Atch_3_BPS_Comm_Ctr_B533_drawings.pdf

PDF 2 MB Posted

Attached to
Consolidated Back-Up Power Building 533 Federal contract opportunity
Solicitation number
FA252119BA009
Issued by
Department of the Air Force Space Command

About this file

Attachment 3 - Project Area and Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Consolidated Back-Up Power Building 533, newest first.
File Type Posted
OF1419_(19BA009).pdf PDF
Answers_w__Attachments_(19BA009__BU_Power_Req).pdf PDF
Solicitation_Amendment_FA252119BA0090001_SF_30.pdf PDF
Section_L_(Amd0001).pdf PDF
Atch_2_BU_Power_Systems_(B533).pdf PDF
Atch_6_Badge_Request_(45_SFS).pdf PDF
Atch_9_Q_&_A_Template.doc DOC document
Atch_7_GPP_Certification_Form.pdf PDF
Atch_1_SOW_(Feb_2019).pdf PDF
Solicitation_-_FA252119BA009.pdf PDF
Atch_8_Hazardous_Waste_Form.doc DOC document
Atch_4_CECC_Form_3052.xls XLS spreadsheet
Atch_5_WRR_(FL190001)_1Mar2019.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR FORCE BASE

MIAMI

TAMPA

ORLANDO

PATRICK

TALLAHASSEE

JACKSONVILLE

T

A

X

I

W

A

Y

B

X

T

A

X

I

W

M

T

A

X

I

W

J

A

X I W

A

X

I W

R

U

N

U

P

D

T

A

X

I

W

D

H

E

A

D

I

N

G

T

A

X

I

W

T

A

X

I

W

Z

A

X

I

W

G

A

X

I

W

L

U

N

W

T A

X I W

I

N

S

T

R

U

M

E

N

N

W

T

R

I

M

U

T

R

I

M

U

T

A

X

I

W

X

F

E

V

T

A

X

I

W

A

X

I W

A

X

I W

C

A

X

I W

R

M

D

E

A

T15

SOQ5

TBD

SOQ6

TBD

T7

Unknown

T968

SOQ2

SOQ4

TBD

PAV4

PAV5

PAV1

SOQ3

T13

T-Golon10

PAV9

T14

TBD

PAV6

PAV8

10992

SOQ7

PAV2

T1619

T12

T6

10985

TBD

PB8

TBD

TBD

10990

10989

10991

SOQ1

TBD

ANT1

TBD

S T

A T

E

R

O A

D

A

A

A

C

C

E

S

S

R

O

A

D

R

E

D

S

T

O

N

E

R

O

A

D

RECREATION ROAD

U

N

K

N

O

W

N

CONTROL ROAD

UNKNOWN

CONTROL ROAD

U

N

K

N

O

W

N

U

N

K

N

O

W

N

A

C

C

E

S

O

A

D

A

C

C

E

S

S

R

O

A

D

PEQUOT TRAIL

A

C

C

E

A

D

F

O

R

E

C

A

N

E

A

T

L

A

S

A

V

E

N

U

E

F

A

L

C

E

N

U

E

SOUTH TECH ROAD

COUGAR RUN

SANDOLLAR C

OVE

E

N

D

E

A

V

O

R

R

O

A

D

ACCESS ROAD

T

I

T

A

D

PORPOISE COVE

T

U

S

K

E

G

R

M

I

V

E

U

N

K

N

O

W

N

S

P

A

C

E

L

I

E

N

U

E

O

M

A

L

L

A

C

C

E

S

S

R

O

A

D

NORTH DRIVE

N C

O

C

L U

B

S

O U

R

K I N

G

U

T

E

T

R

A

IL

SEQUOIA TRAIL

JAGUAR AVENUE

DUSKY RUN

P

H

A

R

M

A

C

Y

D

R

IV

E

ACCESS ROAD

PANTHER R

UN

D

E

L

I

V

E

SHOSHONI TRAIL

C A

N I N

E

D

R I V

E

JU

P

IT

E

R

S

T

R

E

E

T

A

C

C

E

S

S

R

O

A

D

THUNDER LANE

T

H

O

R

S

T

R

E

E

T

E

D

W

A

R

D

H

. W

H

IT

E

II

J

U

P

IT

E

R

S

T

R

E

E

T

C

H

A

L

L

E

N

G

E

R

S

T

R

E

E

T

M

A

T

A

D

O

R

S

T

R

E

E

T

B

R

E

A

K

E

R

S

L

A

N

E

P

E

R

S

H

IN

G

P

L

A

C

E

R

E

S

C

A

D

R

E

L

A

Y

S

T

A

T

IO

N

R

O

A

D

M

A

C

E

R

O

A

D

S

A

T

U

R

N

R

O

A

D

T

H

H

O

L

E

S

U

N

S

E

T

B

L

V

D

G

R

E

E

N

S

K

E

E

P

N

E

STATE ROAD 404

STATE ROAD 404 (ONRAMP)

A

C

C

E

A

D

A C

C E

A

D

H

A

B

I T

N

C O

N T

R O

L

R

O A

D

R

I

V

E

R

S

I

A

I

L

R I V

E R

S I D

E

T

R A

I L

U

N

K

N

O

W

N

U

N

K

N

O

W

N

S O

U T

H

P

A T

R I C

K

D

R I V

E

ACCESS ROAD

ACCESS ROAD

S

C

H

O

O

L

A

V

E

N

U

E

S

C

H

O

O

L

A

V

E

N

U

E

A

R

A

P

A

H

O

T

R

A

I

L

A

N

G

E

L

F

I

S

H

C

O

V

E

C O

N T

R O

L

R

O A

D C

O N

T R

O L

R

O A

D

C

H

IC

K

A

S

A

W

T

R

A

IL

C

H

O

C

K

T

A

W

T

R

A

IL

W E

C

H

R

O A

D

J

U

P

IT

E

R

S

T

R

E

E

T

M

A

I

N

T

E

N

A

N

A

D

COYOTE RUN

COYOTE R

UN

R

E

E

F

C

O

U

R

T

A

C

C

E

S

S

R

O

A

D

S E

Q U

O I A

T R

A

I L

IROQUIS TRAIL

IROQUIS TRAIL

BEAR R

UN

BEAR RUN

ALLIG

ATOR RUN

ALLIGATOR RUN

U N

K N

O W

N

M

IN

U

T

E

M

A

N

S

T

R

E

E

T

R

E

S

C

A

D

R E

S C

A

D

R

E

U

R

T

UNKNOWN

CONTROL ROAD

C

O

N

T

R

O

L

R

O

A

D

S

O

U

T

R

I

K

I V

E

S O

U T

H

P

A T

R I C

K

D

R I V

E

ANVIL ROAD

ANVIL ROAD

ACCESS ROAD

R

E

S

C

A

D

R

E

S

C

A

D

C

H

E

R

O

K

E

E

T

R

A

I

L

A

C

C

E

A

D

A

C

C

E

A

D

A

C

C

E

A

D

A C

C E

A

D

U

N

K

N

O

W

N

PINEDA EXPRESSWAY

SOUTH GATE (PERSONNEL ONLY)

B

A

N

A

V

E

R

B A

N

A N

A

R

I V

E R

A

T

L A

N

T

E

A

N

TRUCK

DELIVERY ONLY

BUILDING 423-CONTRACTING OFFICER

BUILDING 535-45TH CES

MAIN GATE (PERSONNEL ONLY)

S.R. A1A

B

A

N

A

V

E

R

A

T

L A

N

T

E

A

N

GOLF COURSE

P

E

R

S

H

I

A

C

E

S

A

T

U

A

D

PATRICK AIR FORCE BASE

SXHT 14-1046

FLORIDA

SCALE:

LOCATION MAP

NONE

CONSOLIDATE BACKUP POWER

SYSTEMS, COMM CTR B533

CE OPERATIONS:

COMMUNICATIONS:

PROJECT MANAGER:

CHIEF, ENGINEERING FLIGHT:

USER:

SAFETY:

SECURITY FORCES:

ATO:

OTHER:

ENVIRONMENTAL:

FIRE:

A

P

P

R

O

V

E

D

TRUE

NORTH

NORTH

PLAN

G-001

G

B

O G

I A

T Z

I D

I S

L

C

O L

E M

A N

L O

C A

T I O

N

M

A P

P

R O

J E

E

A

A

N D

D R

A W

I N

G

I N

D E

X

C

H

A R

T N

E T

T

S X

F

G

B

E A

R D

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L

E N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

C O

N S

O L I D

A T

E

B

A C

K U

P

P

O W

S

T E

M S

C O

PROJECT

LOCATION

SCALE:

ENLARGED PROJECT AREA

NONE

TRUE

NORTH

NORTH

PLAN

PERMIT(S)/ENVIRONMENTAL ACTIONS

REQUIRED PRIOR TO CONSTRUCTION

ERP/STORMWATER

ERP/WETLANDS/DREDGE & FILL

FDEP/DRINKING WATER

FDEP/DOM. WASTE WATER ARCHEO./HISTORICAL

SURVEY/WILDLIFE

OTHER

NONE

FDEP/IND. WASTE WATER

IRP

FDEP/FUEL TANK

NOI/SWPPP

ASBESTOS

NOTE: IF IT IS SUSPECTED THAT ANY HAZARDOUS MATERIAL NOT

IDENTIFIED ON THESE DRAWINGS IS REQUIRED TO BE DISTURBED IN

ORDER TO PERFORM THE CONTRACT WORK, LEAVE MATERIAL

UNDISTURBED AND IMMEDIATELY INFORM THE CONTRACTING OFFICER.

HEAVY METALS

YES NO

LEAD

PCB

NOT

VERIFIED

HAZARDOUS MATERIALS

DRAWING INDEX

Sheet

Number

Sheet Title

GENERAL

G-001

LOCATION MAP, PROJECT AREA AND DRAWING INDEX

ELECTRICAL

E-001

ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS

ED-101 PARTIAL ELECTRICAL PLAN - DEMOLITION

E-101 PARTIAL ELECTRICAL PLAN - NEW CONSTRUCTION

E-601 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING & DEMO

E-602 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING & REVISED

SCALE:

STATE OF FLORIDA

NONE

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_G-001.dwg, 1/16/2018 12:19:12 PM

ELECTRICAL LEGEND

CONDUIT ROUTING

ABBREVIATIONS:

E-001

G

B

O G

I A

T Z

I D

I S

G

B

O G

I A

T Z

I D

I S

E L

E C

T R

I C

G E

N D

N

O T

D

A B

B R

E V

I A

T I O

N S

L

C

O L E

M A

N

S X

F

G

B

E A

R D

C O

N S

O L

I D

A T

E

B

A C

K U

P

P

O W

E R

S Y

S T

E M

S

C

O M

M

C

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L

E N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

APPLIES TO ALL ELECTRICAL SHEETS

THREE SECTION SWITCHBOARD

ELECTRICAL NOTES:

1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A COMPLETE AND

WORKABLE FACILITY.

2. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS,

ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY BE REQUIRED FOR PROPER

INSTALLATION OF THE WORK. SUCH WORK SHALL BE VERIFIED AT THE SITE.

ADDITIONAL BENDS, OFFSETS, AND CONDUIT AS REQUIRED BY VERTICAL AND

HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS, SHALL BE

PROVIDED TO COMPLETE THE WORK AT NO ADDITIONAL COST TO THE

GOVERNMENT.

3. EXCEPT WHERE SHOWN IN DIMENSIONAL DETAIL, THE LOCATIONS OF EQUIPMENT

SHOWN ON PLANS ARE APPROXIMATE. SUCH ITEMS SHALL BE PLACED TO

ELIMINATE INTERFERENCE WITH OTHER EQUIPMENT. THE EXACT LOCATIONS

SHALL BE DETERMINED IN THE FIELD.

4. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2017 EDITION OF THE NATIONAL

ELECTRICAL CODE (NFPA 70).

5. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. OR

ANOTHER APPROVED/CERTIFIED TESTING LABORATORY. SHOULD PLANS AND

CODES CONFLICT, CONTACT THE CONTRACTING OFFICER. MAKE NO CHANGES,

EVEN IN CASE OF CONFLICT, WITHOUT FIRST OBTAINING THE APPROVAL OF THE

CONTRACTING OFFICER.

6. A GREEN, COPPER GROUND WIRE SHALL BE INSTALLED IN ALL CONDUIT SYSTEMS

AND SHALL BE BONDED TO ALL ENCLOSURES, BOXES, AND EQUIPMENT.

RECEPTACLES WITH GREEN WIRE SHALL BE BONDED TO BOX THEN TO

RECEPTACLE SUCH THAT REMOVAL OF RECEPTACLE DEVICE SHALL NOT

INTERRUPT GREEN WIRE BOND TO METALLIC BOX OR ENCLOSURE.

7. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO ENCLOSURES, BOXES,

AND EQUIPMENT WHERE CONCENTRIC OR ECCENTRIC KNOCKOUTS ARE USED.

8. EQUIPMENT SIZES INDICATED ARE MINIMUM, BEFORE INSTALLING ANY WIRE OR

CONDUIT, THE CONTRACTOR SHALL OBTAIN THE EXACT EQUIPMENT

REQUIREMENTS AND SHALL INSTALL WIRE, CONDUIT, CIRCUIT BREAKERS AND

OTHER ITEMS OF THE CORRECT SIZE FOR THE EQUIPMENT ACTUALLY INSTALLED.

HOWEVER, WIRE AND CONDUIT SIZES FOR THE EQUIPMENT SHALL BE TAKEN AS A

MINIMUM AND SHALL NOT BE REDUCED WITHOUT WRITTEN APPROVAL.

9. THE INSTALLATION OF THE ELECTRICAL WORK SHALL BE COORDINATED WITH THE

WORK OF THE OTHER TRADES.

10. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN THIS TYPE

OF WORK. THE INSTALLATION SHALL BE MADE SO THAT THERE IS NO

DEGRADATION OF THE DESIGNED FIRE RATINGS.

11. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND AT SUCH A

TIME AS WILL REQUIRE A MINIMUM OF CUTTING AND PATCHING OF THE BUILDING

STRUCTURE.

12. 'PROVIDE', AS USED HERE ON THE DRAWINGS, IS AN ALL-INCLUSIVE TERM

REQUIRING CONTRACTOR TO FURNISH, INSTALL, WIRE, AND CONNECT ALL

SPECIFIED EQUIPMENT AS WELL AS COMPONENTS, ACCESSORIES, WIRING, AND

MOUNTING HARDWARE TO INSURE THAT SPECIFIED EQUIPMENT FUNCTIONS TO

MEET SYSTEM(S) REQUIREMENTS.

13. WHERE NEW-TO-EXISTING CONNECTIONS ARE INDICATED, THE CONTRACTOR

SHALL PROVIDE ALL MATERIALS (JUNCTION BOXES, CONDUIT, WIRE, AND

CONNECTIONS) AND LABOR REQUIRED TO MAKE THE CONNECTIONS.

14. UNLESS OTHERWISE NOTED, ALL POWER CIRCUIT CONDUCTORS SHALL BE

COPPER AND MINIMUM #12AWG. CONDUITS SHALL BE 3/4" MINIMUM.

15. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT EXISTING

UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR

REPAIR OR REPLACEMENT OF THE UTILITIES OR OTHER PROPERTY DAMAGED BY

OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK.

16. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND BONDING

CONNECTIONS SHALL BE COPPER. CONTRACTOR SHALL UTILIZE CONNECTORS TO

PREVENT GALVANIC ACTION.

17. FINAL ACCEPTANCE WILL DEPEND UPON SATISFACTORY PERFORMANCE OF

EQUIPMENT. NO CONDUCTOR SHALL BE ENERGIZED UNTIL THE INSTALLATION HAS

BEEN APPROVED.

18. PROVIDE ELECTRICAL CONDUIT AS FOLLOWS:

- RIGID GALVANIZED STEEL - ABOVE GRADE OUTSIDE OR WHERE SUBJECT TO

PHYSICAL DAMAGE

- EMT - ABOVE GRADE INSIDE WHERE NOT SUBJECT TO PHYSICAL DAMAGE

- PVC SCHEDULE 40 - BELOW GRADE

- PVC SCHEDULE 80 - WHERE SUBJECT TO PHYSICAL DAMAGE

EXCEPT: ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO MECHANICAL

DAMAGE SHALL BE RIGID GALVANIZED STEEL (RGS), UNLESS OTHERWISE NOTED.

19. CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR STRAPS TO

PROVIDE A RIGID INSTALLATION. CONDUIT SUPPORTS SHALL NOT BE FASTENED

OR ATTACHED TO OTHER PIPES. PERFORATED STRAP HANGERS WILL NOT BE

ALLOWED. EMPTY CONDUIT SHALL BE THOROUGHLY SWABBED OUT WITH DRY

SWAB TO REMOVE MOISTURE AND DEBRIS BEFORE WIRE IS DRAWN IN. END OF

CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL WIRE IS PULLED. NO CONDUIT SHALL

BE LOCATED TO IMPAIR THE STRENGTH OF STRUCTURAL MEMBERS. MAKE

CHANGES IN DIRECTION OF RUNS WITH SYMMETRICAL BENDS. MAKE FIELD MADE

BENDS AND OFFSETS WITH HICKEY OR CONDUIT BENDING MACHINE. DO NOT

INSTALL CRUSHED OR DEFORMED CONDUITS. AVOID TRAPPED CONDUITS.

PREVENT PLASTER, DIRT, OR TRASH FROM LODGING IN CONDUIT, BOXES,

FITTINGS. FREE CLOGGED CONDUITS OF OBSTRUCTIONS.

20. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON-CURRENT CARRYING

METALLIC PARTS OF ELECTRICAL EQUIPMENT, METALLIC RACEWAY SYSTEMS,

GROUNDING CONDUCTOR IN METALLIC RACEWAYS.

21. FASTEN CONDUITS TO SHEET METAL BOXES AND CABINETS WITH TWO LOCKNUTS

WHERE REQUIRED BY NFPA 70, WHERE INSULATED BUSHINGS ARE USED, AND

WHERE BUSHINGS CANNOT BE BROUGHT INTO FIRM CONTACT WITH THE BOX;

OTHERWISE, USE MINIMUM SINGLE LOCKNUT AND BUSHING. LOCKNUTS SHALL

HAVE SHARP EDGES FOR DIGGING INTO WALLS OF METAL ENCLOSURE. INSTALL

BUSHINGS ON ENDS OF CONDUITS, AND PROVIDE INSULATING TYPE WHERE

REQUIRED BY NFPA 70.

22. THE CORRIDOR AND MECHANICAL ROOM WALLS AND CEILING ARE FIRE RATED.

PENETRATIONS THROUGH THE WALLS SHALL BE A MINIMUM OF 0.5" DIAMETER

LARGER THAN THE CONDUIT REQUIRED TO PENETRATE THE WALL. PROVIDE A

FIRE STOP MATERIAL PER REQUIREMENTS BELOW. CONDUIT THROUGH THE

SLEEVE SHALL BE GALVANIZED RIGID STEEL AND SHALL EXTEND A MINIMUM OF 18"

BEYOND THE SLEEVE OF BOTH SIDES.

23. PROVIDE AND INSTALL AT WALL OR FLOOR PENETRATIONS A PERMANENT FIRE

STOP SYSTEM. THE SYSTEM SHALL CONSIST OF A WATER BASED FIRE STOP

COMPOUND AS THE FILL, VOID, OR CAVITY MATERIAL ALONG WITH APPROPRIATE

DAMMING MATERIAL (AS PER MANUFACTURER'S INSTRUCTIONS). THE FIRE STOP

COMPOUND SHALL NOT CONTAIN ANY SOLVENTS, INORGANIC FIBERS, OR

SILICONE COMPOUNDS AND SHALL NOT REQUIRE HEAT TO ACTIVATE THE SEAL.

THE FIRE STOP COMPOUND SHALL BE ONE-PART MATERIALS, REQUIRING NO

CRITICAL MIXING. THE PENETRATION SEAL MATERIAL MUST BE UNAFFECTED BY

MOISTURE AND MUST MAINTAIN THE INTEGRITY OF THE FLOOR OR WALL

ASSEMBLY FOR ITS RATED TIME PERIOD WHEN TESTED IN ACCORDANCE WITH

ASTM E84. THE SYSTEM SHALL BE UL CLASSIFIED AND INSTALLED TO PROVIDE A 2

HOUR FIRE RATING. THE PENETRATION FIRE STOP MATERIAL SHALL BE

FLAME-SAFE FS1900 SERIES COMPOUND AS MANUFACTURED BY GRACE

CONSTRUCTION PRODUCTS OR EQUAL.

24. DAMAGE DONE TO ZINC COATING OF GALVANIZED CONDUIT, BOXES, AND FITTINGS,

INCLUDING EXPOSED CONDUIT THREADS AND ZINC FINISHES SCRATCHING, SHALL

BE REPAIRED BY CLEANING, PREPPING, AND COATING DAMAGED SURFACE WITH

INORGANIC ZINC COMPOUND.

A - AMPERES

AHU - AIR HANDLING UNIT

AIC - AMPS INTERRUPTING CAPACITY

ATS - AUTOMATIC TRANSFER SWITCH

C - CONDUIT

CKT - CIRCUIT

CTRL - CONTROL

CU - COPPER

DISC - DISCONNECT SWITCH

DWG - DRAWING

ECB - ENCLOSED CIRCUIT BREAKER

ELEC - ELECTRIC

EMT - ELECTRICAL METALLIC TUBING

EQPM - EQUIPMENT

ETR - EXISTING TO REMAIN

EXST - EXISTING

FLA - FULL LOAD AMPS

GEN - GENERATOR

GFCI - GROUND FAULT CIRCUIT INTERRUPTER

GND - GROUND

HP - HORSEPOWER

IAW - IN ACCORDANCE WITH

KCMIL - THOUSAND CIRCULAR MILS

KW - KILOWATT

MECH - MECHANICAL

MTS - MANUAL TRANSFER SWITCH

NIC - NOT IN CONTRACT

NTS - NOT TO SCALE

PAFB - PATRICK AIR FORCE BASE

PNL - PANEL/PANELBOARD

PVC - POLYVINYL CHLORIDE

RGS - RIGID GALVANIZED STEEL

RM - ROOM

SPD - SURGE PROTECTION DEVICE

SWBD - SWITCHBOARD

SWGR - SWITCHGEAR

SYS - SYSTEM

TVSS - TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP - TYPICAL

UG - UNDERGROUND

UON - UNLESS OTHERWISE NOTED

UPS - UNINTERRUPTIBLE POWER SUPPLY

V - VOLTS

VD - VOLTAGE DROP

WP - WEATHERPROOF

XFMR - TRANSFORMER

THROUGH-WALL CONDUIT PENETRATION

GENERATOR OUTLINE

IN-WALL LOUVER

IN-WALL EXHAUST FAN

DISCONNECT SWITCH

208/120V POWER PANEL

SEQUENCE OF CONSTRUCTION:

THE CONTRACTOR SHALL SUBMIT A PROPOSED SEQUENCE OF CONSTRUCTION

FOR APPROVAL. SEQUENCE OF CONSTRUCTION SHALL COMPLY WITH THE

FOLLOWING GUIDELINES:

1. BEFORE ANY OUTAGES INSTALL NEW CONDUIT AND CABLE FROM

SWITCHBOARD 'DP' TO SWITCHBOARD 'DP1'. FINAL CONNECTIONS OF

CONDUIT AND CABLE TO SWITCHBOARDS SHALL BE DONE DURING AN

OUTAGE.

2. SCHEDULE A 4-HOUR MAXIMUM WEEKEND OR NIGHTTIME OUTAGE TO:

· INSTALL NEW BREAKER IN SWITCHBOARD 'DP1'

· CONNECT CONDUIT AND CONDUCTORS TO 'DP1'

· CONNECT CONDUIT AND CONDUCTORS TO 'DP'

· DISCONNECT THE EXISTING 'ATS' FROM THE CRITICAL

SWITCHBOARD

PROVIDE AND CONNECT THE FOLLOWING TEMPORARY GENERATORS:

A. (2) 60 KW UNITS

B. (1) 40 KW UNIT

C. (1) 100 KW UNIT

CONTRACTOR SHALL COORDINATE WITH 45 CES POWER PRODUCTION

SHOP FOR EXACT PLACEMENT LOCATIONS. THE TIE-INS TO THE SWITCHES

AND/ OR PANELS WILL BE PERFORMED BY THE CONTRACTOR AND WILL BE

COORDINATED WITH 45 CES POWER PRODUCTION AND 45 SPACE WING

COMM SQUADRON.

ALL THE NECESSARY PERSONNEL, TOOLS, AND MATERIAL REQUIRED FOR

THE WORK BEING DONE THAT DAY SHALL BE ON SITE PRIOR TO STARTING

WORK.

IF ADDITIONAL OUTAGES ARE REQUIRED, MAXIMUM OUTAGE TIME SHALL

NOT EXCEED 4 HOURS.

NOTIFY PAFB PERSONNEL AT LEAST 14 WORKING DAYS IN ADVANCE OF

ANY OUTAGE.

NEW CONDUCTORS AND BREAKERS SHALL BE TESTED AND ACCEPTED

PRIOR TO CONNECTION OF LOADS.

3.

4.

5.

6.

7.

PULL BOX - 24' x 24" x 12"

APPLIES TO ALL ELECTRICAL SHEETS

BRANCH CIRCUIT CONDUIT RUN. ARROW

INDICATES HOME RUN, MINIMUM CONDUIT SIZE

SHALL BE 3/4". HOMERUNS LONGER THAN 100'

SHALL USE MINIMUM #10 CONDUCTOR.

EXISTING - TO REMAIN

NEW - TO BE INSTALLED

E

NEW - UNDERGROUND ELECTRIC

EXISTING - UNDERGROUND ELECTRIC

E

TO BE REMOVED

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_E-001.dwg, 1/16/2018 12:19:15 PM

MECH 3

MECH 4

1HALL2

109A 109

111A

135C

136C

136B

135B

136A

135A

MECH 5

MECH 6

119A

MECH 1

135C

'DP1'

MECH 3

500 GAL

TANK

'DP'

MTS

ED-101

G

B

O G

I A

T Z

I D

I S

G

B

O G

I A

T Z

I D

I S

P A

R T

I A

L

E

L E

C T

R I C

A L

P

L A

N

D

E M

O L I T

I O

N

L

C

O L

E M

A N

S X

F

G

B

E A

R D

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A

D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L

E N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

C O

N S

O L I D

A T

E

B

A C

K U

P

P

O W

S

T E

M S

C O

24'16'0'4'8' 8'

GRAPHIC SCALE: 1/16" = 1'-0"

32' 40' 48'

SCALE:

PARTIAL ELECTRICAL PLAN - DEMOLITION

1/16" = 1'-0"

T

R

U

E

N

O

R

T

H

NORTH

PLAN

GENERAL NOTES:

1. SCOPE OF WORK IS TO RECONFIGURE (2) EXISTING EMERGENCY POWER SYSTEMS

PLACING CRITICAL LOADS ON EXISTING 600 KW GENERATOR. REMOVE AND DISPOSE OF

EXISTING 350 KW GENERATOR, ATS, FUEL TANK AND ASSOCIATED EQUIPMENT. INSTALL

NEW CONDUIT AND CONDUCTORS TO FEED EMERGENCY PANELS AS REQUIRED.

2. PENETRATIONS THROUGH CONCRETE BLOCK WALL SHOULD ASSUME THE DISTURBANCE

OF LEAD BASED PAINT.

FLAG NOTES:

1. EXISTING CONCRETE ENCASED 8000 GALLON FUEL TANK SHALL REMAIN AND IS SHOWN

FOR REFERENCE ONLY.

2. EXISTING 600 KW GENERATOR SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

3. EXISTING GE SPECTRA SERIES SWITCHBOARD (SWBD) 'DP1' SHALL REMAIN.

4. EXISTING AUTOMATIC TRANSFER SWITCH (ATS-1) SHALL REMAIN AND IS SHOWN FOR

REFERENCE ONLY.

5. EXISTING 1600A, 208/120V, 3P, 4W, SIEMENS/ITE SWITCHBOARD SHALL REMAIN.

6. DISCONNECT AND REMOVE EXISTING 350 KW GENERATOR. GENERATOR SHALL BE

RETURNED TO DEFENSE LOGISTICS AGENCY (DLA) LOCATED IN JACKSONVILLE, FL.

REMOVE ASSOCIATED CONDUIT, CONDUIT SUPPORTS AND WIRING BACK TO SWBD 'DP'.

7. DISCONNECT AND REMOVE EXISTING AUTOMATIC TRANSFER SWITCH 'ATS' FOR

SALVAGE. DELIVER TO BUILDING 1350 AT PAFB. REMOVE ASSOCIATED CONDUIT,

CONDUIT SUPPORTS AND WIRING BACK TO SWBD 'DP'.

8. REMOVE EXISTING 500 GALLON FUEL TANK FOR SALVAGE. DELIVER TO BUILDING 1350

AT PAFB.

9. EXISTING TRANSFORMER TO BE REMOVED. CUT CONDUIT STUB-UPS FLUSH WITH

EXISTING PAD & FILL WITH GROUT. REMOVE EXISTING MEDIUM VOLTAGE FEEDER BACK

TO 48A. SWITCH.

10. EXISTING GENERATOR PANEL SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

GENERATOR PANEL IS FED FROM SWITCHBOARD (SWBD) 'DP1' WITHIN SAME ROOM.

11. REMOVE EXISTING THROUGH-WALL LOUVER. SEE SHEET E-101 FOR NEW

CONSTRUCTION INFORMATION. EXISTING EXHAUST FAN, LOCATED ABOVE LOUVER,

SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

12. DISCONNECT AND REMOVE ASSOCIATED FUEL PIPING AND EXHAUST PIPING.

13. EXISTING MANUAL TRANSFER SWITCH SHALL REMAIN.

14. REMOVE EXISTING CUMMINS ONAN 24V BATTERY FLOAT CHARGER. REMOVE

ASSOCIATED CONDUCTOR, CONDUIT SUPPORTS AND WIRING.

15. EXISTING SWITCH #48A, REFERENCE LOCATION.

16. EXISTING TRANSFORMER SHALL REMAIN.

1 10

24'16'6' 2'4' 0' 8'

GRAPHIC SCALE 1/8" = 1'-0"

SCALE:

ENLARGED MECH ROOM - DEMOLITION

1/8" = 1'-0"

A

ED-101

A

ED-101

SCALE:

PARTIAL ELECTRICAL SITE PLAN - REFERENCE

1/16" = 1'-0"

T

R

U

E

N

O

R

T

H

NORTH

PLAN

SEE CONTINUATION TO THE RIGHT

T533-50

T533-50

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_ED-101.dwg, 1/16/2018 12:19:20 PM

109A 109

111A

135C

135B

135A

MECH 5

MECH 6

MECH 3

MECH 4

GENERATOR

'DP'

'DP1'

E-101

G

B

O G

I A

T Z

I D

I S

G

B

O G

I A

T Z

I D

I S

P A

R T

I A

L

E

L E

C T

R I C

A L

P

L A

N

N E

W

C

O N

S T

R U

C T

I O

N

L

C

O L

E M

A N

S X

F

G

B

E A

R D

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A

D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L

E N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

C O

N S

O L I D

A T

E

B

A C

K U

P

P

O W

S

T E

M S

C O

24'16'0'4'8' 8'

GRAPHIC SCALE: 1/16" = 1'-0"

32' 40' 48'

SCALE:

PARTIAL ELECTRICAL PLAN - NEW CONSTRUCTION

1/16" = 1'-0"

T

R

U

E

N

O

R

T

H

NORTH

PLAN

GENERAL NOTES:

1. SCOPE OF WORK IS TO RECONFIGURE (2) EXISTING EMERGENCY POWER SYSTEMS

PLACING CRITICAL LOADS ON EXISTING 600 KW GENERATOR. REMOVE AND DISPOSE OF

EXISTING 350 KW GENERATOR, ATS, FUEL TANK AND ASSOCIATED EQUIPMENT. INSTALL

NEW CONDUIT AND CONDUCTORS TO FEED EMERGENCY PANELS AS REQUIRED.

2. SEE SINGLE-LINE DIAGRAM ON SHEET E-602 FOR CONDUIT AND WIRE SIZE.

3. PENETRATION THROUGH CONCRETE BLOCK WALL SHOULD ASSUME THE DISTURBANCE

OF LEAD BASED PAINT.

FLAG NOTES:

1. EXISTING CONCRETE ENCASED 8000 GALLON FUEL TANK SHALL REMAIN.

2. EXISTING 600 KW GENERATOR SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

FOR PURPOSES OF THIS DESIGN, THIS ROOM SHALL BE CALLED GENERATOR ROOM.

3. EXISTING SWITCHBOARD 'DP1' SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

4. EXISTING AUTOMATIC TRANSFER SWITCH (ATS-1) SHALL REMAIN AND IS SHOWN FOR

REFERENCE ONLY.

5. EXISTING 1600A, 208/120V, 3P, 4W SWITCHBOARD SHALL REMAIN.

6. EXISTING CONCRETE PAD IS SHOWN FOR REFERENCE ONLY.

7. EXISTING 750 KVA TRANSFORMER SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

8. EXISTING GENERATOR PANEL SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

GENERATOR PANEL IS FED FROM SWITCHBOARD (SWBD) 'DP1' WITHIN SAME ROOM.

9. PROVIDE CONCRETE BLOCK AND MORTAR TO IN-FILL OPENING WHERE THOUGH-WALL

LOUVER WAS REMOVED. SEAL OPENING LEFT BY REMOVAL OF EXHAUST PIPING. PAINT

TO MATCH EXISTING INTERIOR & EXTERIOR WALL COLORS. OPENING IS BELOW

EXISTING EXHAUST FAN, WHICH SHALL REMAIN AND IS SHOWN FOR REFERENCE ONLY.

10. PROPOSED ROUTE FOR NEW CONDUIT IS DIAGRAMMATIC. FIELD CONDITIONS MAY

REQUIRE ADJUSTMENTS TO ROUTING SHOWN. PROVIDE (2) 4" CONDUITS FROM

EXISTING SWITCHBOARD (SWBD) IN ROOM MECH 3 TO EXISTING SWBD IN GENERATOR

ROOM.

11. SUPPORT CONDUIT FROM BUILDING STRUCTURE WHEN ROUTED WITHIN BUILDING.

COORDINATE CONDUIT ROUTING WITH EXISTING AIR HANDLER DUCT WORK, AND PIPING

WITHIN ROOM MECH 4.

12. PROVIDE STAINLESS STEEL SUPPORT BRACKETS, UNISTRUT OR EQUAL, FOR CONDUIT

ROUTED EXTERIOR TO THE BUILDING. SUPPORT BRACKETS SHALL BE SPACED A

MAXIMUM OF 8 FEET ON CENTER. COORDINATE INSTALLATION WITH EXISTING

CONDITIONS SUCH AS EXTERIOR PIPING, WINDOWS AND DOORS. PROVIDE SILICONE

TYPE CAULKING, OR MANUFACTURER'S SUGGESTED SEALANT, TO SEAL ALL FASTENERS

THAT PENETRATE WALLS.

13. SUPPORT NEW CONDUIT FROM BUILDING STRUCTURE AND ROUTE ABOVE ACOUSTICAL

TILE CEILING. COORDINATE AND/OR ADJUST CONDUIT ROUTING WITH EXISTING

CONDITIONS IN ABOVE CEILING SPACE.

14. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE A MINIMUM OF 0.5" DIAMETER

LARGER THAN THE CONDUIT REQUIRED TO PENETRATE THE WALL. PROVIDE A

FIRESTOP MATERIAL. CONDUIT THROUGH THE SLEEVE SHALL BE GALVANIZED RIGID

STEEL AND SHALL EXTEND A MINIMUM OF 18" BEYOND THE SLEEVE OF BOTH SIDES.

REFER TO ELECTRICAL NOTE 23, ON SHEET E-001 FOR ADDITIONAL FIRE STOP

REQUIREMENTS.

15. PROVIDE 24" x 24" x 12" PULL BOXES FOR ROUTING CONDUIT. EXTERIOR PULL BOXES

SHALL BE STAINLESS STEEL.

16. EXISTING SWITCH #48A, REFERENCE LOCATION.

SCALE:

ENLARGED VIEW OF WALL PENETRATION TYPICAL

NONE

TYPICAL

SCALE:

PARTIAL ELECTRICAL SITE PLAN - REFERENCE

NONE

T

R

U

E

N

O

R

T

H

NORTH

PLAN

SEE CONTINUATION TO THE RIGHT

T533-50

T533-50

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_E-101.dwg, 1/16/2018 12:19:24 PM

E-601

G

B

O G

I A

T Z

I D

I S

G

B

O G

I A

T Z

I D

I S

E L E

C T

R I C

A L

S

I N

G L E

L I N

E

D

I A

G R

X

I S

T I N

M

O

L

C

O L

E M

A N

S X

F

G

B

E A

R D

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A

D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L E

N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

C O

N S

O L I D

A T

E

B

A C

K U

P

P

O W

S

T E

M S

C O

GENERAL NOTES:

1. SCOPE OF WORK IS TO RECONFIGURE (2) EXISTING EMERGENCY POWER SYSTEMS

PLACING CRITICAL LOADS ON EXISTING 600 KW GENERATOR. REMOVE EXISTING 350 KW

GENERATOR, ATS, FUEL TANK AND RETURN TO GOVERNMENT. INSTALL NEW CONDUIT

AND CONDUCTORS TO FEED EMERGENCY PANELS AS REQUIRED.

2. CONTRACTOR SHALL PATCH AND PAINT OPENINGS AND/OR WALL PENETRATIONS TO

MATCH EXISTING FINISHES.

FLAG NOTES:

1. EXISTING TRANSFORMER (XFMR) SHALL BE REMOVED.

2. EXISTING MANUAL TRANSFER SWITCH (MTS) SHALL REMAIN.

3. DISCONNECT EXISTING 350 KW GENERATOR AND ITS CONNECTION TO EXISTING

SWITCHBOARD (SWBD) 'DP' VIA AUTOMATIC TRANSFER SWITCH 'ATS' LOCATED IN MECH

ROOM 3. REMOVE EXISTING CONDUIT AND WIRE ASSOCIATED WITH EQUIPMENT BEING

REMOVED. GENERATOR AND FUEL TANK SHALL BE RETURNED TO GOVERNMENT.

4. DISCONNECT AND REMOVE EXISTING AUTOMATIC TRANSFER SWITCH 'ATS'. REMOVE

EXISTING CONDUIT, CONDUIT SUPPORTS AND WIRING ASSOCIATED WITH EQUIPMENT

BEING REMOVED. AUTOMATIC TRANSFER SWITCH SHALL BE RETURNED TO

GOVERNMENT.

5. EXISTING 2000A AUTOMATIC TRANSFER SWITCH 'ATS1' SHALL REMAIN.

6. REMOVE EXISTING 13.2KV FEEDER BACK TO SWITCH #48A.

750 KW XFMR

13.8K, 3PH, PRIMARY

208V, 3PH, SECONDARY

2000A

CB SER

ATS-1

2000A

600 KW

208Y/120V

2000A CB

SWBD 'DP1' 2000A

208/120V, 3 PH, 4 W

(42,000 AIC)

350A 400A 400A 400A

EXST

UPS

RM 105

EXST

PANEL

PP105

400A

EXST

PANEL

PP109

400A

EXST

PANEL

PP103

400A

400A

EXST

PANEL

PP104

400A

100A

GEN

100A

60A

TVSS

EXST

PANEL

PP109A

100A

G

FROM EXISTING

5-WAY SWITCH

'SW-48A'

400A 30A 60A

EXST

PANEL

TPP

EXST

AHU

RM 112

AHU #1

MECH

RM

SPACE

G

100A

EXST

PANEL

6-EL

30A

SPARE SPARE

100A

EXST

PANEL

100A

EXST

PANEL

EXST

PANEL

100A

EXST

PANEL

EXST

PANEL

LPA

200A

EXST

PANEL

NTPP

EXST

3P

RM 144

150A

SE

MECH

RM

EXST

4P

RM 120

175A

EXST

AHU

MECH

RM

350A

EXST

PANEL

DP

BYPASS

SWITCH

FEED

UNKNOWN

LOAD

SWBD 'DP' 1600A

208/120V, 3P, 4W, NON-CRITICAL LOAD

15A

EXST

AHU

RM 111

SPACE

300A

EXST SW

COURT-

YARD

MECH RM

1200A

SPARE SPACE SPACE

100A 100A

SPARE SPARE

Δ

Y

1600A

500 KW XFMR

13.8K, 3PH, PRIMARY

208V, 3PH, SECONDARY

FROM EXISTING

5-WAY SWITCH

'SW-48A'

MTS

SWBD 'DP' 1600A

208/120V, 3 PH

CRITICAL LOAD

1600A

MAIN

BREAKER

SCALE:

ELECTRICAL SINGLE-LINE DIAGRAM OF SWBD 'DP-1' - EXISTING

NONE

SCALE:

ELECTRICAL SINGLE-LINE DIAGRAM OF SWBD 'DP' - EXISTING AND DEMOLITION

NONE

ATS

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_E-601.dwg, 1/16/2018 12:19:28 PM

E-602

G

B

O G

I A

T Z

I D

I S

G

B

O G

I A

T Z

I D

I S

E L E

C T

R I C

A L

S

I N

G L E

L I N

E

D

I A

G R

X

I S

T I N

V

I S

E D

L

C

O L

E M

A N

S X

F

G

B

E A

R D

S X

F

P A

F B

F

L U

S A

F

T

H

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

I

T

E

D E

L I V

E R

Y

N

O

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

S U

B M

I T

T E

D

B

Y

R E

V I E

W E

D

B

Y

D A

T E

SHEET

IDENTIFICATION

C O

N T

R A

F

A D

E I S

R A

N G

E

A

R C

H I T

E C

T E

N G

I N

E E

R

I N

S P

E C

T I O

N

S

E R

V I C

E S

F A

D n g i n e e r i n g I n c

L L

E N

E A

A

B

2 3

C

1 2 3

4 5

4 5

C

D

A

B

D

An O ne id a N at io n Co m pa ny

C O

N S

O L I D

A T

E

B

A C

K U

P

P

O W

S

T E

M S

C O

FLAG NOTES:

1. PROVIDE (1) NEW 500A, 3 PHASE THERMAL MAGNETIC BREAKER IN EXISTING GE

SPECTRA SERIES SWITCHBOARD 'DP1' TO FEED EXISTING SWITCHBOARD 'DP' IN ROOM

MECH 3. BREAKER SHALL BE TYPE 'SGD' OR EQUAL.

2. PROVIDE 2 SETS OF (4) #500 KCMIL, #2 GROUND IN 4" CONDUIT BETWEEN SWBDs 'DP1'

AND 'DP'.

3. CONTRACTOR SHALL PROVIDE PHENOLIC NAMEPLATES WITH 1/4" HIGH BLOCK STYLE

WHITE LETTERING ON BLACK BACKGROUND, MATTE FINISH WITH SQUARE CORNERS.

NAMEPLATES SHALL IDENTIFY CRITICAL AND NON-CRITICAL SECTIONS, AND MAIN

DISCONNECT SECTION OF EXISTING SWBD 'DP'. AFFIX LABELS TO APPLICABLE

SECTIONS.

750 KW XFMR

13.8K, 3PH, PRIMARY

208V, 3PH, SECONDARY

G

FROM EXISTING

5-WAY SWITCH

'SW-48A'

GENERAL NOTE:

1. SCOPE OF WORK IS TO RECONFIGURE (2) EXISTING EMERGENCY POWER SYSTEMS

PLACING CRITICAL LOADS ON EXISTING 600 KW GENERATOR. REMOVE AND RETAIN

EXISTING 350 KW GENERATOR, ATS, FUEL TANK AND RETURN TO GOVERNMENT.

INSTALL NEW CONDUIT AND CONDUCTORS TO FEED EMERGENCY PANELS AS REQUIRED.

SWBD 'DP' 1600A

208/120V, 3 PH

CRITICAL LOAD

400A

AHU #1

MECH

RM

SPARE EXST

PNL

EXST

PNL

LPA

EXST

PNL

NTPP

EXST

3P

RM 144

150A 350A

BYPASS

SWITCH

FEED

EXST

AHU

RM 111

100A30A 60A

EXST

PANEL

TPP

EXST

AHU

RM 112

SPACE

100A

EXST

PANEL

6-EL

30A

SPARE

100A

EXST

PNL

100A

EXST

PNL

100A

EXST

PNL

200A

SE

MECH

RM

EXST

4P

RM 120

175A

EXST

PNL

A/H

MECH

RM

EXST

PANEL

DP

15A

SPACE

300A

EXST SW

COURT-

YARD

MECH RM

1200A

SPARE SPACE

100A

SPARE SPARE

SPACE

SWBD 'DP1' 2000A

208/120V, 3 PH, 4 W

(42,000 AIC)

350A 400A 400A 400A

EXST

UPS

RM 105

EXST

PANEL

PP105

400A

EXST

PANEL

PP109

400A

EXST

PANEL

PP103

400A

400A

EXST

PANEL

PP104

400A

100A

GEN

100A

60A

TVSS

EXST

PANEL

PP109A

100A

UNKNOWN

LOAD

1600A

2000A

CB SER

ATS-1

2000A

600 KW

208Y/120V

2000A CB

Δ

Y

500A

SWBD 'DP' 1600A

208/120V, 3P, 4W, NON-CRITICAL LOAD

1600A

MAIN

BREAKER

3 3 3

MTS-

ETR

SCALE:

ELECTRICAL SINGLE-LINE DIAGRAM OF SWBD 'DP1' - REVISED

NONE

SCALE:

ELECTRICAL SINGLE-LINE DIAGRAM OF SWBD 'DP' - REVISED

NONE

X:\SXHT\14-1046 Consolidate Backup Power Systems, B533\DWG\14-1046_E-602.dwg, 1/16/2018 12:19:30 PM

Sheets and Views
G-001 LOCATION MAP, PROJECT AREA AND DRAWING INDEX
E-001 ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS
ED-101 PARTIAL ELECTRICAL PLAN - DEMOLITION
E-101 PARTIAL ELECTRICAL PLAN - NEW CONSTRUCTION
E-601 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING & DEMO
E-602 ELECTRICAL SINGLE-LINE DIAGRAM - EXISTING & REVISED
2018-01-16T14:37:22-0500
KIBBEY.RICHARD.A.JR.1067247635
2018-01-16T14:45:01-0500
NOEGEL.MARK.A.1065891146
2018-01-17T07:19:57-0500
MARCH.JUAN.JR.1070140957
2018-02-19T14:26:52-0500
DEGUZMAN.DANILO.B.1139909018
2018-02-21T15:58:04-0500
FISHER.LAURIE.B.1292476791
2018-03-29T14:14:56-0400
MORE.DALLAS.Z.1087809486
2018-03-29T14:40:28-0400
ALAMO.SAMANTHA.MARIE.1454416011
2019-02-12T15:51:46-0500
SKUPIEN.JEFFREY.J.1229014770

File details come from the government source that posted it.