B320_DRAWING_-_PAFP201.pdf
PDF 51 KB Posted
- Attached to
- Repair Base Fire Systems
- Solicitation number
- F8R3CE7177AW02-01
About this file
B320 DRAWING - 7
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MASTER_Q&A_DOCUMENT.pdf | ||
| B320_DRAWING_-_PAFP101.pdf | ||
| B320_DRAWING_-_PAFP105.pdf | ||
| B320_DRAWING_-_PAFP106.pdf | ||
| B320_DRAWING_-_PAFP102.pdf | ||
| B320_DRAWING_-_PAFP103.pdf | ||
| B320_DRAWING_-_PAFP104.pdf | ||
| B258_Fire_Alarm_Control_panel__4.jpg | JPG image | |
| B258_Fire_Alarm_Control_panel__5.jpg | JPG image | |
| B258_Fire_Alarm_Control_panel__2.jpg | JPG image | |
| B258_Fire_Alarm_Control_panel__1.jpg | JPG image | |
| B258_Fire_Alarm_Control_panel__6.jpg | JPG image | |
| B258_Fire_Alarm_Control_panel__3.jpg | JPG image |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION DETAILS
SCALE: AS NOTED
AFFF EQUIP. ROOM 700
ASME RATED4'-010'-0HORIZONTAL175 PSI700PRIMARY #1AFFF EQUIP. ROOM
REMARKS
HEIGHT/LENGTH DIAMETER
(MAX. DIMS FT-IN)
OVERALL INSTALLATIONTYPE OF
INSTALLATION
CAPACITY
(GALS) PRESSURE
WORKINGSERVING
BLADDER TANK SCHEDULE
LOCATION
PRIMARY #2 175 PSI HORIZONTAL 10'-0 4'-0 ASME RATED
AREA OF OPERATION FOR WET PIPE SYSTEMS SHALL BE 3000 Sq.ft.
BLADDER MAINTENANCE ROOM
AFFF ROOM
MECHANICAL ROOM
ELECTRICAL/COMM. ROOMS
OFFICES/ADMIN.
AREA TYPE
AREAS SHALL BE PROTECTED BY AUTOMATIC FIRE SPRINKLER SYSTEMS IN ACCORDANCE WITH THE REQUIREMENTS
OF NFPA 13. COORDINATE ALL WORK WITH OTHER TRADES.
NOTES:
1.
2.
WET5000.25ORDINARY - GROUP 3
DENSITY (GPM/Sq.Ft.)
SPRINKLER DESIGN SCHEDULE
ORDINARY - GROUP 2
ORDINARY - GROUP 2
ORDINARY - GROUP 2
LIGHT
HAZARD CLASS HOSE ALLOWANCE (GPM)
0.20
0.20
0.10
0.20
WET
WET
WET/DRY
WET
WET
MANUAL RELEASE STATION - MONITOR NOZZLE SYSTEM
VALVE TAMPER SWITCH
WATERFLOW SWITCH - PRESSURE TYPE
ALARM HORN / STROBE
RATE COMPENSATION HEAT DETECTOR
AFFF DETECTION AND CONTROL LEGEND
R/C
AFFF DETECTION / CONTROL RISER DIAGRAM
RELEASE DELUGE VALVE - MONITORS
RELEASE PREACTION VALVE - ZONE 3
RELEASE PREACTION VALVE - ZONE 2
MONITOR SYSTEM
VALVE TAMPER
VALVE TAMPER SWITCHES SHALL BE GROUPED IN ZONES
NOT TO SCALE
MANUFACTURER'S INSTRUCTIONS AND APPROVAL/LISTING
BY THE CONTRACTOR IN ACCORDANCE WITH THE
AND AUDIBLE/VISIBLE DEVICES SHALL BE DETERMINED
THE EXACT PLACEMENT AND NUMBER OF DETECTORS
TROUBLE
ALARM
PER NFPA 72.
INDIVIDUAL ZONE.
EACH WATERFLOW SWITCH SHALL EACH BE ON A
REQUIREMENTS.
3.
2.
NOTES:
1.
CONTROL PANEL
FIRE ALARM
(FACP)
FACILITY
OVERHEAD PREACTION
ZONE 3
(SEE NOTE 1)
(SEE NOTE 1)
R/C
R/C
BATTERIES
24VDC
120VAC
G
START FIRE PUMPS
(MECH. ROOM 102)
CONTROL PANEL
AFFF SYSTEM
R/C
R/C
R/C
R/C
OVERHEAD PREACTION
ZONE 2
WATERFLOW
AUDIBLE/VISIBLE
AFFF RELEASE
NOTE: ARC OF ELEVATION SHALL BE
OSCILLATING MONITOR NOZZLE (N1, N2, N3)
NOT TO SCALE
30" MAX.
(BY CONTRACTOR)
CUSTOM STEEL
FRAME SUPPORT
12"±
MANUAL OPERATING
NOTE:
HANDLE
FIELD SET BY THE CONTRACTOR IN ACCORDANCE
MANUAL CONTROL
DISENGAGEMENT
NOZZLE STREAM
PATTERN ADJUSTMENT
FP201
RELEASE PREACTION VALVE - ZONE 1
ACTIVATE DRAINAGE DIVERSION VALVE
(SEE NOTE 1)
OVERHEAD PREACTION
ZONE 1
R/C R/CR/C
FP201
NOZZLE HOUSING
WITH MANUFACTURER'S RECOMMENDATIONS TO
ACHIEVE THE DESIGNED PATTERN REACH AND
RADIUS FOR EACH NOZZLE.
NOTE: PROVIDE AUXILIARY DRAIN AT LOW POINT OF
PIPING AT BASE OF MONITOR INLET PIPING.
UV/IR DETECTORS
WET500FIRE PUMP HOUSE
}UV/IR DETECTORS ARRANGEDON VOTING CONFIGURATION
(SEE NOTE 1)
PREACTION SYSTEM
LOW AIR PRESSURE
PREACTION SYSTEM
HIGH AIR PRESSURE
ORDINARY - GROUP 3 0.25
O 'K O N
C O M P A N Y
R
EM
A R K S
D A
TE
N O
REVISIONS
PROJECT NO.: 9141
DATE:
CHECKED:
DRAWN:
SHEET NUMBER:
En gi ne er s/
D es ig ne rs
P ea ch tr ee S tr ee t N .E
Su it e
A tl an ta G eo rg ia
(4
5-
FU
EL
S
YS
TE
M S
M A
IN
TE
N A N C E D O C K
1s t A
IR
R
EF
U
EL
IN
G W
IN
G
P
IT
TS
B U R G H I N
TE
R N A
TI
O N A L A
IR
P O R T, P
A
P
EN
N
SY
LV
A N
IA
A
IR
N
A
TI
O N A L G U A R D
P R O
JE
C T
JL
SQ
12/5/94
FINAL SUBMITTAL
Model