This solicitation is for electrical system preventive maintenance and testing services at two Veterans Affairs medical centers in Little Rock and North Little Rock, Arkansas. The required services include preventive maintenance, testing, and inspection of electrical equipment and systems. The solicitation is set aside for veteran-owned small businesses. Interested parties must be registered in the VA Vendor Information Pages and SAM databases by the date of quote submission. Questions about the solicitation are due by August 22 with site visits scheduled for August 18. Quotes are due on September 9 and must include pricing, certifications, and representations. The award will be a one year contract with four one-year options to renew. The Central Arkansas VA Healthcare System is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VETERANS AFFAIRS MEDICAL
CENTER FORT ROOTS
NORTH LITTLE ROCK,
ARKANSAS
November, 2021
Infrared Inspection Report©
2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227
PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: Logistics@usscanman.com
Veterans Affairs Medical Center Fort Roots 2200 Fort Roots Drive North Little Rock, Arkansas, 72114 Company Contact:
David Barnes Project: 07011121
36C25622Q1188 0001 Exhibit Q
DISCLAIMER
This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not in-tended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility’s condition, maintenance practices or correction of conditions indicated herein.
By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, con-cerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.
ORDER OF REPORT CONTENTS
1: Data To Facilitate Understanding & Utilizing Scan Report
2: Scan Results Overview & Action Taken Form
3: Identified Faulting Conditions, Information & Photographs
4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found
Utilizing Report Contents
Included in this report are Photographs and Thermographs of problem areas found during our recent
Infrared Inspection of your facility.
Each problem area picture is accompanied by:
Date
Location Information
Temperature Calculations
Color-coded Temperature Intensity and/or Condition Significance Data
A Brief Comment Relating The Item In The Photograph To Its Corresponding
Thermograph
Suggested Corrective Recommendations.
In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity.
Thermal intensity is indicated by use of a color-coded data inserts that locate a fault‘s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows:
INSERT Temperature Range
Red 70ºC/126ºF and higher above Ambient Operating Temp.
Orange 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp.
Yellow 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp.
Green *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp.
( * See page 4)
FAULTY EQUIP MONTHS MONTHS TO WEEKS WEEKS TO NOW
Determining Cost Effective Responses
Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate.
Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports.
Built In Trend Monitoring
When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings.
If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.
YEARS
10ºC * 18ºF
25ºC 45ºF
40°C 72ºF
70°C 126ºF
AMBIENT TEMP
STANDARD ELECTRICAL FAULT FAILURE CURVE
(Does Not Include Area In Blue)
DEVICE
TEMP
IS
AMBIENT,
BUT
DEVICE
IS
EITHER
FAULTY
OR
UNSAFE. INTERMEDIATE MINOR SERIOUS CRITICAL
Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use
Total Temperature:
Total Temperature = Ambient Operating Temperature + Fault temperature
Allows you, the customer, to evaluate possible damage to equipment.
Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating.
Contacts start to fail around 130ºC/266ºF
Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes:
Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet.
If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault.
Allows you, the customer, to determine if device will operate at intended amperage.
Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine)
If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip.
1. An intermittent high load.
2. A minor (Green) or intermediate (Yellow) fault.
Report pages with photographs:
PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature
Both black & white and color infrared thermographs are presented to better depict the fault condition.
In addition to the corrective response time frame suggested below and the failure curve lo-cated on the previous page, you may want to consider using the military standard responses presented below.
Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment:
Temperatures rise above Ambient Operating Temperature:
*10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label)
25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label)
40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected.
(Orange Label)
70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label)
Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions.
* Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind.
Fault Correction Recommendation When Our Source Assessment Is Inaccurate:
When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist.
The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located.
Example:
If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp.
in the lead holder lug.
SCAN RESULTS OVERVIEW
PROMPT ATTENTION ITEMS:
Because of:
1. The intensity or heat level indicated at the time of the scan.
2. Deterioration caused by excessive temperature not present at the time of the scan.
3. Physical condition irregularities observed at the time of the scan.
We recommend that the following faults be given prompt attention:
Faults: #3*, #4, #5
Items With Asterisks Have High Total or Ambient Operating Temperatures.
United Spectrographics November, 2021
SUMMARY OF FINDINGS
FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO.
MINOR 3
1/398 2/811 4/126
INTERMEDIATE 0 0
SERIOUS 1 5/78
CRITICAL 1 3/479
SERIOUS 0 0
Number of items located at facility: 999
Number of faults: 5
ACTION TAKEN
Veterans Affairs Medical Center Fort Roots
North Little Rock, Arkansas November, 2021
Fault # Item # Category Repaired Monitor Date Name
1 398 Minor
2 811 Minor
3 479 Critical
4 126 Minor
5 78 Serious
PROJECT: 07011121
CUST REP: Justin & Michael
SCAN REP: Isamu Charleston
DATE: November 1st, 2021
LOCATION: Building 170 Room GB-111 Box Labeled:
Dental Air Compressor Fuse Disconnect
PH # 1 >
ITEM: Cø Disconnect & Fuse Block
SOURCE: Disconnect: Line & load side discon-nect blade contact area.
Fuse Block: Line side fuse blade holder.
TEMP: Temp. of areas indicating a faulting condition range to:
50ºC / 122ºF Total Temp.
- 32ºC / 90ºF AOT
= 18ºC / 32ºF above AOT.
TH # 1 >
COMMENTS
Abnormal heat is being generated in fuse discon-nect components. See green arrows in PH#1 and
TH#1.
Loose and/or corroded contact areas. Clean, in-spect and re-secure.
TEMPERATURE ABOVE
AOT
18°C / 32°F
TH # 1 >
SCAN REP: Isamu Charleston
DATE: November 1st, 2021
LOCATION: Building 170 Penthouse Pod F
MCC-P1
Box Labeled:
MCP-1
Fuse Disconnect
< PH # 2
ITEM: Middleø of Disconnect
SOURCE: Line & load side disconnect blade contact area.
TEMP: Temp. of contact areas range to:
45ºC / 113ºF Total Temp.
- 27ºC / 81ºF AOT
= 18ºC / 32ºF above AOT.
< TH # 2
COMMENTS
Abnormal heat is being generated in disconnect components. See green arrows in PH#2 and
TH#2.
spect and re-secure.
18°C / 32°F
< TH # 2
SCAN REP: Isamu Charleston
DATE: November 1st, 2021
LOCATION: Building 170 Room GJ-103 Box Labeled:
Air Compressor 2 Fuse Disconnect
PH # 3 >
ITEM: Bø Disconnect & Fuse Block
SOURCE: Disconnect: Line & load side discon-nect blade contact area.
Fuse Block: Line side fuse clip.
TEMP: Temp. of areas indicating a faulting condition range to:
115ºC / 239ºF Total Temp.
- 31ºC / 88ºF AOT
= 84ºC / 151ºF above AOT.
TH # 3 >
COMMENTS
Abnormal heat is being generated in fuse discon-nect components. See red arrows in PH#3 and
TH#3.
spect and re-secure serviceable components.
84°C / 151°F
TH # 3 >
SCAN REP: Isamu Charleston
DATE: November 2nd, 2021
LOCATION: Building 68 Outside Box Labeled:
XF-BLDG-68B
Pad Mounted Transformer Secondary Connections
< PH # 4
ITEM: X3 Secondary
SOURCE: Bushing.
TEMP: Temp. of bushing is:
27ºC / 81ºF Total Temp.
- 17ºC / 63ºF AOT
= 10ºC / 18ºF above AOT.
Note: Condition could be much worse than indicated by tempera-ture.
< TH # 4
COMMENTS
Abnormal heat is being generated in transformer component. See green arrows in PH#4 and
TH#4.
Loose and/or corroded contact area. Clean, in-spect and re-secure. Oil analysis should be done to check for internal faulting condition.
10°C / 18°F
< TH # 4
SCAN REP: Isamu Charleston
DATE: November 3rd, 2021
LOCATION: Building 66 Basement Box Labeled:
Hot Water Heater Fuse Disconnect
PH # 5 >
ITEM: Left Pole Disconnect & Fuse Block
SOURCE: Disconnect: Line & load side discon-nect blade contact area.
Fuse Block: Line side fuse clip.
TEMP: Temp. of areas indicating a faulting condition range to:
73ºC / 163ºF Total Temp.
- 27ºC / 81ºF AOT
= 46ºC / 82ºF above AOT.
TH # 5 >
COMMENTS
Abnormal heat is being generated in fuse discon-nect components. See orange arrows in PH#5 and TH#5.
spect and re-secure serviceable components.
46°C / 82°F
TH # 5 >
No. Equipment Operating Visually Inspected
Fault #
BUILDING #1
OUTSIDE
1 XF-BLDG 1—1000 kVA Pad Mounted Transformer X
BASEMENT MECHANICAL ROOM
2 HVP-1—480/277 Volt Distribution Panel X
3 Overhead Square D 3ø Transformer X
4 Supply Fan #1—VFD Cabinet X
NORTH HALLWAY
5 Transformer EMHV1—75 kVA GE 3ø Transformer
MAIN ELECTRICAL ROOM #100
6 1200 Amp GE Switchgear Section 1—480/277 Volt Distribu-tion Panel
X
7 1200 Amp GE Switchgear Section 2—1200 Amp Circuit Breaker
X
8 Panel EMDP—208/120 Volt Distribution Panel X
9 Panel EMHV1—480/277 Volt Distribution Panel X
10 Panel EMLV—208/120 Volt Distribution Panel X
11 Panel LVDP—480/277 Volt Distribution Panel X
12 XFMR-T1—112.5 kVA GE 3ø Transformer
13 XFMR-T2—150 kVA GE 3ø Transformer
14 ATS-1—Automatic Transfer Switch (Utility Side Only) X
ROOM #105
15 Panel HLV1—480/277 Volt Distribution Panel X
16 Panel LVR1—208/120 Volt Distribution Panel X
ROOM #154
AREA/EQUIPMENT LIST
Following is a list of the electrical equipment located at the VA Medical Center Fort Roots, North Little Rock, Arkansas, facility and data relating to its operating condition at the time the scan was performed.
NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection.
Fault #
17 Panel LUR2—208/120 Volt Distribution Panel X
18 Panel HUR2—480/277 Volt Distribution Panel X
BUILDING #11
ROOM #106
19 Panel A—208/120 Volt Distribution Panel
20 Panel A-1—208/120 Volt Distribution Panel
BUILDING #26
OUTSIDE
21 XF-BLDG 26—225 kVA Pad Mounted Transformer X
MAIN ELECTRICAL ROOM
22 MDP—480/277 Volt Distribution Panel
23 ATS-26—Automatic Transfer Switch (Utility Side Only)
24 Panel E-1 Building 102 Computer Room—Molded Case Breaker
CARPENTRY SHOP
25 Panel B—208/120 Volt Distribution Panel
METAL SHOP
26 Panel D—208/120 Volt Distribution Panel
PAINT SHOP
27 Panel A—208/120 Volt Distribution Panel
BUILDING #32
BASEMENT
28 HVAC Panel—208/120 Volt Distribution Panel X
29 Panel A—208/120 Volt Distribution Panel X
30 Panel B—208/120 Volt Distribution Panel X
BUILDING #34
OUTSIDE
31 XF-BLDG 34—500 kVA Pad Mounted Transformer X
32 (Left) Unlabeled Molded Case Breaker X
33 (Right) Unlabeled Molded Case Breaker X
Fault #
BUILDING #36
OUTSIDE
34 XF-BLDG 34—500 kVA Pad Mounted Transformer X
BUILDING #37
INSIDE
35 Unlabeled 240/120 Volt Distribution Panel
36 MDP-1—480/277 Volt Distribution Panel
37 Panel A—208/120 Volt Distribution Panel
BASEMENT MAIN ELECTRICAL ROOM
38 I-T-E Switchboard—480/277 Volt Distribution Panel
39 Unlabeled 240/120 Volt Distribution Panel
40 Emergency Panel—480/277 Volt Distribution Panel
41 Panel A—480/277 Volt Distribution Panel
42 ATS-37—Automatic Transfer Switch (Utility Side Only)
43 Normal Power To ATS Switch—Molded Case Breaker
BUILDING #39
INSIDE
44 Panel MDP-1—240/120 Volt Distribution Panel
45 Unlabeled 240/120 Volt Distribution Panel
BUILDING #41
OUTSIDE
46 XF-BLDG 41—300 kVA Pad Mounted Transformer X
47 Junction Box
THE VAULT
48 41-MDP—208/120 Volt Distribution Panel X
49 Panel 1—208/120 Volt Distribution Panel X
50 Panel 2 / Computer Panel—208/120 Volt Distribution Panel X
51 Panel 3—208/120 Volt Distribution Panel X
52 Panel DP1—480/277 Volt Distribution Panel
Fault #
53 Panel DP2—480/277 Volt Distribution Panel
BUILDING #58
OUTSIDE
54 XF-BLDG 58A—500 kVA Pad Mounted Transformer X
55 XF-BLDG 58B—750 kVA Pad Mounted Transformer X
INSIDE
56 Panel A—240/120 Volt Distribution Panel
57 Panel B—240/120 Volt Distribution Panel
58 Panel B-P—240/120 Volt Distribution Panel
59 Panel DPA—480/277 Volt Distribution Panel
60 Panel DPB—480/277 Volt Distribution Panel
61 Panel DPL / Lights—480/277 Volt Distribution Panel
62 Panel DPP—480/277 Volt Distribution Panel
63 Panel EMB—208/120 Volt Distribution Panel
64 Panel EM—480/277 Volt Distribution Panel
65 Unlabeled 600 Amp Molded Case Breaker
66 AC #1—Molded Case Breaker
67 ATS-58—Automatic Transfer Switch (Utility Side Only)
68 Building 58 Generator Feed To Building 35 ATS—Molded Case Breaker
BUILDING #65
OUTSIDE
69 XF-BLDG 65A—225 kVA Pad Mounted Transformer X
70 XF-BLDG 65B—500 kVA Pad Mounted Transformer X
BASEMENT MAIN ELECTRICAL ROOM
71 2000 Amp GE Switchgear Section 1—Main 2000 Amp Cir-cuit Breaker
72 2000 Amp GE Switchgear Section 2—Chiller 800 Amp Cir-cuit Breaker
73 2000 Amp GE Switchgear Section 3—480/277 Volt Distribu-tion Panel
74 Panel E—208/120 Volt Distribution Panel
Fault #
75 Panel L&R DP—208/120 Volt Distribution Panel
BUILDING #66
OUTSIDE
76 XF-BLDG 66—500 kVA Pad Mounted Transformer X
BASEMENT
77 Unlabeled 240/120 Volt Distribution Panel X
78 Hot Water Heater—Fuse Disconnect X 5
79 HWP-3—Disconnect X
80 HWP-4—Fuse Disconnect X
81 CWP-5—VFD Cabinet X
82 CWP-6—VFD Cabinet X
83 MCC-PPB (Active Buckets Scanned Only)
ROOM #1A
84 Main Switchboard—480/277 Volt Distribution Panel X
85 Panel EDP—480/277 Volt Distribution Panel X
86 Panel HD/GE—480/277 Volt Distribution Panel X
87 75 kVA GE 3ø Transformer
88 T1—75 kVA Square D 3ø Transformer X
89 T2—30 kVA Square D 3ø Transformer X
90 T3—75 kVA Square D 3ø Transformer X
91 T4—45 kVA Square D 3ø Transformer X
92 ATS-66—Automatic Transfer Switch (Utility Side Only) X
ROOM #2C
93 Panel EL/BS—208/120 Volt Distribution Panel X
94 Panel H/BS—480/277 Volt Distribution Panel X
95 Panel L/BS—208/120 Volt Distribution Panel X
96 Panel L/BS-R—208/120 Volt Distribution Panel X
ROOM #61
97 Panel D/BN—208/120 Volt Distribution Panel X
98 Panel H/BN—480/277 Volt Distribution Panel
Fault #
99 Panel EL/BN—208/120 Volt Distribution Panel X
100 Panel G—208/120 Volt Distribution Panel X
101 Panel L/BN—208/120 Volt Distribution Panel X
102 Panel LD/GE—208/120 Volt Distribution Panel X
103 T5—75 kVA Square D 3ø Transformer X
OUTSIDE ROOM #61
104 66-RM-48—208/120 Volt Distribution Panel X
ROOM #106C
105 Panel H/1S—480/277 Volt Distribution Panel X
106 Panel L/1S—208/120 Volt Distribution Panel X
107 ETR/1S—75 kVA Westinghouse 3ø Transformer
108 XF-66-L1S—75 kVA Westinghouse 3ø Transformer
109 Unlabeled 100 Amp GE Fuse Disconnect X
ROOM #138
110 UH-1—Fuse Disconnect X
111 MCP-1 (Only Active Buckets) X
ROOM #158B
112 Panel EL/1N—208/120 Volt Distribution Panel X
113 Panel H/1N—480/277 Volt Distribution Panel X
114 Panel K—208/120 Volt Distribution Panel X
115 Panel L/1N—208/120 Volt Distribution Panel X
ROOM #205B
116 Panel AC—208/120 Volt Distribution Panel X
117 Panel EL/2S—208/120 Volt Distribution Panel X
118 Panel H/2S—480/277 Volt Distribution Panel X
119 Panel L/2S—208/120 Volt Distribution Panel X
120 Panel L/2S-R—208/120 Volt Distribution Panel X
ROOM #249C
121 Panel EL/2N—208/120 Volt Distribution Panel X
122 Panel H/2N—480/277 Volt Distribution Panel X
Fault #
123 Panel L/2N—208/120 Volt Distribution Panel X
124 Panel L/2N-R—208/120 Volt Distribution Panel X
BUILDING #68
OUTSIDE
125 XF-BLDG 68A—225 kVA Pad Mounted Transformer X
126 XF-BLDG 68B—500 kVA Pad Mounted Transformer X 4
BASEMENT MAIN ELECTRICAL ROOM
127 68A-MDP Switchgear Section 1—1600 Amp Circuit Breaker X
128 68A-MDP Switchgear Section 2—480/277 Volt Distribution Panel
X
129 68B MDP—480/277 Volt Distribution Panel X
130 Panel EL/1—208/120 Volt Distribution Panel X
131 XF-EL1—45 kVA Square D 3ø Transformer X
132 Unlabeled Junction Box X
133 ATS-68—Automatic Transfer Switch (Not In Service)
134 MDS—Fuse Disconnect X
135 Transformer Disconnect X
GROUND FLOOR HALLWAY
136 Panel EL/1A—208/120 Volt Distribution Panel X
137 Panel GM—208/120 Volt Distribution Panel (Locked)
138 Panel GN—208/120 Volt Distribution Panel X
139 Panel GN-A—208/120 Volt Distribution Panel X
140 Panel GS—208/120 Volt Distribution Panel (Locked)
ELECTRICAL CLOSET #10
141 Panel BPB—208/120 Volt Distribution Panel X
142 Panel BPB-2—208/120 Volt Distribution Panel X
143 Panel Kitchen—208/120 Volt Distribution Panel X
144 Panel NC—208/120 Volt Distribution Panel X
BUILDING #69
OUTSIDE
Fault #
145 XF-BLDG 69—225 kVA Pad Mounted Transformer X
BOILER AREA
146 Panel 2—208/120 Volt Distribution Panel X
147 Panel 3—208/120 Volt Distribution Panel X
148 Air Compressor 1—Motor Control X
149 Air Compressor 2—Motor Control X
150 Air Compressor 3—Motor Control X
151 Air Compressor Boiler 1—Disconnect X
152 Air Compressor Boiler 2—Disconnect X
153 Air Compressor Boiler 3—Disconnect X
154 Boiler 1—Control Cabinet X
155 Boiler 1—VFD Cabinet X
156 Boiler 2—Control Cabinet X
157 Boiler 2—VFD Cabinet
158 Boiler 3—Control Cabinet X
159 Boiler 3—VFD Cabinet
160 CRP-1—Control Cabinet X
161 DA-1—Control Cabinet X
162 Exhaust Fan 1—Combination Starter X
163 Exhaust Fan 2—Combination Starter X
164 Fuel Oil Pump 1—Combination Starter X
165 Fuel Oil Pump 2—Combination Starter X
166 Make-Up Air—Combination Starter X
167 Pump-1—Disconnect X
168 Pump-1—VFD Cabinet X
169 Pump-2—Disconnect X
170 Pump-2—VFD Cabinet X
171 Pump-3—Disconnect X
172 Sump Pump—Disconnect X
173 Surge Tank—Control Cabinet X
Fault #
COMPRESSOR ROOM
174 Air Compressor 1—Combination Starter X
175 Air Compressor 2—Combination Starter X
ELECTRICAL ROOM
176 Main Distribution Panel—208/120 Volt Distribution Panel X
177 Panel P1—208/120 Volt Distribution Panel X
178 UP Panel—208/120 Volt Distribution Panel X
179 ATS-69—Automatic Transfer Switch (Utility Side Only) X
180 Lighting Contactor—Lighting Contactor X
181 69-Main—Molded Case Breaker X
BUILDING #76
OUTSIDE
182 XF-BLDG 76—750 kVA Pad Mounted Transformer X
ADMINISTRATION HALLWAY
183 Panel P-4—208/120 Volt Distribution Panel X
BASEMENT HALLWAY
184 MDP—480/277 Volt Distribution Panel
185 Panel B-1—208/120 Volt Distribution Panel X
186 Panel PP—480/277 Volt Distribution Panel X
187 Panel PP-3—208/120 Volt Distribution Panel X
188 Panel PP-4—208/120 Volt Distribution Panel X
189 Feeds PP—Molded Case Breaker X
CHEMICAL ROOM
190 Chemical Room Panel—208/120 Volt Distribution Panel X
DINNER HALL
191 Panel 1A (Left)—208/120 Volt Distribution Panel X
192 Panel 1A (Right)—208/120 Volt Distribution Panel X
193 Panel 1B (Left)—208/120 Volt Distribution Panel X
194 Panel 1B (Right)—208/120 Volt Distribution Panel X
195 Panel D-1—208/120 Volt Distribution Panel X
Fault #
196 Panel K-1—208/120 Volt Distribution Panel X
197 Panel K-1B—208/120 Volt Distribution Panel X
FOOD STORAGE ROOM
198 Panel B4—208/120 Volt Distribution Panel X
KITCHEN
199 Panel 1B—208/120 Volt Distribution Panel X
200 Panel 2B—208/120 Volt Distribution Panel X
201 Panel LB—208/120 Volt Distribution Panel X
202 Panel P-2—208/120 Volt Distribution Panel X
203 Panel PP-2—208/120 Volt Distribution Panel X
ROOM #17A
204 76-Basement Switchgear—208/120 Volt Distribution Panel X
205 76-Main Switchgear Section 1—2000 Amp Circuit Breaker X
206 76-Main Switchgear Section 2—480/277 Volt Distribution Panel
X
207 76-MDP Switchgear Section 1—Panel PR 600 Amp Circuit Breaker & Main 1200 Amp Circuit Breaker
X
208 76-MDP Switchgear Section 2—480/277 Volt Distribution Panel
X
209 76-MDP Switchgear Section 3—480/277 Volt Distribution Panel
X
210 MCC-B76 (Active Only Scanned) X
ROOM #107
211 Panel LO—208/120 Volt Distribution Panel X
BUILDING #80
OUTSIDE
212 XF-BLDG 80—225 kVA Pad Mounted Transformer X
INSIDE
213 Unlabeled 480/277 Volt Distribution Panel X
214 Panel P-2—208/120 Volt Distribution Panel X
215 45 kVA Square D 3ø Transformer
216 ATS-80—Automatic Transfer Switch (Utility Side Only) X
Fault #
217 Test Equipment Transformer—Fuse Disconnect X
218 Water Heater—Disconnect X
ELEVATOR ROOM
219 Panel A—208/120 Volt Distribution Panel X
BUILDING #89
OUTSIDE
220 XF-BLDG 89A—225 kVA Pad Mounted Transformer X
221 XF-BLDG 89B—225 kVA Pad Mounted Transformer X
ROOM #102C
222 Panel EL/1A—208/120 Volt Distribution Panel X
ROOM #107
223 Panel SR—208/120 Volt Distribution Panel X
224 Unlabeled VFD Fuse Disconnect X
ROOM #108
225 89A-MDP—208/120 Volt Distribution Panel
226 Panel L1 Bottom—208/120 Volt Distribution Panel X
227 Panel L1 Top—208/120 Volt Distribution Panel X
ROOM #116
228 Emergency Panel—208/120 Volt Distribution Panel X
229 Panel HP1—480/277 Volt Distribution Panel X
230 Unlabeled 400 Amp GE Fuse Disconnect X
231 89A-SW—800 Amp Circuit Breaker X
232 Panel EL-1A Disconnect—Fuse Disconnect X
BUILDING #90
OUTSIDE
233 XF-BLDG 90—150 kVA Pad Mounted Transformer X
BUILDING #101
OUTSIDE
234 XF-BLDG 101—225 kVA Pad Mounted Transformer X
Fault #
ROOM #101
235 Panel DP—208/120 Volt Distribution Panel
236 Panel EP-1—208/120 Volt Distribution Panel
BUILDING #102
OUTSIDE
237 XF-BLDG 102A—500 kVA Pad Mounted Transformer X
238 XF-BLDG 102B—1000 kVA Pad Mounted Transformer X
239 Chiller-1—Disconnect X
240 Chiller-2—Disconnect X
241 Chiller-3—Disconnect X
242 Pump-1—Disconnect X
243 Pump-1—VFD Cabinet X
244 Pump-2—Disconnect X
245 Pump-2—VFD Cabinet X
BASEMENT MAIN ELECTRICAL ROOM
246 EMSB Switchgear Section 1—480/277 Volt Distribution Panel
X
247 EMSB Switchgear Section 2—Main Circuit Breaker X
248 MSB Switchgear Section 1—Incoming Service X
249 MSB Switchgear Section 2—1200 Amp Circuit Breaker X
250 MSB Switchgear Section 3—1200 Amp Circuit Breaker X
251 Panel A—208/120 Volt Distribution Panel X
252 Panel B—208/120 Volt Distribution Panel X
253 ATS-102—Automatic Transfer Switch (Utility Side Only) X
254 Air Compressor—Control Cabinet X
255 Air Compressor—Fuse Disconnect X
UPS ROOM #107
256 ESWB Switchgear Section 1—1600 Amp Circuit Breaker X
257 ESWB Switchgear Section 2—480/277 Volt Distribution Panel
X
Fault #
258 ESWB Switchgear Section 3—480/277 Volt Distribution Panel
X
259 UPS Bypass Switchgear A—480/277 Volt Distribution Panel X
260 UPS Bypass Switchgear B—480/277 Volt Distribution Panel X
261 Panel A1—208/120 Volt Distribution Panel X
262 Panel A2—208/120 Volt Distribution Panel X
263 Panel B1—208/120 Volt Distribution Panel X
264 Panel B2—208/120 Volt Distribution Panel X
265 Panel E1L1H—480/277 Volt Distribution Panel X
266 Panel E1L1L—208/120 Volt Distribution Panel X
267 T-A1—150 kVA Square D 3ø Transformer
268 T-A2—150 kVA Square D 3ø Transformer
269 T-B1—150 kVA Square D 3ø Transformer
270 T-B2—150 kVA Square D 3ø Transformer
271 T-E1L1L—30 kVA Square D 3ø Transformer
272 BCU-1—VFD Cabinet
273 BCU-2—VFD Cabinet
274 Cummins Automatic Transfer Switch (Utility Side Only) X
275 Portable Main—1600 Amp Circuit Breaker X
276 UPS-A—Control Cabinet
277 UPS-B—Control Cabinet
278 Utility Main—1600 Amp Circuit Breaker X
OUTSIDE UPS ROOM #107
279 Panel EDPI—208/120 Volt Distribution Panel X
280 AC-2—Fuse Disconnect X
MECHANICAL ROOM #117
281 Panel A—208/120 Volt Distribution Panel X
ROOM #132
282 Panel C—208/120 Volt Distribution Panel X
283 Panel UPS1—208/120 Volt Distribution Panel X
Fault #
OUTSIDE ROOM #132
284 Panel B—208/120 Volt Distribution Panel X
MECHANICAL ROOM #???
285 Panel 1HA—480/277 Volt Distribution Panel
286 Panel 1LA—208/120 Volt Distribution Panel
287 30 kVA Square D 3ø Transformer
BUILDING #103
OUTSIDE
288 XF-BLDG 103—300 kVA Pad Mounted Transformer X
DINING ROOM
289 Panel E—208/120 Volt Distribution Panel
290 Panel MDP—480/277 Volt Distribution Panel
ROOM #004
291 Panel LPB—208/120 Volt Distribution Panel
292 Panel PPB—208/120 Volt Distribution Panel
BUILDING #104
BASEMENT
293 MDP 104—480/277 Volt Distribution Panel
294 Building #192 Main Breaker—Molded Case Breaker
295 Panel PLB—208/120 Volt Distribution Panel
296 Panel HP1—208/120 Volt Distribution Panel
297 Panel HP2—208/120 Volt Distribution Panel
298 Cooling Tower Fan Combination Starter
299 Cooling Tower Spray Pump Combination Starter
300 Loop Pump P1 Combination Starter
301 Loop Pump P2 Combination Starter
1st FLOOR
302 Panel PL 1—208/120 Volt Distribution Panel
2nd FLOOR
303 Panel PL 2—208/120 Volt Distribution Panel
Fault #
ATTIC
304 Panel PL A—208/120 Volt Distribution Panel
305 AHU-1—Combination Starter
306 Attic Exhaust Fan—Combination Starter
BUILDING #105
OUTSIDE
307 XF-BLDG 105—225 KVA Pad Mounted Transformer X
BASEMENT
308 105-Lights—208/120 Volt Distribution Panel X
309 105-MDP—208/120 Volt Distribution Panel X
310 105-PNL(A)—208/120 Volt Distribution Panel X
311 105-PNL(B)—208/120 Volt Distribution Panel X
OUTSIDE BASEMENT
312 Kitchen 208/120 Volt Distribution Panel X
BUILDING #106
OUTSIDE
313 XF-BLDG 106—225 KVA Pad Mounted Transformer X
UNDER DECK
314 (East) Air Conditioning Unit—Fuse Disconnect X
315 (West) Air Conditioning Unit—Fuse Disconnect X
THE VAULT
316 I-T-E Switchgear Section 1—Terminal Connections
317 I-T-E Switchgear Section 2—600 Amp Switch
318 I-T-E Switchgear Section 3—480/277 Volt Distribution Panel
319 Panel PB1—208/120 Volt Distribution Panel
BUILDING #111
OUTSIDE
320 XF-BLDG 111—500 KVA Pad Mounted Transformer X
321 Chiller—Control Cabinet X
322 Chiller—Fuse Disconnect X
Fault #
MAIN ELECTRICAL ROOM
323 Emergency Panel 1—480/277 Volt Distribution Panel
324 111-PNL-P1—208/120 Volt Distribution Panel X
325 Power #2—208/120 Volt Distribution Panel X
326 Power #3—208/120 Volt Distribution Panel X
327 Lights—480/277 Volt Distribution Panel
328 ATS-111—Automatic Transfer Switch (Utility Side Only) X
329 Square D Switchgear Section 1—1600 Amp Circuit Breaker X
330 Square D Switchgear Section 2—480/277 Volt Distribution Panel
X
GARAGE
Bus 111 MCC
331 Incoming Main Lugs X
332 Spare (Not In Service)
333 Chill Water Pump X
334 Hot Water Pump X
335 Spare (Not In Service)
336 Air Handler X
337 Unlabeled X
338 Distribution Panel X
339 Blank (Not In Service)
340 Blank (Not In Service)
341 Blank (Not In Service)
BUILDING #115
OUTSIDE
342 XF-BLDG 115—225 KVA Pad Mounted Transformer X
VAULT
343 480 Panel—480/277 Volt Distribution Panel X
344 Panel PP1—208/120 Volt Distribution Panel X
345 Panel PP2—208/120 Volt Distribution Panel X
Fault #
346 Panel LP1—208/120 Volt Distribution Panel X
347 Panel LP2—208/120 Volt Distribution Panel X
348 I-T-E Switchgear Section 1—480/277 Volt Distribution Panel
349 I-T-E Switchgear Section 2—480/277 Volt Distribution Panel
350 XF-115-480-PRI—150 kVA GE 3ø Transformer
BUILDING #159
OUTSIDE
351 XF-BLDG 159A—750 KVA Pad Mounted Transformer X
352 XF-BLDG 159B—225 KVA Pad Mounted Transformer X
353 Condenser Fan—Fuse Disconnect X
354 Condenser Heater—Fuse Disconnect X
BASEMENT AIR COMPRESSOR ROOM
355 Panel LPB-2—480/277 Volt Distribution Panel
356 Panel RPB-2—208/120 Volt Distribution Panel
357 Air Compressor #1—Control Cabinet
358 Air Compressor #1—Fuse Disconnect
359 Air Compressor #2—Control Cabinet
360 Air Compressor #2—Fuse Disconnect
361 Cooling Tower—Control Cabinet
BASEMENT LINEN ROOM
362 Panel LPB-1—480/277 Volt Distribution Panel
363 Panel RPB-1—208/120 Volt Distribution Panel
BASEMENT MAIN ELECTRICAL ROOM
364 Panel LDP—480/277 Volt Distribution Panel
365 Panel MDP-1—480/277 Volt Distribution Panel
366 Panel MDP-2—480/277 Volt Distribution Panel
367 Panel RDP—208/120 Volt Distribution Panel
368 XF-159B-RDP—150 kVA Square D 3ø Transformer
LAUNDRY ROOM
369 Panel HP1—480/277 Volt Distribution Panel
Fault #
370 Panel HP2—480/277 Volt Distribution Panel
371 Panel HP3—480/277 Volt Distribution Panel
372 Panel HP4—480/277 Volt Distribution Panel
373 Panel LP1-1—480/277 Volt Distribution Panel
374 Panel RP1-1—208/120 Volt Distribution Panel
375 Panel RP1-2—208/120 Volt Distribution Panel
376 MCC #1 (No Access)
BUILDING #168
OUTSIDE
377 XF-BLDG 168—500 KVA Pad Mounted Transformer X
378 Unlabeled 208/120 Volt Distribution Panel X
BUILDING #169
379 13.8 KV Switchgear (Limited View Through Old View Ports) X
380 Entergy Management Panel—240/120 Volt Distribution Panel
X
BUILDING #170
OUTSIDE
381 XF-BLDG 170—750 KVA Pad Mounted Transformer X
382 Chiller #3 Switchboard—480/277 Volt Distribution Panel
ROOM #GA-001
383 Return Air Fan—VFD Cabinet X
384 Supply Air Fan—VFD Cabinet X
385 MCC-GA2 (Only Active Buckets) X
ROOM #GA-002
386 AH-11B Return Air Fan—VFD Cabinet X
387 AH-11B Supply Air Fan—VFD Cabinet X
388 MCC-GA1 (Only Active Buckets) X
ROOM #GA-107
389 Panel EL/GA—208/120 Volt Distribution Panel X
390 Panel H/GA—480/277 Volt Distribution Panel X
Fault #
391 Panel L/GA—208/120 Volt Distribution Panel X
392 ETR/GA—30 kVA Square D 3ø Transformer
393 TR/GA—45 kVA Square D 3ø Transformer
ROOM #GB-111
394 Circulating Pump—Motor Control X
395 Circulating Pump—Fuse Disconnect X
396 CP2—Fuse Disconnect (Not In Service)
397 Dental Air Compressor—Control Cabinet X
398 Dental Air Compressor—Fuse Disconnect X 1
399 Dental Vacuum—Control Cabinet
400 Dental Vacuum—Disconnect X
401 Domestic Water Pump—Control Cabinet
402 Return Fan #2—VFD Cabinet X
403 Return Fan #3—VFD Cabinet X
404 Return Fan #15—Disconnect X
405 Supply Fan #2—VFD Cabinet X
406 Supply Fan #3—Disconnect X
407 Supply Fan #3—VFD Cabinet X
408 Supply Fan #15—Disconect X
409 MCC-GB (Only Active Buckets) X
ROOM #GB-113
410 Panel D/GB—480/277 Volt Distribution Panel X
411 Panel ED/GB—480/277 Volt Distribution Panel X
412 Panel EL/GB—208/120 Volt Distribution Panel X
413 Panel EH/GB—480/277 Volt Distribution Panel X
414 Panel H/GB—480/277 Volt Distribution Panel X
415 Panel L/GB—208/120 Volt Distribution Panel X
416 Panel L/GB-1A—208/120 Volt Distribution Panel X
417 ED/GB—75 kVA Hevi-Duty 3ø Transformer
418 ETR/GB—30 kVA Square D 3ø Transformer
Fault #
419 TR/GB—30 kVA Square D 3ø Transformer
420 TR/GB-1A—30 kVA Square D 3ø Transformer
421 L2B-P—Fuse Disconnect X
422 Onan Automatic Transfer Switch (Utility Side Only) X
423 Outside Lights—Lighting Contactor X
ROOM #GB-114
424 Substation 1B Feeder F-3 (Limited View Through Old View Ports)
X
425 Substation 1B Feeder F-4 (Limited View Through Old View Ports)
X
426 Substation 1B Transformer (Limited View Through Old View Ports)
X
427 Substation 1B Switchgear (Limited View Through Old View Ports)
X
428 Substation 1A Feeder F-3 (Limited View Through Old View Ports)
X
429 Substation 1A Feeder F-4 (Limited View Through Old View Ports)
X
430 Substation 1A Transformer (Limited View Through Old View Ports)
X
431 Substation 1A Switchgear (Limited View Through Old View Ports)
X
ROOM #GE-103
432 Panel D/GF—480/277 Volt Distribution Panel X
433 Panel ED/GF—480/277 Volt Distribution Panel X
434 Panel EH/GF—480/277 Volt Distribution Panel X
435 Panel EL/GF—208/120 Volt Distribution Panel X
436 Panel H/GF—480/277 Volt Distribution Panel X
437 Panel L/GF-L—208/120 Volt Distribution Panel X
438 Panel L/GF-R—208/120 Volt Distribution Panel X
439 Panel MED-1—480/277 Volt Distribution Panel X
440 ETR/GF—30 kVA Square D 3ø Transformer
441 TR/GF—30 kVA Square D 3ø Transformer
442 ATS-GF—Automatic Transfer Switch (Utility Side Only) X
Fault #
ROOM #GE-118
443 Panel D/GE—480/277 Volt Distribution Panel X
444 Panel ED/GE—480/277 Volt Distribution Panel X
445 Panel EL/GE—208/120 Volt Distribution Panel X
446 Panel H/GE—480/277 Volt Distribution Panel X
447 Panel L/GE-A—208/120 Volt Distribution Panel X
448 Panel L/GE-B—208/120 Volt Distribution Panel X
449 ETR/GE—30 kVA Square D 3ø Transformer
450 TR/GE—225 kVA Square D 3ø Transformer
451 Unlabeled 200 Amp Square D Molded Case Breaker X
452 ATS-GE—Automatic Transfer Switch (Utility Side Only) X
453 MCC-GE (Only Active Buckets)
ROOM #GH-111
454 Panel D/GH—480/277 Volt Distribution Panel X
455 Panel ED/GH—480/277 Volt Distribution Panel X
456 Panel EH/GH—480/277 Volt Distribution Panel X
457 Panel EL/GH—208/120 Volt Distribution Panel X
458 Panel H/GH—480/277 Volt Distribution Panel X
459 Panel L/GH—208/120 Volt Distribution Panel X
460 ETR/GH—30 kVA Square D 3ø Transformer
461 TR/GH—45 kVA Square D 3ø Transformer
462 ATS-GH—Automatic Transfer Switch (Utility Side Only) X
463 Outside Lighting Contactor—Lighting Contactor X
464 Zenith—Junction Box X
ROOM #GJ-103
465 Panel D/GJ—480/277 Volt Distribution Panel X
466 Panel ED/GJ—480/277 Volt Distribution Panel X
467 Panel EH/GJ—480/277 Volt Distribution Panel X
468 Panel EL/GJ—208/120 Volt Distribution Panel X
469 Panel EL/GJ Sub Panel—208/120 Volt Distribution Panel X
Fault #
470 Panel H/GJ—480/277 Volt Distribution Panel X
471 Panel L/GJ-(L)—208/120 Volt Distribution Panel X
472 Panel L/GJ-(R)—208/120 Volt Distribution Panel X
473 ETR/GJ—30 kVA Square D 3ø Transformer
474 TR/GJ—75 kVA Square D 3ø Transformer
475 Unlabeled (Dock Leveler) 30 Amp Square D Fuse Discon-nect
X
476 Air Compressor #1—Control Cabinet X
477 Air Compressor #1—Fuse Disconnect X
478 Air Compressor #2—Control Cabinet X
479 Air Compressor #2—Fuse Disconnect X 3
480 Air Dryer 1—Fuse Disconnect (Not In Service)
481 Air Dryer 2—Fuse Disconnect (Not In Service)
482 ATS-GJ—Automatic Transfer Switch (Utility Side Only) X
483 BKDG 170 MC—Fuse Disconnect X
484 Chilled Water Return Chiller #1—VFD Cabinet X
485 Chilled Water Return Chiller #2—VFD Cabinet X
486 Chilled Water Return Standby—VFD Cabinet X
487 Chiller #1 Compressor #1—Control Cabinet X
488 Chiller #1 Compressor #2—Control Cabinet X
489 Chiller #1 Main—Molded Case Breaker X
490 Chiller #1 Secondary—Molded Case Breaker X
491 Chiller #2—Control Cabinet X
492 Chiller #2—Molded Case Breaker X
493 Chiller #2—PLC Control X
494 Chiller #2 C1—VFD Cabinet X
495 Chiller #2 C2—VFD Cabinet X
496 Chiller #2 C3—VFD Cabinet X
497 Chiller #3—Control Cabinet (Not In Service)
498 Chiller #3—Operator Console (Not In Service)
Fault #
499 CHWP24—Fuse Disconnect X
500 CHWP24—VFD Cabinet X
501 Domestic Water Pumps P-1/P-2/P-3—Control Cabinet X
502 Electric Fire Pump Controller—Control Cabinet X
503 Fire Pump Power Transfer Switch—Automatic Transfer Switch (Utility Side Only)
X
504 GJ103 Exhaust Fan—Disconnect X
505 GJ103A—Fuse Disconnect (Not In Service)
506 Medical Air Compressors #1 & #2—Control Cabinet
507 Medical Vacuum #1 Quincy QSVB7.5—Control Cabinet X
508 Medical Vacuum #1 Quincy QSVB7.5—Fuse Disconnect X
509 Medical Vacuum #2 Quincy QSVB10—Control Cabinet X
510 Medical Vacuum #2 Quincy QSVB10—Fuse Disconnect X
511 P-1 / Heating Hot Water Pump—VFD Cabinet X
512 P-2 / Heating Hot Water Pump—VFD Cabinet X
513 P-3 / Secondary Chill Water Pump—Control Cabinet
514 P-3 / Secondary Chill Water Pump—Fuse Disconnect X
515 P-3 / Secondary Chill Water Pump—VFD Cabinet X
516 P-4 / Secondary Chill Water Pump—Control Cabinet
517 P-4 / Secondary Chill Water Pump—Fuse Disconnect X
518 P-4 / Secondary Chill Water Pump—VFD Cabinet X
519 P-17 / Hot Water Pump—Fuse Disconnect X
520 P-17A / Hot Water Pump—Fuse Disconnect X
521 P-19 / Jockey Pump—Combination Starter X
522 P-22—Fuse Disconnect X
523 P-26 / Chill Water Pump Building 159—Fuse Disconnect X
524 P-26 / Chill Water Pump Building 159—VFD Cabinet X
525 Whirlpool At Pool—Molded Case Breaker X
526 EMCC-GJ (Only Active Buckets) X
527 MCC-2 (Only Active Buckets) X
Fault #
ROOM #GJ-104
528 Substation 2A Feeder F-3 (Limited View Through Old View Ports)
X
529 Substation 2A Feeder F-4 (Limited View Through Old View Ports)
X
530 Substation 2B Feeder F-3 (Limited View Through Old View Ports)
X
531 Substation 2B Feeder F-4 (Limited View Through Old View Ports)
X
532 Substation 2A Switchgear (Limited View Through Old View Ports)
X
533 Substation 2B Switchgear (Limited View Through Old View Ports)
X
534 Substation 2A Transformer (Limited View Through Old View Ports)
X
535 Substation 2B Transformer (Limited View Through Old View Ports)
X
536 Substation 3 Feeder F-1 (No View Ports)
537 Substation 3 Feeder F-2 (No View Ports)
538 Substation 3 Switchgear (Limited View Through Old View Ports)
X
539 Substation 3 Transformer (Limited View Through Old View Ports)
X
540 Panel D/PC—480/277 Volt Distribution Panel X
541 Fire Pump Switch—Molded Case Breaker X
ROOM #GK-102
542 Panel ED/GM—480/277 Volt Distribution Panel X
543 Panel EH/GM—480/277 Volt Distribution Panel X
544 Panel EL/GM—208/120 Volt Distribution Panel X
545 Panel EL/GM-Sub—208/120 Volt Distribution Panel X
546 Panel D/GM—480/277 Volt Distribution Panel X
547 Panel H/GM—480/277 Volt Distribution Panel X
548 Panel L/GM—208/120 Volt Distribution Panel X
549 ETR/GM—30 kVA Square D 3ø Transformer
550 TR/GM—75 kVA Square D 3ø Transformer
Fault #
551 ATS-GM—Automatic Transfer Switch (Utility Side Only) X
ROOM #GK-105
552 Panel D/GK—480/277 Volt Distribution Panel X
553 Panel ED/GK—480/277 Volt Distribution Panel X
554 Panel EL/GK—208/120 Volt Distribution Panel X
555 Panel EL2/GK—208/120 Volt Distribution Panel X
556 Panel H2/GK—480/277 Volt Distribution Panel X
557 Panel L/GK—208/120 Volt Distribution Panel X
558 Panel L2/GK—208/120 Volt Distribution Panel X
559 ETR/GK—30 kVA Square D 3ø Transformer
560 TL2/GK—75 kVA Square D 3ø Transformer
561 TR-EL2/GK—45 kVA Square D 3ø Transformer
562 TR/GK—30 kVA Square D 3ø Transformer
563 TR/GN—45 kVA Square D 3ø Transformer
564 Electrical Junction Cabinet—Junction Box X
565 MK-ATS-GK—Automatic Transfer Switch (Utility Side Only) X
566 MCCMCP-G/K (Only Active Buckets) X
ROOM #GK-109
567 Panel MED-2—480/277 Volt Distribution Panel X
568 Block Heater—Disconnect X
569 Generator—Control Cabinet X
570 Generator—Molded Case Breaker
ROOM #GL-101
571 L.P. #1—208/120 Volt Distribution Panel X
572 L.P. #2—208/120 Volt Distribution Panel X
ROOM #GL-116
573 Panel D/GL—480/277 Volt Distribution Panel X
574 Panel ED/GL—480/277 Volt Distribution Panel X
575 Panel EH/GL—480/277 Volt Distribution Panel X
576 Panel EL/GL—208/120 Volt Distribution Panel X
Fault #
577 Panel H/GL—480/277 Volt Distribution Panel X
578 Panel L/GL-A—208/120 Volt Distribution Panel X
579 Panel L/GL-B—208/120 Volt Distribution Panel X
580 Panel L/GL-C—208/120 Volt Distribution Panel X
581 Panel L/GL-D—208/120 Volt Distribution Panel X
582 ETR/GL—30 kVA Square D 3ø Transformer
583 TR/GL—Overhead Square D 3ø Transformer
584 ATS-GL—Automatic Transfer Switch (Utility Side Only) X
ROOM #GN-108
585 Panel L/GN—208/120 Volt Distribution Panel X
ROOM #GN-109
586 Return Fan #13—Fuse Disconnect X
587 Return Fan #13—VFD Cabinet X
588 Supply Fan #13—Fuse Disconnect X
589 Supply Fan #13—VFD Cabinet X
ROOM #1A-002
590 Unlabeled 208/120 Volt Distribution Panel X
591 30 kVA Square D 3ø Transformer
592 Unlabeled Square D Motor Control (Not In Service)
593 AH11C Return Fan—VFD Cabinet X
594 AH11C Supply Fan—VFD Cabinet X
ROOM #1A-003
595 AH11D Return Fan—Fuse Disconnect X
596 AH11D Return Fan—VFD Cabinet X
597 AH11D Supply Fan—Fuse Disconnect X
598 AH11D Supply Fan—VFD Cabinet X
ROOM #1B-142
599 Panel EL/1B—208/120 Volt Distribution Panel X
600 Panel L/1B-L—208/120 Volt Distribution Panel X
601 Panel L/1B-R—208/120 Volt Distribution Panel X
Fault #
602 ETR/1B—30 kVA Square D 3ø Transformer
603 TR/1B—30 kVA Square D 3ø Transformer
ROOM #1C-142
604 Panel EL/1C—208/120 Volt Distribution Panel X
605 Panel L/1C-L—208/120 Volt Distribution Panel X
606 Panel L/1C-R—208/120 Volt Distribution Panel X
607 ETR/1C—30 kVA Square D 3ø Transformer
608 TR/1C—30 kVA Square D 3ø Transformer
ROOM #1D-142
609 Panel EL/1D—208/120 Volt Distribution Panel X
610 Panel L/1D-L—208/120 Volt Distribution Panel X
611 Panel L/1D-R—208/120 Volt Distribution Panel X
612 ETR/1D—30 kVA Square D 3ø Transformer
613 TR/1D—30 kVA Square D 3ø Transformer
ROOM #1D-173
614 1200 Amp Square D 480/277 Volt Distribution Panel X
615 Unlabeled (Heater) 30 Amp Disconnect X
616 AIR-COMP—Fuse Disconnect X
617 Emergency Generator—Control Cabinet X
618 Emergency Generator—Junction Box X
619 Emergency Generator—Molded Case Breaker X
620 Heater—Fuse Disconnect X
ROOM #1E-142
621 Panel EL/1E—208/120 Volt Distribution Panel X
622 Panel L/1E-L—208/120 Volt Distribution Panel X
623 Panel L/1E-R—208/120 Volt Distribution Panel X
624 ETR/1E—30 kVA Square D 3ø Transformer
625 TR/1E—30 kVA Square D 3ø Transformer
ROOM #1F-111
626 Panel EL/1F—208/120 Volt Distribution Panel X
Fault #
627 Panel EH/1F—480/277 Volt Distribution Panel X
628 Panel H/1F—480/277 Volt Distribution Panel X
629 Panel L/1F—208/120 Volt Distribution Panel X
630 ETR/1F—30 kVA Square D 3ø Transformer
631 TR/1F—30 kVA Square D 3ø Transformer
ROOM #1G-104
632 Panel L/1G—208/120 Volt Distribution Panel X
633 Panel L/1GA—208/120 Volt Distribution Panel X
634 TR/1G—30 kVA Square D 3ø Transformer
635 TR/1G-A—30 kVA Square D 3ø Transformer
636 TR1G-A—Disconnect X
ROOM #1H-140
637 Panel EL/1H—208/120 Volt Distribution Panel X
638 Panel L/1H-L—208/120 Volt Distribution Panel X
639 Panel L/1H-R—208/120 Volt Distribution Panel X
640 ETR/1H—30 kVA Square D 3ø Transformer
641 TR/1H—30 kVA Square D 3ø Transformer
ROOM #1J-140
642 Panel EL/1J—208/120 Volt Distribution Panel X
643 Panel L/1J-L—208/120 Volt Distribution Panel X
644 Panel L/1J-R—208/120 Volt Distribution Panel X
645 ETR/1J—30 kVA Square D 3ø Transformer
646 TR/1J—30 kVA Square D 3ø Transformer
ROOM #1K-140
647 Panel EL/1K—208/120 Volt Distribution Panel X
648 Panel L/1K-L—208/120 Volt Distribution Panel X
649 Panel L/1K-R—208/120 Volt Distribution Panel X
650 ETR/1K—30 kVA Square D 3ø Transformer
651 TR/1K—30 kVA Square D 3ø Transformer
ROOM #1L-140
Fault #
652 Panel EL/1L—208/120 Volt Distribution Panel X
653 Panel L/1L-L—208/120 Volt Distribution Panel X
654 Panel L/1L-R—208/120 Volt Distribution Panel X
655 ETR/1L—30 kVA Square D 3ø Transformer
656 TR/1L—30 kVA Square D 3ø Transformer
ROOM #1M-113
657 Panel EH/1M—480/277 Volt Distribution Panel X
658 Panel EL/1M—208/120 Volt Distribution Panel X
659 Panel H/1M—480/277 Volt Distribution Panel X
660 Panel L/1M—208/120 Volt Distribution Panel X
661 ETR/1M—30 kVA Square D 3ø Transformer
662 TR/1M—30 kVA Square D 3ø Transformer
ROOM #2A-002
663 AH11E Return Fan—Fuse Disconnect X
664 AH11E Return Fan—VFD Cabinet X
665 AH11E Supply Fan—Fuse Disconnect X
666 AH11E Supply Fan—VFD Cabinet X
ROOM #2A-003
667 AH11F Return Fan—Fuse Disconnect X
668 AH11F Return Fan—VFD Cabinet X
669 AH11F Supply Fan—Fuse Disconnect X
670 AH11F Supply Fan—VFD Cabinet X
ROOM #2B-140
671 Panel EL/2B—208/120 Volt Distribution Panel X
672 Panel EL/2B-B—208/120 Volt Distribution Panel X
673 Panel EL/2B-C—208/120 Volt Distribution Panel X
674 Panel L/2B—208/120 Volt Distribution Panel X
675 Panel L/2B-A—208/120 Volt Distribution Panel X
676 Panel LDP/2B—480/277 Volt Distribution Panel X
677 ETR/2B—30 kVA Square D 3ø Transformer
Fault #
678 TR/2B—112.5 kVA Square D 3ø Transformer
679 TR/2B Washer—30 kVA Square D 3ø Transformer (Not In Service)
680 Service Disconnect—Disconnect X
ROOM #2C-140
681 Panel EL/2C—208/120 Volt Distribution Panel X
682 Panel L/2C-L—208/120 Volt Distribution Panel X
683 Panel L/2C-R—208/120 Volt Distribution Panel X
684 ETR/2C—30 kVA Square D 3ø Transformer
685 TR/2C—30 kVA Square D 3ø Transformer
ROOM #2D-140
686 Panel EL/2D—208/120 Volt Distribution Panel X
687 Panel L/2D-L—208/120 Volt Distribution Panel X
688 Panel L/2D-R—208/120 Volt Distribution Panel X
689 ETR/2D—30 kVA Square D 3ø Transformer
690 TR/2D—30 kVA Square D 3ø Transformer
ROOM #2E-140
691 Panel EL/2E—208/120 Volt Distribution Panel X
692 Panel L/2E-L—208/120 Volt Distribution Panel X
693 Panel L/2E-R—208/120 Volt Distribution Panel X
694 ETR/2E—30 kVA Square D 3ø Transformer
695 TR/2E—30 kVA Square D 3ø Transformer
ROOM #2F-116
696 Panel EH/2F—480/277 Volt Distribution Panel X
697 Panel EL/2F—208/120 Volt Distribution Panel X
698 Panel H/2F—480/277 Volt Distribution Panel X
699 Panel L/2F—208/120 Volt Distribution Panel X
700 ETR/2F—30 kVA Square D 3ø Transformer
701 TR/2F—30 kVA Square D 3ø Transformer
ROOM #2G-111A
Fault #
702 Panel L/2G—208/120 Volt Distribution Panel X
703 TR/2G—30 kVA Square D 3ø Transformer
ROOM #2H-140
704 Panel EL/2H—208/120 Volt Distribution Panel X
705 Panel L/2H-L—208/120 Volt Distribution Panel X
706 Panel L/2H-R—208/120 Volt Distribution Panel X
707 ETR/2H—30 kVA Square D 3ø Transformer
708 TR/2H—30 kVA Square D 3ø Transformer
ROOM #2J-140
709 Panel EL/2J—208/120 Volt Distribution Panel X
710 Panel L/2J-L—208/120 Volt Distribution Panel X
711 Panel L/2J-R—208/120 Volt Distribution Panel X
712 ETR/2J—30 kVA Square D 3ø Transformer
713 TR/2J—30 kVA Square D 3ø Transformer
ROOM #2K-140
714 Panel EL/2K—208/120 Volt Distribution Panel X
715 Panel L/2K-L—208/120 Volt Distribution Panel X
716 Panel L/2K-R—208/120 Volt Distribution Panel X
717 ETR/2K—30 kVA Square D 3ø Transformer
718 TR/2K—30 kVA Square D 3ø Transformer
ROOM #2L-140
719 Panel EL/2L—208/120 Volt Distribution Panel X
720 Panel L/2L-L—208/120 Volt Distribution Panel X
721 Panel L/2L-R—208/120 Volt Distribution Panel X
722 ETR/2L—30 kVA Square D 3ø Transformer
723 TR/2L—30 kVA Square D 3ø Transformer
ROOM #2M-113
724 Panel EH/2M—480/277 Volt Distribution Panel X
725 Panel EL/2M—208/120 Volt Distribution Panel X
726 Panel H/2M—480/277 Volt Distribution Panel X
Fault #
727 Panel L/2M—208/120 Volt Distribution Panel X
728 ETR/2M—30 kVA Square D 3ø Transformer
729 TR/2M—30 kVA Square D 3ø Transformer
ROOM #2N-107
730 Panel L/2N—208/120 Volt Distribution Panel X
731 TR/2N—30 kVA Square D 3ø Transformer
ROOM #3A-002
732 AH11G Return Fan—Fuse Disconnect X
733 AH11G Return Fan—VFD Cabinet X
734 AH11G Supply Fan—Fuse Disconnect X
735 AH11G Supply Fan—VFD Cabinet X
ROOM #3B-121
736 Panel EL/3B—208/120 Volt Distribution Panel X
737 Panel L/3B-L—208/120 Volt Distribution Panel X
738 Panel L/3B-R—208/120 Volt Distribution Panel X
739 ETR/3B—30 kVA Square D 3ø Transformer
740 TR/3B—30 kVA Square D 3ø Transformer
ROOM #3C-140
741 Panel EL/3C—208/120 Volt Distribution Panel X
742 Panel L/3C-L—208/120 Volt Distribution Panel X
743 Panel L/3C-R—208/120 Volt Distribution Panel X
744 ETR/3C—30 kVA Square D 3ø Transformer
745 TR/3C—30 kVA Square D 3ø Transformer
ROOM #3D-140
746 Panel EL/3D—208/120 Volt Distribution Panel X
747 Panel L/3D-L—208/120 Volt Distribution Panel X
748 Panel L/3D-R—208/120 Volt Distribution Panel X
749 ETR/3D—30 kVA Square D 3ø Transformer
750 TR/3D—30 kVA Square D 3ø Transformer
ROOM #3E-140
Fault #
751 Panel EL/3E—208/120 Volt Distribution Panel X
752 Panel L/3E-L—208/120 Volt Distribution Panel X
753 Panel L/3E-R—208/120 Volt Distribution Panel X
754 ETR/3E—30 kVA Square D 3ø Transformer
755 TR/3E—30 kVA Square D 3ø Transformer
ROOM #3F-116
756 Panel EH/3F—480/277 Volt Distribution Panel X
757 Panel EL/3F—208/120 Volt Distribution Panel X
758 Panel H/3F—480/277 Volt Distribution Panel X
759 Panel L/3F—208/120 Volt Distribution Panel X
760 ETR/3F—30 kVA Square D 3ø Transformer
761 TR/3F—30 kVA Square D 3ø Transformer
ROOM #3G-113A
762 Panel EL/3G—208/120 Volt Distribution Panel X
763 Panel L/3G—208/120 Volt Distribution Panel X
764 Panel L/3G-2—208/120 Volt Distribution Panel X
765 ETR/3G—30 kVA Square D 3ø Transformer
766 TR/3G—30 kVA Square D 3ø Transformer
ROOM #3H-140
767 Panel EL/3H—208/120 Volt Distribution Panel X
768 Panel L/3H-L—208/120 Volt Distribution Panel X
769 Panel L/3H-R—208/120 Volt Distribution Panel X
770 ETR/3H—30 kVA Square D 3ø Transformer
771 TR/3H—30 kVA Square D 3ø Transformer
ROOM #3J-140
772 Panel EL/3J—208/120 Volt Distribution Panel X
773 Panel L/3J-L—208/120 Volt Distribution Panel X
774 Panel L/3J-R—208/120 Volt Distribution Panel X
775 ETR/3J—30 kVA Square D 3ø Transformer
776 TR/3J—30 kVA Square D 3ø Transformer
Fault #
ROOM #3K-140
777 Panel EL/3K—208/120 Volt Distribution Panel X
778 Panel L/3K-L—208/120 Volt Distribution Panel X
779 Panel L/3K-R—208/120 Volt Distribution Panel X
780 ETR/3K—30 kVA Square D 3ø Transformer
781 TR/3K—30 kVA Square D 3ø Transformer
ROOM #3L-140
782 Panel EL/3L—208/120 Volt Distribution Panel X
783 Panel L/3L-L—208/120 Volt Distribution Panel X
784 Panel L/3L-R—208/120 Volt Distribution Panel X
785 ETR/3L—30 kVA Square D 3ø Transformer
786 TR/3L—30 kVA Square D 3ø Transformer
ROOM #3M-113
787 Panel EH/3M—480/277 Volt Distribution Panel X
788 Panel EL/3M—208/120 Volt Distribution Panel X
789 Panel H/3M—480/277 Volt Distribution Panel X
790 Panel L/3M—208/120 Volt Distribution Panel X
791 ETR/3M—30 kVA Square D 3ø Transformer
792 TR/3M—30 kVA Square D 3ø Transformer
ROOM #3N-107
793 Panel L/3N—208/120 Volt Distribution Panel X
794 TR/3N—30 kVA Square D 3ø Transformer
PENTH…