This solicitation requests electrical system preventive maintenance and testing services for two VA medical facilities in Little Rock and North Little Rock, Arkansas. The opportunity is set aside for veteran-owned small businesses. Interested parties must be registered in the VA's Vendor Information Pages and SAM by the quote submission deadline of August 29, 2022. Questions are due by August 22 and a mandatory site visit will be held on August 18. Quotes must include pricing, certifications, and representations. The work includes preventive maintenance and testing of electrical systems and components at the two medical campuses.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs Little Rock Veterans Affairs Medical Center
Little Rock, Arkansas
VISN 16
ELECTRICAL DISTRIBUTION
SYSTEM CONDITION ASSESSMENT
Study Update
Prepared by:
E.K. FOX & ASSOCIATES, LTD.
CONSULTING ENGINEERS
4500 Southgate Place, Suite 800, Chantilly, VA 20151
July 31, 2020
36C25622Q1188 0001 Exhibit L
Little Rock VAMC – Little Rock, Arkansas Electrical Condition Assessment - Update
Prepared for: Dept. of Veterans Affairs Page 1 Prepared by: E.K. Fox & Associates, Ltd.
4500 Southgate Place, Suite 800 Chantilly, VA 20151
TABLE OF CONTENTS
1. EXECUTIVE SUMMARY
2. INTRODUCTION
2.1. Personnel
2.2. Calculation Methods
2.3. Study Assumptions
3. FAULT CURRENT ANALYSIS
3.1. Introduction
3.2. Sources of Fault Current
3.3. Calculation Scenarios
3.4. SKM Power*Tools Input Data Reports
3.5. Short Circuit Calculation Results
3.6. Equipment Evaluation Results
4. PROTECTIVE DEVICE COORDINATION STUDY
4.1. Introduction
4.2. Existing and Proposed Protective Device Settings
4.3. Underrated Feeders
4.4. Replacement System Components
4.5. Analysis and Recommendations
4.6. Time-Current Characteristic Graphs Descriptions and Analysis
4.7. Time-Current Characteristic Graphs
5. ARC FLASH HAZARD ANALYSIS
5.1. Introduction
5.2. Basis of Study
5.3. Disclaimer
5.4. Results
APPENDICES
A. One-Line Diagrams
Prepared for: Dept. of Veterans Affairs Section 1 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
1. EXECUTIVE SUMMARY
In 2015, The Department of Veterans Affairs – Office of Construction and Facilities Management (CFM), commissioned E.K. Fox and Associates, Ltd. (EKFox) to perform the electrical system condition assessment of the Little Rock Veterans Affairs Medical Center (VAMC). The scope of the assessment was to provide short circuit analysis, protective device coordination study, voltage drop analysis, arc flash hazard analysis, and equipment condition assessment with the purpose of improving the safety and reliability of the electrical distribution system. The report containing the findings and recommended corrections was delivered to the VA CFM and the VAMC in 2016.
The findings and recommended corrections addressed numerous issues that ranged from safety and code related items, to coordination adjustments to reduce nuisance trips, and equipment replacement to address aging or damaged equipment. Safety related items are a higher priority and require a more immediate response whereas some coordination and condition-related equipment replacements allow for more flexibility in how soon they need to be addressed.
Currently, Cornerstone Contracting, Inc. (CCI) is implementing the recommended corrections based on findings from the previous study. Based on the project scope of work (SOW), the equipment replacements and adjustments being provided by CCI are primarily to address the previous coordination adjustments and equipment condition-related findings. However, the CCI SOW does not cover all of the recommended corrective actions that were in the previous study.
EKFox has been tasked with providing an update to the original report and analyses. In lieu of a new complete site survey, EKFox has performed the analyses using input from CCI, the VA, and equipment vendors to update the software model and electrical analyses. In some cases, certain assumptions were necessary to perform the report updates. These assumptions have been detailed in Section 2. Also, the SOW does not specifically state if all of the other recommended corrections had been performed under a previous effort. For example, it is likely that the higher priority activity of replacing the “failed” circuit breakers identified in the device evaluation would have been accomplished under a separate, nearer-term effort. Therefore, we have taken the more conservative approach to re-report these findings, which can then be field verified to determine if they have already been addressed or are still needing correction.
Our updated short circuit analysis, which aims to identify if circuit breakers can safely interrupt the fault current due to a short, has currently shown twenty-three (23) overcurrent protection devices (OCPD’s) have failed the device evaluation for interrupting capacity or voltage rating. However, it is possible that some or all of these failed devices have been replaced since the original study with ones that meet the required ratings. Seventeen (17) of these OCPD’s are in the EES and only fail when both generators are connected to the EES at the same time. The previous study had recommended only connecting one (1) generator to the EES or replacing the entire EES with equipment containing OCPD’s with adequate interrupt capacity. Section 3 of this report has additional details.
The updated protective device coordination study uses the current fixed and adjustable settings of the existing OCPD’s to graphically display how those devices will respond to a short or overload event. The settings are then adjusted to allow the protective device closest to the fault to interrupt
Prepared for: Dept. of Veterans Affairs Section 1 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
the circuit thereby minimizing the disruption of electrical service. Our study currently identifies two
(2) OCPD’s that may require settings adjustment or replacement to either better coordinate with other OCPD’s or to provide the correct level of protection for downstream conductors. One
(1) of these current recommendations is due to the fact that adjustment and replacement for CB- GDQH5-1 was recommended in the previous coordination study but did not seem to appear in the CCI SOW. The other is because the previous study had recommended replacing the main circuit breaker in panel 2QL3 to match the ampacity of the panel. However, the CCI SOW states that this panel is being replaced with a 225A panel that has a correctly rated main circuit breaker. As such, the current recommendation is to leave the new 225A main circuit breaker in place provided that the panel is rated 225A. There is no coordination issue that would necessitate downsizing the main in the new panel. Additional details can be found in Section 4: Protective Device Coordination Study.
We also include the time/current characteristic (TCC) graphs, which that show the interaction of the OCPD’s with the existing and recommended settings applied, in Section 4.
Finally, we performed an updated arc flash hazard analysis to determine the incident energy released by an arcing fault at the location of each device in the electrical distribution system. This analysis is also used to determine safe working distances and the required personal protective equipment (PPE) for personnel working in the panel. The results show a total of two (2) buses that have an incident energy that is greater than 40 cal/cm2. EKFox will also provide an updated set of arc flash labels that can be applied to the panels and equipment to warn of the potential electrical dangers. Additional details of the arc flash analysis can be found in Section 5.
Prepared for: Dept. of Veterans Affairs Section 2 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
2. INTRODUCTION
2.1. Personnel
The EKFox Team that produced this report consisted of highly skilled engineers and technicians. They were:
Raleigh Stewart, P.E. RDStewart@ekfox.com (703-267-6783)
Charles Sisung, P.E. CFSisung@ekfox.com (877-520-4771 x105)
Jarrett Elliott JCElliott@ekfox.com
Tasha Laura TJLaura@ekfox.com
2.2. Calculation Methods
As mentioned, this study includes the following elements: short circuit calculations, overcurrent protective device coordination, voltage drop analysis, arc flash hazard analysis, and a condition assessment of electrical equipment.
All calculations have been performed using software developed by SKM Systems Analysis, Inc. The software is named Power*Tools, Version 9.0.0.3 and it is a modular assembly of programs. The following modules have been used for this study:
System Model Development DAPPER Short Circuit Calculations Comprehensive Fault Evaluation Protective Device Coordination CAPTOR Voltage Drop Analysis DAPPER Arc Flash Hazard Analysis Arc Flash Evaluation Device Evaluation Equipment Evaluation
Version 9.0.0.3 of the Power*Tools software has been used for all of the calculations presented throughout this report. Additional information related to this software package can be found at www.skm.com.
2.3. Study Assumptions
The EKFox team has attempted, to the extent practical, to provide accurate updates for the previous study. In some cases, certain assumptions had to be made as a compromise between the project scope, available and provided equipment information, and required inputs to the software model. The following describes types of data that has been assumed for the purposes of this study:
Prepared for: Dept. of Veterans Affairs Section 2 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
2.3.1. Utility Information
Updated utility fault current information and system parameters were not provided for this analysis. As such, the utility information used in the previous study has been used for these analyses.
2.3.2. Replacement System Components
When complete equipment information was provided for a replacement system component, the model was updated to reflect this information. For items where some information was missing (e.g. breaker type, trip setting, etc.) The previous survey information, previous proposed study recommendation, or engineering judgment was used to fill in the missing information. In cases where the information for a replacement component (e.g. a larger ampacity breaker replacing a smaller ampacity breaker with no change to conductor size) conflicted with the original surveyed information (or introduced a new code or safety related issue), it was assumed that the replacement would have been adjusted or substituted to match the original equipment size or setting.
2.3.3. Previous Study Coordination Recommendations
The current study assumes that all of the previous study recommended coordination changes and replacements have been applied to the system. The updated coordination study has been accomplished by coordinating the replacement system components with the results from the previous coordination study.
2.3.4. Previous Study Device Evaluation Analysis
It is likely that some of the devices that failed the previous fault current and device evaluation analyses have been replaced prior to this project. However, the device parameters were not updated unless equipment information was provided to do so. Thus, devices that failed the current device evaluation should be field verified to determine if they were replaced as part of a previous effort or that the device requires immediate replacement.
2.3.5. Newly Added Equipment or Areas
The scope of equipment and areas for the present study only includes the equipment and areas that were part of the previous study. No equipment or survey information was provided for any newly added equipment or areas, so they have not been considered in this study.
Prepared for: Dept. of Veterans Affairs Section 3 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
3. FAULT CURRENT ANALYSIS
3.1. Introduction
The fault current analysis is developed based on data for the Little Rock VAMC electrical distribution system. The analysis examines the short circuit currents that occur at selected locations in the electrical system and is used to determine the capability of the system to withstand an electrical fault without damage.
One-line diagrams of the system are included in Appendix A. Reports showing the complete input data used to construct each model are included in Section 3.4.
3.2. Sources of Fault Current
The short circuit fault current calculations performed for the Little Rock VAMC electrical system are based on the available fault current information that was originally obtained from the utility (Entergy Arkansas, Inc.) for the original study.
In summary, the available fault current from the Entergy system is:
Supply from Source 1 Feeder (to PSSS-North):
Three-Phase Bolted Fault: 6,154A sym X/R = 2.7 Single-Phase to Ground: 4,384A sym X/R = 0.7
Supply from Source 2 Feeder (to PSSS-South):
Three-Phase Bolted Fault: 4,219A sym X/R = 2.7 Single-Phase to Ground: 3,654A sym X/R = 0.7
Supply from Source 3 Feeder (to Grounds Maintenance Building #2):
Three-Phase Bolted Fault: 9,378A sym X/R = 8.88 Single-Phase to Ground: 7,853A sym X/R = 3.44
Additional sources of short circuit fault current are the induction motors which operate throughout the system. Typically, these motor contributions are relatively small especially when a fault is located some distance from the motor, and when a motor is under 50HP.
3.3. Calculation Scenarios
The original report included four (4) scenarios that will be revisited in this analysis. The first DAPPER report included in this submission is based on normal interconnection of the electrical power system elements fed by the utility service. Additional reports for this system
Prepared for: Dept. of Veterans Affairs Section 3 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
were generated for three (3) other scenarios. The four (4) total scenarios are summarized in the table below.
Scenario Utility Feeds PSSS Tie Breaker Generators ATS’s Normal Interconnection
Utility Feeds Active
Out Out Normal Pos.
All Loads on Larger Utility Feed
Utility Feeds Active except PSSS-South
Feed Out
Active Out Normal Pos.
Emergency - One Generator
Out
Out One Active Emergency Pos.
Emergency – Both Generators
Out
Out Both Active Emergency Pos.
3.4. SKM Power*Tools Input Data Reports
The included DAPPER input report lists the system components used to calculate the short circuit currents for the Normal Interconnection scenario described above. Additional input reports were generated and used for calculations for the other scenarios, but only the report for the Normal Interconnection scenario is included here for brevity. The reports for the other scenarios are included in the soft copy disc.
DAPPER Fault Analysis Input Report (English)
Project: Little Rock
Normal Utility
Utilities
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data -------- PU (100 MVA Base)
X PUR PUX/RUnitsDuty
UTIL-0001 BUS-PSSS-NORTH 13,800 Amps 2.70In 6,154
SLG:
3P:
Amps 1.22 0.940 1.342
Pos:
Zero: 4,384
0.236 0.638
UTIL-0002 BUS-PSSS-SOUTH 13,800 Amps 2.70In 4,219
SLG:
3P:
Amps 1.38 0.925 1.322
Pos:
Zero: 3,654
0.344 0.930
UTIL-0003 BUS-XF-BLDG2-PRI 13,200 Amps 8.88In 9,378
SLG:
3P:
Amps 5.26 0.715 0.208
Pos:
Zero: 7,853
0.052 0.463
Generators
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data --------
Base kVA X" X/R
PU (100 MVA Base)
R PU X PU
GEN-0001 480BUS-0034 2,500.00 26.55 0.00 0.00Out
0.00
0.00 0.00
0.15
0.15
0.15
26.55
26.55 0.00
GEN-0002 480BUS-0035 2,500.00 26.55 0.00 0.00Out
0.00
0.00 0.00
0.15
0.15
0.15
26.55
26.55 0.00
Motors
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
AC-1 BUS-0845 480 10.03 0.1692 10.00 168.695 1,687.015In 1
AT-1 BUS-0751 480 10.03 0.1692 10.00 168.695 1,687.015In 1
AT-2 BUS-0752 480 10.03 0.1692 10.00 168.695 1,687.015In 1
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
AT-3 BUS-0753 480 10.03 0.1692 10.00 168.695 1,687.015In 1
ATC. AIR COMP. BUS-0847 480 50.13 0.1692 10.00 16.869 168.702In 2
BOILER-1 BUS-0840 480 10.78 0.1692 10.00 156.925 1,569.317In 1
BOILER-2 BUS-0841 480 10.78 0.1692 10.00 156.925 1,569.317In 1
BOILER-3 BUS-0842 480 10.78 0.1692 10.00 156.925 1,569.317In 1
C1-NORTH BUS-0871 480 40.11 0.1692 10.00 42.174 421.754In 1
C1-SOUTH BUS-0872 480 40.11 0.1692 10.00 42.174 421.754In 1
CHILLER 3 BUS-0860 480 170.00 0.1692 10.00 9.950 99.503In 1
CHILLER-1 BUS-0026 4,160 1,118.75 0.1692 10.00 1.512 15.120In 1
CHILLER-2 BUS-0025 4,160 1,067.50 0.1692 10.00 1.585 15.846In 1
CHWP-1 BUS-0870 480 75.20 0.1692 10.00 22.493 224.935In 1
CHWP-3 BUS-0823 480 15.04 0.1692 10.00 112.463 1,124.677In 1
CT. 1(1) BUS-0824 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 1(2) BUS-0825 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 1(3) BUS-0826 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 1(4) BUS-0827 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 2(1) BUS-0828 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 2(2) BUS-0829 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 2(3) BUS-0830 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 2(4) BUS-0831 480 40.11 0.1692 10.00 42.174 421.754In 1
CT. 3 BUS-0821 480 25.07 0.1692 10.00 67.478 674.806In 1
CWP-1 BUS-0869 480 75.20 0.1692 10.00 22.493 224.935In 1
CWP-3 BUS-0822 480 20.05 0.1692 10.00 84.347 843.508In 1
DOOR AIR COMP. BUS-0839 480 10.03 0.1692 10.00 168.695 1,687.015In 1
DW-1 BUS-0759 480 2.01 0.1692 10.00 843.474 8,435.076In 1
DW-2 BUS-0760 480 2.01 0.1692 10.00 843.474 8,435.076In 1
ELEV-P1 BUS-0746 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV-P2 BUS-0747 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV-P3 BUS-0750 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV-P4 BUS-0748 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV-P5 BUS-0749 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV-S1 BUS-0754 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV-S2 BUS-0755 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV-S3 BUS-0756 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV-S4 BUS-0757 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV-S5 BUS-0758 480 60.16 0.1692 10.00 28.116 281.169In 1
EX-13 BUS-0780 480 10.03 0.1692 10.00 168.695 1,687.015In 1
EX-14 BUS-0800 480 15.04 0.1692 10.00 112.463 1,124.677In 1
EX-15 BUS-0813 480 15.04 0.1692 10.00 112.463 1,124.677In 1
EX-5 BUS-0790 480 10.03 0.1692 10.00 168.695 1,687.015In 1
EX-7 BUS-0768 480 10.03 0.1692 10.00 168.695 1,687.015In 1
EX-8 BUS-0806 480 10.03 0.1692 10.00 168.695 1,687.015In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
EX-9 BUS-0815 480 10.03 0.1692 10.00 168.695 1,687.015In 1
FHX-12 BUS-0812 480 20.05 0.1692 10.00 84.347 843.508In 1
FIRE PUMP BUS-0330 480 40.11 0.1692 10.00 42.174 421.754In 1
FWP-1 BUS-0843 480 15.04 0.1692 10.00 112.463 1,124.677In 1
FWP-2 BUS-0844 480 15.04 0.1692 10.00 112.463 1,124.677In 1
HWP-1 BUS-0807 480 20.05 0.1692 10.00 84.347 843.508In 1
HWP-2 BUS-0808 480 20.05 0.1692 10.00 84.347 843.508In 1
HWSF-1 BUS-0781 480 10.03 0.1692 10.00 168.695 1,687.015In 1
MCC-1-LOAD BUS-MCC-1 480 3.01 0.1692 10.00 93.719 937.231In 6
MCC-2-LOAD BUS-MCC-2 480 3.76 0.1692 10.00 37.488 374.892In 12
MCC-3-LOAD BUS-MCC-3 480 2.51 0.1692 10.00 56.232 562.339In 12
MCC-4-LOAD BUS-MCC-4 480 2.01 0.1692 10.00 168.695 1,687.015In 5
MCC-NE-LOAD BUS-MCC-NE 480 3.76 0.1692 10.00 44.985 449.871In 10
MCC-NW-LOAD BUS-MCC-NW 480 3.61 0.1692 10.00 29.287 292.885In 16
MCC-Q1A-LOAD BUS-MCC-Q1A 480 2.51 0.1692 10.00 112.463 1,124.677In 6
MCC-Q1B-LOAD BUS-MCC-Q1B 480 5.01 0.1692 10.00 112.463 1,124.677In 3
MCC-QN-LOAD BUS-MCC-QN 480 3.01 0.1692 10.00 56.232 562.339In 10
MCC-QS-LOAD BUS-MCC-QS 480 4.01 0.1692 10.00 84.347 843.508In 5
MCC-SE-LOAD BUS-MCC-SE 480 3.51 0.1692 10.00 34.428 344.289In 14
MCC-SW-LOAD BUS-MCC-SW 480 5.01 0.1692 10.00 42.174 421.754In 8
RF-10 BUS-0789 480 10.03 0.1692 10.00 168.695 1,687.015In 1
RF-15 BUS-0767 480 15.04 0.1692 10.00 112.463 1,124.677In 1
RF-2 BUS-0816 480 10.03 0.1692 10.00 168.695 1,687.015In 1
RF-4 BUS-0805 480 10.03 0.1692 10.00 168.695 1,687.015In 1
RF-8 BUS-0814 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SCHWP-1 BUS-0868 480 125.34 0.1692 10.00 13.496 134.961In 1
SCHWP-2 BUS-0867 480 125.34 0.1692 10.00 13.496 134.961In 1
SF-1 BUS-0782 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-10 BUS-0784 480 40.11 0.1692 10.00 42.174 421.754In 1
SF-11 BUS-0774 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-12 BUS-0775 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-13 BUS-0762 480 30.08 0.1692 10.00 56.232 562.338In 1
SF-14 BUS-0763 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-15 BUS-0804 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-16 BUS-0817 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-17 BUS-0795 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-18 BUS-0785 480 15.04 0.1692 10.00 112.463 1,124.677In 1
SF-19 BUS-0764 480 40.11 0.1692 10.00 42.174 421.754In 1
SF-2 BUS-0819 480 40.11 0.1692 10.00 42.174 421.754In 1
SF-20 BUS-0776 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-21 BUS-0777 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-22 BUS-0765 480 25.07 0.1692 10.00 67.478 674.806In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
SF-23 BUS-0796 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-24 BUS-0797 480 30.08 0.1692 10.00 56.232 562.338In 1
SF-25 BUS-0798 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-26 BUS-0786 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-27 BUS-0778 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-28 BUS-0766 480 15.04 0.1692 10.00 112.463 1,124.677In 1
SF-29 BUS-0779 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-3 BUS-0773 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-30 BUS-0799 480 30.08 0.1692 10.00 56.232 562.338In 1
SF-31 BUS-0787 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-32 BUS-0788 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-4 BUS-0802 480 40.11 0.1692 10.00 42.174 421.754In 1
SF-5 BUS-0761 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-6 BUS-0803 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-7 BUS-0794 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-8 BUS-0818 480 40.11 0.1692 10.00 42.174 421.754In 1
SF-9 BUS-0783 480 40.11 0.1692 10.00 42.174 421.754In 1
V-4 BUS-0838 480 10.03 0.1692 10.00 168.695 1,687.015In 1
V-5 BUS-0801 480 10.03 0.1692 10.00 168.695 1,687.015In 1
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-PSSS-NORTH
BUS-PSSS-SOUTH
1 30 1200 Epoxy Pos:
Zero:
0.0002 0.0010
0.0052
BUS DUCT TIE In
0.0011
BuswayCopper
BUS-PSSS-NORTH
BUS-0003
1 4 1200 Epoxy Pos:
Zero:
0.0000 0.0001
0.0007
BUS-CUBE-01 In
0.0001
BuswayCopper
BUS-PSSS-SOUTH
BUS-0004
1 4 1200 Epoxy Pos:
Zero:
0.0000 0.0001
0.0007
BUS-CUBE-02 In
0.0001
BuswayCopper
BUS-0016
BUS-XF-B1-PRI
1 4 1200 Epoxy Pos:
Zero:
0.0000 0.0001
0.0007
BUS-SUBSTN-B-01 In
0.0001
BuswayCopper
BUS-0018
BUS-0149
1 4 Pos:
Zero:
0.0000 0.0000
0.0000
BUS-SUBSTN-F-01 Out
0.0000
Non-MagneticCopper
BUS-0019
BUS-XF-F1-PRI
1 4 1200 Epoxy Pos:
Zero:
0.0000 0.0001
0.0007
BUS-SUBSTN-F-02 In
0.0001
BuswayCopper
BUS-USSA-B
BUS-USSA-A
1 5 3000 Epoxy Pos:
Zero:
0.0100 0.0056
0.0302
BUS-USSA-TIE In
0.0592
BuswayCopper
BUS-3DQH2
BUS-0194
1 1 1200 Epoxy Pos:
Zero:
0.0048 0.0023
0.0121
CB-3DQH2-14 In
0.0286
BuswayCopper
BUS-GL6(1)
BUS-GL6(2)
2 6 300 PVC Pos:
Zero:
0.3217 0.3419
0.8418
CB-6L6(2) In
1.0138
MagneticCopper
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-0899
BUS-(5E-145)
1 1 1/0 PVC Pos:
Zero:
0.2959 0.1248
0.3072
CBL-(5E-145) Out
0.9324
MagneticCopper
BUS-XF-(GCH2-1)-SEC 1 1 4/0 PVC Pos:
Zero:
0.1479 0.1149
0.2829
CBL-(GCH2-1) Out
0.4662
MagneticCopper
BUS-0908
1 1 4 PVC Pos:
Zero:
0.1393 0.0274
0.0675
CBL-0771 Out
0.4391
MagneticCopper
BUS-XF-1CL1-SEC
BUS-1CL1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1CL1 In
8.8286
MagneticCopper
BUS-XF-1CL2-SEC
BUS-1CL2
1 10 1/0 PVC Pos:
Zero:
2.9586 1.2482
3.0718
CBL-1CL2 In
9.3242
MagneticCopper
BUS-1DH1
BUS-1H1
1 5 2/0 PVC Pos:
Zero:
0.2214 0.1157
0.2847
CBL-1DH1-1 In
0.6975
MagneticCopper
BUS-1DH1
BUS-1H2
1 231 2/0 PVC Pos:
Zero:
10.2266 5.3439
13.1542
CBL-1DH1-2 In
32.2237
BUS-1DH1
BUS-1H3
1 450 4/0 PVC Pos:
Zero:
12.5000 9.7070
23.9063
CBL-1DH1-3 In
39.3945
MagneticCopper
BUS-1DH1
BUS-XF-1L1-PRI
1 8 2 PVC Pos:
Zero:
0.7014 0.2031
0.5000
CBL-1DH1-4 In
2.2104
MagneticCopper
BUS-1DH1
BUS-XF-1L10-PRI
1 4 2/0 PVC Pos:
Zero:
0.1771 0.0925
0.2278
CBL-1DH1-5 In
0.5580
MagneticCopper
BUS-1DH3
BUS-1H9
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-1DH3-1 In
2.7630
BUS-1DH3
BUS-XF-1L9-PRI
1 8 4/0 PVC Pos:
Zero:
0.2222 0.1323
0.3257
CBL-1DH3-2 In
0.7003
MagneticCopper
BUS-1DH3
BUS-1HK
1 30 2/0 PVC Pos:
Zero:
1.3281 0.6940
1.7083
CBL-1DH3-5 In
4.1849
MagneticCopper
BUS-1DH3
BUS-XF-FRYER-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-1DH3-6 In
4.1854
MagneticCopper
BUS-0200
BUS-1DQH1
1 100 500 PVC Pos:
Zero:
1.2760 2.0226
4.9783
CBL-1DQH1 In
4.0191
BUS-1DQH1
BUS-XF-1QL6-PRI
1 8 1 PVC Pos:
Zero:
0.5556 0.1979
0.4872
CBL-1DQH1-1 In
1.7507
MagneticCopper
BUS-XF-TABLE-SEC
BUS-1E205
1 90 2 PVC Pos:
Zero:
42.0211 12.1695
29.9556
CBL-1E205 In
132.4288
MagneticCopper
BUS-1EH1
BUS-XF-1EL1-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-1EH1-1 In
4.1854
MagneticCopper
BUS-1EH2
BUS-XF-1EL2-PRI
1 20 12 PVC Pos:
Zero:
16.2326 0.6042
1.4878
CBL-1EH2-1 In
51.1580
BUS-1EH3
BUS-XF-1EL3-PRI
1 6 12 PVC Pos:
Zero:
4.8698 0.2370
0.5836
CBL-1EH3-1 In
15.3474
MagneticCopper
BUS-1EH4
BUS-XF-1EL4-PRI
1 10 12 PVC Pos:
Zero:
8.1163 0.3950
0.9727
CBL-1EH4-1 In
25.5790
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-XF-1EL1-SEC
BUS-1EL1
1 5 1/0 PVC Pos:
Zero:
1.4793 0.6241
1.5359
CBL-1EL1 In
4.6621
MagneticCopper
BUS-XF-1EL2-SEC
BUS-1EL2
1 6 8 PVC Pos:
Zero:
11.2472 1.0457
2.5740
CBL-1EL2 In
35.4461
BUS-XF-1EL3-SEC
BUS-1EL3
1 10 8 PVC Pos:
Zero:
18.7454 1.7428
4.2899
CBL-1EL3 In
59.0768
MagneticCopper
BUS-XF-1EL4-SEC
BUS-1EL4
1 12 8 PVC Pos:
Zero:
22.4945 2.0913
5.1479
CBL-1EL4 In
70.8922
MagneticCopper
BUS-1H10
BUS-XF-1L13-PRI
1 10 6 PVC Pos:
Zero:
2.2135 0.2973
0.7322
CBL-1H10-1 In
6.9757
MagneticCopper
BUS-1H2
BUS-XF-1L2-PRI
1 173 10 PVC Pos:
Zero:
88.6024 4.9107
12.0890
CBL-1H2-1 In
279.2328
BUS-1H3
BUS-XF-1L3-PRI
1 6 2 PVC Pos:
Zero:
0.5260 0.1167
0.2872
CBL-1H3-1 In
1.6578
MagneticCopper
BUS-1H5
BUS-XF-1L5-PRI
1 5 2 PVC Pos:
Zero:
0.4384 0.0972
0.2394
CBL-1H5-1 In
1.3815
MagneticCopper
BUS-1H8
BUS-XF-1L8-PRI
1 1 4 PVC Pos:
Zero:
0.1393 0.0274
0.0675
CBL-1H8-1 In
0.4391
MagneticCopper
BUS-1HX1
BUS-XF-1LX1-PRI
1 4 1 PVC Pos:
Zero:
0.2778 0.0990
0.2436
CBL-1HX1-1 In
0.8753
BUS-1HX1
BUS-XF-1LX3-PRI
1 10 1 PVC Pos:
Zero:
0.6944 0.2474
0.6089
CBL-1HX1-2 In
2.1884
MagneticCopper
BUS-1HX2
BUS-XF-1LX2-PRI
1 40 2 PVC Pos:
Zero:
3.5069 1.0156
2.5000
CBL-1HX2-1 In
11.0521
MagneticCopper
BUS-XF-1L1-SEC
BUS-1L1(1)
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1L1 In
8.8286
MagneticCopper
BUS-XF-1L10-SEC
BUS-1L10
1 16 4/0 PVC Pos:
Zero:
2.3669 1.8380
4.5266
CBL-1L10 In
7.4593
BUS-1L10
BUS-1L11
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1L10-1 In
8.8286
MagneticCopper
BUS-1L1(1)
BUS-1L1(2)
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1L1-2 In
8.8286
MagneticCopper
BUS-XF-1L13-SEC
BUS-1L13
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-1L13 In
14.7143
MagneticCopper
BUS-XF-1L2-SEC
BUS-1L2
1 8 1 PVC Pos:
Zero:
2.9586 1.0540
2.5943
CBL-1L2 In
9.3232
BUS-XF-1L3-SEC
BUS-1L3 (1)
1 5 300 PVC Pos:
Zero:
0.5362 0.5698
1.4030
CBL-1L3 (1) In
1.6896
MagneticCopper
BUS-1L3 (1)
BUS-1L3 (2)
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-1L3 (2) In
2.0276
MagneticCopper
BUS-1L3 (1)
BUS-1PL1
1 30 2 PVC Pos:
Zero:
14.0070 4.0565
9.9852
CBL-1L3(1)-1 In
44.1429
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-1L3 (1)
BUS-1PL3
1 64 2 PVC Pos:
Zero:
29.8817 8.6538
21.3018
CBL-1L3(1)-2 In
94.1716
BUS-1L3 (1)
BUS-1PL2
1 40 8 PVC Pos:
Zero:
74.9815 6.9712
17.1598
CBL-1L3(1)-3 In
236.3073
MagneticCopper
BUS-XF-1L5-SEC
BUS-1L5(1)
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-1L5(1) In
2.0276
MagneticCopper
BUS-1L5(1)
BUS-1PL4
1 5 4 PVC Pos:
Zero:
3.7098 0.7304
1.7983
CBL-1L5(1)-1 In
11.6910
MagneticCopper
BUS-1L5(1)
BUS-1L5(2)
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-1L5(2) In
2.0276
BUS-XF-1L6-SEC
BUS-1L6(1)
1 8 300 PVC Pos:
Zero:
0.8580 0.9116
2.2448
CBL-1L6 In
2.7034
MagneticCopper
BUS-1L6(1)
BUS-1L6(2)
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-1L6-2 In
2.0276
MagneticCopper
BUS-XF-1L8-SEC
BUS-1L8(1)
1 1 2/0 PVC Pos:
Zero:
0.2358 0.1232
0.3033
CBL-1L8(1) In
0.7429
MagneticCopper
BUS-1L8(1)
BUS-1L8(2)
1 1 2/0 PVC Pos:
Zero:
0.2358 0.1232
0.3033
CBL-1L8(2) In
0.7429
BUS-XF-1L9-SEC
BUS-1L9-A
2 8 300 PVC Pos:
Zero:
0.4290 0.4558
1.1224
CBL-1L9-A In
1.3517
MagneticCopper
BUS-1L9-A
BUS-1L9-C
1 10 4 PVC Pos:
Zero:
7.4196 1.1164
2.7482
CBL-1L9-A-1 In
23.3820
MagneticCopper
BUS-1L9-A
BUS-1PL6(1)
1 90 4/0 PVC Pos:
Zero:
13.3136 10.3389
25.4623
CBL-1L9-A-2 In
41.9587
MagneticCopper
BUS-1L9-A
BUS-1L9-B
2 10 300 PVC Pos:
Zero:
0.5362 0.5698
1.4030
CBL-1L9-B In
1.6896
BUS-1L9-B
BUS-1L9-D
1 10 6 PVC Pos:
Zero:
11.7881 1.5833
3.8993
CBL-1L9-B-1 In
37.1487
MagneticCopper
BUS-XF-1LX1-SEC
BUS-1LX1
1 10 2/0 PVC Pos:
Zero:
2.3576 1.2320
3.0325
CBL-1LX1 In
7.4288
MagneticCopper
BUS-XF-1LX2-SEC
BUS-1LX2
1 10 4/0 PVC Pos:
Zero:
1.4793 1.1488
2.8291
CBL-1LX2 In
4.6621
MagneticCopper
BUS-XF-1LX3-SEC
BUS-1LX3
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-1LX3 In
11.7715
BUS-1PL6(1)
BUS-1PL6(2)
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
CBL-1PL6-2 In
2.7972
MagneticCopper
BUS-1QH1
BUS-XF-1QL1-PRI
1 10 6 PVC Pos:
Zero:
2.2135 0.2973
0.7322
CBL-1QH1-1 In
6.9757
MagneticCopper
BUS-1QH1
BUS-GQHB
1 176 1/0 PVC Pos:
Zero:
9.7778 4.1250
10.1521
CBL-1QH1-2 In
30.8153
MagneticCopper
BUS-1QH1 1 224 6 PVC Pos: 49.5833 6.6597CBL-1QH1-3 In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-XF-2QL2-PRI Zero: 16.4014 156.2556
BUS-1QH1
BUS-XF-1QL3-PRI
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-1QH1-4 In
1.6578
MagneticCopper
BUS-1QH2
BUS-XF-1QL2-PRI
1 6 10 PVC Pos:
Zero:
3.0729 0.2224
0.5477
CBL-1QH2-1 In
9.6844
MagneticCopper
BUS-1QH2
BUS-XF-2QL3-PRI
1 25 4 PVC Pos:
Zero:
3.4831 0.6858
1.6884
CBL-1QH2-2 In
10.9766
MagneticCopper
BUS-1QH3
BUS-XF-1QL5-PRI
1 12 8 PVC Pos:
Zero:
4.2240 0.3927
0.9667
CBL-1QH3-1 In
13.3120
BUS-1QH6
BUS-XF-1QL8-PRI
1 10 2/0 PVC Pos:
Zero:
0.4427 0.2313
0.5694
CBL-1QH6-1 In
1.3950
MagneticCopper
BUS-1QH6
BUS-1QH6-A
1 12 10 PVC Pos:
Zero:
6.1458 0.4448
1.0953
CBL-1QH6-2 In
19.3688
MagneticCopper
BUS-1QH7
BUS-XF-1QL10-PRI
1 10 4 PVC Pos:
Zero:
1.3932 0.2743
0.6753
CBL-1QH7-1 In
4.3906
MagneticCopper
BUS-0130
BUS-1QHX
2 30 250 PVC Pos:
Zero:
0.3594 0.3223
0.7936
CBL-1QHX In
1.1322
BUS-1QHX 1 1 1/0 PVC Pos:
Zero:
0.0556 0.0234
0.0577
CBL-1QHX-1 Out
0.1751
MagneticCopper
BUS-1QHX 1 1 1/0 PVC Pos:
Zero:
0.0556 0.0234
0.0577
CBL-1QHX-2 Out
0.1751
MagneticCopper
BUS-1QHX 1 1 1/0 PVC Pos:
Zero:
0.0556 0.0234
0.0577
CBL-1QHX-4 Out
0.1751
MagneticCopper
BUS-1QHX 1 1 350 PVC Pos:
Zero:
0.0164 0.0213
0.0525
CBL-1QHX-6 Out
0.0517
BUS-XF-1QL1-SEC
BUS-1QL1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1QL1 In
8.8286
MagneticCopper
BUS-XF-1QL10-SEC
BUS-1QL10(1)
1 8 2/0 PVC Pos:
Zero:
1.8861 0.9856
2.4260
CBL-1QL10(1) In
5.9430
MagneticCopper
BUS-1QL10(1)
BUS-1QL10(2)
1 8 2/0 PVC Pos:
Zero:
1.8861 0.9856
2.4260
CBL-1QL10(2) In
5.9430
MagneticCopper
BUS-XF-1QL2-SEC
BUS-1QL2
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-1QL2 In
14.0292
BUS-XF-1QL3-SEC
BUS-1QL3
1 20 3/0 PVC Pos:
Zero:
3.7213 2.3992
5.9079
CBL-1QL3 In
11.7280
MagneticCopper
BUS-XF-1QL4-SEC
BUS-1QL4
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-1QL4 In
14.7143
MagneticCopper
BUS-XF-1QL5-SEC
BUS-1QL5
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1QL5 In
8.8286
MagneticCopper
BUS-XF-1QL6-SEC
BUS-1QL6
1 8 4/0 PVC Pos:
Zero:
1.1834 0.9190
2.2633
CBL-1QL6 In
3.7297
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-1QL6 1 1 2/0 PVC Pos:
Zero:
0.2358 0.1232
0.3033
CBL-1QL6-1 Out
0.7429
MagneticCopper
BUS-XF-1QL8-SEC
BUS-1QL8(1)
2 6 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-1QL8(1) In
1.7592
MagneticCopper
BUS-1QL8(1)
BUS-1QL8(2)
2 6 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-1QL8(2) In
1.7592
MagneticCopper
BUS-1QL8(2)
BUS-1QL9(1)
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-1QL8(2)-1 In
BUS-1QL9(1)
BUS-1QL9(2)
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-1QL9(2) In
8.8286
MagneticCopper
BUS-2CH1 (1)
BUS-2CH1 (2)
1 6 3/0 PVC Pos:
Zero:
0.2096 0.1352
0.3328
CBL-2CH1 (2) In
0.6607
MagneticCopper
BUS-2CH3
BUS-XF-2CL3-PRI
1 4 8 PVC Pos:
Zero:
1.4080 0.1309
0.3222
CBL-2CH3-1 In
4.4373
MagneticCopper
BUS-2CH3
BUS-XF-1CL2-PRI
1 176 1/0 PVC Pos:
Zero:
9.7778 4.1250
10.1521
CBL-2CH3-2 In
30.8153
BUS-2CH4
BUS-XF-2CL4-PRI
1 10 2 PVC Pos:
Zero:
0.8767 0.1944
0.4787
CBL-2CH4-1 In
2.7630
MagneticCopper
BUS-2CH4
BUS-XF-5CL2-PRI
1 304 4 PVC Pos:
Zero:
42.3542 6.3729
15.6882
CBL-2CH4-2 In
133.4750
MagneticCopper
BUS-2CH5
BUS-XF-2CL5-PRI
1 4 6 PVC Pos:
Zero:
0.8854 0.0911
0.2245
CBL-2CH5-1 In
2.7903
MagneticCopper
BUS-XF-2CL1-SEC
BUS-2CL1
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-2CL1 In
8.8286
BUS-XF-2CL2-SEC
BUS-2CL2
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
CBL-2CL2 In
2.7972
MagneticCopper
BUS-XF-2CL3-SEC
BUS-2CL3
1 5 2 PVC Pos:
Zero:
2.3345 0.6761
1.6642
CBL-2CL3 In
7.3572
MagneticCopper
BUS-XF-2CL4-SEC
BUS-2CL4
1 8 300 PVC Pos:
Zero:
0.8580 0.9116
2.2448
CBL-2CL4 In
2.7034
MagneticCopper
BUS-XF-2CL5-SEC
BUS-2CL5
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-2CL5 In
BUS-0066
BUS-2DCH
1 24 500 PVC Pos:
Zero:
0.3063 0.4854
1.1948
CBL-2DCH In
0.9646
MagneticCopper
BUS-2DCH
BUS-XF-2CL1-PRI
1 10 6 PVC Pos:
Zero:
2.2135 0.2279
0.5612
CBL-2DCH-1 In
6.9757
MagneticCopper
BUS-0129
BUS-2DCH2
1 200 500 PVC Pos:
Zero:
2.5521 4.0451
9.9566
CBL-2DCH2 In
8.0382
MagneticCopper
BUS-2DCH
BUS-2CH5
1 123 1 PVC Pos:
Zero:
8.5417 2.3276
5.7283
CBL-2DCH-2 In
26.9169
BUS-2DCH2
BUS-1FCH1
1 1 300 PVC Pos:
Zero:
0.0201 0.0214
0.0527
CBL-2DCH2-7 Out
0.0635
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-2DCH2
BUS-2CH3
1 6 4/0 PVC Pos:
Zero:
0.1667 0.1294
0.3188
CBL-2DCH2-8 In
0.5253
MagneticCopper
BUS-2DCH
BUS-XF-2CL2-PRI
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-2DCH-3 In
2.7630
MagneticCopper
BUS-2DCH
BUS-EH1
1 70 1/0 PVC Pos:
Zero:
3.8889 1.6406
4.0378
CBL-2DCH-4 In
12.2561
BUS-2DCH 1 1 2/0 PVC Pos:
Zero:
0.0443 0.0231
0.0569
CBL-2DCH-6 Out
0.1395
MagneticCopper
BUS-2DCH
BUS-2CH2
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-2DCH-8 In
2.7630
MagneticCopper
BUS-2DCH
BUS-2CH1 (1)
1 4 3/0 PVC Pos:
Zero:
0.1398 0.0901
0.2219
CBL-2DCH-9 In
0.4405
MagneticCopper
BUS-2DH1
BUS-2H4
1 240 4/0 PVC Pos:
Zero:
6.6667 5.1771
12.7500
CBL-2DH1-1 In
21.0104
BUS-2DH1
BUS-XF-2L2-PRI
1 5 6 PVC Pos:
Zero:
1.1068 0.1139
0.2806
CBL-2DH1-2 In
3.4878
MagneticCopper
BUS-2DH1
BUS-2H3
1 214 2 PVC Pos:
Zero:
18.7622 5.4336
13.3750
CBL-2DH1-4 In
59.1287
MagneticCopper
BUS-2DH1
BUS-2H2
1 6 4 PVC Pos:
Zero:
0.8359 0.1646
0.4052
CBL-2DH1-5 In
2.6344
MagneticCopper
BUS-2DH1
BUS-XF-2L1-PRI
1 384 8 PVC Pos:
Zero:
135.1667 9.6167
23.6667
CBL-2DH1-7 In
425.9834
BUS-2DH1
BUS-XF-2L11-PRI
1 20 8 PVC Pos:
Zero:
7.0399 0.6545
1.6111
CBL-2DH1-9 In
22.1866
MagneticCopper
BUS-2DH2
BUS-2H7
1 6 4 PVC Pos:
Zero:
0.8359 0.1646
0.4052
CBL-2DH2-1 In
2.6344
MagneticCopper
BUS-2DH2
BUS-XF-2L7-PRI
1 4 4 PVC Pos:
Zero:
0.5573 0.0839
0.2064
CBL-2DH2-2 In
1.7563
MagneticCopper
BUS-2DH2
BUS-2H6
1 176 4/0 PVC Pos:
Zero:
4.8889 3.7965
9.3500
CBL-2DH2-3 In
15.4076
BUS-2DH2
BUS-2H5
1 178 2/0 PVC Pos:
Zero:
7.8802 4.1178
10.1361
CBL-2DH2-4 In
24.8304
MagneticCopper
BUS-2DH3
BUS-2H8
1 304 1/0 PVC Pos:
Zero:
16.8889 7.1250
17.5354
CBL-2DH3-1 In
53.2264
MagneticCopper
BUS-2DH3
BUS-XF-2L10-PRI
1 10 6 PVC Pos:
Zero:
2.2135 0.2279
0.5612
CBL-2DH3-2 In
6.9757
MagneticCopper
BUS-2DH3
BUS-2H10
1 6 6 PVC Pos:
Zero:
1.3281 0.1784
0.4393
CBL-2DH3-3 In
4.1854
BUS-2DH3
BUS-2H9
1 128 6 PVC Pos:
Zero:
28.3333 3.8056
9.3722
CBL-2DH3-5 In
89.2889
MagneticCopper
BUS-2EH1
BUS-XF-2EL1-PRI
1 6 12 PVC Pos:
Zero:
4.8698 0.2370
0.5836
CBL-2EH1-1 In
15.3474
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-2EH2
BUS-XF-2EL2-PRI
1 5 12 PVC Pos:
Zero:
4.0582 0.1510
0.3720
CBL-2EH2-1 In
12.7895
MagneticCopper
BUS-2EH3
BUS-XF-2EL3-PRI
1 6 12 PVC Pos:
Zero:
4.8698 0.1813
0.4464
CBL-2EH3-1 In
15.3474
BUS-2EH4
BUS-XF-2EL4-PRI
1 4 12 PVC Pos:
Zero:
3.2465 0.1208
0.2976
CBL-2EH4-1 In
10.2316
MagneticCopper
BUS-XF-2EL1-SEC
BUS-2EL1
1 6 8 PVC Pos:
Zero:
11.2472 1.0457
2.5740
CBL-2EL1 In
35.4461
MagneticCopper
BUS-XF-2EL2-SEC
BUS-2EL2
1 10 8 PVC Pos:
Zero:
18.7454 1.7428
4.2899
CBL-2EL2 In
59.0768
MagneticCopper
BUS-XF-2EL3-SEC
BUS-2EL3
1 10 8 PVC Pos:
Zero:
18.7454 1.7428
4.2899
CBL-2EL3 In
59.0768
BUS-XF-2EL4-SEC
BUS-2EL4
1 6 8 PVC Pos:
Zero:
11.2472 1.0457
2.5740
CBL-2EL4 In
35.4461
MagneticCopper
BUS-2H3
BUS-XF-2L3-PRI
1 10 4 PVC Pos:
Zero:
1.3932 0.2743
0.6753
CBL-2H3-1 In
4.3906
MagneticCopper
BUS-2H4
BUS-XF-2L4-PRI
1 6 2/0 PVC Pos:
Zero:
0.2656 0.1388
0.3417
CBL-2H4-1 In
0.8370
MagneticCopper
BUS-2H5
BUS-XF-2L5-PRI
1 8 2 PVC Pos:
Zero:
0.7014 0.2031
0.5000
CBL-2H5-1 In
2.2104
BUS-2H6
BUS-XF-2L6-PRI
1 16 2/0 PVC Pos:
Zero:
0.7083 0.3701
0.9111
CBL-2H6-1 In
2.2319
MagneticCopper
BUS-2H8
BUS-XF-2L8-PRI
1 5 4 PVC Pos:
Zero:
0.6966 0.1372
0.3377
CBL-2H8-1 In
2.1953
MagneticCopper
BUS-2H9
BUS-XF-2L9-PRI
1 10 6 PVC Pos:
Zero:
2.2135 0.2279
0.5612
CBL-2H9-1 In
6.9757
MagneticCopper
BUS-2HX1
BUS-XF-2LX1-PRI
1 48 6 PVC Pos:
Zero:
10.6250 1.4271
3.5146
CBL-2HX1-1 In
33.4833
BUS-XF-2L1-SEC
BUS-2L1
1 10 6 PVC Pos:
Zero:
11.7881 1.5833
3.8993
CBL-2L1 In
37.1487
MagneticCopper
BUS-XF-2L10-SEC
BUS-2L10
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-2L10 In
8.8286
MagneticCopper
BUS-XF-2L11-SEC
BUS-2L11
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-2L11 In
14.7143
MagneticCopper
BUS-XF-2L2-SEC
BUS-2L2
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-2L2 In
4.4573
BUS-XF-2L3-SEC
BUS-2L3(1)
1 15 2/0 PVC Pos:
Zero:
3.5364 1.8480
4.5488
CBL-2L3(1) In
11.1432
MagneticCopper
BUS-2L3(1)
BUS-2PL4
1 100 6 PVC Pos:
Zero:
117.8809 15.8330
38.9932
CBL-2L3(1)-1 In
371.4867
MagneticCopper
BUS-2L3(1)
BUS-2L3(2)
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-2L3(2) In
4.4573
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-XF-2L4-SEC
BUS-2L4-L
2 6 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-2L4-L In
1.7592
BUS-2L4-L
BUS-2PL5
1 105 4 PVC Pos:
Zero:
77.9054 15.3384
37.7635
CBL-2L4-L-1 In
245.5113
MagneticCopper
BUS-2L4-L
BUS-2PL6
1 40 6 PVC Pos:
Zero:
47.1524 6.3332
15.5973
CBL-2L4-L-2 In
148.5947
MagneticCopper
BUS-2L4-L
BUS-2PL7
1 30 8 PVC Pos:
Zero:
56.2361 5.2284
12.8698
CBL-2L4-L-3 In
177.2305
MagneticCopper
BUS-2L4-L
BUS-2PL8
1 55 4 PVC Pos:
Zero:
40.8076 8.0344
19.7809
CBL-2L4-L-4 In
128.6012
BUS-2PL9
1 80 6 PVC Pos:
Zero:
94.3047 12.6664
31.1945
CBL-2L4-L-5 In
297.1894
MagneticCopper
BUS-2L4-L
BUS-2PL10
1 20 8 PVC Pos:
Zero:
37.4908 3.4856
8.5799
CBL-2L4-L-6 In
118.1537
MagneticCopper
BUS-2L4-L
BUS-2PL11
1 55 4 PVC Pos:
Zero:
40.8076 8.0344
19.7809
CBL-2L4-L-7 In
128.6012
MagneticCopper
BUS-2L4-L
BUS-2PL13
1 105 8 PVC Pos:
Zero:
196.8265 18.2993
45.0444
CBL-2L4-L-8 In
620.3068
BUS-2PL12
1 55 2 PVC Pos:
Zero:
25.6796 7.4369
18.3062
CBL-2L4-L-9 In
80.9287
MagneticCopper
BUS-2L4-L
BUS-2L4-R
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
CBL-2L4-R In
3.5184
MagneticCopper
BUS-XF-2L5-SEC
BUS-2L5-L
1 5 300 PVC Pos:
Zero:
0.5362 0.5698
1.4030
CBL-2L5-L In
1.6896
MagneticCopper
BUS-2L5-L
BUS-2L5-R
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-2L5-R In
2.0276
BUS-2L5-R
BUS-2PL14
1 95 1/0 PVC Pos:
Zero:
28.1065 11.8574
29.1825
CBL-2L5-R-1 In
88.5794
MagneticCopper
BUS-XF-2L6-SEC
BUS-2L6
2 6 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-2L6 In
1.7592
MagneticCopper
BUS-2L6
BUS-2PL16
1 115 8 PVC Pos:
Zero:
215.5718 20.0421
49.3343
CBL-2L6-1 In
679.3836
MagneticCopper
BUS-2L6
BUS-2PL15
1 40 2 PVC Pos:
Zero:
18.6760 5.4087
13.3136
CBL-2L6-2 In
58.8573
BUS-2L6
BUS-2PL17
1 60 1/0 PVC Pos:
Zero:
17.7515 7.4889
18.4310
CBL-2L6-3 In
55.9449
MagneticCopper
BUS-2L6
BUS-2PL19
1 70 2 PVC Pos:
Zero:
32.6831 9.4651
23.2988
CBL-2L6-4 In
103.0002
MagneticCopper
BUS-2L6
BUS-2PL18
1 50 4 PVC Pos:
Zero:
37.0978 7.3040
17.9826
CBL-2L6-5 In
116.9101
MagneticCopper
BUS-2L6 1 60 1/0 PVC Pos: 17.7515 7.4889CBL-2L6-6 In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
BUS-2PL20 Zero: 18.4310 55.9449
BUS-XF-2L7-SEC
BUS-2L7
1 10 2/0 PVC Pos:
Zero:
2.3576 1.2320
3.0325
CBL-2L7 In
7.4288
MagneticCopper
BUS-2L7
BUS-2PL21
1 4 4 PVC Pos:
Zero:
2.9678 0.5843
1.4386
CBL-2L7-1 In
9.3528
MagneticCopper
BUS-XF-2L8-SEC
BUS-2L8-L
1 10 2/0 PVC Pos:
Zero:
2.3576 1.2320
3.0325
CBL-2L8-L In
7.4288
MagneticCopper
BUS-2L8-L
BUS-2L8-R
1 8 2/0 PVC Pos:
Zero:
1.8861 0.9856
2.4260
CBL-2L8-R In
5.9430
BUS-XF-2L9-SEC
BUS-2L9
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-2L9 In
22.2892
MagneticCopper
BUS-XF-2LX1-SEC
BUS-2LX1
1 6 1/0 PVC Pos:
Zero:
1.7751 0.7489
1.8431
CBL-2LX1 In
5.5945
MagneticCopper
BUS-2LX1
BUS-2LX2
1 8 6 PVC Pos:
Zero:
9.4305 1.2666
3.1195
CBL-2LX1-1 In
29.7189
MagneticCopper
BUS-XF-2QL2-SEC
BUS-2QL2(A)
1 10 300 PVC Pos:
Zero:
1.0725 1.1395
2.8060
CBL-2QL2(A) In
3.3793
BUS-2QL2(A)
BUS-2QL2(B)
1 6 300 PVC Pos:
Zero:
0.6435 0.6837
1.6836
CBL-2QL2(B) In
2.0276
MagneticCopper
BUS-XF-2QL3-SEC
BUS-2QL3
1 6 4/0 PVC Pos:
Zero:
0.8876 0.6893
1.6975
CBL-2QL3 In
2.7972
MagneticCopper
BUS-2QL3
BUS-2QL3(B)
1 10 2 PVC Pos:
Zero:
4.6690 1.3522
3.3284
CBL-2QL3-1 In
14.7143
MagneticCopper
BUS-2QL3
BUS-2QL3(A)
1 16 2 PVC Pos:
Zero:
7.4704 2.1635
5.3254
CBL-2QL3-2 In
23.5429
BUS-3DH
BUS-3H1
1 25 2 PVC Pos:
Zero:
2.1918 0.6348
1.5625
CBL-3DH-1 In
6.9076
MagneticCopper
BUS-3DH
BUS-XF-7L7-PRI
1 176 4 PVC Pos:
Zero:
24.5208 4.8278
11.8861
CBL-3DH-11 In
77.2750
MagneticCopper
BUS-3DH
BUS-7H2
1 250 2/0 PVC Pos:
Zero:
11.0677 5.7834
14.2361
CBL-3DH-13 In
34.8741
MagneticCopper
BUS-3DH
BUS-6H1
1 40 2/0 PVC Pos:
Zero:
1.7708 0.9253
2.2778
CBL-3DH-2 In
5.5799
BUS-3DH2 1 1 6 PVC Pos:
Zero:
0.2214 0.0297
0.0732
CBL-3DH2-1 Out
0.6976
MagneticCopper
BUS-3DH2
BUS-XF-6L6-PRI
1 260 3/0 PVC Pos:
Zero:
9.0842 4.4800
11.0365
CBL-3DH2-2 In
28.6293
MagneticCopper
BUS-3DH2
BUS-3H2
1 192 2/0 PVC Pos:
Zero:
8.5000 4.4417
10.9333
CBL-3DH2-3 In
26.7833
MagneticCopper
BUS-3DH2
BUS-3DH2A
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-3DH2-4 In
8.7543
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-3DH
BUS-4H1
1 25 2/0 PVC Pos:
Zero:
1.1068 0.5783
1.4236
CBL-3DH-3 In
3.4874
MagneticCopper
BUS-3DH
BUS-XF-4L5-PRI
1 97 4/0 PVC Pos:
Zero:
2.6944 1.6040
3.9490
CBL-3DH-4 In
8.4917
MagneticCopper
BUS-3DH
BUS-XF-4L1-PRI
1 100 2/0 PVC Pos:
Zero:
4.4271 1.7665
4.3490
CBL-3DH-5 In
13.9497
MagneticCopper
BUS-3DH
BUS-XF-4L4-PRI
1 95 4/0 PVC Pos:
Zero:
2.6389 1.5710
3.8676
CBL-3DH-6 In
8.3166
BUS-3DH
BUS-XF-4L2-PRI
1 95 250 PVC Pos:
Zero:
2.2760 1.5627
3.8470
CBL-3DH-7 In
7.1704
MagneticCopper
BUS-3DH
BUS-XF-5L4.1-PRI
1 196 6 PVC Pos:
Zero:
43.3854 5.8273
14.3512
CBL-3DH-8 In
136.7236
MagneticCopper
BUS-3DH
BUS-XF-4L3-PRI
1 45 4/0 PVC Pos:
Zero:
1.2500 0.7441
1.8320
CBL-3DH-9 In
3.9395
MagneticCopper
BUS-0068
BUS-3DQH
1 6 350 PVC Pos:
Zero:
0.0984 0.1279
0.3148
CBL-3DQH In
0.3102
BUS-3DQH
BUS-XF-4QL4-PRI
1 250 2 PVC Pos:
Zero:
21.9184 4.8611
11.9683
CBL-3DQH-1 In
69.0755
MagneticCopper
BUS-3DQH12 2 1 300 PVC Pos:
Zero:
0.0101 0.0107
0.0263
CBL-3DQH12-1 Out
0.0317
MagneticCopper
BUS-3DQH12
BUS-XF-3QL1-PRI
1 30 6 PVC Pos:
Zero:
6.6406 0.6836
1.6836
CBL-3DQH12-3 In
20.9271
MagneticCopper
BUS-0192
BUS-3DQH2
2 6 400 PVC Pos:
Zero:
0.0464 0.0638
0.1570
CBL-3DQH2 In
0.1461
BUS-XF-4QL2-PRI
1 310 2 PVC Pos:
Zero:
27.1788 6.0278
14.8407
CBL-3DQH-2 In
85.6536
MagneticCopper
BUS-0194
BUS-3DQH2-2
2 8 400 PVC Pos:
Zero:
0.0618 0.0851
0.2094
CBL-3DQH2-14 In
0.1948
MagneticCopper
BUS-3DQH
BUS-XF-4QL5-PRI
1 170 2 PVC Pos:
Zero:
14.9045 3.3056
8.1385
CBL-3DQH-3 In
46.9714
MagneticCopper
BUS-3DQH
BUS-XF-4QL1-PRI
1 185 2 PVC Pos:
Zero:
16.2196 3.5972
8.8566
CBL-3DQH-4 In
51.1159
BUS-5DQH
1 86 1 PVC Pos:
Zero:
5.9722 2.1276
5.2369
CBL-3DQH-5 In
18.8200
MagneticCopper
BUS-3DQH
BUS-XF-3QL2-PRI
1 35 2 PVC Pos:
Zero:
3.0686 0.8887
2.1875
CBL-3DQH-6 In
9.6706
MagneticCopper
BUS-3H2
BUS-XF-3L1-PRI
1 8 4 PVC Pos:
Zero:
1.1146 0.2194
0.5403
CBL-3H2-1 In
3.5125
MagneticCopper
BUS-XF-3L1-SEC
BUS-3L1
1 8 1 PVC Pos:
Zero:
2.9586 1.0540
2.5943
CBL-3L1 In
9.3232
BUS-XF-3LNE-SEC
BUS-3LNE
1 20 6 PVC Pos:
Zero:
23.5762 3.1666
7.7986
CBL-3LNE In
74.2973
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-XF-3LSW-SEC
BUS-3LSW
1 20 6 PVC Pos:
Zero:
23.5762 3.1666
7.7986
CBL-3LSW In
74.2973
MagneticCopper
BUS-XF-3QL-SEC
BUS-3QL
1 20 1/0 PVC Pos:
Zero:
5.9172 2.4963
6.1437
CBL-3QL In
18.6483
MagneticCopper
BUS-XF-3QL1-SEC
BUS-3QL1
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-3QL1 In
BUS-3QL
BUS-8QL1
1 140 3/0 PVC Pos:
Zero:
26.0494 16.7946
41.3554
CBL-3QL-1 In
82.0960
MagneticCopper
BUS-XF-3QL2-SEC
BUS-3QL2
1 122 4/0 PVC Pos:
Zero:
18.0473 14.0149
34.5155
CBL-3QL2 In
56.8773
MagneticCopper
BUS-4EH1
BUS-6EH1
1 52 8 PVC Pos:
Zero:
18.3038 1.7017
4.1889
CBL-4EH1-1 In
57.6852
MagneticCopper
BUS-4EH1
BUS-5EH1
1 32 6 PVC Pos:
Zero:
7.0833 0.9514
2.3431
CBL-4EH1-2 In
22.3222
BUS-4EH1
BUS-XF-4EL1-PRI
1 10 10 PVC Pos:
Zero:
5.1215 0.2839
0.6988
CBL-4EH1-3 In
16.1406
MagneticCopper
BUS-4EH1
BUS-7EH1
1 58 6 PVC Pos:
Zero:
12.8385 1.7244
4.2468
CBL-4EH1-4 In
40.4590
MagneticCopper
BUS-4EH1
BUS-7EH2
1 234 6 PVC Pos:
Zero:
51.7969 6.9570
17.1336
CBL-4EH1-5 In
163.2313
MagneticCopper
BUS-XF-4EL1-SEC
BUS-4EL1
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-4EL1 In
22.2892
BUS-4EL1
BUS-5EL1
1 32 8 PVC Pos:
Zero:
59.9852 5.5769
13.7278
CBL-4EL1-1 In
189.0459
MagneticCopper
BUS-4H1
BUS-4H2
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-4H1-1 In
5.5260
MagneticCopper
BUS-4H1
BUS-5H1
1 48 2 PVC Pos:
Zero:
4.2083 1.2188
3.0000
CBL-4H1-2 In
13.2625
MagneticCopper
BUS-4H2
BUS-XF-4L6-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
CBL-4H2-1 In
6.6560
BUS-XF-4L1-SEC
BUS-4L1-L
1 8 3/0 PVC Pos:
Zero:
1.4885 0.9597
2.3632
CBL-4L1-L In
4.6912
MagneticCopper
BUS-4L1-L
BUS-5L1(1)
1 32 2/0 PVC Pos:
Zero:
7.5444 3.9423
9.7041
CBL-4L1-L-1 In
23.7722
MagneticCopper
BUS-4L1-L
BUS-4L1-R
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
CBL-4L1-R In
3.5184
MagneticCopper
BUS-4L1-R
BUS-6L1-R
1 10 1/0 PVC Pos:
Zero:
2.9586 1.2482
3.0718
CBL-4L1-R-1 In
9.3242
BUS-4L2-R
BUS-4L2-L
2 6 300 PVC Pos:
Zero:
0.3217 0.3419
0.8418
CBL-4L2-L In
1.0138
MagneticCopper
BUS-4L2-L
BUS-6L2-L
1 12 4/0 PVC Pos:
Zero:
1.7751 1.3785
3.3950
CBL-4L2-L-1 In
5.5945
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-XF-4L2-SEC
BUS-4L2-R
2 20 300 PVC Pos:
Zero:
1.0725 1.1395
2.8060
CBL-4L2-R In
3.3793
MagneticCopper
BUS-4L2-R
BUS-7L2-L
2 68 1/0 PVC Pos:
Zero:
10.0592 4.2437
10.4442
CBL-4L2-R-1 In
31.7021
BUS-4L3-R
BUS-4L3-L
2 6 3/0 PVC Pos:
Zero:
0.5582 0.3599
0.8862
CBL-4L3-L In
1.7592
MagneticCopper
BUS-XF-4L3-SEC
BUS-4L3-R
2 17 3/0 PVC Pos:
Zero:
1.5816 1.0197
2.5109
CBL-4L3-R In
4.9844
MagneticCopper
BUS-4L3-R
BUS-5L3(1)
1 32 4 PVC Pos:
Zero:
23.7426 4.6746
11.5089
CBL-4L3-R-1 In
74.8225
MagneticCopper
BUS-4L3-R
BUS-6L3-L
1 84 2 PVC Pos:
Zero:
39.2197 11.3582
27.9586
CBL-4L3-R-2 In
123.6002
BUS-4L3-R
BUS-7L3-L
1 68 3/0 PVC Pos:
Zero:
12.6526 8.1574
20.0869
CBL-4L3-R-3 In
39.8752
MagneticCopper
BUS-4L3-R
BUS-8L1
1 86 4 PVC Pos:
Zero:
63.8083 12.5629
30.9301
CBL-4L3-R-4 In
201.0854
MagneticCopper
BUS-4L4-R
BUS-4L4-L
2 6 300 PVC Pos:
Zero:
0.3217 0.3419
0.8418
CBL-4L4-L In
1.0138
MagneticCopper
BUS-4L4-L
BUS-5L7
1 10 2/0 PVC Pos:
Zero:
2.3576 1.2320
3.0325
CBL-4L4-L-1 In
7.4288
BUS-XF-4L4-SEC
BUS-4L4-R
2 15 300 PVC Pos:
Zero:
0.8044 0.8546
2.1045
CBL-4L4-R In
2.5344
MagneticCopper
BUS-4L4-R
BUS-5L4(1)
1 52 4 PVC Pos:
Zero:
38.5817 7.5962
18.7019
CBL-4L4-R-1 In
121.5865
MagneticCopper
BUS-4L4-R
BUS-6L4-R
1 32 2/0 PVC Pos:
Zero:
7.5444 3.9423
9.7041
CBL-4L4-R-2 In
23.7722
MagneticCopper
BUS-4L5-R
BUS-4L5-L
2 6 300 PVC Pos:
Zero:
0.3217 0.3419
0.8418
CBL-4L5-L In
1.0138
BUS-4L5-L
BUS-7L5-L
1 74 2/0 PVC Pos:
Zero:
17.4464 9.1166
22.4408
CBL-4L5-L-1 In
54.9732
MagneticCopper
BUS-4L5-L
BUS-5L8
1 32 4/0 PVC Pos:
Zero:
4.7337 3.6760
9.0533
CBL-4L5-L-2 In
14.9186
MagneticCopper
BUS-XF-4L5-SEC
BUS-4L5-R
2 10 300 PVC Pos:
Zero:
0.5362 0.5698
1.4030
CBL-4L5-R In
1.6896
MagneticCopper
BUS-4L5-R
BUS-5L5(1)
1 32 2/0 PVC Pos:
Zero:
7.5444 3.9423
9.7041
CBL-4L5-R-1 In
23.7722
BUS-4L5-R
BUS-6L5-L
1 84 2/0 PVC Pos:
Zero:
19.8040 10.3486
25.4734
CBL-4L5-R-2 In
62.4020
MagneticCopper
BUS-XF-4L6-SEC
BUS-4L6
1 20 4 PVC Pos:
Zero:
14.8391 2.9216
7.1930
CBL-4L6 In
46.7641
MagneticCopper
BUS-XF-4QL1-SEC
BUS-4QL1
1 20 2 PVC Pos:
Zero:
9.3380 2.7043
6.6568
CBL-4QL1 In
29.4286
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-4QL1
BUS-5QL1
1 30 8 PVC Pos:
Zero:
56.2361 5.2284
12.8698
CBL-4QL1-1 In
177.2305
BUS-4QL1
BUS-6QL1
1 50 8 PVC Pos:
Zero:
93.7269 8.7139
21.4497
CBL-4QL1-2 In
295.3842
MagneticCopper
BUS-XF-4QL2-SEC
BUS-4QL2
1 20 2/0 PVC Pos:
Zero:
4.7152 2.4639
6.0651
CBL-4QL2 In
14.8576
MagneticCopper
BUS-4QL2
BUS-5QL2
1 60 2 PVC Pos:
Zero:
28.0141 8.1130
19.9704
CBL-4QL2-1 In
88.2859
MagneticCopper
BUS-4QL2
BUS-6QL2
1 70 6 PVC Pos:
Zero:
82.5166 11.0831
27.2952
CBL-4QL2-2 In
260.0407
BUS-4QL2
BUS-7QL2
1 90 6 PVC Pos:
Zero:
106.0928 14.2497
35.0938
CBL-4QL2-3 In
334.3380
MagneticCopper
BUS-4QL2
BUS-4QL2-B
1 10 6 PVC Pos:
Zero:
11.7881 1.5833
3.8993
CBL-4QL2-4 In
37.1487
MagneticCopper
BUS-XF-4QL4-SEC
BUS-4QL4
1 20 2/0 PVC Pos:
Zero:
4.7152 2.4639
6.0651
CBL-4QL4 In
14.8576
MagneticCopper
BUS-4QL4
BUS-5QL4
1 70 8 PVC Pos:
Zero:
131.2176 12.1995
30.0296
CBL-4QL4-1 In
413.5378
BUS-4QL4
BUS-6QL4
1 90 8 PVC Pos:
Zero:
168.7084 15.6851
38.6095
CBL-4QL4-2 In
531.6915
MagneticCopper
BUS-4QL4
BUS-7QL4
1 110 6 PVC Pos:
Zero:
129.6690 17.4163
42.8925
CBL-4QL4-3 In
408.6354
MagneticCopper
BUS-XF-4QL5-SEC
BUS-4QL5
1 20 2/0 PVC Pos:
Zero:
4.7152 2.4639
6.0651
CBL-4QL5 In
14.8576
MagneticCopper
BUS-4QL5
BUS-5QL5
1 40 6 PVC Pos:
Zero:
47.1524 6.3332
15.5973
CBL-4QL5-1 In
148.5947
BUS-4QL5
BUS-6QL5
1 60 8 PVC Pos:
Zero:
112.4723 10.4567
25.7396
CBL-4QL5-2 In
354.4610
MagneticCopper
BUS-4QL5
BUS-7QL5
1 70 8 PVC Pos:
Zero:
131.2176 12.1995
30.0296
CBL-4QL5-3 In
413.5378
MagneticCopper
BUS-XF-5CL1-SEC
BUS-5CL1
1 15 300 PVC Pos:
Zero:
1.6087 1.7093
4.2090
CBL-5CL1 Out
5.0689
MagneticCopper
BUS-XF-5CL2-SEC
BUS-5CL2
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-5CL2 In
BUS-5DQH
BUS-XF-5QL6-PRI
1 256 6 PVC Pos:
Zero:
56.6667 7.6111
18.7444
CBL-5DQH-1 In
178.5778
MagneticCopper
BUS-5L1(1)
BUS-5L1(2)
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-5L1-2 In
4.4573
MagneticCopper
BUS-5L3(1)
BUS-5L3(2)
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-5L3(2) In
14.0292
MagneticCopper
BUS-5L4(1) 1 6 4 PVC Pos: 4.4517 0.8765CBL-5L4(2) In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
BUS-5L4(2) Zero: 2.1579 14.0292
BUS-XF-5L4.1-SEC
BUS-5L4.1
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-5L4.1 In
14.0292
MagneticCopper
BUS-5L5(1)
BUS-5L5(2)
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-5L5(2) In
4.4573
MagneticCopper
BUS-5QH1 1 1 1/0 PVC Pos:
Zero:
0.0556 0.0234
0.0577
CBL-5QH1-1 Out
0.1751
MagneticCopper
BUS-5QH1
BUS-5QH2
1 10 1/0 PVC Pos:
Zero:
0.5556 0.2344
0.5768
CBL-5QH1-2 In
1.7509
BUS-5QH1
BUS-XF-7L4-PRI
1 48 2 PVC Pos:
Zero:
4.2083 1.2188
3.0000
CBL-5QH1-3 In
13.2625
MagneticCopper
BUS-5QH1
BUS-XF-5QL3-PRI
1 10 4 PVC Pos:
Zero:
1.3932 0.2743
0.6753
CBL-5QH1-4 In
4.3906
MagneticCopper
BUS-XF-5QL3-SEC
BUS-5QL3
1 12 1/0 PVC Pos:
Zero:
3.5503 1.4978
3.6862
CBL-5QL3 In
11.1890
MagneticCopper
BUS-XF-5QL6-SEC
BUS-5QL6
1 12 1 PVC Pos:
Zero:
4.4379 1.5810
3.8915
CBL-5QL6 In
13.9848
BUS-6CL1-R
BUS-6CL1-L
1 5 2/0 PVC Pos:
Zero:
1.1788 0.6160
1.5163
CBL-6CL1-L In
3.7144
MagneticCopper
BUS-XF-6CL1-SEC
BUS-6CL1-R
1 20 2/0 PVC Pos:
Zero:
4.7152 2.4639
6.0651
CBL-6CL1-R In
14.8576
MagneticCopper
BUS-6EH1
BUS-XF-6EL1-PRI
1 5 10 PVC Pos:
Zero:
2.5608 0.1419
0.3494
CBL-6EH1-1 In
8.0703
MagneticCopper
BUS-XF-6EL1-SEC
BUS-6EL1
1 5 6 PVC Pos:
Zero:
5.8940 0.7917
1.9497
CBL-6EL1 In
18.5743
BUS-6EL1
BUS-7EL1
1 35 8 PVC Pos:
Zero:
65.6088 6.0998
15.0148
CBL-6EL1-1 In
206.7689
MagneticCopper
BUS-6H1
BUS-7H1
1 35 4…