Exhibit M - NLR Complete Study Report Updated.pdf

PDF 22 MB Posted

Attached to
J061--Electrical System Preventive Maintenance And Testing Services Federal contract opportunity
Solicitation number
36C25622Q1188
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This solicitation is for electrical system preventive maintenance and testing services at two VA medical centers in Little Rock and North Little Rock, Arkansas. Interested parties must be veteran-owned small businesses and registered in SAM and VIP databases by the August 22nd deadline for submitting any questions. Quotes are due by August 29th and must include pricing, certifications, and representations. A mandatory site visit will be held on August 18th at noon at the North Little Rock facility, after which attendees may view the Little Rock location. The services sought include preventive maintenance, testing, repair, and emergency services for electrical systems at the two medical centers.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs North Little Rock Veterans Affairs Medical Center

North Little Rock, Arkansas

VISN 16

ELECTRICAL DISTRIBUTION

SYSTEM CONDITION ASSESSMENT

Study Update

Prepared by:

E.K. FOX & ASSOCIATES, LTD.

CONSULTING ENGINEERS

4500 Southgate Place, Suite 800, Chantilly, VA 20151

July 31, 2020

36C25622Q1188 0001 Exhibit M

North Little Rock VAMC – North Little Rock, Arkansas Electrical Condition Assessment - Update

Prepared for: Dept. of Veterans Affairs Page 1 Prepared by: E.K. Fox & Associates, Ltd.

4500 Southgate Place, Suite 800 Chantilly, VA 20151

TABLE OF CONTENTS

1. EXECUTIVE SUMMARY

2. INTRODUCTION

2.1. Personnel

2.2. Calculation Methods

2.3. Study Assumptions

3. FAULT CURRENT ANALYSIS

3.1. Introduction

3.2. Sources of Fault Current

3.3. Calculation Scenarios

3.4. SKM Power*Tools Input Data Reports

3.5. Short Circuit Calculation Results

3.6. Equipment Evaluation Results

4. PROTECTIVE DEVICE COORDINATION STUDY

4.1. Introduction

4.2. Existing and Proposed Protective Device Settings

4.3. Underrated Feeders

4.4. Replacement System Components

4.5. Analysis and Recommendations

4.6. Time-Current Characteristic Graphs Descriptions and Analysis

4.7. Time-Current Characteristic Graphs

5. ARC FLASH HAZARD ANALYSIS

5.1. Introduction

5.2. Basis of Study

5.3. Disclaimer

5.4. Results

APPENDICES

A. One-Line Diagrams

Prepared for: Dept. of Veterans Affairs Section 1 Page 1 Prepared by: E.K. Fox & Associates, Ltd.

1. EXECUTIVE SUMMARY

In 2015, The Department of Veterans Affairs – Office of Construction and Facilities Management (CFM), commissioned E.K. Fox and Associates, Ltd. (EKFox) to perform the electrical system condition assessment of the North Little Rock Veterans Affairs Medical Center (VAMC). The scope of the assessment was to provide short circuit analysis, protective device coordination study, voltage drop analysis, arc flash hazard analysis, and equipment condition assessment with the purpose of improving the safety and reliability of the electrical distribution system. The report containing the findings and recommended corrections was delivered to the VA CFM and the VAMC in 2016.

The findings and recommended corrections addressed numerous issues that ranged from safety and code related items, to coordination adjustments to reduce nuisance trips, and equipment replacement to address aging or damaged equipment. Safety related items are a higher priority and require a more immediate response whereas some coordination and condition-related equipment replacements allow for more flexibility in how soon they need to be addressed.

Currently, Cornerstone Contracting, Inc. (CCI) is implementing the recommended corrections based on findings from the previous study. Based on the project scope of work (SOW), the equipment replacements and adjustments being provided by CCI are primarily to address the previous coordination adjustments and equipment condition-related findings. However, the CCI SOW does not cover all of the recommended corrective actions that were in the previous study.

EKFox has been tasked with providing an update to the original report and analyses. In lieu of a new complete site survey, EKFox has performed the analyses using input from CCI, the VA, and equipment vendors to update the software model and electrical analyses. In some cases, certain assumptions were necessary to perform the report updates. These assumptions have been detailed in Section 2. Also, the SOW does not specifically state if all of the other recommended corrections had been performed under a previous effort. For example, it is likely that the higher priority activity of replacing the “failed” circuit breakers identified in the device evaluation would have been accomplished under a separate, nearer-term effort. Therefore, we have taken the more conservative approach to re-report these findings, which can then be field verified to determine if they have already been addressed or are still needing correction.

Our updated short circuit analysis, which aims to identify if circuit breakers can safely interrupt the fault current due to a short, has currently shown eleven (11) overcurrent protection devices (OCPD’s) have failed the device evaluation for interrupting capacity. However, it is possible that some or all of these failed devices have been replaced since the original study with ones that meet the required ratings. These eleven (11) OCPD’s were also reported as failed in the previous study. No new failed devices were identified in the current study. Section 3 of this report has additional details.

The updated protective device coordination study uses the current fixed and adjustable settings of the existing OCPD’s to graphically display how those devices will respond to a short or overload event. The settings are then adjusted to allow the protective device closest to the fault to interrupt the circuit thereby minimizing the disruption of electrical service. Our study currently identifies ten

(10) OCPD’s that may require settings adjustment or replacement to either better coordinate

Prepared for: Dept. of Veterans Affairs Section 1 Page 2 Prepared by: E.K. Fox & Associates, Ltd.

with other OCPD’s or to provide the correct level of protection for downstream conductors. Some of these current recommendations are due to the fact that adjustment and replacement certain OCPD’s was recommended in the previous coordination study but did not seem to appear in the CCI SOW. There are five (5) new, recommended adjustments that are due to the fact that some of the new replacement panels in Building 170 have circuit breakers that have slightly different trip curves than what was used for the previous coordination study. Additional details can be found in Section 4: Protective Device Coordination Study. We also include the time/current characteristic (TCC) graphs, which that show the interaction of the OCPD’s with the existing and recommended settings applied, in Section 4.

Finally, we performed an updated arc flash hazard analysis to determine the incident energy released by an arcing fault at the location of each device in the electrical distribution system. This analysis is also used to determine safe working distances and the required personal protective equipment (PPE) for personnel working in the panel. The results show a total of one (1) bus in Building 170 and thirty-three (33) buses for the secondary buildings that have an incident energy level at or above 40 cal/cm2. It should be noted that the majority of these buses are located at the secondaries of the service transformers to the buildings. EKFox will also provide an updated set of arc flash labels that can be applied to the panels and equipment to warn of the potential electrical dangers.

Additional details of the arc flash analysis can be found in Section 5.

Prepared for: Dept. of Veterans Affairs Section 2 Page 1 Prepared by: E.K. Fox & Associates, Ltd.

2. INTRODUCTION

2.1. Personnel

The EKFox Team that produced this report consisted of highly skilled engineers and technicians. They were:

Raleigh Stewart, P.E. RDStewart@ekfox.com (703-267-6783)

Charles Sisung, P.E. CFSisung@ekfox.com (877-520-4771 x105)

Jarrett Elliott JCElliott@ekfox.com

Tasha Laura TJLaura@ekfox.com

2.2. Calculation Methods

As mentioned, this study includes the following elements: short circuit calculations, overcurrent protective device coordination, voltage drop analysis, arc flash hazard analysis, and a condition assessment of electrical equipment.

All calculations have been performed using software developed by SKM Systems Analysis, Inc. The software is named Power*Tools, Version 9.0.0.3 and it is a modular assembly of programs. The following modules have been used for this study:

System Model Development DAPPER Short Circuit Calculations Comprehensive Fault Evaluation Protective Device Coordination CAPTOR Voltage Drop Analysis DAPPER Arc Flash Hazard Analysis Arc Flash Evaluation Device Evaluation Equipment Evaluation

Version 9.0.0.3 of the Power*Tools software has been used for all of the calculations presented throughout this report. Additional information related to this software package can be found at www.skm.com.

2.3. Study Assumptions

The EKFox team has attempted, to the extent practical, to provide accurate updates for the previous study. In some cases, certain assumptions had to be made as a compromise between the project scope, available and provided equipment information, and required inputs to the software model. The following describes types of data that has been assumed for the purposes of this study:

Prepared for: Dept. of Veterans Affairs Section 2 Page 2 Prepared by: E.K. Fox & Associates, Ltd.

2.3.1. Utility Information

Updated utility fault current information and system parameters were not provided for this analysis. As such, the utility information used in the previous study has been used for these analyses.

2.3.2. Replacement System Components

When complete equipment information was provided for a replacement system component, the model was updated to reflect this information. For items where some information was missing (e.g. breaker type, trip setting, etc.) The previous survey information, previous proposed study recommendation, or engineering judgment was used to fill in the missing information. In cases where the information for a replacement component (e.g. a larger ampacity breaker replacing a smaller ampacity breaker with no change to conductor size) conflicted with the original surveyed information (or introduced a new code or safety related issue), it was assumed that the replacement would have been adjusted or substituted to match the original equipment size or setting.

2.3.3. Previous Study Coordination Recommendations

The current study assumes that all of the previous study recommended coordination changes and replacements have been applied to the system. The updated coordination study has been accomplished by coordinating the replacement system components with the results from the previous coordination study.

2.3.4. Previous Study Device Evaluation Analysis

It is likely that some of the devices that failed the previous fault current and device evaluation analyses have been replaced prior to this project. However, the device parameters were not updated unless equipment information was provided to do so. Thus, devices that failed the current device evaluation should be field verified to determine if they were replaced as part of a previous effort or that the device requires immediate replacement.

2.3.5. Newly Added Equipment or Areas

The scope of equipment and areas for the present study only includes the equipment and areas that were part of the previous study. No equipment or survey information was provided for any newly added equipment or areas, so they have not been considered in this study.

Prepared for: Dept. of Veterans Affairs Section 3 Page 1 Prepared by: E.K. Fox & Associates, Ltd.

3. FAULT CURRENT ANALYSIS

3.1. Introduction

The fault current analysis is developed based on data for the North Little Rock VAMC electrical distribution system. The analysis examines the short circuit currents that occur at selected locations in the electrical system and is used to determine the capability of the system to withstand an electrical fault without damage.

Due to the size and complexity of Patient Building #170 and the overall campus, the original electrical studies were performed with separate SKM project models – one (1) for Building #170 and one (1) for the secondary buildings (i.e. the buildings for the rest of the campus).

The present study update has kept this separation between the two (2) projects.

One-line diagrams of the system are included in Appendix A. Reports showing the complete input data used to construct each model are included in Section 3.4.

3.2. Sources of Fault Current

The short circuit fault current calculations performed for the North Little Rock VAMC electrical system are based on the available fault current information that was originally obtained from the utility (City of North Little Rock Electrical Department) for the original study.

In summary, the available fault current from the City of North Little Rock system is:

Supply from Source 1 Feeder (Westgate Substation):

Max Fault 3phase: 2773.2 A Max Fault 3phase to Ground: 2773.2 A Max Fault Phase to Phase: 2401.7 A Max Fault 2 phases to Ground: 2552.5 A Max Fault Phase to Ground: 1995.0 A Min Fault: 191.7 A

Transformer: 18 MVA base, %Z=9.45, Primary 115kV Transmission (Delta) Secondary 13.8kV Y-grounded

Prepared for: Dept. of Veterans Affairs Section 3 Page 2 Prepared by: E.K. Fox & Associates, Ltd.

Supply from Source 2 Feeder (Levy 2 Substation):

Max Fault 3phase: 1980.0 A Max Fault 3phase to Ground: 1890.0 A Max Fault Phase to Phase: 1636.8 A Max Fault 2 phases to Ground: 1705.2 A Max Fault Phase to Ground: 1233.3 A Min Fault: 198.8 A

Transformer: 30 MVA base, %Z=12.07 Primary 115kV Transmission (Delta) Secondary 13.8kV Y‐grounded

Additional sources of short circuit fault current are the induction motors which operate throughout the system. Typically, these motor contributions are relatively small especially when a fault is located some distance from the motor, and when a motor is under 50HP.

3.3. Calculation Scenarios

The original report included three (3) scenarios that will be revisited in this analysis. These scenarios are run in both the Secondary Buildings project model and the Building 170 project model. The first DAPPER report included in this submission for each project is based on the normal interconnection of the electrical power system elements fed by the utility service.

Additional reports for this system were generated for two (2) other scenarios. The three (3) total scenarios are summarized in the table below.

Scenario Utility Feeds Tie Breaker Generators ATS’s Normal Interconnection

Utility Feeds Active

Out Out Normal Pos.

All Loads on Larger Utility Feed

Only Larger Utility Feed Active

Active Out Normal Pos.

Emergency – On Generator

Out

Out Active Emergency Pos.

3.4. SKM Power*Tools Input Data Reports

The included DAPPER input reports list the system components used to calculate the short circuit currents for the Normal Interconnection scenario in each project described above.

Additional input reports were generated and used for calculations for the other scenarios, but only the report for the Normal Interconnection scenario for each project is included here for brevity. The reports for the other scenarios are included in the soft copy disc.

DAPPER Fault Analysis Input Report (English)

Project: VA NLR BLDG 170

Normal Utility

Utilities

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data -------- PU (100 MVA Base)

X PUR PUX/RUnitsDuty

UTIL-LEVY 2 MAIN 2 SG 13,800 Amps 8.00In 1,980

SLG:

3P:

Amps 8.00 5.905 0.738

Pos:

Zero: 1,233

0.262 2.097

UTIL-WESTGATE 2 MAIN 1 SG 13,800 Amps 8.00In 2,773

SLG:

3P:

Amps 8.00 3.249 0.406

Pos:

Zero: 1,995

0.187 1.497

Generators

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

-------- Contribution Data --------

Base kVA X" X/R

PU (100 MVA Base)

R PU X PU

GEN-0001 480BUS-0029 625.00 20.00 0.00 0.00Out

0.00

0.00 0.00

0.15

0.15

0.15

20.00

20.00 0.00

GEN-0002 480BUS-0030 625.00 20.00 0.00 0.00Out

0.00

0.00 0.00

0.15

0.15

0.15

20.00

20.00 0.00

Motors

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

AIR-COMP-1 BUS-0581 480 10.03 0.1692 10.00 168.695 1,687.015In 1

AIR-COMP-2 BUS-0582 480 10.03 0.1692 10.00 168.695 1,687.015In 1

AIR-DRYER-2 BUS-0583 480 10.03 0.1692 10.00 168.695 1,687.015In 1

CHILLER 1 BUS-0591 480 618.28 0.1692 10.00 2.513 25.127In 1

CHILLER 2 BUS-0592 480 586.02 0.1692 10.00 2.651 26.510In 1

Contribution

From Name

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

CHILLER 3 BUS-0593 480 331.99 0.1692 10.00 4.679 46.794In 1

CT-1 BUS-0523 480 50.13 0.1692 10.00 33.739 337.403In 1

CT-2 BUS-0524 480 50.13 0.1692 10.00 33.739 337.403In 1

EF-103 BUS-0587 480 5.01 0.1692 10.00 337.390 3,374.031In 1

EF-40 BUS-0588 480 5.01 0.1692 10.00 337.390 3,374.031In 1

ELEV. P1 BUS-0401 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. P2 BUS-0402 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. P3 BUS-0404 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. P4 BUS-0405 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. P5 BUS-0495 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. P6 BUS-0496 480 50.13 0.1692 10.00 33.739 337.403In 1

ELEV. S11 BUS-0497 480 60.16 0.1692 10.00 28.116 281.169In 1

ELEV. S12 BUS-0494 480 60.16 0.1692 10.00 28.116 281.169In 1

ELEV. S14 BUS-0434 480 40.11 0.1692 10.00 42.174 421.754In 1

ELEV. S7 BUS-0406 480 60.16 0.1692 10.00 28.116 281.169In 1

ELEV. S9 BUS-0403 480 60.16 0.1692 10.00 28.116 281.169In 1

EMCC/P1-LOAD BUS-0584 480 5.01 0.1692 10.00 84.347 843.508In 4

GG-100 BUS-0554 480 5.01 0.1692 10.00 337.390 3,374.031In 1

JOCKEY-PUMP BUS-0578 480 10.03 0.1692 10.00 168.695 1,687.015In 1

MCP/1-LOAD BUS-0556 480 1.00 0.1692 10.00 105.434 1,054.385In 16

MCP/2-LOAD BUS-0557 480 1.75 0.1692 10.00 64.265 642.673In 15

MCP/GA1-LOAD BUS-0562 480 2.01 0.1692 10.00 168.695 1,687.015In 5

MCP/GA2-LOAD BUS-0568 480 2.01 0.1692 10.00 168.695 1,687.015In 5

MCP/GB-LOAD BUS-0572 480 3.01 0.1692 10.00 187.439 1,874.462In 3

MCP/GK-LOAD BUS-0574 480 2.51 0.1692 10.00 168.695 1,687.015In 4

MED-AIR-1 BUS-0579 480 10.03 0.1692 10.00 168.695 1,687.015In 1

MED-AIR-2 BUS-0580 480 10.03 0.1692 10.00 168.695 1,687.015In 1

MED-VAC-1 BUS-0576 480 10.03 0.1692 10.00 168.695 1,687.015In 1

MED-VAC-2 BUS-0577 480 10.03 0.1692 10.00 168.695 1,687.015In 1

P-1 BUS-0540 480 15.04 0.1692 10.00 112.463 1,124.677In 1

P-10 BUS-0522 480 50.13 0.1692 10.00 33.739 337.403In 1

P-17 BUS-0534 480 1.50 0.1692 10.00 1124.632 11,246.770In 1

P-17A BUS-0535 480 1.50 0.1692 10.00 1124.632 11,246.770In 1

P-2 BUS-0575 480 15.04 0.1692 10.00 112.463 1,124.677In 1

P-22 BUS-0541 480 1.50 0.1692 10.00 1124.632 11,246.770In 1

P-23 BUS-0539 480 30.08 0.1692 10.00 56.232 562.338In 1

P-24 BUS-0533 480 1.50 0.1692 10.00 1124.632 11,246.770In 1

P-26 BUS-0536 480 1.50 0.1692 10.00 1124.632 11,246.770In 1

P-3 BUS-0537 480 30.08 0.1692 10.00 56.232 562.338In 1

P-4 BUS-0538 480 30.08 0.1692 10.00 56.232 562.338In 1

P-5 BUS-0530 480 20.05 0.1692 10.00 84.347 843.508In 1

P-6 BUS-0532 480 20.05 0.1692 10.00 84.347 843.508In 1

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

P-7 BUS-0531 480 20.05 0.1692 10.00 84.347 843.508In 1

P-8 BUS-0520 480 50.13 0.1692 10.00 33.739 337.403In 1

P-9 BUS-0521 480 50.13 0.1692 10.00 33.739 337.403In 1

RF-1 BUS-0551 480 7.52 0.1692 10.00 224.926 2,249.354In 1

RF-10 BUS-0442 480 7.52 0.1692 10.00 224.926 2,249.354In 1

RF-11G BUS-0567 480 5.01 0.1692 10.00 337.390 3,374.031In 1

RF-12 BUS-0553 480 5.01 0.1692 10.00 337.390 3,374.031In 1

RF-4 BUS-0397 480 25.07 0.1692 10.00 67.478 674.806In 1

RF-4A BUS-0489 480 25.07 0.1692 10.00 67.478 674.806In 1

RF-5 BUS-0399 480 25.07 0.1692 10.00 67.478 674.806In 1

RF-5A BUS-0488 480 25.07 0.1692 10.00 67.478 674.806In 1

RF-6 BUS-0398 480 20.05 0.1692 10.00 84.347 843.508In 1

RF-6A BUS-0487 480 25.07 0.1692 10.00 67.478 674.806In 1

RF-7 BUS-0400 480 20.05 0.1692 10.00 84.347 843.508In 1

RF-7A BUS-0486 480 20.05 0.1692 10.00 84.347 843.508In 1

RF-8 BUS-0471 480 7.52 0.1692 10.00 224.926 2,249.354In 1

SF/RF-1A BUS-0552 480 3.01 0.1692 10.00 281.158 2,811.692In 2

SF/RF-1B BUS-0555 480 3.01 0.1692 10.00 281.158 2,811.692In 2

SF-1 BUS-0550 480 30.08 0.1692 10.00 56.232 562.338In 1

SF-10 BUS-0441 480 25.07 0.1692 10.00 67.478 674.806In 1

SF-11A BUS-0563 480 5.01 0.1692 10.00 337.390 3,374.031In 1

SF-11B BUS-0558 480 5.01 0.1692 10.00 337.390 3,374.031In 1

SF-11C BUS-0564 480 10.03 0.1692 10.00 168.695 1,687.015In 1

SF-11D BUS-0559 480 10.03 0.1692 10.00 168.695 1,687.015In 1

SF-11E BUS-0565 480 10.03 0.1692 10.00 168.695 1,687.015In 1

SF-11F BUS-0560 480 10.03 0.1692 10.00 168.695 1,687.015In 1

SF-11G BUS-0566 480 20.05 0.1692 10.00 84.347 843.508In 1

SF-11H BUS-0561 480 10.03 0.1692 10.00 168.695 1,687.015In 1

SF-13 BUS-0573 480 20.05 0.1692 10.00 84.347 843.508In 1

SF-15 BUS-0569 480 5.01 0.1692 10.00 337.390 3,374.031In 1

SF-16 BUS-0586 480 15.04 0.1692 10.00 112.463 1,124.677In 1

SF-2 BUS-0570 480 15.04 0.1692 10.00 112.463 1,124.677In 1

SF-3 BUS-0571 480 20.05 0.1692 10.00 84.347 843.508In 1

SF-4 BUS-0407 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-4A BUS-0490 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-5 BUS-0409 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-5A BUS-0491 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-6 BUS-0410 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-6A BUS-0492 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-7 BUS-0408 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-7A BUS-0493 480 75.20 0.1692 10.00 22.493 224.935In 1

SF-8 BUS-0470 480 40.11 0.1692 10.00 42.174 421.754In 1

Bus

Name

In/Out

Service

Nominal

Voltage

--------- Contribution Data --------

Base kVA Xd" X/R

PU (100 MVA Base)

R PU X PU

# of

Motors

SM COOLING BUS-0594 480 100.27 0.1692 10.00 16.869 168.702In 1

Cables

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-0543

BUS-(GE-114)

1 100 4/0 PVC Pos:

Zero:

14.7929 11.4876

28.2914

CBL-(GE-114) In

46.6208

MagneticCopper

BUS-SS3

BUS-0591

3 135 500 PVC Pos:

Zero:

0.5742 0.9102

2.2402

CBL-CHILLER 1 In

1.8086

MagneticCopper

BUS-SS3

BUS-0592

3 120 500 PVC Pos:

Zero:

0.5104 0.8090

1.9913

CBL-CHILLER 2 In

1.6076

MagneticCopper

BUS-SS4

BUS-0593

2 120 350 PVC Pos:

Zero:

0.9844 1.2786

3.1484

CBL-CHILLER 3 In

3.1016

MagneticCopper

BUS-SS1-A

BUS-D/GB

1 50 500 PVC Pos:

Zero:

0.6380 1.0113

2.4891

CBL-D/GB In

2.0095

MagneticCopper

BUS-D/GB

BUS-MCP/GB

1 100 4/0 PVC Pos:

Zero:

2.7778 2.1571

5.3125

CBL-D/GB-1 In

8.7543

MagneticCopper

BUS-D/GB

BUS-H/GB

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-D/GB-2 In

1.6578

MagneticCopper

BUS-D/GB

BUS-TR-GB-PRI

1 30 6 PVC Pos:

Zero:

6.6406 0.6836

1.6836

CBL-D/GB-3 In

20.9271

BUS-D/GB

BUS-TR-1B-PRI

1 16 6 PVC Pos:

Zero:

3.5417 0.3646

0.8979

CBL-D/GB-4 In

11.1611

MagneticCopper

BUS-D/GB 1 65 6 PVC Pos:

Zero:

14.3880 1.4811

3.6478

CBL-D/GB-5 In

45.3420

MagneticCopper

BUS-D/GB

BUS-TR-2B-PRI

1 100 1/0 PVC Pos:

Zero:

5.5556 1.7969

4.4227

CBL-D/GB-6 In

17.5087

MagneticCopper

BUS-D/GB

BUS-ATS-GB (N)

1 8 3/0 PVC Pos:

Zero:

0.2795 0.1802

0.4438

CBL-D/GB-7 In

0.8809

BUS-D/GB

BUS-TR-GB1-A-PRI

1 30 8 PVC Pos:

Zero:

10.5599 0.7513

1.8490

CBL-D/GB-8 In

33.2799

MagneticCopper

BUS-SS1-A

BUS-D/GE

2 395 500 PVC Pos:

Zero:

2.5202 3.9946

9.8321

CBL-D/GE In

7.9377

MagneticCopper

BUS-D/GE

BUS-MCC/GE

1 10 4/0 PVC Pos:

Zero:

0.2778 0.2157

0.5313

CBL-D/GE-1 In

0.8754

MagneticCopper

BUS-D/GE

BUS-TR-GA-PRI

1 150 6 PVC Pos:

Zero:

33.2031 3.4180

8.4180

CBL-D/GE-10 In

104.6354

BUS-D/GE

BUS-TR-2E-PRI

1 160 4 PVC Pos:

Zero:

22.2917 3.3542

8.2569

CBL-D/GE-11 In

70.2500

MagneticCopper

BUS-D/GE

BUS-TR-3E-PRI

1 170 6 PVC Pos:

Zero:

37.6302 3.8737

9.5404

CBL-D/GE-12 In

118.5868

MagneticCopper

Cable

Name

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-D/GE

BUS-H/GE

1 25 2 PVC Pos:

Zero:

2.1918 0.6348

1.5625

CBL-D/GE-2 In

6.9076

MagneticCopper

BUS-D/GE

BUS-ATS-GE (N)

1 20 4/0 PVC Pos:

Zero:

0.5556 0.4314

1.0625

CBL-D/GE-3 In

1.7509

BUS-TR-1E-PRI

1 150 6 PVC Pos:

Zero:

33.2031 3.4180

8.4180

CBL-D/GE-4 In

104.6354

MagneticCopper

BUS-D/GE

BUS-TR-GE-PRI

1 8 250 PVC Pos:

Zero:

0.1917 0.1316

0.3240

CBL-D/GE-5 In

0.6038

MagneticCopper

BUS-D/GE

BUS-TR-1D-PRI

1 285 6 PVC Pos:

Zero:

63.0859 6.4941

15.9941

CBL-D/GE-6 In

198.8073

MagneticCopper

BUS-D/GE

BUS-H/GA

1 150 2 PVC Pos:

Zero:

13.1510 3.8086

9.3750

CBL-D/GE-7 In

41.4453

BUS-TR-2D-PRI

1 295 4 PVC Pos:

Zero:

41.1003 6.1842

15.2237

CBL-D/GE-8 In

129.5235

MagneticCopper

BUS-D/GE

BUS-TR-3D-PRI

1 305 4 PVC Pos:

Zero:

42.4935 6.3939

15.7398

CBL-D/GE-9 In

133.9141

MagneticCopper

BUS-SS1-A

BUS-D/GF

1 255 500 PVC Pos:

Zero:

3.2539 5.1576

12.6947

CBL-D/GF In

10.2487

MagneticCopper

BUS-D/GF

BUS-ATS-GF (N)

1 10 4/0 PVC Pos:

Zero:

0.2778 0.2157

0.5313

CBL-D/GF-1 In

0.8754

BUS-D/GF

BUS-TR-GF-PRI

1 25 6 PVC Pos:

Zero:

5.5339 0.5697

1.4030

CBL-D/GF-10 In

17.4392

MagneticCopper

BUS-D/GF

BUS-H/GF

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

CBL-D/GF-2 In

5.5260

MagneticCopper

BUS-D/GF

BUS-H/1F

1 45 2 PVC Pos:

Zero:

3.9453 1.1426

2.8125

CBL-D/GF-3 In

12.4336

MagneticCopper

BUS-D/GF

BUS-H/2F

1 80 2 PVC Pos:

Zero:

7.0139 2.0313

5.0000

CBL-D/GF-4 In

22.1042

BUS-H/3F

1 90 2 PVC Pos:

Zero:

7.8906 2.2852

5.6250

CBL-D/GF-5 In

24.8672

MagneticCopper

BUS-D/GF

BUS-MCP/GA1

1 255 2 PVC Pos:

Zero:

22.3568 6.4746

15.9375

CBL-D/GF-6 In

70.4570

MagneticCopper

BUS-D/GF

BUS-TR-2C-PRI

1 285 6 PVC Pos:

Zero:

63.0859 8.4733

20.8678

CBL-D/GF-7 In

198.8073

MagneticCopper

BUS-D/GF

BUS-TR-1C-PRI

1 16 6 PVC Pos:

Zero:

3.5417 0.3646

0.8979

CBL-D/GF-8 In

11.1611

BUS-TR-3C-PRI

1 295 6 PVC Pos:

Zero:

65.2995 6.7220

16.5553

CBL-D/GF-9 In

205.7830

MagneticCopper

BUS-SS1-B

BUS-D/GG

1 450 250 PVC Pos:

Zero:

10.7813 9.6680

23.8086

CBL-D/GG In

33.9648

MagneticCopper

BUS-D/GG

BUS-TR-1G-PRI

1 40 6 PVC Pos:

Zero:

8.8542 0.9115

2.2448

CBL-D/GG-1 In

27.9028

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-D/GG

BUS-TR-2G-PRI

1 70 8 PVC Pos:

Zero:

24.6398 1.7530

4.3142

CBL-D/GG-2 In

77.6532

BUS-D/GG

BUS-TR-3G-PRI

1 80 8 PVC Pos:

Zero:

28.1597 2.0035

4.9306

CBL-D/GG-3 In

88.7465

MagneticCopper

BUS-D/GG

BUS-TR-GG-PRI

1 6 10 PVC Pos:

Zero:

3.0729 0.1703

0.4193

CBL-D/GG-4 In

9.6844

MagneticCopper

BUS-D/GG

BUS-TR-1G-A-PRI

1 40 8 PVC Pos:

Zero:

14.0799 1.0017

2.4653

CBL-D/GG-5 In

44.3733

MagneticCopper

BUS-SS2-B

BUS-D/GH

1 280 500 PVC Pos:

Zero:

3.5729 5.6632

13.9392

CBL-D/GH In

11.2535

BUS-D/GH

BUS-ATS-GH (N)

1 40 2 PVC Pos:

Zero:

3.5069 1.0156

2.5000

CBL-D/GH-1 In

11.0521

MagneticCopper

BUS-D/GH

BUS-H/GH

1 10 2 PVC Pos:

Zero:

0.8767 0.2539

0.6250

CBL-D/GH-2 In

2.7630

MagneticCopper

BUS-D/GH

BUS-TR-GH-PRI

1 6 2 PVC Pos:

Zero:

0.5260 0.1167

0.2872

CBL-D/GH-3 In

1.6578

MagneticCopper

BUS-D/GH

BUS-TR-2H-PRI

1 80 6 PVC Pos:

Zero:

17.7083 1.8229

4.4896

CBL-D/GH-4 In

55.8056

BUS-D/GH

BUS-TR-3H-PRI

1 90 6 PVC Pos:

Zero:

19.9219 2.0508

5.0508

CBL-D/GH-5 In

62.7813

MagneticCopper

BUS-D/GH

BUS-TR-1H-PRI

1 70 6 PVC Pos:

Zero:

15.4948 1.5951

3.9284

CBL-D/GH-6 In

48.8299

MagneticCopper

BUS-SS2-A

BUS-D/GJ

2 45 500 PVC Pos:

Zero:

0.2871 0.4551

1.1201

CBL-D/GJ In

0.9043

MagneticCopper

BUS-D/GJ

BUS-0441

1 50 6 PVC Pos:

Zero:

11.0677 1.4865

3.6610

CBL-D/GJ-1 In

34.8785

BUS-D/GJ

BUS-0442

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-D/GJ-12 In

127.8950

MagneticCopper

BUS-D/GJ

BUS-ATS-GJ (N)

2 6 250 PVC Pos:

Zero:

0.0719 0.0645

0.1587

CBL-D/GJ-2 In

0.2264

MagneticCopper

BUS-D/GJ

BUS-TR-1J-PRI

1 70 6 PVC Pos:

Zero:

15.4948 1.5951

3.9284

CBL-D/GJ-3 In

48.8299

MagneticCopper

BUS-D/GJ

BUS-H/GJ

1 30 2 PVC Pos:

Zero:

2.6302 0.7617

1.8750

CBL-D/GJ-4 In

8.2891

BUS-D/GJ

BUS-TR-2J-PRI

1 80 6 PVC Pos:

Zero:

17.7083 1.8229

4.4896

CBL-D/GJ-6 In

55.8056

MagneticCopper

BUS-D/GJ

BUS-TR-GJ-PRI

1 35 2/0 PVC Pos:

Zero:

1.5495 0.6183

1.5221

CBL-D/GJ-7 In

4.8824

MagneticCopper

BUS-D/GJ

BUS-TR-3J-PRI

1 90 6 PVC Pos:

Zero:

19.9219 2.0508

5.0508

CBL-D/GJ-8 In

62.7813

MagneticCopper

BUS-SS2-A 1 470 500 PVC Pos: 5.9974 9.5061CBL-D/GK In MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-D/GK Zero: 23.3980 18.8898

BUS-D/GK

BUS-ATS-GK (N)

1 20 4/0 PVC Pos:

Zero:

0.5556 0.4314

1.0625

CBL-D/GK-1 In

1.7509

MagneticCopper

BUS-D/GK

BUS-TR-GN-PRI

1 6 4 PVC Pos:

Zero:

0.8359 0.1258

0.3096

CBL-D/GK-10 In

2.6344

MagneticCopper

BUS-D/GK

BUS-TR-GK-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-D/GK-11 In

6.6560

MagneticCopper

BUS-D/GK

BUS-TR-1N-PRI

1 150 8 PVC Pos:

Zero:

52.7995 3.7565

9.2448

CBL-D/GK-12 In

166.3997

BUS-MCP/GK

1 30 2 PVC Pos:

Zero:

2.6302 0.7617

1.8750

CBL-D/GK-2 In

8.2891

MagneticCopper

BUS-D/GK

BUS-TR-LP1/LP2-PRI

1 195 1/0 PVC Pos:

Zero:

10.8333 3.5039

8.6243

CBL-D/GK-3 In

34.1419

MagneticCopper

BUS-D/GK

BUS-TR-2K-PRI

1 110 6 PVC Pos:

Zero:

24.3490 2.5065

6.1732

CBL-D/GK-4 In

76.7326

MagneticCopper

BUS-D/GK

BUS-TR-1K-PRI

1 100 6 PVC Pos:

Zero:

22.1354 2.2786

5.6120

CBL-D/GK-5 In

69.7570

BUS-TR-3K-PRI

1 120 6 PVC Pos:

Zero:

26.5625 2.7344

6.7344

CBL-D/GK-6 In

83.7083

MagneticCopper

BUS-D/GK

BUS-TR-2N-PRI

1 160 8 PVC Pos:

Zero:

56.3194 4.0069

9.8611

CBL-D/GK-7 In

177.4931

MagneticCopper

BUS-D/GK

BUS-TR-3N-PRI

1 170 8 PVC Pos:

Zero:

59.8394 4.2574

10.4774

CBL-D/GK-8 In

188.5864

MagneticCopper

BUS-D/GK

BUS-H2/GK

1 30 1/0 PVC Pos:

Zero:

1.6667 0.7031

1.7305

CBL-D/GK-9 In

5.2526

BUS-SS2-B

BUS-D/GL

2 660 350 PVC Pos:

Zero:

5.4141 7.0326

17.3164

CBL-D/GL In

17.0586

MagneticCopper

BUS-D/GL

BUS-TR-GL-PRI

1 20 250 PVC Pos:

Zero:

0.4792 0.3290

0.8099

CBL-D/GL-1 In

1.5095

MagneticCopper

BUS-D/GL

BUS-H/GL

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

CBL-D/GL-2 In

5.5260

MagneticCopper

BUS-D/GL

BUS-ATS-GL (N)

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

CBL-D/GL-3 In

5.5260

BUS-D/GL

BUS-0470

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

CBL-D/GL-4 In

13.8151

MagneticCopper

BUS-D/GL

BUS-TR-1L-PRI

1 100 6 PVC Pos:

Zero:

22.1354 2.2786

5.6120

CBL-D/GL-5 In

69.7570

MagneticCopper

BUS-D/GL

BUS-TR-3L-PRI

1 120 6 PVC Pos:

Zero:

26.5625 2.7344

6.7344

CBL-D/GL-6 In

83.7083

MagneticCopper

BUS-D/GL

BUS-TR-2L-PRI

1 110 6 PVC Pos:

Zero:

24.3490 2.5065

6.1732

CBL-D/GL-7 In

76.7326

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-D/GL

BUS-0471

1 50 10 PVC Pos:

Zero:

25.6076 1.8533

4.5638

CBL-D/GL-8 In

80.7031

MagneticCopper

BUS-SS2-A

BUS-D/GM

1 350 500 PVC Pos:

Zero:

4.4661 7.0790

17.4240

CBL-D/GM In

14.0668

MagneticCopper

BUS-D/GM

BUS-H/2M

1 60 2 PVC Pos:

Zero:

5.2604 1.5234

3.7500

CBL-D/GM-1 In

16.5781

MagneticCopper

BUS-D/GM

BUS-H/1M

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

CBL-D/GM-2 In

13.8151

BUS-D/GM

BUS-ATS-GM (N)

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-D/GM-3 In

1.6578

MagneticCopper

BUS-D/GM

BUS-H/3M

1 70 2 PVC Pos:

Zero:

6.1372 1.7773

4.3750

CBL-D/GM-4 In

19.3411

MagneticCopper

BUS-D/GM

BUS-H/GM

1 20 2 PVC Pos:

Zero:

1.7535 0.5078

1.2500

CBL-D/GM-5 In

5.5260

MagneticCopper

BUS-D/GM

BUS-MCP/GA2

1 295 2 PVC Pos:

Zero:

25.8637 7.4902

18.4375

CBL-D/GM-6 In

81.5091

BUS-D/GM

BUS-TR-GM-PRI

1 6 4 PVC Pos:

Zero:

0.8359 0.1258

0.3096

CBL-D/GM-9 In

2.6344

MagneticCopper

BUS-0033

BUS-ED/GB

1 20 3/0 PVC Pos:

Zero:

0.6988 0.4505

1.1094

CBL-ED/GB In

2.2023

MagneticCopper

BUS-ED/GB

BUS-EH/GB

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GB-1 In

1.6578

MagneticCopper

BUS-ED/GB

BUS-TR-E/1B-PRI

1 16 8 PVC Pos:

Zero:

5.6319 0.4007

0.9861

CBL-ED/GB-2 In

17.7493

BUS-ED/GB

BUS-TR-E/2B-PRI

1 25 8 PVC Pos:

Zero:

8.7999 0.6261

1.5408

CBL-ED/GB-3 In

27.7333

MagneticCopper

BUS-ED/GB 1 35 8 PVC Pos:

Zero:

12.3199 0.8765

2.1571

CBL-ED/GB-4 In

38.8266

MagneticCopper

BUS-ED/GB

BUS-TR-E/2B-B-PRI

1 30 3/0 PVC Pos:

Zero:

1.0482 0.5169

1.2734

CBL-ED/GB-5 In

3.3034

MagneticCopper

BUS-0034

BUS-ED/GE

1 20 4/0 PVC Pos:

Zero:

0.5556 0.4314

1.0625

CBL-ED/GE In

1.7509

BUS-ED/GE

BUS-TR-E/1D-PRI

1 285 8 PVC Pos:

Zero:

100.3190 7.1374

17.5651

CBL-ED/GE-1 In

316.1595

MagneticCopper

BUS-ED/GE

BUS-TR-E/GA-PRI

1 150 8 PVC Pos:

Zero:

52.7995 3.7565

9.2448

CBL-ED/GE-2 In

166.3997

MagneticCopper

BUS-ED/GE

BUS-TR-E/2D-PRI

1 295 8 PVC Pos:

Zero:

103.8390 7.3878

18.1814

CBL-ED/GE-3 In

327.2528

MagneticCopper

BUS-ED/GE

BUS-TR-E/1E-PRI

1 150 8 PVC Pos:

Zero:

52.7995 3.7565

9.2448

CBL-ED/GE-4 In

166.3997

BUS-TR-E/3D-PRI

1 305 8 PVC Pos:

Zero:

107.3589 7.6382

18.7977

CBL-ED/GE-5 In

338.3462

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-ED/GE

BUS-TR-E/2E-PRI

1 160 8 PVC Pos:

Zero:

56.3194 4.0069

9.8611

CBL-ED/GE-6 In

177.4931

MagneticCopper

BUS-ED/GE

BUS-TR-E/3G-PRI

1 365 8 PVC Pos:

Zero:

128.4787 9.1408

22.4957

CBL-ED/GE-7 In

404.9061

MagneticCopper

BUS-ED/GE

BUS-TR-E/3E-PRI

1 170 8 PVC Pos:

Zero:

59.8394 4.2574

10.4774

CBL-ED/GE-8 In

188.5864

BUS-TR-E/GE-PRI

1 20 8 PVC Pos:

Zero:

7.0399 0.5009

1.2326

CBL-ED/GE-9 In

22.1866

MagneticCopper

BUS-0035

BUS-ED/GF

1 15 4/0 PVC Pos:

Zero:

0.4167 0.3236

0.7969

CBL-ED/GF In

1.3132

MagneticCopper

BUS-ED/GF

BUS-EH/3F

1 90 2 PVC Pos:

Zero:

7.8906 2.2852

5.6250

CBL-ED/GF-1 In

24.8672

MagneticCopper

BUS-ED/GF

BUS-EH/1F

1 70 2 PVC Pos:

Zero:

6.1372 1.7773

4.3750

CBL-ED/GF-2 In

19.3411

BUS-ED/GF

BUS-EH/GF

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GF-3 In

1.6578

MagneticCopper

BUS-ED/GF

BUS-EH/2F

1 80 2 PVC Pos:

Zero:

7.0139 2.0313

5.0000

CBL-ED/GF-4 In

22.1042

MagneticCopper

BUS-ED/GF

BUS-TR-E/3C-PRI

1 295 8 PVC Pos:

Zero:

103.8390 7.3878

18.1814

CBL-ED/GF-5 In

327.2528

MagneticCopper

BUS-ED/GF

BUS-TR-E/2C-PRI

1 285 8 PVC Pos:

Zero:

100.3190 7.1374

17.5651

CBL-ED/GF-6 In

316.1595

BUS-ED/GF

BUS-TR-E/1C-PRI

1 275 8 PVC Pos:

Zero:

96.7990 6.8869

16.9488

CBL-ED/GF-7 In

305.0662

MagneticCopper

BUS-0036

BUS-ED/GH

1 40 2 PVC Pos:

Zero:

3.5069 1.0156

2.5000

CBL-ED/GH In

11.0521

MagneticCopper

BUS-ED/GH

BUS-EH/GH

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GH-1 In

1.6578

MagneticCopper

BUS-ED/GH

BUS-TR-E/1H-PRI

1 70 8 PVC Pos:

Zero:

24.6398 1.7530

4.3142

CBL-ED/GH-2 In

77.6532

BUS-ED/GH

BUS-TR-E/2H-PRI

1 80 8 PVC Pos:

Zero:

28.1597 2.6181

6.4444

CBL-ED/GH-4 In

88.7465

MagneticCopper

BUS-ED/GH

BUS-TR-E/3H-PRI

1 90 8 PVC Pos:

Zero:

31.6797 2.9453

7.2500

CBL-ED/GH-6 In

99.8399

MagneticCopper

BUS-0037

BUS-ED/GJ

2 6 350 PVC Pos:

Zero:

0.0492 0.0639

0.1574

CBL-ED/GJ In

0.1551

MagneticCopper

BUS-ED/GJ

BUS-EMCC/GJ

1 65 500 PVC Pos:

Zero:

0.8294 1.3147

3.2359

CBL-ED/GJ-1 In

2.6124

BUS-ED/GJ

BUS-TR-E/1J-PRI

1 70 8 PVC Pos:

Zero:

24.6398 1.7530

4.3142

CBL-ED/GJ-2 In

77.6532

MagneticCopper

BUS-ED/GJ

BUS-EH/GJ

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GJ-3 In

1.6578

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-ED/GJ

BUS-TR-E/2J-PRI

1 80 8 PVC Pos:

Zero:

28.1597 2.0035

4.9306

CBL-ED/GJ-4 In

88.7465

MagneticCopper

BUS-ED/GJ

BUS-TR-E/3J-PRI

1 90 8 PVC Pos:

Zero:

31.6797 2.2539

5.5469

CBL-ED/GJ-5 In

99.8399

BUS-0038

BUS-ED/GK

1 6 4/0 PVC Pos:

Zero:

0.1667 0.1294

0.3188

CBL-ED/GK In

0.5253

MagneticCopper

BUS-ED/GK

BUS-0434

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

CBL-ED/GK-1 In

13.8151

MagneticCopper

BUS-ED/GK

BUS-TR-E2/GK-PRI

1 30 1 PVC Pos:

Zero:

2.0833 0.5677

1.3971

CBL-ED/GK-2 In

6.5651

MagneticCopper

BUS-ED/GK

BUS-TR-E/1K-PRI

1 100 8 PVC Pos:

Zero:

35.1997 2.5043

6.1632

CBL-ED/GK-3 In

110.9332

BUS-ED/GK

BUS-TR-E/GK-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-ED/GK-4 In

6.6560

MagneticCopper

BUS-ED/GK

BUS-TR-E/2K-PRI

1 110 8 PVC Pos:

Zero:

38.7196 2.7548

6.7795

CBL-ED/GK-5 In

122.0265

MagneticCopper

BUS-ED/GK

BUS-TR-E/3K-PRI

1 120 8 PVC Pos:

Zero:

42.2396 3.0052

7.3958

CBL-ED/GK-6 In

133.1198

MagneticCopper

BUS-0039

BUS-ED/GL

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GL In

1.6578

BUS-ED/GL

BUS-EH/GL

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GL-1 In

1.6578

MagneticCopper

BUS-ED/GL

BUS-TR-E/3L-PRI

1 120 8 PVC Pos:

Zero:

42.2396 3.0052

7.3958

CBL-ED/GL-2 In

133.1198

MagneticCopper

BUS-ED/GL

BUS-TR-E/1L-PRI

1 100 8 PVC Pos:

Zero:

35.1997 2.5043

6.1632

CBL-ED/GL-3 In

110.9332

MagneticCopper

BUS-ED/GL

BUS-TR-E/2L-PRI

1 110 8 PVC Pos:

Zero:

38.7196 2.7548

6.7795

CBL-ED/GL-4 In

122.0265

BUS-0040

BUS-ED/GM

1 6 2 PVC Pos:

Zero:

0.5260 0.1523

0.3750

CBL-ED/GM In

1.6578

MagneticCopper

BUS-ED/GM

BUS-EH/3M

1 70 2 PVC Pos:

Zero:

6.1372 1.7773

4.3750

CBL-ED/GM-1 In

19.3411

MagneticCopper

BUS-ED/GM

BUS-EH/2M

1 60 2 PVC Pos:

Zero:

5.2604 1.5234

3.7500

CBL-ED/GM-2 In

16.5781

MagneticCopper

BUS-ED/GM

BUS-EH/GM

1 15 2 PVC Pos:

Zero:

1.3151 0.3809

0.9375

CBL-ED/GM-3 In

4.1445

BUS-ED/GM

BUS-EH/1M

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

CBL-ED/GM-4 In

13.8151

MagneticCopper

BUS-0041

BUS-ED/RF

2 6 350 PVC Pos:

Zero:

0.0492 0.0639

0.1574

CBL-ED/RF In

0.1551

MagneticCopper

BUS-ED/RF

BUS-0401

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RF-1 In

8.7543

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-ED/RF

BUS-0402

1 50 3 PVC Pos:

Zero:

5.4905 1.3129

3.2313

CBL-ED/RF-2 In

17.3025

BUS-ED/RF

BUS-0403

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RF-3 In

8.7543

MagneticCopper

BUS-ED/RF

BUS-0404

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RF-4 In

8.7543

MagneticCopper

BUS-ED/RF

BUS-TR-E/RF-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-ED/RF-5 In

6.6560

MagneticCopper

BUS-ED/RF

BUS-0405

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RF-6 In

8.7543

BUS-ED/RF

BUS-0406

1 50 2 PVC Pos:

Zero:

4.3837 1.2695

3.1250

CBL-ED/RF-7 In

13.8151

MagneticCopper

BUS-0043

BUS-ED/RM

2 6 3/0 PVC Pos:

Zero:

0.1048 0.0676

0.1664

CBL-ED/RM In

0.3303

MagneticCopper

BUS-ED/RM

BUS-0494

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RM-1 In

8.7543

MagneticCopper

BUS-ED/RM

BUS-0495

1 50 1 PVC Pos:

Zero:

3.4722 1.2370

3.0447

CBL-ED/RM-2 In

10.9418

BUS-ED/RM

BUS-0496

1 50 1 PVC Pos:

Zero:

3.4722 1.2370

3.0447

CBL-ED/RM-3 In

10.9418

MagneticCopper

BUS-ED/RM

BUS-0497

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-ED/RM-4 In

8.7543

MagneticCopper

BUS-ED/RM

BUS-TR-UPS/1-PRI

1 35 6 PVC Pos:

Zero:

7.7474 0.7975

1.9642

CBL-ED/RM-5 In

24.4149

MagneticCopper

BUS-ED/RM

BUS-TR-E/RM-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-ED/RM-6 In

6.6560

BUS-EH/1F

BUS-TR-E/1F-PRI

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

CBL-EH/1F-1 In

4.1854

MagneticCopper

BUS-EH/1M

BUS-TR-E/1M-PRI

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

CBL-EH/1M-1 In

4.1854

MagneticCopper

BUS-EH/2F

BUS-TR-E/2F-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

CBL-EH/2F-1 In

6.6560

MagneticCopper

BUS-EH/2M

BUS-TR-E/2M-PRI

1 8 8 PVC Pos:

Zero:

2.8160 0.2618

0.6444

CBL-EH/2M-1 In

8.8747

BUS-EH/3F

BUS-EH/RF

1 150 10 PVC Pos:

Zero:

76.8229 5.5599

13.6914

CBL-EH/3F-1 In

242.1094

MagneticCopper

BUS-EH/3F

BUS-TR-E/3F-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

CBL-EH/3F-2 In

6.6560

MagneticCopper

BUS-EH/3M

BUS-EH/RM

1 150 10 PVC Pos:

Zero:

76.8229 5.5599

13.6914

CBL-EH/3M-1 In

242.1094

MagneticCopper

BUS-EH/3M 1 8 8 PVC Pos: 2.8160 0.2618CBL-EH/3M-2 In MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

BUS-TR-E/3M-PRI Zero: 0.6444 8.8747

BUS-EH/GB

BUS-TR-E/GB-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1964

0.4833

CBL-EH/GB-1 In

6.6560

MagneticCopper

BUS-EH/GF

BUS-TR-E/GF-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-EH/GF-1 In

6.6560

MagneticCopper

BUS-EH/GH

BUS-TR-E/GH-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-EH/GH-2 In

6.6560

MagneticCopper

BUS-EH/GJ

BUS-TR-E/GJ-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-EH/GJ-1 In

6.6560

BUS-EH/GL

BUS-TR-E/GL-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-EH/GL-1 In

6.6560

MagneticCopper

BUS-EH/GM

BUS-TR-E/GM-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-EH/GM-7 In

6.6560

MagneticCopper

BUS-TR-E/1B-SEC

BUS-EL/1B

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/1B In

22.2892

MagneticCopper

BUS-TR-E/1C-SEC

BUS-EL/1C

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/1C In

14.0292

BUS-TR-E/1D-SEC

BUS-EL/1D

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/1D In

8.8286

MagneticCopper

BUS-TR-E/1E-SEC

BUS-EL/1E

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/1E In

8.8286

MagneticCopper

BUS-TR-E/1F-SEC

BUS-EL/1F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/1F In

8.8286

MagneticCopper

BUS-TR-E/1H-SEC

BUS-EL/1H

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/1H In

22.2892

BUS-TR-E/1J-SEC

BUS-EL/1J

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/1J In

14.0292

MagneticCopper

BUS-TR-E/1K-SEC

BUS-EL/1K

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/1K In

22.2892

MagneticCopper

BUS-TR-E/1L-SEC

BUS-EL/1L

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/1L In

22.2892

MagneticCopper

BUS-TR-E/1M-SEC

BUS-EL/1M

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/1M In

8.8286

BUS-TR-E/2B-SEC

BUS-EL/2B

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/2B In

8.8286

MagneticCopper

BUS-TR-E/2B-B-SEC

BUS-EL/2B-B

1 100 2/0 PVC Pos:

Zero:

23.5762 12.3197

30.3254

CBL-EL/2B-B In

74.2881

MagneticCopper

BUS-EL/2B-B

BUS-EL/2B-C

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-EL/2B-C In

4.4573

MagneticCopper

BUS-TR-E/2C-SEC

BUS-EL/2C

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/2C In

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-TR-E/2D-SEC

BUS-EL/2D

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/2D In

8.8286

MagneticCopper

BUS-TR-E/2E-SEC

BUS-EL/2E

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/2E In

8.8286

MagneticCopper

BUS-TR-E/2F-SEC

BUS-EL/2F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/2F In

8.8286

MagneticCopper

BUS-TR-E/2H-SEC

BUS-EL/2H

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/2H In

BUS-TR-E/2J-SEC

BUS-EL/2J

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/2J In

22.2892

MagneticCopper

BUS-TR-E/2K-SEC

BUS-EL/2K

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/2K In

22.2892

MagneticCopper

BUS-TR-E/2L-SEC

BUS-EL/2L

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/2L In

22.2892

MagneticCopper

BUS-TR-E/2M-SEC

BUS-EL/2M

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/2M In

BUS-0548

BUS-EL/3B

1 1 Pos:

Zero:

0.0000 0.0000

0.0000

CBL-EL/3B In

0.0000

Non-MagneticCopper

BUS-TR-E/3C-SEC

BUS-EL/3C

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3C In

8.8286

MagneticCopper

BUS-TR-E/3D-SEC

BUS-EL/3D

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3D In

8.8286

MagneticCopper

BUS-TR-E/3E-SEC

BUS-EL/3E

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3E In

BUS-TR-E/3F-SEC

BUS-EL/3F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3F In

8.8286

MagneticCopper

BUS-TR-E/3G-SEC

BUS-EL/3G

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3G In

8.8286

MagneticCopper

BUS-TR-E/3H-SEC

BUS-EL/3H

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/3H In

22.2892

MagneticCopper

BUS-TR-E/3J-SEC

BUS-EL/3J

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/3J In

BUS-TR-E/3K-SEC

BUS-EL/3K

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/3K In

14.0292

MagneticCopper

BUS-TR-E/3L-SEC

BUS-EL/3L

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/3L In

22.2892

MagneticCopper

BUS-TR-E/3M-SEC

BUS-EL/3M

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-EL/3M In

8.8286

MagneticCopper

BUS-TR-E/GA-SEC

BUS-EL/GA

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/GA In

BUS-TR-E/GB-SEC

BUS-EL/GB

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/GB In

14.0292

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-TR-E/GE-SEC

BUS-EL/GE

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/GE In

22.2892

MagneticCopper

BUS-TR-E/GF-SEC

BUS-EL/GF

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/GF In

14.0292

MagneticCopper

BUS-TR-E/GH-SEC

BUS-EL/GH

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/GH In

BUS-TR-E/GJ-SEC

BUS-EL/GJ

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/GJ In

22.2892

MagneticCopper

BUS-TR-E/GK-SEC

BUS-EL/GK

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/GK In

22.2892

MagneticCopper

BUS-TR-E/GL-SEC

BUS-EL/GL

1 6 6 PVC Pos:

Zero:

7.0729 0.9500

2.3396

CBL-EL/GL In

22.2892

MagneticCopper

BUS-TR-E/GM-SEC

BUS-EL/GM

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/GM In

BUS-EL/GM

BUS-EL/GM SUB

1 6 4 PVC Pos:

Zero:

4.4517 0.6698

1.6489

CBL-EL/GM-10 In

14.0292

MagneticCopper

BUS-TR-E/RF2-SEC

BUS-EL/RF2

1 6 3/0 PVC Pos:

Zero:

1.1164 0.7198

1.7724

CBL-EL/RF2 In

3.5184

MagneticCopper

BUS-TR-E/RF-SEC

BUS-EL/RF-L

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/RF-L In

14.0292

MagneticCopper

BUS-EL/RF-L

BUS-EL/RF-R

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/RF-R In

BUS-TR-E/RM-SEC

BUS-EL/RM

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-EL/RM In

14.0292

MagneticCopper

BUS-TR-E2/GK-SEC

BUS-EL2/GK

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-EL2/GK In

4.4573

MagneticCopper

BUS-EMCC/GJ

BUS-0575

1 50 10 PVC Pos:

Zero:

25.6076 1.8533

4.5638

CBL-EMCC/GJ-1 In

80.7031

MagneticCopper

BUS-EMCC/GJ

BUS-0576

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-2 In

127.8950

BUS-EMCC/GJ

BUS-0577

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-3 In

127.8950

MagneticCopper

BUS-EMCC/GJ

BUS-0578

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-4 In

127.8950

MagneticCopper

BUS-EMCC/GJ

BUS-0579

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-5 In

127.8950

MagneticCopper

BUS-EMCC/GJ

BUS-0580

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-6 In

BUS-EMCC/GJ

BUS-0581

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-7 In

127.8950

MagneticCopper

BUS-EMCC/GJ

BUS-0582

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-8 In

127.8950

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-EMCC/GJ

BUS-0583

1 50 12 PVC Pos:

Zero:

40.5816 1.9748

4.8633

CBL-EMCC/GJ-9 In

127.8950

MagneticCopper

BUS-0042

BUS-EMCC/P1

2 20 350 PVC Pos:

Zero:

0.1641 0.2131

0.5247

CBL-EMCC/P1 In

0.5169

BUS-EMCC/P1

BUS-TR-E/RF2-PRI

1 35 2 PVC Pos:

Zero:

3.0686 0.6806

1.6756

CBL-EMCC/P1-1 In

9.6706

MagneticCopper

BUS-EMCC/P1

BUS-0407

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P1-2 In

8.7543

MagneticCopper

BUS-EMCC/P1

BUS-0408

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P1-3 In

8.7543

MagneticCopper

BUS-EMCC/P1

BUS-0409

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P1-4 In

BUS-EMCC/P1

BUS-0410

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P1-5 In

8.7543

MagneticCopper

BUS-EMCC/P1

BUS-0584

1 50 8 PVC Pos:

Zero:

17.5998 1.6363

4.0278

CBL-EMCC/P1-6 In

55.4666

MagneticCopper

BUS-EMCC/P2

BUS-TR-UPS-PRI

1 35 8 PVC Pos:

Zero:

12.3199 1.1454

2.8194

CBL-EMCC/P2-1 In

38.8266

MagneticCopper

BUS-EMCC/P2

BUS-0490

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P2-2 In

BUS-EMCC/P2

BUS-0491

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P2-3 In

8.7543

MagneticCopper

BUS-EMCC/P2

BUS-0492

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P2-4 In

8.7543

MagneticCopper

BUS-EMCC/P2

BUS-0493

1 50 1/0 PVC Pos:

Zero:

2.7778 1.1719

2.8841

CBL-EMCC/P2-5 In

8.7543

MagneticCopper

BUS-0044

BUS-EMCC/P2

2 40 350 PVC Pos:

Zero:

0.3281 0.4262

1.0495

CBL-EMCC-P2 In

1.0339

BUS-H/1F

BUS-TR-1F-PRI

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

CBL-H/1F-1 In

4.1854

MagneticCopper

BUS-H/1M

BUS-TR-1M-PRI

1 6 6 PVC Pos:

Zero:

1.3281 0.1367

0.3367

CBL-H/1M-1 In

4.1854

MagneticCopper

BUS-H/2F

BUS-TR-2F-PRI

1 6 8 PVC Pos:

Zero:

2.1120 0.1503

0.3698

CBL-H/2F-1 In

6.6560

MagneticCopper

BUS-H/2F

BUS-H1

1 200 8 PVC Pos:

Zero:

70.3993 6.5451

16.1111

CBL-H/2F-2 In

221.8663

BUS-H/2M

BUS-TR-2M-PRI

1 8 6 PVC Pos:

Zero:

1.7708 0.1823

0.4490

CBL-H/2M-1 In

5.5806

MagneticCopper

BUS-H/3F

BUS-TR-3F-PRI

1 8 8 PVC Pos:

Zero:

2.8160 0.2003

0.4931

CBL-H/3F-1 In

8.8747

MagneticCopper

BUS-H/3M

BUS-TR-3M-PRI

1 8 8 PVC Pos:

Zero:

2.8160 0.2003

0.4931

CBL-H/3M-1 In

8.8747

MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-H2/GK

BUS-TR-2/GK-PRI

1 20 1 PVC Pos:

Zero:

1.3889 0.3785

0.9314

CBL-H2/GK-2 In

4.3767

BUS-TR-1B-SEC

BUS-L/1B-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1B-L In

8.8286

MagneticCopper

BUS-L/1B-L

BUS-L/1B-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1B-R In

8.8286

MagneticCopper

BUS-L/1C-R

BUS-L/1C-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1C-L In

8.8286

MagneticCopper

BUS-TR-1C-SEC

BUS-L/1C-R

1 16 2 PVC Pos:

Zero:

7.4704 2.1635

5.3254

CBL-L/1C-R In

23.5429

BUS-L/1D-R

BUS-L/1D-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1D-L In

8.8286

MagneticCopper

BUS-TR-1D-SEC

BUS-L/1D-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1D-R In

8.8286

MagneticCopper

BUS-TR-1E-SEC

BUS-L/1E-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1E-L In

8.8286

MagneticCopper

BUS-L/1E-L

BUS-L/1E-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1E-R In

BUS-TR-1F-SEC

BUS-L/1F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1F In

8.8286

MagneticCopper

BUS-TR-1G-SEC

BUS-L/1G

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1G In

8.8286

MagneticCopper

BUS-TR-1G-A-SEC

BUS-L/1G-A

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1G-A In

8.8286

MagneticCopper

BUS-TR-1H-SEC

BUS-L/1H-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1H-L In

BUS-L/1H-L

BUS-L/1H-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1H-R In

8.8286

MagneticCopper

BUS-TR-1J-SEC

BUS-L/1J-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1J-L In

8.8286

MagneticCopper

BUS-L/1J-L

BUS-L/1J-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1J-R In

8.8286

MagneticCopper

BUS-TR-1K-SEC

BUS-L/1K-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1K-L In

BUS-L/1K-L

BUS-L/1K-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1K-R In

8.8286

MagneticCopper

BUS-L/1L-R

BUS-L/1L-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1L-L In

8.8286

MagneticCopper

BUS-TR-1L-SEC

BUS-L/1L-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1L-R In

8.8286

MagneticCopper

BUS-TR-1M-SEC 1 6 2 PVC Pos: 2.8014 0.8113CBL-L/1M In MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

BUS-L/1M Zero: 1.9970 8.8286

BUS-TR-1N-SEC

BUS-L/1N

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/1N In

8.8286

MagneticCopper

BUS-L/2C-R

BUS-L/2C-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2C-L In

8.8286

MagneticCopper

BUS-TR-2C-SEC

BUS-L/2C-R

1 8 2 PVC Pos:

Zero:

3.7352 1.0817

2.6627

CBL-L/2C-R In

11.7715

MagneticCopper

BUS-L/2D-R

BUS-L/2D-L

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/2D-L In

4.4573

BUS-TR-2D-SEC

BUS-L/2D-R

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/2D-R In

4.4573

MagneticCopper

BUS-TR-2E-SEC

BUS-L/2E-L

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/2E-L In

4.4573

MagneticCopper

BUS-L/2E-L

BUS-L/2E-R

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/2E-R In

4.4573

MagneticCopper

BUS-TR-2F-SEC

BUS-L/2F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2F In

BUS-TR-2G-SEC

BUS-L/2G

1 8 2 PVC Pos:

Zero:

3.7352 1.0817

2.6627

CBL-L/2G In

11.7715

MagneticCopper

BUS-TR-2H-SEC

BUS-L/2H-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2H-L In

8.8286

MagneticCopper

BUS-L/2H-L

BUS-L/2H-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2H-R In

8.8286

MagneticCopper

BUS-TR-2J-SEC

BUS-L/2J-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2J-L In

BUS-L/2J-L

BUS-L/2J-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2J-R In

8.8286

MagneticCopper

BUS-TR-2K-SEC

BUS-L/2K-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2K-L In

8.8286

MagneticCopper

BUS-L/2K-L

BUS-L/2K-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2K-R In

8.8286

MagneticCopper

BUS-TR-2L-SEC

BUS-L/2L-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2L-L In

BUS-L/2L-L

BUS-L/2L-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/2L-R In

8.8286

MagneticCopper

BUS-TR-2M-SEC

BUS-L/2M

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-L/2M In

14.0292

MagneticCopper

BUS-TR-2N-SEC

BUS-L/2N

1 6 4 PVC Pos:

Zero:

4.4517 0.8765

2.1579

CBL-L/2N In

14.0292

MagneticCopper

BUS-0549

BUS-L/3B-L

1 1 Pos:

Zero:

0.0000 0.0000

0.0000

CBL-L/3B-L In

0.0000

Non-MagneticCopper

From Bus

To Bus

Qty

/Ph

Length

Feet

------ Cable Description ------

Size Cond. Type Duct Type Insul

Per Unit (100 MVA Base)

R pu jX pu

In/Out

Service

BUS-L/3B-L

BUS-L/3B-R

1 1 Pos:

Zero:

0.0000 0.0000

0.0000

CBL-L/3B-R In

0.0000

Non-MagneticCopper

BUS-L/3C-R

BUS-L/3C-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/3C-L In

8.8286

MagneticCopper

BUS-TR-3C-SEC

BUS-L/3C-R

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/3C-R In

8.8286

MagneticCopper

BUS-L/3D-R

BUS-L/3D-L

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/3D-L In

4.4573

BUS-TR-3D-SEC

BUS-L/3D-R

1 6 2/0 PVC Pos:

Zero:

1.4146 0.7392

1.8195

CBL-L/3D-R In

4.4573

MagneticCopper

BUS-L/3E-R

BUS-L/3E-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/3E-L In

8.8286

MagneticCopper

BUS-TR-3E-SEC

BUS-L/3E-R

1 8 2 PVC Pos:

Zero:

3.7352 1.0817

2.6627

CBL-L/3E-R In

11.7715

MagneticCopper

BUS-TR-3F-SEC

BUS-L/3F

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/3F In

BUS-TR-3G-SEC

BUS-L/3G

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/3G In

8.8286

MagneticCopper

BUS-TR-3H-SEC

BUS-L/3H-L

1 6 2 PVC Pos:

Zero:

2.8014 0.8113

1.9970

CBL-L/…