwise contro l led. The abi l i t y to per form these procedures automatically or manually at the location where work is being performed when the engine generator is separated by a considerable distance provides high fuel and oil savings, extends engine life substantially, and leads to a surprising level of reduction in manpower and energy requirements. In addition, this also minimizes noise and exhaust gas discharge levels, and in turn helps improve the worksite environment.
Automatic Idling Device or Slowdown Device Automatic Idling Device (For DCA-45 to 150, provided as standard feature for DCA-220 and above) (Cannot be used with 45ESI, 45USI2) This device automates warm-up operation when the engine is started. The addition of a remote-control box allows remote changeover between low-speed and high-speed operation.(Please note that the engine cannot be started and stopped with the remote-control box.)
Remote Controller (For DCA-220 to 1100) T h i s d ev i c e a l l ow s t h e e n g i n e starting/stoppingand automatic idling function(idling when engine is started) to be operated from a remote location.
In addition to a switch for changeover between high-speed and low-speed operation, the remote-control box has a high-speed/low-speed operation indicator lamp, a startup warming lamp (comes on when generator set is not started up using normal remote controller operation),and a malfunction indicator lamp (illuminated when the emergency stop device is triggered).
Note: The remote-control box for the DCA-800SPM differs from the picture.
Automatic Oil Lubrication Device (For DCA-25 to 800, provided as standard feature for 610SPM, 800SPM and 1100SPM,1100SPC)(Cannot be used with 25USI2,25ESK)
This system automatically maintains engine oil at the proper level, making it possible to reduce costs for oil-related maintenance, and elimi- nates the need to check the engine oil level.
Automatic Fuel Replenishment Device (For DCA-25ESI, 45 to 60)
When the level in the unit tank drops after an extended period of operation, a level sensor detects this and an electric pump is operated to automatically replenish fuel in the unit tank from a separate tank. (Cannot be used with three-way valve.)
Salt Corrosion Specifications (For DCA-13 to DCA-220, provided as standard feature for DCA-300 and above)
These specifications are designed for when the unit will be used on the coast or on the ocean, and include treatment to prevent insulation resistance from dropping, and corrosion resistant treatment of the parts.
Parallel Operation Device A variety of optional devices are available to change from manual parallel operation to the desired type of automatic operation.
Select the desired option from the table below according to the power supply application, site conditions and other factors.
(1)Manual Parallel Operation Device: Parallel operation system with unique Denyo AVR equipped with a cross-current compensation circuit(CCR system).
This is the most inexpensive system, where no addition equipment is required for the DCA-125 and above.
(2)Automatic Load Sharing Device: This device operates a governor motor to share the load uniformly among the respective generators when parallel operation is being performed. It facilitates stable parallel operation, and dramatically reduces the workload of monitoring during parallel operation.
(3)Automatic Parallel Operation Device: The troublesome synchronization verification and synchronization activation process can be automatically performed by simply pressing a pushbutton. After synchronization is activated, the Automatic Load Sharing Device is capable of performing stable parallel operation.
(4)Fully Automatic Parallel Operation Device: High-speed digital control enables all operations from starting and stopping to synchronization verification, synchronization activation and load sharing to be performed at the touch of one button. This device has multiple functions that enable parallel operation of generators with differing capacities, the number of units being operated to be controlled and other operations.
Applicable models: DCA-220ESM, 610SPM, 800SPK, provided as standard feature for DCA-800SPM.
(5)The generator may be classified as a normal use generator according to the Electricity Enterprises Law depending upon the installation and operation procedure. Consult with a sales person for details.
Trailer Trailers can be fitted to generators to facilitate on-site movement.
(trailers for DCA-60 and below are two-wheel;those for DCA-75SP through 400 are four-wheel) Bolt connectors make mounting and dismounting simple.
Options
Two-wheel type
Four-wheel type
Frequency (Hz)
EG capacity (kVA)
Frequency (Hz)
EG capacity (kVA)
42.5
63.8
76.5
34.5
51.8
42.5
63.8
34.5
51.8
27.2
40.8
21.5
32.3
48.8
37.5
38.4
20.5
30.8
12.3
18.5
28.2
14.9
22.4
34.3
6.3
9.5
15.7
7.6
11.4
19.5
9.4
14.3
23.1
11.6
17.5
27.7
Frequency (Hz)
EG capacity (kVA)
550/554
600/610
DCA-400DCA-300DCA-220DCA-150DCA-125DCA-100DCA-75
DCA-60DCA-45DCA-35DCA-25DCA-13 DCA-15 DCA-20
5.4
8.2
13.1
6.3
9.5
15.7
10.5
3.4
5.2
8.3
4.1
6.4
10.2
12.5
9.6
7.5
11.9
Model
Model
Model
Item
Item
Item DCA-500 DCA-600/610 DCA-800
Direct startup
Y-△ startup(1)
Y-△ startup(2)
Motor capacity (kW)
Direct startup
Y-△ startup(1)
Y-△ startup(2)
Motor capacity (kW)
Direct startup
Y-△ startup(1)
Y-△ startup(2)
Motor capacity (kW)
HOW TO SELECT
A GENERATOR
Range of motor capacities that can be used with Denyo generators.
Choosing generator output according to motors and other loads is made simple by referring to the motor capacity range and generator output in this table.
Notes
● Momentary voltage drop when a motor starts up is assumed to be within 30% of no- load voltage.
● Motor startup kVA is assumed to be 7kVA per 1kW.
● Motor efficiency is assumed to be 85%, and load factor about 90%.
● Values shown for Y-△ startup(1)and Y-△ startup(2)are open and closed, respectively; needed generator capacity differs depending on startup state.
● Not appropriate for determining the capacity of emergency generating equipment(especially disaster-prevention generating equipment).
Other Options The following options are also available:
● Reverse power relay (For DCA-125 and above.Provided as standard feature for DCA-800SPK, 800SPM,DCA-1100SPM,1100SPC)
● AC power meter (For DCA-125 and above.Provided as standard feature for DCA-800SPK, 800SPM,DCA-1100SPM,1100SPC)
● Dual-voltage specifications (For DCA-25USI2,45USI2,60ESH,60USH2.Provided as standard feature for DCA-25ESK,25ESI,45ESI,60ESI2,75SPI,DCA-100 to 800.Not available for
DCA-13LSK,13LSY,15LSK,20LSK,35SPK,DCA-1100SPM,1100SPC)
● Bearing/stator temperature gauge (For DCA-125 and above. Provided as standard feature for DCA-800SPK,800SPM,DCA-1100SPM)
● Lubricant temperature gauge (Provided as standard feature for DCA-220 and above)
● Overspeed protection device (Provided as standard feature for DCA-600SPK,DCA-610SPM,DCA-800SPK, 800SPM, 1100SPM,1100SPC)
● Keyed fuel tank cap (For DCA-13 to 1100)
● Mounting of muffler flange Other options for different ranges and operating capabilities are available. Please feel free to consult with Denyo.
* Some options may not be available depending upon the model. Confirm the details with a Denyo sales person.
Motor usage examples in the above table are benchmark values :
generator capacity will differ according to the required momentary voltage drop, motor load factor, and size of startup capacity, as well as motor age and efficiency.
Printed in japan (T)
Direct inquiries to the nearest Denyo distributor or to Denyo co.,Ltd.
ISO 9001 Certified
CAT.No.FG04-15-20140416-05
No.0263-ISO 9001MGMT. SYS.
RvA C 086
Head office:2-8-5,Nihonbashi-horidomecho,Chuo-ku,Tokyo 103-8566,Japan Tel:+81-3-6861-1111 Fax:+81-3-6861-1181 http://www.denyo.co.jp
The Denyo trademark is widely recognized as a brand , and is a registered trademark in 90 countries around the world.