Exhibit A - Little Rock Equipment List.xlsx
XLSX spreadsheet 58 KB Posted
- Attached to
- J061--Electrical System Preventive Maintenance And Testing Services Federal contract opportunity
- Solicitation number
- 36C25622Q1188
About this file
This solicitation from the Central Arkansas VA Healthcare System seeks quotes for electrical system preventive maintenance and testing services at two VA medical centers in Little Rock and North Little Rock, Arkansas. The requirement is set aside for Veteran-Owned, Small Businesses under NAICS code 238210. Interested parties must be registered in the VA Vendor Information Pages and SAM, and submit all questions by August 22. Quotes are due by the date specified and must include the contractor's entity information from SAM, points of contact, completed price schedule, and required provisions. A mandatory site visit will be held on August 18 at the specified locations to view the sites. Exhibits A through E are provided for information only and are not part of the solicitation or resultant contract.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ALL IR SCAN
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | Comments IR SCAN Annual | |
| SUBSTATIONS | |||||
| GE-116 | MV Switchgear | 13800V | C | ||
| GE-117 | Substation A | 13800V - 480V | C | Breaker adjustments required for proper coordination | |
| GD-123 | Substation B | 13800V - 480V | C | Breaker adjustments required for proper coordination | |
| GD-123 | Substation C | 13800V - 480V | C | ||
| GD-123 | Substation D | 13800V - 480V | C | ||
| 3A-102 | Substation F | 13800V - 480V | C | Breaker adjustments required for proper coordination | |
| 3A-102 | Substation G | 13800V - 480V | C | ||
| GD-123 | Substation H | 13800V - 480V | B | Breaker adjustments required for proper coordination | |
| GD-134 | Generators | 480V | A | ||
| GD-134 | Substation EES | 480V | D | Clearance issues. Gear in poor condition. | |
| GD-134 | Substation EES-A | 480V | B | ||
| ATS'S | |||||
| GE-117 | ATS-CR1 | 480V | A | ||
| 2B-137 | ATS-CR2 | 480V | A | ||
| GE-117 | ATS-CR3 | 480V | B | ||
| GE-117 | ATS-E1 | 480V | D | Good Condition, Cable Replacement Suggested | |
| GE-117 | ATS-Q1 | 480V | D | Good Condition, Cable Replacement Suggested | |
| GD-133 | ATS-Q2 | 480V | A | ||
| GD133 | ATS-Q3 | 480V | B-C | No Neutral Used, Feeds MCC | |
| 3A-100 | ATS-Q4 | 480V | A | ||
| 8A-100 | ATS-Q5 | 480V | A | ||
| 8A-100 | ATS-Q6 | 480V | A | ||
| 3A-102 | ATS-Q7 | 480V | A | ||
| 1E-161 | ATS-Q8 | 480V | A | No Bypass Isolation | |
| GE-115 | ATS-Q9 | 480V | A | No Bypass Isolation | |
| GE-121 | ATS-Q10 | 480V | D | Good condition, Cable Replacement Suggested | |
| 3A-100 | ATS-Q11 | 480V | A | ||
| 3E-100 | ATS-Q12 | 480V | A | ||
| GE-117 | ATS-Q13 | 480V | A | No Bypass Isolation | |
| GD-123 | ATS-Q14 | 480V | A | ||
| GD-123 | ATS-Q15 | 480V | A | ||
| GD-123 | ATS-Q16 | 480V | A | ||
| 3A-100 | ATS-Q17 | 480V | A | ||
| GD-133 | ATS-MG | 480V | A | ||
| MCC'S | |||||
| GD-133 | MCC-1 | 480V | C | ||
| GD-133 | MCC-2 | 480V | C | ||
| GE-115 | MCC-3 | 480V | C | ||
| 1E-162 | MCC-4 | 480V | C | ||
| 3RD FLOOR | |||||
| NORTH EAST | MCC-NE | 480V | C | ||
| 3RD FLOOR | |||||
| NORTH WEST | MCC-NW | 480V | C | ||
| GD-129 | MCC-Q1A | 480V | C | ||
| GD-133 | MCC-Q1B | 480V | C | ||
| 3A-100 | MCC-QN | 480V | C | ||
| 3A-100 | MCC-QS | 480V | C | ||
| 3RD FLOOR | |||||
| SOUTH EAST | MCC-SE | 480V | C | ||
| 3RD FLOOR | |||||
| SOUTH WEST | MCC-SW | 480V | C | ||
| PANELBOARDS | |||||
| GD-128 | GCH2 | 480V | C | ||
| GB-110 | GCH3 | 480V | C | ||
| GD-130 | GCL1 | 208V | C | ||
| GC197 | GCL2 | 208V | |||
| GB-110 | GCL3 | 208V | C | ||
| GE-117 | GDCH | 480V | replaced 2020 | ||
| GE-117 | GDEH | 480V | D | ||
| GE-117 | GDH1 | 480V | replaced 2020 | ||
| GA-105 | GDH2 | 480V | C | ||
| GB-134 | GDH3 | 480V | replaced 2020 | ||
| GE-117 | GDH4 | 480V | replaced 2020 | ||
| GD-123 | GDH5 | 480V | replaced 2020 | ||
| GF-140 | GDH6 | 480V | A | ||
| GE-117 | GDHX | 480V | D | ||
| GE-117 | GDQH | 480V | replaced 2020 | ||
| GD-123 | GDQH2 | 480V | A | ||
| GD-133 | GDQH4 | 480V | B | ||
| GD-123 | GDQH5 | 480V | D | ||
| GE-117 | GEH1 | 480V | C | ||
| GD-112 | GEH2 | 480V | C | ||
| GC-138 | GEH3 | 480V | replaced 2020 | ||
| GB-110 | GEH4 | 480V | C | ||
| GF-140 | GEH5 | 480V | A | ||
| GE-117 | GEL1 | 208V | C | ||
| GD-112 | GEL2 | 208V | C | ||
| GC197 | GEL2A | 208V | |||
| GC-138 | GEL3 | 208V | C | ||
| GF-140 | GEL5 | 208V | A | ||
| GE-117 | GH1 | 480V | C | ||
| GD-128 | GH2 | 480V | C | ||
| GD-112 | GH3 | 480V | D | ||
| GC-138 | GH4 | 480V | C | ||
| GA-105 | GH5 | 480V | C | ||
| GB-110 | GH6 | 480V | D | ||
| GB-134 | GH7 | 480V | C | ||
| GE-123 | GH8 | 480V | C | ||
| GC-162 | GH9 | 480V | F | 240V Panel with 480V connected | |
| GD-139 | GH9 (MISLABELED) | 480V | C | ||
| GE-117 | GH10 | 480V | C | ||
| GF-140 | GH12 | 480V | A | ||
| GC-167 | GHK | 480V | C | ||
| GD-133 | GHMG | 480V | D | ||
| GE-123 | GHP1 | 480V | C | ||
| GE-121 | GHP2 | 480V | C | ||
| GE-117 | GL1 | 208V | C | ||
| GD-128 | GL2 | 208V | C | ||
| GD-139 | GL2 (139) | 208V | C | ||
| GD-112 | GL3 (1) | 208V | C | ||
| GD-112 | GL3 (2) | 208V | C | ||
| GC-138 | GL4 (1) | 208V | C | ||
| GC-138 | GL4 (2) | 208V | C | ||
| GA-105 | GL5 | 208V | C | ||
| GB-110 | GL6 (1) | 208V | C | ||
| GB-110 | GL6 (2) | 208V | C | ||
| GB-134 | GL7 (1) | 208V | replaced 2020 | ||
| GB-134 | GL7 (2) | 208V | replaced 2020 | ||
| GC-162 | GL9 | 208V | A | ||
| GE-117 | GL10 | 208V | C | ||
| GF-140 | GL11 | 208V | A | ||
| GF-140 | GL12 | 208V | A | ||
| GF-140 | GL13 | 208V | A | ||
| GD-133 | GLB | 208V | C- | Surface rust | |
| GD-133 | GLMG | 208V | A | ||
| GE-123 | GPL1 | 208V | C | ||
| GC-157 | GPL2 | 208V | C | ||
| GC-155 | GPL3 | 208V | C | ||
| GD-114 | GPL4A | 208V | C* | ||
| GD-114 | GPL4B | 208V | C | ||
| GD-101 | GPL4C | 208V | C | ||
| GD-114B | GPL5 | 208V | C | ||
| GC-124 | GPL6 | 208V | C* | ||
| GC-116 | GPL7 | 208V | C | ||
| GC-112 | GPL8 | 208V | C* | ||
| GC-114 | GPL9 | 208V | C* | ||
| GC-128 | GPL10 | 208V | C* | ||
| GC-135 | GPL11 | 208V | C* | ||
| GC-136 | GPL12 | 208V | C* | ||
| GP-143 | GPL13 | 208V | C | ||
| GC-150 | GPL14 | 208V | C | ||
| GC-149 | GPL15 | 208V | C* | ||
| GC-147 | GPL16 | 208V | C* | ||
| GA-105 | GPL17 | 208V | C | ||
| GC-167 | GPL18 (1) | 208V | C | ||
| GC-167 | GPL18 (2) | 208V | C | ||
| GB-165 | GPL19 | 208V | C* | ||
| GB-190 | GPL21 | 208V | C | ||
| GB-106 | GPL22 | 208V | C | ||
| GB-113 | GPL23 | 208V | C | ||
| GB-115 | GPL24 | 208V | C* | ||
| GB-103 | GPL25 | 208V | C | ||
| GB-101 | GPL26 | 208V | C | ||
| GC-106 | GPL27 | 208V | C* | ||
| GC-103 | GPL28 | 208V | C | ||
| GC-101 | GPL29 | 208V | C* | ||
| GB-131 | GPL30 | 208V | C* | ||
| GB-136 | GPL31 | 208V | C* | ||
| GB-130 | GPL32 | 208V | C* | ||
| GB-118 | GPL33 | 208V | C* | ||
| GB-120 | GPL34 | 208V | C | ||
| GB-122 | GPL35 | 208V | C* | ||
| GF-115 | GPL37 | 208V | A** | ||
| GF-114 | GLP38 | 208V | A** | ||
| GF-107 | GLP39 | 208V | A** | ||
| GF-106 | GLP40 | 208V | A** | ||
| GF-105 | GLP41 | 208V | A** | ||
| GF-104 | GLP42 | 208V | A** | ||
| GF-126 | GLP43 | 208V | A** | ||
| GF-127 | GLP44 | 208V | A** | ||
| GF-122 | GLP45 | 208V | A** | ||
| GE-117 | GQH1 | 480V | C | ||
| GD-128 | GQH2 | 480V | C | ||
| GA-105 | GQH3 | 480V | C | ||
| GB-134 | GQH4 | 480V | C | ||
| GE-117 | GQH5 | 480V | B | ||
| GE-123 | GQH6 | 480V | C | ||
| GF-140 | GQH7 | 480V | A | ||
| GF-140 | GQH8 | 480V | A | ||
| GD-130 | GQHB | 480V | C | ||
| GE-121 | GQHP | 480V | A | ||
| GD-123 | GQHP ? | 480V | B | ||
| GE-117 | GQL1 | 208V | C | ||
| GC-138 | GQL2 (1) | 208V | C | ||
| GC-138 | GQL2 (2) | 208V | C | ||
| GA-105 | GQL3 (1) | 208V | C | ||
| GA-105 | GQL3 (2) | 208V | C | ||
| GB-134 | GQL4 | 208V | C | ||
| GB-110 | GQL5 | 208V | C | ||
| GE-123 | GQL6 (Mislabeled) | 208V | A | ||
| GC-138 | GQL6 | 208V | C | ||
| GB-110 | GQL7 | 208V | C | ||
| GB-110 | GQL8 | 208V | C | ||
| GE-123 | GQL9 | 208V | C | ||
| GF-140 | GQL10 | 208V | A | ||
| GF-140 | GQL11 | 208V | A | ||
| GF-140 | GQL12 | 208V | A | ||
| GF-140 | GQL13 | 208V | A | ||
| GF-140 | GQL14 | 208V | A | ||
| GF-140 | GQL15 | 208V | A | ||
| GD-123 | GQL16 | 208V | A | ||
| GD-129 | GQLB | 208V | C | ||
| GD-134 | GQLG | 208V | C- | Extra holes in top of enclosure | |
| GD-133 | HP-1 | 480V | A | Breaker trip setting adjustment suggested | |
| GD-133 | LP-1 | 208V | A | ||
| GB-110 | Unmarked (XMAS) | 208V | A | ||
| 1D-176 | 1CL1 | 208V | C | ||
| 1D-131 | 1CL2 | 208V | A | ||
| 1E-110 | 1DH1 | 480V | C | ||
| 1A-113 | 1DH2 | 480V | C- | Bent Enclosure | |
| 1B-154 | 1DH3 | 480V | C | ||
| 1D-131 | 1DH4 | 480V | A | ||
| 1E-162 | 1DQH1 | 480V | D | ||
| 1E-189 | 1E-189 | 480V | ? | MARKED ON 1DH2, UNABLE TO LOCATE | |
| 1E-205 | 1E-205 | 208V | D | ||
| 1E-110 | 1EH1 | 480V | C | ||
| 1D-176 | 1EH2 | 480V | C | ||
| 1C-158 | 1EH3 | 480V | C | ||
| 1B-168 | 1EH4 | 480V | C | ||
| 1E-110 | 1EL1 | 208V | C- | Missing Hardware (No Latch) | |
| 1D-176 | 1EL2 | 208V | C | ||
| 1C-158 | 1EL3 | 208V | C | ||
| 1B-168 | 1EL4 | 208V | C | ||
| 1F138 | 1FCH1 | 480V | |||
| 1F138 | 1FCL1 sec 1 | 208V | |||
| 1F138 | 1FCL1 sec 2 | 208V | |||
| 1F138 | 1FCL2 sec 1 | 208V | |||
| 1F138 | 1FCL2 sec 2 | 208V | |||
| 1F138 | 1FEQL1 | 208V | |||
| 1F138 | 1FLSH1 | 480V | |||
| 1F138 | 1FNL1 sec 1 | 208V | |||
| 1F138 | 1FNL1 sec 2 | 208V | |||
| 1F138 | 1FNL2 | 208V | |||
| 1F138 | 1FEQH1 | 480V | |||
| 1F138 | 1FNH1 | 480V | |||
| 1E-110 | 1H1 | 480V | C | ||
| 1E-161 | 1H2 | 480V | C | ||
| 1D-176 | 1H3 | 480V | D | ||
| 1D-116 | 1H5 | 480V | D | ||
| 1A-113 | 1H6 | 480V | C | ||
| 1B-168 | 1H8 | 480V | C | ||
| 1B-154 | 1H9 | 480V | C | ||
| 1D-131 | 1H10 | 480V | A | ||
| 1B-161A | 1HK | 480V | C | ||
| 1E-161 | 1HX1 | 480V | replaced 2020 | ||
| 1A-113 | 1HX2 | 480V | C | ||
| 1E-176 | 1HX3 | 480V | |||
| 1E-110 | 1L1 (1) | 208V | C | ||
| 1E-110 | 1L1 (2) | 208V | C | ||
| 1E-161 | 1L2 | 208V | C | ||
| 1D-176 | 1L3 (1) | 208V | C | ||
| 1D-176 | 1L3 (2) | 208V | C | ||
| 1D-116 | 1L5 (1) | 208V | C | ||
| 1D-116 | 1L5 (2) | 208V | C | ||
| GA-113 | 1L6 (1) | 208V | C | ||
| GA-113 | 1L6 (2) | 208V | C | ||
| 1B-168 | 1L8 (1) | 208V | C | ||
| 1B-168 | 1L8 (2) | 208V | C | ||
| 1B-154A | 1L9 (A) | 208V | C | ||
| 1B-154A | 1L9 (B) | 208V | C- | Bent cover | |
| 1B-154A | 1L9 (C ) | 208V | A | ||
| 1B-154A | 1L9 (D) | 208V | C | ||
| 1E-110 | 1L10 | 208V | C- | Missing Hardware (No Latch) | |
| 1E-110 | 1L11 | 208V | B | ||
| 1D-131 | 1L13 | 208V | A | ||
| 1E-161 | 1LX1 | 208V | C | ||
| GA-113 | 1LX2 | 208V | C | ||
| 1E-161 | 1LX3 | 208V | A | ||
| 1D-178 | 1PL1 | 208V | C* | ||
| 1D-179 | 1PL2 | 208V | C* | ||
| 1D-159 | 1PL3 | 208V | C* | ||
| 1D-116 | 1PL4 | 208V | C | ||
| 1B-159A | 1PL6 (1) | 208V | C* | Cover was locked | |
| 1B-159A | 1PL6 (2) | 208V | C* | Cover was locked | |
| 1E-161 | 1QH1 | 480V | C | ||
| 1D-116 | 1QH2 | 480V | C | ||
| 1D-131 | 1QH3 | 480V | A | ||
| 1C-146 | 1QH6 | 480V | C | ||
| 1C-146 | 1QH6-A | 480V | C | ||
| 1C-158 | 1QH7 | 480V | C | ||
| 1E-161 | 1QHX | 480V | C | ||
| 1E-161 | 1QL1 | 208V | B | ||
| 1D-116 | 1QL2 | 208V | C | ||
| 1E-162 | 1QL3 | 208V | C | ||
| 1B-154A | 1QL4 | 208V | C | ||
| 1D-131 | 1QL5 | 208V | A | ||
| 1E-162 | 1QL6 | 208V | A | ||
| 1C158 | 1QL7 | 208V | |||
| 1C-146 | 1QL8(1) | 208V | C | ||
| 1C-146 | 1QL8(2) | 208V | C | ||
| 1C-146 | 1QL9(1) | 208V | C | ||
| 1C-146 | 1QL9(2) | 208V | C | ||
| 1C-158 | 1QL10(1) | 208V | C | ||
| 1C-158 | 1QL10(2) | 208V | C |
| 2B-137 | 2CH1 (1) | 480V | C | |
| 2B-137 | 2CH1 (2) | 480V | C | |
| 2B-137 | 2CH2 | 480V | C | |
| 2E-160 | 2CH3 | 480V | C | |
| 2C-107 | 2CH4 | 480V | D | |
| 2B-168 | 2CH5 | 480V | C | |
| 2B-137 | 2CL1 | 208V | C | |
| 2B-137 | 2CL2 | 208V | C | |
| 2E-160 | 2CL3 | 208V | C | |
| 2C-107 | 2CL4 | 208V | C | |
| 2B-168 | 2CL5 | 208V | C | |
| 2B-137 | 2DCH | 480V | C | |
| 2E-160 | 2DCH2 | 480V | C | |
| 2A-124A | 2DH1 | 480V | C | |
| 2A-113 | 2DH2 | 480V | C | |
| 2B-168 | 2DH3 | 480V | C | |
| 2A-124A | 2EH1 | 480V | C | |
| 2E-111 | 2EH2 | 480V | C | |
| 2D-110 | 2EH3 | 480V | C | |
| 2C-107 | 2EH4 | 480V | C | |
| 2A-124A | 2EL1 | 208V | C | |
| 2E-111 | 2EL2 | 208V | C | |
| 2D-110 | 2EL3 | 208V | C | |
| 2C-107 | 2EL4 | 208V | C | |
| 2A-124A | 2H2 | 480V | C | |
| 2E-160 | 2H3 | 480V | C | |
| 2E-111 | 2H4 | 480V | C | |
| 2D-110 | 2H5 | 480V | C | |
| 2D-168 | 2H6 | 480V | D | |
| 2A-113 | 2H7 | 480V | C | |
| 2C-158 | 2H8 | 480V | C | |
| 2C-107 | 2H9 | 480V | C | |
| 2B-168 | 2H10 | 480V | C | |
| 2B-137 | 2HX1 | 480V | C | |
| 2B-137 | 2L1 | 208V | C | |
| 2A-124A | 2L2 | 208V | C | |
| 2E-160 | 2L3 (1) | 208V | C | |
| 2E-160 | 2L3 (2) | 208V | C- | Missing Hardware (Door Latch) |
| 2E-111 | 2L4-L | 208V | C | |
| 2E-111 | 2L4-R | 208V | C | |
| 2D-110 | 2L5-L | 208V | D | Wiring issues inside of panel - panel |
replacement not required
| 2D-110 | 2L5-R | 208V | C | |
| 2D-168 | 2L6 | 208V | C | |
| 2A-113 | 2L7 | 208V | C- | Bent Cover |
| 2C-158 | 2L8-L | 208V | C | |
| 2C-158 | 2L8-R | 208V | C | |
| 2C-107 | 2L9 | 208V | D | Wiring - Double tapped Breakers. Sub panel required |
| 2B-168 | 2L10 | 208V | C | |
| 2A-124A | 2L11 | 208V | C | |
| 2B-151 | 2LX1 | 208V | C | |
| 2B-151 | 2LX2 | 208V | A | |
| 2E-141 | 2PL4 | 208V | C* | |
| 2D-184 | 2PL5 | 208V | C* | |
| 2E-105 | 2PL6 | 208V | C* | |
| 2E-107 | 2PL7 | 208V | C* | |
| 2E-138 | 2PL8 | 208V | C* | |
| 2E-135 | 2PL9 | 208V | C* | |
| 2E-110 | 2PL10 | 208V | C* | |
| 2E-127 | 2PL11 | 208V | C* | |
| 2E-114 | 2PL12 | 208V | C* | |
| 2E-119 | 2PL13 | 208V | C* | |
| 2D-134 | 2PL14 | 208V | C* | |
| 2D-162 | 2PL15 | 208V | C* | |
| 2D-169 | 2PL16 | 208V | C* | |
| 2D-171 | 2PL17 | 208V | C* | |
| 2D-173 | 2PL18 | 208V | C* | |
| 2D-176 | 2PL19 | 208V | C* | |
| 2D-183 | 2PL20 | 208V | C* | |
| 2A-113 | 2PL21 | 208V | C- | Missing Hardware |
| 2E-111 | 2QL2A | 208V | C | |
| 2E-111 | 2QL2B | 208V | C | |
| 2D-168 | 2QL3 | 208V | replaced 2020 | |
| 2D-168 | 2QL3A | 208V | C | |
| 2D-168 | 2QL3B | 208V | B | |
| 2B-151 | EH-1 | 480V | A | |
| 2B-151 | EL-1 | 208V | A | |
| 3A-104 | 3DH | 480V | C | |
| 3A-104 | 3DH2 | 480V | F | |
| 3A-100 | 3DH2A | 480V | A | |
| 3A-104 | 3DQH | 480V | C | |
| 3CE-PH | 3DQH12 | 480V | A | |
| 3A-104 | 3DQH2 | 480V | A | |
| 3A-104 | 3DQH2 (B) | 480V | A | |
| 3A-104 | 3H1 | 480V | C | |
| 3C-100 | 3H2 | 480V | C | |
| 3C-100 | 3L1 | 208V | C | |
| 3A-100 | 3LNE | 208V | C | |
| 3A-100 | 3LSW | 208V | C | |
| 3A-100 | 3QL | 208V | C | |
| 3CE-PH | 3QL1 | 208V | A | |
| 3A-100 | 3QL2 | 208V | C | |
| 3A-100 | NP1 | 480V | A | |
| 3A-100 | SUB PANEL - 3A | 208V | B | |
| 4A-109 | 4EH1 | 480V | C | |
| 4A-109 | 4EL1 | 208V | C- | Rust in corners |
| 4A-109 | 4H1 | 480V | C | |
| 4A-109 | 4H2 | 480V | C | |
| 4E-145 | 4L1-L | 208V | C | |
| 4E-145 | 4L1-R | 208V | C | |
| 4D-122 | 4L2-L | 208V | C | |
| 4D-122 | 4L2-R | 208V | C | |
| 4A-109 | 4L3-L | 208V | C | |
| 4A-109 | 4L3-R | 208V | C | |
| 4C-145 | 4L4-L | 208V | C- | Extra holes in top. Very crowded inside |
| 4C-145 | 4L4-R | 208V | C- | Extra holes in top. Very crowded inside |
| 4B-122 | 4L5-L | 208V | C | |
| 4B-122 | 4L5-R | 208V | C | |
| 4A-109 | 4L6 | 208V | B | |
| 4E-145 | 4QL1 | 208V | C | |
| 4D-122 | 4QL2 | 208V | C | |
| 4D-122 | 4QL2-B | 208V | A | |
| 4C-145 | 4QL4 | 208V | C | |
| 4B-122 | 4QL5 | 208V | C |
| 5D-137 | 5CL1 | 208V | ? | Area Under Construction | |
| 5C-129 | 5CL2 | 208V | A | ||
| 5A-110 | 5DQH | 480V | A | ||
| 5A-110 | 5EH1 | 480V | C | ||
| 5A-110 | 5EL1 | 208V | C | ||
| 5A-110 | 5H1 | 480V | C | ||
| 5E-145 | 5L1 (1) | 208V | C | ||
| 5E-145 | 5L1 (2) | 208V | C | ||
| 5D-1137 | 5L2 | 208V | ? | Area Under Construction | |
| 5A-110 | 5L3 (1) | 208V | C | ||
| 5A-110 | 5L3 (2) | 208V | C | ||
| 5C-129 | 5L4 (1) | 208V | C | ||
| 2C-129 | 5L4 (2) | 208V | C | ||
| 5B-122 | 5L5 (1) | 208V | C | ||
| 5B-122 | 5L5 (2) | 208V | C | ||
| 5C-129 | 5L6 (5L4.1) | 208V | C | ||
| 5C-129 | 5L7 | 208V | C | ||
| 5B-122 | 5L8 | 208V | C | ||
| 5D111 | 5L9 | 208V | |||
| 5C-122 | 5QH1 | 480V | B | ||
| 5C-122 | 5QH2 | 480V | B | ||
| 5E-145 | 5QL1 | 208V | C | ||
| 5D-137 | 5QL2 | 208V | ? | Area Under Construction | |
| 5C-122 | 5QL3 | 208V | B | ||
| 5C-129 | 5QL4 | 208V | C | ||
| 5B-122 | 5QL5 | 208V | C | ||
| 5B-122 | 5QL6 | 208V | A | ||
| 5C-141 | DP | 480V | B | ||
| 5E-145 | 5QL7 | 208V | A | ||
| 6B-121 | 6CL1-L | 208V | C | ||
| 6B-121 | 6CL1-R | 208V | C | ||
| 6A-109 | 6EH1 | 480V | C | ||
| 6A-109 | 6EL1 | 208V | C | ||
| 6A-109 | 6H1 | 480V | C | ||
| 6E-145 | 6L1-L | 208V | C | ||
| 6E-145 | 6L1-R | 208V | C | ||
| 6D-122 | 6L2-L | 208V | C | ||
| 6D-122 | 6L2-R | 208V | C | ||
| 6A-109 | 6L3-L | 208V | C | ||
| 6A-109 | 6L3-R | 208V | C | ||
| 6C-145 | 6L4-L | 208V | C | ||
| 6C-145 | 6L4-R | 208V | C | ||
| 6B-121 | 6L5-L | 208V | C | ||
| 6B-121 | 6L5-R | 208V | C | ||
| 6E-145 | 6L6 | 208V | A | ||
| 6E-145 | 6QL1 | 208V | C | ||
| 6D-122 | 6QL2 | 208V | C | ||
| 6C-145 | 6QL4 | 208V | C | ||
| 6B-121 | 6QL5 | 208V | C | ||
| 6C-145 | NP2 | 208V | A | ||
| 7A-113 | 7EH1 | 480V | C | ||
| 7E-108 | 7EH2 | 480V | B | ||
| 7A-113 | 7EL1 | 208V | C | ||
| 7E-108 | 7EL2 | 208V | B | ||
| 7A-113 | 7H1 | 480V | C | ||
| 7E-108 | 7H2 | 480V | B | ||
| 7D-116 | 7L2-L | 208V | D | ||
| 7D-116 | 7L2-R | 208V | C | ||
| 7A-113 | 7L3-L | 208V | C | ||
| 7A-113 | 7L3-R | 208V | C | ||
| 7C-145 | 7L4-L | 208V | C | ||
| 7C-145 | 7L4-R | 208V | C | ||
| 7C-145 | 7L4A | 208V | A | ||
| 7B-123 | 7L5-L | 208V | C | ||
| 7B-123 | 7L5-R | 208V | C | ||
| 7E-108 | 7L6-L | 208V | B | ||
| 7E-108 | 7L6-R | 208V | B | ||
| 7D-116 | 7L7 | 208V | B | ||
| 7D-116 | 7QL2 | 208V | C | ||
| 7C-145 | 7QL4 | 208V | C | ||
| 7B-123 | 7QL5 | 208V | C | ||
| PH (8TH FLOOR) | 8HP | 480V | C | ||
| PH (8TH FLOOR) | 8L1 | 208V | C | ||
| PH (8TH FLOOR) | 8QL1 | 208V | C | ||
| 9TH FLOOR | QHELEV1 | 480V | C | ||
| 9TH FLOOR | QHELEV2 | 480V | D | Enclosure bent and missing hardware | |
| Bldg. 2 | |||||
| SOUTH WALL | PANEL A | 208V | B |
| *Unable to survey panel. Panel original to building. Grade based on similar surveyed panels |
| **Unable to survey panel. Panel installed during Substation H upgrade. Grade based on similar surveyed panels |
| TRANSFORMERS | ||||
| GD-134A | T-GCL1 | 480V - 208V | replaced 2020 | |
| GB-110 | T-GCL3 | 480V - 208V | C | Needs 6" to back wall |
| GE-117 | T-GEL1 | 480V - 208V | D | Needs 6" to back wall |
| GD-112 | T-GEL2 | 480V - 208V | A | Needs 6" to back wall |
| GC-138 | T-GEL3 | 480V - 208V | replaced 2020 | |
| GF-140 | T-GEL5 | 480V - 208V | A | |
| GE-117 | T-GL1 | 480V - 208V | C | Needs 6" to back wall |
| GD-128 | T-GL2 | 480V - 208V | C | |
| GD-139 | T-GL2 (139) | 480V - 208V | C | |
| GD-112 | T-GL3 | 480V - 208V | replaced 2020 | |
| GC-138 | T-GL4 | 480V - 208V | C | Needs 6" to back wall |
| GA-105 | T-GL5 | 480V - 208V | replaced 2020 | |
| GB-110 | T-GL6 | 480V - 208V | C | Needs 6" to back wall |
| GB-134 | T-GL7 | 480V - 208V | C | Needs 6" to back wall |
| GC-162 | T-GL9 | 480V - 208V | D | Needs 6" to back wall |
| GE-117 | T-GL10 | 480V - 208V | C | |
| GF-140 | T-GL11 | 480V - 208V | B | Needs 6" to back wall |
| GD-133 | T-GLB | 480V - 208V | D | Not accessible, obstructions blocking cover |
| GD-133 | T-GLMG | 480V - 208V | D | No GEC |
| GE-117 | T-GQL1 | 480V - 208V | replaced 2020 | |
| GC-138 | T-GQL2 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GA-105 | T-GQL3 | 480V - 208V | C | Needs 6" to back wall |
| GB-134 | T-GQL4 | 480V - 208V | C | Needs 6" to back wall |
| GB-110 | T-GQL5 | 480V - 208V | C | Needs 6" to back wall |
| GC-138 | T-GQL6 | 480V - 208V | C | Needs 6" to back wall |
| GB-110 | T-GQL8 | 480V - 208V | B | |
| GE-117 | T-GQL9 | 480V - 208V | C | |
| GF-140 | T-GQL10 | 480V - 208V | C | Cable Replaced 2020 |
| GD-123 | T-GQL16 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GD-129 | T-GQLB | 480V - 208V | replaced 2020 | |
| GE-123 | T-GQT6 | 480V - 208V | D | Needs 6" to back wall |
| GD-133 | T-LP1 | 480V - 208V | D | Needs 6" to back wall |
| GD-128 | T-GCH2 | 480V - 208V | C |
| 1D-176 | T-1CL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-131 | T-1CL2 | 480V - 208V | C | |
| 1E-110 | T-1EL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-176 | T-1EL2 | 480V - 208V | replaced 2020 | |
| 1C-158 | T-1EL3 | 480V - 208V | replaced 2020 | |
| 1B-168 | T-1EL4 | 480V - 208V | replaced 2020 | |
| 1E-110 | T-1L1 | 480V - 208V | C | Needs 6" to back wall |
| 1E-161 | T-1L2 | 480V - 208V | replaced 2020 | |
| 1D-176 | T-1L3 | 480V - 208V | C | Needs 6" to back wall |
| 1D-116 | T-1L5 | 480V - 208V | C | Needs 6" to back wall |
| 1A-113 | T-1L6 | 480V - 208V | C | Needs 6" to back wall |
| 1B-168 | T-1L8 | 480V - 208V | C | Needs 6" to back wall |
| 1B-154 | T-1L9 | 480V - 208V | D | Running hot |
| 1E-110 | T-1L10 | 480V - 208V | replaced 2020 | |
| 1D-131 | T-1L13 | 480V - 208V | C | |
| 1E-161 | T-1LX1 | 480V - 208V | C | Needs 6" to back wall |
| 1A-113 | T-1LX2 | 480V - 208V | C | Needs 6" to back wall |
| 1E-161 | T-1LX3 | 480V - 208V | C | |
| 1E-161 | T-1QL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-118 | T-1QL2 | 480V - 208V | C | Needs 6" to back wall |
| 1E-162 | T-1QL3 | 480V - 208V | C | |
| 1B-154 | T-1QL4 | 480V - 208V | C | Needs 6" to back wall |
| 1D-131 | T-1QL5 | 480V - 208V | C | |
| 1E-162 | T-1QL6 | 480V - 208V | D | Needs 6" to back wall |
| 1C-146 | T-1QL8 | 480V - 208V | C | Needs 6" to back wall |
| 1C158 | T-1QL7 | 480V - 208V | ||
| 1C-158 | T-1QL10 | 480V - 208V | D | Poor condition |
| 1F138 | T-FCL1 | 480V - 208V | ||
| 1F138 | T-FNL1 | 480V - 208V | ||
| 1B-154 | T-FRYER | 480V - 208V | A | Needs 6" to back wall |
| 1E-205 | T-TABLE | 480V - 208V | C |
| 2B-137 | T-2CL1 | 480V - 208V | D | Needs 6" to back wall |
| 2B-136 | T-2CL2 | 480V - 208V | C | |
| 2E-160 | T-2CL3 | 480V - 208V | B | Needs 6" to back wall |
| 2C-107 | T-2CL4 | 480V - 208V | C | Needs 6" to back wall |
| 2B-168 | T-2CL5 | 480V - 208V | C | Needs 6" to back wall |
| 2A-124A | T-2EL1 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2EL2 | 480V - 208V | C | Needs 6" to back wall |
| 2C-110 | T-2EL3 | 480V - 208V | replaced 2020 | |
| 2C-107 | T-2EL4 | 480V - 208V | replaced 2020 | |
| 2B-137 | T-2L1 | 480V - 208V | C | |
| 2A-124A | T-2L2 | 480V - 208V | C | Needs 6" to back wall |
| 2E-160 | T-2L3 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2L4 | 480V - 208V | C | Needs 6" to back wall |
| 2C-110 | T-2L5 | 480V - 208V | C | Needs 6" to back wall |
| 2D-168 | T-2L6 | 480V - 208V | C | Needs 6" to back wall |
| 2A-113 | T-2L7 | 480V - 208V | C | Needs 6" to back wall |
| 2C-158 | T-2L8 | 480V - 208V | C | Needs 6" to back wall |
| 2C-107 | T-2L9 | 480V - 208V | replaced 2020 | |
| 2B-168 | T-2L10 | 480V - 208V | C | Needs 6" to back wall |
| 2A-124A | T-2L11 | 480V - 208V | D | Needs 6" to back wall |
| 2B-151 | T-2LX1 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2QL2 | 480V - 208V | C | Needs 6" to back wall |
| 2D-168 | T-2QL3 | 480V - 208V | C | Needs 6" to back wall |
| 2B-151 | T-EL1 | 480V - 208V | D | Needs 6" to back wall |
| 3L-100 | T-3L1 | 480V - 208V | B | Needs 6" to back wall |
| 3A-100 | T-3LNE | 480V - 208V | C | Needs 6" to back wall |
| 3A-100 | T-3LSW | 480V - 208V | C | |
| 3A-100 | T-3QL | 480V - 208V | A | Needs 6" to back wall |
| 3C-PH | T-3QL1 (PH) | 480V - 208V | C | |
| 3A-100 | T-3QL2 | 480V - 208V | D | Needs 6" to back wall |
| 4A-109 | T-4EL1 | 480V - 208V | replaced 2020 | |
| 4E-145 | T-4L1 | 480V - 208V | C | Needs 6" to back wall |
| 4D-122 | T-4L2 | 480V - 208V | C | Needs 6" to back wall |
| 4A-109 | T-4L3 | 480V - 208V | C | Needs 6" to back wall |
| 4C-145 | T-4L4 | 480V - 208V | C | Needs 6" to back wall |
| 4B-122 | T-4L5 | 480V - 208V | C | Needs 6" to back wall |
| 4A-109 | T-4L6 | 480V - 208V | B | |
| 4E-145 | T-4QL1 | 480V - 208V | C | Needs 6" to back wall |
| 4D-122 | T-4QL2 | 480V - 208V | C | Needs 6" to back wall |
| 4C-145 | T-4QL4 | 480V - 208V | C | Needs 6" to back wall |
| 4B-122 | T-4QL5 | 480V - 208V | C | Housing, Needs clearance |
| 5D-137 | T-5CL1 | 480V - 208V | ? | Area Under Construction |
| 5C-129 | T-5CL2 | 480V - 208V | C | |
| 5D137 | T-5L2 | |||
| 5C-129 | T-5L6 | 480V - 208V | C | |
| 5D111 | T-5L9 | 480V - 208V | ||
| 5C-122 | T-5QL3 | 480V - 208V | A | |
| 5B-122 | T-5QL6 | 480V - 208V | A | |
| 5E-145 | T-(5E-145) | 480V - 208V | C | |
| 6B-121 | T-6CL1 | 480V - 208V | C | Needs 6" to back wall |
| 6A-109 | T-6EL1 | 480V - 208V | replaced 2020 | |
| 6E-145 | T-6L6 | 480V - 208V | B | Needs 6" to back wall |
| 6C-145 | T-NP2 | 480V - 208V | A |
| 7E-108 | T-7EL2 | 480V - 208V | C | Needs 6" to back wall |
| 7C-145 | T-7L4 | 480V - 208V | C | |
| 7E-108 | T-7L6 | 480V - 208V | C | Needs 6" to back wall |
| 7D-116 | T-7L7 | 480V - 208V | B | Needs 6" to back wall |
| Notes: No Vibration Isolators found on any transformers. Transformer clearance of 6" is required by UL1591, not NEC |
SUBSTATIONS
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month & IR Annual |
| SUBSTATIONS | ||||
| GE-116 | MV Switchgear (UTIL-001 & UTIL-002) | 13800V | C | |
| GE-117 | Substation A (AA & AB) | 13800V - 480V | C | Breaker adjustments required for proper coordination |
| GD-123 | Substation B (B1) | 13800V - 480V | C | Breaker adjustments required for proper coordination |
| GD-123 | Substation C (C1) | 13800V - 480V | C | |
| GD-123 | Substation D (D1) | 13800V - 480V | C | |
| 3A-102 | Substation F (F1) | 13800V - 480V | C | Breaker adjustments required for proper coordination |
| 3A-102 | Substation G (G1) | 13800V - 480V | C | |
| GD-123 | Substation H (H1) | 13800V - 480V | B | Breaker adjustments required for proper coordination |
| GD-134 | Generator Main (GEN-1) | 480V | A | |
| GD-134 | Substation EES | 480V | D | Clearance issues. Gear in poor condition. |
| GD-134 | Substation EES-A | 480V | B |
MVL SW
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month & IR Annual |
| MEDIUM VOLTAGE FUSED SWITCHES | ||||
| GE-117 | Substation A-A (SW-AA) | 13800V | C | fused switch |
| GE-117 | Substation A-B (SW-AB) | 13800V | C | fused switch |
| GD-123 | Substation B (SW-B1) | 13800V | C | fused switch |
| GD-123 | Substation C (SW-C1) | 13800V | C | fused switch |
| GD-123 | Substation D (SW-D1) | 13800V | C | fused switch |
| 3A-102 | Substation F (SW-F1) | 13800V | C | fused switch |
| 3A-102 | Substation G (SW-G1) | 13800V | C | fused switch |
| GD-123 | Substation H (SW-H1) | 13800V | B | fused switch |
| outside | PV MAIN 1 HVL | 13800V | LI switch with fixed mounted vacuum circuit breaker | |
| outside | PV MAIN 2 HVL | 13800V | LI switch with fixed mounted vacuum circuit breaker |
PROTECTIVE RELAYS
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month |
| PROTECTIVE RELAYS | ||||
| GE-116 | MV Switchgear | 13800V | ||
| GE-117 | Substation A | 13800V - 480V | ||
| GD-123 | Substation B | 13800V - 480V | ||
| GD-123 | Substation C | 13800V - 4160V | ||
| GD-123 | Substation D | 13800V - 4160V | ||
| 3A-102 | Substation F | 13800V - 480V | ||
| 3A-102 | Substation G | 13800V - 480V | ||
| GD-123 | Substation H | 13800V - 480V | ||
| GD-134 | Substation EES | 480V | ||
| GD-134 | Substation EES-A | 480V | ||
| outside | PV MAIN 1 HVL | 13800V | Schwietzer SEL 751 | |
| outside | PV MAIN 2 HVL | 13800V | Schwietzer SEL 751 |
ATS'S
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| ATS'S | ||||
| Location | Equipment | Voltage | Assessment | comments IR SCAN Annual |
| GE-117 | ATS-CR1 | 480V | A | |
| 2B-137 | ATS-CR2 | 480V | A | |
| GE-117 | ATS-CR3 | 480V | B | |
| GE-117 | ATS-E1 | 480V | D | Good Condition, Cable Replacement Suggested |
| GE-117 | ATS-Q1 | 480V | D | Good Condition, Cable Replacement Suggested |
| GD-133 | ATS-Q2 | 480V | A | |
| GD133 | ATS-Q3 | 480V | B-C | No Neutral Used, Feeds MCC |
| 3A-100 | ATS-Q4 | 480V | A | |
| 8A-100 | ATS-Q5 | 480V | A | |
| 8A-100 | ATS-Q6 | 480V | A | |
| 3A-102 | ATS-Q7 | 480V | A | |
| 1E-161 | ATS-Q8 | 480V | A | No Bypass Isolation |
| GE-115 | ATS-Q9 | 480V | A | No Bypass Isolation |
| GE-121 | ATS-Q10 | 480V | D | Good condition, Cable Replacement Suggested |
| 3A-100 | ATS-Q11 | 480V | A | |
| 3E-100 | ATS-Q12 | 480V | A | |
| GE-117 | ATS-Q13 | 480V | A | No Bypass Isolation |
| GD-123 | ATS-Q14 | 480V | A | |
| GD-123 | ATS-Q15 | 480V | A | |
| GD-123 | ATS-Q16 | 480V | A | |
| 3A-100 | ATS-Q17 | 480V | A | |
| GD-133 | ATS-MG | 480V | A |
MCC'S
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month & IR Scan Annual | |
| MCC'S | |||||
| GD-133 | MCC-1 | 480V | D | Good condition, Breaker Replacement Suggested | |
| GD-133 | MCC-2 | 480V | C | ||
| GE-115 | MCC-3 | 480V | C | ||
| 1E-162 | MCC-4 | 480V | C | ||
| 3RD FLOOR | |||||
| NORTH EAST | MCC-NE | 480V | C | ||
| 3RD FLOOR | |||||
| NORTH WEST | MCC-NW | 480V | C | ||
| GD-129 | MCC-Q1A | 480V | C | ||
| GD-133 | MCC-Q1B | 480V | C | ||
| 3A-100 | MCC-QN | 480V | C | ||
| 3A-100 | MCC-QS | 480V | C | ||
| 3RD FLOOR | |||||
| SOUTH EAST | MCC-SE | 480V | C | ||
| 3RD FLOOR | |||||
| SOUTH WEST | MCC-SW | 480V | C |
PANELBOARDS
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month (250A UP) & IR Scan Annual |
| PANELBOARDS | ||||
| GD-128 | GCH2 | 480V | C | |
| GB-110 | GCH3 | 480V | C | |
| GD-130 | GCL1 | 208V | C | |
| GC197 | GCL2 | 208V | ||
| GB-110 | GCL3 | 208V | C | |
| GE-117 | GDCH | 480V | D | Enclosure bent and missing hardware |
| GE-117 | GDEH | 480V | D | Breaker Replacement Suggested |
| GE-117 | GDH1 | 480V | F | Enclosure condition, and one breaker fails AIC |
| GA-105 | GDH2 | 480V | C | |
| GB-134 | GDH3 | 480V | D | Enclosure bent, cover doesn't fit properly |
| GE-117 | GDH4 | 480V | F | Fails AIC, replacement required |
| GD-123 | GDH5 | 480V | F | Fails AIC, replacement required |
| GF-140 | GDH6 | 480V | A | |
| GE-117 | GDHX | 480V | D | Breaker Replacement Suggested |
| GE-117 | GDQH | 480V | D | Enclosure bent and missing hardware |
| GD-123 | GDQH2 | 480V | A | |
| GD-133 | GDQH4 | 480V | B | |
| GD-123 | GDQH5 | 480V | D | Breaker Replacement Suggested |
| GE-117 | GEH1 | 480V | C | |
| GD-112 | GEH2 | 480V | C | |
| GC-138 | GEH3 | 480V | C | |
| GB-110 | GEH4 | 480V | C | |
| GF-140 | GEH5 | 480V | A | |
| GE-117 | GEL1 | 208V | C | |
| GD-112 | GEL2 | 208V | C | |
| GC197 | GEL2A | 208V | ||
| GC-138 | GEL3 | 208V | C | |
| GF-140 | GEL5 | 208V | A | |
| GE-117 | GH1 | 480V | C | |
| GD-128 | GH2 | 480V | C | |
| GD-112 | GH3 | 480V | F | 240V Breaker Installed in 480V panel. |
| GC-138 | GH4 | 480V | C | |
| GA-105 | GH5 | 480V | C | |
| GB-110 | GH6 | 480V | D | Breaker Replacement Suggested |
| GB-134 | GH7 | 480V | C | |
| GE-123 | GH8 | 480V | C | |
| GC-162 | GH9 | 480V | F | 240V Panel with 480V connected |
| GD-139 | GH9 (MISLABELED) | 480V | C | |
| GE-117 | GH10 | 480V | C | |
| GF-140 | GH12 | 480V | A | |
| GC-167 | GHK | 480V | C | |
| GD-133 | GHMG | 480V | D | Breaker Replacement Suggested |
| GE-123 | GHP1 | 480V | C | |
| GE-121 | GHP2 | 480V | C | |
| GE-117 | GL1 | 208V | C | |
| GD-128 | GL2 | 208V | C | |
| GD-139 | GL2 (139) | 208V | C | |
| GD-112 | GL3 (1) | 208V | C | |
| GD-112 | GL3 (2) | 208V | C | |
| GC-138 | GL4 (1) | 208V | C | |
| GC-138 | GL4 (2) | 208V | C | |
| GA-105 | GL5 | 208V | C | |
| GB-110 | GL6 (1) | 208V | C | |
| GB-110 | GL6 (2) | 208V | C | |
| GB-134 | GL7 (1) | 208V | F | Significant water damage |
| GB-134 | GL7 (2) | 208V | D | Minor water damage |
| GC-162 | GL9 | 208V | A | |
| GE-117 | GL10 | 208V | C | |
| GF-140 | GL11 | 208V | A | |
| GF-140 | GL12 | 208V | A | |
| GF-140 | GL13 | 208V | A | |
| GD-133 | GLB | 208V | C- | Surface rust |
| GD-133 | GLMG | 208V | A | |
| GE-123 | GPL1 | 208V | C | |
| GC-157 | GPL2 | 208V | C | |
| GC-155 | GPL3 | 208V | C | |
| GD-114 | GPL4A | 208V | C* | |
| GD-114 | GPL4B | 208V | C | |
| GD-101 | GPL4C | 208V | C | |
| GD-114B | GPL5 | 208V | C | |
| GC-124 | GPL6 | 208V | C* | |
| GC-116 | GPL7 | 208V | C | |
| GC-112 | GPL8 | 208V | C* | |
| GC-114 | GPL9 | 208V | C* | |
| GC-128 | GPL10 | 208V | C* | |
| GC-135 | GPL11 | 208V | C* | |
| GC-136 | GPL12 | 208V | C* | |
| GP-143 | GPL13 | 208V | C | |
| GC-150 | GPL14 | 208V | C | |
| GC-149 | GPL15 | 208V | C* | |
| GC-147 | GPL16 | 208V | C* | |
| GA-105 | GPL17 | 208V | C | |
| GC-167 | GPL18 (1) | 208V | C | |
| GC-167 | GPL18 (2) | 208V | C | |
| GB-165 | GPL19 | 208V | C* | |
| GB-190 | GPL21 | 208V | C | |
| GB-106 | GPL22 | 208V | C | |
| GB-113 | GPL23 | 208V | C | |
| GB-115 | GPL24 | 208V | C* | |
| GB-103 | GPL25 | 208V | C | |
| GB-101 | GPL26 | 208V | C | |
| GC-106 | GPL27 | 208V | C* | |
| GC-103 | GPL28 | 208V | C | |
| GC-101 | GPL29 | 208V | C* | |
| GB-131 | GPL30 | 208V | C* | |
| GB-136 | GPL31 | 208V | C* | |
| GB-130 | GPL32 | 208V | C* | |
| GB-118 | GPL33 | 208V | C* | |
| GB-120 | GPL34 | 208V | C | |
| GB-122 | GPL35 | 208V | C* | |
| GF-115 | GPL37 | 208V | A** | |
| GF-114 | GLP38 | 208V | A** | |
| GF-107 | GLP39 | 208V | A** | |
| GF-106 | GLP40 | 208V | A** | |
| GF-105 | GLP41 | 208V | A** | |
| GF-104 | GLP42 | 208V | A** | |
| GF-126 | GLP43 | 208V | A** | |
| GF-127 | GLP44 | 208V | A** | |
| GF-122 | GLP45 | 208V | A** | |
| GE-117 | GQH1 | 480V | C | |
| GD-128 | GQH2 | 480V | C | |
| GA-105 | GQH3 | 480V | C | |
| GB-134 | GQH4 | 480V | C | |
| GE-117 | GQH5 | 480V | B | |
| GE-123 | GQH6 | 480V | C | |
| GF-140 | GQH7 | 480V | A | |
| GF-140 | GQH8 | 480V | A | |
| GD-130 | GQHB | 480V | C | |
| GE-121 | GQHP | 480V | A | |
| GD-123 | GQHP ? | 480V | B | |
| GE-117 | GQL1 | 208V | C | |
| GC-138 | GQL2 (1) | 208V | C | |
| GC-138 | GQL2 (2) | 208V | C | |
| GA-105 | GQL3 (1) | 208V | C | |
| GA-105 | GQL3 (2) | 208V | C | |
| GB-134 | GQL4 | 208V | C | |
| GB-110 | GQL5 | 208V | C | |
| GE-123 | GQL6 (Mislabeled) | 208V | A | |
| GC-138 | GQL6 | 208V | C | |
| GB-110 | GQL7 | 208V | C | |
| GB-110 | GQL8 | 208V | C | |
| GE-123 | GQL9 | 208V | C | |
| GF-140 | GQL10 | 208V | A | |
| GF-140 | GQL11 | 208V | A | |
| GF-140 | GQL12 | 208V | A | |
| GF-140 | GQL13 | 208V | A | |
| GF-140 | GQL14 | 208V | A | |
| GF-140 | GQL15 | 208V | A | |
| GD-123 | GQL16 | 208V | A | |
| GD-129 | GQLB | 208V | C | |
| GD-134 | GQLG | 208V | C- | Extra holes in top of enclosure |
| GD-133 | HP-1 | 480V | A | Breaker trip setting adjustment suggested |
| GD-133 | LP-1 | 208V | A | |
| GB-110 | Unmarked (XMAS) | 208V | A | |
| 1D-176 | 1CL1 | 208V | C | |
| 1D-131 | 1CL2 | 208V | A | |
| 1E-110 | 1DH1 | 480V | C | |
| 1A-113 | 1DH2 | 480V | C- | Bent Enclosure |
| 1B-154 | 1DH3 | 480V | C | |
| 1D-131 | 1DH4 | 480V | A | |
| 1E-162 | 1DQH1 | 480V | D | Breaker Replacement Suggested |
| 1E-189 | 1E-189 | 480V | ? | MARKED ON 1DH2, UNABLE TO LOCATE |
| 1E-205 | 1E-205 | 208V | D | Breaker Replacement Suggested |
| 1E-110 | 1EH1 | 480V | C | |
| 1D-176 | 1EH2 | 480V | C | |
| 1C-158 | 1EH3 | 480V | C | |
| 1B-168 | 1EH4 | 480V | C | |
| 1E-110 | 1EL1 | 208V | C- | Missing Hardware (No Latch) |
| 1D-176 | 1EL2 | 208V | C | |
| 1C-158 | 1EL3 | 208V | C | |
| 1B-168 | 1EL4 | 208V | C | |
| 1F138 | 1FCH1 | 480V | ? | UNABLE TO LOCATE |
| 1F138 | 1FCL1 sec 1 | 208V | ||
| 1F138 | 1FCL1 sec 2 | 208V | ||
| 1F138 | 1FCL2 sec 1 | 208V | ||
| 1F138 | 1FCL2 sec 2 | 208V | ||
| 1F138 | 1FEQL1 | 208V | ||
| 1F138 | 1FLSH1 | 480V | ||
| 1F138 | 1FNL1 sec 1 | 208V | ||
| 1F138 | 1FNL1 sec 2 | 208V | ||
| 1F138 | 1FNL2 | 208V | ||
| GF140 | 1FEQH1 | 480V | ? | |
| 1F138 | 1FNH1 | 480V | ? | UNABLE TO LOCATE |
| 1E-110 | 1H1 | 480V | C | |
| 1E-161 | 1H2 | 480V | C | |
| 1D-176 | 1H3 | 480V | D | Breaker Replacement Suggested |
| 1D-116 | 1H5 | 480V | D | Breaker Replacement Suggested |
| 1A-113 | 1H6 | 480V | C | |
| 1B-168 | 1H8 | 480V | C | |
| 1B-154 | 1H9 | 480V | C | |
| 1D-131 | 1H10 | 480V | A | |
| 1B-161A | 1HK | 480V | C | |
| 1E-161 | 1HX1 | 480V | F | Breakers fail AIC, replacement required |
| 1A-113 | 1HX2 | 480V | C | |
| 1E-176 | 1HX3 | 480V | ||
| 1E-110 | 1L1 (1) | 208V | C | |
| 1E-110 | 1L1 (2) | 208V | C | |
| 1E-161 | 1L2 | 208V | C | |
| 1D-176 | 1L3 (1) | 208V | C | |
| 1D-176 | 1L3 (2) | 208V | C | |
| 1D-116 | 1L5 (1) | 208V | C | |
| 1D-116 | 1L5 (2) | 208V | C | |
| GA-113 | 1L6 (1) | 208V | C | |
| GA-113 | 1L6 (2) | 208V | C | |
| 1B-168 | 1L8 (1) | 208V | C | |
| 1B-168 | 1L8 (2) | 208V | C | |
| 1B-154A | 1L9 (A) | 208V | C | |
| 1B-154A | 1L9 (B) | 208V | C- | Bent cover |
| 1B-154A | 1L9 (C ) | 208V | A | |
| 1B-154A | 1L9 (D) | 208V | C | |
| 1E-110 | 1L10 | 208V | C- | Missing Hardware (No Latch) |
| 1E-110 | 1L11 | 208V | B | |
| 1D-131 | 1L13 | 208V | A | |
| 1E-161 | 1LX1 | 208V | C | |
| GA-113 | 1LX2 | 208V | C | |
| 1E-161 | 1LX3 | 208V | A | |
| 1D-178 | 1PL1 | 208V | C* | |
| 1D-179 | 1PL2 | 208V | C* | |
| 1D-159 | 1PL3 | 208V | C* | |
| 1D-116 | 1PL4 | 208V | C | |
| 1B-159A | 1PL6 (1) | 208V | C* | Cover was locked |
| 1B-159A | 1PL6 (2) | 208V | C* | Cover was locked |
| 1E-161 | 1QH1 | 480V | C | |
| 1D-116 | 1QH2 | 480V | C | |
| 1D-131 | 1QH3 | 480V | A | |
| 1C-146 | 1QH6 | 480V | C | |
| 1C-146 | 1QH6-A | 480V | C | |
| 1C-158 | 1QH7 | 480V | C | |
| 1E-161 | 1QHX | 480V | C | |
| 1E-161 | 1QL1 | 208V | B | |
| 1D-116 | 1QL2 | 208V | C | |
| 1E-162 | 1QL3 | 208V | C | |
| 1B-154A | 1QL4 | 208V | C | |
| 1D-131 | 1QL5 | 208V | A | |
| 1E-162 | 1QL6 | 208V | A | |
| 1C158 | 1QL7 | 208V | ||
| 1C-146 | 1QL8(1) | 208V | C | |
| 1C-146 | 1QL8(2) | 208V | C | |
| 1C-146 | 1QL9(1) | 208V | C | |
| 1C-146 | 1QL9(2) | 208V | C | |
| 1C-158 | 1QL10(1) | 208V | C | |
| 1C-158 | 1QL10(2) | 208V | C |
| 2B-137 | 2CH1 (1) | 480V | C | |
| 2B-137 | 2CH1 (2) | 480V | C | |
| 2B-137 | 2CH2 | 480V | C | |
| 2E-160 | 2CH3 | 480V | C | |
| 2C-107 | 2CH4 | 480V | D | Breaker Replacement Suggested |
| 2B-168 | 2CH5 | 480V | C | |
| 2B-137 | 2CL1 | 208V | C | |
| 2B-137 | 2CL2 | 208V | C | |
| 2E-160 | 2CL3 | 208V | C | |
| 2C-107 | 2CL4 | 208V | C | |
| 2B-168 | 2CL5 | 208V | C | |
| 2B-137 | 2DCH | 480V | C | |
| 2E-160 | 2DCH2 | 480V | C | |
| 2A-124A | 2DH1 | 480V | C | |
| 2A-113 | 2DH2 | 480V | C | |
| 2B-168 | 2DH3 | 480V | C | |
| 2A-124A | 2EH1 | 480V | C | |
| 2E-111 | 2EH2 | 480V | C | |
| 2D-110 | 2EH3 | 480V | C | |
| 2C-107 | 2EH4 | 480V | C | |
| 2A-124A | 2EL1 | 208V | C | |
| 2E-111 | 2EL2 | 208V | C | |
| 2D-110 | 2EL3 | 208V | C | |
| 2C-107 | 2EL4 | 208V | C | |
| 2A-124A | 2H2 | 480V | C | |
| 2E-160 | 2H3 | 480V | C | |
| 2E-111 | 2H4 | 480V | C | |
| 2D-110 | 2H5 | 480V | C | |
| 2D-168 | 2H6 | 480V | D | Breaker Replacement Suggested |
| 2A-113 | 2H7 | 480V | C | |
| 2C-158 | 2H8 | 480V | C | |
| 2C-107 | 2H9 | 480V | C | |
| 2B-168 | 2H10 | 480V | C | |
| 2B-137 | 2HX1 | 480V | C | |
| 2B-137 | 2L1 | 208V | C | |
| 2A-124A | 2L2 | 208V | C | |
| 2E-160 | 2L3 (1) | 208V | C | |
| 2E-160 | 2L3 (2) | 208V | C- | Missing Hardware (Door Latch) |
| 2E-111 | 2L4-L | 208V | C | |
| 2E-111 | 2L4-R | 208V | C | |
| 2D-110 | 2L5-L | 208V | D | Wiring issues inside of panel - panel |
replacement not required
| 2D-110 | 2L5-R | 208V | C | |
| 2D-168 | 2L6 | 208V | C | |
| 2A-113 | 2L7 | 208V | C- | Bent Cover |
| 2C-158 | 2L8-L | 208V | C | |
| 2C-158 | 2L8-R | 208V | C | |
| 2C-107 | 2L9 | 208V | D | Wiring - Double tapped Breakers. Sub panel required |
| 2B-168 | 2L10 | 208V | C | |
| 2A-124A | 2L11 | 208V | C | |
| 2B-151 | 2LX1 | 208V | C | |
| 2B-151 | 2LX2 | 208V | A | |
| 2E-141 | 2PL4 | 208V | C* | |
| 2D-184 | 2PL5 | 208V | C* | |
| 2E-105 | 2PL6 | 208V | C* | |
| 2E-107 | 2PL7 | 208V | C* | |
| 2E-138 | 2PL8 | 208V | C* | |
| 2E-135 | 2PL9 | 208V | C* | |
| 2E-110 | 2PL10 | 208V | C* | |
| 2E-127 | 2PL11 | 208V | C* | |
| 2E-114 | 2PL12 | 208V | C* | |
| 2E-119 | 2PL13 | 208V | C* | |
| 2D-134 | 2PL14 | 208V | C* | |
| 2D-162 | 2PL15 | 208V | C* | |
| 2D-169 | 2PL16 | 208V | C* | |
| 2D-171 | 2PL17 | 208V | C* | |
| 2D-173 | 2PL18 | 208V | C* | |
| 2D-176 | 2PL19 | 208V | C* | |
| 2D-183 | 2PL20 | 208V | C* | |
| 2A-113 | 2PL21 | 208V | C- | Missing Hardware |
| 2E-111 | 2QL2A | 208V | C | |
| 2E-111 | 2QL2B | 208V | C | |
| 2D-168 | 2QL3 | 208V | F | 225A Main on a 110A Panel |
| 2D-168 | 2QL3A | 208V | C | |
| 2D-168 | 2QL3B | 208V | B | |
| 2B-151 | EH-1 | 480V | A | |
| 2B-151 | EL-1 | 208V | A | |
| 3A-104 | 3DH | 480V | C | |
| 3A-104 | 3DH2 | 480V | F | Two breakers fail AIC, replacement required |
| 3A-100 | 3DH2A | 480V | A | |
| 3A-104 | 3DQH | 480V | C | |
| 3CE-PH | 3DQH12 | 480V | A | |
| 3A-104 | 3DQH2 | 480V | A | |
| 3A-104 | 3DQH2 (B) | 480V | A | |
| 3A-104 | 3H1 | 480V | C | |
| 3C-100 | 3H2 | 480V | C | |
| 3C-100 | 3L1 | 208V | C | |
| 3A-100 | 3LNE | 208V | C | |
| 3A-100 | 3LSW | 208V | C | |
| 3A-100 | 3QL | 208V | C | |
| 3CE-PH | 3QL1 | 208V | A | |
| 3A-100 | 3QL2 | 208V | C | |
| 3A-100 | NP1 | 480V | A | |
| 3A-100 | SUB PANEL - 3A | 208V | B | |
| 4A-109 | 4EH1 | 480V | C | |
| 4A-109 | 4EL1 | 208V | C- | Rust in corners |
| 4A-109 | 4H1 | 480V | C | |
| 4A-109 | 4H2 | 480V | C | |
| 4E-145 | 4L1-L | 208V | C | |
| 4E-145 | 4L1-R | 208V | C | |
| 4D-122 | 4L2-L | 208V | C | |
| 4D-122 | 4L2-R | 208V | C | |
| 4A-109 | 4L3-L | 208V | C | |
| 4A-109 | 4L3-R | 208V | C | |
| 4C-145 | 4L4-L | 208V | C- | Extra holes in top. Very crowded inside |
| 4C-145 | 4L4-R | 208V | C- | Extra holes in top. Very crowded inside |
| 4B-122 | 4L5-L | 208V | C | |
| 4B-122 | 4L5-R | 208V | C | |
| 4A-109 | 4L6 | 208V | B | |
| 4E-145 | 4QL1 | 208V | C | |
| 4D-122 | 4QL2 | 208V | C | |
| 4D-122 | 4QL2-B | 208V | A | |
| 4C-145 | 4QL4 | 208V | C | |
| 4B-122 | 4QL5 | 208V | C |
| 5D-137 | 5CL1 | 208V | ? | Area Under Construction | |
| 5C-129 | 5CL2 | 208V | A | ||
| 5A-110 | 5DQH | 480V | A | ||
| 5A-110 | 5EH1 | 480V | C | ||
| 5A-110 | 5EL1 | 208V | C | ||
| 5A-110 | 5H1 | 480V | C | ||
| 5E-145 | 5L1 (1) | 208V | C | ||
| 5E-145 | 5L1 (2) | 208V | C | ||
| 5D-1137 | 5L2 | 208V | ? | Area Under Construction | |
| 5A-110 | 5L3 (1) | 208V | C | ||
| 5A-110 | 5L3 (2) | 208V | C | ||
| 5C-129 | 5L4 (1) | 208V | C | ||
| 2C-129 | 5L4 (2) | 208V | C | ||
| 5B-122 | 5L5 (1) | 208V | C | ||
| 5B-122 | 5L5 (2) | 208V | C | ||
| 5C-129 | 5L6 (5L4.1) | 208V | C | ||
| 5C-129 | 5L7 | 208V | C | ||
| 5B-122 | 5L8 | 208V | C | ||
| 5D111 | 5L9 | 208V | |||
| 5C-122 | 5QH1 | 480V | B | ||
| 5C-122 | 5QH2 | 480V | B | ||
| 5E-145 | 5QL1 | 208V | C | ||
| 5D-137 | 5QL2 | 208V | ? | Area Under Construction | |
| 5C-122 | 5QL3 | 208V | B | ||
| 5C-129 | 5QL4 | 208V | C | ||
| 5B-122 | 5QL5 | 208V | C | ||
| 5B-122 | 5QL6 | 208V | A | ||
| 5C-141 | DP | 480V | B | ||
| 5E-145 | 5QL7 | 208V | A | ||
| 6B-121 | 6CL1-L | 208V | C | ||
| 6B-121 | 6CL1-R | 208V | C | ||
| 6A-109 | 6EH1 | 480V | C | ||
| 6A-109 | 6EL1 | 208V | C | ||
| 6A-109 | 6H1 | 480V | C | ||
| 6E-145 | 6L1-L | 208V | C | ||
| 6E-145 | 6L1-R | 208V | C | ||
| 6D-122 | 6L2-L | 208V | C | ||
| 6D-122 | 6L2-R | 208V | C | ||
| 6A-109 | 6L3-L | 208V | C | ||
| 6A-109 | 6L3-R | 208V | C | ||
| 6C-145 | 6L4-L | 208V | C | ||
| 6C-145 | 6L4-R | 208V | C | ||
| 6B-121 | 6L5-L | 208V | C | ||
| 6B-121 | 6L5-R | 208V | C | ||
| 6E-145 | 6L6 | 208V | A | ||
| 6E-145 | 6QL1 | 208V | C | ||
| 6D-122 | 6QL2 | 208V | C | ||
| 6C-145 | 6QL4 | 208V | C | ||
| 6B-121 | 6QL5 | 208V | C | ||
| 6C-145 | NP2 | 208V | A | ||
| 7A-113 | 7EH1 | 480V | C | ||
| 7E-108 | 7EH2 | 480V | B | ||
| 7A-113 | 7EL1 | 208V | C | ||
| 7E-108 | 7EL2 | 208V | B | ||
| 7A-113 | 7H1 | 480V | C | ||
| 7E-108 | 7H2 | 480V | B | ||
| 7D-116 | 7L2-L | 208V | D | Wiring - (2) 1P used as 2P breaker | |
| 7D-116 | 7L2-R | 208V | C | ||
| 7A-113 | 7L3-L | 208V | C | ||
| 7A-113 | 7L3-R | 208V | C | ||
| 7C-145 | 7L4-L | 208V | C | ||
| 7C-145 | 7L4-R | 208V | C | ||
| 7C-145 | 7L4A | 208V | A | ||
| 7B-123 | 7L5-L | 208V | C | ||
| 7B-123 | 7L5-R | 208V | C | ||
| 7E-108 | 7L6-L | 208V | B | ||
| 7E-108 | 7L6-R | 208V | B | ||
| 7D-116 | 7L7 | 208V | B | ||
| 7D-116 | 7QL2 | 208V | C | ||
| 7C-145 | 7QL4 | 208V | C | ||
| 7B-123 | 7QL5 | 208V | C | ||
| PH (8TH FLOOR) | 8HP | 480V | C | ||
| PH (8TH FLOOR) | 8L1 | 208V | C | ||
| PH (8TH FLOOR) | 8QL1 | 208V | C | ||
| 9TH FLOOR | QHELEV1 | 480V | C | ||
| 9TH FLOOR | QHELEV2 | 480V | D | Enclosure bent and missing hardware | |
| Bldg. 2 | |||||
| SOUTH WALL | PANEL A | 208V | B |
| *Unable to survey panel. Panel original to building. Grade based on similar surveyed panels |
| **Unable to survey panel. Panel installed during Substation H upgrade. Grade based on similar surveyed panels |
DRY TRANSFORMERS
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments IR Scan Annual |
| TRANSFORMERS (XF-****) | ||||
| GD-134A | T-GCL1 | 480V - 208V | D | Poor condition |
| GB-110 | T-GCL3 | 480V - 208V | C | Needs 6" to back wall |
| GE-117 | T-GEL1 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GD-112 | T-GEL2 | 480V - 208V | A | Needs 6" to back wall |
| GC-138 | T-GEL3 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| GF-140 | T-GEL5 | 480V - 208V | A | |
| GE-117 | T-GL1 | 480V - 208V | C | Needs 6" to back wall |
| GD-128 | T-GL2 | 480V - 208V | C | |
| GD-139 | T-GL2 (139) | 480V - 208V | D | No GEC |
| GD-112 | T-GL3 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| GC-138 | T-GL4 | 480V - 208V | C | Needs 6" to back wall |
| GA-105 | T-GL5 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| GB-110 | T-GL6 | 480V - 208V | C | Needs 6" to back wall |
| GB-134 | T-GL7 | 480V - 208V | C | Needs 6" to back wall |
| GC-162 | T-GL9 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GE-117 | T-GL10 | 480V - 208V | C | |
| GF-140 | T-GL11 | 480V - 208V | B | Needs 6" to back wall |
| GD-133 | T-GLB | 480V - 208V | D | Not accessible, obstructions blocking cover |
| GD-133 | T-GLMG | 480V - 208V | D | No GEC |
| GE-117 | T-GQL1 | 480V - 208V | D | Poor condition |
| GC-138 | T-GQL2 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GA-105 | T-GQL3 | 480V - 208V | C | Needs 6" to back wall |
| GB-134 | T-GQL4 | 480V - 208V | C | Needs 6" to back wall |
| GB-110 | T-GQL5 | 480V - 208V | C | Needs 6" to back wall |
| GC-138 | T-GQL6 | 480V - 208V | C | Needs 6" to back wall |
| GB-110 | T-GQL8 | 480V - 208V | B | |
| GE-117 | T-GQL9 | 480V - 208V | D | No GEC |
| GF-140 | T-GQL10 | 480V - 208V | D | Cable Replacement Suggested |
| GD-123 | T-GQL16 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GD-129 | T-GQLB | 480V - 208V | D | Poor condition, needs 6" to back wall |
| GE-123 | T-GQT6 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GD-133 | T-LP1 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| GD-128 | T-(FROM GCH2) | 480V - 208V | D | No GEC |
| 1D-176 | T-1CL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-131 | T-1CL2 | 480V - 208V | D | No GEC |
| 1E-110 | T-1EL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-176 | T-1EL2 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 1C-158 | T-1EL3 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 1B-168 | T-1EL4 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 1E-110 | T-1L1 | 480V - 208V | C | Needs 6" to back wall |
| 1E-161 | T-1L2 | 480V - 208V | D | Poor condition, no clearance above and behind |
| 1D-176 | T-1L3 | 480V - 208V | C | Needs 6" to back wall |
| 1D-116 | T-1L5 | 480V - 208V | C | Needs 6" to back wall |
| 1A-113 | T-1L6 | 480V - 208V | C | Needs 6" to back wall |
| 1B-168 | T-1L8 | 480V - 208V | C | Needs 6" to back wall |
| 1B-154 | T-1L9 | 480V - 208V | D | Running hot |
| 1E-110 | T-1L10 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 1D-131 | T-1L13 | 480V - 208V | D | No GEC |
| 1E-161 | T-1LX1 | 480V - 208V | C | Needs 6" to back wall |
| 1A-113 | T-1LX2 | 480V - 208V | C | Needs 6" to back wall |
| 1E-161 | T-1LX3 | 480V - 208V | D | No GEC |
| 1E-161 | T-1QL1 | 480V - 208V | C | Needs 6" to back wall |
| 1D-118 | T-1QL2 | 480V - 208V | C | Needs 6" to back wall |
| 1E-162 | T-1QL3 | 480V - 208V | C | |
| 1B-154 | T-1QL4 | 480V - 208V | C | Needs 6" to back wall |
| 1D-131 | T-1QL5 | 480V - 208V | D | No GEC |
| 1E-162 | T-1QL6 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 1C-146 | T-1QL8 | 480V - 208V | C | Needs 6" to back wall |
| 1C158 | T-1QL7 | 480V - 208V | ||
| 1C-158 | T-1QL10 | 480V - 208V | D | Poor condition |
| 1F138 | T-FCL1 | 480V - 208V | ||
| 1F138 | T-FNL1 | 480V - 208V | ||
| 1B-154 | T-FRYER | 480V - 208V | A | Needs 6" to back wall |
| 1E-205 | T-TABLE | 480V - 208V | C |
| 2B-137 | T-2CL1 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 2B-136 | T-2CL2 | 480V - 208V | C | |
| 2E-160 | T-2CL3 | 480V - 208V | B | Needs 6" to back wall |
| 2C-107 | T-2CL4 | 480V - 208V | C | Needs 6" to back wall |
| 2B-168 | T-2CL5 | 480V - 208V | C | Needs 6" to back wall |
| 2A-124A | T-2EL1 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2EL2 | 480V - 208V | C | Needs 6" to back wall |
| 2C-110 | T-2EL3 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 2C-107 | T-2EL4 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 2B-137 | T-2L1 | 480V - 208V | C | |
| 2A-124A | T-2L2 | 480V - 208V | C | Needs 6" to back wall |
| 2E-160 | T-2L3 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2L4 | 480V - 208V | C | Needs 6" to back wall |
| 2C-110 | T-2L5 | 480V - 208V | C | Needs 6" to back wall |
| 2D-168 | T-2L6 | 480V - 208V | C | Needs 6" to back wall |
| 2A-113 | T-2L7 | 480V - 208V | C | Needs 6" to back wall |
| 2C-158 | T-2L8 | 480V - 208V | C | Needs 6" to back wall |
| 2C-107 | T-2L9 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 2B-168 | T-2L10 | 480V - 208V | C | Needs 6" to back wall |
| 2A-124A | T-2L11 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 2B-151 | T-2LX1 | 480V - 208V | C | Needs 6" to back wall |
| 2E-111 | T-2QL2 | 480V - 208V | C | Needs 6" to back wall |
| 2D-168 | T-2QL3 | 480V - 208V | C | Needs 6" to back wall |
| 2B-151 | T-EL1 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 3L-100 | T-3L1 | 480V - 208V | B | Needs 6" to back wall |
| 3A-100 | T-3LNE | 480V - 208V | C | Needs 6" to back wall |
| 3A-100 | T-3LSW | 480V - 208V | C | |
| 3A-100 | T-3QL | 480V - 208V | A | Needs 6" to back wall |
| 3C-PH | T-3QL1 (PH) | 480V - 208V | D | No GEC |
| 3A-100 | T-3QL2 | 480V - 208V | D | No GEC, Needs 6" to back wall |
| 4A-109 | T-4EL1 | 480V - 208V | D | Poor condition, needs 6" to back wall |
| 4E-145 | T-4L1 | 480V - 208V | C | Needs 6" to back wall |
| 4D-122 | T-4L2 | 480V - 208V | C | Needs 6" to back wall |
| 4A-109 | T-4L3 | 480V - 208V | C | Needs 6" to back wall |
| 4C-145 | T-4L4 | 480V - 208V | C | Needs 6" to back wall |
| 4B-122 | T-4L5 | 480V - 208V | C | Needs 6" to back wall |
| 4A-109 | T-4L6 | 480V - 208V | B | |
| 4E-145 | T-4QL1 | 480V - 208V | C | Needs 6" to back wall |
| 4D-122 | T-4QL2 | 480V - 208V | C | Needs 6" to back wall |
| 4C-145 | T-4QL4 | 480V - 208V | C | Needs 6" to back wall |
| 4B-122 | T-4QL5 | 480V - 208V | C | Housing, Needs clearance |
| 5D-137 | T-5CL1 | 480V - 208V | ? | Area Under Construction |
| 5C-129 | T-5CL2 | 480V - 208V | C | |
| 5D137 | T-5L2 | |||
| 5C-129 | T-5L6 | 480V - 208V | C | |
| 5D111 | T-5L9 | 480V - 208V | ||
| 5C-122 | T-5QL3 | 480V - 208V | A | |
| 5B-122 | T-5QL6 | 480V - 208V | A | |
| 5E-145 | T-(5E-145) | 480V - 208V | D | No GEC |
| 6B-121 | T-6CL1 | 480V - 208V | C | Needs 6" to back wall |
| 6A-109 | T-6EL1 | 480V - 208V | D | Poor condition |
| 6E-145 | T-6L6 | 480V - 208V | B | Needs 6" to back wall |
| 6C-145 | T-NP2 | 480V - 208V | A |
| 7E-108 | T-7EL2 | 480V - 208V | C | Needs 6" to back wall |
| 7C-145 | T-7L4 | 480V - 208V | C | |
| 7E-108 | T-7L6 | 480V - 208V | C | Needs 6" to back wall |
| 7D-116 | T-7L7 | 480V - 208V | B | Needs 6" to back wall |
| Notes: No Vibration Isolators found on any transformers. Transformer clearance of 6" is required by UL1591, not NEC |
OIL FILLED PAD MOUNT XFORMERS
| Equipment Condition Assessment |
| * EQUIPMENT CONDITION: |
(A) Like New Condition - Majority of useful life span remains. "Excellent"
(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"
(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"
(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"
(F) Critical Condition - Needs immediate attention. "Failing"
| Location | Equipment | Voltage | Assessment | comments 36 month & IR Scan Annual |
| OIL FILLED PAD MOUNT TRANSFORMERS | ||||
| GE-117 | Substation A-A (XF-AA) | 13800V - 480V | C | |
| GE-117 | Substation A-B (XF-AB) | 13800V - 480V | C | |
| GD-123 | Substation B (XF-B1) | 13800V - 480V | C | |
| GD-123 | Substation C (XF-C1) | 13800V - 480V | C | |
| GD-123 | Substation D (XF-D1) | 13800V - 480V | C | |
| 3A-102 | Substation F (XF-F1) | 13800V - 480V | C | |
| 3A-102 | Substation G (XF-G1) | 13800V - 480V | C | |
| GD-123 | Substation H (XF-H1) | 13800V - 480V | B | |
| outside | PV SITE 1 | 13800V - 480V | B | |
| outside | PV SITE 2 | 13800V - 480V | B | |
| outside | PV SITE 3 | 13800V - 480V | B |