This solicitation is for electrical system preventive maintenance and testing services at two VA medical centers in Little Rock and North Little Rock, Arkansas. Interested parties must be veteran-owned small businesses and registered in SAM and VIP databases by the August 22nd deadline for submitting any questions. Quotes are due by August 29th and must include pricing, certifications, and representations. A mandatory site visit will be held on August 18th at noon at the North Little Rock facility, after which attendees may view the Little Rock location. The services sought include preventive maintenance, testing, repair, and emergency services for electrical systems at the two medical centers.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs North Little Rock Veterans Affairs Medical Center
North Little Rock, Arkansas
VISN 16
ELECTRICAL DISTRIBUTION
SYSTEM CONDITION ASSESSMENT
Study Update
Prepared by:
E.K. FOX & ASSOCIATES, LTD.
CONSULTING ENGINEERS
4500 Southgate Place, Suite 800, Chantilly, VA 20151
July 31, 2020
36C25622Q1188 0001 Exhibit M
North Little Rock VAMC – North Little Rock, Arkansas Electrical Condition Assessment - Update
Prepared for: Dept. of Veterans Affairs Page 1 Prepared by: E.K. Fox & Associates, Ltd.
4500 Southgate Place, Suite 800 Chantilly, VA 20151
TABLE OF CONTENTS
1. EXECUTIVE SUMMARY
2. INTRODUCTION
2.1. Personnel
2.2. Calculation Methods
2.3. Study Assumptions
3. FAULT CURRENT ANALYSIS
3.1. Introduction
3.2. Sources of Fault Current
3.3. Calculation Scenarios
3.4. SKM Power*Tools Input Data Reports
3.5. Short Circuit Calculation Results
3.6. Equipment Evaluation Results
4. PROTECTIVE DEVICE COORDINATION STUDY
4.1. Introduction
4.2. Existing and Proposed Protective Device Settings
4.3. Underrated Feeders
4.4. Replacement System Components
4.5. Analysis and Recommendations
4.6. Time-Current Characteristic Graphs Descriptions and Analysis
4.7. Time-Current Characteristic Graphs
5. ARC FLASH HAZARD ANALYSIS
5.1. Introduction
5.2. Basis of Study
5.3. Disclaimer
5.4. Results
APPENDICES
A. One-Line Diagrams
Prepared for: Dept. of Veterans Affairs Section 1 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
1. EXECUTIVE SUMMARY
In 2015, The Department of Veterans Affairs – Office of Construction and Facilities Management (CFM), commissioned E.K. Fox and Associates, Ltd. (EKFox) to perform the electrical system condition assessment of the North Little Rock Veterans Affairs Medical Center (VAMC). The scope of the assessment was to provide short circuit analysis, protective device coordination study, voltage drop analysis, arc flash hazard analysis, and equipment condition assessment with the purpose of improving the safety and reliability of the electrical distribution system. The report containing the findings and recommended corrections was delivered to the VA CFM and the VAMC in 2016.
The findings and recommended corrections addressed numerous issues that ranged from safety and code related items, to coordination adjustments to reduce nuisance trips, and equipment replacement to address aging or damaged equipment. Safety related items are a higher priority and require a more immediate response whereas some coordination and condition-related equipment replacements allow for more flexibility in how soon they need to be addressed.
Currently, Cornerstone Contracting, Inc. (CCI) is implementing the recommended corrections based on findings from the previous study. Based on the project scope of work (SOW), the equipment replacements and adjustments being provided by CCI are primarily to address the previous coordination adjustments and equipment condition-related findings. However, the CCI SOW does not cover all of the recommended corrective actions that were in the previous study.
EKFox has been tasked with providing an update to the original report and analyses. In lieu of a new complete site survey, EKFox has performed the analyses using input from CCI, the VA, and equipment vendors to update the software model and electrical analyses. In some cases, certain assumptions were necessary to perform the report updates. These assumptions have been detailed in Section 2. Also, the SOW does not specifically state if all of the other recommended corrections had been performed under a previous effort. For example, it is likely that the higher priority activity of replacing the “failed” circuit breakers identified in the device evaluation would have been accomplished under a separate, nearer-term effort. Therefore, we have taken the more conservative approach to re-report these findings, which can then be field verified to determine if they have already been addressed or are still needing correction.
Our updated short circuit analysis, which aims to identify if circuit breakers can safely interrupt the fault current due to a short, has currently shown eleven (11) overcurrent protection devices (OCPD’s) have failed the device evaluation for interrupting capacity. However, it is possible that some or all of these failed devices have been replaced since the original study with ones that meet the required ratings. These eleven (11) OCPD’s were also reported as failed in the previous study. No new failed devices were identified in the current study. Section 3 of this report has additional details.
The updated protective device coordination study uses the current fixed and adjustable settings of the existing OCPD’s to graphically display how those devices will respond to a short or overload event. The settings are then adjusted to allow the protective device closest to the fault to interrupt the circuit thereby minimizing the disruption of electrical service. Our study currently identifies ten
(10) OCPD’s that may require settings adjustment or replacement to either better coordinate
Prepared for: Dept. of Veterans Affairs Section 1 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
with other OCPD’s or to provide the correct level of protection for downstream conductors. Some of these current recommendations are due to the fact that adjustment and replacement certain OCPD’s was recommended in the previous coordination study but did not seem to appear in the CCI SOW. There are five (5) new, recommended adjustments that are due to the fact that some of the new replacement panels in Building 170 have circuit breakers that have slightly different trip curves than what was used for the previous coordination study. Additional details can be found in Section 4: Protective Device Coordination Study. We also include the time/current characteristic (TCC) graphs, which that show the interaction of the OCPD’s with the existing and recommended settings applied, in Section 4.
Finally, we performed an updated arc flash hazard analysis to determine the incident energy released by an arcing fault at the location of each device in the electrical distribution system. This analysis is also used to determine safe working distances and the required personal protective equipment (PPE) for personnel working in the panel. The results show a total of one (1) bus in Building 170 and thirty-three (33) buses for the secondary buildings that have an incident energy level at or above 40 cal/cm2. It should be noted that the majority of these buses are located at the secondaries of the service transformers to the buildings. EKFox will also provide an updated set of arc flash labels that can be applied to the panels and equipment to warn of the potential electrical dangers.
Additional details of the arc flash analysis can be found in Section 5.
Prepared for: Dept. of Veterans Affairs Section 2 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
2. INTRODUCTION
2.1. Personnel
The EKFox Team that produced this report consisted of highly skilled engineers and technicians. They were:
Raleigh Stewart, P.E. RDStewart@ekfox.com (703-267-6783)
Charles Sisung, P.E. CFSisung@ekfox.com (877-520-4771 x105)
Jarrett Elliott JCElliott@ekfox.com
Tasha Laura TJLaura@ekfox.com
2.2. Calculation Methods
As mentioned, this study includes the following elements: short circuit calculations, overcurrent protective device coordination, voltage drop analysis, arc flash hazard analysis, and a condition assessment of electrical equipment.
All calculations have been performed using software developed by SKM Systems Analysis, Inc. The software is named Power*Tools, Version 9.0.0.3 and it is a modular assembly of programs. The following modules have been used for this study:
System Model Development DAPPER Short Circuit Calculations Comprehensive Fault Evaluation Protective Device Coordination CAPTOR Voltage Drop Analysis DAPPER Arc Flash Hazard Analysis Arc Flash Evaluation Device Evaluation Equipment Evaluation
Version 9.0.0.3 of the Power*Tools software has been used for all of the calculations presented throughout this report. Additional information related to this software package can be found at www.skm.com.
2.3. Study Assumptions
The EKFox team has attempted, to the extent practical, to provide accurate updates for the previous study. In some cases, certain assumptions had to be made as a compromise between the project scope, available and provided equipment information, and required inputs to the software model. The following describes types of data that has been assumed for the purposes of this study:
Prepared for: Dept. of Veterans Affairs Section 2 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
2.3.1. Utility Information
Updated utility fault current information and system parameters were not provided for this analysis. As such, the utility information used in the previous study has been used for these analyses.
2.3.2. Replacement System Components
When complete equipment information was provided for a replacement system component, the model was updated to reflect this information. For items where some information was missing (e.g. breaker type, trip setting, etc.) The previous survey information, previous proposed study recommendation, or engineering judgment was used to fill in the missing information. In cases where the information for a replacement component (e.g. a larger ampacity breaker replacing a smaller ampacity breaker with no change to conductor size) conflicted with the original surveyed information (or introduced a new code or safety related issue), it was assumed that the replacement would have been adjusted or substituted to match the original equipment size or setting.
2.3.3. Previous Study Coordination Recommendations
The current study assumes that all of the previous study recommended coordination changes and replacements have been applied to the system. The updated coordination study has been accomplished by coordinating the replacement system components with the results from the previous coordination study.
2.3.4. Previous Study Device Evaluation Analysis
It is likely that some of the devices that failed the previous fault current and device evaluation analyses have been replaced prior to this project. However, the device parameters were not updated unless equipment information was provided to do so. Thus, devices that failed the current device evaluation should be field verified to determine if they were replaced as part of a previous effort or that the device requires immediate replacement.
2.3.5. Newly Added Equipment or Areas
The scope of equipment and areas for the present study only includes the equipment and areas that were part of the previous study. No equipment or survey information was provided for any newly added equipment or areas, so they have not been considered in this study.
Prepared for: Dept. of Veterans Affairs Section 3 Page 1 Prepared by: E.K. Fox & Associates, Ltd.
3. FAULT CURRENT ANALYSIS
3.1. Introduction
The fault current analysis is developed based on data for the North Little Rock VAMC electrical distribution system. The analysis examines the short circuit currents that occur at selected locations in the electrical system and is used to determine the capability of the system to withstand an electrical fault without damage.
Due to the size and complexity of Patient Building #170 and the overall campus, the original electrical studies were performed with separate SKM project models – one (1) for Building #170 and one (1) for the secondary buildings (i.e. the buildings for the rest of the campus).
The present study update has kept this separation between the two (2) projects.
One-line diagrams of the system are included in Appendix A. Reports showing the complete input data used to construct each model are included in Section 3.4.
3.2. Sources of Fault Current
The short circuit fault current calculations performed for the North Little Rock VAMC electrical system are based on the available fault current information that was originally obtained from the utility (City of North Little Rock Electrical Department) for the original study.
In summary, the available fault current from the City of North Little Rock system is:
Supply from Source 1 Feeder (Westgate Substation):
Max Fault 3phase: 2773.2 A Max Fault 3phase to Ground: 2773.2 A Max Fault Phase to Phase: 2401.7 A Max Fault 2 phases to Ground: 2552.5 A Max Fault Phase to Ground: 1995.0 A Min Fault: 191.7 A
Transformer: 18 MVA base, %Z=9.45, Primary 115kV Transmission (Delta) Secondary 13.8kV Y-grounded
Prepared for: Dept. of Veterans Affairs Section 3 Page 2 Prepared by: E.K. Fox & Associates, Ltd.
Supply from Source 2 Feeder (Levy 2 Substation):
Max Fault 3phase: 1980.0 A Max Fault 3phase to Ground: 1890.0 A Max Fault Phase to Phase: 1636.8 A Max Fault 2 phases to Ground: 1705.2 A Max Fault Phase to Ground: 1233.3 A Min Fault: 198.8 A
Transformer: 30 MVA base, %Z=12.07 Primary 115kV Transmission (Delta) Secondary 13.8kV Y‐grounded
Additional sources of short circuit fault current are the induction motors which operate throughout the system. Typically, these motor contributions are relatively small especially when a fault is located some distance from the motor, and when a motor is under 50HP.
3.3. Calculation Scenarios
The original report included three (3) scenarios that will be revisited in this analysis. These scenarios are run in both the Secondary Buildings project model and the Building 170 project model. The first DAPPER report included in this submission for each project is based on the normal interconnection of the electrical power system elements fed by the utility service.
Additional reports for this system were generated for two (2) other scenarios. The three (3) total scenarios are summarized in the table below.
Scenario Utility Feeds Tie Breaker Generators ATS’s Normal Interconnection
Utility Feeds Active
Out Out Normal Pos.
All Loads on Larger Utility Feed
Only Larger Utility Feed Active
Active Out Normal Pos.
Emergency – On Generator
Out
Out Active Emergency Pos.
3.4. SKM Power*Tools Input Data Reports
The included DAPPER input reports list the system components used to calculate the short circuit currents for the Normal Interconnection scenario in each project described above.
Additional input reports were generated and used for calculations for the other scenarios, but only the report for the Normal Interconnection scenario for each project is included here for brevity. The reports for the other scenarios are included in the soft copy disc.
DAPPER Fault Analysis Input Report (English)
Project: VA NLR BLDG 170
Normal Utility
Utilities
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data -------- PU (100 MVA Base)
X PUR PUX/RUnitsDuty
UTIL-LEVY 2 MAIN 2 SG 13,800 Amps 8.00In 1,980
SLG:
3P:
Amps 8.00 5.905 0.738
Pos:
Zero: 1,233
0.262 2.097
UTIL-WESTGATE 2 MAIN 1 SG 13,800 Amps 8.00In 2,773
SLG:
3P:
Amps 8.00 3.249 0.406
Pos:
Zero: 1,995
0.187 1.497
Generators
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
-------- Contribution Data --------
Base kVA X" X/R
PU (100 MVA Base)
R PU X PU
GEN-0001 480BUS-0029 625.00 20.00 0.00 0.00Out
0.00
0.00 0.00
0.15
0.15
0.15
20.00
20.00 0.00
GEN-0002 480BUS-0030 625.00 20.00 0.00 0.00Out
0.00
0.00 0.00
0.15
0.15
0.15
20.00
20.00 0.00
Motors
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
AIR-COMP-1 BUS-0581 480 10.03 0.1692 10.00 168.695 1,687.015In 1
AIR-COMP-2 BUS-0582 480 10.03 0.1692 10.00 168.695 1,687.015In 1
AIR-DRYER-2 BUS-0583 480 10.03 0.1692 10.00 168.695 1,687.015In 1
CHILLER 1 BUS-0591 480 618.28 0.1692 10.00 2.513 25.127In 1
CHILLER 2 BUS-0592 480 586.02 0.1692 10.00 2.651 26.510In 1
Contribution
From Name
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
CHILLER 3 BUS-0593 480 331.99 0.1692 10.00 4.679 46.794In 1
CT-1 BUS-0523 480 50.13 0.1692 10.00 33.739 337.403In 1
CT-2 BUS-0524 480 50.13 0.1692 10.00 33.739 337.403In 1
EF-103 BUS-0587 480 5.01 0.1692 10.00 337.390 3,374.031In 1
EF-40 BUS-0588 480 5.01 0.1692 10.00 337.390 3,374.031In 1
ELEV. P1 BUS-0401 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. P2 BUS-0402 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. P3 BUS-0404 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. P4 BUS-0405 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. P5 BUS-0495 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. P6 BUS-0496 480 50.13 0.1692 10.00 33.739 337.403In 1
ELEV. S11 BUS-0497 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV. S12 BUS-0494 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV. S14 BUS-0434 480 40.11 0.1692 10.00 42.174 421.754In 1
ELEV. S7 BUS-0406 480 60.16 0.1692 10.00 28.116 281.169In 1
ELEV. S9 BUS-0403 480 60.16 0.1692 10.00 28.116 281.169In 1
EMCC/P1-LOAD BUS-0584 480 5.01 0.1692 10.00 84.347 843.508In 4
GG-100 BUS-0554 480 5.01 0.1692 10.00 337.390 3,374.031In 1
JOCKEY-PUMP BUS-0578 480 10.03 0.1692 10.00 168.695 1,687.015In 1
MCP/1-LOAD BUS-0556 480 1.00 0.1692 10.00 105.434 1,054.385In 16
MCP/2-LOAD BUS-0557 480 1.75 0.1692 10.00 64.265 642.673In 15
MCP/GA1-LOAD BUS-0562 480 2.01 0.1692 10.00 168.695 1,687.015In 5
MCP/GA2-LOAD BUS-0568 480 2.01 0.1692 10.00 168.695 1,687.015In 5
MCP/GB-LOAD BUS-0572 480 3.01 0.1692 10.00 187.439 1,874.462In 3
MCP/GK-LOAD BUS-0574 480 2.51 0.1692 10.00 168.695 1,687.015In 4
MED-AIR-1 BUS-0579 480 10.03 0.1692 10.00 168.695 1,687.015In 1
MED-AIR-2 BUS-0580 480 10.03 0.1692 10.00 168.695 1,687.015In 1
MED-VAC-1 BUS-0576 480 10.03 0.1692 10.00 168.695 1,687.015In 1
MED-VAC-2 BUS-0577 480 10.03 0.1692 10.00 168.695 1,687.015In 1
P-1 BUS-0540 480 15.04 0.1692 10.00 112.463 1,124.677In 1
P-10 BUS-0522 480 50.13 0.1692 10.00 33.739 337.403In 1
P-17 BUS-0534 480 1.50 0.1692 10.00 1124.632 11,246.770In 1
P-17A BUS-0535 480 1.50 0.1692 10.00 1124.632 11,246.770In 1
P-2 BUS-0575 480 15.04 0.1692 10.00 112.463 1,124.677In 1
P-22 BUS-0541 480 1.50 0.1692 10.00 1124.632 11,246.770In 1
P-23 BUS-0539 480 30.08 0.1692 10.00 56.232 562.338In 1
P-24 BUS-0533 480 1.50 0.1692 10.00 1124.632 11,246.770In 1
P-26 BUS-0536 480 1.50 0.1692 10.00 1124.632 11,246.770In 1
P-3 BUS-0537 480 30.08 0.1692 10.00 56.232 562.338In 1
P-4 BUS-0538 480 30.08 0.1692 10.00 56.232 562.338In 1
P-5 BUS-0530 480 20.05 0.1692 10.00 84.347 843.508In 1
P-6 BUS-0532 480 20.05 0.1692 10.00 84.347 843.508In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
P-7 BUS-0531 480 20.05 0.1692 10.00 84.347 843.508In 1
P-8 BUS-0520 480 50.13 0.1692 10.00 33.739 337.403In 1
P-9 BUS-0521 480 50.13 0.1692 10.00 33.739 337.403In 1
RF-1 BUS-0551 480 7.52 0.1692 10.00 224.926 2,249.354In 1
RF-10 BUS-0442 480 7.52 0.1692 10.00 224.926 2,249.354In 1
RF-11G BUS-0567 480 5.01 0.1692 10.00 337.390 3,374.031In 1
RF-12 BUS-0553 480 5.01 0.1692 10.00 337.390 3,374.031In 1
RF-4 BUS-0397 480 25.07 0.1692 10.00 67.478 674.806In 1
RF-4A BUS-0489 480 25.07 0.1692 10.00 67.478 674.806In 1
RF-5 BUS-0399 480 25.07 0.1692 10.00 67.478 674.806In 1
RF-5A BUS-0488 480 25.07 0.1692 10.00 67.478 674.806In 1
RF-6 BUS-0398 480 20.05 0.1692 10.00 84.347 843.508In 1
RF-6A BUS-0487 480 25.07 0.1692 10.00 67.478 674.806In 1
RF-7 BUS-0400 480 20.05 0.1692 10.00 84.347 843.508In 1
RF-7A BUS-0486 480 20.05 0.1692 10.00 84.347 843.508In 1
RF-8 BUS-0471 480 7.52 0.1692 10.00 224.926 2,249.354In 1
SF/RF-1A BUS-0552 480 3.01 0.1692 10.00 281.158 2,811.692In 2
SF/RF-1B BUS-0555 480 3.01 0.1692 10.00 281.158 2,811.692In 2
SF-1 BUS-0550 480 30.08 0.1692 10.00 56.232 562.338In 1
SF-10 BUS-0441 480 25.07 0.1692 10.00 67.478 674.806In 1
SF-11A BUS-0563 480 5.01 0.1692 10.00 337.390 3,374.031In 1
SF-11B BUS-0558 480 5.01 0.1692 10.00 337.390 3,374.031In 1
SF-11C BUS-0564 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-11D BUS-0559 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-11E BUS-0565 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-11F BUS-0560 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-11G BUS-0566 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-11H BUS-0561 480 10.03 0.1692 10.00 168.695 1,687.015In 1
SF-13 BUS-0573 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-15 BUS-0569 480 5.01 0.1692 10.00 337.390 3,374.031In 1
SF-16 BUS-0586 480 15.04 0.1692 10.00 112.463 1,124.677In 1
SF-2 BUS-0570 480 15.04 0.1692 10.00 112.463 1,124.677In 1
SF-3 BUS-0571 480 20.05 0.1692 10.00 84.347 843.508In 1
SF-4 BUS-0407 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-4A BUS-0490 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-5 BUS-0409 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-5A BUS-0491 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-6 BUS-0410 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-6A BUS-0492 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-7 BUS-0408 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-7A BUS-0493 480 75.20 0.1692 10.00 22.493 224.935In 1
SF-8 BUS-0470 480 40.11 0.1692 10.00 42.174 421.754In 1
Bus
Name
In/Out
Service
Nominal
Voltage
--------- Contribution Data --------
Base kVA Xd" X/R
PU (100 MVA Base)
R PU X PU
# of
Motors
SM COOLING BUS-0594 480 100.27 0.1692 10.00 16.869 168.702In 1
Cables
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-0543
BUS-(GE-114)
1 100 4/0 PVC Pos:
Zero:
14.7929 11.4876
28.2914
CBL-(GE-114) In
46.6208
MagneticCopper
BUS-SS3
BUS-0591
3 135 500 PVC Pos:
Zero:
0.5742 0.9102
2.2402
CBL-CHILLER 1 In
1.8086
MagneticCopper
BUS-SS3
BUS-0592
3 120 500 PVC Pos:
Zero:
0.5104 0.8090
1.9913
CBL-CHILLER 2 In
1.6076
MagneticCopper
BUS-SS4
BUS-0593
2 120 350 PVC Pos:
Zero:
0.9844 1.2786
3.1484
CBL-CHILLER 3 In
3.1016
MagneticCopper
BUS-SS1-A
BUS-D/GB
1 50 500 PVC Pos:
Zero:
0.6380 1.0113
2.4891
CBL-D/GB In
2.0095
MagneticCopper
BUS-D/GB
BUS-MCP/GB
1 100 4/0 PVC Pos:
Zero:
2.7778 2.1571
5.3125
CBL-D/GB-1 In
8.7543
MagneticCopper
BUS-D/GB
BUS-H/GB
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-D/GB-2 In
1.6578
MagneticCopper
BUS-D/GB
BUS-TR-GB-PRI
1 30 6 PVC Pos:
Zero:
6.6406 0.6836
1.6836
CBL-D/GB-3 In
20.9271
BUS-D/GB
BUS-TR-1B-PRI
1 16 6 PVC Pos:
Zero:
3.5417 0.3646
0.8979
CBL-D/GB-4 In
11.1611
MagneticCopper
BUS-D/GB 1 65 6 PVC Pos:
Zero:
14.3880 1.4811
3.6478
CBL-D/GB-5 In
45.3420
MagneticCopper
BUS-D/GB
BUS-TR-2B-PRI
1 100 1/0 PVC Pos:
Zero:
5.5556 1.7969
4.4227
CBL-D/GB-6 In
17.5087
MagneticCopper
BUS-D/GB
BUS-ATS-GB (N)
1 8 3/0 PVC Pos:
Zero:
0.2795 0.1802
0.4438
CBL-D/GB-7 In
0.8809
BUS-D/GB
BUS-TR-GB1-A-PRI
1 30 8 PVC Pos:
Zero:
10.5599 0.7513
1.8490
CBL-D/GB-8 In
33.2799
MagneticCopper
BUS-SS1-A
BUS-D/GE
2 395 500 PVC Pos:
Zero:
2.5202 3.9946
9.8321
CBL-D/GE In
7.9377
MagneticCopper
BUS-D/GE
BUS-MCC/GE
1 10 4/0 PVC Pos:
Zero:
0.2778 0.2157
0.5313
CBL-D/GE-1 In
0.8754
MagneticCopper
BUS-D/GE
BUS-TR-GA-PRI
1 150 6 PVC Pos:
Zero:
33.2031 3.4180
8.4180
CBL-D/GE-10 In
104.6354
BUS-D/GE
BUS-TR-2E-PRI
1 160 4 PVC Pos:
Zero:
22.2917 3.3542
8.2569
CBL-D/GE-11 In
70.2500
MagneticCopper
BUS-D/GE
BUS-TR-3E-PRI
1 170 6 PVC Pos:
Zero:
37.6302 3.8737
9.5404
CBL-D/GE-12 In
118.5868
MagneticCopper
Cable
Name
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-D/GE
BUS-H/GE
1 25 2 PVC Pos:
Zero:
2.1918 0.6348
1.5625
CBL-D/GE-2 In
6.9076
MagneticCopper
BUS-D/GE
BUS-ATS-GE (N)
1 20 4/0 PVC Pos:
Zero:
0.5556 0.4314
1.0625
CBL-D/GE-3 In
1.7509
BUS-TR-1E-PRI
1 150 6 PVC Pos:
Zero:
33.2031 3.4180
8.4180
CBL-D/GE-4 In
104.6354
MagneticCopper
BUS-D/GE
BUS-TR-GE-PRI
1 8 250 PVC Pos:
Zero:
0.1917 0.1316
0.3240
CBL-D/GE-5 In
0.6038
MagneticCopper
BUS-D/GE
BUS-TR-1D-PRI
1 285 6 PVC Pos:
Zero:
63.0859 6.4941
15.9941
CBL-D/GE-6 In
198.8073
MagneticCopper
BUS-D/GE
BUS-H/GA
1 150 2 PVC Pos:
Zero:
13.1510 3.8086
9.3750
CBL-D/GE-7 In
41.4453
BUS-TR-2D-PRI
1 295 4 PVC Pos:
Zero:
41.1003 6.1842
15.2237
CBL-D/GE-8 In
129.5235
MagneticCopper
BUS-D/GE
BUS-TR-3D-PRI
1 305 4 PVC Pos:
Zero:
42.4935 6.3939
15.7398
CBL-D/GE-9 In
133.9141
MagneticCopper
BUS-SS1-A
BUS-D/GF
1 255 500 PVC Pos:
Zero:
3.2539 5.1576
12.6947
CBL-D/GF In
10.2487
MagneticCopper
BUS-D/GF
BUS-ATS-GF (N)
1 10 4/0 PVC Pos:
Zero:
0.2778 0.2157
0.5313
CBL-D/GF-1 In
0.8754
BUS-D/GF
BUS-TR-GF-PRI
1 25 6 PVC Pos:
Zero:
5.5339 0.5697
1.4030
CBL-D/GF-10 In
17.4392
MagneticCopper
BUS-D/GF
BUS-H/GF
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-D/GF-2 In
5.5260
MagneticCopper
BUS-D/GF
BUS-H/1F
1 45 2 PVC Pos:
Zero:
3.9453 1.1426
2.8125
CBL-D/GF-3 In
12.4336
MagneticCopper
BUS-D/GF
BUS-H/2F
1 80 2 PVC Pos:
Zero:
7.0139 2.0313
5.0000
CBL-D/GF-4 In
22.1042
BUS-H/3F
1 90 2 PVC Pos:
Zero:
7.8906 2.2852
5.6250
CBL-D/GF-5 In
24.8672
MagneticCopper
BUS-D/GF
BUS-MCP/GA1
1 255 2 PVC Pos:
Zero:
22.3568 6.4746
15.9375
CBL-D/GF-6 In
70.4570
MagneticCopper
BUS-D/GF
BUS-TR-2C-PRI
1 285 6 PVC Pos:
Zero:
63.0859 8.4733
20.8678
CBL-D/GF-7 In
198.8073
MagneticCopper
BUS-D/GF
BUS-TR-1C-PRI
1 16 6 PVC Pos:
Zero:
3.5417 0.3646
0.8979
CBL-D/GF-8 In
11.1611
BUS-TR-3C-PRI
1 295 6 PVC Pos:
Zero:
65.2995 6.7220
16.5553
CBL-D/GF-9 In
205.7830
MagneticCopper
BUS-SS1-B
BUS-D/GG
1 450 250 PVC Pos:
Zero:
10.7813 9.6680
23.8086
CBL-D/GG In
33.9648
MagneticCopper
BUS-D/GG
BUS-TR-1G-PRI
1 40 6 PVC Pos:
Zero:
8.8542 0.9115
2.2448
CBL-D/GG-1 In
27.9028
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-D/GG
BUS-TR-2G-PRI
1 70 8 PVC Pos:
Zero:
24.6398 1.7530
4.3142
CBL-D/GG-2 In
77.6532
BUS-D/GG
BUS-TR-3G-PRI
1 80 8 PVC Pos:
Zero:
28.1597 2.0035
4.9306
CBL-D/GG-3 In
88.7465
MagneticCopper
BUS-D/GG
BUS-TR-GG-PRI
1 6 10 PVC Pos:
Zero:
3.0729 0.1703
0.4193
CBL-D/GG-4 In
9.6844
MagneticCopper
BUS-D/GG
BUS-TR-1G-A-PRI
1 40 8 PVC Pos:
Zero:
14.0799 1.0017
2.4653
CBL-D/GG-5 In
44.3733
MagneticCopper
BUS-SS2-B
BUS-D/GH
1 280 500 PVC Pos:
Zero:
3.5729 5.6632
13.9392
CBL-D/GH In
11.2535
BUS-D/GH
BUS-ATS-GH (N)
1 40 2 PVC Pos:
Zero:
3.5069 1.0156
2.5000
CBL-D/GH-1 In
11.0521
MagneticCopper
BUS-D/GH
BUS-H/GH
1 10 2 PVC Pos:
Zero:
0.8767 0.2539
0.6250
CBL-D/GH-2 In
2.7630
MagneticCopper
BUS-D/GH
BUS-TR-GH-PRI
1 6 2 PVC Pos:
Zero:
0.5260 0.1167
0.2872
CBL-D/GH-3 In
1.6578
MagneticCopper
BUS-D/GH
BUS-TR-2H-PRI
1 80 6 PVC Pos:
Zero:
17.7083 1.8229
4.4896
CBL-D/GH-4 In
55.8056
BUS-D/GH
BUS-TR-3H-PRI
1 90 6 PVC Pos:
Zero:
19.9219 2.0508
5.0508
CBL-D/GH-5 In
62.7813
MagneticCopper
BUS-D/GH
BUS-TR-1H-PRI
1 70 6 PVC Pos:
Zero:
15.4948 1.5951
3.9284
CBL-D/GH-6 In
48.8299
MagneticCopper
BUS-SS2-A
BUS-D/GJ
2 45 500 PVC Pos:
Zero:
0.2871 0.4551
1.1201
CBL-D/GJ In
0.9043
MagneticCopper
BUS-D/GJ
BUS-0441
1 50 6 PVC Pos:
Zero:
11.0677 1.4865
3.6610
CBL-D/GJ-1 In
34.8785
BUS-D/GJ
BUS-0442
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-D/GJ-12 In
127.8950
MagneticCopper
BUS-D/GJ
BUS-ATS-GJ (N)
2 6 250 PVC Pos:
Zero:
0.0719 0.0645
0.1587
CBL-D/GJ-2 In
0.2264
MagneticCopper
BUS-D/GJ
BUS-TR-1J-PRI
1 70 6 PVC Pos:
Zero:
15.4948 1.5951
3.9284
CBL-D/GJ-3 In
48.8299
MagneticCopper
BUS-D/GJ
BUS-H/GJ
1 30 2 PVC Pos:
Zero:
2.6302 0.7617
1.8750
CBL-D/GJ-4 In
8.2891
BUS-D/GJ
BUS-TR-2J-PRI
1 80 6 PVC Pos:
Zero:
17.7083 1.8229
4.4896
CBL-D/GJ-6 In
55.8056
MagneticCopper
BUS-D/GJ
BUS-TR-GJ-PRI
1 35 2/0 PVC Pos:
Zero:
1.5495 0.6183
1.5221
CBL-D/GJ-7 In
4.8824
MagneticCopper
BUS-D/GJ
BUS-TR-3J-PRI
1 90 6 PVC Pos:
Zero:
19.9219 2.0508
5.0508
CBL-D/GJ-8 In
62.7813
MagneticCopper
BUS-SS2-A 1 470 500 PVC Pos: 5.9974 9.5061CBL-D/GK In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-D/GK Zero: 23.3980 18.8898
BUS-D/GK
BUS-ATS-GK (N)
1 20 4/0 PVC Pos:
Zero:
0.5556 0.4314
1.0625
CBL-D/GK-1 In
1.7509
MagneticCopper
BUS-D/GK
BUS-TR-GN-PRI
1 6 4 PVC Pos:
Zero:
0.8359 0.1258
0.3096
CBL-D/GK-10 In
2.6344
MagneticCopper
BUS-D/GK
BUS-TR-GK-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-D/GK-11 In
6.6560
MagneticCopper
BUS-D/GK
BUS-TR-1N-PRI
1 150 8 PVC Pos:
Zero:
52.7995 3.7565
9.2448
CBL-D/GK-12 In
166.3997
BUS-MCP/GK
1 30 2 PVC Pos:
Zero:
2.6302 0.7617
1.8750
CBL-D/GK-2 In
8.2891
MagneticCopper
BUS-D/GK
BUS-TR-LP1/LP2-PRI
1 195 1/0 PVC Pos:
Zero:
10.8333 3.5039
8.6243
CBL-D/GK-3 In
34.1419
MagneticCopper
BUS-D/GK
BUS-TR-2K-PRI
1 110 6 PVC Pos:
Zero:
24.3490 2.5065
6.1732
CBL-D/GK-4 In
76.7326
MagneticCopper
BUS-D/GK
BUS-TR-1K-PRI
1 100 6 PVC Pos:
Zero:
22.1354 2.2786
5.6120
CBL-D/GK-5 In
69.7570
BUS-TR-3K-PRI
1 120 6 PVC Pos:
Zero:
26.5625 2.7344
6.7344
CBL-D/GK-6 In
83.7083
MagneticCopper
BUS-D/GK
BUS-TR-2N-PRI
1 160 8 PVC Pos:
Zero:
56.3194 4.0069
9.8611
CBL-D/GK-7 In
177.4931
MagneticCopper
BUS-D/GK
BUS-TR-3N-PRI
1 170 8 PVC Pos:
Zero:
59.8394 4.2574
10.4774
CBL-D/GK-8 In
188.5864
MagneticCopper
BUS-D/GK
BUS-H2/GK
1 30 1/0 PVC Pos:
Zero:
1.6667 0.7031
1.7305
CBL-D/GK-9 In
5.2526
BUS-SS2-B
BUS-D/GL
2 660 350 PVC Pos:
Zero:
5.4141 7.0326
17.3164
CBL-D/GL In
17.0586
MagneticCopper
BUS-D/GL
BUS-TR-GL-PRI
1 20 250 PVC Pos:
Zero:
0.4792 0.3290
0.8099
CBL-D/GL-1 In
1.5095
MagneticCopper
BUS-D/GL
BUS-H/GL
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-D/GL-2 In
5.5260
MagneticCopper
BUS-D/GL
BUS-ATS-GL (N)
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-D/GL-3 In
5.5260
BUS-D/GL
BUS-0470
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-D/GL-4 In
13.8151
MagneticCopper
BUS-D/GL
BUS-TR-1L-PRI
1 100 6 PVC Pos:
Zero:
22.1354 2.2786
5.6120
CBL-D/GL-5 In
69.7570
MagneticCopper
BUS-D/GL
BUS-TR-3L-PRI
1 120 6 PVC Pos:
Zero:
26.5625 2.7344
6.7344
CBL-D/GL-6 In
83.7083
MagneticCopper
BUS-D/GL
BUS-TR-2L-PRI
1 110 6 PVC Pos:
Zero:
24.3490 2.5065
6.1732
CBL-D/GL-7 In
76.7326
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-D/GL
BUS-0471
1 50 10 PVC Pos:
Zero:
25.6076 1.8533
4.5638
CBL-D/GL-8 In
80.7031
MagneticCopper
BUS-SS2-A
BUS-D/GM
1 350 500 PVC Pos:
Zero:
4.4661 7.0790
17.4240
CBL-D/GM In
14.0668
MagneticCopper
BUS-D/GM
BUS-H/2M
1 60 2 PVC Pos:
Zero:
5.2604 1.5234
3.7500
CBL-D/GM-1 In
16.5781
MagneticCopper
BUS-D/GM
BUS-H/1M
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-D/GM-2 In
13.8151
BUS-D/GM
BUS-ATS-GM (N)
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-D/GM-3 In
1.6578
MagneticCopper
BUS-D/GM
BUS-H/3M
1 70 2 PVC Pos:
Zero:
6.1372 1.7773
4.3750
CBL-D/GM-4 In
19.3411
MagneticCopper
BUS-D/GM
BUS-H/GM
1 20 2 PVC Pos:
Zero:
1.7535 0.5078
1.2500
CBL-D/GM-5 In
5.5260
MagneticCopper
BUS-D/GM
BUS-MCP/GA2
1 295 2 PVC Pos:
Zero:
25.8637 7.4902
18.4375
CBL-D/GM-6 In
81.5091
BUS-D/GM
BUS-TR-GM-PRI
1 6 4 PVC Pos:
Zero:
0.8359 0.1258
0.3096
CBL-D/GM-9 In
2.6344
MagneticCopper
BUS-0033
BUS-ED/GB
1 20 3/0 PVC Pos:
Zero:
0.6988 0.4505
1.1094
CBL-ED/GB In
2.2023
MagneticCopper
BUS-ED/GB
BUS-EH/GB
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GB-1 In
1.6578
MagneticCopper
BUS-ED/GB
BUS-TR-E/1B-PRI
1 16 8 PVC Pos:
Zero:
5.6319 0.4007
0.9861
CBL-ED/GB-2 In
17.7493
BUS-ED/GB
BUS-TR-E/2B-PRI
1 25 8 PVC Pos:
Zero:
8.7999 0.6261
1.5408
CBL-ED/GB-3 In
27.7333
MagneticCopper
BUS-ED/GB 1 35 8 PVC Pos:
Zero:
12.3199 0.8765
2.1571
CBL-ED/GB-4 In
38.8266
MagneticCopper
BUS-ED/GB
BUS-TR-E/2B-B-PRI
1 30 3/0 PVC Pos:
Zero:
1.0482 0.5169
1.2734
CBL-ED/GB-5 In
3.3034
MagneticCopper
BUS-0034
BUS-ED/GE
1 20 4/0 PVC Pos:
Zero:
0.5556 0.4314
1.0625
CBL-ED/GE In
1.7509
BUS-ED/GE
BUS-TR-E/1D-PRI
1 285 8 PVC Pos:
Zero:
100.3190 7.1374
17.5651
CBL-ED/GE-1 In
316.1595
MagneticCopper
BUS-ED/GE
BUS-TR-E/GA-PRI
1 150 8 PVC Pos:
Zero:
52.7995 3.7565
9.2448
CBL-ED/GE-2 In
166.3997
MagneticCopper
BUS-ED/GE
BUS-TR-E/2D-PRI
1 295 8 PVC Pos:
Zero:
103.8390 7.3878
18.1814
CBL-ED/GE-3 In
327.2528
MagneticCopper
BUS-ED/GE
BUS-TR-E/1E-PRI
1 150 8 PVC Pos:
Zero:
52.7995 3.7565
9.2448
CBL-ED/GE-4 In
166.3997
BUS-TR-E/3D-PRI
1 305 8 PVC Pos:
Zero:
107.3589 7.6382
18.7977
CBL-ED/GE-5 In
338.3462
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-ED/GE
BUS-TR-E/2E-PRI
1 160 8 PVC Pos:
Zero:
56.3194 4.0069
9.8611
CBL-ED/GE-6 In
177.4931
MagneticCopper
BUS-ED/GE
BUS-TR-E/3G-PRI
1 365 8 PVC Pos:
Zero:
128.4787 9.1408
22.4957
CBL-ED/GE-7 In
404.9061
MagneticCopper
BUS-ED/GE
BUS-TR-E/3E-PRI
1 170 8 PVC Pos:
Zero:
59.8394 4.2574
10.4774
CBL-ED/GE-8 In
188.5864
BUS-TR-E/GE-PRI
1 20 8 PVC Pos:
Zero:
7.0399 0.5009
1.2326
CBL-ED/GE-9 In
22.1866
MagneticCopper
BUS-0035
BUS-ED/GF
1 15 4/0 PVC Pos:
Zero:
0.4167 0.3236
0.7969
CBL-ED/GF In
1.3132
MagneticCopper
BUS-ED/GF
BUS-EH/3F
1 90 2 PVC Pos:
Zero:
7.8906 2.2852
5.6250
CBL-ED/GF-1 In
24.8672
MagneticCopper
BUS-ED/GF
BUS-EH/1F
1 70 2 PVC Pos:
Zero:
6.1372 1.7773
4.3750
CBL-ED/GF-2 In
19.3411
BUS-ED/GF
BUS-EH/GF
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GF-3 In
1.6578
MagneticCopper
BUS-ED/GF
BUS-EH/2F
1 80 2 PVC Pos:
Zero:
7.0139 2.0313
5.0000
CBL-ED/GF-4 In
22.1042
MagneticCopper
BUS-ED/GF
BUS-TR-E/3C-PRI
1 295 8 PVC Pos:
Zero:
103.8390 7.3878
18.1814
CBL-ED/GF-5 In
327.2528
MagneticCopper
BUS-ED/GF
BUS-TR-E/2C-PRI
1 285 8 PVC Pos:
Zero:
100.3190 7.1374
17.5651
CBL-ED/GF-6 In
316.1595
BUS-ED/GF
BUS-TR-E/1C-PRI
1 275 8 PVC Pos:
Zero:
96.7990 6.8869
16.9488
CBL-ED/GF-7 In
305.0662
MagneticCopper
BUS-0036
BUS-ED/GH
1 40 2 PVC Pos:
Zero:
3.5069 1.0156
2.5000
CBL-ED/GH In
11.0521
MagneticCopper
BUS-ED/GH
BUS-EH/GH
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GH-1 In
1.6578
MagneticCopper
BUS-ED/GH
BUS-TR-E/1H-PRI
1 70 8 PVC Pos:
Zero:
24.6398 1.7530
4.3142
CBL-ED/GH-2 In
77.6532
BUS-ED/GH
BUS-TR-E/2H-PRI
1 80 8 PVC Pos:
Zero:
28.1597 2.6181
6.4444
CBL-ED/GH-4 In
88.7465
MagneticCopper
BUS-ED/GH
BUS-TR-E/3H-PRI
1 90 8 PVC Pos:
Zero:
31.6797 2.9453
7.2500
CBL-ED/GH-6 In
99.8399
MagneticCopper
BUS-0037
BUS-ED/GJ
2 6 350 PVC Pos:
Zero:
0.0492 0.0639
0.1574
CBL-ED/GJ In
0.1551
MagneticCopper
BUS-ED/GJ
BUS-EMCC/GJ
1 65 500 PVC Pos:
Zero:
0.8294 1.3147
3.2359
CBL-ED/GJ-1 In
2.6124
BUS-ED/GJ
BUS-TR-E/1J-PRI
1 70 8 PVC Pos:
Zero:
24.6398 1.7530
4.3142
CBL-ED/GJ-2 In
77.6532
MagneticCopper
BUS-ED/GJ
BUS-EH/GJ
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GJ-3 In
1.6578
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-ED/GJ
BUS-TR-E/2J-PRI
1 80 8 PVC Pos:
Zero:
28.1597 2.0035
4.9306
CBL-ED/GJ-4 In
88.7465
MagneticCopper
BUS-ED/GJ
BUS-TR-E/3J-PRI
1 90 8 PVC Pos:
Zero:
31.6797 2.2539
5.5469
CBL-ED/GJ-5 In
99.8399
BUS-0038
BUS-ED/GK
1 6 4/0 PVC Pos:
Zero:
0.1667 0.1294
0.3188
CBL-ED/GK In
0.5253
MagneticCopper
BUS-ED/GK
BUS-0434
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-ED/GK-1 In
13.8151
MagneticCopper
BUS-ED/GK
BUS-TR-E2/GK-PRI
1 30 1 PVC Pos:
Zero:
2.0833 0.5677
1.3971
CBL-ED/GK-2 In
6.5651
MagneticCopper
BUS-ED/GK
BUS-TR-E/1K-PRI
1 100 8 PVC Pos:
Zero:
35.1997 2.5043
6.1632
CBL-ED/GK-3 In
110.9332
BUS-ED/GK
BUS-TR-E/GK-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-ED/GK-4 In
6.6560
MagneticCopper
BUS-ED/GK
BUS-TR-E/2K-PRI
1 110 8 PVC Pos:
Zero:
38.7196 2.7548
6.7795
CBL-ED/GK-5 In
122.0265
MagneticCopper
BUS-ED/GK
BUS-TR-E/3K-PRI
1 120 8 PVC Pos:
Zero:
42.2396 3.0052
7.3958
CBL-ED/GK-6 In
133.1198
MagneticCopper
BUS-0039
BUS-ED/GL
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GL In
1.6578
BUS-ED/GL
BUS-EH/GL
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GL-1 In
1.6578
MagneticCopper
BUS-ED/GL
BUS-TR-E/3L-PRI
1 120 8 PVC Pos:
Zero:
42.2396 3.0052
7.3958
CBL-ED/GL-2 In
133.1198
MagneticCopper
BUS-ED/GL
BUS-TR-E/1L-PRI
1 100 8 PVC Pos:
Zero:
35.1997 2.5043
6.1632
CBL-ED/GL-3 In
110.9332
MagneticCopper
BUS-ED/GL
BUS-TR-E/2L-PRI
1 110 8 PVC Pos:
Zero:
38.7196 2.7548
6.7795
CBL-ED/GL-4 In
122.0265
BUS-0040
BUS-ED/GM
1 6 2 PVC Pos:
Zero:
0.5260 0.1523
0.3750
CBL-ED/GM In
1.6578
MagneticCopper
BUS-ED/GM
BUS-EH/3M
1 70 2 PVC Pos:
Zero:
6.1372 1.7773
4.3750
CBL-ED/GM-1 In
19.3411
MagneticCopper
BUS-ED/GM
BUS-EH/2M
1 60 2 PVC Pos:
Zero:
5.2604 1.5234
3.7500
CBL-ED/GM-2 In
16.5781
MagneticCopper
BUS-ED/GM
BUS-EH/GM
1 15 2 PVC Pos:
Zero:
1.3151 0.3809
0.9375
CBL-ED/GM-3 In
4.1445
BUS-ED/GM
BUS-EH/1M
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-ED/GM-4 In
13.8151
MagneticCopper
BUS-0041
BUS-ED/RF
2 6 350 PVC Pos:
Zero:
0.0492 0.0639
0.1574
CBL-ED/RF In
0.1551
MagneticCopper
BUS-ED/RF
BUS-0401
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RF-1 In
8.7543
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-ED/RF
BUS-0402
1 50 3 PVC Pos:
Zero:
5.4905 1.3129
3.2313
CBL-ED/RF-2 In
17.3025
BUS-ED/RF
BUS-0403
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RF-3 In
8.7543
MagneticCopper
BUS-ED/RF
BUS-0404
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RF-4 In
8.7543
MagneticCopper
BUS-ED/RF
BUS-TR-E/RF-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-ED/RF-5 In
6.6560
MagneticCopper
BUS-ED/RF
BUS-0405
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RF-6 In
8.7543
BUS-ED/RF
BUS-0406
1 50 2 PVC Pos:
Zero:
4.3837 1.2695
3.1250
CBL-ED/RF-7 In
13.8151
MagneticCopper
BUS-0043
BUS-ED/RM
2 6 3/0 PVC Pos:
Zero:
0.1048 0.0676
0.1664
CBL-ED/RM In
0.3303
MagneticCopper
BUS-ED/RM
BUS-0494
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RM-1 In
8.7543
MagneticCopper
BUS-ED/RM
BUS-0495
1 50 1 PVC Pos:
Zero:
3.4722 1.2370
3.0447
CBL-ED/RM-2 In
10.9418
BUS-ED/RM
BUS-0496
1 50 1 PVC Pos:
Zero:
3.4722 1.2370
3.0447
CBL-ED/RM-3 In
10.9418
MagneticCopper
BUS-ED/RM
BUS-0497
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-ED/RM-4 In
8.7543
MagneticCopper
BUS-ED/RM
BUS-TR-UPS/1-PRI
1 35 6 PVC Pos:
Zero:
7.7474 0.7975
1.9642
CBL-ED/RM-5 In
24.4149
MagneticCopper
BUS-ED/RM
BUS-TR-E/RM-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-ED/RM-6 In
6.6560
BUS-EH/1F
BUS-TR-E/1F-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-EH/1F-1 In
4.1854
MagneticCopper
BUS-EH/1M
BUS-TR-E/1M-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-EH/1M-1 In
4.1854
MagneticCopper
BUS-EH/2F
BUS-TR-E/2F-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
CBL-EH/2F-1 In
6.6560
MagneticCopper
BUS-EH/2M
BUS-TR-E/2M-PRI
1 8 8 PVC Pos:
Zero:
2.8160 0.2618
0.6444
CBL-EH/2M-1 In
8.8747
BUS-EH/3F
BUS-EH/RF
1 150 10 PVC Pos:
Zero:
76.8229 5.5599
13.6914
CBL-EH/3F-1 In
242.1094
MagneticCopper
BUS-EH/3F
BUS-TR-E/3F-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
CBL-EH/3F-2 In
6.6560
MagneticCopper
BUS-EH/3M
BUS-EH/RM
1 150 10 PVC Pos:
Zero:
76.8229 5.5599
13.6914
CBL-EH/3M-1 In
242.1094
MagneticCopper
BUS-EH/3M 1 8 8 PVC Pos: 2.8160 0.2618CBL-EH/3M-2 In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
BUS-TR-E/3M-PRI Zero: 0.6444 8.8747
BUS-EH/GB
BUS-TR-E/GB-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1964
0.4833
CBL-EH/GB-1 In
6.6560
MagneticCopper
BUS-EH/GF
BUS-TR-E/GF-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-EH/GF-1 In
6.6560
MagneticCopper
BUS-EH/GH
BUS-TR-E/GH-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-EH/GH-2 In
6.6560
MagneticCopper
BUS-EH/GJ
BUS-TR-E/GJ-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-EH/GJ-1 In
6.6560
BUS-EH/GL
BUS-TR-E/GL-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-EH/GL-1 In
6.6560
MagneticCopper
BUS-EH/GM
BUS-TR-E/GM-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-EH/GM-7 In
6.6560
MagneticCopper
BUS-TR-E/1B-SEC
BUS-EL/1B
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/1B In
22.2892
MagneticCopper
BUS-TR-E/1C-SEC
BUS-EL/1C
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/1C In
14.0292
BUS-TR-E/1D-SEC
BUS-EL/1D
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/1D In
8.8286
MagneticCopper
BUS-TR-E/1E-SEC
BUS-EL/1E
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/1E In
8.8286
MagneticCopper
BUS-TR-E/1F-SEC
BUS-EL/1F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/1F In
8.8286
MagneticCopper
BUS-TR-E/1H-SEC
BUS-EL/1H
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/1H In
22.2892
BUS-TR-E/1J-SEC
BUS-EL/1J
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/1J In
14.0292
MagneticCopper
BUS-TR-E/1K-SEC
BUS-EL/1K
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/1K In
22.2892
MagneticCopper
BUS-TR-E/1L-SEC
BUS-EL/1L
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/1L In
22.2892
MagneticCopper
BUS-TR-E/1M-SEC
BUS-EL/1M
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/1M In
8.8286
BUS-TR-E/2B-SEC
BUS-EL/2B
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/2B In
8.8286
MagneticCopper
BUS-TR-E/2B-B-SEC
BUS-EL/2B-B
1 100 2/0 PVC Pos:
Zero:
23.5762 12.3197
30.3254
CBL-EL/2B-B In
74.2881
MagneticCopper
BUS-EL/2B-B
BUS-EL/2B-C
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-EL/2B-C In
4.4573
MagneticCopper
BUS-TR-E/2C-SEC
BUS-EL/2C
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/2C In
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-TR-E/2D-SEC
BUS-EL/2D
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/2D In
8.8286
MagneticCopper
BUS-TR-E/2E-SEC
BUS-EL/2E
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/2E In
8.8286
MagneticCopper
BUS-TR-E/2F-SEC
BUS-EL/2F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/2F In
8.8286
MagneticCopper
BUS-TR-E/2H-SEC
BUS-EL/2H
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/2H In
BUS-TR-E/2J-SEC
BUS-EL/2J
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/2J In
22.2892
MagneticCopper
BUS-TR-E/2K-SEC
BUS-EL/2K
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/2K In
22.2892
MagneticCopper
BUS-TR-E/2L-SEC
BUS-EL/2L
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/2L In
22.2892
MagneticCopper
BUS-TR-E/2M-SEC
BUS-EL/2M
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/2M In
BUS-0548
BUS-EL/3B
1 1 Pos:
Zero:
0.0000 0.0000
0.0000
CBL-EL/3B In
0.0000
Non-MagneticCopper
BUS-TR-E/3C-SEC
BUS-EL/3C
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3C In
8.8286
MagneticCopper
BUS-TR-E/3D-SEC
BUS-EL/3D
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3D In
8.8286
MagneticCopper
BUS-TR-E/3E-SEC
BUS-EL/3E
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3E In
BUS-TR-E/3F-SEC
BUS-EL/3F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3F In
8.8286
MagneticCopper
BUS-TR-E/3G-SEC
BUS-EL/3G
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3G In
8.8286
MagneticCopper
BUS-TR-E/3H-SEC
BUS-EL/3H
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/3H In
22.2892
MagneticCopper
BUS-TR-E/3J-SEC
BUS-EL/3J
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/3J In
BUS-TR-E/3K-SEC
BUS-EL/3K
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/3K In
14.0292
MagneticCopper
BUS-TR-E/3L-SEC
BUS-EL/3L
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/3L In
22.2892
MagneticCopper
BUS-TR-E/3M-SEC
BUS-EL/3M
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-EL/3M In
8.8286
MagneticCopper
BUS-TR-E/GA-SEC
BUS-EL/GA
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/GA In
BUS-TR-E/GB-SEC
BUS-EL/GB
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/GB In
14.0292
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-TR-E/GE-SEC
BUS-EL/GE
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/GE In
22.2892
MagneticCopper
BUS-TR-E/GF-SEC
BUS-EL/GF
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/GF In
14.0292
MagneticCopper
BUS-TR-E/GH-SEC
BUS-EL/GH
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/GH In
BUS-TR-E/GJ-SEC
BUS-EL/GJ
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/GJ In
22.2892
MagneticCopper
BUS-TR-E/GK-SEC
BUS-EL/GK
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/GK In
22.2892
MagneticCopper
BUS-TR-E/GL-SEC
BUS-EL/GL
1 6 6 PVC Pos:
Zero:
7.0729 0.9500
2.3396
CBL-EL/GL In
22.2892
MagneticCopper
BUS-TR-E/GM-SEC
BUS-EL/GM
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/GM In
BUS-EL/GM
BUS-EL/GM SUB
1 6 4 PVC Pos:
Zero:
4.4517 0.6698
1.6489
CBL-EL/GM-10 In
14.0292
MagneticCopper
BUS-TR-E/RF2-SEC
BUS-EL/RF2
1 6 3/0 PVC Pos:
Zero:
1.1164 0.7198
1.7724
CBL-EL/RF2 In
3.5184
MagneticCopper
BUS-TR-E/RF-SEC
BUS-EL/RF-L
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/RF-L In
14.0292
MagneticCopper
BUS-EL/RF-L
BUS-EL/RF-R
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/RF-R In
BUS-TR-E/RM-SEC
BUS-EL/RM
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-EL/RM In
14.0292
MagneticCopper
BUS-TR-E2/GK-SEC
BUS-EL2/GK
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-EL2/GK In
4.4573
MagneticCopper
BUS-EMCC/GJ
BUS-0575
1 50 10 PVC Pos:
Zero:
25.6076 1.8533
4.5638
CBL-EMCC/GJ-1 In
80.7031
MagneticCopper
BUS-EMCC/GJ
BUS-0576
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-2 In
127.8950
BUS-EMCC/GJ
BUS-0577
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-3 In
127.8950
MagneticCopper
BUS-EMCC/GJ
BUS-0578
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-4 In
127.8950
MagneticCopper
BUS-EMCC/GJ
BUS-0579
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-5 In
127.8950
MagneticCopper
BUS-EMCC/GJ
BUS-0580
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-6 In
BUS-EMCC/GJ
BUS-0581
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-7 In
127.8950
MagneticCopper
BUS-EMCC/GJ
BUS-0582
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-8 In
127.8950
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-EMCC/GJ
BUS-0583
1 50 12 PVC Pos:
Zero:
40.5816 1.9748
4.8633
CBL-EMCC/GJ-9 In
127.8950
MagneticCopper
BUS-0042
BUS-EMCC/P1
2 20 350 PVC Pos:
Zero:
0.1641 0.2131
0.5247
CBL-EMCC/P1 In
0.5169
BUS-EMCC/P1
BUS-TR-E/RF2-PRI
1 35 2 PVC Pos:
Zero:
3.0686 0.6806
1.6756
CBL-EMCC/P1-1 In
9.6706
MagneticCopper
BUS-EMCC/P1
BUS-0407
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P1-2 In
8.7543
MagneticCopper
BUS-EMCC/P1
BUS-0408
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P1-3 In
8.7543
MagneticCopper
BUS-EMCC/P1
BUS-0409
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P1-4 In
BUS-EMCC/P1
BUS-0410
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P1-5 In
8.7543
MagneticCopper
BUS-EMCC/P1
BUS-0584
1 50 8 PVC Pos:
Zero:
17.5998 1.6363
4.0278
CBL-EMCC/P1-6 In
55.4666
MagneticCopper
BUS-EMCC/P2
BUS-TR-UPS-PRI
1 35 8 PVC Pos:
Zero:
12.3199 1.1454
2.8194
CBL-EMCC/P2-1 In
38.8266
MagneticCopper
BUS-EMCC/P2
BUS-0490
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P2-2 In
BUS-EMCC/P2
BUS-0491
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P2-3 In
8.7543
MagneticCopper
BUS-EMCC/P2
BUS-0492
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P2-4 In
8.7543
MagneticCopper
BUS-EMCC/P2
BUS-0493
1 50 1/0 PVC Pos:
Zero:
2.7778 1.1719
2.8841
CBL-EMCC/P2-5 In
8.7543
MagneticCopper
BUS-0044
BUS-EMCC/P2
2 40 350 PVC Pos:
Zero:
0.3281 0.4262
1.0495
CBL-EMCC-P2 In
1.0339
BUS-H/1F
BUS-TR-1F-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-H/1F-1 In
4.1854
MagneticCopper
BUS-H/1M
BUS-TR-1M-PRI
1 6 6 PVC Pos:
Zero:
1.3281 0.1367
0.3367
CBL-H/1M-1 In
4.1854
MagneticCopper
BUS-H/2F
BUS-TR-2F-PRI
1 6 8 PVC Pos:
Zero:
2.1120 0.1503
0.3698
CBL-H/2F-1 In
6.6560
MagneticCopper
BUS-H/2F
BUS-H1
1 200 8 PVC Pos:
Zero:
70.3993 6.5451
16.1111
CBL-H/2F-2 In
221.8663
BUS-H/2M
BUS-TR-2M-PRI
1 8 6 PVC Pos:
Zero:
1.7708 0.1823
0.4490
CBL-H/2M-1 In
5.5806
MagneticCopper
BUS-H/3F
BUS-TR-3F-PRI
1 8 8 PVC Pos:
Zero:
2.8160 0.2003
0.4931
CBL-H/3F-1 In
8.8747
MagneticCopper
BUS-H/3M
BUS-TR-3M-PRI
1 8 8 PVC Pos:
Zero:
2.8160 0.2003
0.4931
CBL-H/3M-1 In
8.8747
MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-H2/GK
BUS-TR-2/GK-PRI
1 20 1 PVC Pos:
Zero:
1.3889 0.3785
0.9314
CBL-H2/GK-2 In
4.3767
BUS-TR-1B-SEC
BUS-L/1B-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1B-L In
8.8286
MagneticCopper
BUS-L/1B-L
BUS-L/1B-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1B-R In
8.8286
MagneticCopper
BUS-L/1C-R
BUS-L/1C-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1C-L In
8.8286
MagneticCopper
BUS-TR-1C-SEC
BUS-L/1C-R
1 16 2 PVC Pos:
Zero:
7.4704 2.1635
5.3254
CBL-L/1C-R In
23.5429
BUS-L/1D-R
BUS-L/1D-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1D-L In
8.8286
MagneticCopper
BUS-TR-1D-SEC
BUS-L/1D-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1D-R In
8.8286
MagneticCopper
BUS-TR-1E-SEC
BUS-L/1E-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1E-L In
8.8286
MagneticCopper
BUS-L/1E-L
BUS-L/1E-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1E-R In
BUS-TR-1F-SEC
BUS-L/1F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1F In
8.8286
MagneticCopper
BUS-TR-1G-SEC
BUS-L/1G
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1G In
8.8286
MagneticCopper
BUS-TR-1G-A-SEC
BUS-L/1G-A
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1G-A In
8.8286
MagneticCopper
BUS-TR-1H-SEC
BUS-L/1H-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1H-L In
BUS-L/1H-L
BUS-L/1H-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1H-R In
8.8286
MagneticCopper
BUS-TR-1J-SEC
BUS-L/1J-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1J-L In
8.8286
MagneticCopper
BUS-L/1J-L
BUS-L/1J-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1J-R In
8.8286
MagneticCopper
BUS-TR-1K-SEC
BUS-L/1K-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1K-L In
BUS-L/1K-L
BUS-L/1K-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1K-R In
8.8286
MagneticCopper
BUS-L/1L-R
BUS-L/1L-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1L-L In
8.8286
MagneticCopper
BUS-TR-1L-SEC
BUS-L/1L-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1L-R In
8.8286
MagneticCopper
BUS-TR-1M-SEC 1 6 2 PVC Pos: 2.8014 0.8113CBL-L/1M In MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
BUS-L/1M Zero: 1.9970 8.8286
BUS-TR-1N-SEC
BUS-L/1N
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/1N In
8.8286
MagneticCopper
BUS-L/2C-R
BUS-L/2C-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2C-L In
8.8286
MagneticCopper
BUS-TR-2C-SEC
BUS-L/2C-R
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-L/2C-R In
11.7715
MagneticCopper
BUS-L/2D-R
BUS-L/2D-L
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/2D-L In
4.4573
BUS-TR-2D-SEC
BUS-L/2D-R
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/2D-R In
4.4573
MagneticCopper
BUS-TR-2E-SEC
BUS-L/2E-L
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/2E-L In
4.4573
MagneticCopper
BUS-L/2E-L
BUS-L/2E-R
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/2E-R In
4.4573
MagneticCopper
BUS-TR-2F-SEC
BUS-L/2F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2F In
BUS-TR-2G-SEC
BUS-L/2G
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-L/2G In
11.7715
MagneticCopper
BUS-TR-2H-SEC
BUS-L/2H-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2H-L In
8.8286
MagneticCopper
BUS-L/2H-L
BUS-L/2H-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2H-R In
8.8286
MagneticCopper
BUS-TR-2J-SEC
BUS-L/2J-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2J-L In
BUS-L/2J-L
BUS-L/2J-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2J-R In
8.8286
MagneticCopper
BUS-TR-2K-SEC
BUS-L/2K-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2K-L In
8.8286
MagneticCopper
BUS-L/2K-L
BUS-L/2K-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2K-R In
8.8286
MagneticCopper
BUS-TR-2L-SEC
BUS-L/2L-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2L-L In
BUS-L/2L-L
BUS-L/2L-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/2L-R In
8.8286
MagneticCopper
BUS-TR-2M-SEC
BUS-L/2M
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-L/2M In
14.0292
MagneticCopper
BUS-TR-2N-SEC
BUS-L/2N
1 6 4 PVC Pos:
Zero:
4.4517 0.8765
2.1579
CBL-L/2N In
14.0292
MagneticCopper
BUS-0549
BUS-L/3B-L
1 1 Pos:
Zero:
0.0000 0.0000
0.0000
CBL-L/3B-L In
0.0000
Non-MagneticCopper
From Bus
To Bus
Qty
/Ph
Length
Feet
------ Cable Description ------
Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base)
R pu jX pu
In/Out
Service
BUS-L/3B-L
BUS-L/3B-R
1 1 Pos:
Zero:
0.0000 0.0000
0.0000
CBL-L/3B-R In
0.0000
Non-MagneticCopper
BUS-L/3C-R
BUS-L/3C-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/3C-L In
8.8286
MagneticCopper
BUS-TR-3C-SEC
BUS-L/3C-R
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/3C-R In
8.8286
MagneticCopper
BUS-L/3D-R
BUS-L/3D-L
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/3D-L In
4.4573
BUS-TR-3D-SEC
BUS-L/3D-R
1 6 2/0 PVC Pos:
Zero:
1.4146 0.7392
1.8195
CBL-L/3D-R In
4.4573
MagneticCopper
BUS-L/3E-R
BUS-L/3E-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/3E-L In
8.8286
MagneticCopper
BUS-TR-3E-SEC
BUS-L/3E-R
1 8 2 PVC Pos:
Zero:
3.7352 1.0817
2.6627
CBL-L/3E-R In
11.7715
MagneticCopper
BUS-TR-3F-SEC
BUS-L/3F
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/3F In
BUS-TR-3G-SEC
BUS-L/3G
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/3G In
8.8286
MagneticCopper
BUS-TR-3H-SEC
BUS-L/3H-L
1 6 2 PVC Pos:
Zero:
2.8014 0.8113
1.9970
CBL-L/…