Exhibit A - Little Rock Equipment List.xlsx

XLSX spreadsheet 58 KB Posted

Attached to
J061--Electrical System Preventive Maintenance And Testing Services Federal contract opportunity
Solicitation number
36C25622Q1188
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This solicitation from the Central Arkansas VA Healthcare System seeks quotes for electrical system preventive maintenance and testing services at two VA medical centers in Little Rock and North Little Rock, Arkansas. The requirement is set aside for Veteran-Owned, Small Businesses under NAICS code 238210. Interested parties must be registered in the VA Vendor Information Pages and SAM, and submit all questions by August 22. Quotes are due by the date specified and must include the contractor's entity information from SAM, points of contact, completed price schedule, and required provisions. A mandatory site visit will be held on August 18 at the specified locations to view the sites. Exhibits A through E are provided for information only and are not part of the solicitation or resultant contract.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ALL IR SCAN

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentComments IR SCAN Annual
SUBSTATIONS
GE-116MV Switchgear13800VC
GE-117Substation A13800V - 480VCBreaker adjustments required for proper coordination
GD-123Substation B13800V - 480VCBreaker adjustments required for proper coordination
GD-123Substation C13800V - 480VC
GD-123Substation D13800V - 480VC
3A-102Substation F13800V - 480VCBreaker adjustments required for proper coordination
3A-102Substation G13800V - 480VC
GD-123Substation H13800V - 480VBBreaker adjustments required for proper coordination
GD-134Generators480VA
GD-134Substation EES480VDClearance issues. Gear in poor condition.
GD-134Substation EES-A480VB
ATS'S
GE-117ATS-CR1480VA
2B-137ATS-CR2480VA
GE-117ATS-CR3480VB
GE-117ATS-E1480VDGood Condition, Cable Replacement Suggested
GE-117ATS-Q1480VDGood Condition, Cable Replacement Suggested
GD-133ATS-Q2480VA
GD133ATS-Q3480VB-CNo Neutral Used, Feeds MCC
3A-100ATS-Q4480VA
8A-100ATS-Q5480VA
8A-100ATS-Q6480VA
3A-102ATS-Q7480VA
1E-161ATS-Q8480VANo Bypass Isolation
GE-115ATS-Q9480VANo Bypass Isolation
GE-121ATS-Q10480VDGood condition, Cable Replacement Suggested
3A-100ATS-Q11480VA
3E-100ATS-Q12480VA
GE-117ATS-Q13480VANo Bypass Isolation
GD-123ATS-Q14480VA
GD-123ATS-Q15480VA
GD-123ATS-Q16480VA
3A-100ATS-Q17480VA
GD-133ATS-MG480VA
MCC'S
GD-133MCC-1480VC
GD-133MCC-2480VC
GE-115MCC-3480VC
1E-162MCC-4480VC
3RD FLOOR
NORTH EASTMCC-NE480VC
3RD FLOOR
NORTH WESTMCC-NW480VC
GD-129MCC-Q1A480VC
GD-133MCC-Q1B480VC
3A-100MCC-QN480VC
3A-100MCC-QS480VC
3RD FLOOR
SOUTH EASTMCC-SE480VC
3RD FLOOR
SOUTH WESTMCC-SW480VC
PANELBOARDS
GD-128GCH2480VC
GB-110GCH3480VC
GD-130GCL1208VC
GC197GCL2208V
GB-110GCL3208VC
GE-117GDCH480Vreplaced 2020
GE-117GDEH480VD
GE-117GDH1480Vreplaced 2020
GA-105GDH2480VC
GB-134GDH3480Vreplaced 2020
GE-117GDH4480Vreplaced 2020
GD-123GDH5480Vreplaced 2020
GF-140GDH6480VA
GE-117GDHX480VD
GE-117GDQH480Vreplaced 2020
GD-123GDQH2480VA
GD-133GDQH4480VB
GD-123GDQH5480VD
GE-117GEH1480VC
GD-112GEH2480VC
GC-138GEH3480Vreplaced 2020
GB-110GEH4480VC
GF-140GEH5480VA
GE-117GEL1208VC
GD-112GEL2208VC
GC197GEL2A208V
GC-138GEL3208VC
GF-140GEL5208VA
GE-117GH1480VC
GD-128GH2480VC
GD-112GH3480VD
GC-138GH4480VC
GA-105GH5480VC
GB-110GH6480VD
GB-134GH7480VC
GE-123GH8480VC
GC-162GH9480VF240V Panel with 480V connected
GD-139GH9 (MISLABELED)480VC
GE-117GH10480VC
GF-140GH12480VA
GC-167GHK480VC
GD-133GHMG480VD
GE-123GHP1480VC
GE-121GHP2480VC
GE-117GL1208VC
GD-128GL2208VC
GD-139GL2 (139)208VC
GD-112GL3 (1)208VC
GD-112GL3 (2)208VC
GC-138GL4 (1)208VC
GC-138GL4 (2)208VC
GA-105GL5208VC
GB-110GL6 (1)208VC
GB-110GL6 (2)208VC
GB-134GL7 (1)208Vreplaced 2020
GB-134GL7 (2)208Vreplaced 2020
GC-162GL9208VA
GE-117GL10208VC
GF-140GL11208VA
GF-140GL12208VA
GF-140GL13208VA
GD-133GLB208VC-Surface rust
GD-133GLMG208VA
GE-123GPL1208VC
GC-157GPL2208VC
GC-155GPL3208VC
GD-114GPL4A208VC*
GD-114GPL4B208VC
GD-101GPL4C208VC
GD-114BGPL5208VC
GC-124GPL6208VC*
GC-116GPL7208VC
GC-112GPL8208VC*
GC-114GPL9208VC*
GC-128GPL10208VC*
GC-135GPL11208VC*
GC-136GPL12208VC*
GP-143GPL13208VC
GC-150GPL14208VC
GC-149GPL15208VC*
GC-147GPL16208VC*
GA-105GPL17208VC
GC-167GPL18 (1)208VC
GC-167GPL18 (2)208VC
GB-165GPL19208VC*
GB-190GPL21208VC
GB-106GPL22208VC
GB-113GPL23208VC
GB-115GPL24208VC*
GB-103GPL25208VC
GB-101GPL26208VC
GC-106GPL27208VC*
GC-103GPL28208VC
GC-101GPL29208VC*
GB-131GPL30208VC*
GB-136GPL31208VC*
GB-130GPL32208VC*
GB-118GPL33208VC*
GB-120GPL34208VC
GB-122GPL35208VC*
GF-115GPL37208VA**
GF-114GLP38208VA**
GF-107GLP39208VA**
GF-106GLP40208VA**
GF-105GLP41208VA**
GF-104GLP42208VA**
GF-126GLP43208VA**
GF-127GLP44208VA**
GF-122GLP45208VA**
GE-117GQH1480VC
GD-128GQH2480VC
GA-105GQH3480VC
GB-134GQH4480VC
GE-117GQH5480VB
GE-123GQH6480VC
GF-140GQH7480VA
GF-140GQH8480VA
GD-130GQHB480VC
GE-121GQHP480VA
GD-123GQHP ?480VB
GE-117GQL1208VC
GC-138GQL2 (1)208VC
GC-138GQL2 (2)208VC
GA-105GQL3 (1)208VC
GA-105GQL3 (2)208VC
GB-134GQL4208VC
GB-110GQL5208VC
GE-123GQL6 (Mislabeled)208VA
GC-138GQL6208VC
GB-110GQL7208VC
GB-110GQL8208VC
GE-123GQL9208VC
GF-140GQL10208VA
GF-140GQL11208VA
GF-140GQL12208VA
GF-140GQL13208VA
GF-140GQL14208VA
GF-140GQL15208VA
GD-123GQL16208VA
GD-129GQLB208VC
GD-134GQLG208VC-Extra holes in top of enclosure
GD-133HP-1480VABreaker trip setting adjustment suggested
GD-133LP-1208VA
GB-110Unmarked (XMAS)208VA
1D-1761CL1208VC
1D-1311CL2208VA
1E-1101DH1480VC
1A-1131DH2480VC-Bent Enclosure
1B-1541DH3480VC
1D-1311DH4480VA
1E-1621DQH1480VD
1E-1891E-189480V?MARKED ON 1DH2, UNABLE TO LOCATE
1E-2051E-205208VD
1E-1101EH1480VC
1D-1761EH2480VC
1C-1581EH3480VC
1B-1681EH4480VC
1E-1101EL1208VC-Missing Hardware (No Latch)
1D-1761EL2208VC
1C-1581EL3208VC
1B-1681EL4208VC
1F1381FCH1480V
1F1381FCL1 sec 1208V
1F1381FCL1 sec 2208V
1F1381FCL2 sec 1208V
1F1381FCL2 sec 2208V
1F1381FEQL1208V
1F1381FLSH1480V
1F1381FNL1 sec 1208V
1F1381FNL1 sec 2208V
1F1381FNL2208V
1F1381FEQH1480V
1F1381FNH1480V
1E-1101H1480VC
1E-1611H2480VC
1D-1761H3480VD
1D-1161H5480VD
1A-1131H6480VC
1B-1681H8480VC
1B-1541H9480VC
1D-1311H10480VA
1B-161A1HK480VC
1E-1611HX1480Vreplaced 2020
1A-1131HX2480VC
1E-1761HX3480V
1E-1101L1 (1)208VC
1E-1101L1 (2)208VC
1E-1611L2208VC
1D-1761L3 (1)208VC
1D-1761L3 (2)208VC
1D-1161L5 (1)208VC
1D-1161L5 (2)208VC
GA-1131L6 (1)208VC
GA-1131L6 (2)208VC
1B-1681L8 (1)208VC
1B-1681L8 (2)208VC
1B-154A1L9 (A)208VC
1B-154A1L9 (B)208VC-Bent cover
1B-154A1L9 (C )208VA
1B-154A1L9 (D)208VC
1E-1101L10208VC-Missing Hardware (No Latch)
1E-1101L11208VB
1D-1311L13208VA
1E-1611LX1208VC
GA-1131LX2208VC
1E-1611LX3208VA
1D-1781PL1208VC*
1D-1791PL2208VC*
1D-1591PL3208VC*
1D-1161PL4208VC
1B-159A1PL6 (1)208VC*Cover was locked
1B-159A1PL6 (2)208VC*Cover was locked
1E-1611QH1480VC
1D-1161QH2480VC
1D-1311QH3480VA
1C-1461QH6480VC
1C-1461QH6-A480VC
1C-1581QH7480VC
1E-1611QHX480VC
1E-1611QL1208VB
1D-1161QL2208VC
1E-1621QL3208VC
1B-154A1QL4208VC
1D-1311QL5208VA
1E-1621QL6208VA
1C1581QL7208V
1C-1461QL8(1)208VC
1C-1461QL8(2)208VC
1C-1461QL9(1)208VC
1C-1461QL9(2)208VC
1C-1581QL10(1)208VC
1C-1581QL10(2)208VC
2B-1372CH1 (1)480VC
2B-1372CH1 (2)480VC
2B-1372CH2480VC
2E-1602CH3480VC
2C-1072CH4480VD
2B-1682CH5480VC
2B-1372CL1208VC
2B-1372CL2208VC
2E-1602CL3208VC
2C-1072CL4208VC
2B-1682CL5208VC
2B-1372DCH480VC
2E-1602DCH2480VC
2A-124A2DH1480VC
2A-1132DH2480VC
2B-1682DH3480VC
2A-124A2EH1480VC
2E-1112EH2480VC
2D-1102EH3480VC
2C-1072EH4480VC
2A-124A2EL1208VC
2E-1112EL2208VC
2D-1102EL3208VC
2C-1072EL4208VC
2A-124A2H2480VC
2E-1602H3480VC
2E-1112H4480VC
2D-1102H5480VC
2D-1682H6480VD
2A-1132H7480VC
2C-1582H8480VC
2C-1072H9480VC
2B-1682H10480VC
2B-1372HX1480VC
2B-1372L1208VC
2A-124A2L2208VC
2E-1602L3 (1)208VC
2E-1602L3 (2)208VC-Missing Hardware (Door Latch)
2E-1112L4-L208VC
2E-1112L4-R208VC
2D-1102L5-L208VDWiring issues inside of panel - panel

replacement not required

2D-1102L5-R208VC
2D-1682L6208VC
2A-1132L7208VC-Bent Cover
2C-1582L8-L208VC
2C-1582L8-R208VC
2C-1072L9208VDWiring - Double tapped Breakers. Sub panel required
2B-1682L10208VC
2A-124A2L11208VC
2B-1512LX1208VC
2B-1512LX2208VA
2E-1412PL4208VC*
2D-1842PL5208VC*
2E-1052PL6208VC*
2E-1072PL7208VC*
2E-1382PL8208VC*
2E-1352PL9208VC*
2E-1102PL10208VC*
2E-1272PL11208VC*
2E-1142PL12208VC*
2E-1192PL13208VC*
2D-1342PL14208VC*
2D-1622PL15208VC*
2D-1692PL16208VC*
2D-1712PL17208VC*
2D-1732PL18208VC*
2D-1762PL19208VC*
2D-1832PL20208VC*
2A-1132PL21208VC-Missing Hardware
2E-1112QL2A208VC
2E-1112QL2B208VC
2D-1682QL3208Vreplaced 2020
2D-1682QL3A208VC
2D-1682QL3B208VB
2B-151EH-1480VA
2B-151EL-1208VA
3A-1043DH480VC
3A-1043DH2480VF
3A-1003DH2A480VA
3A-1043DQH480VC
3CE-PH3DQH12480VA
3A-1043DQH2480VA
3A-1043DQH2 (B)480VA
3A-1043H1480VC
3C-1003H2480VC
3C-1003L1208VC
3A-1003LNE208VC
3A-1003LSW208VC
3A-1003QL208VC
3CE-PH3QL1208VA
3A-1003QL2208VC
3A-100NP1480VA
3A-100SUB PANEL - 3A208VB
4A-1094EH1480VC
4A-1094EL1208VC-Rust in corners
4A-1094H1480VC
4A-1094H2480VC
4E-1454L1-L208VC
4E-1454L1-R208VC
4D-1224L2-L208VC
4D-1224L2-R208VC
4A-1094L3-L208VC
4A-1094L3-R208VC
4C-1454L4-L208VC-Extra holes in top. Very crowded inside
4C-1454L4-R208VC-Extra holes in top. Very crowded inside
4B-1224L5-L208VC
4B-1224L5-R208VC
4A-1094L6208VB
4E-1454QL1208VC
4D-1224QL2208VC
4D-1224QL2-B208VA
4C-1454QL4208VC
4B-1224QL5208VC
5D-1375CL1208V?Area Under Construction
5C-1295CL2208VA
5A-1105DQH480VA
5A-1105EH1480VC
5A-1105EL1208VC
5A-1105H1480VC
5E-1455L1 (1)208VC
5E-1455L1 (2)208VC
5D-11375L2208V?Area Under Construction
5A-1105L3 (1)208VC
5A-1105L3 (2)208VC
5C-1295L4 (1)208VC
2C-1295L4 (2)208VC
5B-1225L5 (1)208VC
5B-1225L5 (2)208VC
5C-1295L6 (5L4.1)208VC
5C-1295L7208VC
5B-1225L8208VC
5D1115L9208V
5C-1225QH1480VB
5C-1225QH2480VB
5E-1455QL1208VC
5D-1375QL2208V?Area Under Construction
5C-1225QL3208VB
5C-1295QL4208VC
5B-1225QL5208VC
5B-1225QL6208VA
5C-141DP480VB
5E-1455QL7208VA
6B-1216CL1-L208VC
6B-1216CL1-R208VC
6A-1096EH1480VC
6A-1096EL1208VC
6A-1096H1480VC
6E-1456L1-L208VC
6E-1456L1-R208VC
6D-1226L2-L208VC
6D-1226L2-R208VC
6A-1096L3-L208VC
6A-1096L3-R208VC
6C-1456L4-L208VC
6C-1456L4-R208VC
6B-1216L5-L208VC
6B-1216L5-R208VC
6E-1456L6208VA
6E-1456QL1208VC
6D-1226QL2208VC
6C-1456QL4208VC
6B-1216QL5208VC
6C-145NP2208VA
7A-1137EH1480VC
7E-1087EH2480VB
7A-1137EL1208VC
7E-1087EL2208VB
7A-1137H1480VC
7E-1087H2480VB
7D-1167L2-L208VD
7D-1167L2-R208VC
7A-1137L3-L208VC
7A-1137L3-R208VC
7C-1457L4-L208VC
7C-1457L4-R208VC
7C-1457L4A208VA
7B-1237L5-L208VC
7B-1237L5-R208VC
7E-1087L6-L208VB
7E-1087L6-R208VB
7D-1167L7208VB
7D-1167QL2208VC
7C-1457QL4208VC
7B-1237QL5208VC
PH (8TH FLOOR)8HP480VC
PH (8TH FLOOR)8L1208VC
PH (8TH FLOOR)8QL1208VC
9TH FLOORQHELEV1480VC
9TH FLOORQHELEV2480VDEnclosure bent and missing hardware
Bldg. 2
SOUTH WALLPANEL A208VB
*Unable to survey panel. Panel original to building. Grade based on similar surveyed panels
**Unable to survey panel. Panel installed during Substation H upgrade. Grade based on similar surveyed panels
TRANSFORMERS
GD-134AT-GCL1480V - 208Vreplaced 2020
GB-110T-GCL3480V - 208VCNeeds 6" to back wall
GE-117T-GEL1480V - 208VDNeeds 6" to back wall
GD-112T-GEL2480V - 208VANeeds 6" to back wall
GC-138T-GEL3480V - 208Vreplaced 2020
GF-140T-GEL5480V - 208VA
GE-117T-GL1480V - 208VCNeeds 6" to back wall
GD-128T-GL2480V - 208VC
GD-139T-GL2 (139)480V - 208VC
GD-112T-GL3480V - 208Vreplaced 2020
GC-138T-GL4480V - 208VCNeeds 6" to back wall
GA-105T-GL5480V - 208Vreplaced 2020
GB-110T-GL6480V - 208VCNeeds 6" to back wall
GB-134T-GL7480V - 208VCNeeds 6" to back wall
GC-162T-GL9480V - 208VDNeeds 6" to back wall
GE-117T-GL10480V - 208VC
GF-140T-GL11480V - 208VBNeeds 6" to back wall
GD-133T-GLB480V - 208VDNot accessible, obstructions blocking cover
GD-133T-GLMG480V - 208VDNo GEC
GE-117T-GQL1480V - 208Vreplaced 2020
GC-138T-GQL2480V - 208VDNo GEC, Needs 6" to back wall
GA-105T-GQL3480V - 208VCNeeds 6" to back wall
GB-134T-GQL4480V - 208VCNeeds 6" to back wall
GB-110T-GQL5480V - 208VCNeeds 6" to back wall
GC-138T-GQL6480V - 208VCNeeds 6" to back wall
GB-110T-GQL8480V - 208VB
GE-117T-GQL9480V - 208VC
GF-140T-GQL10480V - 208VCCable Replaced 2020
GD-123T-GQL16480V - 208VDNo GEC, Needs 6" to back wall
GD-129T-GQLB480V - 208Vreplaced 2020
GE-123T-GQT6480V - 208VDNeeds 6" to back wall
GD-133T-LP1480V - 208VDNeeds 6" to back wall
GD-128T-GCH2480V - 208VC
1D-176T-1CL1480V - 208VCNeeds 6" to back wall
1D-131T-1CL2480V - 208VC
1E-110T-1EL1480V - 208VCNeeds 6" to back wall
1D-176T-1EL2480V - 208Vreplaced 2020
1C-158T-1EL3480V - 208Vreplaced 2020
1B-168T-1EL4480V - 208Vreplaced 2020
1E-110T-1L1480V - 208VCNeeds 6" to back wall
1E-161T-1L2480V - 208Vreplaced 2020
1D-176T-1L3480V - 208VCNeeds 6" to back wall
1D-116T-1L5480V - 208VCNeeds 6" to back wall
1A-113T-1L6480V - 208VCNeeds 6" to back wall
1B-168T-1L8480V - 208VCNeeds 6" to back wall
1B-154T-1L9480V - 208VDRunning hot
1E-110T-1L10480V - 208Vreplaced 2020
1D-131T-1L13480V - 208VC
1E-161T-1LX1480V - 208VCNeeds 6" to back wall
1A-113T-1LX2480V - 208VCNeeds 6" to back wall
1E-161T-1LX3480V - 208VC
1E-161T-1QL1480V - 208VCNeeds 6" to back wall
1D-118T-1QL2480V - 208VCNeeds 6" to back wall
1E-162T-1QL3480V - 208VC
1B-154T-1QL4480V - 208VCNeeds 6" to back wall
1D-131T-1QL5480V - 208VC
1E-162T-1QL6480V - 208VDNeeds 6" to back wall
1C-146T-1QL8480V - 208VCNeeds 6" to back wall
1C158T-1QL7480V - 208V
1C-158T-1QL10480V - 208VDPoor condition
1F138T-FCL1480V - 208V
1F138T-FNL1480V - 208V
1B-154T-FRYER480V - 208VANeeds 6" to back wall
1E-205T-TABLE480V - 208VC
2B-137T-2CL1480V - 208VDNeeds 6" to back wall
2B-136T-2CL2480V - 208VC
2E-160T-2CL3480V - 208VBNeeds 6" to back wall
2C-107T-2CL4480V - 208VCNeeds 6" to back wall
2B-168T-2CL5480V - 208VCNeeds 6" to back wall
2A-124AT-2EL1480V - 208VCNeeds 6" to back wall
2E-111T-2EL2480V - 208VCNeeds 6" to back wall
2C-110T-2EL3480V - 208Vreplaced 2020
2C-107T-2EL4480V - 208Vreplaced 2020
2B-137T-2L1480V - 208VC
2A-124AT-2L2480V - 208VCNeeds 6" to back wall
2E-160T-2L3480V - 208VCNeeds 6" to back wall
2E-111T-2L4480V - 208VCNeeds 6" to back wall
2C-110T-2L5480V - 208VCNeeds 6" to back wall
2D-168T-2L6480V - 208VCNeeds 6" to back wall
2A-113T-2L7480V - 208VCNeeds 6" to back wall
2C-158T-2L8480V - 208VCNeeds 6" to back wall
2C-107T-2L9480V - 208Vreplaced 2020
2B-168T-2L10480V - 208VCNeeds 6" to back wall
2A-124AT-2L11480V - 208VDNeeds 6" to back wall
2B-151T-2LX1480V - 208VCNeeds 6" to back wall
2E-111T-2QL2480V - 208VCNeeds 6" to back wall
2D-168T-2QL3480V - 208VCNeeds 6" to back wall
2B-151T-EL1480V - 208VDNeeds 6" to back wall
3L-100T-3L1480V - 208VBNeeds 6" to back wall
3A-100T-3LNE480V - 208VCNeeds 6" to back wall
3A-100T-3LSW480V - 208VC
3A-100T-3QL480V - 208VANeeds 6" to back wall
3C-PHT-3QL1 (PH)480V - 208VC
3A-100T-3QL2480V - 208VDNeeds 6" to back wall
4A-109T-4EL1480V - 208Vreplaced 2020
4E-145T-4L1480V - 208VCNeeds 6" to back wall
4D-122T-4L2480V - 208VCNeeds 6" to back wall
4A-109T-4L3480V - 208VCNeeds 6" to back wall
4C-145T-4L4480V - 208VCNeeds 6" to back wall
4B-122T-4L5480V - 208VCNeeds 6" to back wall
4A-109T-4L6480V - 208VB
4E-145T-4QL1480V - 208VCNeeds 6" to back wall
4D-122T-4QL2480V - 208VCNeeds 6" to back wall
4C-145T-4QL4480V - 208VCNeeds 6" to back wall
4B-122T-4QL5480V - 208VCHousing, Needs clearance
5D-137T-5CL1480V - 208V?Area Under Construction
5C-129T-5CL2480V - 208VC
5D137T-5L2
5C-129T-5L6480V - 208VC
5D111T-5L9480V - 208V
5C-122T-5QL3480V - 208VA
5B-122T-5QL6480V - 208VA
5E-145T-(5E-145)480V - 208VC
6B-121T-6CL1480V - 208VCNeeds 6" to back wall
6A-109T-6EL1480V - 208Vreplaced 2020
6E-145T-6L6480V - 208VBNeeds 6" to back wall
6C-145T-NP2480V - 208VA
7E-108T-7EL2480V - 208VCNeeds 6" to back wall
7C-145T-7L4480V - 208VC
7E-108T-7L6480V - 208VCNeeds 6" to back wall
7D-116T-7L7480V - 208VBNeeds 6" to back wall
Notes: No Vibration Isolators found on any transformers. Transformer clearance of 6" is required by UL1591, not NEC

SUBSTATIONS

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month & IR Annual
SUBSTATIONS
GE-116MV Switchgear (UTIL-001 & UTIL-002)13800VC
GE-117Substation A (AA & AB)13800V - 480VCBreaker adjustments required for proper coordination
GD-123Substation B (B1)13800V - 480VCBreaker adjustments required for proper coordination
GD-123Substation C (C1)13800V - 480VC
GD-123Substation D (D1)13800V - 480VC
3A-102Substation F (F1)13800V - 480VCBreaker adjustments required for proper coordination
3A-102Substation G (G1)13800V - 480VC
GD-123Substation H (H1)13800V - 480VBBreaker adjustments required for proper coordination
GD-134Generator Main (GEN-1)480VA
GD-134Substation EES480VDClearance issues. Gear in poor condition.
GD-134Substation EES-A480VB

MVL SW

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month & IR Annual
MEDIUM VOLTAGE FUSED SWITCHES
GE-117Substation A-A (SW-AA)13800VCfused switch
GE-117Substation A-B (SW-AB)13800VCfused switch
GD-123Substation B (SW-B1)13800VCfused switch
GD-123Substation C (SW-C1)13800VCfused switch
GD-123Substation D (SW-D1)13800VCfused switch
3A-102Substation F (SW-F1)13800VCfused switch
3A-102Substation G (SW-G1)13800VCfused switch
GD-123Substation H (SW-H1)13800VBfused switch
outsidePV MAIN 1 HVL13800VLI switch with fixed mounted vacuum circuit breaker
outsidePV MAIN 2 HVL13800VLI switch with fixed mounted vacuum circuit breaker

PROTECTIVE RELAYS

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month
PROTECTIVE RELAYS
GE-116MV Switchgear13800V
GE-117Substation A13800V - 480V
GD-123Substation B13800V - 480V
GD-123Substation C13800V - 4160V
GD-123Substation D13800V - 4160V
3A-102Substation F13800V - 480V
3A-102Substation G13800V - 480V
GD-123Substation H13800V - 480V
GD-134Substation EES480V
GD-134Substation EES-A480V
outsidePV MAIN 1 HVL13800VSchwietzer SEL 751
outsidePV MAIN 2 HVL13800VSchwietzer SEL 751

ATS'S

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

ATS'S
LocationEquipmentVoltageAssessmentcomments IR SCAN Annual
GE-117ATS-CR1480VA
2B-137ATS-CR2480VA
GE-117ATS-CR3480VB
GE-117ATS-E1480VDGood Condition, Cable Replacement Suggested
GE-117ATS-Q1480VDGood Condition, Cable Replacement Suggested
GD-133ATS-Q2480VA
GD133ATS-Q3480VB-CNo Neutral Used, Feeds MCC
3A-100ATS-Q4480VA
8A-100ATS-Q5480VA
8A-100ATS-Q6480VA
3A-102ATS-Q7480VA
1E-161ATS-Q8480VANo Bypass Isolation
GE-115ATS-Q9480VANo Bypass Isolation
GE-121ATS-Q10480VDGood condition, Cable Replacement Suggested
3A-100ATS-Q11480VA
3E-100ATS-Q12480VA
GE-117ATS-Q13480VANo Bypass Isolation
GD-123ATS-Q14480VA
GD-123ATS-Q15480VA
GD-123ATS-Q16480VA
3A-100ATS-Q17480VA
GD-133ATS-MG480VA

MCC'S

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month & IR Scan Annual
MCC'S
GD-133MCC-1480VDGood condition, Breaker Replacement Suggested
GD-133MCC-2480VC
GE-115MCC-3480VC
1E-162MCC-4480VC
3RD FLOOR
NORTH EASTMCC-NE480VC
3RD FLOOR
NORTH WESTMCC-NW480VC
GD-129MCC-Q1A480VC
GD-133MCC-Q1B480VC
3A-100MCC-QN480VC
3A-100MCC-QS480VC
3RD FLOOR
SOUTH EASTMCC-SE480VC
3RD FLOOR
SOUTH WESTMCC-SW480VC

PANELBOARDS

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month (250A UP) & IR Scan Annual
PANELBOARDS
GD-128GCH2480VC
GB-110GCH3480VC
GD-130GCL1208VC
GC197GCL2208V
GB-110GCL3208VC
GE-117GDCH480VDEnclosure bent and missing hardware
GE-117GDEH480VDBreaker Replacement Suggested
GE-117GDH1480VFEnclosure condition, and one breaker fails AIC
GA-105GDH2480VC
GB-134GDH3480VDEnclosure bent, cover doesn't fit properly
GE-117GDH4480VFFails AIC, replacement required
GD-123GDH5480VFFails AIC, replacement required
GF-140GDH6480VA
GE-117GDHX480VDBreaker Replacement Suggested
GE-117GDQH480VDEnclosure bent and missing hardware
GD-123GDQH2480VA
GD-133GDQH4480VB
GD-123GDQH5480VDBreaker Replacement Suggested
GE-117GEH1480VC
GD-112GEH2480VC
GC-138GEH3480VC
GB-110GEH4480VC
GF-140GEH5480VA
GE-117GEL1208VC
GD-112GEL2208VC
GC197GEL2A208V
GC-138GEL3208VC
GF-140GEL5208VA
GE-117GH1480VC
GD-128GH2480VC
GD-112GH3480VF240V Breaker Installed in 480V panel.
GC-138GH4480VC
GA-105GH5480VC
GB-110GH6480VDBreaker Replacement Suggested
GB-134GH7480VC
GE-123GH8480VC
GC-162GH9480VF240V Panel with 480V connected
GD-139GH9 (MISLABELED)480VC
GE-117GH10480VC
GF-140GH12480VA
GC-167GHK480VC
GD-133GHMG480VDBreaker Replacement Suggested
GE-123GHP1480VC
GE-121GHP2480VC
GE-117GL1208VC
GD-128GL2208VC
GD-139GL2 (139)208VC
GD-112GL3 (1)208VC
GD-112GL3 (2)208VC
GC-138GL4 (1)208VC
GC-138GL4 (2)208VC
GA-105GL5208VC
GB-110GL6 (1)208VC
GB-110GL6 (2)208VC
GB-134GL7 (1)208VFSignificant water damage
GB-134GL7 (2)208VDMinor water damage
GC-162GL9208VA
GE-117GL10208VC
GF-140GL11208VA
GF-140GL12208VA
GF-140GL13208VA
GD-133GLB208VC-Surface rust
GD-133GLMG208VA
GE-123GPL1208VC
GC-157GPL2208VC
GC-155GPL3208VC
GD-114GPL4A208VC*
GD-114GPL4B208VC
GD-101GPL4C208VC
GD-114BGPL5208VC
GC-124GPL6208VC*
GC-116GPL7208VC
GC-112GPL8208VC*
GC-114GPL9208VC*
GC-128GPL10208VC*
GC-135GPL11208VC*
GC-136GPL12208VC*
GP-143GPL13208VC
GC-150GPL14208VC
GC-149GPL15208VC*
GC-147GPL16208VC*
GA-105GPL17208VC
GC-167GPL18 (1)208VC
GC-167GPL18 (2)208VC
GB-165GPL19208VC*
GB-190GPL21208VC
GB-106GPL22208VC
GB-113GPL23208VC
GB-115GPL24208VC*
GB-103GPL25208VC
GB-101GPL26208VC
GC-106GPL27208VC*
GC-103GPL28208VC
GC-101GPL29208VC*
GB-131GPL30208VC*
GB-136GPL31208VC*
GB-130GPL32208VC*
GB-118GPL33208VC*
GB-120GPL34208VC
GB-122GPL35208VC*
GF-115GPL37208VA**
GF-114GLP38208VA**
GF-107GLP39208VA**
GF-106GLP40208VA**
GF-105GLP41208VA**
GF-104GLP42208VA**
GF-126GLP43208VA**
GF-127GLP44208VA**
GF-122GLP45208VA**
GE-117GQH1480VC
GD-128GQH2480VC
GA-105GQH3480VC
GB-134GQH4480VC
GE-117GQH5480VB
GE-123GQH6480VC
GF-140GQH7480VA
GF-140GQH8480VA
GD-130GQHB480VC
GE-121GQHP480VA
GD-123GQHP ?480VB
GE-117GQL1208VC
GC-138GQL2 (1)208VC
GC-138GQL2 (2)208VC
GA-105GQL3 (1)208VC
GA-105GQL3 (2)208VC
GB-134GQL4208VC
GB-110GQL5208VC
GE-123GQL6 (Mislabeled)208VA
GC-138GQL6208VC
GB-110GQL7208VC
GB-110GQL8208VC
GE-123GQL9208VC
GF-140GQL10208VA
GF-140GQL11208VA
GF-140GQL12208VA
GF-140GQL13208VA
GF-140GQL14208VA
GF-140GQL15208VA
GD-123GQL16208VA
GD-129GQLB208VC
GD-134GQLG208VC-Extra holes in top of enclosure
GD-133HP-1480VABreaker trip setting adjustment suggested
GD-133LP-1208VA
GB-110Unmarked (XMAS)208VA
1D-1761CL1208VC
1D-1311CL2208VA
1E-1101DH1480VC
1A-1131DH2480VC-Bent Enclosure
1B-1541DH3480VC
1D-1311DH4480VA
1E-1621DQH1480VDBreaker Replacement Suggested
1E-1891E-189480V?MARKED ON 1DH2, UNABLE TO LOCATE
1E-2051E-205208VDBreaker Replacement Suggested
1E-1101EH1480VC
1D-1761EH2480VC
1C-1581EH3480VC
1B-1681EH4480VC
1E-1101EL1208VC-Missing Hardware (No Latch)
1D-1761EL2208VC
1C-1581EL3208VC
1B-1681EL4208VC
1F1381FCH1480V?UNABLE TO LOCATE
1F1381FCL1 sec 1208V
1F1381FCL1 sec 2208V
1F1381FCL2 sec 1208V
1F1381FCL2 sec 2208V
1F1381FEQL1208V
1F1381FLSH1480V
1F1381FNL1 sec 1208V
1F1381FNL1 sec 2208V
1F1381FNL2208V
GF1401FEQH1480V?
1F1381FNH1480V?UNABLE TO LOCATE
1E-1101H1480VC
1E-1611H2480VC
1D-1761H3480VDBreaker Replacement Suggested
1D-1161H5480VDBreaker Replacement Suggested
1A-1131H6480VC
1B-1681H8480VC
1B-1541H9480VC
1D-1311H10480VA
1B-161A1HK480VC
1E-1611HX1480VFBreakers fail AIC, replacement required
1A-1131HX2480VC
1E-1761HX3480V
1E-1101L1 (1)208VC
1E-1101L1 (2)208VC
1E-1611L2208VC
1D-1761L3 (1)208VC
1D-1761L3 (2)208VC
1D-1161L5 (1)208VC
1D-1161L5 (2)208VC
GA-1131L6 (1)208VC
GA-1131L6 (2)208VC
1B-1681L8 (1)208VC
1B-1681L8 (2)208VC
1B-154A1L9 (A)208VC
1B-154A1L9 (B)208VC-Bent cover
1B-154A1L9 (C )208VA
1B-154A1L9 (D)208VC
1E-1101L10208VC-Missing Hardware (No Latch)
1E-1101L11208VB
1D-1311L13208VA
1E-1611LX1208VC
GA-1131LX2208VC
1E-1611LX3208VA
1D-1781PL1208VC*
1D-1791PL2208VC*
1D-1591PL3208VC*
1D-1161PL4208VC
1B-159A1PL6 (1)208VC*Cover was locked
1B-159A1PL6 (2)208VC*Cover was locked
1E-1611QH1480VC
1D-1161QH2480VC
1D-1311QH3480VA
1C-1461QH6480VC
1C-1461QH6-A480VC
1C-1581QH7480VC
1E-1611QHX480VC
1E-1611QL1208VB
1D-1161QL2208VC
1E-1621QL3208VC
1B-154A1QL4208VC
1D-1311QL5208VA
1E-1621QL6208VA
1C1581QL7208V
1C-1461QL8(1)208VC
1C-1461QL8(2)208VC
1C-1461QL9(1)208VC
1C-1461QL9(2)208VC
1C-1581QL10(1)208VC
1C-1581QL10(2)208VC
2B-1372CH1 (1)480VC
2B-1372CH1 (2)480VC
2B-1372CH2480VC
2E-1602CH3480VC
2C-1072CH4480VDBreaker Replacement Suggested
2B-1682CH5480VC
2B-1372CL1208VC
2B-1372CL2208VC
2E-1602CL3208VC
2C-1072CL4208VC
2B-1682CL5208VC
2B-1372DCH480VC
2E-1602DCH2480VC
2A-124A2DH1480VC
2A-1132DH2480VC
2B-1682DH3480VC
2A-124A2EH1480VC
2E-1112EH2480VC
2D-1102EH3480VC
2C-1072EH4480VC
2A-124A2EL1208VC
2E-1112EL2208VC
2D-1102EL3208VC
2C-1072EL4208VC
2A-124A2H2480VC
2E-1602H3480VC
2E-1112H4480VC
2D-1102H5480VC
2D-1682H6480VDBreaker Replacement Suggested
2A-1132H7480VC
2C-1582H8480VC
2C-1072H9480VC
2B-1682H10480VC
2B-1372HX1480VC
2B-1372L1208VC
2A-124A2L2208VC
2E-1602L3 (1)208VC
2E-1602L3 (2)208VC-Missing Hardware (Door Latch)
2E-1112L4-L208VC
2E-1112L4-R208VC
2D-1102L5-L208VDWiring issues inside of panel - panel

replacement not required

2D-1102L5-R208VC
2D-1682L6208VC
2A-1132L7208VC-Bent Cover
2C-1582L8-L208VC
2C-1582L8-R208VC
2C-1072L9208VDWiring - Double tapped Breakers. Sub panel required
2B-1682L10208VC
2A-124A2L11208VC
2B-1512LX1208VC
2B-1512LX2208VA
2E-1412PL4208VC*
2D-1842PL5208VC*
2E-1052PL6208VC*
2E-1072PL7208VC*
2E-1382PL8208VC*
2E-1352PL9208VC*
2E-1102PL10208VC*
2E-1272PL11208VC*
2E-1142PL12208VC*
2E-1192PL13208VC*
2D-1342PL14208VC*
2D-1622PL15208VC*
2D-1692PL16208VC*
2D-1712PL17208VC*
2D-1732PL18208VC*
2D-1762PL19208VC*
2D-1832PL20208VC*
2A-1132PL21208VC-Missing Hardware
2E-1112QL2A208VC
2E-1112QL2B208VC
2D-1682QL3208VF225A Main on a 110A Panel
2D-1682QL3A208VC
2D-1682QL3B208VB
2B-151EH-1480VA
2B-151EL-1208VA
3A-1043DH480VC
3A-1043DH2480VFTwo breakers fail AIC, replacement required
3A-1003DH2A480VA
3A-1043DQH480VC
3CE-PH3DQH12480VA
3A-1043DQH2480VA
3A-1043DQH2 (B)480VA
3A-1043H1480VC
3C-1003H2480VC
3C-1003L1208VC
3A-1003LNE208VC
3A-1003LSW208VC
3A-1003QL208VC
3CE-PH3QL1208VA
3A-1003QL2208VC
3A-100NP1480VA
3A-100SUB PANEL - 3A208VB
4A-1094EH1480VC
4A-1094EL1208VC-Rust in corners
4A-1094H1480VC
4A-1094H2480VC
4E-1454L1-L208VC
4E-1454L1-R208VC
4D-1224L2-L208VC
4D-1224L2-R208VC
4A-1094L3-L208VC
4A-1094L3-R208VC
4C-1454L4-L208VC-Extra holes in top. Very crowded inside
4C-1454L4-R208VC-Extra holes in top. Very crowded inside
4B-1224L5-L208VC
4B-1224L5-R208VC
4A-1094L6208VB
4E-1454QL1208VC
4D-1224QL2208VC
4D-1224QL2-B208VA
4C-1454QL4208VC
4B-1224QL5208VC
5D-1375CL1208V?Area Under Construction
5C-1295CL2208VA
5A-1105DQH480VA
5A-1105EH1480VC
5A-1105EL1208VC
5A-1105H1480VC
5E-1455L1 (1)208VC
5E-1455L1 (2)208VC
5D-11375L2208V?Area Under Construction
5A-1105L3 (1)208VC
5A-1105L3 (2)208VC
5C-1295L4 (1)208VC
2C-1295L4 (2)208VC
5B-1225L5 (1)208VC
5B-1225L5 (2)208VC
5C-1295L6 (5L4.1)208VC
5C-1295L7208VC
5B-1225L8208VC
5D1115L9208V
5C-1225QH1480VB
5C-1225QH2480VB
5E-1455QL1208VC
5D-1375QL2208V?Area Under Construction
5C-1225QL3208VB
5C-1295QL4208VC
5B-1225QL5208VC
5B-1225QL6208VA
5C-141DP480VB
5E-1455QL7208VA
6B-1216CL1-L208VC
6B-1216CL1-R208VC
6A-1096EH1480VC
6A-1096EL1208VC
6A-1096H1480VC
6E-1456L1-L208VC
6E-1456L1-R208VC
6D-1226L2-L208VC
6D-1226L2-R208VC
6A-1096L3-L208VC
6A-1096L3-R208VC
6C-1456L4-L208VC
6C-1456L4-R208VC
6B-1216L5-L208VC
6B-1216L5-R208VC
6E-1456L6208VA
6E-1456QL1208VC
6D-1226QL2208VC
6C-1456QL4208VC
6B-1216QL5208VC
6C-145NP2208VA
7A-1137EH1480VC
7E-1087EH2480VB
7A-1137EL1208VC
7E-1087EL2208VB
7A-1137H1480VC
7E-1087H2480VB
7D-1167L2-L208VDWiring - (2) 1P used as 2P breaker
7D-1167L2-R208VC
7A-1137L3-L208VC
7A-1137L3-R208VC
7C-1457L4-L208VC
7C-1457L4-R208VC
7C-1457L4A208VA
7B-1237L5-L208VC
7B-1237L5-R208VC
7E-1087L6-L208VB
7E-1087L6-R208VB
7D-1167L7208VB
7D-1167QL2208VC
7C-1457QL4208VC
7B-1237QL5208VC
PH (8TH FLOOR)8HP480VC
PH (8TH FLOOR)8L1208VC
PH (8TH FLOOR)8QL1208VC
9TH FLOORQHELEV1480VC
9TH FLOORQHELEV2480VDEnclosure bent and missing hardware
Bldg. 2
SOUTH WALLPANEL A208VB
*Unable to survey panel. Panel original to building. Grade based on similar surveyed panels
**Unable to survey panel. Panel installed during Substation H upgrade. Grade based on similar surveyed panels

DRY TRANSFORMERS

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments IR Scan Annual
TRANSFORMERS (XF-****)
GD-134AT-GCL1480V - 208VDPoor condition
GB-110T-GCL3480V - 208VCNeeds 6" to back wall
GE-117T-GEL1480V - 208VDNo GEC, Needs 6" to back wall
GD-112T-GEL2480V - 208VANeeds 6" to back wall
GC-138T-GEL3480V - 208VDPoor condition, needs 6" to back wall
GF-140T-GEL5480V - 208VA
GE-117T-GL1480V - 208VCNeeds 6" to back wall
GD-128T-GL2480V - 208VC
GD-139T-GL2 (139)480V - 208VDNo GEC
GD-112T-GL3480V - 208VDPoor condition, needs 6" to back wall
GC-138T-GL4480V - 208VCNeeds 6" to back wall
GA-105T-GL5480V - 208VDPoor condition, needs 6" to back wall
GB-110T-GL6480V - 208VCNeeds 6" to back wall
GB-134T-GL7480V - 208VCNeeds 6" to back wall
GC-162T-GL9480V - 208VDNo GEC, Needs 6" to back wall
GE-117T-GL10480V - 208VC
GF-140T-GL11480V - 208VBNeeds 6" to back wall
GD-133T-GLB480V - 208VDNot accessible, obstructions blocking cover
GD-133T-GLMG480V - 208VDNo GEC
GE-117T-GQL1480V - 208VDPoor condition
GC-138T-GQL2480V - 208VDNo GEC, Needs 6" to back wall
GA-105T-GQL3480V - 208VCNeeds 6" to back wall
GB-134T-GQL4480V - 208VCNeeds 6" to back wall
GB-110T-GQL5480V - 208VCNeeds 6" to back wall
GC-138T-GQL6480V - 208VCNeeds 6" to back wall
GB-110T-GQL8480V - 208VB
GE-117T-GQL9480V - 208VDNo GEC
GF-140T-GQL10480V - 208VDCable Replacement Suggested
GD-123T-GQL16480V - 208VDNo GEC, Needs 6" to back wall
GD-129T-GQLB480V - 208VDPoor condition, needs 6" to back wall
GE-123T-GQT6480V - 208VDNo GEC, Needs 6" to back wall
GD-133T-LP1480V - 208VDNo GEC, Needs 6" to back wall
GD-128T-(FROM GCH2)480V - 208VDNo GEC
1D-176T-1CL1480V - 208VCNeeds 6" to back wall
1D-131T-1CL2480V - 208VDNo GEC
1E-110T-1EL1480V - 208VCNeeds 6" to back wall
1D-176T-1EL2480V - 208VDPoor condition, needs 6" to back wall
1C-158T-1EL3480V - 208VDPoor condition, needs 6" to back wall
1B-168T-1EL4480V - 208VDPoor condition, needs 6" to back wall
1E-110T-1L1480V - 208VCNeeds 6" to back wall
1E-161T-1L2480V - 208VDPoor condition, no clearance above and behind
1D-176T-1L3480V - 208VCNeeds 6" to back wall
1D-116T-1L5480V - 208VCNeeds 6" to back wall
1A-113T-1L6480V - 208VCNeeds 6" to back wall
1B-168T-1L8480V - 208VCNeeds 6" to back wall
1B-154T-1L9480V - 208VDRunning hot
1E-110T-1L10480V - 208VDNo GEC, Needs 6" to back wall
1D-131T-1L13480V - 208VDNo GEC
1E-161T-1LX1480V - 208VCNeeds 6" to back wall
1A-113T-1LX2480V - 208VCNeeds 6" to back wall
1E-161T-1LX3480V - 208VDNo GEC
1E-161T-1QL1480V - 208VCNeeds 6" to back wall
1D-118T-1QL2480V - 208VCNeeds 6" to back wall
1E-162T-1QL3480V - 208VC
1B-154T-1QL4480V - 208VCNeeds 6" to back wall
1D-131T-1QL5480V - 208VDNo GEC
1E-162T-1QL6480V - 208VDNo GEC, Needs 6" to back wall
1C-146T-1QL8480V - 208VCNeeds 6" to back wall
1C158T-1QL7480V - 208V
1C-158T-1QL10480V - 208VDPoor condition
1F138T-FCL1480V - 208V
1F138T-FNL1480V - 208V
1B-154T-FRYER480V - 208VANeeds 6" to back wall
1E-205T-TABLE480V - 208VC
2B-137T-2CL1480V - 208VDNo GEC, Needs 6" to back wall
2B-136T-2CL2480V - 208VC
2E-160T-2CL3480V - 208VBNeeds 6" to back wall
2C-107T-2CL4480V - 208VCNeeds 6" to back wall
2B-168T-2CL5480V - 208VCNeeds 6" to back wall
2A-124AT-2EL1480V - 208VCNeeds 6" to back wall
2E-111T-2EL2480V - 208VCNeeds 6" to back wall
2C-110T-2EL3480V - 208VDPoor condition, needs 6" to back wall
2C-107T-2EL4480V - 208VDPoor condition, needs 6" to back wall
2B-137T-2L1480V - 208VC
2A-124AT-2L2480V - 208VCNeeds 6" to back wall
2E-160T-2L3480V - 208VCNeeds 6" to back wall
2E-111T-2L4480V - 208VCNeeds 6" to back wall
2C-110T-2L5480V - 208VCNeeds 6" to back wall
2D-168T-2L6480V - 208VCNeeds 6" to back wall
2A-113T-2L7480V - 208VCNeeds 6" to back wall
2C-158T-2L8480V - 208VCNeeds 6" to back wall
2C-107T-2L9480V - 208VDPoor condition, needs 6" to back wall
2B-168T-2L10480V - 208VCNeeds 6" to back wall
2A-124AT-2L11480V - 208VDNo GEC, Needs 6" to back wall
2B-151T-2LX1480V - 208VCNeeds 6" to back wall
2E-111T-2QL2480V - 208VCNeeds 6" to back wall
2D-168T-2QL3480V - 208VCNeeds 6" to back wall
2B-151T-EL1480V - 208VDNo GEC, Needs 6" to back wall
3L-100T-3L1480V - 208VBNeeds 6" to back wall
3A-100T-3LNE480V - 208VCNeeds 6" to back wall
3A-100T-3LSW480V - 208VC
3A-100T-3QL480V - 208VANeeds 6" to back wall
3C-PHT-3QL1 (PH)480V - 208VDNo GEC
3A-100T-3QL2480V - 208VDNo GEC, Needs 6" to back wall
4A-109T-4EL1480V - 208VDPoor condition, needs 6" to back wall
4E-145T-4L1480V - 208VCNeeds 6" to back wall
4D-122T-4L2480V - 208VCNeeds 6" to back wall
4A-109T-4L3480V - 208VCNeeds 6" to back wall
4C-145T-4L4480V - 208VCNeeds 6" to back wall
4B-122T-4L5480V - 208VCNeeds 6" to back wall
4A-109T-4L6480V - 208VB
4E-145T-4QL1480V - 208VCNeeds 6" to back wall
4D-122T-4QL2480V - 208VCNeeds 6" to back wall
4C-145T-4QL4480V - 208VCNeeds 6" to back wall
4B-122T-4QL5480V - 208VCHousing, Needs clearance
5D-137T-5CL1480V - 208V?Area Under Construction
5C-129T-5CL2480V - 208VC
5D137T-5L2
5C-129T-5L6480V - 208VC
5D111T-5L9480V - 208V
5C-122T-5QL3480V - 208VA
5B-122T-5QL6480V - 208VA
5E-145T-(5E-145)480V - 208VDNo GEC
6B-121T-6CL1480V - 208VCNeeds 6" to back wall
6A-109T-6EL1480V - 208VDPoor condition
6E-145T-6L6480V - 208VBNeeds 6" to back wall
6C-145T-NP2480V - 208VA
7E-108T-7EL2480V - 208VCNeeds 6" to back wall
7C-145T-7L4480V - 208VC
7E-108T-7L6480V - 208VCNeeds 6" to back wall
7D-116T-7L7480V - 208VBNeeds 6" to back wall
Notes: No Vibration Isolators found on any transformers. Transformer clearance of 6" is required by UL1591, not NEC

OIL FILLED PAD MOUNT XFORMERS

Equipment Condition Assessment
* EQUIPMENT CONDITION:

(A) Like New Condition - Majority of useful life span remains. "Excellent"

(B) Good Condition - Over half of useful life span remains. "Good" (C+) Above Average Condition - Less than half of useful life span remains, but in good condition. "Above Average"

(C) Average Condition - Less than half of useful life span remains. "Average" (C-) Workable Condition - May be past assigned useful life, but still working. "Keep an eye on it"

(D) Poor Condition - Past assigned useful life. Failure is not critical. "Poor"

(F) Critical Condition - Needs immediate attention. "Failing"

LocationEquipmentVoltageAssessmentcomments 36 month & IR Scan Annual
OIL FILLED PAD MOUNT TRANSFORMERS
GE-117Substation A-A (XF-AA)13800V - 480VC
GE-117Substation A-B (XF-AB)13800V - 480VC
GD-123Substation B (XF-B1)13800V - 480VC
GD-123Substation C (XF-C1)13800V - 480VC
GD-123Substation D (XF-D1)13800V - 480VC
3A-102Substation F (XF-F1)13800V - 480VC
3A-102Substation G (XF-G1)13800V - 480VC
GD-123Substation H (XF-H1)13800V - 480VB
outsidePV SITE 113800V - 480VB
outsidePV SITE 213800V - 480VB
outsidePV SITE 313800V - 480VB

File details come from the government source that posted it. Updated .