This solicitation requests quotes for electrical system preventive maintenance and testing services at two VA medical facilities in Little Rock and North Little Rock, Arkansas. Interested vendors must be veteran-owned small businesses and registered in the System for Award Management (SAM) database. Quotes are due by August 22nd and must include pricing, certifications, and representations. A site visit will be held on August 18th for vendors to view the facilities. The solicitation sets aside this opportunity for veteran-owned small businesses under NAICS code 238210 for electrical contractors. Exhibits provided do not constitute part of the solicitation and will not be incorporated into any resultant contract.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JOHN L. MCCLELLAN

VA HOSPITAL

LITTLE ROCK,

ARKANSAS

August, 2021

Infrared Inspection Report©

2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: Logistics@usscanman.com

John L. McClellan VA Hospital 4300 West 7th Street Little Rock, Arkansas, 72114 Company Contact:

David Barnes Project: 02250821

36C25622Q1188 0001 Exhibit P

DISCLAIMER

This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not in-tended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility’s condition, maintenance practices or correction of conditions indicated herein.

By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, con-cerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

ORDER OF REPORT CONTENTS

1: Data To Facilitate Understanding & Utilizing Scan Report

2: Scan Results Overview & Action Taken Form

3: Identified Faulting Conditions, Information & Photographs

4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found

Utilizing Report Contents

Included in this report are Photographs and Thermographs of problem areas found during our recent

Infrared Inspection of your facility.

Each problem area picture is accompanied by:

Date

Location Information

Temperature Calculations

Color-coded Temperature Intensity and/or Condition Significance Data

A Brief Comment Relating The Item In The Photograph To Its Corresponding

Thermograph

Suggested Corrective Recommendations.

In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity.

Thermal intensity is indicated by use of a color-coded data inserts that locate a fault‘s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows:

INSERT Temperature Range

Red 70ºC/126ºF and higher above Ambient Operating Temp.

Orange 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp.

Yellow 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp.

Green *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp.

( * See page 4)

FAULTY EQUIP MONTHS MONTHS TO WEEKS WEEKS TO NOW

Determining Cost Effective Responses

Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate.

Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports.

Built In Trend Monitoring

When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings.

If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

YEARS

10ºC * 18ºF

25ºC 45ºF

40°C 72ºF

70°C 126ºF

AMBIENT TEMP

STANDARD ELECTRICAL FAULT FAILURE CURVE

(Does Not Include Area In Blue)

DEVICE

TEMP

IS

AMBIENT,

BUT

DEVICE

IS

EITHER

FAULTY

OR

UNSAFE. INTERMEDIATE MINOR SERIOUS CRITICAL

Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use

Total Temperature:

Total Temperature = Ambient Operating Temperature + Fault temperature

Allows you, the customer, to evaluate possible damage to equipment.

Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating.

Contacts start to fail around 130ºC/266ºF

Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes:

Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet.

If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault.

Allows you, the customer, to determine if device will operate at intended amperage.

Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine)

If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip.

1. An intermittent high load.

2. A minor (Green) or intermediate (Yellow) fault.

Report pages with photographs:

PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature

Both black & white and color infrared thermographs are presented to better depict the fault condition.

In addition to the corrective response time frame suggested below and the failure curve lo-cated on the previous page, you may want to consider using the military standard responses presented below.

Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment:

Temperatures rise above Ambient Operating Temperature:

*10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label)

25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label)

40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected.

(Orange Label)

70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label)

Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions.

* Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind.

Fault Correction Recommendation When Our Source Assessment Is Inaccurate:

When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist.

The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located.

Example:

If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp.

in the lead holder lug.

SCAN RESULTS OVERVIEW

PROMPT ATTENTION ITEMS:

Because of:

1. The intensity or heat level indicated at the time of the scan.

2. Deterioration caused by excessive temperature not present at the time of the scan.

3. Physical condition irregularities observed at the time of the scan.

We recommend that the following faults be given prompt attention:

Faults: #2, #5, #6

Items With Asterisks Have High Total or Ambient Operating Temperatures.

United Spectrographics August, 2021

SUMMARY OF FINDINGS

FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO.

MINOR 2 1/76 4/889

INTERMEDIATE 1 3/349

SERIOUS 0 0

CRITICAL 0 0

SERIOUS 3 2/226 5/836 6/836

Number of items located at facility: 892

Number of faults: 6

ACTION TAKEN

VA Medical Center CAVHS JLM

Little Rock, Arkansas August, 2021

Fault # Item # Category Repaired Monitor Date Name

1 76 Minor

2 226 Serious

3 349 Intermediate

4 889 Minor

5 836 Serious

6 836 Serious

PROJECT: 02250821

CUST REP: Terry Robert

SCAN REP: Tim Charleston

DATE: August 25, 2021

LOCATION: Roof Top Box Labeled:

A/C #3 Fuse Disconnect

PH # 1 >

ITEM: Cø Disconnect & Fuse Block

SOURCE: Disconnect: Line and load side dis-connect blade contact area.

Fuse Block: Line side fuse clip.

TEMP: Temp. of areas indicating a faulting condition range to:

54ºC / 129ºF Total Temp

- 31ºC / 88ºF AOT

= 23ºC / 41ºF above AOT.

TH # 1 >

COMMENTS

Abnormal heat is being generated in fuse discon-nect components. See green arrows in PH#1 and TH#1.

Loose and/or corroded contact areas. Clean, in-spect and re-secure.

TEMPERATURE ABOVE

AOT

23°C / 41°F

TH # 1 >

Robert

SCAN REP: Tim Charleston

DATE: August 25, 2021

LOCATION: Floor Level #3 Sub Station Room 3A-102 Sub Station G Switchgear Pad Mounted Transformer Cooling Fins

< PH # 2

ITEM: Rear Cooling Fins

SOURCE: Oil not circulating.

TEMP: Cooling Fins are ambient tempera-ture.

< TH # 2

COMMENTS

Abnormal condition exists in transformer compo-nents. See blue arrows in PH#2 and TH#2.

Determine cause of abnormal condition.

TEMPERATURE NOT A FACTOR

< TH # 2

Robert

SCAN REP: Tim Charleston

DATE: August 26, 2021

LOCATION: Room 2D-168 Box Labeled:

2QL3

Fuse Disconnect

PH # 3 >

ITEM: Bø Disconnect & Fuse Block

SOURCE: Disconnect: Load side disconnect blade contact area.

Fuse Block: Line side fuse blade holder.

TEMP: Temp. of areas indicating a faulting condition range to:

66ºC / 151ºF Total Temp.

- 36ºC / 97ºF AOT

= 30ºC / 54ºF above AOT.

TH # 3 >

COMMENTS

Abnormal heat is being generated in fuse discon-nect components. See yellow arrows in PH#3 and TH#3.

Loose and/or corroded contact areas. Clean, in-spect and re-secure.

30°C / 54°F

TH # 3 >

Robert

SCAN REP: Tim Charleston

DATE: August 26, 2021

LOCATION: Parking Deck (Room 118) Distribution Panel Labeled:

LP

Left Side Breakers

< PH # 4

ITEM: Breaker #8 “Comm Room Recept”

SOURCE: Possible overload condition or inter-nal contact area.

TEMP: Temp. of area indicating a faulting condition is:

55ºC / 131ºF Total Temp.

- 37ºC / 99ºF AOT

= 18ºC / 32ºF above AOT.

< TH # 4

COMMENTS

Abnormal heat is being generated in breaker component. See green arrows in PH#4 and

TH#4.

18°C / 32°F

< TH # 4

Check amperage to ensure it doesn’t exceed 80% of manufacturer rating. If no overload is pre-sent and breaker begins tripping, replace break-er.

Robert

SCAN REP: Tim Charleston

DATE: August 26, 2021

LOCATION: Room GE-117 Unit Sub Station A Switchgear Pad Mounted Transformer Cooling Fins

PH # 5 >

ITEM: Rear Cooling Fins

SOURCE: Oil not circulating.

TEMP: Cooling Fins are ambient tempera-ture.

TH # 5 >

COMMENTS

Abnormal condition exists in transformer compo-nents. See blue arrows in PH#5 and TH#5.

Determine cause of abnormal cooling condition.

Check oil levels in transformers.

TH # 5 >

Robert

SCAN REP: Tim Charleston

DATE: August 26, 2021

LOCATION: Room GE-117 Unit Sub Station A Switchgear Pad Mounted Transformer Cooling Fins

< PH # 6

ITEM: Front Cooling Fins

SOURCE: Oil not circulating.

TEMP: Cooling Fins are ambient tempera-ture.

< TH # 6

COMMENTS

Abnormal condition exists in transformer compo-nents. See blue arrows in PH#6 and TH#6.

Determine cause of abnormal cooling condition.

Check oil levels in transformers.

< TH # 6

No. Equipment Operating Visually Inspected

Fault #

EQUIPMENT LIST

FLOOR LEVEL #9

PENTHOUSE ELEVATOR ROOM

1 QH-ELEV2-PH—480 Volt Distribution Panel X

2 QH-ELEV1-PH—480 Volt Distribution Panel X

3 AC-34—Disconnect X

4 SF-34—Fuse Disconnect X

5 P-Common—Disconnect X

6 S-Common—Disconnect X

7 S-1 Service Elevator—Control Cabinet X

8 S-1 Service Elevator—150 Amp Molded Case Breaker X

9 S-1 Service Elevator—68 KVA 3ø Jefferson Transformer X

10 S-1 Service Elevator—D.C. Output Filter X

11 Cab Lights S-1—Disconnect X

12 S-2 Service Elevator—Control Cabinet X

13 S-2 Service Elevator—150 Amp Molded Case Breaker X

14 S-2 Service Elevator—68 KVA 3ø Jefferson Transformer X

15 S-2 Service Elevator—D.C. Output Filter X

16 Cab Lights S-2—Disconnect X

17 S-3 Service Elevator—Control Cabinet X

18 S-3 Service Elevator—150 Amp Molded Case Breaker X

19 S-3 Service Elevator—68 KVA 3ø Jefferson Transformer X

20 S-3 Service Elevator—D.C. Output Filter X

21 Cab Lights S-3—Disconnect X

AREA/EQUIPMENT LIST

Following is a list of the electrical equipment located at the John L. McClellan VA Hospital, Little Rock, Arkansas, facility and data relating to its operating condition at the time the scan was performed.

NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection.

Fault #

22 S-4 Service Elevator—Control Cabinet X

23 S-4 Service Elevator—150 Amp Molded Case Breaker X

24 S-4 Service Elevator—68 KVA 3ø Jefferson Transformer X

25 S-4 Service Elevator—D.C. Output Filter X

26 Cab Lights S-4—Disconnect X

27 S-5 Service Elevator—Control Cabinet X

28 S-5 Service Elevator—150 Amp Molded Case Breaker X

29 S-5 Service Elevator—68 KVA 3ø Jefferson Transformer X

30 S-5 Service Elevator—D.C. Output Filter X

31 Cab Lights S-5—Disconnect X

32 P-1 Passenger Elevator—Control Cabinet X

33 P-1 Passenger Elevator—125 Amp Molded Case Breaker X

34 P-1 Passenger Elevator—68 KVA 3ø Jefferson Transformer X

35 P-1 Passenger Elevator—D.C. Output Filter X

36 Cab Lights P-1—Disconnect X

37 P-2 Passenger Elevator—Control Cabinet X

38 P-2 Passenger Elevator—125 Amp Molded Case Breaker X

39 P-2 Passenger Elevator—68 KVA 3ø Jefferson Transformer X

40 P-2 Passenger Elevator—D.C. Output Filter X

41 Cab Lights P-2—Disconnect X

42 P-3 Passenger Elevator—Control Cabinet X

43 P-3 Passenger Elevator—125 Amp Molded Case Breaker X

44 P-3 Passenger Elevator—68 KVA 3ø Jefferson Transformer X

45 P-3 Passenger Elevator—D.C. Output Filter X

46 Cab Lights P-3—Disconnect X

47 P-4 Passenger Elevator—Control Cabinet X

48 P-4 Passenger Elevator—125 Amp Molded Case Breaker X

49 P-4 Passenger Elevator—68 KVA 3ø Jefferson Transformer X

Fault #

50 P-4 Passenger Elevator—D.C. Output Filter X

51 Cab Lights P-4—Disconnect X

52 P-5 Passenger Elevator—Control Cabinet X

53 P-5 Passenger Elevator—125 Amp Molded Case Breaker X

54 P-5 Passenger Elevator—68 KVA 3ø Jefferson Transformer

X

55 P-5 Passenger Elevator—D.C. Output Filter X

56 Cab Lights P-5—Disconnect X

PENTHOUSE #1 (DUMBWAITER)

57 AT2—Control Cabinet X

58 AT2—Disconnect X

59 AT2—VFD X

60 AT3—Disconnect X

61 AT3—Control Cabinet X

62 AT3—VFD X

63 DW1—Control Cabinet X

64 DW1—Disconnect X

65 DW1—VFD X

66 VFD (ABB) “Graham” X

67 SF-36—Disconnect X

PENTHOUSE #2 (DUMBWAITER)

68 AT1—Control Cabinet X

69 VFD AT1—Disconnect X

70 AT1—Breaker X

71 DW2—Control Cabinet X

72 SF-35—Disconnect X

73 DW-2—Disconnect X

74 AT1 Car Lights—Disconnect X

ROOTOP

75 A/C 3—Control Cabinet X

Fault #

76 A/C 3—Disconnect X 1

77 MEB7 “AC33”—Disconnect X

FLOOR LEVEL #8

MECHANICAL ROOM

78 SF-33 Combination Starter X

COMMUNICATION EQUIPMENT ROOM

79 8L1-PH—208/120 Volt Distribution Panel X

80 8QL1-PH—208/120 Volt Distribution Panel X

81 8QL1-PH—Fuse Disconnect X

82 Pware Fuse Disconnect X

83 8HP-PH—480 Volt Distribution Panel X

84 ATS-Q6 Penthouse Passenger Elevator Switch X

85 ATS-Q5 Penthouse Service Elevator Switch X

86 Nextel D.P.—240/120 Volt Distribution Panel Not In Use

87 Nextel—50 KVA 3ø Cutler-Hammer Transformer Not In Use

88 Nextel—Disconnect Not In Use

89 8QL2 Communication Equipment 208/120 Volt Distribution Panel

X

FLOOR LEVEL #7

ROOM 7A-113

90 7L3 Section 1—208/120 Volt Distribution Panel X

91 7L3 Section 2—208/120 Volt Distribution Panel X

92 7EL1—208/120 Volt Distribution Panel X

93 7EH1—480/277 Volt Distribution Panel X

94 7H1—480/277 Volt Distribution Panel X

ROOM 7B-123

95 7L5 Section 1—208/120 Volt Distribution Panel X

96 7L5 Section 2—208/120 Volt Distribution Panel X

97 7QL5 Section 2—208/120 Volt Distribution Panel X

Fault #

ROOM 7C-145

98 7L4 Section 1—208/120 Volt Distribution Panel X

99 7L4 Section 2—208/120 Volt Distribution Panel X

100 7QL4 Section 2—208/120 Volt Distribution Panel X

101 75 KVA 3ø GE Transformer X

102 75 KVA 3ø GE Transformer Fuse Disconnect X

103 Panel 7L4—208/120 Volt Distribution Panel X

ROOM 7D-116

104 7L2 Section 1—208/120 Volt Distribution Panel X

105 7L2 Section 2—208/120 Volt Distribution Panel X

106 7QL2—208/120 Volt Distribution Panel X

107 7QL3A Section 1—208/120 Volt Distribution Panel X

108 7QL3A Section 2—208/120 Volt Distribution Panel X

ROOM 7E-108

109 7L6 Section 1—208/120 Volt Distribution Panel X

110 7L6 Section 2—208/120 Volt Distribution Panel X

111 7H2—480/277 Volt Distribution Panel X

112 7EH2 Section 1—480/277 Volt Distribution Panel X

113 7EL2 Section 2—208/120 Volt Distribution Panel X

114 15 KVA 3ø Square D Transformer X

115 75 KVA 3ø Square D Transformer X

FLOOR LEVEL #6

ROOM 6A-109

116 6L3 Section 1—208/120 Volt Distribution Panel X

117 6L3 Section 2—208/120 Volt Distribution Panel X

118 6H1—480/277 Volt Distribution Panel X

119 6EL1—208/120 Volt Distribution Panel X

120 6EH1—480/277 Volt Distribution Panel X

121 15 KVA 3ø GE Transformer X

ROOM 6B-121

Fault #

122 6L5 Section 1—208/120 Volt Distribution Panel X

123 6L5 Section 2—208/120 Volt Distribution Panel X

124 6CL1 Section 1—208/120 Volt Distribution Panel X

125 6CL1 Section 2—208/120 Volt Distribution Panel X

126 6CL1 XFMR Disconnect X

127 45 KVA 3ø GE Transformer X

128 6QL5—208/120 Volt Distribution Panel X

ROOM 6C-145

129 NP2—208/120 Volt Distribution Panel X

130 45 KVA Square D 3ø Transformer X

131 Unlabeled 70 Amp Molded Case Breaker X

132 6L4 Section 1—208/120 Volt Distribution Panel X

133 6L4 Section 2—208/120 Volt Distribution Panel X

134 6QL4 Section 2—208/120 Volt Distribution Panel X

ROOM 6D-122

135 6L2 Section 1—208/120 Volt Distribution Panel X

136 6L2 Section 2—208/120 Volt Distribution Panel X

137 6QL2 Section 2—208/120 Volt Distribution Panel X

ROOM 6E-145

138 6L1 Section 1—208/120 Volt Distribution Panel X

139 6L1 Section 2—208/120 Volt Distribution Panel X

140 6QL1—208/120 Volt Distribution Panel X

141 6L6—208/120 Volt Distribution Panel X

142 6L6—112.5 KVA 3ø Square D Transformer X

143 6L6 XFMR Disconnect X

FLOOR LEVEL #5

ROOM 5A-110

144 5H1—480/277 Volt Distribution Panel X

Fault #

145 5EH1—480/277 Volt Distribution Panel X

146 5EL1—208/120 Volt Distribution Panel X

147 5DQH—480/277 Volt Distribution Panel X

148 5L3 Section 1—208/120 Volt Distribution Panel X

149 5L3 Section 2—208/120 Volt Distribution Panel X

150 45 KVA 3ø Square D Transformer X

ROOM 5B-122

151 5L5 Section 1—208/120 Volt Distribution Panel X

152 5L5 Section 2—208/120 Volt Distribution Panel X

153 5QL5—208/120 Volt Distribution Panel X

154 5QL6—208/120 Volt Distribution Panel X

155 5L8—208/120 Volt Distribution Panel X

ROOM 5C-122

156 5QH2—480/277 Volt Distribution Panel X

157 5QH1—480/277 Volt Distribution Panel X

158 5QL3—208/120 Volt Distribution Panel X

159 T5QL3—45 KVA 3ø GE Transformer X

ROOM 5C-129

160 5L7—208/120 Volt Distribution Panel X

161 5L4 Section 1—208/120 Volt Distribution Panel X

162 5L4 Section 2—208/120 Volt Distribution Panel X

163 5L6—208/120 Volt Distribution Panel X

164 5QL4—208/120 Volt Distribution Panel X

165 5CL2—208/120 Volt Distribution Panel X

166 45 KVA 3ø Square D Transformer X

167 45 KVA 3ø Square D Transformer Fuse Disconnect X

168 45 KVA 3ø GE Transformer X

169 45 KVA 3ø GE Transformer Disconnect X

ROOM 5D-137

170 (2) 5CL1 XFMR Disconnects X

Fault #

171 5L2—208/120 Volt Distribution Panel X

172 5QL2—208/120 Volt Distribution Panel X

173 5CL1—208/120 Volt Distribution Panel X

174 (2) 112.5 KVA 3ø GE Transformers X

ROOM 5E-145

175 5QL7—208/120 Volt Distribution Panel X

176 40 KVA Transformer X

177 Transformer Fuse Disconnect X

178 5L1 Section 1—208/120 Volt Distribution Panel X

179 5L1 Section 2—208/120 Volt Distribution Panel X

180 5QL1—208/120 Volt Distribution Panel X

ROOM 5D-111

181 5L9—208/120 Volt Distribution Panel X

182 30kVA Transformer X

183 30kVA Transformer Disconnect X

FLOOR LEVEL #4

ROOM 4A-109

184 4L3 Section 1—208/120 Volt Distribution Panel X

185 4L3 Section 2—208/120 Volt Distribution Panel X

186 4H2—480/277 Volt Distribution Panel X

187 4L6—208/120 Volt Distribution Panel X

188 4EL1—208/120 Volt Distribution Panel X

189 4EHI—480/277 Volt Distribution Panel X

190 4H1—480 Volt Distribution Panel X

191 4L3 XFMR—Disconnect X

192 112.5 KVA 3ø GE Transformer X

193 30 KVA 3ø GE Transformer X

194 15 KVA 3ø Overhead GE Transformer X

Fault #

ROOM 4B-122

195 4QL5 XFMR Disconnect X

196 45 KVA 3ø GE Transformer X

197 4L5 XFMR Disconnect X

198 150 KVA 3ø GE Transformer X

199 4QL5—208/120 Volt Distribution Panel X

200 4L5 Section 1—208/120 Volt Distribution Panel X

201 4L5 Section 2—208/120 Volt Distribution Panel X

ROOM 4C-145

202 4L4 XFMR Disconnect X

203 150 KVA 3ø GE Transformer X

204 4L4 Section 1—208/120 Volt Distribution Panel X

205 4L4 Section 2—208/120 Volt Distribution Panel X

206 4QL4—208/120 Volt Distribution Panel X

207 4QL4 XFMR Disconnect X

208 45 KVA 3ø GE Transformer X

209 Unlabeled Fuse Disconnect X

ROOM 4D-122

210 4QL2B 208/120 Volt Distribution Panel X

211 4QL2 XFMR Disconnect X

212 45 KVA 3ø GE Transformer X

213 4QL2—208/120 Volt Distribution Panel X

214 4L2 Section 1—208/120 Volt Distribution Panel X

215 4L2 Section 2—208/120 Volt Distribution Panel X

216 4L2 XFMR Disconnect X

217 150 KVA 3ø GE Transformer X

ROOM 4E-145

218 4L1 XFMR Disconnect X

219 112.5 KVA 3ø GE Transformer X

220 4E1—208/120 Volt Distribution Panel X

Fault #

221 4L1—208/120 Volt Distribution Panel X

222 4QL1—208/120 Volt Distribution Panel X

223 4QL1 XFMR Disconnect X

224 30 KVA 3ø GE Transformer X

FLOOR LEVEL #3

SUB STATION ROOM “3A-102”

225 Sub Station F Switchgear (Cooling Fins Only)

226 Sub Station G Switchgear (Cooling Fins Only) 2

227 Capacitor Bank Sub F Not In Use

228 Capacitor Bank Sub G Not In Use

229 ATS-Q17 X

230 ATS-Q18 X

231 3DQH1—480/277 Volt Distribution Panel X

232 3DQH1—Transformer X

233 Main “7QL3”—Breaker X

234 3DQH2 Section 1—480/277 Volt Distribution Panel X

235 3DQH2 Section 2—480/277 Volt Distribution Panel X

236 3DH—480/277 Volt Distribution Panel X

237 3DH2—480/277 Volt Distribution Panel X

238 3DQH—480/277 Volt Distribution Panel X

239 ATS-Q7 X

240 LP1—208/120 Volt Distribution Panel X

241 45kVA Transformer X

242 QN Disconnect X

243 3H1—480/277 Volt Distribution Panel X

244 EX-45 Disconnect X

245 EX-46 Disconnect Locked Out

POD D NORTHWEST AIR HANDLING AREA

Fault #

246 MCC-NW X

POD E NORTHEAST AIR HANDLING AREA

247 MCC-NE X

248 ATS-Q12 X

POD A QUAD NORTH AIR HANDLING AREA

249 Work Bench Panel—208/120 Volt Distribution Panel X

250 MCC-QN X

251 ATS-Q4 X

252 3LNE—208/120 Volt Distribution Panel X

253 3QL-2—208/120 Volt Distribution Panel X

254 15 KVA 3ø GE Transformer X

255 3LNE XFMR Disconnect X

256 3QL-2—75 KVA 3ø GE Transformer X

257 3QL—208/120 Volt Distribution Panel X

258 30 KVA 3ø GE Transformer X

259 3QL XFMR Disconnect X

POD A QUAD SOUTH AIR HANDLING AREA

260 MCC-QS X

261 3DH2A 480/277 Volt Distribution Panel X

262 ATS-Q-11 X

263 3LSW—208/120 Volt Distribution Panel X

POD B SOUTHEAST AIR HANDLING AREA

264 MCC-SE X

265 GE Transformer Disconnect Not In Use

266 GE Transformer Not In Use

NEW SUB ROOM #3A-102

267 3QL—208/120 Volt Distribution Panel X

268 45kVA Transformer X

269 3DQH2—480/277 Volt Distribution Panel X

270 15 H.P. Circ. Pump—Combination Starter X

Fault #

271 15 H.P. Circ. Pump—Combination Starter X

272 3 H.P. Circ. Pump—Combination Starter X

POD C SOUTHWEST AIR HANDLING AREA

273 MCC-SW X

274 3H2—480/277 Volt Distribution Panel X

275 3L1—208/120 Volt Distribution Panel X

276 TL31—30 KVA GE 3ø Transformer X

POD A NORTH AIR HANDLING AREA

277 NP1—480/277 Volt Distribution Panel X

278 MCC (Chiller No. 1) X

FLOOR LEVEL #2

ROOM 2A-113

279 (Left) 20A Square D Breaker “Red Atrium” X

280 (Center) 20A Square D Breaker X

281 (Right) 20A Square D Breaker “Green Atrium” X

282 Unlabeled Square D Lighting Contactor X

283 Unlabeled GE Lighting Contactor X

284 2H7—480/277 Volt Distribution Panel X

285 2DH2—480/277 Volt Distribution Panel X

286 45 KVA 3ø GE Transformer X

287 2L7—208/120 Volt Distribution Panel X

288 2PL21—208/120 Volt Distribution Panel X

ROOM 2A-124 (MSD Clean)

289 2L11—208/120 Volt Distribution Panel X

290 2EL1—208/120 Volt Distribution Panel X

291 2EH1—480/277 Volt Distribution Panel X

292 2L2—208/120 Volt Distribution Panel X

293 45 KVA 3ø GE Transformer X

Fault #

294 2DH1—480/277 Volt Distribution Panel X

295 2H2—480/277 Volt Distribution Panel X

296 Transformer 2L11—30 KVA 3ø GE Transformer X

297 9 KVA 3ø GE Transformer Didn’t Scan

ROOM 2B-137

298 2CL2-A—208/120 Volt Distribution Panel X

299 2CL1—208/120 Volt Distribution Panel X

300 75 KVA 3ø GE Transformer X

301 2DCH—480/277 Volt Distribution Panel X

302 2CH1 Section 1—208/120 Volt Distribution Panel X

303 2CH1 Section 2—208/120 Volt Distribution Panel X

304 2CH2—480/277 Volt Distribution Panel X

305 2HX1—480/277 Volt Distribution Panel X

306 ATS-CR-2 Switch X

307 2L1—208/120 Volt Distribution Panel X

308 45 KVA 3ø Square D Transformer X

309 9 KVA 3ø GE Overhead Transformer Didn’t Scan

310 2L1 XFMR Disconnect X

ROOM 2B-168

311 2CH5—480/277 Volt Distribution Panel X

312 2CL5—208/120 Volt Distribution Panel X

313 2L10—208/120 Volt Distribution Panel X

314 2DH3—480/277 Volt Distribution Panel X

315 2H10—480/277 Volt Distribution Panel X

316 Left 30 KVA 3ø GE Transformer X

317 Right 30 KVA 3ø GE Transformer X

318 Unlabeled GE Lighting Contactor X

ROOM 2C-107

319 2L9—208/120 Volt Distribution Panel X

320 2H9—480/277 Volt Distribution Panel X

Fault #

321 2EH4—480/277 Volt Distribution Panel X

322 2EL4—208/120 Volt Distribution Panel X

323 2CL4—208/120 Volt Distribution Panel X

324 2CH4—480/277 Volt Distribution Panel X

325 75 KVA 3ø GE Transformer X

326 Unlabeled GE Lighting Contactor X

327 30 KVA 3ø GE Transformer X

328 9 KVA 3ø GE Transformer Didn’t Scan

ROOM 2C-158

329 Unlabeled GE Lighting Contactor X

330 2L8 Section 1—208/120 Volt Distribution Panel X

331 2L8 Section 2—208/120 Volt Distribution Pane X

332 2H8—480/277 Volt Distribution Panel X

333 45 KVA 3ø GE Transformer X

ROOM 2D-110

334 Unlabeled GE Lighting Contactor X

335 2EH3—480/277 Volt Distribution Panel X

336 2EL3—208/120 Volt Distribution Panel X

337 2H5—480/277 Volt Distribution Panel X

338 2L5 Section 1—208/120 Volt Distribution Panel X

339 2L5 Section 2—208/120 Volt Distribution Panel X

340 75 KVA 3ø GE Transformer X

341 9 KVA 3ø GE Transformer Didn’t Scan

ROOM 2D-134 / 2D-145 (REHABILITATION)

342 (Left) 2PL14 Distribution Panel X

343 (Right) 2PL14 Distribution Panel X

ROOM 2D-162

344 2PL15—208/120 Volt Distribution Panel X

Fault #

ROOM 2D-168

345 2H6—480/277 Volt Distribution Panel X

346 2L6—480/277 Volt Distribution Panel X

347 2QL3-A—208/120 Volt Distribution Panel X

348 2QL3—208/120 Volt Distribution Panel X

349 2QL3 Fuse Disconnect X 3

350 2QL3-B—208/120 Volt Distribution Panel X

351 75 KVA 3ø GE Transformer X

352 112.5 KVA 3ø GE Transformer X

353 Computer Room Switch Locked Out

354 2D169 Air Conditioner Switch Not In Use

ROOM 2D-169 (Can’t Find)

355 2PL16—208/120 Volt Distribution Panel

356 2QL169—208/120 Volt Distribution Panel

ROOM 2D-171 (CHEMISTRY)

357 2PL17—208/120 Volt Distribution Panel X

ROOM 2D-173 (BLOOD BANK)

358 2PL18—208/120 Volt Distribution Panel X

ROOM 2D-176 (Serology)

359 2PL19—208/120 Volt Distribution Panel X

ROOM 2D-183 (HEMATOLOGY LAB)

360 2PL20—208/120 Volt Distribution Panel X

ROOM 2D-184

361 2PL5—208/120 Volt Distribution Panel X

ROOM 2E-110

362 2PL10—208/120 Volt Distribution Panel X

ROOM 2E-111

363 2EH2—480/277 Volt Distribution Panel X

364 Unlabeled GE Lighting Contactor X

365 2EL2—208/120 Volt Distribution Panel X

Fault #

366 2L4 Section 1—208/120 Volt Distribution Panel X

367 2L4 Section 2—208/120 Volt Distribution Pane X

368 2H4—480/277 Volt Distribution Panel X

369 2QL2 XFMR Disconnect X

370 75 KVA 3ø GE Transformer X

371 Mortuary Compressor Fuse Disconnect X

372 112.5 KVA 3ø GE Transformer X

373 9 KVA 3ø GE Transformer Didn’t Scan

374 2QL2 Section 1—208/120 Volt Distribution Panel X

375 2QL2 Section 2—208/120 Volt Distribution Pane X

ROOM 2E-112

376 2PL12—208/120 Volt Distribution Panel X

ROOM 2E-119

377 2PL13—208/120 Volt Distribution Panel X

ROOM 2E-127

378 2PL11—208/120 Volt Distribution Panel X

ROOM 2E-135

380 2PL9—208/120 Volt Distribution Panel X

ROOM 2E-138

381 2PL8—208/120 Volt Distribution Panel X

ROOM 2E-141

382 2PL4—208/120 Volt Distribution Panel X

ROOM 2E-160

383 2H3—480/277 Volt Distribution Panel X

384 2L3 Section 1—208/120 Volt Distribution Panel X

385 2L3 Section 2—208/120 Volt Distribution Pane X

386 45 KVA 3ø GE Transformer X

379 2QL2—Disconnect X

Fault #

387 30 KVA 3ø GE Transformer X

388 2CL3—208/120 Volt Distribution Panel X

389 2CH3—480/277 Volt Distribution Panel X

390 2DCH2—480/277 Volt Distribution Panel X

ROOM 2F-209

391 2FCH2—480/277 Volt Distribution Panel X

392 2FLSL—208/120 Volt Distribution Panel X

393 Transformer T2 FLSL—Disconnect X

394 Transformer T2 FCL1—Disconnect X

395 T2FLSL—Transformer X

396 T2FNL1—Transformer X

397 T2FCL1—Transformer X

398 2FNH1—480/277 Volt Distribution Panel X

399 2FNL1—208/120 Volt Distribution Panel X

400 2FCL1—208/120 Volt Distribution Panel X

401 2FCL2—208/120 Volt Distribution Panel X

402 2FCH1—480/277 Volt Distribution Panel X

FLOOR LEVEL #1

ROOM 1A-113

403 1L6 Section 1—208/120 Volt Distribution Panel X

404 1L6 Section 2—208/120 Volt Distribution Pane X

405 1DH2—480/277 Volt Distribution Panel X

406 1H6—480/277 Volt Distribution Panel X

407 1HX2—480/277 Volt Distribution Panel X

408 1LX2—208/120 Volt Distribution Panel X

409 Unlabeled GE Lighting Contactor X

410 50 KVA GE 3ø Transformer X

411 75 KVA GE 3ø Transformer X

412 Unlabeled 40 Amp Molded Case Breaker X

ROOM 1B-154

Fault #

413 1L9 Section 1—208/120 Volt Distribution Panel X

414 1L9 Section 2—208/120 Volt Distribution Pane X

415 1L9D—208/120 Volt Distribution Panel X

416 1L9C—208/120 Volt Distribution Panel X

417 1DH3—480/277 Volt Distribution Panel X

418 1H9—480/277 Volt Distribution Panel X

419 1QL4—208/120 Volt Distribution Panel X

420 Fryer in Grill—60 Amp Molded Case Breaker X

421 30 KVA 3ø Square D Transformer X

422 30 KVA 3ø GE Transformer X

423 150 KVA 3ø GE Transformer X

424 1B-163 Refrigeration Fuse Disconnect Not In Use

425 1B-164 Freezer Fuse Disconnect X

426 1QL4 XFMR Disconnect X

ROOM 1B-160 (CAFETERIA)

427 1HK—480/277 Volt Distribution Panel X

428 1PL6 Section 1 “A”—208/120 Volt Distribution Panel X

429 1PL6 Section 2 “B:—208/120 Volt Distribution Panel X

ROOM 1B-168-01

430 1QH8—480/277 Volt Distribution Panel X

431 45kVA Transformer X

432 1QL8—208/120 Volt Distribution Panel X

433 1EH4—480/277 Volt Distribution Panel X

434 9KVA Transformer Didn’t Scan

435 1EL4—208/120 Volt Distribution Panel X

ROOM 1C-146

436 1H7A “1QH6A” 480/277 Volt Distribution Panel X

437 Unlabeled GE Lighting Contactor X

Fault #

438 112.5 KVA 3ø GE Transformer Didn’t Scan

439 1H7 “1QH6”—480/277 Volt Distribution Panel X

440 1L7 Section 1 “1QL8”—208/120 Volt Distribution Panel X

441 1L7 Section 2 “1QL8”—208/120 Volt Distribution Pane X

442 1L7A Section 1 “1QL9”—208/120 Volt Distribution Panel X

443 1L7A Section 2 “1QL9”—208/120 Volt Distribution Panel X

ROOM 1E-77D

444 PDB Disconnect X

ROOM 1E-177C

445 PDB Disconnect X

ROOM 1C-158

446 1QL7 “New”—208/120 Volt Distribution Panel X

447 1QH7—480/277 Volt Distribution Panel X

448 1Ql10 Section 1—208/120 Volt Distribution Panel X

449 1Ql10 Section 2—208/120 Volt Distribution Panel X

450 1EH3—480/277 Volt Distribution Panel X

451 1EL3—208/120 Volt Distribution Panel X

452 45 KVA 3ø GE Transformer X

453 Small Unlabeled GE Lighting Contactor X

454 Large Unlabeled GE Lighting Contactor X

455 9 KVA 3ø GE Transformer X

ROOM 1D-116

456 1PL4—208/120 Volt Distribution Panel X

457 1QH2—480/277 Volt Distribution Panel X

458 1QL2—208/120 Volt Distribution Panel X

459 15 KVA 3ø GE Transformer X

460 1H5—480/277 Volt Distribution Panel X

461 75 KVA 3ø GE Transformer X

462 1L5 Section 1—208/120 Volt Distribution Panel X

463 1L5 Section 2—208/120 Volt Distribution Pane X

Fault #

464 Unlabeled GE Lighting Contactor X

ROOM 1D-131-A

465 1DH4—480/277 Volt Distribution Panel X

466 1CL2—208/120 Volt Distribution Panel X

467 1QH3—480/277 Volt Distribution Panel X

468 1QL5—208/120 Volt Distribution Panel X

469 1L13—208/120 Volt Distribution Panel X

470 1H10—480/277 Volt Distribution Panel X

471 1CL5 Disconnect X

472 Transformer 1L13—30 KVA 3ø Transformer X

473 Transformer 1QL5—30 KVA 3ø Transformer X

474 Transformer 1CL2—45 KVA 3ø Transformer X

ROOM 1D-176

475 Unlabeled GE Lighting Contactor X

476 1L3 Section 1—208/120 Volt Distribution Panel X

477 1L3 Section 2—208/120 Volt Distribution Pane X

478 75 KVA 3ø GE Transformer X

479 1H3—480/277 Volt Distribution Panel X

480 1CL XFMR Disconnect X

481 30 KVA 3ø GE Transformer X

482 1CL1—208/120 Volt Distribution Panel X

483 1EH2—480/277 Volt Distribution Panel X

484 9 KVA 3ø GE Transformer Didn’t Scan

485 1EL2—208/120 Volt Distribution Panel X

ROOM 1D-178

486 1PL1—208/120 Volt Distribution Panel X

487 Unlabeled Sub Panel X

488 Unlabeled Square D 30 Amp Fuse Disconnect X

Fault #

ROOM 1D-159

489 1PL3—208/120 Volt Distribution Panel X

ROOM 1E-110

490 1L10—208/120 Volt Distribution Panel X

491 1L1 Section 1—208/120 Volt Distribution Panel X

492 1L1 Section 2—208/120 Volt Distribution Pane X

493 1DH1—480/277 Volt Distribution Panel X

494 1H1—480/277 Volt Distribution Panel X

495 1EH1—480/277 Volt Distribution Panel X

496 1EL1—208/120 Volt Distribution Panel X

497 1L11—208/120 Volt Distribution Panel X

498 Unlabeled GE Lighting Contactor X

499 Left 30 KVA 3ø GE Transformer X

500 Right 30 KVA 3ø GE Transformer X

501 75 KVA 3ø GE Transformer X

ROOM 1E-161

502 1LX3—208/120 Volt Distribution Panel X

503 1QHX—480/277 Volt Distribution Panel X

504 1LX1—208/120 Volt Distribution Panel X

505 Unlabeled GE Lighting Contactor X

506 Left 30 KVA 3ø GE Transformer X

507 Right 30 KVA 3ø GE Transformer X

508 1QH1—480/277 Volt Distribution Panel X

509 1LX3 Fuse Disconnect X

510 1HX1—45 KVA 3ø GE Transformer X

511 ATS-Q8 IE161 X-Ray Switch X

512 1HX1—480/277 Volt Distribution Panel X

513 1L2—208/120 Volt Distribution Panel X

514 15 KVA 3ø GE Transformer X

515 1H2—480/277 Volt Distribution Panel X

Fault #

516 1QL1—208/120 Volt Distribution Panel X

ROOM 1E-162

517 Exhaust Fan 37 Disconnect X

518 Exhaust Fan 38 Disconnect X

519 75 KVA 3ø GE Transformer Fuse Disconnect X

520 75 KVA 3ø GE Transformer X

521 1QL3—208/120 Volt Distribution Panel X

522 1DQH1—480/277 Volt Distribution Panel X

523 XFMR 1QL6—75 KVA Square D 3ø Transformer X

524 Liebert Unit Fuse Disconnect X

525 1H1 15 Disconnect X

526 1QL6—208/120 Volt Distribution Panel X

527 25 KVA 1ø Square D Transformer X

528 EX-36 Disconnect X

529 AC2 Disconnect X

MCC 4

530 EX-35 X

531 EX-36 X

532 EX-37 X

533 EX-38 X

534 AC-1 X

535 CU-1 X

536 AC-47 X

537 Incoming Main Cables X

538 Blank

539 Blank

ROOM 1E-189 (Can’t Access)

540 1LRA—208/120 Volt Distribution Panel

Fault #

541 TLRA-1 Fuse Disconnect

542 TLRA-1—30 KVA GE 3ø Transformer

ROOM 1E-176

543 1HX3—480/277 Volt Distribution Panel X

ELEVATOR CONTROL ROOM 1F-101

544 Elevator Control Cabinet X

545 Elevator Disconnect X

546 Cab Light Disconnect X

ROOM 1F-138

547 1FNL2—208/120 Volt Distribution Panel X

548 Sec. #2 1FNL1—208/120 Volt Distribution Panel X

549 Sec. #1 1FNL1—208/120 Volt Distribution Panel X

550 75 KVA Square D 3ø Transformer X

551 1FNH1—480/277 Volt Distribution Panel X

552 1FEQL1—208/120 Volt Distribution Panel X

553 Sec. #2 1FCL2—208/120 Volt Distribution Panel X

554 Sec. #1 1FCL2—208/120 Volt Distribution Panel X

555 Sec. #2 1FCL1—208/120 Volt Distribution Panel X

556 Sec. #1 1FCL1—208/120 Volt Distribution Panel X

557 112.5 KVA Square D 3ø Transformer X

558 1FCH1—480/277 Volt Distribution Panel X

559 1FLSH1—480/277 Volt Distribution Panel X

ROOM 1E-176

560 1HX3—480/277 Volt Distribution Panel X

FLOOR LEVEL GROUND

ROOM GA-105

561 GPL17—208/120 Volt Distribution Panel X

562 GDH2—480/277 Volt Distribution Panel X

563 GL5—208/120 Volt Distribution Panel X

564 GH5—480/277 Volt Distribution Panel X

Fault #

565 GQH3—480/277 Volt Distribution Panel X

566 GQL3 Section 1—208/120 Volt Distribution Panel X

567 GQL3 Section 2—208/120 Volt Distribution Pane X

568 45 KVA 3ø GE Transformer X

569 Unlabeled GE Lighting Contactor X

570 150 KVA 3ø GE Transformer X

ROOM GB-110

571 Christmas Tree 208/120 Volt Distribution Panel X

572 GCH3—480/277 Volt Distribution Panel X

573 GQL7—208/120 Volt Distribution Panel X

574 GCL3—208/120 Volt Distribution Panel X

575 GH6—480/277 Volt Distribution Panel X

576 GL6 Section 1—208/120 Volt Distribution Panel X

577 GL6 Section 2—208/120 Volt Distribution Panel X

578 GQL5—208/120 Volt Distribution Panel X

579 GEH4—480/277 Volt Distribution Panel X

580 GQL8—208/120 Volt Distribution Panel X

581 GQL8 XFMR Disconnect X

582 75 KVA 3ø GE Transformer X

583 45 KVA 3ø GE Transformer X

584 30 KVA 3ø GE Transformer X

585 GQL5 XFMR Disconnect X

586 150 KVA 3ø GE Transformer X

587 Unlabeled GE Lighting Contactor X

588 Unlabeled 200 Line Lighting Contactor X

589 (Left) Unlabeled 300 Line Lighting Contactor X

590 (Right) Unlabeled 300 Line Lighting Contactor X

ROOM GB-101

Fault #

591 GPL 26 208/120 Volt Distribution Panel X

ROOM GB-103

592 GPL 25 208/120 Volt Distribution Panel X

ROOM GB-106

593 GPL 22 208/120 Volt Distribution Panel X

ROOM GB-113

594 GPL 23 208/120 Volt Distribution Panel X

ROOM GB-115

595 GPL 24 208/120 Volt Distribution Panel X

ROOM GB-118

596 GPL 33 208/120 Volt Distribution Panel X

ROOM GB-120

597 GPL 34 208/120 Volt Distribution Panel X

ROOM GB-122

598 GPL 35 208/120 Volt Distribution Panel X

ROOM GB-130

599 GPL 30 208/120 Volt Distribution Panel X

ROOM GB-136

600 GPL 31 208/120 Volt Distribution Panel X

ROOM GB-134

601 GL7 Section 1—208/120 Volt Distribution Panel X

602 GL7 Section 2—208/120 Volt Distribution Panel X

603 112.5 KVA 3ø GE Transformer X

604 GDH3—480/277 Volt Distribution Panel X

605 GH7—480/277 Volt Distribution Panel X

606 GQH4—480/277 Volt Distribution Panel X

607 45 KVA 3ø GE Transformer X

608 GQL4—208/120 Volt Distribution Panel X

609 Unlabeled GE Lighting Contactor X

ROOM GB-174

Fault #

610 GPL13 208/120 Volt Distribution Panel Can’t Locate

ROOM GC-106

611 GPL 27 208/120 Volt Distribution Panel X

ROOM GC-101

612 GPL 29 208/120 Volt Distribution Panel X

ROOM GC-124

613 GPL 6 208/120 Volt Distribution Panel X

ROOM GC-116

614 GPL 7 208/120 Volt Distribution Panel X

ROOM GC-128

615 GPL 10 208/120 Volt Distribution Panel X

ROOM GC-135

616 GPL11 208/120 Volt Distribution Panel X

ROOM GC-136

617 GPL12 208/120 Volt Distribution Panel X

ROOM GC-138

618 GQL6—208/120 Volt Distribution Panel X

619 GQL2 Section 1—208/120 Volt Distribution Panel X

620 GQL2 Section 2—208/120 Volt Distribution Panel X

621 GL4 Section 1—208/120 Volt Distribution Panel X

622 GL4 Section 2—208/120 Volt Distribution Panel X

623 (Left) Unlabeled 200 Line Lighting Contactor X

624 (Right) Unlabeled 200 Line Lighting Contactor X

625 75 KVA 3ø GE Transformer X Didn’t Scan

626 45 KVA 3ø GE Transformer X Didn’t Scan

627 15 KVA 3ø GE Transformer X Didn’t Scan

628 GEH3—480/277 Volt Distribution Panel X

629 GEL3—208/120 Volt Distribution Panel X

Fault #

630 GH4—480/277 Volt Distribution Panel X

631 GQL6—200 Amp Fuse Disconnect X

632 112.5 KVA 3ø GE Transformer Didn’t Scan

633 GQL2 XFMR Disconnect X

634 #G-8 Fuse Disconnect X

635 #G-9 Fuse Disconnect X

636 #G-10 Fuse Disconnect X

637 G5 Control Cabinet X

ROOM GC-143

638 GPL13 208/120 Volt Distribution Panel X

ROOM GC-150

639 GPL 14 208/120 Volt Distribution Panel X

ROOM GC-155

640 GPL 3 208/120 Volt Distribution Panel X

ROOM GC-157

641 GPL 2 208/120 Volt Distribution Panel X

GC-162

642 GL9—208/120 Volt Distribution Panel X

643 GL-9—45 KVA 3ø GE Transformer Didn’t Scan

644 GQH9 240 Volt Distribution Panel X

645 GQH9—480/277 Volt Distribution Panel X

646 GQL17—208/120 Volt Distribution Panel X

647 GL9X Transformer X

ROOM GC-167 (KITCHEN)

648 Tray Wash Disconnect X

649 Meta Cooler Disconnect X

650 Milk Box Disconnect X

651 Diet Cooler Disconnect X

652 Diet Freezer Disconnect X

653 Meta Freezer Disconnect X

Fault #

654 GHK—480/277 Volt Distribution Panel X

655 GPL18 (Left)—480/277 Volt Distribution Panel X

656 GPL18 (Right)—480/277 Volt Distribution Panel X

ROOM GD-123

657 30 KVA Square D 3ø Transformer X

658 GQL16—208/120 Volt Distribution Panel X

659 GDQH5—480/277 Volt Distribution Panel X

660 ATS-Q16 Automatic Transfer Switch X

661 ATS-Q15 Automatic Transfer Switch X

662 ATS-Q14 Automatic Transfer Switch X

663 GDQH2—480/277 Volt Distribution Panel X

664 GQHPCT GE 480/277 Volt Distribution Panel X

ROOM GD-112

665 GE 200 Line Lighting Contactor X

666 GE Control Lighting Contactor X

667 GL3 Section 1—208/120 Volt Distribution Panel X

668 GL3 Section 2—208/120 Volt Distribution Panel X

669 GEL2—208/120 Volt Distribution Panel X

670 75 KVA 3ø GE Transformer X

671 75 KVA 3ø GE Transformer X

672 GH3—480/277 Volt Distribution Panel X

673 GEH2—480/277 Volt Distribution Panel X

SWITCHGEAR ROOM

674 Unit Sub Station D (Cooling Fins Only)

675 Unit Sub Station B (Cooling Fins Only)

676 Unit Sub Station C (Cooling Fins Only)

677 ABB Capacitor Bank (Cooling Fins Only)

678 Chiller #1 Switchgear (Cooling Fins Only)

Fault #

679 Chiller #2 Switchgear (Cooling Fins Only)

680 GDH5—480/277 Volt Distribution Panel X

ROOM GD-128

681 GQH2—480/277 Volt Distribution Panel X

682 GH2—480/277 Volt Distribution Panel X

683 30 KVA 3ø GE Transformer X

684 GL2—208/120 Volt Distribution Panel X

685 GCH2—480/277 Volt Distribution Panel X

686 75 KVA 3ø GE Transformer X

ROOM GD-129 (BOILER ROOM)

687 GQLB—208/120 Volt Distribution Panel X

688 GQLB—30 KVA GE 3ø Transformer X

689 GQLB X-FMR—Disconnect X

690 Onan ATS Q-3 GD133 Automatic Transfer Switch X

691 Boiler #1 Control Cabinet X

692 Boiler #2 Control Cabinet X

693 Boiler #3 Control Cabinet X

694 FW-1 Fuse Disconnect (Drive) X

695 FW-2 Fuse Disconnect (Drive) X

696 CTPS #1 Disconnect (Drive) X

697 CTPS #2 Disconnect (Drive) X

MCC-Q1A

698 FWP-1 X

699 FWP-2 X

700 Spare X

701 Spare X

702 CTP-1 X

703 CTP-2 X

704 FOP-1 X

705 FOP-2 X

Fault #

706 Spare X

707 Spare X

708 Spare X

709 ATC Air Compressor X

710 Incoming Line X

711 Blank

712 Blank

713 Blank Boiler-3 X

714 Blank Boiler-2 LOTO

715 Blank Boiler-1 X

716 Deaerator X

717 Sump Pump X

718 Transformer GQLB X

719 Blank

ROOM GD-129 (BOILER ROOM MEZZANINE)

720 H/V-3 Disconnect X

ROOM GD-139 (OUTSIDE)

721 GL2—240/120 Volt Distribution Panel X

722 GH9—480/277 Volt Distribution Panel X

ROOM GD-130 (CONTROL ROOM)

723 GQHB—480/277 Volt Distribution Panel X

724 GCL1—208/120 Volt Distribution Panel X

725 9 KVA 3ø GE Overhead Transformer Didn’t Scan

726 9 KVA 3ø GE Transformer Disconnect X

ROOM GD-133 (CHILLER PLANT)

727 Chiller #1 Control Cabinet X

728 Chiller #2 Control Cabinet X

729 Chiller #3 Control Cabinet X

Fault #

730 UH-3 Combination Starter X

731 UH-5 Combination Starter X

732 (Left) #1 Quincy Air Compressor Fuse Disconnect X

733 (Left) #1 Quincy Air Compressor Control Cabinet X

734 (Right) #2 Quincy Air Compressor Fuse Disconnect X

735 (Right) #2 Quincy Air Compressor Control Cabinet X

736 CWP-1 Drive Cabinet X

737 CHWP-1 Drive Cabinet X

738 CLWP-10 Disconnect LOTO

739 CLWP-11 Disconnect X

740 GLMG—208/120 Volt Distribution Panel X

741 North Tower Drive Cabinet X

742 Air Conditioning Starter X

743 30 KVA Square D 3ø Transformer X

744 Chiller 1 South Fan Drive X

745 GHMG—480/277 Volt Distribution Panel X

746 ATS-MG Automatic Transfer Switch X

747 Cooling Tower #3 Drive X

748 ATS-Q2 Automatic Transfer Switch X

749 GDQH4—480 Volt Distribution Panel X

750 Yaskawa Z1000 VFD (Left) X

751 Yaskawa Z1000 VFD (Right) X

752 Condenser Pump P4 Disconnect X

753 Condenser Pump P5 Disconnect X

754 Cooling Tower #2A Drive X

755 Cooling Tower #2B Drive X

756 CWP-3 Disconnect X

757 CHWP-3 Disconnect X

758 GLB—208/120 Volt Distribution Panel X

759 SCHWP #1 Drive Cabinet X

Fault #

760 SCHWP #2 Drive Cabinet X

761 MCC-1 X

762 MCC-2 X

763 MCC-Q1B X

764 HP-1—480/277 Volt Distribution Panel X

765 LP-1—208/120 Volt Distribution Panel X

766 T/LP-1—45 KVA Square D 3ø Transformer Didn’t Scan

767 (Left) Fuel Oil Pump Disconnect X

768 (Right) Fuel Oil Pump Disconnect X

769 Chemical Feed Pump Combination Starter X

770 Back-Up Air Compressor Motor Control X

771 Back-Up Air Compressor Disconnect X

772 Overhead GE Transformer Didn’t Scan

773 Unlabeled 60 Amp Disconnect (Right of Panel GLB) X

ROOM GD-134

774 GQLG—208/120 Volt Distribution Panel X

ROOM GE-115

775 Fire Pump Controller Control Cabinet X

776 Jockey Pump Controller Control Cabinet X

777 ATS-Q9 Fire Pump Switch X

778 Welder Fuse Disconnect X

MCC-3

779 HV-1 X

780 V-1 X

781 V-2 X

782 Blank

783 V-6 X

784 HV-2 X

Fault #

785 P-1 X

786 P-2 X

787 P-3 X

788 Hot Water Circulation Pump X

789 Incoming Line X

790 Blank

791 De-ionization Booster Pump X

792 De-ionization Circulation Pump X

793 CPU-8 X

794 Spare

795 Spare

ROOM GE-116

SUB STATION UNIT A

796 Unit 1A Incoming Line Terminals X

797 Unit 2A Incoming Service Auxiliary X

798 Unit 3A—Bus Tie Breaker X

799 Unit 4A—Feeder HV-1-2 & HV-1-3 X

800 Unit 5A—Feeder HV-1-1 X

801 Unit 6A—Feeder Spare X

SUB STATION UNIT B

802 Unit 1B Incoming Line Terminals X

803 Unit 2B Incoming Service Auxiliary X

804 Unit 3B—Auxiliary X

805 Unit 4B—Feeder HV-2-2 & HV-2-3 X

806 Unit 5B—Feeder HV-2-1 X

807 Unit 6B—Feeder HV-2-4 X

ROOM GE-117

808 GDH4—480/277 Volt Distribution Panel X

809 GDHX—480/277 Volt Distribution Panel X

810 ATS-E1 GE-117 Switch X

Fault #

811 GDEH—480/277 Volt Distribution Panel X

812 GEH1—480/277 Volt Distribution Panel X

813 GEL1—208/120 Volt Distribution Panel X

814 ATS-CR3 Ambulatory Surgery 2nd Floor Switch X

815 ATS-Q13 Cath Lab Switch X

816 GDQH—480/277 Volt Distribution Panel X

817 GQH1—480/277 Volt Distribution Panel X

818 GH1—480/277 Volt Distribution Panel X

819 GL1—208/120 Volt Distribution Panel X

820 GH10—480/277 Volt Distribution Panel X

821 GL10—208/120 Volt Distribution Panel X

822 GQH5—480/277 Volt Distribution Panel X

823 GDH1—480/277 Volt Distribution Panel X

824 ATS-Q1 Switch X

825 GQL1—208/120 Volt Distribution Panel X

826 (Left) 9 KVA 3ø GE Transformer Didn’t Scan

827 GQL9 XFMR—75 KVA 3ø GE Transformer X

828 GDCH—480/277 Volt Distribution Panel X

829 ATS-CR-1 Switch X

830 (Right) 9 KVA 3ø GE Transformer Didn’t Scan

831 75 KVA 3ø GE Transformer X

832 GE 200 Line Lighting Contactor X

833 GE 300 Line Lighting Contactor X

834 GE Control Lighting Contactor X

835 GE117—30 KVA 3ø GE Transformer X

836 Unit Sub Station A Switchgear X 5,6

837 Unit Sub Station B Switchgear X

ROOM GE-121

Fault #

838 GQHP—480 Volt Distribution Panel X

839 ATS-Q10 Medical Vacuum & Air Switch X

840 GHP2—480 Volt Distribution Panel X

841 Medical Vacuum #1 Compressor Control Cabinet X

842 Medical Vacuum #2 Compressor Control Cabinet X

843 Medical Vacuum #1 & #2—Disconnect X

844 Oral Evacuator Compressor Control Cabinet Not In Use

845 Serial #7217 Pump Control Cabinet X

846 Domestic Water Booster Pump Control Cabinet X

847 Medical Vacuum #3 Compressor Control Cabinet X

848 Medical Air Unit #1 Compressor Control Cabinet Can’t Open

849 Medical Air Unit #1 Compressor Fuse Disconnect X

850 Medical Air Unit #2 Compressor Control Cabinet X

851 Medical Air Unit #2 Compressor Fuse Disconnect X

ROOM GE-123

852 GH8—480/277 Volt Distribution Panel X

853 GQLA Transformer Fuse Disconnect X

854 GQL9— 208/120 Volt Distribution Panel X

855 GHP1— 480/277 Volt Distribution Panel X

856 GPL1—208/120 Volt Distribution Panel X

857 GQH6—480/277 Volt Distribution Panel X

858 GQL18—480/277 Volt Distribution Panel X

ROOM GF-105

859 GPL 41 208/120 Volt Distribution Panel X

ROOM GF-106

860 GPL 40 208/120 Volt Distribution Panel X

ROOM GF-107

861 GPL 39 208/120 Volt Distribution Panel X

ROOM GF-114

862 GPL 38 208/120 Volt Distribution Panel X

Fault #

ROOM GF-115

863 GPL 37 208/120 Volt Distribution Panel X

ROOM GF-140

864 GQL14—208/120 Volt Distribution Panel X

865 GQH8—480/277 Volt Distribution Panel X

866 GQH7—480/277 Volt Distribution Panel X

867 225 KVA GE 3ø Transformer X

868 GQL10—480/277 Volt Distribution Panel X

869 GQL13—208/120 Volt Distribution Panel X

870 GQL12—208/120 Volt Distribution Panel X

871 GQL11—208/120 Volt Distribution Panel X

872 GL13—208/120 Volt Distribution Panel X

873 GL12—208/120 Volt Distribution Panel X

874 GH12—480/277 Volt Distribution Panel X

875 GL11—150 KVA GE 3ø Transformer X

876 GDH6—480/277 Volt Distribution Panel X

877 GEH5—480/277 Volt Distribution Panel X

878 GEL5—30 KVA GE 3ø Transformer X

879 GEL5—208/120 Volt Distribution Panel X

880 GE Lighting Contactor X

881 GQL15—208/120 Volt Distribution Panel X

ROOM GF-143

882 2FEQH1—480/277 Volt Distribution Panel X

883 GFEQL1—208/120 Volt Distribution Panel X

884 TGFEQL1—75 KVA Square D 3ø Transformer X

885 1FEQH1—480/277 Volt Distribution Panel X

ROOM GF-144

886 GFEQL2—208/120 Volt Distribution Panel X

Fault #

PARKING DECK (ROOM 118)

887 MBP 480/277 Volt Distribution Panel X

888 Panel P1 480/277 Volt Distribution Panel X

889 Panel LP 208/120 Volt Distribution Panel X 4

890 EF-1 Disconnect X

891 T1 45 kVA Transformer X

OUTSIDE ROOM 118

892 AUH-1 Disconnect X

Note: Items not marked as “Operating” or “Visually Inspected” were not included in the scan due to inaccessibility, could not open, being locked out, not in service, deemed not safe to open, not in-cluded at customer direction or time constraints.